Instructions for calculating FIRE ALARM, SPRINKLER or ASBESTOS ABATEMENT permit fees (see applica-
ble section below):
1. Determine the valuation (labor & materials)
2. See base Permit Fee (flat fee)
3. Calculate the Plan review fee (multiply the valuation by the applicable percentage listed)
Fire Alarm:
Permit Fee: 3.75% of the valuation
Plan Review Fee: $288.00, due at permit submittal
Fire Sprinkler:
Permit Fee: 4.25% of the valuation
Plan Review Fee: $432.00, due at permit submittal
Asbestos Abatement:
Permit Fee: $144.00
Plan Review Fee: No review fee
OTHER Fire Permit Fees:
• Permits issued under a Scope of Work letter shall be assessed a fee not less than $144.00 and may be increased at a
rate of $72.00 per hour for inspections, revisions, and similar elements.
• Re-inspections and plan review for re-submittals shall be billed at $72.00 per hour.
• Operational Permits, Special Event Permits, and Construction Permits other than those required for Fire Alarm and Fire
Sprinkler systems, issued under provisions of the International Fire Code shall be based on an hourly rate of $72.00
per hour per person for site inspections, plan review and permit processing.
Town of Vail
Fire Permit Fee Schedule
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bu
l
l
e
t
i
n
1
3
5
Re
v
.
H
Bulletin 135 Rev. H
Model F1
Residential Sprinklers for
Design Density of .05 gpm/ft2
Types:
F1 Res 30 Pendent
F1 Res 30 Recessed Pendent/F2
F1 Res 30 Recessed Pendent/FP
F1 Res 49 Pendent
F1 Res 49 Recessed Pendent/F1
F1 Res 49 Recessed Pendent/FP
F1 Res 58 Pendent
F1 Res 58 Recessed Pendent/F1
F1 Res 58 Recessed Pendent/FP
F1 Res 76 Pendent
F1 Res 76 Recessed Pendent/F1
F1 Res 76 Recessed Pendent/FP
F1 Res 30 CCP Pendent
F1 Res 49 CCP Pendent
F1 Res 58 CCP Pendent
F1 Res 76 CCP Pendent
F1 Res 44 HSW
F1 Res 44 Recessed HSW/F2
F1 Res 58 HSW
F1 Res 58 HSW Recessed HSW/F2
F1 Res 44 SWC
Listings & Approvals
Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
NYC MEA 258-93-E
Slope Ceiling Approvals: Refer to Bulletin 035
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the
Model F1 Res 49 & 58 Pendent Sprinklers
Product Description
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are
fast response sprinklers combining excellent durability,
high sensitivity glass-bulb and low profile decorative de-
sign. The F1 Res Horizontal Sidewall sprinklers (Figs. 5, 6
& 7) are equally attractive when above ceiling piping can-
not be used.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
1.
2.
F1 Res 30, 49, 58 & 76
Recessed Pendent / FP
F1 Res 30, 49, 58 & 76
Recessed Pendent / F1
F1 Res 44 & 58
Recessed HSW/F2
F1 Res 30, 49, 58 & 76
CCP Pendent
F1 Res 44 SWC
The 3mm glass-bulb pendent sprinklers permit the effi-
cient use of residential water supplies for sprinkler cover-
age in residential fire protection design.
The low flow F1 Res sprinklers are specially engineered
for fast thermal response to meet the sensitive fire protec-
tion application needs of the latest residential market stan-
dards (UL 1626 Standard). Upon fire conditions, rising
heat causes a sprinkler’s heat-sensitive glass-bulb to shat-
ter, releasing the waterway for water flow onto the deflector,
evenly distributing the discharged water to control a fire.
Technical Data:
Thermal Sensor: Nominal 3mm glass-bulb
Sprinkler Frame : Brass Casting
Sprinklers’ Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size: ½” NPT (R½)
K-Factor: 3.0 (Actual) - F1 Res 30 Pendent Sprinkler
4.9 (Actual) - F1 Res 49 Pendent Sprinkler
5.8 (Actual) - F1 Res 58 Pendent & HSW Sprinkler
7.6 (Actual) - F1 Res 76 Pendent Sprinkler
4.4 (Actual) - F1 Res 44 HSW Sprinkler
Density: Minimum 0.05 gpm/ft2
•
•
•
•
•
•
Model F1 Res Sprinklers engineered for the lowest fl ows
to meet the minimum design density of .05 gpm/ft2
2.
