HomeMy WebLinkAboutB12-0270 REV2 091912 LOAD CALCSElectrical Load Calculation 1320 Westhaven Dr. Unit 6C, Vail, CO 1600 sq ft x 3w/ft = 4800w 2 small appliance crts x 1500w = 3000w Microwave 1000w Disposal 500w Dishwasher 1200w Range 8000w Laundry 1500w Dryer 5000w Water heater 4500w Total 29500w 29500w – 8000w = 21500w 21500w x 40% = 8600w 8600w + 8000w = 16600w (total adjusted load) Electric baseboard heat 12000W 16600w + 12000w = 28600w (total load) 28600w/240v = 119.2a Service is 125A