Application
Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. Be sure that ori-
fice size, temperature rating, deflector style and sprinkler
type are in accordance with the latest published standards
of The National Fire Protection Association or the approving
authority having jurisdiction.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith,
are the only recessed escutcheons to be used with Model
F1 Res sprinklers. Use of any other recessed escutcheon
will void all approvals and warranties. For installing Model
F1 Res Pendent sprinklers use only the Model D sprinkler
Wrench; for installing Models F1 Res Recessed Pendent,
CCP & SWC sprinklers use only the Model GFR2 sprinkler
wrench; for installing Model F1 Res Recessed HSW sprin-
klers use only the Model GFR2 Sprinkler Wrench. Use of
wrenches other than those specified may damage these
sprinklers. Install F1 Res 44 with a ceiling to deflector dis-
tance of 4” - 12”. Flow arrow on deflector must point away
from near wall and “Top” marking must face ceiling.
Escutcheon*, F1 or F2, Data:
Type Adjustment
Inch (mm)
“A”
Inch (mm)
Face of fi tting
to ceiling
Inch (mm)
F13/4 (19.0)Min.=3/4” (19.1)
Max.=11/2” (38.1)
3/16 - 15/16
(4.7 - 24.0)
F21/2 (12.7)Min.=15/16” (23.8)
Max.=11/2” (38.1)
3/16 - 11/16
(4.7 - 17.4)
* Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler
Model F1 Res 30, 49, 58 & 76 Pendent•
Model F1 Res 30 Recessed Pendent / F2
Model F1 Res 49, 58 & 76 Recessed Pendent / F1
•
•
Fig. 1 Fig. 2
F1 escutcheon, 3/4” (19mm) adjustment
3.
Technical Data: F1Res 30 Pendent and Recessed Pendent
Thread
Size
Nominal Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.
Actual
K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C
½” NPT
(R½)21/64” (8.2)155
175
68
79 175 (12)100383.02.25 (57)
Defl ector - to - ceiling
Maximum 1” (25mm) to 4” (100mm)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6) 8 (30.3)7.0 (0,48)R351114 x 14 (4,3 x 4,3) 10 (37.8)11 (0,76)
Technical Data: F1Res 49 Pendent and Recessed Pendent.
Thread
Size
Nominal Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.
Actual
K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C
½” NPT
(R½)7/16” (11)155
175
68
79 175 (12)100
150
38
66 4.92.25 (57)
Defl ector - to - ceiling
Maximum 1” (25mm) to 4” (100mm)
Max.
Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6) 13 (49)7.0 (0,48)
R3516
14 x 14 (4,3 x 4,3) 13 (49)7.0 (0,48)
16 x 16 (4,9 x 4,9)13 (49)7.0 (0,48)
18 x 18 (5,5 x 5,5) 17 (64.3)12.0 (0,83)
20 x 20 (6,1 x 6,1)20 (75.7)16.7 (1,14)
Defl ector - to - ceiling
Maximum 4” (100mm) to 8” (203mm)
Max.
Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6) 15 (57)9.4 (0,65)
R3516
14 x 14 (4,3 x 4,3) 16 (60.5)10.6 (0,73)
16 x 16 (4,9 x 4,9)17 (64.3)12.0 (0,83)
18 x 18 (5,5 x 5,5) 19 (72)15.0 (1,0)
20 x 20 (6,1 x 6,1)22 (83.2)20.2 (1,4)
*Note: The F1 Res 49 pendent and recessed pendent residential sprin-
klers can be installed per NFPA 13 in beamed ceilings meeting
the following criteria:
1. Maximum beam depth = 7” (178mm)
2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: F1Res 58 Pendent and Recessed Pendent.
Thread
Size
Nominal Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.Actual
K Factor
Sprinkler
Length
Inch (mm)°F°C°F°C
½” NPT
(R½)½” (13)155
175
68
79 175 (12)100
150
38
66 5.82.25 (57)
Max.
Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Ceiling -to- Defl ector
Inch (mm)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6) 16 (61)7.6 (0,53)
1- 4
(25 - 100)R3513
14 x 14 (4,3 x 4,3)16 (61)7.6 (0,53)
16 x 16 (4,9 x 4,9)16 (61)7.6 (0,53)
18 x 18 (5,5 x 5,5) 19 (72)10.8 (0,75)
20 x 20 (6,1 x 6,1)22 (83.3)14.4 (1,0)
Note: The F1 Res 76 will use a 1” x ¾” reducer.
FP push-on/thread-off escutcheon
Fig. 3 Fig. 4
4.
Model F1 Res 30, 49, 58 & 76 CCP Pendent•Model F1 Res 30, 49, 58 & 76
Recessed Pendent / FP
•
Technical Data: F1 Res 76 Pendent and Recessed Pendent
Thread
Size
Nominal Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C
3/4” NPT
(R½)17/32” (13.5)155
175
68
79 175 (12)100
150
38
66 7.62.25 (57)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6) 21 (79.5)7.6 (0,53)
R7618
14 x 14 (4,3 x 4,3) 21 (79.5)7.6 (0,53)
16 x 16 (4,9 x 4,9) 21 (79.5)7.6 (0,53)
18 x 18 (5,5 x 5,5) 21 (79.5)7.6 (0,53)
20 x 20 (6,1 x 6,1)23 (87.1)9.2 (0,63)
5.
Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
CCP Assembly
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C°F°C
½” NPT
(R½)21/64” (8.2)1556813557175 (12)100383.02.25 (57)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number
(SIN)
12 x 12 (3,6 x 3,6) 8 (30.3)7.0 (0,48)R351114 x 14 (4,3 x 4,3) 11 (41.6)13.4 (0,92)
Technical Data: F1Res 49 CCP Pendent and Recessed Pendent/FP
Thread
Size
Nominal
Orifi ce
Inch
(mm)
Sprinkler
Temp.
Rating
CCP
Assembly
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch
(mm)°F°C°F°C°F°C
½” NPT
(R½)7/16” (11)1556813557175 (12)100384.92.25 (57)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6) 13 (49)7.0 (0,48)
R3516
14 x 14 (4,3 x 4,3) 13 (49)7.0 (0,48)
16 x 16 (4,9 x 4,9)14 (53)8.2 (0,56)
18 x 18 (5,5 x 5,5) 18 (68.1)13.5 (0,93)
20 x 20 (6,1 x 6,1)20 (75.7)16.7 (1,14)
CCP Options Data:
“A”
Cover Adjustment
Inch (mm)
“B”
CCP Height
Inch (mm)
1/2 (12.7)15/16 (24)
5/16 (7.9)3/4 (19)
FP Data “A”:
FP Position “A”
Inch (mm)
Max. Recessed 7/16 (11)
Min. Recessed 15/16 (24)
Note: Sprinklers shown in Fig. 3 and Fig. 4
are not suitable for installation in ceil-
ings which have positive pressure in
the space above.
Technical Data: F1Res 58 CCP Pendent and Recessed Pendent/FP
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
CCP Assembly
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C°F°C
½” NPT
(R½)1/2” (13)1556813557175 (12)100385.82.25 (57)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number
(SIN)
12 x 12 (3,6 x 3,6) 16 (61)7.6 (0,53)
R3513
14 x 14 (4,3 x 4,3) 16 (61)7.6 (0,53)
16 x 16 (4,9 x 4,9)16 (61)7.6 (0,53)
18 x 18 (5,5 x 5,5) 19 (72)10.8 (0,75)
20 x 20 (6,1 x 6,1)22 (83.3)14.4 (1,0)
Technical Data: F1Res 76 CCP Pendent and Recessed Pendent/FP
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
CCP Assembly
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C°F°C
3/4” NPT
(R3/4)17/32” (13.5)155
175
68
79 13557175 (12)100
150
38
66 7.62.25 (57)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number
(SIN)
12 x 12 (3,6 x 3,6) 21 (79.5)7.6 (0,53)
R7618
14 x 14 (4,3 x 4,3) 21 (79.5)7.6 (0,53)
16 x 16 (4,9 x 4,9) 21 (79.5)7.6 (0,53)
18 x 18 (5,5 x 5,5)22 (83.3)8.4 (0,58)
20 x 20 (6,1 x 6,1)25 (94.6)10.8 (0,74)
6.
Model F1 Res 44 & 58 HSW•
Model F1 Res 44 & 58 Recessed HSW/F2•
F2 escutcheon,
1/2” (13mm) adjustment
Technical Data: F1Res 44 HSW & HSW/F2
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C
½” NPT
(R½)3/8” (10)155
175
68
79 175 (12)100
150
38
66 4.42.45 (62)
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting
to wall
Inch (mm)
F2 1/2 (13)3/16 - 11/16
(4.7 - 17.4)
Max.
Sprinkler Spacing
ft (m)
“A”
Ceiling to
Defl ector
Inch (mm)
Sprinkler Temp.
Rating
°F (°C)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6)
4 - 6
(101 - 152)
155 (68)175 (79)12 (45,4)7.5 (0,52)
R3531
14 x 14 (4,3 x 4,3)155 (68)175 (79)14 (53,0)10.2 (0,71)
16 x 16 (4,9 x 4,9)155 (68)175 (79)16 (60,6)13.3 (0,92)
16 x 18 (4,9 x 5,5)155 (68)175 (79)18 (68,1)16.8 (1,16)
18 x 18 (5,5 x 5,5)155 (68)175 (79)19 (72,0)18.7 (1,29)
16 x 20 (4,9 x 6,1)155 (68)175 (79)23 (87,1)27.4 (1,89)
12 x 12 (3,6 x 3,6)
6 - 12
(152 - 305)
155 (68)175 (79)14 (53,0)10.2 (0,71)
14 x 14 (4,3 x 4,3)155 (68)175 (79)16 (60,6)13.3 (0,92)
16 x 16 (4,9 x 4,9)155 (68)175 (79)17 (64,4)15.0 (1,04)
16 x 18 (4,9 x 5,5)155 (68)175 (79)20 (75,7)20.7 (1,43)
16 x 20 (4,9 x 6,1)155 (68)175 (79)23 (87,1)27.4 (1,89)
Fig. 5
7.
Technical Data: F1Res 58 HSW & HSW/F2
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C
½” NPT
(R½)1/2” (13)155
175
68
79 175 (12)100
150
38
66 5.82.45 (62)
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting
to wall
Inch (mm)
F2 1/2 (13)3/16 - 11/16
(4.7 - 17.4)
Technical Data: F1Res 44 SWC
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
Cover
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F°C°F°C°F°C
½” NPT
(R½)3/8” (10)1556813557175 (12)100384.42.45 (62)
Max.
Sprinkler Spacing
ft (m)
“A”
Ceiling to
Defl ector
Inch (mm)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6)
4 - 6
(101 - 152)
13 (49,2)8.7 (0,60)
R3531
14 x 14 (4,3 x 4,3)14 (53,0)10.2 (0,71)
16 x 16 (4,9 x 4,9)17 (64,3)15.0 (1,1)
16 x 18 (4,9 x 5,5)19 (71,8)18.7 (1,13)
16 x 20 (4,9 x 6,1)23 (87,1)27.4 (1,89)
12 x 12 (3,6 x 3,6)
6 - 12
(152 - 305)
14 (52,9)10.2 (0,71)
14 x 14 (4,3 x 4,3)15 (56,7)11.7 (0,81)
16 x 16 (4,9 x 4,9)18 (68,1)16.8 (1,16)
16 x 18 (4,9 x 5,5)20 (75,6)20.7 (1,43)
Model F1 Res 44 SWC•
Fig. 6
Max.
Sprinkler Spacing
ft (m)
“A”
Ceiling to Defl ector
Inch (mm)
Sprinkler Temp.
Rating
°F (°C)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3,6 x 3,6)
4 - 6
(101 - 152)
155 (68)175 (79)16 (60,6)7.6 (0,53)
R3533
14 x 14 (4,3 x 4,3)155 (68)175 (79)18 (68,2)9.7 (0,67)
16 x 16 (4,9 x 4,9)155 (68)175 (79)21 (79,5)13.2 (0,91)
16 x 18 (4,9 x 5,5)155 (68)175 (79)25 (94,7)18.6 (1,28)
16 x 20 (4,9 x 6,1)155 (68)175 (79)29 (109,8)25 (1,73)
12 x 12 (3,6 x 3,6)
6 - 12
(152 - 305)
155 (68)175 (79)22 (83,3)14.4 (1,0)
14 x 14 (4,3 x 4,3)155 (68)175 (79)22 (83,3)14.4 (1,0)
16 x 16 (4,9 x 4,9)155 (68)175 (79)26 (98,4)20.1 (1,39)
16 x 18 (4,9 x 5,5)155 (68)175 (79)31 (117,4)28.6 (1,97)
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res 44
Sprinklers should be inspected quarterly, and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D, and 13R.
Do not clean sprinkler with soap and water, Ammonia or any oth-
er cleaning fluids. Remove dust by using a soft brush or gentle
vacuuming. Remove any sprinkler which has been painted (oth-
er than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers that could
cause improper operation or non-operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifi cations
Sprinklers shall be [cULus Listed] [New York City MEA Ap-
proved (258-93-E)] low flow residential pendent sprinklers en-
gineered to provide a minimum design density of 0.05 gpm/ft2
over the listed coverage area. Listed flows as specified by the
manufacturer’s technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installation stan-
dard. Where pendent residential sprinklers are installed under
sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance listing
shall be 1” to 8” maximum. Sprinkler frame and deflector shall
be of bronze frame construction having a ½” NPT thread. Water
seal assembly shall consist of a Teflon-coated Belleville spring
washer with top-loaded extruded or cold head cup with 3 mm
glass bulb containing no plastic parts, and having a temperature
rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a
nominal K-factor of 3.0, 4.9 and 5.8. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish– specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res 30, 49
& 58, SIN R3511, R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/F1,
Model F1 Res 30, 49 & 58 Recessed Pendent/F2,
Model F1 Res 30, 49 & 58 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] [New York City MEA Ap-
proved (258-93-E)] low flow residential recessed pendent
sprinklers engineered to provide a minimum design density
of 0.05 gpm/ft2 over the listed coverage area. Listed flows as
specified by the manufacturer’s technical data sheets are to be
used. Residential sprinklers shall be installed in conformance
with the manufacturer’s installation guidelines and the applica-
ble installation standard. Where pendent residential sprinklers
are installed under sloped ceilings having a pitch from [4/12]
to [8/12], the sprinklers shall be listed for such use. Deflector-
to-ceiling distance listing shall be 1” to 8” maximum. Sprinkler
frame and deflector shall be of bronze frame construction hav-
ing a ½” NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with top-loaded extruded
or cold head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (68°C)] [175°F
(79°C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9 &
5.8. Standard finish: [Bronze] [Chrome-plated] [White Polyester]
[Special finish– specify]. Recessed escutcheon assembly shall
be a steel, two-piece escutcheon [with ½” adjustment (Model
F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off
design with ½” adjustment (Model FP)]. Standard finish shall be
[brass][bright chrome] [white painted]. Residential recessed
pendent sprinklers shall be Reliable [Model F1 Res 30, 49 & 58
Recessed Pendent/F1] [Model F1 Res 30, 49 & 58 Recessed
Pendent/F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP]
SIN R3511, R3516 & R3513 (Bulletin 135).
Model F1 Res 30, 49 & 58 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA Ap-
proved (258-93-E)] low flow residential concealed sprinklers en-
gineered to provide a minimum design density of 0.05 gpm/ft2
over the listed coverage area. Listed flows as specified by the
manufacturer’s technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installation stan-
dard. Where pendent residential sprinklers are installed under
sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Sprinkler frame and deflector shall
be of bronze frame construction having a ½” NPT thread. Water
seal assembly shall consist of a Teflon-coated Belleville spring
washer with top-loaded extruded or cold head cup with 3 mm
glass bulb containing no plastic parts, and having a temperature
rating of 155°F (68°C). Cover plate assembly shall consist of a
brass cover plate and copper alloy retainer flange. Method of
attaching the cover plate to the sprinkler cup shall be a push-
on and thread-off design allowing a ½” cover plate adjustment.
Cover plate temperature rating shall be 135°F (57°C). A plastic
protective cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which could
occur during construction before the cover plate is installed.
Standard cover plate finish: [White] [Custom Color– specify]. ].
Concealed pendent sprinklers shall be Reliable Model F1 Res
30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bulletin 135).
Model F1 Res 44 Horizontal Sidewall
Residential Sprinkler Specifi cations
Sprinklers shall be [cULus Listed] [New York City MEA Ap-
proved (258-93-E)] low flow residential horizontal sidewall sprin-
klers engineered to provide a minimum design density of 0.05
gpm/ft2 over the listed coverage area. Listed flows as speci-
fied by the manufacturer’s technical data sheets are to be used.
Residential sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the applicable instal-
lation standard. Where horizontal sidewall residential sprinklers
are installed under sloped ceilings having a pitch from [4/12] to
[8/12], the sprinklers shall be listed for such use. Sprinkler frame
and deflector shall be of bronze frame construction having a ½”
NPT thread. Water seal assembly shall consist of a Teflon-coat-
ed Belleville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 4.4 (62.8). Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Special fin-
ish– specify]. Residential horizontal sidewall sprinklers shall be
Reliable Model F1 Res 44, SIN R3531 (Bulletin 135).
8.
9.
Model F1 Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
“horizontal sidewall sprinkler” with “recessed horizontal
sprinkler.” Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½” adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish– specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model F1
Res 44/F2, SIN R3531 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum de-
sign density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer’s technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer’s in-
stallation guidelines and the applicable installation stan-
dard. Sprinkler frame and deflector shall be of bronze
frame construction having a ¾” NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer with machined or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a tempera-
ture rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers
shall have a nominal K-factor of 7.6. Standard finish:
[Bronze] [Chrome-plated] [White Polyester] [Special fin-
ish– specify]. Residential pendent sprinklers shall be Reli-
able Model F1 Res 76, SIN R7618 (Bulletin 135).
Model F1 Res 76 Recessed Pendent/F1,
Model F1 Res 76 Recessed Pendent/F2,
Model F1 Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer’s technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a ¾” NPT thread.
Water seal assembly shall consist of a Teflon-coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish– specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with ½” adjust-
ment (Model F2)] [with ¾” adjustment (Model F1)] [of
push-on and thread off design with ½” adjustment (Mod-
el FP)]. Standard finish shall be [brass][bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model F1 Res 76 Recessed Pendent/
F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer’s
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable instal-
lation standard. Sprinkler frame and deflector shall be
of bronze frame construction having a ¾” NPT thread.
Water seal assembly shall consist of a Teflon-coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a ½” cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color– specify]. ]. Concealed pendent sprinklers shall be
Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes (1)
Standard Finishes
Sprinkler F1, F2, FP
Escutcheons Cover Plates
Bronze
Chrome Plated
White and Black Polyester
Coated
Brass
Bright Chrome Plated
White Painted
White Painted
Chrome
Special Application Finishes
Sprinkler F1, F2,
Escutcheons Cover Plates
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are available on special order.
Consult factory for details.
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish
Cover Plate Finish
1.
2.
3.
4.
5.
6.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A 09/10 P/N 9999970235
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gaugesIdentification signs
Fire department connection
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bu
l
l
e
t
i
n
0
0
6
Re
v
.
G
Bulletin 006 Rev. G
Model RFC30 (SIN RA0611)
Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Residential Flat Concealed
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2 with
low GPM requirements.
Features
1. Very low water flow requirements.
2. Cover plate attachment (Plain or Perforated)
with ½” (13mm) Total adjustment.
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
2. NYC MEA 258-93-E
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ from
standard sprinklers primarily in their response time and
water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has dem-
onstrated, in fire testing, an ability for controlling residen-
tial fires, and thereby providing significant evacuation time
for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and ½” (13mm) of cover adjustment for ease of
installation. The small diameter cover plate is easily and
positively attached and blends into the ceiling, concealing
the most dependable fire protection available, an automat-
ic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residential
Sprinklers to be installed in the residential portions of any
occupancy in accordance with NFPA 13, 13R, & 13D.
The RFC30, RFC43 and RFC49 can reduce the need for
precise cutting of drop nipples. The threaded cover plate
assembly can be adjusted without tools to fit accurately
against the ceiling. The fire protection system need not be
shut down to adjust or remove the cover plate assembly.
Application and Installation
The RFC30, RFC43 and RFC49, for residential installa-
tions, use a 165°F (74°C) fusible solder link in a tuning fork
style sprinkler frame with a drop-down deflector. This as-
sembly is recessed into the ceiling and concealed by a flat
cover plate. The cover plate is attached to the skirt, using
135°F (57°C) ordinary temperature classification solder.
When the ceiling temperature rises, the solder holding
the cover plate releases the cover allowing the deflector
to drop into position and exposing the sprinkler inside to
2.
ceiling temperature. The subsequent operation of the sol-
der link opens the waterway and causes the deflector to
drop into position to distribute the discharging water in a
hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover
plate and cup will assure that the drop-down deflector is
properly located below the ceiling. The residential distri-
bution pattern contains a finer droplet size than a standard
sprinkler, and the pattern produces significantly higher
wall wetting.
After a 25/8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexagonal
body of the sprinkler frame. The Wrench must bottom out
against the cup in order to ensure proper, safe installation.
The sprinkler is then tightened into the pipe fitting. When
inserting or removing the wrench from the sprinkler/cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30,
RFC43 AND RFC49 CONCEALED SPRINKLERS MUST
BE INSTALLED ONLY WITH 135°F RATED COVERS.
Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2” (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option, the
cover assembly is pushed onto the cup and final adjust-
ment is made by turning the cover clockwise until the skirt
flange makes full contact with the ceiling. Cover removal
requires turning in the counter-clockwise direction.
In ceilings that have a plenum space above the sprinkler,
the plenum space may have neutral or negative pressur-
ization but must not be positively pressurized. Inspect all
sprinklers after installation to ensure that the gap between
the cover plate and ceiling and the 4 slots in the cup are
all open and free from any air flow impediment.
Temperature Rating
SprinklerCover PlateMax. Ambient Temp.
165°F/74°C135°F/57°C100°F/38°C
Installation Data: RFC30 (SIN RA0611)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
ft. (m)
Minimum
Distance between
sprinklers
ft. (m)
Minimum Required
Sprinkler Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
½” (15mm)
½” (15mm)
3.0
3.0
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
6 (1.83)
7 (2.13)
8 (2.43)
8 (2.43)
9 (34.1)
10 (37.8)
9.0 (0.62)
11 (0.76)
Note: 1 bar = 100 Kpa
Installation Data: RFC43 (SIN RA0612)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
ft. (m)
Minimum
Distance between
sprinklers
ft. (m)
Minimum Required
Sprinkler Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
4.3
4.3
4.3
4.3
4.3
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)
6 (1.83)
7 (2.13)
8 (2.43)
9 (2.74)
10 (3.05)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
12 (45)
13 (49)
13 (49)
18 (68)
21 (79)
7.8 (0.54)
9.1 (0.63)
9.1 (0.63)
17.5 (1.21)
23.8 (1.64)
Note: 1 bar = 100 Kpa
Installation Data: RFC49 (RA0616)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
ft. (m)
Minimum
Distance between
sprinklers
ft. (m)
Minimum Required
Sprinkler Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
4.9
4.9
4.9
4.9
4.9
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)
6 (1.83)
7 (2.13)
8 (2.43)
9 (2.74)
10 (3.05)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
13 (49)
13 (49)
13 (49)
17 (64.3)
20 (75.7)
7.0 (0.48)
7.0 (0.48)
7.0 (0.48)
12.0 (0.83)
16.7 (1.14)
Note: 1 bar = 100 Kpa
FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.
3.
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler cover plate assem-
bly which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specifi cation
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a ½” NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler
K-factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91
(70) having a 5/16”, 3/8” and 7/16” orifice. Temperature rating
shall be Ordinary 165°F (74°C); cover plate temperature
rating to be 135°F (57°C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a ½” cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty – specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA0611
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
Ordering Information
Specify:
1. Sprinkler Model
2. Cover Plate Finish
3. Thread-On or
Push-On Feature
Cover Plate Finishes(1)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 05/12 P/N 9999970261
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection