F12-0060 Cut Sheets
Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage Page 1 of 10 JULY 2010 TFP171 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Technical Services 800-381-9312 | +1-401-781-8220 www.tyco-fire.com General Description The TYCO Series TY-FRB, 2.8, 4.2, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are quick response, standard coverage, decorative 3 mm glass bulb-type spray sprinklers designed for use in light or ordinary hazard, commercial occupan-cies such as banks, hotels, and shop-ping malls. The recessed version of the Series TY-FRB Pendent Sprinkler, where applica-ble, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following, • A two-piece Style 10 (1/2 inch NPT) or Style 40 (3/4 inch NPT) Recessed Escutcheon with 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush pendent position, or a • A two-piece Style 20 (1/2 inch NPT) or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo-spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli-cable approval agencies, the testing is not representative of all possible cor-rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit-ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level of the Series TY-FRB Pendent Sprinklers is detailed in Technical Data Sheet TFP356, and Sprinkler Guards are detailed in Tech-nical Data Sheet TFP780. NOTIce The Series TY-FRB Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the appli-cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manu-facturer should be contacted with any questions. Model/Sprinkler Identification Number (SIN) TY1131: Upright 2.8K, 1/2˝ NPT TY1231: Pendent 2.8K, 1/2˝ NPT TY2131: Upright 4.2K, 1/2˝ NPT TY2231: Pendent 4.2K, 1/2˝ NPT TY3131: Upright 5.6K, 1/2˝ NPT TY3231: Pendent 5.6K, 1/2˝ NPT TY4131: Upright 8.0K, 3/4˝ NPT TY4231: Pendent 8.0K, 3/4˝ NPT TY4831: Upright* 8.0K, 1/2˝ NPT TY4931: Pendent* 8.0K, 1/2˝ NPT *Eastern Hemisphere Sales Only TFP171 Page 2 of 10 WRENCH (38,1 mm)(55,6 mm) 2-7/8" (73,0 mm) DIA. 1 3 1/2" NPT SSP DEFLECTOR FLATS STYLE 10 or 20RECESSEDESCUTCHEON 7/16" (11,1 mm) 5 4 2 6 7/16" MAKE-INNOMINAL (11,1 mm) 2-3/16" DEFLECTORSSU ESCUTCHEONPLATE SEATING (55,6 mm) SURFACE 1-1/2" 1/2"NPT NOMINALMAKE-IN 2-3/16" RECESSED PENDENTCROSS SECTION UPRIGHT PENDENT * * * FIGURe 1 QUIcK ReSPONSe SeRIeS TY-FRB UPRIGHT (TY1131) AND PeNDeNT (TY1231) SPRINKLeRS 2.8 K-FAcTOR, 1/2 INcH NPT FIGURe 2 QUIcK ReSPONSe SeRIeS TY-FRB UPRIGHT (TY2131) AND PeNDeNT (TY2231) SPRINKLeRS 4.2 K-FAcTOR, 1/2 INcH NPT PENDENTCROSS SECTION UPRIGHT RECESSED PENDENT SSP DEFLECTOR 2-1/4"(57,2 mm) (39,7 mm)1-9/16" PLATE SEATINGSURFACE ESCUTCHEON 1/2"NPT WRENCH FLATS MAKE-INNOMINAL 7/16" (11,1 mm) MAKE-INNOMINAL (11,1 mm)7/16" 2-3/16"(55,6 mm) SSUDEFLECTOR 2 7 1 3 5 4 6 2-7/8" (73,0 mm) DIA. RECESSEDSTYLE 10 or 20 ESCUTCHEON 1/2" NPT * * * 1 - Frame 3 - Sealing Assembly 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.2 - Button 5 - Compression Screw 7 - Bushing 1 - Frame 3 - Sealing Assembly 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.2 - Button 5 - Compression Screw TFP171 Page 3 of 10 SSP DEFLECTOR WRENCH(55,6 mm) 1 3 1/2" NPT FLATS 5 4 2 6 7/16" (11,1 mm) SSU DEFLECTOR 7/16" 2-3/16" NOMINAL MAKE-IN (11,1 mm) NOMINAL MAKE-IN 1/2" NPT (38,1 mm) 2-7/8" (73,0 mm) DIA. STYLE 10 or 20ESCUTCHEON 2-3/16"(55,6 mm) 1-1/2" PLATE SEATING SURFACE RECESSED ESCUTCHEON PENDENTCROSS SECTION UPRIGHT RECESSED PENDENT * * * (39,7 mm)(57,2 mm) 1 3 3/4" NPT SSP DEFLECTOR 2-7/8" (73,0 mm) DIA. (12,7 mm) MAKE-INNOMINAL 5 4 2 2-1/4" 6 ESCUTCHEON1/2" (12,7 mm) 1/2" DEFLECTOR SSU NOMINALMAKE-IN 1-9/16" 2-5/16"(58,7 mm) PLATE SEATINGSURFACE3/4" NPT STYLE 30 or 40 RECESSED ESCUTCHEON CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT * * * FIGURe 3 QUIcK ReSPONSe SeRIeS TY-FRB UPRIGHT (TY3131) AND PeNDeNT (TY3231) SPRINKLeRS 5.6 K-FAcTOR, 1/2 INcH NPT FIGURe 4 QUIcK ReSPONSe SeRIeS TY-FRB UPRIGHT (TY4131) AND PeNDeNT (TY4231) SPRINKLeRS 8.0 K-FAcTOR, 3/4 INcH NPT 1 - Frame 3 - Sealing Assembly 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.2 - Button 5 - Compression Screw 1 - Frame 3 - Sealing Assembly 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.2 - Button 5 - Compression Screw TFP171 Page 4 of 10 † Registered Trademark of Dupont Technical Data ApprovalsUL and C-UL Listed FM, LPCB, and NYC Approved Refer to Table A and B for complete approval information including corrosion-resistant status. Maximum Working Pressure Refer to Table C. Discharge Coefficient K=2.8 GPM/psi1/2 (40,3 LPM/bar1/2) K=4.2 GPM/psi1/2 (60,5 LPM/bar1/2) K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) K=8.0 GPM/psi1/2 (115,2 LPM/bar1/2) Temperature Rating Refer to Table A and B. Finishes Sprinkler: Refer to Table A and B. Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated. Physical CharacteristicsFrame...................Bronze Button..............Brass/Copper Sealing Assembly. . . . . . . . .Beryllium Nickel w/Teflon† Bulb ......................Glass Compression Screw. . . . . . . . Bronze Deflector...........Copper/Bronze Bushing (K=2.8) . . . . . . . . . . . Bronze (39,7 mm)WRENCH(55,6 mm)3 1 DEFLECTOR1/2" NPT SSP FLATS DEFLECTOR (11,1 mm) NOMINAL 2 4 5 6 MAKE-IN 2-3/16" 7/16" 7/16" (11,1 mm) 1/2"NPT NOMINAL MAKE-IN SSU 2-1/4"(57,2 mm) 1-9/16" SECTION CROSS PENDENTUPRIGHT * * * FIGURe 5 QUIcK ReSPONSe SeRIeS TY-FRB UPRIGHT (TY4831) AND PeNDeNT (TY4931) SPRINKLeRS 8.0 K-FAcTOR, 1/2 INcH NPT Operation The glass Bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB Pendent and Upright Sprinklers are intended for fire protection systems designed in accordance with the standard installa-tion rules recognized by the applicable Listing or Approval agency (such as, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Preven-tion Data Sheets). Only the Style 10, 20, 30, or 40 Recessed Escutcheon, as applicable, is to be used for recessed pendent installations. Installation The TYCO Series TY-FRB Sprinklers must be installed in accordance with the following instructions. NOTIce Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bub-ble should be present. The diameter of the air bubble is approximately 1/16 1 - Frame 3 - Sealing Assembly 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.2 - Button 5 - Compression Screw inch (1,6 mm) for the 135°F/57°C and 3/32 inch (2,4 mm) for the 286°F/141°C temperature ratings. Obtain a leak-tight 1/2 inch NPT sprin-kler joint by applying a minimum to maximum torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with con-sequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutch-eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. The Series TY-FRB Pendent and Upright Sprinklers must be installed in accordance with the following instructions. 1. Install Pendent sprinklers in the pendent position. Install upright sprinklers in the upright position. 2. With pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. 3. Tighten the sprinkler into the sprin-kler fitting using only the W-Type 6 Sprinkler Wrench (Figure 14). With reference to Figures 1 through 5, apply the W-Type 6 Sprinkler Wrench to the sprinkler wrench flats. TFP171 Page 5 of 10 SPRINKLER FINISH (See Note 5) K FACToR TYPE TEMPERATuRE BuLB LIQuID CoLoR NATuRAL BRASS CHRoME PLATED WHITE*** PoLYESTER 2.8 1/2” NPT PENDENT (TY1231) and uPRIGHT (TY1131) 135°F/57°C Orange 1, 2, 3, 4 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY1231)* Figure 6 135°F/57°C Orange 1, 2, 4 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green RECESSED PENDENT (TY1231)** Figure 7 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 4.2 1/2” NPT PENDENT (TY2231) and uPRIGHT (TY2131) 135°F/57°C Orange 1, 2 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY2231)* Figure 8 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green RECESSED PENDENT (TY2231)** Figure 9 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green NoTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. * Installed with Style 10 (1/2” NPT) or Style 40 (3/4” NPT) 3/4” Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2” NPT) or Style 30 (3/4” NPT) 1/2” Total Adjustment Recessed Escutcheon, as applicable. *** Frame and Deflector only. Listings and approvals apply to color (Special Order). N/A: Not Available TABLe A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FAcTOR SPRINKLeRS TFP171 Page 6 of 10 SPRINKLER FINISH (See Note 8) K FACToR TYPE TEMPERATuRE BuLB LIQuID CoLoR NATuRAL BRASS CHRoME PLATED WHITE*** PoLYESTER LEAD CoATED 5.6 1/2” NPT PENDENT (TY3231) and uPRIGHT (TY3131) 135°F/57°C Orange 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY3231)* Figure 10 135°F/57°C Orange 1, 2, 4, 5 N/A 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY3231)** Figure 11 135°F/57°C Orange 1, 2, 3, 4, 5 N/A 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue 8.0 3/4” NPT PENDENT (TY4231) and uPRIGHT (TY4131) 135°F/57°C Orange 1, 2, 3, 4, 5, 6, 7 1, 2, 5 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY4231)* Figure 12 135°F/57°C Orange 1, 2, 5 N/A 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY4231)** Figure 13 135°F/57°C Orange 1, 2, 3, 5 N/A 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue 8.0 1/2” NPT PENDENT (TY4931) and uPRIGHT (TY4831) 135°F/57°C Orange 1, 2, 4, 5, 6 1, 2, 5 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue NoTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. * Installed with Style 10 (1/2” NPT) or Style 40 (3/4” NPT) 3/4” Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2” NPT) or Style 30 (3/4” NPT) 1/2” Total Adjustment Recessed Escutcheon, as applicable. *** Frame and Deflector only. Listings and approvals apply to color (Special Order). N/A: Not Available TABLe B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FAcTOR SPRINKLeRS TFP171 Page 7 of 10 The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor-dance with the following instructions. 1. After installing the Style 10, 20, 30, or 40 Mounting Plate, as applica-ble, over the sprinkler threads and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. 2. Tighten the sprinkler into the sprin-kler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Fig-ure 15). With reference to Figures 1 to 4, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. 3. After ceiling installation and finish-ing, slide on the Style 10, 20, 30, or 40 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Care and Maintenance The TYCO Series TY-FRB must be maintained and serviced in accordance with the following instructions. NOTIce Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Exercise care to avoid damage to sprinklers before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory. Replace sprinklers that: • were modified or over-heated. • were damaged by dropping, striking, wrench twisting, wrench slippage, or the like. • are leaking or exhibiting visible signs of corrosion. • were exposed to corrosive products of combustion but have not oper-ated, if you cannot easily remove combustion by-products with a cloth. • have a cracked bulb or have lost liq-uid from the bulb. Refer to the Instal-lation section in this data sheet. SPRINKLER FINISH K FACToR TYPE NATuRAL BRASS CHRoME PLATED WHITE PoLYESTER LEAD CoATED 2.8 1/2” NPT PENDENT (TY1231) and uPRIGHT (TY1131)175 PSI (12,1 BAR)N/A RECESSED PENDENT (TY1231) 4.2 1/2” NPT PENDENT (TY2231) and uPRIGHT (TY2131)175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY2231) 5.6 1/2” NPT PENDENT (TY3231) and uPRIGHT (TY3131) 250 PSI (17,2 BAR) OR 175 PSI (12,1 BAR) (SEE NOTE 1) 175 PSI (12,1 BAR) RECESSED PENDENT (TY3231)N/A 8.0 3/4” NPT PENDENT (TY4231) and uPRIGHT (TY4131)175 PSI (12,1 BAR) 175 PSI (12,1 BAR) RECESSED PENDENT (TY4231)N/A 8.0 1/2” NPT PENDENT (TY4931) and uPRIGHT (TY4831)175 PSI (12,1 BAR)175 PSI (12,1 BAR) NoTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. TABLe c MAXIMUM WORKING PReSSURe TFP171 Page 8 of 10 Initial and frequent visual inspections of random samples are recommended for corrosion-resistant sprinklers to verify the integrity of the corrosion-resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice. Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprin-kler condition and the long-term integ-rity of the corrosion-resistant material, which can be affected by the corrosive conditions present. Responsibility lies with the owner for the inspection, testing, and mainte-nance of their fire protection system and devices in compliance with this document, as well as with the appli-cable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any other authorities having jurisdic-tion. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes. Care must be exercised to avoid dam-age to the sprinklers -before, during, and after installation. Sprinklers dam-aged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). Initial and frequent visual inspections of random samples are recommended for corrosion-resistant sprinklers to verify the integrity of the corrosion-resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice. FIGURe 6 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 3/4 INcH TOTAL ADJUSTMeNT STYLe 10 ReceSSeD eScUTcHeON 2.8 K-FAcTOR, 1/2 INcH NPT (57,2 mm)2-1/4" DIA. (73,0 mm)2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SERIES SURFACE FACE OF FITTING (15,9±6,4 mm)5/8±1/4" (3,2 mm) 13/16" (20,6 mm) 1-5/16" (33,3 mm) PLATEMOUNTING 1/8" 1/4" (6,4 mm) 3/4" (19,1 mm) TY-FRB (12,7±3,2 mm)1/2±1/8" 2-1/4" DIA.(57,2 mm) (73,0 mm)2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SURFACE FACE OF FITTING (3,2 mm) 1-1/16" (27,0 mm) 1-5/16" (33,3 mm) PLATEMOUNTING 1/8" 1/4" (6,4 mm) 1/2" (12,7 mm) TY-FRB SERIES FIGURe 7 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 1/2 INcH TOTAL ADJUSTMeNT STYLe 20 ReceSSeD eScUTcHeON 2.8 K-FAcTOR, 1/2 INcH NPT (57,2 mm)2-1/4" DIA. (73,0 mm)2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SERIES SURFACE FACE OF FITTING (15,9±6,4 mm)5/8±1/4" (3,2 mm) 3/4" (19,1 mm) 1-1/4" (31,8 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 3/4" (19,1 mm) TY-FRB FIGURe 8 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 3/4 INcH TOTAL ADJUSTMeNT STYLe 10 ReceSSeD eScUTcHeON 4.2 K-FAcTOR, 1/2 INcH NPT (12,7±3,2 mm)1/2±1/8" 2-1/4" DIA.(57,2 mm) (73,0 mm)2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SURFACE FACE OF FITTING (3,2 mm) 1" (25,4 mm) 1-1/4" (31,8 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 1/2" (12,7 mm) TY-FRB SERIES FIGURe 9 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 1/2 INcH TOTAL ADJUSTMeNT STYLe 20 ReceSSeD eScUTcHeON 4.2 K-FAcTOR, 1/2 INcH NPT TFP171 Page 9 of 10 FIGURe 10 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 3/4 INcH TOTAL ADJUSTMeNT STYLe 10 ReceSSeD eScUTcHeON 5.6 K-FAcTOR, 1/2 INcH NPT (57,2 mm)2-1/4" DIA. (73,0 mm)2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SERIES SURFACE FACE OF FITTING (15,9±6,4 mm)5/8±1/4" (3,2 mm) 3/4" (19,1 mm) 1-1/4" (31,8 mm) PLATEMOUNTING 1/8" 1/4" (6,4 mm) 3/4" (19,1 mm) TY-FRB (12,7±3,2 mm)1/2±1/8" 2-1/4" DIA.(57,2 mm) (73,0 mm)2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SURFACE FACE OF FITTING (3,2 mm) 1" (25,4 mm) 1-1/4" (31,8 mm) PLATEMOUNTING 1/8" 1/4" (6,4 mm) 1/2" (12,7 mm) TY-FRBSERIES FIGURe 11 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 1/2 INcH TOTAL ADJUSTMeNT STYLe 20 ReceSSeD eScUTcHeON 5.6 K-FAcTOR, 1/2 INcH NPT 2-7/8" DIA.(73,0 mm) 2-1/4" DIA.(57,2 mm) MOUNTING SPRINKLER CLOSURE SURFACE FITTING FACE OF (12,7±3,2 mm)1/2±1/8" 1-5/16" (33,3 mm) 1-1/16" (27,0 mm) MOUNTING PLATE (3,2 mm)1/8" 1/2" (12,7 mm) 1/4" (6,4 mm) SERIES TY-FRB FIGURe 12 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 3/4 INcH TOTAL ADJUSTMeNT STYLe 40 ReceSSeD eScUTcHeON 8.0 K-FAcTOR, 3/4 INcH NPT 2-7/8" DIA.(73,0 mm) 2-1/4" DIA.(57,2 mm) MOUNTING SPRINKLER CLOSURE SURFACE FITTING FACE OF (15,9±6,4 mm)5/8±1/4" MOUNTING PLATE 1-5/16" (33,3 mm) 13/16" (20,6 mm) (3,2 mm)1/8" 3/4" (19,1 mm) 1/4" (6,4 mm) SERIES TY-FRB FIGURe 13 SeRIeS TY-FRB ReceSSeD PeNDeNT WITH TWO-PIece 1/2 INcH TOTAL ADJUSTMeNT STYLe 30 ReceSSeD eScUTcHeON 8.0 K-FAcTOR, 3/4 INcH NPT WRENCH RECESS(END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS(END "B" USED FOR3/4" NPT MODELS) RECESS WRENCH PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREAFIGURe 14 W-TYPe 6 SPRINKLeR WReNcH FIGURe 15 W-TYPe 7 ReceSSeD SPRINKLeR WReNcH Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprin-kler condition and the long-term integ-rity of the corrosion-resistant material, which can be affected by the corrosive conditions present. Copyright © 2007-2010 Tyco Fire Suppression & Building Products. All rights reserved. TFP171 Page 10 of 10 Limited Warranty Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for prod-ucts or components manufactured by companies not affiliated by ownership with TFSBP or for products and com-ponents which have been subject to misuse, improper installation, corro-sion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Associa-tion, and/or the standards of any other Authorities Having Jurisdiction. Mate-rials found by TFSBP to be defective shall be either repaired or replaced, at TFSBP’s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete infor-mation supplied by Buyer or Buyer’s representatives. In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam-ages, including but not limited to labor charges, regardless of whether TFSBP was informed about the possibility of such damages, and in no event shall TFSBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of mer-chantability and fitness for a particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materi-als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread ConnectionsSpecify: (Specify Model/SIN), Quick Response, (specify K-factor), (specify temperature rating), Series TY-FRB (specify Pendent or Upright) Sprinkler with (specify type of finish or coating), P/N (specify from Table D). Recessed Escutcheon: Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify*) finish, P/N (specify*). Sprinkler WrenchSpecify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. * Refer to Technical Data Sheet TFP770. TABLe D PART NUMBeR SeLecTION SeRIeS TY-FRB PeNDeNT AND UPRIGHT SPRINKLeRS P/N 57 – XXX – X – XXX SPRINKLER FINISH 1 NATURAL BRASS 4 WHITE POLYESTER 3 WHITE (RAL9010)* 9 CHROME PLATED 7 LEAD COATED TEMPERATURE RATINGS 135 135°F (57°C) 155 155°F (68°C) 175 175°F (79°C) 200 200°F (93°C) 286 286°F (141°C) MODEL/SIN 330 2.8K UPRIGHT (1/2”NPT)TY1131 331 2.8K PENDENT (1/2”NPT)TY1231 340 4.2K UPRIGHT (1/2”NPT)TY2131 341 4.2K PENDENT (1/2”NPT)TY2231 370 5.6K UPRIGHT (1/2”NPT)TY3131 371 5.6K PENDENT (1/2”NPT)TY3231 390 8.0K UPRIGHT (3/4”NPT)TY4131 391 8.0K PENDENT (3/4”NPT)TY4231 360 8.0K UPRIGHT (1/2”NPT)TY4831* 361 8.0K PENDENT (1/2”NPT)TY4931* * Eastern Hemisphere sales only. Ball Valves 18 FullPortBallValves Multi-purpose shut-off valve for use in domestic hot and cold water systems, natural and bottled gas applications, and compressed air services. 1/4—2 600psi CWP@100¡F; 21/2—4400psi CWP@100¡F PARTSPECIFICATION Handle Zinc-Plated Steel with Vinyl Sleeve Handle Nut Zinc-Plated Steel Threaded Packing Gland Brass Packing PTFE Stem Seal Viton “O” Ring Thrust Washer PTFE Seats PTFE Stem Brass Ball Chrome-Plated Brass Body Forged Brass Body End Forged Brass Bronze Full Port Threaded Valve (Female)T-FP-600 NOM.APPROXDIMENSIONS/INCHESSIZENET WT./LBS.ABC PORTDE 1/4.40 1.813.35.391.52- 3/8.40 1.813.35.471.52- 1/2.51 2.323.35.591.61- 3/4.73 2.653.35.791.78- 11.19 3.054.131.001.97- 1 1/41.72 3.624.131.262.19- 1 1/22.50 4.005.121.572.70- 24.25 4.825.122.002.99- 2 1/27.00 5.579.452.504.25- 39.40 6.389.453.005.00- 416.50 7.769.454.005.51- B D C A] • All valves: AGA 3-88, CR 91-002 • ULSubject 258 • Each valve is individually tested in ISO9002 certified facility NIBCO INC. World Headquarters 1516 Middlebury St. Elkhart, IN46516-4714 U.S.A. www.nibco.com Series LFII Residential Sprinklers 4.2K Horizontal and Recessed Horizontal Sidewall Wet Pipe and Dry Pipe Systems Page 1 of 10 SEPTEMBER 2010 TFP410 Technical Services 800-381-9312 | +1-401-781-8220 www.tyco-fire.com General Description The TYCO RAPID RESPONSE Series LFII Residential Horizontal Sidewall Sprinklers (TY1334) are decorative, fast response, frangible bulb sprin-klers designed for use in residential occupancies such as homes, apart-ments, dormitories, and hotels. When aesthetics and optimized flow charac-teristics are the major consideration, the Series LFII Residential Sidewall Sprinklers should be the first choice. The Series LFII Residential Sprinklers are intended for use in the following scenarios: • wet and dry pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 Historically residential sprinklers, based on their Listing, have been limited to wet pipe sprinkler systems to assure speed of water delivery for a given prescribed design area (number of design sprinklers). The Listing for the Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers now offers the laboratory approved option of designing dry pipe residential sprinkler systems. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Sprinklers need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/ area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residential Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. Non-water filled pipe will permit options for areas sensitive to freezing The Series LFII Residential Sprinklers has a 4.2 (60,5) K-Factor that provides the required residential flow rates at reduced pressures, enabling smaller pipe sizes and water supply requirements. The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished walls. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjust-ment from the flush mounting surface position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe nipples to the sprinklers must be cut. The Series LFII Residential Sprinklers has been designed with heat sensitivity and water distribution characteristics proven to help in the control of residen-tial fires and to improve the chance for occupants to escape or be evacuated. IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. NOTICE The Series LFII Residential Horizontal Sidewall Sprinklers described herein must be installed and maintained in compliance with this document and the applicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manu-facturer should be contacted with any questions. Model/Sprinkler Identification Number (SIN) TY1334 TFP410 Page 2 of 10 WRENCH RECESS(END "A" USEDFOR TY1334) 1-3/8" (34,9 mm) 1-1/8" (28,6 mm) MOUNTING PLATE TY1334 MOUNTING SURFACE CLOSURE (73,0 mm) 1/2" (12,7 mm) (57,2 mm)2-1/4" DIA. 1/4" (6,4 mm) 1/8"(3,2 mm) (11,1±3,2 mm) SPRINKLER FITTING FACE OF 7/16±1/8" 2-7/8" DIA. BOSS END-OF- DEFLECTOR TOP-OF- DEFLECTOR 7/16"(11,1 mm) 7/16" (11,1 mm) MAKE-IN NOMINAL SURFACE ESCUTCHEONPLATE SEATING Sealing Assembly-3 5 4 * 6 Compression Screw of Deector.is indicated on top Temperature rating Bulb Deector- - - * 1 Components: 2 Button Assembly Frame- - TO P (57,2 mm) 2-1/4" (41,3 mm) 1-5/8" *6 4 5 3 2 1 2-7/8" DIA. (73,0 mm) RECESSED ESCUTCHEON STYLE 20 FLATS WRENCH CENTERLINE OF WATERWAY 1/2" NPT BOSS END-OF-DEFLECTOR TOP-OF- DEFLECTOR 7/16"(11,1 mm) FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER (TY1334) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH RECESS WRENCH WITH SPRINKLER ENGAGEMENTIN TO ENSURE WRENCHING AREA PUSH WRENCH TFP410 Page 3 of 10 Technical Data Approvals• UL Listed for use with wet pipe and dry pipe systems • C-UL Listed for use only with wet pipe systems • NYC Approved under MEA 44-03-E For details on these approvals, refer to the Design Criteria section. Maximum Working Pressure175 psi (12,1 bar) Discharge CoefficientK=4.2 GPM/psi1/2 (60,5 LPM/bar1/2) Temperature Rating155°F (68°C) or 175°F (79°C) Finishes• White Polyester • Chrome Plated • Natural Brass Physical CharacteristicsFrame ....................Brass Button ...................Bronze Sealing Assembly ........Beryllium Nickel w/Teflon* Bulb (3 mm) ................Glass Compression Screw ........Bronze Deflector .................Copper Operation The glass Bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, allowing the sprinkler to activate and flow water. Design Criteria The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers (TY1334) are UL and C-UL Listed for installa-tion in accordance with the following criteria. Note: When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer’s recommendations that may be acceptable to the local authority having jurisdiction. *Registered trademark of Dupont System TypesPer the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. • For dry systems corrosion-resistant or internally galvanized pipe shall be utilized with the sprinklers de-scribed in this data sheet. • For dry systems not using CPVC, pendent sprinklers shall be installed on return bends, where the sprin-klers, return bends, and branch line piping (that is, potential areas for trapped water) are in areas at or above 40°F (4°C). Refer to technical data sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems. NOTICE When corrosion-resistant or inter-nally galvanized pipe and fittings with a potable water supply is utilized, return bends need not be installed. However, any portion of the piping that has the potential to trap water must be maintained at or above 40°F (4°C) unless provision to drain such areas is provided and maintained dry. Water DeliveryWhen using the Series LFII Residential Horizontal Sidewall Sprinklers (TY1334) in dry pipe sprinkler systems, the requirements for “Dry System Water Delivery” per the Section 8.3.4.3 of the 2010 edition of NFPA 13D apply. For a residential hazard, in no case shall the time of water delivery exceed 15 seconds for the most remote operating sprinkler. Hydraulic Design (NFPA 13D and 13R)The minimum re quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A, B, C, D and E as a function of tempera-ture rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. NOTICE The number of “design sprinklers” specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. There is no need to increase the design area, as is the case for density/area systems, in accordance with U.S. Patent 7,712,543. Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A or B for NFPA 13D and 13R as a function of temperature rating and the maxi-mum allowable coverage area. • A minimum discharge of 0.1 GPM/sq. ft. over the “design area” com-prised of the four most hydraulical-ly demanding sprinklers for actu-al coverage areas protected by the four sprinklers. NOTICE The number of “design sprin-klers” specified in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. There is no need to increase the design area, as is the case for density/area systems, in accordance with U.S. Patent 7,712,543. Obstruction to Water DistributionSprinklers are to be located in accor-dance with the obstruction rules defined by NFPA 13 for residential sprinklers. Operational SensitivityThe sprinklers are to be installed with an end-of- deflector-boss to wall distance of 1-3/8 to 6 inches or in the recessed position using only the Style 20 Recessed Escutcheon as shown in Figure 2. In addition the top-of-deflector-to-ceiling distance is to be within the range (Tables A, B, C, D or E) being hydrauli-cally calculated. Sprinkler SpacingThe minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the width of the coverage area (Tables A and B) being hydraulically calculated; (maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 16 feet for a 16 ft. x 20 ft. coverage area. TFP410 Page 4 of 10 ELEVATION TABLE A SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334) FOR HORIZONTAL CEILINGS NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS (Maximum 2-Inch Rise for 12-Inch Run) Maximum Coverage Area (a) Width x Length (b) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow (c) and Residual Pressure Top-of-Deflector-to-Ceiling: 4 to 6 Inches (100 to 150 mm)Top-of-Deflector-to-Ceiling: 6 to 12 Inches (150 to 300 mm) 155°F (68°C)175°F (79°C) 155°F (68°C)175°F (79°C) 12 x 12 (3,7 x 3,7)12 (3,7)12 GPM (45,4 LPM) 8.2 psi (0,57 bar) 12 GPM (45,4 LPM) 8.2 psi (0,57 bar) 13 GPM (49,2 LPM) 9.6 psi (0,66 bar) 13 GPM (49,2 LPM) 9.6 psi (0,66 bar) 14 x 14 (4,3 x 4,3)14 (4,3)14 GPM (53,0 LPM) 11.1 psi (0,77 bar) 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) 17 GPM (64,3 LPM) 16.4 psi (1,13 bar)18 GPM (68,1 LPM) 18.4 psi (1,27 bar) 16 x 16 (4,9 x 4,9)16 (4,9)16 GPM (60,6 LPM) 14.5 psi (1,00 bar) 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) 18 GPM (68,1 LPM) 18.4 psi (1,27 bar)18 GPM (68,1 LPM) 18.4 psi (1,27 bar) 16 x 18 (4,9 x 5,5)16 (4,9)19 GPM (71,9 LPM) 20.5 psi (1,41 bar) 19 GPM (71,9 LPM) 20.5 psi (1,41 bar) 21 GPM (79,5 LPM) 25.0 psi (1,72 bar) 21 GPM (79,5 LPM) 25.0 psi (1,72 bar) 16 x 20 (4,9 x 6,1)16 (4,9)23 GPM (87,1 LPM) 30.0 psi (2,07 bar) 23 GPM (87,1 LPM) 30.0 psi (2,07 bar) 26 GPM (98,4 LPM) 38.3 psi (2,64 bar) 26 GPM (98,4 LPM) 38.3 psi (2,64 bar) Sidewall sprinklers, where installed under a ceiling with a slope greater than a 0-inch rise for a 12-inch run to a slope up to a 2-inch rise for a 12-inch run, must be located per one of the following: • At the high positioned to discharge down the slope. • Along the slope and positioned to discharge across the slope. (a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler). (c). The Minimum Flow Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details. TFP410 Page 5 of 10 Maximum Coverage Area (a) Width x Length (b) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) DRY PIPE SYSTEM Minimum Flow (c) and Residual Pressure Top-of-Deflector-to-Ceiling: 4 to 6 Inches (100 to 150 mm)Top-of-Deflector-to-Ceiling: 6 to 12 Inches (100 to 150 mm) 155°F (68°C)175°F (79°C) 155°F (68°C)175°F (79°C) 12 x 12(3,7 x 3,7)12(3,7)12 GPM (45,4 LPM)8.2 psi (0,57 bar)12 GPM (45,4 LPM)8.2 psi (0,57 bar)13 GPM (49,2 LPM)9.6 psi (0,48 bar)13 GPM (49,2 LPM)9.6 psi (0,48 bar) 14 x 14(4,3 x 4,3)14(4,3)16 GPM (60,6 LPM)14.5 psi (1,00 bar)16 GPM (60,6 LPM)14.5 psi (1,00 bar)18 GPM (68,1 LPM)18.4 psi (1,27 bar)18 GPM (68,1 LPM)18.4 psi (1,27 bar) 16 x 16(4,9 x 4,9)16(4,9)16 GPM (60,6 LPM)14.5 psi (1,00 bar)16 GPM (60,6 LPM)14.5 psi (1,00 bar)18 GPM (68,1 LPM)18.4 psi (1,27 bar)21 GPM (79,5 LPM)25.0 psi (1,72 bar) 16 x 18(4,9 x 5,5)16(4,9)19 GPM (71,9 LPM) 20.5 psi (1,41 bar) Not Applicable 21 GPM (79,5 LPM)25.0 psi (1,72 bar)21 GPM (79,5 LPM)25.0 psi (1,72 bar) 16 x 20(4,9 x 6,1)16(4,9)23 GPM (87,1 LPM)30.0 psi (2,07 bar)Not Applicable Not Applicable Not Applicable Sidewall sprinklers, where installed under a ceiling with a slope greater than a 0-inch rise for a 12-inch run to a slope up to a 2-inch rise for a 12-inch run, must be located per one of the following: • At the high positioned to discharge down the slope. • Along the slope and positioned to discharge across the slope. (a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler). (c). The Minimum Flow Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details. TABLE B SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334) FOR HORIZONTAL CEILINGS NFPA 13D HYDRAULIC DESIGN CRITERIADRY PIPE SYSTEMS (Maximum 2-Inch Rise for 12-Inch Run) ELEVATION TFP410 Page 6 of 10 ELEVATION 12" 8"MAXIMUM TABLE C SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334) AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS (Greater Than 2-Inch Rise for 12-Inch Run Up To 8-Inch Rise for 12-Inch Run) Maximum Coverage Area (a) Width x Length (b) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow (c) and Residual Pressure ( I ) Two sprinkler design with the sprinklers at the high point of the slope and positioned to discharge down the slope. Top-of-Deflector-to-Ceiling: 4 to 6 Inches (100 to 150 mm)Top-of-Deflector-to-Ceiling: 6 to 12 Inches (150 to 300 mm) 155°F (68°C)175°F (79°C) 155°F (68°C)175°F (79°C) 12 x 12 (3,7 x 3,7)12 (3,7)I 12 GPM (45,4 LPM) 8.2 psi (0,57 bar) I 12 GPM (45,4 LPM) 8.2 psi (0,57 bar) I 13 GPM (49,2 LPM) 9.6 psi (0,66 bar) I 13 GPM (49,2 LPM) 9.6 psi (0,66 bar) 14 x 14 (4,3 x 4,3)14 (4,3)I 14 GPM (53,0 LPM) 11.1 psi (0,77 bar) I 14 GPM (53,0 LPM) 11.1 psi (0,77 bar) I 17 GPM (64,3 LPM) 16.4 psi (1,13 bar)I 17 GPM (64,3 LPM) 16.4 psi (1,13 bar) 16 x 16 (4,9 x 4,9)16 (4,9)I 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) I 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) I 18 GPM (68,1 LPM) 18.4 psi (1,27 bar)I 18 GPM (68,1 LPM) 18.4 psi (1,27 bar) 16 x 18 (4,9 x 5,5)16 (4,9)I 19 GPM (71,9 LPM) 20.5 psi (1,41 bar) I 19 GPM (71,9 LPM) 20.5 psi (1,41 bar) I 21 GPM (79,5 LPM) 25.0 psi (1,72 bar) I 21 GPM (79,5 LPM) 25.0 psi (1,72 bar) 16 x 20 (4,9 x 6,1)16 (4,9)I 24 GPM (90,8 LPM) 32.7 psi (2,25 bar) I 24 GPM (90,8 LPM) 32.7 psi (2,25 bar) I 26 GPM (98,4 LPM) 38.3 psi (2,64 bar) I 26 GPM (98,4 LPM) 38.3 psi (2,64 bar) (a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler). (c). The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details. TFP410 Page 7 of 10 ELEVATION 12" MAXIMUM4" TABLE D SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334) LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS (Greater Than 2-Inch Rise for 12-Inch Run Up To 4-Inch Rise for 12-Inch Run) Maximum Coverage Area (a) Width x Length (b) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow (c) and Residual Pressure ( II ) Two sprinkler design with the sprinklers located along the slope and positioned to discharge across the slope. ( III ) Three sprinkler design when there are more than two sprinklers in a compartment and with the sprinklers located along the slope and positioned to discharge across the slope. Top-of-Deflector-to-Ceiling: 4 to 6 Inches (100 to 150 mm) Top-of-Deflector-to-Ceiling: 6 to 12 Inches (150 to 300 mm) 155°F (68°C)175°F (79°C)155°F (68°C)175°F (79°C) 12 x 12 (3,7 x 3,7)12 (3,7)II 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) II 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) II 18 GPM (68,1 LPM) 18.4 psi (1,27 bar) II 18 GPM (68,1 LPM) 18.4 psi (1,27 bar) 14 x 14 (4,3 x 4,3)14 (4,3)II 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) II 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) II 18 GPM (68,1 LPM) 18.4 psi (1,27 bar)II 18 GPM (68,1 LPM) 18.4 psi (1,27 bar) 16 x 16 (4,9 x 4,9)16 (4,9)II 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) II 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) II 18 GPM (68,1 LPM) 18.4 psi (1,27 bar)II 18 GPM (68,1 LPM) 18.4 psi (1,27 bar) 16 x 18 (4,9 x 5,5)16 (4,9)II 22 GPM (83,3 LPM) 27.4 psi (1,89 bar) II 22 GPM (83,3 LPM) 27.4 psi (1,89 bar) II 22 GPM (83,3 LPM) 27.4 psi (1,89 bar) II 22 GPM (83,3 LPM) 27.4 psi (1,89 bar) 16 x 20 (4,9 x 6,1)16 (4,9)III 23 GPM (87,1 LPM) 30.0 psi (2,07 bar) III 23 GPM (87,1 LPM) 30.0 psi (2,07 bar) III 26 GPM (98,4 LPM) 38.3 psi (2,64 bar) III 26 GPM (98,4 LPM) 38.3 psi (2,64 bar) (a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler). (c). The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details. TFP410 Page 8 of 10 ELEVATION 12" 8"MAXIMUM TABLE E SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334) LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS (Greater Than 4-Inch Rise for 12-Inch Run Up to 8-Inch Rise for 12-Inch Run) Maximum Coverage Area (a) Width x Length (b) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow (c) and Residual Pressure ( III ) Three sprinkler design when there are more than two sprinklers in a compartment and with the sprinklers located along the slope and positioned to discharge across the slope. Top-of-Deflector-to-Ceiling: 4 to 6 Inches (100 to 150 mm) 155°F (68°C)175°F (79°C) 12 x 12 (3,7 x 3,7)12 (3,7)III 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) III 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) 14 x 14 (4,3 x 4,3)14 (4,3)III 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) III 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) 16 x 16 (4,9 x 4,9)16 (4,9)III 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) III 16 GPM (60,6 LPM) 14.5 psi (1,00 bar) 16 x 18 (4,9 x 5,5)16 (4,9) N/A N/A 16 x 20 (4,9 x 6,1)16 (4,9) N/A N/A (a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler). (c). The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details. TFP410 Page 9 of 10 Installation The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers (TY1334) must be installed in accordance with the following instructions. NOTICE Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). Obtain a leak-tight 1/2 inch NPT sprinkler joint by applying a minimum to maximum torque of 7 to 14 ft. lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under- or over-tightening the Sprinkler. Re-adjust the position of the sprinkler fitting to suit. Series LFII Residential Horizontal Sidewall Sprinklers The Series LFII Residential Horizontal Sidewall Sprinklers must be installed in accordance with the following instructions. 1. Install horizontal sidewall sprinklers in the horizontal position with their center-line of waterway perpen-dicular to the backwall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling with the front edge of the Deflector parallel to the ceiling. 2. With pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. 3. Tighten the sprinkler into the sprin-kler fitting using only the W-Type 6 Sprinkler Wrench. (Figure 3). With reference to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats. Series LFII Residential Recessed Horizontal Sidewall Sprinklers The Series LFII Residential Recessed Horizontal Sidewall Sprinklers must be installed in accordance with the following instructions. 1. Install recessed horizontal sidewall sprinklers in the horizontal position with their center-line of waterway perpendicular to the backwall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling. 2. After installing the Style 20 Mounting Plate over the sprin-kler threads and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. 3. Tighten the sprinkler into the sprin-kler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 4). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. 4. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Care and Maintenance The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers (TY1334) must be maintained and serviced in accordance with the following instructions. NOTICE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Owners must assure that the sprin-klers are not used for hanging of any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result. Exercise care to avoid damage to sprinklers before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory. Replace sprinklers that: • were modified or over-heated. • were damaged by dropping, striking, wrench twisting, wrench slippage, or the like. • are leaking or exhibiting visible signs of corrosion. • were exposed to corrosive products of combustion but have not operated, if you cannot easily remove combus-tion by-products with a cloth. • have a cracked bulb or have lost liquid from the bulb. Refer to the Installation section in this data sheet. Initial and frequent visual inspections of random samples are recommended for corrosion-resistant sprinklers to verify the integrity of the corrosion-resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice. Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprinkler condition and the long-term integrity of the corrosion-resistant material, which can be affected by the corrosive condi-tions present. Responsibility lies with the owner for the inspection, testing, and mainte-nance of their fire protection system and devices in compliance with this document, as well as with the appli-cable standards of the National Fire Protection Association (that is, NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recom-mended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. Copyright © 2006-2010 Tyco Fire Suppression & Building Products. All rights reserved. TFP410 Page 10 of 10 Limited Warranty Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for products or components manufac-tured by companies not affiliated by ownership with TFSBP or for products and components which have been subject to misuse, improper instal-lation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with appli-cable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFSBP to be defective shall be either repaired or replaced, at TFSBP’s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be respon-sible for sprinkler system design errors or inaccurate or incomplete infor-mation supplied by Buyer or Buyer’s representatives. In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFSBP was informed about the possi-bility of such damages, and in no event shall TFSBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warran-ties of merchantability and fitness for a particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler AssemblySpecify Series LFII Residential Horizontal Sidewall Sprinkler (TY1334), K=4.2, with (temperature rating) and (finish), and P/N (below). 155°F (68°C) Chrome Plated ............P/N 51-211-9-155 155°F (68°C) White Polyester ............P/N 51-211-4-155 155°F (68°C) White (RAL9010)* ................P/N 51-211-3-155 155°F (68°C) Natural Brass ...............P/N 51-211-1-155 175°F (79°C) or Chrome Plated ............P/N 51-211-9-175 175°F (79°C) White Polyester ............P/N 51-211-4-175 175°F (79°C) White (RAL9010)* ................P/N 51-211-3-175 175°F (79°C) Natural Brass ...............P/N 51-211-1-175 *Eastern Hemisphere sales only. Recessed EscutcheonSpecify Style 20 Recessed Escutcheon with finish and P/N. Refer to Technical Data Sheet TFP770. Sprinkler WrenchSpecify W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. General Description The Tyco® Series DS-1, 5.6 K-factor, Quick Response (3 mm Bulb) and Stan-dard Response (5 mm Bulb), Extend-ed Coverage Horizontal Sidewall, Dry Type Sprinklers are decorative glass bulb automatic sprinklers. They are in-tended for use in applications where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures (e.g., horizontal piping extensions through a wall to protect an unheated area of a build-ing). The Series DS-1 Extended Cov-erage Horizontal Sidewall Sprinklers are designed for extended cover-age use in light hazard occupancies (ECLH). WARNINGS The Series DS-1 Dry Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addi-tion to the standards of any other au-thorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. The Series DS-1 Dry Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Model/Sprinkler Identification Numbers TY3338 - (3 mm Bulb Type) TY3358 - (5 mm Bulb Type) Technical Data Approvals UL and C-UL Listed. NYC Approved. (Refer to Table A) Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connection 1 inch NPT Discharge Coefficient K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Temperature Ratings Refer to Table A FinishesSprinkler: Natural Brass, Chrome Plated, White Polyester Escutcheon: White Coated or Chrome Plated, Brass Plated Physical Characteristics Inlet..................... Copper Plug .....................CopperYoke ...............Stainless Steel Casing ....Galvanized Carbon Steel Insert ....................Bronze Bulb Seat ...........Stainless SteelBulb ......................Glass Compression Screw ........Bronze Deflector ................ Bronze Frame ....................Bronze Guide Tube..........Stainless Steel Water Tube .........Stainless Steel Spring .............Stainless Steel Sealing Assembly ................ . . . . . . . . . Beryllium Nickel w/Teflon* Escutcheon ..........Carbon Steel *Registered Trademark of DuPont Patents U.S.A. Patent No. 5,188,185 Operation When the Series DS-1 is in service, water is prevented from entering the assembly by the Plug & Belleville Seal-ing Assembly (Ref. Figure 1) in the Inlet of the Sprinkler. The glass Bulb contains a fluid that expands when exposed to heat. When the rated tem-perature is reached, the fluid expands sufficiently to shatter the glass Bulb, and the Bulb Seat is released. The compressed Spring is then able to ex-pand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug & Belleville Seal from the Inlet allowing the sprin-kler to activate and flow water. Series DS-1 — 5.6 K-factor Dry Type Sprinklers Standard & Quick Response, Extended Coverage Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Page of 6 MAY, 2008 TFP520 IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. SPRINKLER FINISH TY3338 HSW (3 mm Bulb Type) w/ Standard Escutcheon (Ref. Fig. 2) TY3358 HSW (5 mm Bulb Type) w/ Standard Escutcheon (Ref. Fig. 2) Temperature Rating Bulb Color Code Natural Brass Chrome Plated White Polyester 135°F/57°C Orange 1, 2, 3 155°F/68°C Red 1, 2, 3 Notes: 1. Listed by Underwriters Laboratories, Inc. (Maximum order length of 48 inches). 2. Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches). 3. Approved by the City of New York under MEA 352-01-E. TABLE A SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVAL APPLICATION Coverage (1) W x L Ft. x Ft. (m x m) Min Flow GPM (LPM) Min Pressure PSI (bar) Temperature Rating °F (C°) Top Of Deflector To Ceiling Distance (2) Inches (mm) TY3338 HSW (3 mm Bulb Type) For Quick Response Light Hazard Extended Coverage Per NFPA 13 16 x 16 (4,9 x 4,9)26 (98)21.6 (1,49) 135 & 155 (57 & 68) 4 to 12 (100 to 300) 16 x 18 (4,9 x 5,5)29 (110)26.8 (1,85) 16 x 20 (4,9 x 6,1)32 (121)32.7 (2,25) 18 x 16 (5,5 x 4,9)29 (110)26.8 (1,85) APPLICATION Coverage (1) W x L Ft. x Ft. (m x m) Min Flow GPM (LPM)Min Pressure PSI (bar )Temperature Rating °F (C°) Top Of Deflector To Ceiling Distance (2) Inches (mm) TY3358 HSW (5 mm Bulb Type) For Standard Response Light Hazard Extended Coverage Per NFPA 13 16 x 16 (4,9 x 4,9)26 (98)21.6 (1,49) 135 & 155 (57 & 68) 4 to 12 (100 to 300) 16 x 18 (4,9 x 5,5)29 (110)26.8 (1,85) 16 x 20 (4,9 x 6,1)32 (121)32.7 (2,25) 18 x 16 (5,5 x 4,9)29 (110)26.8 (1,85) Notes: 1. The minimum allowable spacing between sprinklers to prevent cold soldering is 14 feet (4,3 m). 2. To meet the deflector-to-ceiling distance of 4 to 12 inches (100 to 300 mm), the centerline of the sprinkler waterway must be 4-7/16 to 12-7/16 inches below the ceiling. TABLE B SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS UL AND C-UL INSTALLATION CRITERIA Page 2 of 6 TFP520 Design Criteria The Tyco® Series DS-1 Sprinklers are in-tended for use in fire sprinkler systems designed in accordance with the ex-tended coverage installation guide-lines provided by NFPA 13 and the in-stallation criteria provide by Table B. The 1 inch NPT Series DS-1 Sprin-klers are to be installed in the 1 inch NPT outlet or run of malleable or duc-tile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3 (Class 150) or cast iron threaded tee fittings that meet the dimension-al requirements of ANSI B16.4 (Class 125). The Series DS-1 Sprinklers may also be installed in the 1 inch NPT out-let of a Grinnell Figure 730 Mechani-cal Tee. Typically, the end sprinkler fitting on a branch line is plugged as shown in Figure 2. The DS-1 Sprinklers cannot be installed into an elbow fitting. For wet pipe systems, the DS-1 Sprin-klers may also be installed in the fol-lowing Tyco® CPVC fittings: (P/N 80145) 1” x 1” NPT Female Adapter or (P/N 80249) 1” x 1” x 1” NPT Sprinkler Head Adapter Tee. NOTEDo not install the Series DS-1 into any other type fitting without first con-sulting the Technical Services De-partment. Failure to use the appro-priate fitting may result in: failure of the sprinkler to properly operate due to formation of ice over the inlet Plug or binding of the inlet Plug; or, insuf-ficient engagement of the inlet pipe threads with consequent leakage. Branch, cross, and feedmain piping connected to Dry Sprinklers and sub-ject to freezing temperatures must be pitched for drainage in accordance with the minimum requirements of the FIGURE 1 TY3338 (3 mm BULB) TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY FIGURE 2 TY3338 (3 mm BULB) TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL w/ STANDARD ESCUTCHEON FIGURE 3 W-TYPE SPRINKLER WRENCH WATER TUBE GUIDE TUBE HOLEINLET INSERT DEFLECTOR 3 or 5 mm SCREW COMPRESSION GASKETED SPRING PLUG WITH BULB SEAT YOKE 1" NPT CASING SPRING VENT FRAME BULB PLATE SEAL SPRINKLER FITTING(REFER TO DESIGN CRITERIA SECTION) MOUNTING FACE OF 4" ± 1/8" (101,6 ± 3,2 mm) SURFACE 7/16"(11,1 mm)CENTERLINE OF WATERWAY (76,2 mm)3" DIA. ORDER LENGTHS: (63,5 to 1219,2 mm)2-1/2" to 48" IN 1/4" (6,4 mm) INCREMENTS 1-3/4" DIA.(44,5 mm) FACE OF SPRINKLER FITTING ENGAGEMENT IN TO ENSURE WITH SPRINKLER FLAT WRENCH PUSH WRENCH WRENCH FLATS RECESS WRENCH TFP520 Page of 6 National Fire Protection Association for dry pipe sprinkler systems. When Dry Sprinklers are to be used in wet pipe sprinkler systems protecting areas subject to freezing temperatures (e.g., sprinkler drops into freezers), consideration must be given to the appropriate length of the sprinkler that will prevent freezing of the water in the connecting pipes due to conduction. When the temperature surrounding the wet pipe sprinkler system is main-tained at a minimum temperature of 40°F/4°C, the following are the mini-mum recommended lengths between the face of the sprinkler fitting and the outside surface of the protected area (i.e., length exposed to minimum am-bient of 40°F/4°C – Ref. Figure 4): • 12 inches (300 mm) when the tem-perature within the protected area is -20°F/-29°C • 18 inches (450 mm) when the tem-perature within the protected area is -40°F/-40°C • 24 inches (600 mm) when the tem-perature within the protected area is -60°F/-51°C For protected area temperatures be-tween those given above, the minimum recommended length from the face of the fitting to the outside of the protect-ed area may be determined by interpo-lating between the indicated values. The 2007 edition of NFPA 13, Sec-tion 8.4.10.2 requires that dry sprin-klers connected to wet pipe sprinkler systems protecting insulated freezer structures have the clearance space around the sprinkler barrel be sealed. The use of the Model DSB-2 Dry Sprin-kler Boot described in Technical Data Sheet TFP591, and illustrated in Figure 5, will meet the intent of NFPA 13. INSULATED FREEZER STRUCTURE (ENDS ON OPPOSING SIDES OF STRAP TIES BOOT) ADHESIVE SHOWN WITH STANDARD ESCUTCHEON DS-1 1-3/4"DIA.(44,5 mm) CLEARANCE HOLE DSB-2 BOOT HEATED AREA FACE OF SPRINKLER FITTING (SEE DESIGN CRITERIA SECTION) LENGTH EXPOSURE DSB-2 INTENDED FOR FREEZER STRUCTURES Installation The Tyco® Series DS-1 Dry Type Sprin-klers must be installed in accordance with the following instructions: NOTES The Series DS-1 must only be installed in fittings that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important requirements regard-ing piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bub-ble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A 1 inch NPT sprinkler joint should be obtained with a minimum to maximum torque of 20 to 30 ft. lbs. (26,8 to 40,2 Nm). Higher levels of torque may dis-tort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for in-sufficient adjustment in an Escutcheon Plate by under-or over-tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water-way perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face to-wards the ceiling. Step 2. With pipe thread sealant ap-plied to the inlet threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Wrench tighten the sprinkler by wrenching on the Casing with a pipe wrench whenever the casing is readily accessible. Otherwise, use a W-Type 7 Sprinkler Wrench (Ref. Figure 3). The wrench recess of the W-Type 7 is to be applied to the sprinkler wrench flats (Ref. Figure 3). Step 4. After the wall has been in-stalled/finished, slide on the outer piece of the Escutcheon until it comes in contact with the ceiling/wall. FIGURE 4, EXPOSURE LENGTH FIGURE 5 MODEL DSB-2 SPRINKLER BOOT WITH SIDEWALL SERIES DS-1 DRY SPRINKLER Page of 6 TFP520 Care and Maintenance The Series DS-1 Dry Type Sprin-klers must be maintained and ser-viced in accordance with the following instructions: NOTES Absence of the outer piece of an es-cutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper au-thorities and all personnel who may be affected by this action must be notified. A Vent Hole is provided in the Bulb Seat (Ref. Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evi-dence of leakage from the Vent Hole is an indication that there may be weepage past the Inlet seal and that the sprinkler needs to be removed for determining the cause of leakage (e.g. an improper installation or an ice plug). The fire protection system control valve must be closed and the system drained before removing the sprinkler. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be com-pletely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam-age -before, during, and after instal-lation. Sprinklers damaged by drop-ping, striking, wrench twist/slippage, or the like, must be replaced. Also, re-place any sprinkler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installation Section). The owner is responsible for the in-spection, testing, and maintenance of their fire protection system and de-vices in compliance with this docu-ment, as well as with the applicable standards of the National Fire Protec-tion Association (e.g., NFPA 25), in addition to the standards of any oth-er authorities having jurisdiction. The installing contractor or sprinkler manu-facturer should be contacted relative to any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national code. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war-ranted solely to the original Buyer for ten (10) years against defects in mate-rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warran-ty is given for products or components manufactured by companies not affili-ated by ownership with TFBP or for products and components which have been subject to misuse, improper in-stallation, corrosion, or which have not been installed, maintained, modi-fied or repaired in accordance with applicable Standards of the Nation-al Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFBP shall not be respon-sible for sprinkler system design er-rors or inaccurate or incomplete infor-mation supplied by Buyer or Buyer’s representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam-ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warran-ties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex-clusive remedy for claims based on failure of or defect in products, materi-als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex-tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. TFP520 Page 5 of 6 P/N 60 – XXX – X – XXX NOTES (1). Dry Type Sprinklers are furnished based upon “Order Length” as measured per Figure 2 After the measurement is taken, round it to the nearest 1/4 inch increment. * Eastern Hemisphere sales only. SPRINKLER FINISH ESCUTCHEON FINISH 1 NATURAL BRASS WHITE 4 WHITE POLYESTER WHITE 9 CHROME PLATED CHROME PLATED 0 CHROME PLATED WHITE 3 WHITE (RAL9010)*WHITE (RAL9010)* 2 NATURAL BRASS BRASS PLATED ORDER LENGTH (1) (EXAMPLES) 055 5.50” 082 8.25” 180 18.00” 187 18.75” 372 37.25” 480 48.00” TABLE C PART NUMBER SELECTION SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS(Use Prefix “I” for ISO 7-R1 Connection, e.g., I-60-361-1-180) MODEL/SIN 350 EC Sidewall 3 mm Bulb (1” NPT), 135°F/57°C TY3338 351 EC Sidewall 3 mm Bulb (1” NPT), 155°F/68°C TY3338 950 EC Sidewall 5 mm Bulb (1” NPT), 135°F/57°C TY3358 951 EC Sidewall 5 mm Bulb (1” NPT), 155°F/68°C TY3358 Ordering Procedure Dry Sprinklers:Contact your local distributor for availability, and please specify the following: 1. Sprinkler. • Model/SIN. • Bulb Size (3 or 5 mm) • Extended Coverage Horizontal Sidewall Dry Type Sprinkler. • 5.6 K-factor. • Order Length. Dry Type Sprinklers are furnished based upon Order Length as mea-sured from the face of the wall to the face of the sprinkler fitting (Ref. Figure 2). After the measurement is taken, round it to the nearest 1/4 inch increment. • 1 Inch NPT Inlet Connection. • Temperature Rating. • Sprinkler Finish. • Standard Escutcheon and Finish. • Part Number from Table C. 2. W-Type 7 Sprinkler Wrench. Refer to the Price List for complete listing of Part Numbers. Model DSB-2:Specify: Model DSB-2 Dry Sprinkler Boot*, P/N 63-000-0-002. * Includes one Boot, two Strap Ties, and 1/3 oz. of Adhesive (quantity of adhesive is sufficient for installing one Boot) Page 6 of 6 TFP520 © 2007-2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446 General Description The Tyco® Series 800 Threaded Pipe Fittings and California Tees & Elbows are manufactured from ductile iron. They are stronger and more corrosion resistant than cast iron fittings. The additional strength is provided by the ductile properties and by adding magnesium while the iron is being poured into the final cast shape. Although lighter than standard cast iron, the fittings have an added advantage of being less susceptible to cracking due to their added strength. The Series 800, California, and Figure 719 Threaded Pipe Fittings are a redesignation for the Central Series 800, California, and Figure 719 Threaded Pipe Fittings. WARNINGSThe Threaded Pipe Fittings described herein must be installed and main-tained in compliance with this docu-ment, as well as with the applicable standards of the National Fire Pro-tection Association, in addition to the standards of any other authorities hav-ing jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Approvals: UL Listed and FM Approved Maximum Working Pressure: Series 800 and California Fittings: 250 psi (17,2 bar) Figure 719 Plug: 250 psi (17,2 bar) Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure When placing an order, indicate the full product name. Please specify the quantity, figure number, wall thickness, and size. Material: Series 800 and California Fittings: Ductile Iron Figure 719 Plug: Cast Iron Pipe Thread: NPT per ANSI B1.20.1 Installation Apply Teflon† tape or high quality pipe joint compound on male pipe threads and tighten two to three turns beyond hand tight. NoteInstallers who have not used ductile iron threaded fittings should be in-structed that the fittings are stron-ger than the pipe and overtightening the fitting can create leaks and cause damage to pipe threads. In general, there is about one-half turn difference between cast iron and ductile iron fit-tings. Apply Teflon tape or high qual-ity pipe joint compound on the male pipe threads and tighten two to three turns beyond hand tight. If an auto-matic make-on machine is being used, please exercise caution in setting the machine to the proper parameters pri-or to tightening fittings onto the male pipe threads. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or components manufactured by companies not affiliated by ownership with TFBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Pipe Fittings NPT Threaded, Ductile Iron Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Page of 0 JANUARY, 2008 TFP70 † registered trademark of E. I. du Pont de Nemours and Company or its affiliates. Nominal Pipe Size Figure 811 Figure 813 ANSI InchesDN A Inches(mm) B Inches(mm) Approx. Weight Lbs. (kg) Part Number A Inches(mm) B Inches(mm) Approx. Weight Lbs. (kg) Part Number 1/2 DN15 1.13(28,7)0.56(14,2)0.24 (0,11)86206 0.88(22,4)0.38(9,7)0.22 (0,09)86780 3/4 DN20 1.31(33,3)0.75(19,0)0.40 (0,18)86205 1.00(25,4)0.44(11,2)0.33 (0,15)86781 1 DN25 1.50(38,1)0.81(20,6)0.64 (0,29)86200 1.13(28,7)0.81(20,6)0.48 (0,21)86280 1-1/4 DN32 1.75(44,5)1.06(26,9)0.95 (0,43)86201 1.31(33,3)0.63(16,0)0.73 (0,33)86281 1-1/2 DN40 1.94(49,3)1.19(30,2)1.24 (0,56)86202 1.44(36,6)0.69(17,5)0.93 (0,42)86282 2 DN50 2.25(57,1)1.50(38,1)1.74 (0,79)86203 1.68(42,7)0.94(23,9)1.55 (0,70)86283 2-1/2 DN65 2.69 (68,3)1.56 (39,6)3.28 (1,49)86204 1.94(49,3)1.00 (25,4)2.70 (1,22)86782 Figure 811 90° eLBOW A A A B B B C D A A B B BB B A A A A B C D E F Figure 813 45° eLBOW A A ABBBCD A A B B BB B A A A AB CDEF tAble 1 NomINAl DImeNSIoNS FIGuReS 811 & 813 Page 2 of 0 TFP70 Figure 812 90° reDuCiNg eLBOW A A A B B B C D A A B B BB B A A A A B C D E F Nominal Pipe Size Figure 812 ANSI InchesDN AInches(mm) BInches(mm) CInches(mm) DInches(mm) Approx. WeightLbs. (kg) Part Number 3/4 x 1/2 DN20 x 15 1.19(30,2)1.19(30,2)0.63(16,0)0.63(16,0)0.33 (0,15)86342 1 x 1/2 DN25 x 15 1.25(31,8)1.38(35,1)0.56(14,2)0.81(20,6)0.44 (0,20)86210 1 x 3/4 DN25 x 20 1.38(35,1)1.44(36,6)0.69(17,5)0.88(22,4)0.53 (0,24)86211 1-1/4 x 1/2 DN32 x 15 1.31(33,3)1.50(38,1)0.63(16,0)0.94(23,9)0.64 (0,29)86212 1-1/4 x 3/4 DN32 x 20 1.44(36,6)1.63(41,4)0.75(19,0)1.06(26,9)0.75 (0,34)86213 1-1/4 x 1 DN32 x 25 1.56(39,6)1.68(42,7)0.88(22,4 1.00(25,4)0.77 (0,35)86214 1-1/2 x 3/4 DN40 x 20 1.50(38,1)1.75(44,4)0.75(19,0)1.19(30,2)0.95 (0,43)86221 1-1/2 x 1 DN40 x 25 1.63(41,4)1.81(46,0)0.88(22,4)1.13(28,7)0.99 (0,45)86215 1-1/2 x 1-1/4 DN40 x 32 1.81(46,0)1.88(47,8)1.13(28,7)1.19(30,2)1.14 (0,52)86216 2 x 3/4 DN50 x 20 1.63(41,4)1.94(49,3)0.88(22,4)1.38(35,1)1.39 (0,63)86217 2 x 1 DN50 x 25 1.75(44,4)2.06(52,3)2.00 (50,8)1.31(33,3)1.58 (0,72)86218 2 x 1-1/2 DN50 x 40 2.00 (50,8)2.19(55,6)1.25(31,8)1.44(36,6)1.67 (0,76)86220 2-1/2 x 2 DN65 x 50 2.38(60,5)2.63 (66,8)1.25(31,8)1.88(47,8)3.01 (1,36)86262 tAble 2 NomINAl DImeNSIoNS FIGuRe 812 TFP70 Page of 0 Nominal Pipe Size Figure 817 ANSI Inches DN A Inches (mm) B Inches (mm) C Inches (mm) D Inches (mm) Approx. Weight Lbs. (kg) Part Number 1 DN25 1.50 (38,1)1.50 (38,1)0.81(20,6) 0.81(20,6)0.97 (0,44)86284 1-1/4 DN32 1.75(44,4)1.75(44,4)1.06(26,9) 1.06(27,0) 1.59 (0,72)86285 1-1/2 DN40 1.94(49,3)1.94(49,3)1.19(30,2) 1.19(30,2) 1.89 (0,86)86286 2 DN50 2.25 (57,1)2.25 (57,1)1.50 (38,1)1.50 (38,1)2.93 (1,33)86287 1-1/4 x 1-1/4 x 1 x 1 DN32 x 32 x 25 x 25 1.69 (42,9)1.56 (39,6)1.00 (25,4)0.88 (22,4)1.25 (0,56)86289 1-1/2 x 1-1/2 x 1 x 1 DN40 x 40 x 25 x 25 1.81 (46,0)1.63 (41,4)1.06(26,9) 1.94(49,3)1.48 (0,71)86322 2 x 2 x 1 x 1 DN50 x 50 x 25 x 25 2.00 (50,8)1.75(44,4)1.25 (31,8)1.06(26,9) 2.64 (1,20)86291 Figure 817 CrOSS A A B A A B BC C D D A AA B A tAble 3 NomINAl DImeNSIoNS FIGuRe 817 Page of 0 TFP70 Nominal Pipe Size Figure 814 Figure 818 ANSI Inches DN A Inches(mm) B Inches(mm) Approx. Weight Lbs. (kg) Part Number A Inches(mm) B Inches(mm) Approx. Weight Lbs. (kg) Part Number 1/2 DN15 1.13 (28,7)0.56(14,2)0.33 (0,15)86340 1.38 (35,1)0.31(7,9)0.18 (0,08)72779 3/4 DN20 1.31 (33,3)0.75 (19,0)0.50 (0,23)86341 1.63 (41,4)0.56 (14,0)0.26 (0,11)72778 1 DN25 1.50 (38,1)0.81 (20,6)0.85 (0,38)86230 1.75 (44,4)0.38 (9,7)0.44 (0,20)72755 1-1/4 DN32 1.75 (44,4)1.06 (26,9)1.30 (0,59)86231 2.00 (50,8)0.56 (14,0)0.54 (0,24)72754 1-1/2 DN40 1.94 (49,3)1.19 (30,2)1.63 (0,74)86232 2.19 (55,6)0.75 (19,0)0.71 (0,32)72753 2 DN50 2.25 (57,1)1.50 (38,1)2.63 (1,19)86233 2.63 (66,8)1.13 (28,7)1.15 (0,52)72752 2-1/2 DN65 2.69 (68,3)1.56 (39,6)4.55 (2,06)86234 3.00 (76,2)0.75 (19,0)2.29 (1,04)72758 Figure 814 irON Tee A A ABBBCDAABB BB B A A A AB CDEF Figure 818 STraighT COupLiNg A ABAABBCCDD A AA B A tAble 4 NomINAl DImeNSIoNS FIGuReS 814 & 818 TFP70 Page of 0 Nominal Pipe Size Figure 815 ANSI Inches DN A Inches (mm) B Inches (mm) C Inches (mm) D Inches (mm) E Inches (mm) F Inches (mm) Approx. Weight Lbs. (kg) Part Number 3/4 x 3/4 x 1/2 DN20 x 20 x 15 1.19(30,2)1.19(30,2)1.25(31,8)0.63(16,0)0.63(16,0)0.69(17,5)0.46 (0,21)86235 3/4 x 3/4 x 1 DN20 x 20 x 25 1.44(36,6)1.44(36,6)1.38(35,1)0.88(22,4)0.88(22,4)0.69(17,5)0.68 (0,31)86755 1 x 1/2 x 1 DN25 x 15 x 25 1.50(38,1)1.38(35,1)1.50(38,1)0.81(20,6)0.81(20,6)0.81(20,6)0.70 (0,32)86236 1 x 3/4 x 1/2 DN25 x 20 x 15 1.25(31,8)1.19(30,2)1.38(35,1)0.56(14,2)0.63(16,0)0.81(20,6)0.63 (0,28)86756 1 x 3/4 x 3/4 DN25 x 20 x 20 1.38(35,1)1.31(33,3)1.44(36,6)0.69(17,5)0.75 (19,0)0.88(22,4)0.68 (0,31)86757 1 x 3/4 x 1 DN25 x 20 x 25 1.50(38,1)1.44(36,6)1.50(38,1)0.81(20,6)0.88(22,4)0.81(20,6)0.77 (0,35)86237 1 x 1 x 1/2 DN25 x 25 x 15 1.25(31,8)1.25(31,8)1.38(35,1)0.56(14,3)0.56(14,3)0.81(20,6)0.66 (0,30)86238 1 x 1 x 3/4 DN25 x 25 x 20 1.38(35,1)1.38(35,1)1.44(36,6)0.69(17,5)0.69(17,5)0.88(22,4)0.73 (0,33)86239 1 x 1 x 1-1/4 DN25 x 25 x 32 1.69(42,9)1.69(42,9)1.56(39,6)1.00(25,4)1.00(25,4)0.88(22,4)0.97 (0,44)86240 1 x 1 x 1-1/2 DN25 x 25 x 40 1.81(46,0)1.81(46,0)1.63(41,4)1.13(28,6)1.13(28,6)0.88(22,4)1.14 (0,52)86241 1-1/4 x 1 x 1/2 DN32 x 25 x 15 1.94(49,2)1.25(31,8)1.56(39,6)0.63(15,9)0.56(14,3)1.00(25,4)0.81 (0,37)86242 1-1/4 x 1 x 3/4 DN32 x 25 x 20 1.44(36,6)1.38(35,1)1.62(41,2)0.75 (19,0)0.69(17,5)1.06(27,0)0.90 (0,41)86243 1-1/4 x 1 x 1 DN32 x 25 x 25 1.56(39,6)1.50(38,1)1.69(42,9)0.88(22,4)0.81(20,6)1.00(25,4)1.03 (0,47)86244 1-1/4 x 1 x 1-1/4 DN32 x 25 x 32 1.75(44,4)1.69(42,9)1.75(44,4)1.06(27,0)1.00(25,4)1.06(27,0)1.10 (0,50)86245 1-1/4 x 1 x 1-1/2 DN32 x 25 x 40 1.88(47,6)1.81(46,0)1.81(46,0)1.19(30,1)1.13(28,6)1.06(27,0)1.43 (0,65)86246 1-1/4 x 1-1/4 x 1/2 DN32 x 32 x 15 1.38(35,1)1.38(35,1)1.56(39,6)0.69(17,5)0.69(17,5)1.00(25,4)0.87 (0,39)86247 1-1/4 x 1-1/4 x 3/4 DN32 x 32 x 20 1.44(36,6)1.44(36,6)1.63(41,4)0.75 (19,0)0.75 (19,0)1.06(27,0)0.96 (0,43)86248 1-1/4 x 1-1/4 x 1 DN32 x 32 x 25 1.56(39,6)1.56(39,6)1.69(42,9)0.88(22,4)0.88(22,4)1.00(25,4)1.10 (0,50)86249 1-1/4 x 1-1/4 x 1-1/2 DN32 x 32 x 40 1.88(47,6)1.88(47,6)1.81(46,0)1.81(46,0)1.81(46,0)1.06(27,0)1.50 (0,68)86250 1-1/4 x 1-1/4 x 2 DN32 x 32 x 50 2.13(54,1)2.13(54,1)2.00 (50,8) 1.44(36,6)1.44(36,6)1.13(28,6)2.00 (0,91)86251 1-1/2 x 1 x 1/2 DN40 x 25 x 15 1.44(36,6)1.31(33,3)1.69(42,9)0.69(17,5)0.63(15,9)1.13(28,6)0.97 (0,44)86252 1-1/2 x 1 x 3/4 DN40 x 25 x 20 1.50(38,1)1.38(35,1)1.75(44,4)0.75 (19,0)0.69(17,5)1.19(30,2)1.14 (0,52)86253 1-1/2 x 1 x 1 DN40 x 25 x 25 1.63(41,4)1.50(38,1)1.81(46,0)0.88(22,4)0.81(20,6)1.13(28,7)1.14 (0,52)86254 1-1/2 x 1 x 1-1/2 DN40 x 25 x 40 1.94(49,3)1.81(46,0)1.94(49,2)1.19(30,2)1.13(28,6)1.19(30,2)1.52 (0,69)86255 Figure 815 reDuCiNg Tee A A A B B B C D A AB B BB B A A A A B C D E F tAble 5 (1 oF 2) NomINAl DImeNSIoNS FIGuRe 815 TFP70 Page of 0 Nominal Pipe Size Figure 815 ANSI Inches DN A Inches(mm) B Inches(mm) C Inches(mm) D Inches(mm) E Inches(mm) F Inches(mm) Approx. Weight Lbs. (kg) Part Number 1-1/2 x 1-1/4 x 1/2 DN40 x 32 x 15 1.44(36,6)1.31(33,3)1.69(42,9)0.69(17,5)0.63 (16,0)1.13(28,7)1.03 (0,47)86257 1-1/2 x 1-1/4 x 3/4 DN40 x 32 x 20 1.50(38,1)1.44(36,6)1.75(44,5)0.75(19,0)0.75(19,0)1.19(30,1)1.10 (0,50)86258 1-1/2 x 1-1/4 x 1 DN40 x 32 x 25 1.63(41,4)1.56(39,7)1.81(46,0)0.88(22,4)0.88(22,4)1.13(28,7)1.31 (0,59)86259 1-1/2 x 1-1/4 x 2 DN40 x 32 x 50 2.19(55,6)2.13(54,1)2.00(50,8)1.44(36,6)1.44(36,6)1.25 (57,1)1.94 (0,88)86260 1-1/2 x 1-1/2 x 1/2 DN40 x 40 x 15 1.44(36,6)1.44(36,6)1.69(42,9)0.69(17,5)0.69(17,5)1.13(28,7)1.14 (0,52)86261 1-1/2 x 1-1/2 x 3/4 DN40 x 40 x 20 1.50 (38,1)1.50(38,1)1.75(44,4)0.75(19,0)0.75(19,0)1.19(30,1)1.23 (0,56)86262 1-1/2 x 1-1/2 x 1 DN40 x 40 x 25 1.63(41,2)1.63(41,2)1.81 (46,0)0.88(22,4)0.88(22,4)1.13(28,7)1.38 (0,62)86263 1-1/2 x 1-1/2 x 1-1/4 DN40 x 40 x 32 1.81 (46,0)1.81 (46,0)1.88 (47,6)1.06 (27,0)1.06 (27,0)1.19(30,1)1.50 (0,68)86264 1-1/2 x 1-1/2 x 2 DN40 x 40 x 50 2.19(55,5)2.19(55,5)2.00(50,8)1.44(36,6)1.44(36,6)1.25 (31,7)2.00 (0,91)86265 2 x 1 x 2 DN50 x 25 x 50 2.25 (57,2)2.00(50,8)2.25 (57,2)1.50(38,1)1.31(33,3)1.50 (38,1)2.18 (0,99)86266 2 x 1-1/4 x 2 DN50 x 32 x 50 2.25 (57,2)2.13 (54,1)2.25 (57,2)1.50(38,1)1.44(36,6)1.50 (38,1)2.31 (1,05)86267 2 x 1-1/2 x 1/2 DN50 x 40 x 15 1.50(38,1)1.44(36,6)1.88 (47,8)0.75(19,0)0.69(17,5)1.31(33,3)1.50 (0,68)86268 2 x 1-1/2 x 3/4 DN50 x 40 x 20 1.63(41,4)1.50(38,1)1.94(49,3)0.88(22,4)0.75(19,0)1.38 (35,0)1.61 (0,73)86269 2 x 1-1/2 x 1 DN50 x 40 x 25 1.75(44,5)1.63 (41,4)2.00(50,8)1.00 (25,4)0.88(22,4)1.31(33,3)1.65 (0,75)86270 2 x 1-1/2 x 1-1/2 DN50 x 40 x 40 2.06 (52,4)1.94 (49,2)2.19 (55,5)1.31 (33,3)1.19(30,2)1.44(36,6)2.03 (0,92)86272 2 x 1-1/2 x 2 DN50 x 40 x 50 2.25 (57,1)2.19 (55,5)2.50 (63,5)1.50(38,1)1.44(36,6)1.50(38,1)2.37 (1,07)86273 2 x 2 x 1/2 DN50 x 50 x 15 1.50(38,1)1.50(38,1)1.88 (47,8)0.75(19,0)0.75(19,0)1.31(33,3)1.50 (0,68)86222 2 x 2 x 3/4 DN50 x 50 x 20 1.63 (41,4)1.63 (41,4)1.94 (49,3)0.88(22,4)0.88(22,4)1.38 (35,0)1.67 (0,76)86223 2 x 2 x 1 DN50 x 50 x 25 1.75(44,5)1.75(44,5)2.00(50,8)1.00 (25,4)1.00 (25,4)1.31(33,3)1.91 (0,86)86224 2 x 2 x 1-1/4 DN50 x 50 x 32 1.88 (47,8)1.88 (47,8)2.13 (54,1)1.13(28,7)1.13(28,7)1.44(36,6)2.05 (0,93)86225 2 x 2 x 1-1/2 DN50 x 50 x 40 2.00(50,8)2.00(50,8)2.19 (55,6)1.25 (31,8)1.25 (31,8)1.50(38,1)2.11 (0,96)86226 2 x 2 x 2-1/2 DN50 x 50 x 65 2.63 (66,8)2.63 (66,8)2.38 (60,5)1.75(44,5)1.88 (47,8)1.44(36,6)3.67 (1,66)86227 2-1/2 x 2 x 3/4 DN65 x 50 x 20 1.75(44,5)1.63 (41,4)2.31 (58,7)0.63 (15,9)0.88(22,4)1.75(44,5)2.22 (1,01)86274 Figure 815 reDuCiNg Tee A A A B B B C D A AB B BB B A A A A B C D E F tAble 5 (2 oF 2) NomINAl DImeNSIoNS FIGuRe 815 Page 7 of 0 TFP70 Nominal Pipe Size Figure 820 Figure 830 Figure 719 ANSI InchesDN A Inches(mm) Approx. Weight Lbs. (kg) Part Number A Inches(mm) B Inches(mm) Approx. Weight Lbs. (kg) Part Number A Inches(mm) Approx. Weight Lbs. (kg) Part Number 1/2 DN15 0.88(22,4)0.15 (0,06)72776 1.88(47,8) 0.81(20,6)0.47 (0,21)86207 0.94(23,9)0.10 (0,04)86292 3/4 DN20 1.00(25,4)0.22 (0,10)72777 2.00(50,8)0.94(23,9)0.66 (0,30)86275 1.13(28,7)0.18 (0,08)86293 1 DN25 1.18(30,0)0.33 (0,15)72824 2.19(55,6)0.81(20,6)1.08 (0,49)86276 1.25(31,7)0.28 (0,13)86294 1-1/4 DN32 1.31(33,3)0.54 (0,24)72756 2.50(63,5)1.06(26,9)1.54 (0,70)86277 1.38(35,1)0.50 (0,23)86295 1-1/2 DN40 1.38(35,1)0.68 (0,31)72822 2.63(66,8)1.19(30,2)2.03 (0,92)86278 1.44(36,6)0.70 (0,32)86296 2 DN50 1.50(38,1)0.96 (0,43)72823 3.13 (79,5)1.63 (41,4)3.15 (1,43)86279 1.50 (38,1)0.90 (0,41)86297 2-1/2 DN65 1.75 (44,5)1.80 (0,82)72825 Figure 820 Cap A ABAABBCCDD A AA B A Figure 830 BraSS SeaT uNiON A ABAABBCCDD A AA B A Figure 719 pLug A ABAABBCCDD A AA B A tAble 6 NomINAl DImeNSIoNS FIGuReS 820, 830 & 719 Page 8 of 0 TFP70 Nominal Pipe Size Figure 825 Extension Piece Figure 827 Hex Bushing Figure 816 Reducing Coupling ANSI Inches DN A Inches(mm) Approx. Weight Lbs. (kg) Part Number A Inches(mm) Approx. Weight Lbs. (kg) Part Number A Inches(mm) B Inches(mm) Approx. Weight Lbs. (kg) Part Number 1/2 x 1/2 DN15 x 15 1.50(38,1)0.20 (0,09)72751 1/2 x 1/2 DN15 x 15 2.00(50,8)0.27 (0,12)72980 3/4 x 3/4 DN20 x 20 1.50(38,1)0.22 (0,10)72981 3/4 x 3/4 DN20 x 20 2.00(50,8)0.31 (0,14)73982 3/4 x 1/2 DN20 x 15 1.75 (43,2)0.69 (17,5)0.38 (0,17)86772 1 x 1/2 DN25 x 15 1.06(26,9)0.22 (0,10)72726 1.69 (42,9)0.50 (12,7)0.38 (0,17)86228 1 x 3/4 DN25 x 20 1.06(26,9)0.18 (0,08)72762 1.75 (43,2)0.50 (12,7)0.53 (0,24)86229 1-1/4 x 1 DN32 x 25 1.19(30,2)0.31 (0,14)72763 1-1/2 x 1 DN40 x 25 1.25(31,7)0.53 (0,24)72757 1-1/2 x 1-1/4 DN40 x 32 1.25(31,7)0.35 (0,10)72764 2 x 1 DN50 x 25 1.38(35,1)0.75 (0,34)72759 2 x 1-1/4 DN50 x 32 1.38(35,1)0.69 (0,31)72761 2 x 1-1/2 DN50 x 40 1.38(35,1)0.62 (0,28)72775 tAble 7 NomINAl DImeNSIoNS FIGuRe 825, 827 & 816 Figure 825 exTeNSiON pieCe A A B AA B BC C D D A AA BA Figure 827 hex BuShiNg A A B A A B BC C D D A AA B A Figure 816 reDuCiNg COupLiNg A A B A A B BC C D D A AA B A TFP70 Page of 0 Nominal Pipe Size Street Elbows ANSI InchesDN A Inches (mm) B Inches (mm) C Inches (mm) Approx. Weight Lbs. (kg) Part Number 1 x 1/2 DN25 x 15 1.50 (38,1)0.75 (19,1)3.00 (76,2)0.70 (0,32)42003 1 x 1 DN25 x 25 1.50 (38,1)0.75 (19,1)3.00 (76,2)0.90 (0,40)42002 STreeT eLBOWS A A B B C C DD CC BABA A A B B C C DD CC BABA CaLiFOrNia TeeS Nominal Pipe Size California Tees ANSI InchesDN A Inches (mm) B Inches (mm) C Inches (mm) D Inches (mm) Approx. Weight Lbs. (kg) Part Number 1 x 1/2 x 1 DN25 x 15 x 25 1.50 (38,1)0.88 (22,4)3.00 (76,2)0.75 (19,1)0.95 (0,43)42000 1 x 1 x 1 DN25 x 25 x 25 1.50 (38,1)0.75 (19,1)3.00 (76,2)0.75 (19,1)0.95 (0,43)42001 tAble 9 NomINAl DImeNSIoNS StReet elboWS tAble 8 NomINAl DImeNSIoNS cAlIFoRNIA teeS Page 0 of 0 TFP70 © 2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon avenue, Lansdale pennsylvania 19446 Identification Signs For Sprinkler Systems and Devices NFPA 13 Signing Requirements Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Page of 4 AUGUST, 2007 TFP65 WARNINGSThe Identification Signs described herein must be installed and main-tained in compliance with this docu-ment, as well as with the applicable standards of the National Fire Pro-tection Association, in addition to the standards of any other authorities hav-ing jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Material & Finish 18 gauge aluminum with mylar facing. Installation The Identification Signs are provid-ed with 1⁄8 Inch (3,2 mm) diameter or larger holes (or slots) in the corners for easy attachment using standard hard-ware chain, wire, plastic lock ties, or light gauge metal strap (not included). General Description Identification Signs (Ref. Figure 1) are designed to provide information to the end user about the sprinkler system and its components. They are avail-able with a variety of wording combi-nations to meet the signing require-ments of NFPA 13. The five basic types of Identification Signs are as follows: Type A- Control Valve Sign Type B- Multi-Purpose Text Signs (See Below) Type D- Fire Alarm Sign Type E- Hydraulic Calculation Sign Type B- Identification Signs are avail-able with the following text options: AIR CONTROL AIR LINE ALARM TEST ANTIFREEZE SYSTEM AUXILIARY DRAIN CONTROL VALVE DRAIN DRAIN VALVE INSPECTORS TEST MAIN CONTROL MAIN DRAIN Care and Maintenance The following inspection procedure must be performed as indicated, in ad-dition to any specific requirements of the NFPA, and any impairments must be immediately corrected. The owner is responsible for the in-spection, testing, and maintenance of their fire protection system and devic-es in compliance with this document, as well as with the applicable stan-dards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authority hav-ing jurisdiction. The installing contrac-tor or product manufacturer should be contacted relative to any questions. It is recommended that automatic sprin-kler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local re-quirements and/or national codes. After placing a fire protection system in service, notify the proper authorities and advise those responsible for mon-itoring proprietary and/or central sta-tion alarms. INSPECTION PROCEDURE Annual visual inspections are recom-mended to ensure that Identification Signs are properly located. Width x Height Inches (mm) Type A 9 x 7 (229 x 178) Type B 6 x 2 (152 x 51) Type C 7¾ x 1¼(197 x 32) Type D 9 x 7 (229 x 178) Type E 5 x 7 (127 x 178) Page 2 of 4 TFP65 SIGN- type B, AvAIlABle WIth the FolloWING text optIoNS “AIR CONTROL” .........................P/N 2328 “AIR LINE” ..............................P/N 2302 “ALARM TEST” ........................P/N 2304A “ANTIFREEZE SYSTEM” ..................P/N 2306 “AUXILIARY DRAIN”. . . . . . . . . . . . . . . . . . . . . .P/N 2307 “CONTROL VALVE” ......................P/N 2310 “DRAIN” ...............................P/N 2311 “DRAIN VALVE” .........................P/N 2327 “INSPECTORS TEST” ....................P/N 2313 “MAIN CONTROL” .......................P/N 2319 “MAIN DRAIN” ..........................P/N 2320 SIGN- type e, p/N 2317 SIGN- type D RectANGulAR 6-1/2” x 8-1/2”, p/N 2316 oR RouND 7-1/4” DIAmeteR, p/N 2329 SIGN- type A, p/N 2300A FIGuRe 1 IDeNtIFIcAtIoN SIGNS TFP65 Page of 4 Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war-ranted solely to the original Buyer for ten (10) years against defects in mate-rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warran-ty is given for products or components manufactured by companies not af-filiated by ownership with TFBP or for products and components which have been subject to misuse, improper in-stallation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protec-tion Association, and/or the standards of any other Authorities Having Juris-diction. Materials found by TFBP to be defective shall be either repaired or re-placed, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other ob-ligation in connection with the sale of products or parts of products. TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam-ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex-press or implied, including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex-clusive remedy for claims based on failure of or defect in products, materi-als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex-tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Orders must include the description and Part Number (P/N). Contact your local distributor for availability. Hardware for hanging is not sup-plied with the Sign. It must be ordered separately. Identification Signs, (Types A, C, D, or E)Specify: Type (A, C, D, or E) Identification Sign, P/N (specify). Identification Signs(Type B)Specify: Type B Identification Sign in-scribed (specify, e.g. “AIR CONTROL”), P/N (specify). Type A ..........................P/N 2300A Type D (Round) ....................P/N 2329 Type D (Rectangle) .................P/N 2316 Type E ...........................P/N 2317 Type B “AIR CONTROL” ...................P/N 2328 “AIR LINE” ........................P/N 2302 “ALARM TEST” ...................P/N 2304A “ANTIFREEZE SYSTEM” ............P/N 2306 “AUXILIARY DRAIN”. . . . . . . . . . . . . . . . P/N 2307 “CONTROL VALVE” ................P/N 2310 “DRAIN” .........................P/N 2311 “DRAIN VALVE” ...................P/N 2327 “INSPECTORS TEST” ..............P/N 2313 “MAIN CONTROL” .................P/N 2319 “MAIN DRAIN” ....................P/N 2320 Page 4 of 4 TFP65 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446 Model CV-1F Check Valves 2 to 12 Inch (DN50 to DN300) Page 1 of 4 OCTOBER 2010 TFP1550 Technical Services 800-381-9312 | +1-401-781-8220 www.tyco-fire.com General Description The TYCO Model CV-1F Check Valve is a compact and rugged swing-type unit that allows water flow in one direction and prevents flow in the opposite direc-tion. A resilient elastomer seal facing on the spring-loaded clapper ensures a leak-tight seal and non-sticking oper-ation. The Model CV-1F Check Valves are designed to minimize water hammer caused by flow reversal. The Model CV-1F Check Valve is furnished with grooved ends and can be installed using Grinnell Grooved Couplings or GRINNELL Figure 71 Flange Adapters. The Model CV-1F Check Valves have been designed with a removable cover for ease of field maintenance. These valves can be installed horizontally (with cover in the upward position) or vertically with the flow in the upward direction. Refer to Figure 4. A Maintenance Check Valve Kit (TFP1555) is available to allow the maintenance procedure of back- flushing through the fire department connection without removing the Model CV-1F Check Valve from the pipe line. The Model CV-1F Check Valves are a redesign for the Central Figure 590F and GRINNELL Figure 590F. NOTICE Never remove any piping component nor correct or modify any piping defi-ciencies without first de-pressurizing and draining the system. Failure to do so may result in serious personal injury, property damage, and/or impaired device performance. The Model CV-1F Check Valves described herein must be installed and maintained in compliance with this document and with the applicable stan-dards of the National Fire Protection Association, in addition to the stan-dards of any authorities having juris-diction. Failure to do so may impair the performance of this device. Owners are responsible for maintain-ing their fire protection system and devices in proper operating condition. The installing contractor or manufac-turer should be contacted with any questions. Technical Data Approvals UL, C-UL, and FM Sizes2 to 12 Inch (DN50 to DN300) Maximum Working Pressure 300 psi (20,7 bar) Valve Assembly Finish Red, non-lead paint Installation The Model CV-1F Check Valves are to be installed in accordance with the following instructions: 1. The arrow cast on the Body must point in the direction of the flow. 2. Valves installed vertically must be positioned with the flow in the up- ward direction. 3. Valves installed horizontally must be positioned with the Cover facing up. Refer to Figure 4. 4. Grooved end pipe couplings used with the Model CV-1F Check Valve must be installed in accordance with manufacturer’s instructions. TFP1550 Page 2 of 4 Nominal Pipe Size Nominal Dimensions Inches (mm)CoverBolt Torq.Lbs.-ft. (Nm) Approx. WeightLbs. (kg)ANSI InchesDN O.D.Inches (mm)A B C D E F J 2DN50 2.375 (60,3)6.75(171,5)4.38(111,3)2.55(64,8)2.57(65,3)3.25(82,3)4.75(120,7)1.62(41,5)18(25)9.0(4,5) 2-1/2DN65 2.875 (73,0)8.00(203,2)5.80(147,3)3.41(86,6)3.40(86,4)3.88(98,6)6.00(152,4)1.70(43,2)39(54)10.0(4,5) 76,1 DN65 - (76,1)8.00(203,2)5.80(147,3)3.41(86,6)3.40(86,4)3.88(98,6)6.00(152,4)1.70(43,2)39(54)10.00(4,5) 3DN80 3.500 (88,9)8.37(212,6)5.76(146,3)3.60(91,4)3.40(86,4)3.88(98,6)6.00(152,4)1.70(43,2)39(54)11.0(5,0) 4DN100 4.500 (114,3)9.63(244,6)6.74(171,2)4.61(117,1)3.63(92,2)4.56(115,1)7.13(181,1)1.84(46,7)50(69)25.0(11.3) 139.7 DN125 - (139.7)10.50(266,7)7.50(190,5)5.29(134,4)4.20(106,7)4.90(124,5)7.60(193,0)1.90(48,3)39(54)29.0(13.2) 5DN125 5.563 (141,3)10.50(266,7)7.50(190,5)5.29(134,4)4.20(106,7)4.90(124,5)7.60(193,0)1.90(48,3)39(54)29.0(13,2) 165.1DN150 - (165.1)11.50(292,1)8.05(204,5)5.75(146,1)4.50(114,3)5.00(127,0)7.60(193,0)1.48(37,6)60(82)47.0(21,3) 6DN150 6.625 (168,3)11.50(292,1)8.05(204,5)5.75(146,1)4.50(114,3)5.00(127,0)7.60(193,0)1.48(37,6)60(82)47.0(21,3) 8DN200 8.625 (219,1)14.00(355,6)10.25(260,4)7.75(196,9)5.62(142,7)5.45(138,4)8.40(213,4)2.20(58,9)120(164)66.0(29,9) 10DN250 10.750 (273,1)18.00(457,2)13.00(330,2)10.21(259,3)6.38(162.1)7.50(190.5)10.50(266,7)3.00(76,2)130(178)109.7(49,4) 12DN300 12.750 (323,9)21.00(533,4)14.28(362,7)11.31(287,2)7.26(184,4)7.62(193,5)10.62(269,7)2.75(69.9)130(178)151.0(68,0) FIGURE 1 MODEL CV-1F CHECK VALVES NOMINAL DIMENSIONS NPT1/2" NPT1/2" B A C D O.D. J E F TFP1550 Page 3 of 4 FIGURE 2 MODEL CV-1F CHECK VALVES ASSEMBLY 0,04 0,05 0,07 0,06 0,09 0,08 0,10 0,20 0,30 IN P O U N D S P E R S Q U A R E I N C H ( P S I ) NO M I N A L P R E S S U R E D R O P NO M I N A L P R E S S U R E D R O P I N B A R (1 P S I = 0 , 0 6 8 9 5 B A R ) 0.5 0.6 1.00.9 0.8 0.7 4.0 2.0 3.0 5.0 200 300 400 600 1000 2000 3000 4000 6000 10000 700 1000 2000 3000 5000 7000 10000 20000 30000 15000 50000 100 500 FLOW RATE IN LITRES PER MINUTE (LPM) (1 GPM = 3,785 LPM) FLOW RATE IN GALLONS PER MINUTE (GPM) 2-1 / 2 I N C H ( D N 6 5 ) 3 IN C H ( D N 8 0 ) 5 IN C H ( D N 1 2 5 ) 8 IN C H ( D N 2 0 0 ) 6 IN C H ( D N 1 5 0 ) 4 IN C H ( D N 1 0 0 ) 10 I N C H ( D N 2 5 0 ) 2 IN C H ( D N 5 0 ) 12 I N C H ( D N 3 0 0 ) 15 VIEW A DETAIL B SEE DETAIL B 2" - 8"(DN50-DN200)10" - 12"1 VIEW A SEE 2" - 8"(DN50-DN200)10" - 12" (DN250 - DN300) 1718 2 9 8 7 5 (DN250 - DN300) 8 9 2 7 5 13 14,16 6 13 11,16 19 5 6 5 11 3 2 4,16 Detail Part Material Qty.Detail Part Material Qty.Detail Part Material Qty. 1 Body Ductile Iron 1 6 Clapper Facing EPDM Grade “E”1 14 Locknut Stainless Steel 1 2 Cover Ductile Iron 1 7 Spring Stainless Steel 1 15 Plug- 1/2˝-14 NPT Cast Iron 2 3 Cover Gasket Nitrile Rubber 1 8 Hinge Shaft Stainless Steel 1 16 Adhesive Thread Sealer AR 4 Hex Cap Screw Steel, Zinc Plated AR 9 Retaining Ring Stainless Steel AR 17 Nameplate Aluminum 1 5 Clapper2˝ - 8˝ (DN50-200) Stainless Steel 1 11 Retention Bolt Stainless Steel 1 18 Rivet Steel 2 Clapper10˝-12˝ (DN250-300)Ductile Iron 13 Retaining Disc Stainless Steel 1 19 Spacer Stainless Steel 1 FIGURE 3 MODEL CV-1F CHECK VALVES PRESSURE LOSS DATA Copyright © 2008-2010 Tyco Fire Suppression & Building Products. All rights reserved. TFP1550 Page 4 of 4 Care and Maintenance NOTICE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affect-ed by this decision. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni-toring proprietary and/or central station alarms. Responsibility lies with owners for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any authority having jurisdiction. The installing contractor or product manufacturer should be contacted relative to any questions. Any impairments must be immediately corrected. Automatic sprinkler systems are recom-mended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. Limited Warranty Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for products or components manufac-tured by companies not affiliated by ownership with TFSBP or for products and components which have been subject to misuse, improper instal-lation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with appli-cable Standards of the National Fire Protection Association, and/or the stan-dards of any other Authorities Having Jurisdiction. Materials found by TFSBP to be defective shall be either repaired or replaced, at TFSBP’s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for inciden-tal, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFSBP was informed about the possi-bility of such damages, and in no event shall TFSBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of merchantability and fitness for a partic-ular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materi-als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N). Model CV-1F Check ValvesSpecify: size and P/N (below). 2˝ (DN50) ...............P/N 59-590-0-020 2-1/2˝ (DN65) ............P/N 59-590-0-025 76,1 mm (DN65) .........P/N 59-590-0-076 3˝ (DN80) ...............P/N 59-590-0-030 4˝ (DN100) ..............P/N 59-590-0-040 139,7 mm (DN125) .......P/N 59-590-0-139 5˝ (DN125) ..............P/N 59-590-0-050 165,1 mm (DN150) .......P/N 59-590-0-165 6˝ (DN150) ..............P/N 59-590-0-060 8˝ (DN200) ..............P/N 59-590-0-080 10˝ (DN250) .............P/N 59-590-0-100 12˝ (DN300) .............P/N 59-590-0-120 FIGURE 4 MODEL CV-1F CHECK VALVES INSTALLATION HORIZONTAL ORIENTATIONVERTICAL ORIENTATION FLOW FLOW COVER COVEROUTLET INLET OUTLETINLET Technical Data ModelBFV-N Sizes: ANSI Inches / DN 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250) ApprovalsThe 2-1/2 through 10 inch (DN65 - DN250) Model BFV-N Grooved End Butterfly Valves are UL and C-UL List-ed and FM Approved. In addition, the Model BFV-N Grooved End Butterfly Valves are listed by the California State Fire Marshall under Listing No. 7770-1670:100. All laboratory listings and approvals are for indoor and outdoor use. Maximum Working Pressure • 2-1/2 - 8 Inch (DN65 - DN200): 300 psi (20,7) bar • 10 Inch (DN250): 175 psi (12,0 bar) Materials of Construction: BodyDuctile iron conforming to ASTM A-395 Body CoatingPolyamide DiscDuctile iron conforming to ASTM A-395 Disc SealGrade EPDM “E” encapsulated rubber conforming to ASTM D-2000 Upper & Lower StemType 416 Stainless Steel conforming to ASTM 582 Lower PlugPVC OperatorGear operator with iron housing General Description The Model BFV-N Grooved End But-terfly Valves (Ref. Figure 1) are indicat-ing type valves designed for use in fire protection systems where a visual in-dication is required as to whether the valve is open or closed. They are used, for example, as system, sectional, and pump water control valves. They have cut groove inlet and outlet connections that are suitable for use with grooved end pipe couplings that are listed and approved for fire protection systems. For applications requiring supervision of the open position of the valve, the Gear Operators for the Model BFV-N Butterfly Valves are provided with two sets of factory installed internal switches each having SPDT contacts. The supervisory switches transfer their electrical contacts when there is move-ment from the valve’s normal open po-sition during the first two revolutions of the handwheel. WARNINGSThe Model BFV-N Grooved End But-terfly Valves described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori-ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Friction LossThe approximate friction loss, based on the Hazen Williams formula and ex-pressed in equivalent length of pipe with C= 120, is as follows. The data is based on friction loss information col-lected at a typical flow rate of 15 feet per second. • 6.9 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch valve. • 8.7 feet of 3 inch Sch. 40 pipe for the 3 inch valve. • 4.5 feet of 4 inch Sch. 40 pipe for the 4 inch valve. • 6.6 feet of 5 inch Sch. 40 pipe for the 5 inch valve. • 11.1 feet of 6 inch Sch. 40 pipe for the 6 inch valve. • 10.2 feet of 8 inch Sch. 30 pipe for the 8 inch valve. • 12.1 feet of 10 inch Sch. 30 pipe for the 10 inch valve. Model BFV-N Butterfly Valve Grooved End 2-1/2 Inch - 10 Inch (DN65 - DN250) Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Page of 4 MAY, 2008 TFP50 Valve Nominal Sizes A B C D E Nominal Installation Dimensions in Inches and (mm)Weight (kg)lbs.F G Pipe O.D.H F DN100 4" DN150 6" DN80 3" (116,0)4.56 (98,0)3.85 (110,0)4.35 (90,0)3.54 (12,7)28 (10,4)23 DN65 2-1/2"(98,0)3.85 (83,0)3.25 (10,0)22 DN125 5"(149,0)5.86 (123,0)4.84 (14,1)31 DN200 8"(134,0)5.26 (174,0)6.87 (24,1)53 DN250 10"(160,0)6.29 (233,0)9.17 (40,0)88 FLAGINDICATORHANDWHEEL DISC OPERATOR GEAR BODY CONDUIT 1/2"NPT CONNECTION E D C B G A H (149,0)5.86 (151,0)5.93 (18,6)41 (114,3)4.50 (168,3)6.63 (88,9)3.50 (73,0)2.88 (141,3)5.56 (219,1)8.63 (273,1)10.75 0 0 0 0 (17,0)0.67 12.25 17.31 (487,7) 25.11(637,8) (439,7) 19.20 (354,3) 14.93(379,2) (311,1) 13.95 11.71(297,4) 7.07(179,6)6.00(152,4)7.81(198,4) 11.50(292,1) (236,0) (212,0) 9.29 8.35 9.00(228,6) 6.00 (152,4) (152,4) 6.00 7.68(195,1) 7.81 (198,4) (198,4) 7.81 3.00(76,2)7.41(188,2) (148,8)5.86 (137,9) (167,1) (144,2) 6.58 5.68 5.43 (152,4) 6.00 (152,4)6.00 (152,4) 6.00 (198,4) 7.81 (198,4)7.81 (198,4) 7.81 (63,5)2.50 (63,5)2.50 (63,5)2.50 (63,5)2.50 (63,5)2.50 (63,5)2.50 FIGuRe 1 model bFv-N GRooved eNd butteRFly vAlve – NomINAl dImeNSIoNS – Page 2 of 4 TFP50 FIGuRe 2 model bFv-N butteRFly vAlve – INteRNAl SWItch WIRING dIAGRAm – Installation The Model BFV-N Grooved End But-terfly Valves may be installed with flow in either direction and can be posi-tioned either horizontally or vertically. The grooved end pipe couplings used with the Model BFV-N must be listed or approved for fire protection service and installed in accordance with the manufacturers instructions. The Model BFV-N Butterfly Valve may be installed with any schedule of pres-sure class of pipe or tubing that is list-ed or approved for fire protection. As applicable, refer to Figure 2 for the internal switch wiring diagram. Conduit and electrical connections are to be made in accordance with the authority having jurisdiction and/or the National Electrical Code. With reference to Figure 2, the “supervi-sory switch” is intended for connec-tion to the supervisory circuit of a fire alarm control panel in accordance with NFPA 72. The “auxiliary switch” is in-tended for the unsupervised connec-tion to auxiliary equipment in accor-dance with NFPA 70, National Electric Code. NoteFor outdoor applications with inter-nal supervisory switches, it is recom-mended that wiring connections be made at a temperature above 15°F (-9°C), in order to insure sufficient flex-ibility of the wire lead insulation. Care and Maintenance The owner is responsible for the in-spection, testing, and maintenance of their fire protection system and devic-es in accordance with the applicable standards of the National Fire Pro-tection Association (e.g., NFPA25), in addition to the standards of any au-thority having jurisdiction. The install-ing contractor or product manufac-turer should be contacted relative to any questions. Any impairment must be immediately corrected. It is recommended that automatic sprinkler systems be inspected, test-ed, and maintained by a qualified in-spection service. 1/2A@ 125 VDCCONTACTRATING 1/4A@ 250 VDC .... 15.1A/12HP @ 125,250VAC 5A@ 125 VAC "L" END OFLINE RESISTOR PANEL ORANGE ORANGE YELLOW YELLOW SUPERVISORY SWITCH SWITCH SHOWN WITH VALVEFULLOPEN GREEN VIOLET AUXILIARY SWITCH SHOWN WITH VALVE FULL OPEN BLUE RED BELL SWITCHGND POWER NOT USED + -- + NoteBefore closing a fire protection system control valve for maintenance or in-spection work on either the valve or fire protection system which it controls, permission to shut down the affected fire protection systems must be ob-tained from the proper authorities and all personnel who may be affected by this decision must be notified. TFP50 Page of 4 Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war-ranted solely to the original Buyer for ten (10) years against defects in mate-rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warran-ty is given for products or components manufactured by companies not af-filiated by ownership with TFBP or for products and components which have been subject to misuse, improper in-stallation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protec-tion Association, and/or the standards of any other Authorities Having Juris-diction. Materials found by TFBP to be defective shall be either repaired or re-placed, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other ob-ligation in connection with the sale of products or parts of products. TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam-ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex-press or implied, including warranties of merchantability and fitness for a par-ticular purpose. This limited warranty sets forth the ex-clusive remedy for claims based on failure of or defect in products, materi-als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex-tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Grooved End Butterfly Valves:Specify: (specify inch size) Model BFV-N Grooved End Butterfly Valve with internal supervisory switches, P/N (specify). Valve Size Valve Part Number 2-1/2 ......................59-300-F-025N 3. . . . . . . . . . . . . . . . . . . . . . . . . . 59-300-F-030N 4. . . . . . . . . . . . . . . . . . . . . . . . . . 59-300-F-040N 5. . . . . . . . . . . . . . . . . . . . . . . . . . 59-300-F-050N 6. . . . . . . . . . . . . . . . . . . . . . . . . . 59-300-F-060N8. . . . . . . . . . . . . . . . . . . . . . . . . . 59-300-F-080N 10 .........................59-300-F-100N Page 4 of 4 TFP50 ©2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 General Description TheTyco®ModelDPV-1DryPipe Valvesaredifferentialvalvesusedto automaticallycontroltheflowofwater intodrypipefireprotectionsprinkler systemsuponoperationofoneor moreautomaticsprinklers.TheDPV-1 alsoprovidesforactuationoffire alarmsuponsystemoperation.The ModelDPV-1featuresareasfollows: •Externalreset. •250psi(17,2bar)pressurerating. •Uniqueoffsetsingleclapperdesign enablingasimplecompactvalveto minimizeinstallationlabor. •Ductileironconstructiontoensurea lightweightvalvetominimizeship- pingcost. •Avarietyofinletandoutletconnec- tions. •Compact,semi-preassembledor fullyassembled,andeasytooperate valvetrim. •Simpleresetprocedurethroughthe eliminationofprimingwater. Drypipesprinklersystemsareusedin unheatedwarehouses,parkingga- rages,storewindows,atticspaces, loadingdocks,andotherareasex- posedtofreezingtemperatures,where waterfilledpipecannotbeutilized. Whensetforservice,thedrypipe sprinklersystemispressurizedwithair (ornitrogen).Thelossofpressure throughanoperatedautomaticsprin- klerinresponsetoheatfromafire permitstheDPV-1DryPipeValveto openandallowaflowofwaterintothe sprinklersystempiping.TableBes- tablishestheminimumrequiredsys- temairpressurethatincludesasafety factortohelppreventfalseoperations thatmightoccurduetowatersupply fluctuations. WARNING TheModelDPV-1DryPipeValvesde- scribedhereinmustbeinstalledand maintainedincompliancewiththis document,aswellaswiththeapplica- blestandardsoftheNationalFirePro- tectionAssociation,inadditiontothe standardsofanyotherauthoritieshav- ingjurisdiction.Failuretodosomay impairtheperformanceofthesede- vices. Theownerisresponsibleformaintain- ingtheirfireprotectionsystemandde- vicesinproperoperatingcondition. Theinstallingcontractorormanufac- turershouldbecontactedwithany questions. ModelDPV-1DryPipeValve,ExternalResetting 2-1/2thru6Inch(DN65thruDN150) 250psi(17,2bar) Page1of20 TFP1020AUGUST,2007 TechnicalServices:Tel:(800)381-9312/Fax:(800)791-5500 EndConnection 2-1/2 Inch (DN65) 3Inch (DN80) 4Inch (DN100) 6Inch (DN150) NominalValveSize FlangexFlange FlangexGroove Groove xGroove AvailableEndConnectionsandSizes Available NotAvailableN/A N/AN/A N/AN/A FIGURE1—Part1of2 MODELDPV-1DRYPIPEVALVES 2-1/2,3,and4INCH(DN65,DN80,andDN100) —ASSEMBLY— 5 3 4 1 1ValveBody1NR NR NR See(a) See(a)or(b) See(a) See(c) 2 3 6 7 8 10 11 12 15 AirandWater HandholeCover Clapper ClapperFacing 1/4"x3/8"Long ClapperHinge ResetKnob ResetSpring 1 1 1 1 1 1 17 18 ResetLatch Seat RetainingPlate #10-32Shoulder Pin .... ...... ............ ....... ... .......... ............. 4HandholeCover See(b)Gasket1.......... 51/2-13UNCx1"Hex CH 2-1/2&3Inch 5........... ClapperFacing See(a)1.... HeadCapScrew: See(a)5Screw........... See(c)1..... 13ResetBushingSee(c)1.... 14ResetBushing See(b)or(c)O-Ring1........... ResetPlunger See(b)or(c)O-Ring1.......... 16ResetPlungerSee(c)1..... 9 11 12 13 14 15, 18 16 DowCorningFS3452 See(b)or(c)Grease,1.5g1..... Flourosilicone Subassembly1See(c)..... 17 2 6 7 8 10 CLAPPER ASSEMBLY RESET PLUNGER PARTS NO.QTY.DESCRIPTIONREF. (a)ClapperAssembly (b)RepairPartsKit (c)ResetPlungerPartsKit IncludesItems: IncludesItems 6-10: IncludesItems 4,7, 14,15,&18: 11through1892-309-1-405........ CH4InchValve6...... Valves ..2-1/2&3InchValves 4InchValve......... 92-309-2-203 92-309-2-403 ..2-1/2&3InchValves 4InchValve......... 92-309-1-204 92-309-1-404 92-1/2and3InchValves: 1/4-20UNCx1/2" SocketHeadCap See(a)7Screw........... 4InchValve: NR:NotReplaceable CH:CommonHardware NO.DESCRIPTIONP/N REPLACEMENT PARTS Page2of20 TFP1020 Page3of20TFP1020 FIGURE1—Part2of2 MODELDPV-1DRYPIPEVALVES 6INCH(DN150) —ASSEMBLY— 4 6 7 8 2 3 5 13 14 15 16 17 18, 21 19 20 9 10 11 12 CLAPPER ASSEMBLY RESET PLUNGER PARTS NRSee(a) See(a)or(b) See(a) See(c) 9 10 11 12 13 14 15 18 HandholeCoverClapper ClapperFacing 1/4-20UNCx1/2" ClapperHinge ResetKnob ResetSpring 11 1 1 1 20ResetLatch Subassembly1See(c) RetainingPlate SocketHeadCap Pin .... ...... ..... ............. ............. 7HandholeCover See(b)Gasket1.......... 85/8-11UNCx1" CHScrew6........... ClapperFacing See(a)1.... HexHeadCap See(a)9Screw........... See(c)1..... 16ResetBushingSee(c)1.... 17ResetBushing See(b)or(c)O-Ring1........... ResetPlunger See(b)or(c)O-Ring1........... 19ResetPlungerSee(c)1..... 21DowCorningFS3452 See(b)or(c)Grease,1.5g1..... Flourosilicone NO.QTY.DESCRIPTIONREF. (a)ClapperAssembly 92-309-2-603......... (b)RepairPartsKit (c)ResetPlungerParts Kit IncludesItems: IncludesItems: 9 through13 92-309-1-604...... IncludesItems: 7,10,17,18,21 14 through2192-309-1-405........ NRAirSealO-Ring1.... 53/8-16UNCx1" SocketHeadCap NR8Screw........... NO.QTY.DESCRIPTIONREF. 2AirandWater 3WaterSeal O-Ring ..........NR1 1ValveBody1NR....... NO.QTY.DESCRIPTIONREF. 4 NRSeat1............ 6 1 NR:NotReplaceable CH:CommonHardware NO.DESCRIPTIONP/N REPLACEMENT PARTS Technical Data Approvals: ULandC-ULListed.FMApproved. NYCunderMEA172-02-E(4and6 inch). DryPipeValve: TheModelDPV-1DryPipeValvesare forverticalinstallations(flowgoing up),andtheyareratedforuseata maximumservicepressureof250psi (17,2bar).TheValvedimensionsare showninFigure7. Flangedconnectionsareavailable drilledperANSI,ISO,AS,andJIS specifications(Ref.TableA).The groovedoutletconnections,asappli- cable,arecutinaccordancewith standardgroovespecificationsfor steelpipe.Theyaresuitableforuse withgroovedendpipecouplingsthat arelistedorapprovedforfireprotec- tionsystemservice.Availablecombi- nationsofinletandoutletconnections aredetailedintheOrderingProcedure section. Threadedportconnectionsofvalves havingflangesdrilledtoANSI,AS,or JISspecificationsareNPTthreaded perANSIStandardB1.20.1.Threaded portconnectionsofvalveshaving flangesdrilledtoISOareavailable eitherthreadedperISO7/1orNPT threadedperANSIStandardB1.20.1. ValveswithNPTthreadedportswill readilyacceptthetrimarrangements detailedinFigures4,5,and6. ComponentsoftheDPV-1Valvesare showninFigure1.TheBodyand HandholeCoverareductileiron.The HandholeCoverGasketisneoprene, andtheClapperFacingisEPDM.The Air/WaterSeatRingisbrass,theClap- perisbronzeoraluminumbronze,and boththeClapperRetainingPlateand Latcharebronze.TheHingePinis aluminumbronze,andthefasteners fortheHandholeCoverarecarbon steel. ValveTrim: Installationdimensionsaregivenin Figure7,andtheValveTrimisillus- tratedinFigures4,5,and6.TheValve Trimformsapartofthelaboratory listingsandapprovaloftheDPV-1 Valveandisnecessaryfortheproper operationoftheDPV-1Valve.Each packageoftrimincludesthefollowing items: •WaterSupplyPressureGauge •SystemAirPressureGauge •AirSupplyConnections •MainDrainValve •LowBodyDrainValve •AlarmTestValve •AutomaticDrainValve •DripFunnel •ConnectionsForOptionalQuick OpeningDevice(Accelerator) NOTE Whenthesystempressureisgreater than175psi(12,1bar),provisionisto bemadetoreplacethestandardorder 300psi(20,7bar)WaterPressure gaugewithaseparatelyordered600 psi(41,4bar)WaterPressureGauge. AirSupply: TableBshowsthesystemairpressure requirementsasafunctionofthewater supplypressure.Theair(ornitrogen) pressureinthesprinklersystemisrec- ommendedtobeautomaticallymain- tainedbyusingoneofthefollowing pressuremaintenancedevices,asap- propriate: •ModelAMD-1AirMaintenanceDe- vice(pressurereducingtype). •ModelAMD-2AirMaintenanceDe- vice(compressorcontroltype). •ModelAMD-3NitrogenMainte- nanceDevice(highpressurereduc- ingtype). ThePressureReliefValveprovided withthevalvetrimisfactorysetto relieveatapressureofapproxi- mately45psi(3,1bar).Ifthenormal systemairpressureislessthanor exceeds40psi(2,8bar),thenthe pressureReliefValvemustberesetto relieveatapressurethatisinaccord- ancewiththeAuthorityHavingJuris- diction. QuickOpeningDevice: Asanoption,theModelDPV-1Dry PipeValvemaybeequippedwiththe ModelQRSElectronicDryPipeValve Accelerator(4and6inchsizes)as detailedinTechnicalDataSheet TFP1100ortheModelACC-1Me- chanicalDryPipeValveAccelerator (2-1/2,3,4,and6inchsizes)asde- tailedinTechnicalDataSheet TFP1112. TheQRSortheACC-1isusedtore- ducethetimetovalveactuationfol- lowingtheoperationofoneormore automaticsprinklers.Insomecases theuseofaquickopeningdevicesuch astheQRSortheACC-1maybere- quiredtomeettherequirementsofthe NationalFireProtectionAssociationto meetwaterdeliverytimes. Patents: U.S.A.PatentNo.6,557,645 Page4of20 TFP1020 ANSIB16.1 AS2129JISB 2210 (Class125)(TableE)(10K) A 7.50 9.50 (190,5) (241,3) B 0.75 0.88 (19,0) (22,2) 7.00 9.25 (178,0) (235,0) 0.71 0.87 (18,0) (22,0) 6.89 (175,0) FlangeDrillingSpecification NominalDimensionsinInchesand(mm) 9.45 (240,0) Valve 4Inch 6Inch (DN100) (DN150) N 8 8 ISO7005-2 (PN16) 7.09 9.45 (180,0) (240,0) ABN 8 8 ABN 8 8 ABN 8 8 Dim.Dim. Nominal Qty.Dim.Dim.Qty.Dim.Dim.Qty.Dim.Dim.Qty. SamedrillingasforBS4504Section3.2(PN16)andDIN2532(PN16). Dim.A BoltCircle Diameter Dim.B BoltHole Diameter Qty.N Numberof BoltHoles 2 2 Size SamedrillingasforANSIB16.5(Class150)andANSIB16.42(Class150).1 1 0.75 (19,0) 0.91 (23,0) 0.75 (19,0) 0.59 (15,0) TABLEA DIMENSIONALSPECIFICATIONS FORSELECTIONOFFLANGEDRILLING Page5of20TFP1020 FIGURE2 MODELDPV-1DRYPIPEVALVES —NOMINALPRESSURELOSSVERSUSFLOW— Theapproximatefrictionlosses,basedontheHazenandWilliamsformulaandexpressedinequivalentlengthofSchedule40pipe withC=100areasfollows: 2.2feetforthe2-1/2inchvalveatatypicalflowrateof250GPM 4.9feetforthe3inchvalveatatypicalflowrateof350GPM 8.9feetforthe4inchvalveatattypicalflowrateof600GPM 22feetforthe6inchvalveatatypicalflowrateof1500GPM 200030005000100007000 0,08 0,03 0,04 0,06 0,05 0,07 0,09 0,10 0,20 0,30 0,40 0,50 0,60 5007001000 300700500400100020003000 0.4 0.3 NO M I NA L PR E S S U R E DR O P I N P O U N DS P E R SQ U A RE I N C H (P S I ) 0.9 1.0 0.8 0.7 0.5 0.6 2.0 6.0 5.0 3.0 4.0 9.0 8.0 7.0 0.2 0.1 200100 0,02 0,01 FLOWRATEINGALLONSPERMINUTE(GPM) FLOWRATEINLITRESPERMINUTE(LPM) (1GPM=3.785LPM) (1 P S I = 0 . 0 6 8 9 5 BA R ) NO M I NA L PR E S S U R E DR O P I N B A R 2-1 / 2 IN C H (D N 6 5 ) & 3 IN C H (D N 8 0 ) 4 IN C H (D N 1 0 0 ) 6 IN C H (D N 1 5 0 ) Operating Principles TheModelDPV-1DryPipeValveisa differentialtypevalvethatutilizesa substantiallylowersystem(airornitro- gen)pressurethanthesupply(water) pressure,tomaintainthesetposition showninFigure3A.Thedifferential natureoftheDPV-1isbasedonthe areadifferencebetweentheairseat andthewaterseatincombinationwith theratiooftheradialdifferencefrom theHingePintothecenterofthe WaterSeatandtheHingePintothe centeroftheAirSeat.Thedifference issuchthat1psi(0,07bar)ofsystem airpressurecanholdapproximately 5.5psi(0,38bar)ofwatersupplypres- sure. TableBestablishestheminimumre- quiredsystemairpressurethatin- cludesasafetyfactortohelpprevent falseoperationsthatoccurdueto watersupplyfluctuations. TheIntermediateChamberofthe DPV-1isformedbytheareabetween theAirSeatandWaterSeatasshown inFigure3B.TheIntermediateCham- bernormallyremainsatatmospheric pressurethroughtheAlarmPortcon- nectionandthevalvetrimtothenor- mallyopenAutomaticDrainValve (Fig.4,5,or6).HavingtheIntermedi- ateChamber,Figure3B,opentoat- mosphereiscriticaltotheDPV-1 Valveremainingset,otherwisethefull resultingpressureofthesystemair pressureontopoftheClapperAssem- blycannotberealized. Forexampleandassumingawater supplypressureof100psi(6,9bar),if thesystemairpressureis25psi(1,7 bar)andtherewas15psi(1,0bar) pressuretrappedintheIntermediate Chamber,theresultingpressure acrossthetopoftheClapperwould onlybe10psi(0,7bar).Thispressure wouldbeinsufficienttoholdtheClap- perAssemblyclosedagainstawater supplypressureof100psi(6,9bar).It isforthisreasonthattheplungerofthe AutomaticDrainValvemustbede- pressedduringseveraloftheresetting steps,aswellasduringinspections, makingcertainthattheAutomatic DrainValveisopen. Whenoneormoreautomaticsprin- klersoperateinresponsetoafire,air pressurewithinthesystempipingis relievedthroughtheopensprinklers. Whentheairpressureissufficiently reduced,thewaterpressureover- comesthedifferentialholdingthe ClapperAssemblyclosedandthe ClapperAssemblyswingsclearofthe waterseat,asshowninFigure3C, Thisactionpermitswaterflowintothe systempipingandsubsequentlytobe dischargedfromanyopensprinklers. Also,withtheClapperAssemblyopen, theintermediatechamberispressur- izedandwaterflowsthroughthealarm port(Ref.Figure3B)attherearofthe DPV-1Valvetoactuatesystemwater flowalarms.Theflowfromthealarm portisalsosufficienttoclosetheoth- erwisenormallyopenAutomaticDrain Valveinthevalvetrim. Afteravalveactuationanduponsub- sequentclosingofasystemmaincon- trolvalvetostopwaterflow,theClap- perAssemblywilllatchopenasshown inFigure3D.Latchingopenofthe DPV-1willpermitcompletedrainingof thesystem(includinganyloosescale) throughthemaindrainport. Duringthevalveresettingprocedure andafterthesystemiscompletely drained,theexternalresetknobcan beeasilydepressedtoexternallyun- latchtheClapperAssemblyasshown inFigure3E.Assuch,theClapper Assemblyisreturnedtoitsnormalset positiontofacilitatesettingofthedry pipesprinklersystem,withouthaving toremovetheHandholeCover. Page6of20 TFP1020 Maximum WaterSupply Pressure, psi SystemAir Pressure Range, psi 20 60 80 100 120 145 10 15-23 20-28 25-33 30-38 35-43 165 185 205 40-48 45-53 50-58 225 55-63 250 60-68 TABLEB SYSTEMAIRPRESSURE REQUIREMENTS Page7of20TFP1020 FIGURE3—Part1of2 MODELDPV-1DRYPIPEVALVES 2-1/2,3,and4INCH(DN65,DN80,andDN100) —SETANDOPENPOSITIONS— INTERMEDIATE CHAMBER FULLY OPEN ASSEMBLY CLAPPER &ALARM FIGURE3D FIGURE3A DRAINPOSITION SETPOSITION SHUTOFF WATERSUPPLY FROM SYSTEM WATERSUPPLY OPEN 3/4"NPT LOWBODY DRAIN 04 ASSEMBLY LATCHED CLAPPER TESTPORT 02 LATCH CLAPPER 05 RESET SETPOSITION FIGURE3B AIR PRESSURE TO SYSTEM 1"NPT PORT 1/2"NPT WATER AIR SUPPLY PRESSURE SUPPLY 01 RESEATED ASSEMBLY CLAPPER TOALARM ALARMPORT WATERFLOW LATCH FIGURE3E RESETPOSITION SHUTOFF WATERSUPPLY ASSEMBLY CLAPPER PIVOTSTO UNLATCH FIGURE3C OPERATEDPOSITION COMPLETE SYSTEM WATERSUPPLY CLAPPER FROM WATERFLOW TO SYSTEM CLAPPERLATCH CLAPPERASSEMBLY PIVOTSTOALLOW TOFULLYOPEN ASSEMBLY ATMOSPHERE 3/4"NPTALARM PORTOPENTO 03 PORT KNOB RESET DRAIN FROM DRAIN FROM CLAPPER INSET ASSEMBLY POSITION PUSHHERE VALVE TORESET INTERMEDIATE WATER VALVE WATERWAY SEAT ASSEMBLY CLAPPER PORT CHAMBER ALARM AIR SEAT 03 & 3 INCHVALVES) 1-1/4" NPT* (2-1/2INCH 2"NPT(4INCHVALVE) MAIN DRAINPORT: DN40FOR VALVESWITH ISOTHREADEDPORTS * Page8of20 TFP1020 FIGURE3—Part2of2 MODELDPV-1DRYPIPEVALVES 6INCH(DN150) —SETANDOPENPOSITIONS— ATMOSPHERE PORTOPENTO 3/4"NPTALARM TO FULLYOPEN PIVOTSTOALLOW CLAPPERASSEMBLY CLAPPER LATCH TESTPORT PRESSURE FULLY OPEN ASSEMBLY WATERSUPPLY AIR SEAT VALVE WATERWAY LATCH CLAPPER ASSEMBLY CLAPPER UNLATCH PIVOTSTO FROM DRAIN FIGURE3A SET POSITION WATERSUPPLY FROMSYSTEM SHUTOFF FIGURE3D DRAINPOSITION WATERSUPPLY PORT 2"NPT PORT MAINDRAIN 05 04 3/4"NPT DRAIN OPEN LOWBODY ASSEMBLY LATCHED CLAPPER LATCH CLAPPER INTERMEDIATE CHAMBER WATER SEAT CHAMBER RESET FIGURE3B SET POSITION INTERMEDIATE ASSEMBLY ASSEMBLY CLAPPER TOSYSTEM AIRPRESSURE 1"NPT PORT AIRSUPPLY INSET ASSEMBLY CLAPPER POSITION 01 02 03 &ALARM 1/2"NPT CLAPPER TOALARM TO RESET VALVE PUSH HERE WATERFLOW CLAPPER RESEATED ASSEMBLY FIGURE 3E RESETPOSITION SHUTOFF WATERSUPPLY FROM SYSTEM FIGURE3C DRAIN FROM COMPLETE OPERATED POSITION WATERSUPPLY ALARM PORT 03 RESET KNOB ALARMPORT WATERFLOW TOSYSTEM Page9of20TFP1020 FIGURE4—Part1of2 2-1/2and3INCH(DN65andDN80)MODELDPV-1DRYPIPEVALVES —EXPLODEDVIEWOFVALVETRIM— 31 18 34 24 10 12 16 4 23 9 31 32 11 16 3 1 32 23 15 20 or3INCH(DN80) MODELDPV-1 DRYPIPEVALVE 41 22 40 8 6 30 3 26 26 14 15 2 37 38 7 28 39 2132 1735 31 32 NOTES: 1.SEEFIGURE3FORVALVE PORTIDENTIFICATION. ROUTE1/4"TUBING,ITEM14, TODRIP FUNNEL,ITEM12. 2. 33 25 LOCATION FOROPTIONAL ELECTRICALLY SUPERVISED N.O.ALARM (BVS-1/2") VALVE CONTROL 32 20 36 20 9 NO. 1250psi/1750kPa 1 QTY. 92-343-1-012 DESCRIPTIONP/N 92-343-1-005 46-005-1-002 46-050-1-004 46-049-1-004 92-211-1-005 2 3 4 5 6 9 300psi/2000kPa 1/4"Gauge Test 1/2"BallValve 1/2"Swing DripFunnel 1 2 2 2 1 WaterPressure Gauge AirPressure Gauge Valve CheckValve Connector .... ........... ........... ............ ...... ........ NO. 11 QTY.DESCRIPTIONP/N 92-211-1-003 92-343-1-00712 DripFunnel DripFunnel 1 1 1"x1"x1/2" 1CH 24 15 16 17 18 20 26 27 1/4" Tube, 1/4"Plug 1/2"Plug 1"Plug 1/2"90°Elbow 1/2"x1/4"x1/2" 1/2"x1/2"x3/4" CH1 2 2 1 3 2 1 CH CH CH CH CH CH 1/2"Union1CH 13 92-032-1-002 3/32"Vent 28 14 Bracket Fitting 18"Long Reducing Tee Reducing Tee Reducing Tee ....... ......... ......... .......... .... ........ .......... ........... ......... ..... ..... ..... 1 CH:CommonHardware 33 34 35 37 38 40 41 NotUsed 1/2"x1-1/2" 1/2"x2"Nipple 1/2"x4-1/2" 1/2"x6"Nipple 3/4"x1-1/2" 3/4"x2-1/2" 1-1/4"xClose 1-1/4"x4"Nipple 8 1 1 1 1 CH CH CH CH CH 32 Nipple Nipple Nipple .... .... ........... ........... ........... 29 10 areGalvanized AllFittingsandNipples NO.QTY.DESCRIPTIONP/N 1/2"xClose 4CH 31 Nipple........... 363/4"xClose 1CHNipple........... 191/2"x1/4"Reducing Bushing1CH......... 231/2"Cross2CH........ 92-343-1-020 1/4"Pressure 1ReliefValve....... 52-793-2-004 ModelAD-1 1 Automatic DrainValve....... 46-048-1-00573/4"AngleValve1... 46-048-1-00781-1/4"AngleValve1.213/4"90°Elbow1CH.... 221-1/4"90°Elbow1CH... 251/2" Tee1CH......... 1/4"x3"Nipple2CH....30 1CHNipple........... 391"xCloseNipple1CH.. 1CHNipple........... 1CH.. TINT) (GREEN 13 2-1/2INCH(DN65) 1/2"x1/2"x1/4" 1CHReducing Tee..... 19 30 31 27 325 32 6 32 Page10of20 TFP1020 FIGURE4—Part2of2 2-1/2and3INCH(DN65andDN80)MODELDPV-1DRYPIPEVALVES —ASSEMBLYPROCEDUREFORVALVETRIM— AUTOMATIC DRAINVALVE TEST VALVE ALARM (NORMALLY CLOSED) CLOSED) (NORMALLY DRAINVALVE MAIN 1-1/4 INCHNPT CONNECTION FUNNEL DRIP AIRSUPPLY CONTROLVALVE (NORMALLYOPEN) 1/2INCHNPT TODRAIN PRESSURE GAUGE AIRSUPPLY SYSTEM 1-1/4 INCHNPT CONNECTION TODRAIN DRAINVALVE LOWBODY (NORMALLY CLOSED) 1INCHNPT CONNECTION FORLOCAL SPRINKLER PRESSURE GAUGE WATERSUPPLY SYSTEM 1/2INCHNPT 1/2INCHNPT CONNECTION FORWATERFLOW PRESSUREALARM SWITCH NOTES: 2.SEEFIGURE3 FORVALVEPORT IDENTIFICATION. 1.INSTALLTRIMASSEMBLIESIN ALPHABETICALORDER. 3.ROUTE1/4"TUBING TODRIP A 1/2INCHNPT CONNECTION FOROPTIONAL AIRPRESSURE SWITCH 3/4INCHNPT CONNECTION TO DRAIN B C D H E F G or3INCH(DN80) MODELDPV-1 DRY PIPEVALVE 2-1/2INCH(DN65) CONNECTION FORSYSTEM AIRSUPPLY CONNECTION FOROPTIONAL ACCELERATOR FUNNEL. Page11of20TFP1020 FIGURE5—Part1of2 4INCH(DN100)MODELDPV-1DRYPIPEVALVES —EXPLODEDVIEWOFVALVETRIM— NOTES: 1.SEEFIGURE3FORVALVE PORTIDENTIFICATION. ROUTE1/4"TUBING,ITEM16, TODRIPFUNNEL,ITEM14. 2. TINT) (GREEN 15 SLOPE3/4"ANGLEVALVE, ITEM9,DOWNTOWARDBACK 3. OFVALVETOFACILITATE SUFFICIENTLOWBODY SLOPE DOWN 9 DRAINAGE. NO. 1250psi/1750kPa 1 QTY. 92-343-1-012 DESCRIPTIONP/N 92-343-1-005 46-005-1-002 92-343-1-020 46-048-1-004 52-793-2-004 46-050-1-004 46-049-1-004 46-048-1-005 46-049-1-005 46-048-1-009 92-211-1-005 2 3 4 5 6 7 8 9 10 11 300psi/2000kPa 1/4"Gauge Test 1/4"Pressure 1/2"AngleValve ModelAD-1 1/2"BallValve 1/2"Swing 3/4"AngleValve 3/4"Swing 2"AngleValve DripFunnel 1 2 1 1 1 1 1 1 1 1 1 WaterPressure Gauge AirPressure Gauge Valve ReliefValve Automatic DrainValve CheckValve CheckValve Connector ... .... ... .... ........... ........... ............ ....... ....... ...... ...... ........ NO. 13 QTY.DESCRIPTIONP/N 92-211-1-003 92-343-1-00714 DripFunnel DripFunnel 1 1 3/4"x1/2"x3/4" 1"x1"x1/2" 3 1 CH CH 27 17 18 19 20 22 23 24 28 29 1/4" Tube, 1/4"Plug 1/2"Plug 3/4"Plug 1"Plug 1/2"90°Elbow 1/2"45°Elbow 1/2" Tee 1/2"x1/4"x1/2" 1/2"x1/2"x1/4" CH1 2 2 1 1 1 1 2 2 1 CH CH CH CH CH CH CH CH CH 1/2"Union 3/4"Union 1 1 CH CH 15 92-032-1-002 3/32"Vent 31 16 25 Bracket Fitting 24"Long Reducing Tee Reducing Tee Reducing Tee Reducing Tee ....... ......... ......... ......... .......... .... .... ......... ........ ........ .......... ........... ......... ..... ..... ..... ..... 1 CH:CommonHardware 35 36 37 38 40 41 42 43 44 1/4"x3"Nipple 1/2"x1-1/2" 1/2"x2"Nipple 1/2"x2-1/2" 1/2"x3"Nipple 1/2"x3-1/2" 3/4"x1-1/2" 3/4"x2"Nipple 3/4"x3"Nipple 1"x4"Nipple 2"x4-1/2" 2 7 1 1 1 1 2 1 1 CH CH CH CH CH CH CH CH CH 34 Nipple Nipple Nipple Nipple .... .... .... .... ..... ........... ........... ........... ........... Nipple1CH........... 30 32 12 1CH.... areGalvanized AllFittingsandNipples NO.QTY.DESCRIPTIONP/N 1/2"xClose 2CH 33 Nipple........... 393/4"xClose 2CHNipple........... 34 30 39 10 3940 3041 30 36 19 34 40 23 12 13 14 18 34 27 628 44 11 33 25 33 4334 31 9 42 28 35 24 37 22 32 2 3 TINT) (GREEN 15 38 17 20 7 16 29 4 34 5 3 1 17 21 34 32 27 1834 26 4INCH(DN100) MODELDPV-1 DRY PIPEVALVE LOCATION FOROPTIONAL ELECTRICALLY SUPERVISED N.O.ALARM (BVS-3/4") VALVE CONTROL 8 211/2"x1/4"Reducing Bushing1CH......... 261/2"Cross1CH........ Page12of20 TFP1020 FIGURE5—Part2of2 4INCH(DN100)MODELDPV-1DRYPIPEVALVES —ASSEMBLYPROCEDUREFORVALVETRIM— AUTOMATIC DRAINVALVE TEST VALVE ALARM (NORMALLY CLOSED) CLOSED) (NORMALLY DRAINVALVE MAIN 2INCHNPT CONNECTION FUNNEL DRIP AIRSUPPLY CONTROLVALVE (NORMALLY OPEN) 1/2INCHNPT CONNECTION FORSYSTEM AIRSUPPLY TODRAIN PRESSURE GAUGE AIRSUPPLY SYSTEM 1-1/4 INCHNPT CONNECTION TO DRAIN DRAINVALVE LOWBODY (NORMALLY CLOSED) D B 1INCHNPT CONNECTION FORLOCAL SPRINKLER PRESSURE GAUGE WATERSUPPLY SYSTEM 1/2INCHNPT CONNECTION FOROPTIONAL ACCELERATOR C 3/4INCHNPT CONNECTION FORWATER MOTORALARM 1/2INCHNPT CONNECTION FORWATERFLOW PRESSUREALARM SWITCHSLOPE DOWN B INCHNPT CONNECTION TODRAIN NOTES: 2.SEEFIGURE3 FORVALVEPORT IDENTIFICATION. 1.INSTALLTRIMASSEMBLIESIN ALPHABETICALORDER. SLOPEASSEMBLYBDOWN TOWARD BACKOFVALVETOFACILITATE 4. SUFFICIENT LOWBODYDRAINAGE. 3.ROUTE1/4"TUBING TODRIPFUNNEL. 4INCH(DN100) MODELDPV-1 DRY PIPEVALVE A 1/2INCHNPT CONNECTION FOROPTIONAL AIRPRESSURE SWITCH 3/4 Page13of20TFP1020 FIGURE6—Part1of2 6INCH(DN150)MODELDPV-1DRYPIPEVALVES —EXPLODEDVIEWOFVALVETRIM 42 9 14 TO FIT SLOPE 6INCH(DN150) MODELDPV-1 DRY PIPEVALVE 44 11 36 33 35 34 25 31 40 40 41 35 42 23 27 18 35 27 6 28 TINT) (GREEN 1516 42 40 9 35 35 35 43 26 35 20 8 29 4 5 40 22 30 24 12 14 13 31 40 37 31 19 10 NOTES: 1.SEEFIGURE3FORVALVEPORTIDENTIFICATION. ROUTE1/4" TUBING,ITEM16,TODRIPFUNNEL,ITEM14.2. SLOPE3/4"ANGLEVALVE,ITEM9,AND 3/4"x4-1/2"NIPPLE, ITEM42,INTODRIPFUNNEL,ITEM14,TOFACILITATE 3. SUFFICIENTLOW BODYDRAINAGE. 1250psi/1750kPa 192-343-1-012 92-343-1-005 46-005-1-002 92-343-1-020 46-048-1-004 52-793-2-004 46-050-1-004 46-049-1-004 2 3 4 5 6 7 8 300psi/2000kPa 1/4"GaugeTest 1/4"Pressure 1/2"AngleValve ModelAD-1 1/2"BallValve 1/2"Swing 1 2 1 1 1 1 1 WaterPressure Gauge AirPressure Gauge Valve Relief Valve Automatic DrainValve CheckValve ... .... ........... ........... ............ ....... ....... ...... 46-048-1-0053/4"AngleValve1...9 NO.QTY.DESCRIPTIONP/N 46-049-1-005 46-048-1-009 92-211-1-005 10 11 3/4"Swing 2"AngleValve DripFunnel 1 1 1 CheckValve Connector .... ...... ........ 13 92-211-1-003 92-343-1-00714 DripFunnel DripFunnel 1 1 17 18 19 20 1/4"Tube, 1/4"Plug 1/2"Plug 3/4"Plug 1"Plug 1/2"90°Elbow CH1 2 2 1 1 1 1/2"Union 3/4"Union 1 1 15 92-032-1-002 3/32"Vent 16 Bracket Fitting 24"Long ....... ......... ......... ......... .......... .... ........ ........ .......... ........... ......... 1 12 23 22 24 CH CH CH CH CH CH CH 1/2"45°Elbow 1/2"Tee 1 2 CH CH .... ......... 25 27 NO.QTY.DESCRIPTIONP/N 3/4"x1/2"x3/4" 1"x1"x1/2" 3 1 CH CH 28 29 1/2"x1/4"x1/2" 1/2"x1/2"x1/4" 2 1 CH CH 32 ReducingTee ReducingTee ReducingTee ReducingTee ..... ..... ..... ..... 36 37 38 39 40 41 42 43 44 1/4"x3"Nipple 1/2"x1-1/2" 1/2"x2"Nipple 1/2"x2-1/2" 1/2"x3"Nipple 3/4"x1-1/2" 3/4"x2"Nipple 3/4"x4-1/2" 1"x4"Nipple 2"x4-1/2" 2 8 1 1 1 5 1 2 1 CH CH CH CH CH CH CH CH CH 35 Nipple Nipple 1/2"x6"Nipple Nipple Nipple .... .... .... ..... ........... ........... .... ........... ........... Nipple1CH........... 31 33 1CH3/4"90°Elbow....30 1/2"xClose 1CH 34 Nipple........... NO.QTY.DESCRIPTIONP/N CH:CommonHardware areGalvanized AllFittingsandNipples LOCATION FOROPTIONAL ELECTRICALLY SUPERVISED N.O.ALARM (BVS-3/4") VALVE CONTROL 28 39 2 3 17 35 7 38 1CH.... 1 3 17 21 32 33 18 211/2"x1/4"Reducing 1CHBushing......... 1/2"Cross1CH.......26 Page14of20 TFP1020 FIGURE6—Part2of2 6INCH(DN150)MODELDPV-1DRYPIPEVALVES —ASSEMBLYPROCEDUREFORVALVETRIM— NOTES: SEEFIGURE3FORVALVEPORT IDENTIFICATION. INSTALLTRIMASSEMBLIESIN ALPHABETICALORDER. SLOPE3/4"ANGLEVALVEAND 3/4"x4-1/2"NIPPLE(OFASSEMBLYB) INTODRIP FUNNELTOFACILITATE SUFFICIENT LOWBODYDRAINAGE. TEST VALVE ALARM (NORMALLY CLOSED) DRAINVALVE 2INCHNPT CONNECTION AIRSUPPLY CONTROLVALVE (NORMALLY OPEN) 1/2INCHNPT CONNECTION FORSYSTEM AIRSUPPLY TODRAIN PRESSURE GAUGE AIRSUPPLY SYSTEM 1-1/4 INCHNPT CONNECTION TODRAIN DRAINVALVE LOWBODY (NORMALLY CLOSED) 1INCHNPT CONNECTION FORLOCAL SPRINKLER PRESSURE GAUGE WATERSUPPLY SYSTEM 1/2INCHNPT CONNECTION FOROPTIONAL ACCELERATOR 3/4INCHNPT CONNECTION FORWATER MOTORALARM 1/2INCHNPT CONNECTION FORWATERFLOW PRESSUREALARM SWITCH MAIN (NORMALLY CLOSED) A D B C TOFIT SLOPE B FUNNEL DRIP NOTES: 2. 1. 4. FUNNEL DRIP AUTOMATIC DRAINVALVE ROUTE1/4"TUBINGTODRIP FUNNEL. 3. 6INCH(DN150) MODELDPV-1 DRY PIPEVALVE 1/2INCHNPT CONNECTION FOROPTIONAL AIRPRESSURE SWITCH Page15of20TFP1020 FIGURE7 MODELDPV-1DRYPIPEVALVE —INSTALLATIONDIMENSIONS— 16-9/16" (420,7mm) 6" (150mm) (311,2mm) 2-1/2or3INCH 14-7/8" (380mm) 9-1/4" (235mm) 6-3/4" (170mm) 8" (200mm) 12-1/4" VALVES 2-1/2&3INCH (DN65&DN80) VALVE 6" (150mm) 17-1/4" (440mm) 2-1/2"(65mm) 12" (300mm) 14" (355mm) 12" (300mm) FxF:13-5/8"(346,1mm) GxG:13-3/4" (349,3 mm) FxG:13-11/16"(347,7mm) 4INCH (DN100) VALVE 7-1/4" (190mm) 18-3/4" (475mm) 4-1/2" 11-1/2" (290mm) 14-3/4" (375mm) 15" (380mm) (115 mm) 16" FxF,FxG, (406.4 mm) orGxG 6INCH (DN150) VALVE Installation NOTES ProperoperationoftheModelDPV-1 DryPipeValvedependsuponitstrim beinginstalledinaccordancewiththe instructionsgiveninthisTechnical DataSheet.Failuretofollowtheap- propriatetrimdiagrammayprevent theDPV-1Valvefromfunctioning properly,aswellasvoidlistings,ap- provals,andthemanufacturer’swar- ranties. FailuretolatchopentheClapperAs- semblypriortoasystemhydrostatic testmayresultindamagetotheClap- perAssembly. TheDPV-1Valvemustbeinstalledin areadilyvisibleandaccessibleloca- tion. TheDPV-1Valveandassociatedtrim mustbemaintainedataminimumtem- peratureof40°F/4°C. HeattracingoftheDPV-1Valveorits associatedtrimisnotpermitted.Heat tracingcanresultintheformationof hardenedmineraldepositsthatareca- pableofpreventingproperoperation. TheModelDPV-1DryPipeValveisto beinstalledinaccordancewiththefol- lowingcriteria: Step1.Allnipples,fittings,andde- vicesmustbecleanandfreeofscale andburrsbeforeinstallation.Usepipe threadsealantsparinglyonmalepipe threadsonly. Step2.TheDPV-1Valvemustbe trimmedinaccordancewithFigures4, 5,or6,asapplicable.IftheDPV-1is tobeequippedwithaDryPipeValve Accelerator,refertotheTechnical DataSheetTFP1100fortheModel QRSElectronicDryPipeValveAccel- eratororTFP1112fortheModelACC- 1MechanicalDryPipeValveAccel- erator. Step3.Caremustbetakentomake surethatcheckvalves,strainers, globevalves,etc.areinstalledwiththe flowarrowsintheproperdirection. Step4.Draintubingtothedripfunnel mustbeinstalledwithsmoothbends thatwillnotrestrictflow. Step5.Themaindrainanddripfunnel drainmaybeinterconnectedprovided acheckvalveislocatedatleast12 inches(300mm)belowthedripfunnel. TheLowBodyDrainValve(Fig.4,5, or6)maybepipedsoastodischarge intotheDripFunnelortoaseparate drain. Step6.Suitableprovisionmustbe madefordisposalofdrainwater. Drainagewatermustbedirectedsuch thatitwillnotcauseaccidentaldam- agetopropertyordangertopersons. Step7.Unusedpressurealarmswitch and/orwatermotoralarmconnections mustbeplugged. Step8.ThePressureReliefValvepro- videdwiththeValveTrimisfactoryset torelieveatapressureofapproxi- mately45psi(3,1bar),whichcantypi- callybeusedforamaximumnormal systemairpressureof40psi(2,8bar). ThePressureReliefValvemaybere- settoalowerorhigherpressure;how- ever,itmustbeberesettorelieveata pressurewhichisinaccordancewith therequirementsoftheAuthorityHav- ingJurisdiction. ToresetthePressureReliefValve, firstloosenthejamnutandthenadjust thecapaccordingly—clockwisefora higherpressuresettingorcounter- clockwiseforalowerpressuresetting. Afterverifyingthedesiredpressure setting,tightenthejamnut. Step9.InstallationofanAirMainte- nanceDevice,asdescribedinthe TechnicalDataSection,isrecom- mended. Step10.AnInspector’sTestConnec- tionasrequiredByNFPA13mustbe providedonthesystempipingatthe mostremotelocationfromtheModel DPV-1Valve. Step11.Conduitandelectricalcon- nectionsaretobemadeinaccordance withtherequirementsoftheauthority havingjurisdictionand/ortheNational ElectricCode. Step12.Beforeasystemhydrostatic testisperformedinaccordancewith NFPA13systemacceptancetestre- quirements,theClapperAssemblyis tobemanuallylatchedopen(Ref.Fig. 3D);theAutomaticDrainValve(Fig.4, 5,or6)istobetemporarilyreplaced witha1/2inchNPTplug,the3/32inch VentFitting(Item13,Fig.4;Item15, Fig.5;orItem15,Fig.6)istobe temporarilyreplacedwitha1/4inch NPTplug,andtheHandholeCover Boltsaretobetightenedusingacross- drawsequence. ValveSetting Procedure Steps1through11aretobeper- formedwheninitiallysettingtheModel DPV-1DryPipeValve;afteranopera- tionaltestofthefireprotectionsystem; or,aftersystemoperationduetoafire. NOTES IftheDPV-1isequippedwithaDry PipeValveAccelerator,refertoitsre- settinginstructionsbeforeresetting theDPV-1.RefertoTFP1100forthe QRSorTFP1112fortheACC-1. Basedontheinstructionsprovided,re- settheAcceleratorattheappropriate timeduringtheresettingoftheDPV-1. Step1.ClosetheMainControlValve, andclosetheAirSupplyControlValve (Fig.4,5,or6).IftheDPV-1is equippedwithaDryPipeValveAccel- erator,removetheDryPipeValveAc- celeratorfromserviceinaccordance withitsTechnicalDataSheet(Referto TFP1100fortheQRSorTFP1112for theACC-1). Step2.OpentheMainDrainValve (Fig.4,5,or6)andallauxiliarydrains inthesystem.Closetheauxiliarydrain valvesafterwaterceasestodis- charge.LeavetheMainDrainValve open. Step3.Depresstheplungerofthe AutomaticDrainValve(Fig.4,5,or6) toverifythatitisopenandthatthe DPV-1Valveiscompletelydrained. Step4.OpentheOptionalAlarmCon- trolValve(Fig.4,5,or6),asapplica- ble,ifitwasclosedtosilencelocal alarms. Step5.Asnecessary,replaceall sprinklersthathaveoperated.Re- placementsprinklersmustbeofthe sametypeandtemperatureratingas thosewhichhaveoperated. NOTE Inordertopreventthepossibilityofa subsequentoperationofanover- heatedsoldertypesprinkler,anysol- dertypesprinklerswhichwerepossi- blyexposedtoatemperaturegreater thantheirmaximumratedambient mustbereplaced. Step6.PushdownontheResetKnob (Fig.3E)toallowtheClapperAssem- blytoreseat. Step7.Pressurizethesystemwithair (ornitrogen)to10psi(0,7bar),and thenindividuallyopenallauxiliary drainvalvesinthesystempipingto drainanyremainingwaterintrapped sections.Closeeachdrainvalveas soonaswaterceasestodischarge. Page16of20 TFP1020 AlsopartiallyopentheLowBodyDrain Valve(Fig.4,5,or6)toassurethatthe riseriscompletelydrained.Closethe LowBodyDrainValveassoonas waterceasestodischarge. Step8.RefertoTableBandthen restorethesystemtothenormalsys- temairpressureasnecessarytohold theDPV-1Valveclosed. Step9.Depresstheplungeronthe AutomaticDrainValvetomakesureit isopenandthatthereisnoairdis- charging. Theabsenceofairdischargingfrom theAutomaticDrainValveisanindica- tionofaproperlysetairseatwithinthe DPV-1Valve.Ifairisdischarging,refer totheCareandMaintenancesection underAutomaticDrainValveInspec- tiontodetermine/correctthecauseof theleakageproblem. Step10.PartiallyopentheMainCon- trolValve.SlowlyclosetheMainDrain Valveassoonaswaterdischarges fromthedrainconnection. DepresstheplungerontheAutomatic DrainValvetomakesurethatitisopen andthatthereisnowaterdischarging. Theabsenceofwaterdischarging fromtheAutomaticDrainValveisan indicationofaproperlysetwaterseat withintheDPV-1Valve.Ifwaterisdis- charging,refertotheCareandMain- tenancesectionundertheAutomatic DrainValveInspectiontodeter- mine/correctthecauseoftheleakage problem. Iftherearenoleaks,theDPV-1Valve isreadytobeplacedinserviceandthe MainControlValvemustthenbefully opened. NOTE Aftersettingafireprotectionsystem, notifytheproperauthoritiesandad- visethoseresponsibleformonitoring proprietaryand/orcentralstation alarms. Step11.Onceaweekafteravalveis resetfollowinganoperationaltestor systemoperation,theLowBodyDrain Valve(andanylowpointdrainvalves) shouldbepartiallyopened(andthen subsequentlyclosed)torelievedrain- backwater.Continuethisprocedure untildrain-backwaterisnolongerpre- sent. Careand Maintenance Thefollowingproceduresandinspec- tionsshouldbeperformedasindi- cated,inadditiontoanyspecificre- quirementsoftheNFPA,andany impairmentmustbeimmediatelycor- rected. Theownerisresponsibleforthein- spection,testing,andmaintenanceof theirfireprotectionsystemandde- vicesincompliancewiththisdocu- ment,aswellaswiththeapplicable standardsoftheNationalFireProtec- tionAssociation(e.g.,NFPA25),in additiontothestandardsofany authorityhavingjurisdiction.Thein- stallingcontractororproductmanufac- turershouldbecontactedrelativeto anyquestions. Itisrecommendedthatautomatic sprinklersystemsbeinspected, tested,andmaintainedbyaqualified InspectionService. NOTES Theoperationaltestprocedureand waterflowpressurealarmtestproce- durewillresultinoperationoftheas- sociatedalarms.Consequently,notifi- cationmustfirstbegiventotheowner andthefiredepartment,centralsta- tion,orothersignalstationtowhichthe alarmsareconnected. Beforeclosingafireprotectionsystem maincontrolvalveformaintenance workonthefireprotectionsystemthat itcontrols,permissiontoshutdownthe affectedfireprotectionsystemsmust firstbeobtainedfromtheproper authoritiesandallpersonnelwhomay beaffectedbythisdecisionmustbe notified. AnnualOperationTestProcedure ProperoperationoftheDPV-1Valve (i.e.,openingoftheDPV-1Valvedur- ingafirecondition)shouldbeverified atleastonceayearasfollows: Step1.Ifwatermustbeprevented fromflowingbeyondtheriser,perform thefollowingsteps. •ClosetheMainControlValve. •OpentheMainDrainValve. •OpentheMainControlValveone turnbeyondthepositionatwhich waterjustbeginstoflowfromthe MainDrainValve. •ClosetheMainDrainValve. Step2.Openthesystem’sInspector’s TestConnection. Step3.VerifythattheDPV-1Valve hasoperated,asindicatedbytheflow ofwaterintothesystemandthatall waterflowalarmsoperateproperly. Step4.Closethesystem’sMainCon- trolValve. Step5.ResettheDPV-1Valveinac- cordancewiththeValveSettingProce- dure. NOTE Itisrecommendedthattherequire- mentofNFPA25toannuallyinspect theinsideofthevalvebeperformedat thistimeandpriortoresettingthe DPV-1Valve.RefertotheAutomatic DrainValveInspectionsub-section Steps2through5forinstructionswith regardtotheinspectionoftheClapper Facing. QuarterlyWaterflowAlarmTest Procedure Testingofthesystemwaterflow alarmsshouldbeperformedquarterly. Totestthewaterflowalarm,openthe AlarmTestValve,whichwillallowa flowofwatertotheWaterflowPres- sureAlarmSwitchand/orWaterMotor Alarm.Uponsatisfactorycompletion ofthetest,closetheAlarmTestValve. WaterPressureInspection TheWaterPressureGaugeistobe inspectedmonthly(perNFPA25)to ensurethatnormalsystemwaterpres- sureisbeingmaintained. AirPressureInspection TheAirPressureGaugeistobein- spectedmonthly(perNFPA25)toen- surethatnormalsystemairpressure isbeingmaintained. AutomaticDrainValveInspection TheAutomaticDrainValveshouldbe inspectedmonthly(perNFPA25)by depressingtheplungerandchecking toensurethattheAutomaticDrain Valveisnotdischargingwaterand/or air.Adischargeofwaterand/orairis anindicationthattheairand/orwater seatsareleaking,whichcouldsub- sequentlycauseafalseoperation shouldtheintermediatechamberbe- comeinadvertentlypressurized. Ifleakageispresent,taketheDPV-1 Valveoutofservice(i.e.,closethe maincontrolvalve,openthemain drainvalve,closetheairsupplycontrol valve,removetheDryPipeValveAc- celeratorfromservice,asapplicable, inaccordancewithitsTechnicalData Sheet(RefertoTFP1100fortheQRS orTFP1112fortheACC-1),andopen theInspector’sTestConnectiontore- lievethesystemairpressureto0psig asindicatedontheSystemAirPres- sureGauge),andthenafterremoving Page17of20TFP1020 theHandholeCover,performthefol- lowingsteps: Step1.MakesurethattheSeatRing iscleanandfreeofanynicksorsignifi- cantscratches. Step2.RemovetheClapperAssem- blyfromthevalvebyfirstpullingout theHingePin. Step3.DisassembletheClapperFac- ingRetainerfromtheClappersothat theClapperFacingcanberemoved andinspected.Makesurethatthe ClapperFacingdoesnotshowsignsof compressionset,damage,etc.Re- placetheClapperFacingifthereisany signsofwear. Step4.CleantheClapperFacing, Clapper,andClapperFacingRetainer, andthenreassembletheClapperAs- sembly. Step5.ReinstalltheClapperAssem- blywithitsHingePinandthenreinstall theHandholeCover. Limited Warranty ProductsmanufacturedbyTycoFire& BuildingProducts(TFBP)arewar- rantedsolelytotheoriginalBuyerfor ten(10)yearsagainstdefectsinmate- rialandworkmanshipwhenpaidfor andproperlyinstalledandmaintained undernormaluseandservice.This warrantywillexpireten(10)years fromdateofshipmentbyTFBP.No warrantyisgivenforproductsorcom- ponentsmanufacturedbycompanies notaffiliatedbyownershipwithTFBP orforproductsandcomponentswhich havebeensubjecttomisuse,improper installation,corrosion,orwhichhave notbeeninstalled,maintained,modi- fiedorrepairedinaccordancewithap- plicableStandardsoftheNationalFire ProtectionAssociation,and/orthe standardsofanyotherAuthorities HavingJurisdiction.Materialsfound byTFBPtobedefectiveshallbeeither repairedorreplaced,atTFBP’ssole option.TFBPneitherassumes,nor authorizesanypersontoassumeforit, anyotherobligationinconnectionwith thesaleofproductsorpartsofprod- ucts.TFBPshallnotberesponsiblefor sprinklersystemdesignerrorsorinac- curateorincompleteinformationsup- pliedbyBuyerorBuyer’srepre- sentatives. InnoeventshallTFBPbeliable,in contract,tort,strictliabilityorunder anyotherlegaltheory,forincidental, indirect,specialorconsequentialdam- ages,includingbutnotlimitedtolabor charges,regardlessofwhetherTFBP wasinformedaboutthepossibilityof suchdamages,andinnoeventshall TFBP’sliabilityexceedanamount equaltothesalesprice. Theforegoingwarrantyismadeinlieu ofanyandallotherwarranties,ex- pressorimplied,includingwarranties ofmerchantabilityandfitnessforapar- ticularpurpose. Thislimitedwarrantysetsforththeex- clusiveremedyforclaimsbasedon failureofordefectinproducts,materi- alsorcomponents,whethertheclaim ismadeincontract,tort,strictliability oranyotherlegaltheory. Thiswarrantywillapplytothefullex- tentpermittedbylaw.Theinvalidity,in wholeorpart,ofanyportionofthis warrantywillnotaffecttheremainder. Page18of20 TFP1020 Ordering Procedure NOTE RefertoTableAforFlangeDrilling Specifications. PartNumbersforfactorypre-trimmed ModelDPV-1Valvesareprovidedin thePriceBook. StandardDPV-1DryPipeValve (AmericanStandardFlange Drilling,ThreadedPorts,and GrooveOutsideDiameter,asappli- cable): Specify:(specifysize)ModelDPV-1 DryPipeValvewith(specifyinletx outlet)endconnections,P/N(specify). 2-1/2Inch(DN65) GxG, 2.88inch(73,1 mm)O.D. Groovex2.88 inch(73,1mm) O.D.Groove...........P/N52-310-1-925 3Inch(DN80) GxG, 3.50inch(88,9 mm)O.D. Groovex3.50 inch(88,9mm) O.D.Groove...........P/N52-310-1-930 4Inch(DN100) GxG, 4.50inch(114,3 mm)O.D. Groovex4.50 inch(114,3mm) O.D.Groove...........P/N52-310-1-940 FxG, ANSIDrilled Flangex4.50 inch(114,3mm) O.D.Groove...........P/N52-310-1-440 FxF, ANSIDrilled FlangexANSI DrilledFlanged.........P/N52-310-1-040 6Inch(DN150) GxG, 6.62inch(168,3 mm)O.D. Groovex6.62 inch(168,3mm) O.D.Groove...........P/N52-310-1-960 FxG, ANSIDrilled Flangex6.62 inch(168,3mm) O.D.Groove...........P/N52-310-1-460 FxF, ANSIDrilled FlangexANSI DrilledFlanged.........P/N52-310-1-060 StandardGalvanizedDPV-1Trim (Ref.FigureF): Specify:2-1/2and3InchDPV-1Semi- PreassembledGalvanizedTrim, P/N52-309-2-005. Specify:4InchDPV-1Semi-Preas- sembledGalvanizedTrim, P/N52-309-2-001. Specify:6InchDPV-1Semi-Preas- sembledGalvanizedTrim, P/N52-309-2-002. OptionalAccelerator: ModelQRSElectronic Accelerator (DetailsprovidedinTFP1100) Specify:ModelQRSElectronicDry PipeValveAcceleratorPackage, P/N52-312-2-101. ModelACC-1Mechanical Accelerator (DetailsprovidedinTFP1112) Specify:ModelACC-1DryPipeAc- celerator,P/N52-311-1-001,and GalvanizedAcceleratorTrimfor ModelDPV-1DryPipeValve, P/N52-311-2-010. Optional600PSIWaterPressure Gauge: Specify:600PSIWaterPressure Gauge,P/N92-343-1-004. Accessories: OrdertheTechnicalDataSheetsfor thefollowing,asapplicable,fordetails andadditionalaccessories: ModelPS10-2A PotterElectric Waterflow PressureAlarm Switch................P/N54-281-1-002 ModelWMA1 WaterMotor Alarm................P/N52-630-1-001 ModelAMD-1 AirMaintenance Device................P/N52-324-2-002 ModelAMD-2 AirMaintenance Device................P/N52-326-2-001 ModelAMD-3 Nitrogen MaintenanceDe- vice..................P/N52-328-2-001 ReplacementValveParts: Specify:(description)forusewith (specifysize)ModelDPV-1DryPipe Valve,P/N(seeFigure1Aand1B). ReplacementTrimParts: Specify:(description)forusewith (specifysize)ModelDPV-1DryPipe Valve,P/N(seeFigure4,5,or6,as applicable). Weights: Thefollowingarethenominalweightsfor thevalvesandtrim: 2-1/2Inch(DN65) ModelDPV-1 GxGDryPipeValve.........37lbs.(17kg) 3Inch(DN80) ModelDPV-1 GxGDryPipeValve.........38lbs.(18kg) 2-1/2&3Inch(DN65/80)ValveTrim ...........................23lbs.(11kg) 4Inch(DN100) ModelDPV-1 GxGDryPipeValve.........57lbs.(26kg) 4Inch(DN100) ModelDPV-1 FxGDryPipeValve..........67lbs.(31kg) 4Inch(DN100) ModelDPV-1 FxFDryPipeValve..........77lbs.(36kg) 4Inch(DN100)ValveTrim......30lbs.(14kg) 6Inch(DN150) ModelDPV-1 GxGDryPipeValve..........95lbs.(44kg) 6Inch(DN150) ModelDPV-1 FxGDryPipeValve..........108lbs.(50kg) 6Inch(DN150) ModelDPV-1 FxFDryPipeValve..........121lbs.(56kg) 6Inch(DN150)ValveTrim......30lbs.(14kg) OtherDPV-1DryPipeValves: NOTES OtherDPV-1DryPipeValvesare valvesorderedwithaanycombination offlange,threadedports,orgroove outsidediameternotofferedunder “StandardDPV-1DryPipeValve”of- ferings. ValveswithNPTthreadedportsare intendedforusewiththe“Standard GalvanizedDPV-1ValveTrim”offered anddetailedinthisdocument.Valves withISOthreadedportsareintended forusewithspecialordertrimthatis providedbylocaldistributorstomeet thespecificneedsofcertainlocalities. Pleasecontactyourlocaldistributor regardingvalvesandvalvetrimfor specificlocalities. Specify:(specifysize)ModelDPV-1 DryPipeValvewith(specifyinletx outlet)connectionswith(specifyNPT orISO)threadedports,P/N(specify). Page19of20TFP1020 Page20of20 TFP1020 TYCOFIRE&BUILDINGPRODUCTS,451NorthCannonAvenue,Lansdale,Pennsylvania19446 PartNumbersForOther 4Inch(DN100)DryPipeValves: ValveswithNPTPorts FxG, ISOFlangex 4.50"(114,3 mm)Outside Dia.Groove...........P/N52-309-1-253 FxG, ASFlangex 4.50"(114,3 mm)Outside Dia.Groove...........P/N52-309-1-613 FxG, JISFlangex 4.50"(114,3 mm)Outside Dia.Groove...........P/N52-309-1-813 FxF, ISOFlangex ISOFlange............P/N52-309-1-133 FxF, ASFlangex ASFlange.............P/N52-309-1-513 FxF, JISFlangex JISFlange............P/N52-309-1-713 ValveswithISOPorts GxG, 4.50"(114,3 mm)Outside Dia.Groovex 4.50"(114,3 mm)Outside Dia.Groove...........P/N52-309-1-923 FxG, ISOFlangex 4.50"(114,3 mm)Outside Dia.Groove...........P/N52-309-1-213 FxF, ISOFlangex ISOFlange............P/N52-309-1-113 PartNumbersForOther 6Inch(DN150)DryPipeValves: ValveswithNPTPorts GxG, 6.50"(165,1 mm)Outside Dia.Groovex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-935 FxG, ANSIFlangex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-435 FxG, ISOFlangex 6.62"(168,3 mm)Outside Dia.Groove............P/N52-309-1-255 FxG, ISOFlangex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-335 FxG, ASFlangex 6.62"(168,3 mm)Outside Dia.Groove............P/N52-309-1-615 FxG, ASFlangex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-635 FxG, JISFlangex 6.62"(168,3 mm)Outside Dia.Groove............P/N52-309-1-815 FxG, JISFlangex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-835 FxF, ISOFlangex ISOFlange.............P/N52-309-1-135 FxF, ASFlangex ASFlange.............P/N52-309-1-515 FxF, JISFlangex JISFlange.............P/N52-309-1-715 ValveswithISOPorts GxG, 6.62"(168,3 mm)Outside Dia.Groovex 6.62"(168,3 mm)Outside Dia.Groove............P/N52-309-1-925 GxG, 6.50"(165,1 mm)Outside Dia.Groovex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-945 FxG, ISOFlangex 6.62"(168,3 mm)Outside Dia.Groove............P/N52-309-1-215 FxG, ISOFlangex 6.50"(165,1 mm)Outside Dia.Groove............P/N52-309-1-315 FxF, ISOFlangex ISOFlange.............P/N52-309-1-115 PartNumbersForOther 2-1/2Inch(DN65)DryPipe Valves: ValveswithNPTPorts GxG, 3.00"(76,1 mm)Outside Dia.Groovex 3.00"(76,1 mm)Outside Dia.Groove............P/N52-309-1-930 ValveswithISOPorts GxG, 2.88"(73,0 mm)Outside Dia.Groovex 2.88"(73,0 mm)Outside Dia.Groove............P/N52-309-1-920 GxG, 3.00"(76,1 mm)Outside Dia.Groovex 3.00"(76,1 mm)Outside Dia.Groove............P/N52-309-1-940 PartNumbersForOther 3Inch(DN80)DryPipeValves: ValveswithISOPorts GxG, 3.50"(88,9 mm)Outside Dia.Groovex 3.50"(88,9 mm)Outside Dia.Groove............P/N52-309-1-922 RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Pendent Wet Pipe and Dry Pipe Systems Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fi re.com Page 1 of 8 APRIL 2012 TFP400 General Description The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are deco- rative, fast response, frangible bulb sprinklers designed for use in residen- tial occupancies such as homes, apart- ments, dormitories, and hotels. When aesthetics and optimized fl ow charac- teristics are the major consideration, the Series LFII Residential Sprinklers (TY2234) should be the fi rst choice. The Series LFII Residential Sprinklers are intended for use in the following scenarios: • wet and dry pipe residential sprin- kler systems for one- and two-family dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with fi nished ceilings. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the fl ush ceiling position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. The Series LFII Residential Sprinklers have been designed with heat sensi- tivity and water distribution charac- teristics proven to help in the control of residential fi res and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application The Series LFII Residential Pendent and Recessed Pendent Sprinklers offers a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are laboratory approved for wet systems only. Through extensive testing and as refer- enced in U.S. Patent 7,712,543, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) need not be increased over the number of design sprinklers (hydraulic design area) as specifi ed for wet pipe sprinkler systems, as is accustomed for density/ area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residential Sprinklers offer the features of non-water fi lled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. Non-water fi lled pipe will permit options for areas sensitive to freezing. NOTICE The Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) described herein must be installed and maintained in compliance with this document and the applicable stan- dards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the perfor- mance of these devices. IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fi re situation or cause it to operate prematurely. The owner is responsible for main- taining their fi re protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identifi cation Number (SIN) TY2234 TFP400 Page 2 of 8 SURFACE ESCUTCHEON PLATE SEATING 1-5/8" (41,3 mm) -2Button Temperature rating is indicated on Deflector. Deflector Compression Screw Bulb Sealing Assembly -6 * -4 5 - 3 - * * 6 4 5 1 3 2 Components: Frame1- 1/2" NPT 7/16" (11,1 mm) MAKE-IN NOMINAL ESCUTCHEON STYLE 20 RECESSEDWRENCH (57,2 mm) 2-1/4" FLATS (73,0 mm) 2-7/8" DIA. CROSS SECTIONPENDENTRECESSED PENDENT FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) TY2234 2-7/8" DIA. (73,0 mm) (57,2 mm) 2-1/4" DIA. MOUNTING SPRINKLER CLOSURE SURFACE FITTING FACE OF (11,1±3,2 mm) 7/16±1/8" MOUNTING PLATE 1-3/8" (34,9 mm) 1-1/8" (28,6 mm) (3,2 mm) 1/8" 1/2" (12,7 mm) 1/4" (6,4 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER (TY2234) WRENCH RECESS (END "A" USED FOR TY2234) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH RECESS WRENCH WITH SPRINKLER ENGAGEMENT IN TO ENSURE WRENCHING AREA PUSH WRENCH TFP400 Page 3 of 8 Dry Pipe System Water Delivery When using the Series LFII Residential Sprinklers (TY2234) in dry pipe sprin- kler systems, the time for water delivery must not exceed 15 seconds for the most remote operating sprinkler. Obstruction to Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as appli- cable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity For "Horizontal Ceilings" (maximum 2 inch rise for 12 inch run), the sprin- klers are to be installed with a defl ector- to-ceiling distance of 1-3/8 to 4 inches or in the recessed position using only the Style 20 Recessed Escutcheon as shown in Figure 2. The “Beam Ceiling Design Criteria” section permits defl ector-to-ceiling distances up to 15-3/4 inches. For "Sloped Ceilings" (greater than 2 inch rise up to 8 inch rise for 12 inch run), the sprinklers are to be installed with a defl ector-to-ceiling distance of 1-3/8 to 4 inches or in the recessed position using only the Style 20 Recessed Escutcheon as shown in Figure 2. Sprinkler Spacing The minimum spacing between sprin- klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x 20 ft. coverage area). Technical Data Approvals UL Listed for use with wet pipe and dry pipe systems C-UL Listed for use only with wet pipe systems For details on these approvals, refer to the Design Criteria section. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coeffi cient K=4.9 GPM/psi1/2 (70,6 LPM/bar1/2) Temperature Rating 155°F (68°C) or 175°F (79°C) Finishes White Polyester Coated Chrome Plated Natural Brass Physical Characteristics Frame . . . . . . . . . . . . . . . . . . . .Brass Button . . . . . . . . . . . . . . . . . . .Bronze Sealing Assembly . . . . . . . . Beryllium Nickel w/TEFLON Bulb (3 mm) . . . . . . . . . . . . . . . . Glass Compression Screw . . . . . . . .Bronze Defl ector . . . . . . . . . . . . . . . . .Bronze Ejection Spring . . . . . .Stainless Steel Operation The glass Bulb contains a fl uid that expands when exposed to heat. When the rated temperature is reached, the fl uid expands suffi ciently to shatter the glass Bulb, allowing the sprinkler to activate and fl ow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are UL and C-UL Listed for installation in accordance with this section: Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer’s recommendations that may be acceptable to the local authority having jurisdiction. System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of residential sprinklers in residential dry pipe systems. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum re quired sprinkler fl ow rates are given in Tables A and B as a func- tion of temperature rating and the maximum allowable coverage areas. The sprinkler fl ow rate is the minimum required discharge from each of the total number of “design sprinklers” as specifi ed in NFPA 13D or NFPA 13R. The number of “design sprinklers” specifi ed in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The fl ow rates given in Tables A or B as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the “design area” comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. The number of “design sprinklers” specifi ed in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. TFP400 Page 4 of 8 Maximum Coverage Area (a) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow and Residual Pressure (b) For Horizontal Ceiling (c, d, e) (Maximum 2 Inch Rise for 12 Inch Run) For Sloped Ceiling (c, d, e) (Greater than 2 Inch Rise up to Maximum 4 Inch Rise for 12 Inch Run) For Sloped Ceiling (c, d, e) (Greater than 4 Inch Rise up to Maximum 8 Inch Rise for 12 Inch Run) 155°F (68°C) or 175°F (79°C) 155°F (68°C)175°F (79°C) 155°F (68°C)175°F (79°C) 12 x 12 (3,7 x 3,7) 12 (3,7) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 17 GPM (64,3 LPM) 12.0 psi (0,83 bar) 20 x 20 (6,1 x 6,1) 20 (6,1) 20 GPM (75,7 LPM) 16.7 psi (1,15 bar) 20 GPM (75,7 LPM) 16.7 psi (1,15 bar) 20 GPM (75,7 LPM) 16.7 psi (1,15 bar) 21 GPM (79,5 LPM) 18.4 psi (1,27 bar) 22 GPM (83,3 LPM) 20.2 psi (1,39 bar) (a) For coverage area dimensions less than or between those indicated, use the minimum required fl ow for the next highest coverage area for which hydraulic design criteria are stated. (b) The Minimum Flow requirement is based on minimum fl ow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13D 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped ceiling confi gurations up to 8:12 pitch. Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontal ceiling criteria. (d) For NFPA 13R applications, Horizontal Ceiling criteria may be used for sloped ceiling confi gurations up to 8:12 pitch when acceptable to the local authority having jurisdiction. (e) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area or the fl ow in accordance with the criteria in this table must be used. TABLE A SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS Maximum Coverage Area (a) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) DRY PIPE SYSTEM Minimum Flow and Residual Pressure (b) For Horizontal Ceiling (Maximum 2 Inch Rise for 12 Inch Run) 155°F (68°C)175°F (79°C) 12 x 12 (3,7 x 3,7) 12 (3,7) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 13 GPM (49,2 LPM) 7.0 psi (0,48 bar) 14 x 14 (4,3 x 4,3) 14 (4,3) 14 GPM (53,0 LPM) 8.2 psi (0,57 bar) 14 GPM (53,0 LPM) 8.2 psi (0,57 bar) 16 x 16 (4,9 x 4,9) 16 (4,9) 15 GPM (56,8 LPM) 9.4 psi (0,65 bar) 15 GPM (56,8 LPM) 9.4 psi (0,65 bar) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 GPM (68,1 LPM) 13.5 psi (0,93 bar) 18 GPM (68,1 LPM) 13.5 psi (0,93 bar) 20 x 20 (6,1 x 6,1) 20 (6,1) 21 GPM (79,5 LPM) 18.4 psi (1,27 bar) 21 GPM (79,5 LPM) 18.4 psi (1,27 bar) (a) For coverage area dimensions less than or between those indicated, use the minimum required fl ow for the next highest coverage area for which hydraulic design criteria are stated. (b) The Minimum Flow requirement is based on minimum fl ow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. TABLE B SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEMS TFP400 Page 5 of 8 Beam Ceiling Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are UL and C-UL Listed for installation in wet pipe systems only for residential occu- pancies with horizontal ceilings (that is, slopes up to a 2 inch rise over a 12 inch run) with beams when installed in accordance with this section: General Information The basic concept of this protection scheme is to locate the sprinklers on the underside of the beams, refer Figure 5, (not in the beam pockets); to identify the main beams that princi- pally run in one direction as “primary beams”; and, to identify the beams that run principally perpendicular to the main beams, as may be present (or in some cases may be necessary for proper sprinkler protection), as “secondary beams”. Primary and Secondary Beam Types Solid surface, solid or hollow core, combustible or non-combustible. Primary and Secondary Beam Positioning Directly attached to the underside of a combustible or non-combustible smooth ceiling at any elevation. Primary Beam Cross-Section Maximum depth of 14 inches and the maximum width is unlimited. The cross- sectional shape of the primary beam may be rectangular to circular. Secondary Beam Cross-Section Maximum depth to be no greater than the primary beam and the maximum width is unlimited. The cross-sectional shape of the secondary beam may be rectangular to circular. Primary Beam Spacing The primary beams (Figure 6A) are to be 3 ft.-4 in. to 6 ft. from the compart- ment wall to center of the nearest beam and from center to center between beams. Secondary Beam Spacing The secondary beams principally run perpendicular to the primary beams. Secondary beams of a depth equal to the primary beam must be placed so that the beam pockets created by the primary beams do not exceed 20 feet in length (Figure 6B). When the beam pockets created by the primary beams exceed 20 feet in length, the installation will require the use of secondary beams as described above. Otherwise, secondary beams need not be present. Secondary beams of a cross-sectional depth greater than one-quarter the depth of the primary beams are to be a minimum of 3 ft - 4 in from the compart- ment wall to center of the nearest beam and from center to center between beams (Figure 6C). Secondary beams of a cross-sectional depth no greater than one-quarter the depth of the primary beams may be placed at any compartment wall to center of the nearest beam distance and from any center to center distance between beams (Figure 6C). Lintels Lintels over doorways exiting the compartment must be present. The minimum height for the lintels is 8 inches or no less than the depth of the Primary Beams, whichever is greater. Sprinkler Types Series LFII Pendent and Recessed Pendent Residential Sprinklers (TY2234), 155°F (68°C) and 175°F (79°C). Sprinkler Coverage Area and Hydraulic Design The sprinkler coverage areas and hydraulic design criteria as presented in the Table A for “Horizontal Ceilings” are to be applied. Sprinkler Position The defl ector to bottom of primary beams for the Series LFII Pendent and Recessed Pendent Sprinklers (TY2234) is to be 1-1/4 to 1-3/4 inches (Figure 5A). The vertical centerline of the Series LFII Pendent Sprinklers is to be no greater than half the primary beam cross-sectional width plus 2 inches from the centerline of the primary beam (Figure 5B). NOTICE Core drilling of beams to allow the installation of sprinkler drops requires consulting with a structural engineer. Where core drilling is not permitted, the previously stated sprinkler position criteria for the Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) allows placement of the sprinkler drop adjacent to the primary beam. Beam and Soffi t Arrangements A soffi t is permitted to be placed around the perimeter of a compart- ment with the beam arrangement within the soffi t area (Figure 7). The cross-section of the soffi t may be any size as long as it does not create an obstruction to water distribution per the obstruction rules of NFPA 13 for residential sprinklers. When soffi ts are present, the previ- ously provided 3 ft.-4 in. to 6 ft. “compartment wall to adjacent beam” distance for the primary and secondary beams is to be measured from the face of the soffi t as opposed to the compartment wall. Although the distance to the beams is measured from the face of the soffi t, the sprinkler coverage area is to be measured from the compart- ment wall. TY2234 1- 3 / 4 " ( 4 4 , 5 m m ) M A X . 1- 1 / 4 " ( 3 1 , 8 m m ) M I N . ONE-HALF BEAM WIDTH PLUS MAXIMUM 2" (50,8 mm) TY2234 1- 3 / 4 " ( 4 4 , 5 m m ) M A X . 1- 1 / 4 " ( 3 1 , 8 m m ) M I N . A B FIGURE 5 SPRINKLER POSITIONING UNDER PRIMARY BEAMS WET PIPE SYSTEMS ONLY (Refer to the “Beam Ceiling Design Criteria” section.) TFP400 Page 6 of 8 AAA PRIMARY BEAM SPANS UP TO 20'-0" (6,1 m) PRIMARY BEAM SPANS GREATER THAN 20'-0" (6,1 m) COMBINATIONS OF PRIMARY AND SECONDARY BEAMS B B C C FOR SECONDARY BEAMS THAT ARE TO BE EQUAL IN DEPTH TO PRIMARY BEAMS AND THAT MUST BE IN PLACE SO THAT PRIMARY BEAM POCKETS DO NOT EXCEED 20'-0" (6,1 m) SECONDARY BEAMS HAVING DEPTHS GREATER THAN 25% OF PRIMARY BEAMS B = 20'-0" (6,1 m) MAXIMUM C = 3'-4" (1,0 m) MINIMUM FOR or A = 3'-4" to 6'-0" (1,0 to 1,8 m) FOR PRIMARY BEAMS HAV- DEPTH ING A 14" (356 mm) MAXIMUM ONDARY BEAMS HAVING DEPTHS UP TO 25% OF PRIMARY BEAMS C = ANY DISTANCE FOR SEC- A = 3'-4" to 6'-0" (1,0 to 1,8 m) FOR PRIMARY BEAMS HAV- DEPTH ING A 14" (356 mm) MAXIMUM A = 3'-4" to 6'-0" (1,0 to 1,8 m) FOR PRIMARY BEAMS HAV- DEPTH ING A 14" (356 mm) MAXIMUM MAXIMUM 14" (356 mm) 20'-0" (6,1 m) MAXIMUM REFER TO FOR SPANS FIGURE 6B 20'-0" (6,1 m) EXCEEDING PRIMARY BEAM DISTANCES ARE COMPARTMENT TO CENTERLINES OF BEAMS WALL FACES AND MEASURED TO SECONDARY BEAM ALL FIGURES: COMPARTMENT WALLS PRIMARY BEAM COMPARTMENT WALLS AAA AAA SECONDARY BEAM PRIMARY BEAM COMPARTMENT WALLS FIGURE 6A FIGURE 6B FIGURE 6C * * FIGURE 6 BEAM ARRANGEMENTS WET PIPE SYSTEMS ONLY (Refer to the “Beam Ceiling Design Criteria” section.) TFP400 Page 7 of 8 SOFFIT FACE OF COMPARTMENT WALLS SECONDARY BEAM PRIMARY BEAM IN FIGURES 6A, 6B & 6C, EXCEPT MEASUREMENTS ARE TAKEN FROM FACES OF SOFFITS INSTEAD OF FROM COMPARTMENT WALL SURFACES USE DISTANCES SHOWN * * * FIGURE 7 BEAM AND SOFFIT ARRANGEMENTS WET PIPE SYSTEMS ONLY (Refer to the “Beam Ceiling Design Criteria” section.) Installation The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) must be installed in accor- dance with this section: General Instructions Do not install any bulb type sprin- kler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diam- eter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprin- kler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insuffi cient adjustment in an Escutcheon Plate by under- or over- tightening the sprinkler. Re-adjust the position of the sprinkler fi tting to suit. Series LFII Residential Pendent Sprinklers The Series LFII Residential Pendent Sprinklers must be installed in accor- dance with the following instructions. Step 1. Install pendent sprinklers in the pendent position with the defl ector parallel to the ceiling. Step 2. With pipe thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fi tting. Step 3. Tighten the sprinkler into the sprinkler fi tting using only the W-Type 6 Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench fl ats. Series LFII Residential Recessed Pendent Sprinklers The Series LFII Residential Recessed Pendent Sprinklers must be installed in accordance with the following instructions. Step A. Install recessed pendent sprinklers in the pendent position with the defl ector parallel to the ceiling. Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fi tting. Step C. Tighten the sprinkler into the sprinkler fi tting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 4). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench fl ats. Step D. After the ceiling has been installed or the fi nish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its fl ange comes in contact with the ceiling. TFP400 Page 8 of 8 Copyright © 2012 Tyco Fire Protection Products. All rights reserved. TEFLON is trademark of The DuPont Corporation. Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) must be maintained and serviced in accordance with this section: Before closing a fi re protection system main control valve for maintenance work on the fi re protection system that it controls, permission to shut down the affected fi re protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fi re situation. The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; other- wise, non-operation in the event of a fi re or inadvertent operation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modifi ed sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and mainte- nance of their fi re protection system and devices in compliance with this document, as well as with the appli- cable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualifi ed Inspection Service in accordance with local requirements and/or national codes. Limited Warranty Products manufactured by Tyco Fire Protection Products (TFPP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFPP. No warranty is given for products or components manufac- tured by companies not affi liated by ownership with TFPP or for products and components which have been subject to misuse, improper instal- lation, corrosion, or which have not been installed, maintained, modifi ed or repaired in accordance with appli- cable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFPP to be defective shall be either repaired or replaced, at TFPP’s sole option. TFPP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFPP shall not be respon- sible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. In no event shall TFPP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFPP was informed about the possi- bility of such damages, and in no event shall TFPP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warran- ties of merchantability and fi tness for a particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, mate- rials or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assembly Specify: Series LFII (TY2234), K=4.9, Residential Pendent Sprinkler with (specify) temperature rating and (specify) fi nish, P/N (specify). 155°F (68°C) or Chrome Plated . . . . . . . . . . . . P/N 51-201-9-155 155°F (68°C) White Polyester . . . . . . . . . . . . P/N 51-201-4-155 155°F (68°C) White (RAL9010)* . . . . . . . . . . . . . . . . P/N 51-201-3-155 155°F (68°C) Natural Brass . . . . . . . . . . . . . . P/N 51-201-1-155 175°F (79°C) or Chrome Plated . . . . . . . . . . . . P/N 51-201-9-175 175°F (79°C) White Polyester . . . . . . . . . . . . P/N 51-201-4-175 175°F (79°C) White (RAL9010)* . . . . . . . . . . . . . . . . P/N 51-201-3-175 175°F (79°C) Natural Brass . . . . . . . . . . . . . . P/N 51-201-1-175 *Eastern Hemisphere sales only. Recessed Escutcheon Specify: Style 20 Recessed Escutcheon with (specify*) fi nish, P/N (specify*). *Refer to Technical Data Sheet TFP770. Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. PAGE 1 OF 4MKT. #8820004 - REV P 12/01 PRINTED IN USA OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH UL and CSFM Listed, FM Approved, NYMEA Accepted, CE Marked Dimensions: 6.19"L X 2.25"W X 5.88"H 15,7cm L X 5,7cm W X 14,6cm H Weight: 2 lbs. (0,9 kg.) Enclosure: Cover - Die-Cast Finish - Red Spatter Enamel Base - Die Cast Zinc All parts have corrosion resistant fi nishes. Cover Tamper: Tamper resistant screws, Optional cover tamper kit available. Contact Ratings: OSYSU-1: One set of SPDT (Form C) OSYSU-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Limitations: • NEMA 4 and NEMA 6P Enclosure (IP67) when used with appropriate watertight conduit fi ttings. • Indoor or Outdoor use (Not for use in hazardous locations. See bulletin no. 5400705 OSYS-U-EX for hazardous locations.) • Temperature Range: -40°F to 140°F (-40°C to 60°C) Conduit Entrances: 2 knockouts for 1/2" conduit provided Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 OPTIONAL COVER TAMPER SWITCH A fi eld installable cover tamper switch is available as an option which may be used to indicate removal of the cover. See ordering information on page 4. TESTING The OSYSU and its associated protective monitoring system should be inspected and tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). GENERAL INFORMATION The OSYSU is used to monitor the open position of an OS & Y (outside screw and yoke) type gate valve. This device is available in two models; the OSYSU-1, containing one set of SPDT (Form C) contacts and the OSYSU-2, containing two sets of SPDT (Form C) contacts. These switches mount conveniently to most OS & Y valves ranging in size from 2" to 12" (50mm to 300mm). They will mount on some valves as small as 1/2" (12,5mm). The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or additional cover screws and hex keys are available. See ordering information on page 4. OSYSU-1 Stock No. 1010106 OSYSU-2 Stock No. 1010206 Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PAGE 2 OF 4MKT. #8820004 - REV P 12/01 PRINTED IN USA OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG. 1 SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" (12,5mm THRU 63,5mm) SIZES THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME VALVES AS SMALL AS 1/2" (12,5MM). J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE. 6. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered on the mark on the valve stem utilizing a 3/16" (4,8mm) round, non-tapered fi le. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. 7. Mount the OSYSU with the trip rod centered in groove. 8. Final adjustment is made by loosening 2 screws (see Fig. 1) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate when the trip rod moves out of the groove. 9. Tighten the adjustment screws and all mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION. SMALL VALVE INSTALLATION 1. Remove and discard "C" washer and roller from the trip rod. 2. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non-threaded portion of the valve stem. 3. Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the 1" (25mm) long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. 4. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. On valves with limited clearance use J-hooks supplied instead of the carriage bolts and clamp bar to mount the OSYSU. 5. Mark the valve stem at the center of the trip rod. PAGE 3 OF 4MKT. #8820004 - REV P 12/01 PRINTED IN USA OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG. 2 LARGE VALVE INSTALLATION - 3" THRU 12" (76mm THRU 300mm) SIZES LARGE VALVE INSTALLATION 1. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non-threaded portion of the valve stem. 2. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. 3. Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one 1" (25mm) long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. 4. Mark the valve stem at the center of the trip rod. 5. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered on the mark of the valve stem utilizing a 3/8" (9,5mm) round, non-tapered fi le. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. 6. Mount the OSYSU loosely with the trip rod centered in groove. 7. Final adjustment is made by loosening 2 screws (see Fig. 2) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. 8. Tighten the adjustment screws and mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION. PAGE 4 OF 4MKT. #8820004 - REV P 12/01 PRINTED IN USA OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH TYPICAL SWITCH ACTION Contacts shown in normal (valve open) condition. FIG. 3 DIMENSIONS FIG. 4 PARTS BREAKING EXCESSIVE ROD LENGTH SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL TYPICAL ELECTRICAL CONNECTIONS ORDERING INFORMATION MODEL DESCRIPTION STOCK NO. OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106 OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206 -- Cover Screw 5490344 -- Hex Key for Cover Screws and Installation Adjustments 5250062 -- Optional Cover Tamper Switch Kit 0090131 For pressure reducer type valve installation kits (if required) contact valve manufacturer. CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. FIG. 5 4 For the most up to date information, visit www.sammysuperscrew.com Wood Flooring Wood Joist Double Sheetrock Ceiling Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs)UL Test Load (lbs)FM Test Load (lbs)Box Qty CaseQty 1/4"8002957 GST 100 1/4 x 1"210 (7/16” OSB)670 (3/4” Ply)25 125 1/4"8003957 GST 200 1/4 x 2"1760 (Fir)25 125 1/4"8004957 GST 300 1/4 x 3"2060 (Fir)25 125 3/8"8006957 GST .75 1/4 x 3/4"564 (3/4" Ply)25 125 3/8"8007957 GST 10 1/4 x 1"210 (7/16” OSB)670 (3/4” Ply)300 25 125 3/8"8008957 GST 20 1/4 x 2"1760 (Fir)850 1475 25 125 3/8"8068925 GST 20-SS 1/4 x 2"1760 (Fir)850 25 125 3/8"8009925 GST 25-380 3/8 x 2-1/2"2113 (Fir)1500 25 125 3/8"8010957 GST 30 1/4 x 3"2060 (Fir)1500 1475 25 125 3/8"8069925 GST 30-SS 1/4 x 3"2060 (Fir)25 125 3/8"8011925 GST 40 1/4 x 4"2180 (Fir)25 125 3/8"8012925 GST 60 1/4 x 6"2230 (Fir)25 125 1/2"8013925 GST 2 1/4 x 2"1760 (Fir)25 125 1/2"8014925 GST 2.5-380 3/8 x 2-1/2"2113 (Fir)25 125 1/2"8015925 GST 3 1/4 x 3"2275 (Fir)25 125 1/2"8016925 GST 4 1/4 x 4"2180 (Fir)25 125 1/2"8017925 GST 6 1/4 x 6"2230 (Fir)25 125 Not less than2” nominal width (1-1/2”) Not less than 3” nominal thickness (2-1/2”) (depth or side of vertical member) VERTICAL MOUNT WO O D W O O D W O O D W O O D W O O D SAMMYS® for Wood Installs VERTICALLY into the bottom of wood structures easily and quickly! #14 Black Nut DriverPart # 8113910 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes intocontact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. #14 SW Red Nut Driver Part # 8114910 Composite / TrussConsult truss manufacturer for recommended installation point. *Pre-drilling may be required for GST 25-380 . Tool available on page 10. For vertical use - install in center of lower face. Minimum 2” embedment into base material for NFPA 13 compliance. Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs)UL Test Load (lbs)FM Test Load (lbs)Min Thickness Box Qty Case Qty 3/8"8139957 SH-GST 20 1/4 x 2"1257 (Fir)1050 1475 25 125 125 3/8"8141957 SH-GST 30 1/4 x 3"1720 (Fir)1500 1475 25 125 #14 Black Nut DriverPart # 8113910 SAMMY Swivel Head® for Wood Product Features • No pre-drilling required. • Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. • Saves time from traditional methods. • Reduces installation cost. • Made in the U.S.A. Product Features • Eliminates distortion of threaded rod. • Accommodates up to 3 ½” x 12 pitch roof. • Allows 17° deflection from vertical. • Saves time from traditional methods. • Reduces installation cost. • Made in the U.S.A. Installs VERTICALLY and swivels up to 17° in wood structure 5 To find a distributor near you, call 800-BUILDEX Not less than 2” nominal width (1-1/2”) up to 3-1/2” pipe; not less than 3” (2-1/2”) nominal width 4” & 5” pipe Minimum 2-1/2” from bottom for branch lines. Minimum 3” from bottom for main lines. Exception: This requirement shall not apply to 2” or thicker nailing strips resting on top of steel beams. Floor Joist HORIZONTAL MOUNT WO O D W O O D W O O D W O O D W O O D SIDEWINDERS® for Wood Installs HORIZONTALLY into the side of wood structures easily and quickly! Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs)UL Test Load (lbs)Box Qty Case Qty 1/4"8018957 SWG 100 1/4 x 1"622 (Fir)25 125 1/4"8019957 SWG 200 1/4 x 2"1725 (Fir)25 125 3/8"8020957 SWG 10 1/4 x 1"622 (Fir)300 25 125 3/8"8021957 SWG 20 1/4 x 2"1725 (Fir)1050 25 125 3/8"8073925 SWG 20-SS 1/4 x 2"1725 (Fir)850 25 125 3/8"8022925 SWG 25-380 3/8 x 2-1/2"2249 (Fir)1500 25 125 3/8"8023925 SWG 30 1/4 x 3"1884 (Fir)25 125#14 SW Red Nut Driver Part # 8114910 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. INSTALLATION STEPS - VERTICAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill. 2. Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill should be in a vertical position. 3. Push the face of the nut driver tight to the member. When the nut driver spins freely on the SAMMYS, stop drill and remove. 4. The SAMMYS is now ready to receive 1/4”, 3/8”, 1/2” or metric all thread rod, bolt stock. (The 1/2” requires the #14SW red nut driver) Note: When installing DSTR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximumpullout in purlin steel. INSTALLATION STEPS - HORIZONTAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill. 2. Insert the SAMMYS into the #14SW (red) nut driver (p/n 8114910). With drill unit in a horizontal position and at a right angle to the structural member, begin installation. 3. When the nut driver spins free on the SAMMYS, stop the drill and remove. 4. The unit is now ready to receive 1/4”, 3/8” or metric all thread rod or bolt stock. Note: When installing SWDR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. Composite/TrussConsult truss manufacturer for recommended installation point. *Pre-drilling may be required for Model SWG 25-380 (tools available on pg 10 ) Product Features • No pre-drilling required. • Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. • Saves time from traditional methods. • Reduces installation cost. • Made in the U.S.A. Installs VERTICALLY and swivels up to 17° in wood structure STAR SPRINKLER INC.A TYCO International Ltd. CompanyCD 3-3.1.10 Star Sprinkler Inc. • 7071 S. 13th Street • Suite 103 • Oak Creek, WI 53154 • (414) 570-5000 • (800) 558-5236 • FAX (414) 570-5010 Star CD technical data version 2.1, release 3/99. For further information contact Star Customer Service. S5 - 4 Schedule-10®/Schedule-40® Fully Listed and FM Approved Sprinkler Pipe When you specify Schedule-10/Schedule-40 sprinkler pipe you get UL listed and FM approved product. Although these products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand. Our Sch-10 (11⁄4" – 8") pipe and Sch-40 (1" – 21⁄2") pipe have passed the same thorough lab testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. Galvanized Pipe Schedule-10/Schedule-40 product can be “hot-dip” galvanized to meet FM. Superior Coating Our advanced formula mill coating offers a clean, durable surface. It is also paint- ready for custom color applications without special preparation. The internal surface of all black Fire Sprinkler pipe up to 4.5000” in diameter shall be coated with Allied Tube & Conduit Antibacterial Formula “ABF”. American Made Meets “Buy American” requirement and is available through distributors in the USA, Canada and Mexico. Specifications & Approvals Schedule-10/Schedule-40 pipe are in compliance with the following: ASTM A135 and NFPA 13. Both pipe products have a working pressure rating of 300 psi maximum and also meet the stringent requirement for the following tests: Welded Outlets, Hydrostatic Pressure, Side Wall Rupture, Vibration Test. Submittal Data Sheet Project: Engineer: Locations: Sprinkler Contractor: Specification Reference: Date: System Type: Comments: Stamp Here FM ListedApprovedListed American Tube and Pipe was acquired by Allied Tube and Conduit on February 1, 1997. The engineered lightwall and standard wall family of products although they have different names are the same in all respects with regard to strength, weight, bundle count, listings and approvals. For example, Dyna-Flow and Super Flo are the same product as are Dyna Thread and Super 40. XL is manufactured with Exterior galvanized coating. BLT is manufactured with Black lacquer coating. Sch-40 Specications NPSNominal I.D.Wt.Wt. (H2O Filled)Pcs/Wt/Lift (21')Wt/Lift (24')Wt/Lift (25') In; mmIn; mmLbs/Ft; Kg/mLbs/Ft; Kg/mLiftLbs; KgLbs; KgLbs; Kg 1"1.0491.6802.05702,4702,8222,940 2526.62.53.05701,1201,2801,334 11⁄4"1.3802.2702.93512,4312,7782,894 3235.14.364.36511,1031,2601,313 11⁄2"1.6102.7203.61442,5132,8722,992 4040.94.05.37441,1401,3031,357 2"2.0673.6505.13302,3002,6282,738 5052.55.47.63301,0431,1921,242 21⁄2"2.4695.7907.86192,3102,6402,750 6562.78.611.73191,0481,1971,247 Sch-10 Specications NPSNominal I.D.Wt.Wt. (H2O Filled)Pcs/Wt/Lift (21')Wt/Lift (24')Wt/Lift (25') In; mmIn; mmLbs/Ft; Kg/mLbs/Ft; Kg/mLiftLbs; KgLbs; KgLbs; Kg 1"1.0971.4001.81912,6753,0533,185 2527.92.12.70911,2131,3851,445 11⁄4"1.4421.8102.52612,3192,6642,760 3236.62.73.75611,0521,2081,252 11⁄2"1.6822.0803.04612,6643,0453,172 4042.73.14.52611,2081,3811,439 2"2.1572.6404.22372,0512,3442,442 5054.83.96.28379301,0631,108 21⁄2"2.6353.5305.89302,2242,5422,648 6566.95.38.77301,0091,1531,201 3"3.2604.3307.94191,7281,9752,057 8082.86.411.8219784896933 4"4.2605.61011.78192,2382,5582,665 90108.28.317.53191,0151,1601,209 5"5.2957.7717.33101,6321,8651,943 125134.511.5625.8010740846881 6"6.3579.29023.03101,9512,2302,322 150161.513.834.27108851,0121,053 8"8.24916.49040.1572,4242,7702,885 200209.524.559.7571,1001,2561,309 Michigan Hanger - ERICO 28 28 Model #112 One-Hole Strap for CPVC Pipe SIZE RANGE:3/4" thru 1" pipe MATERIAL:Pre-galvanized carbon steel LISTED BY: Underwriters Laboratories Inc. to U. S. and Canadian safety standards SERVICE: To support C.P.V.C. or Polybutalene fire sprinkler piping in horizontal position from top or side of beam, in Fire Sprinkler Systems installed per N. F. P. A. 13, 13R and 13D, with the hanger tab upward only*. Fasten with Hardened Hex Head Screw, #10 x 1”, supplied, needs no pre-drilling. Offset edge for abrasion prevention and added strength. ORDERING: Specify pipe size, model number and name. NOTE: *If installed inverted, with the hanger tab downward it does not function as a hanger, but as a restrainer. Do not install on the bottom of a beam or under horizontal surface. For these applications, see Model #108. Pipe Size CL OD Max. Hanger Spacing 3/4" 1" 1-1/4” 1-3/8” 1-11/16” 1-5/16” 5-1/2’ 6’ Model #115 Swivel Loop Hanger Heavy Duty (NFPA Rod Sizes) SIZE RANGE: 1/2" thru 8" pipe sizes MATERIAL: Pre-galvanized carbon steel with a zinc electroplate insert nut APPROVED BY: Factory Mutual LISTED BY: Underwriters Laboratories Inc. to U. S. and Canadian safety standards CONFORMS WITH: Federal Specification WW-H-171 (Type 10), Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10); install in accordance with ANSI/MSS-SP-69. SERVICE: Pipe support manufactured to use minimum rod sizes permitted by NFPA for fire sprinkler piping. ORDERING: Specify pipe size, model number and name. Pipe size H CL RS MRI A Max. recom. load lbs. 1/2" 3/4" 1" 3-1/8" 3-1/16" 3-3/16" 1-5/8" 1-1/2" 1-1/2" 3/8" 3/8" 3/8" 1" 1" 1" 1-1/4" 15/16" 15/16" 300 300 300 1-1/4" 1-1/2" 2" 3-1/2" 3-15/16" 4-1/2" 1-11/16" 1-15/16" 2-1/4" 3/8" 3/8" 3/8" 1" 1" 1" 7/8" 1" 1-1/16" 300 300 300 2-1/2" 3" 3-1/2" 5-15/16" 6-1/2" 7-1/16" 3-3/8" 3-5/8" 3-15/16" 3/8" 3/8" 3/8" 1" 1" 1" 1-1/2" 1-7/8" 1-7/8" 525 525 585 4" 5" 6" 8" 7-1/2" 8-15/16" 11-1/16" 12-7/8" 4-1/8" 4-13/16" 6-9/16" 7-3/8" 3/8" 1/2" 1/2" 1/2" 1" 1-1/4" 1-1/4" 1-1/4" 1-7/8" 2-3/16" 3-3/16" 3-1/16" 650 1000 1000 1000 Wrot and Cast Pressure Fittings NIBCO INC. World Headquarters n 1516 Middlebury St. n Elkhart, IN46516-4714 U.S.A. n www.nibco.com 11 n COUPLINGS continued 600-RS Coupling with Rolled Tube Stop C x C – Wrot APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES 1/8 O.D.0.01 1/16 3/16 O.D.0.01 3/32 1/80.01 1/16 5/16 O.D.0.01 3/32 1/40.01 1/16 3/80.01 3/32 1/20.03 3/32 5/80.04 3/32 3/40.06 3/32 7/80.09 3/32 10.11 3/32 1 1/40.16 1/8 1 1/20.23 1/8 20.41 1/8 2 1/20.65 1/8 30.93 1/8 3 1/21.45 5/32 41.93 7/32 §Made to Order.Consult price sheet for minimum order quantities. 601 Coupling without Stop C x C – Wrot APPROX.DIM.B NOM.SIZENET WT./LBS.INCHES §5/16 O.D.0.01 21/32 §1/40.01 11/16 §3/80.01 27/32 1/20.031 §5/80.04111/32 3/40.06119/32 10.11129/32 1 1/40.1621/16 1 1/20.2325/16 20.41213/16 2 1/20.64215/16 30.8635/16 §3 1/21.40313/16 41.8445/16 53.5055/16 65.6063/16 813.6883/32 701 Reducing Coupling C x C – Cast APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES 3 x 1 1/41.35 23/32 3 x 11.64 27/32 600-DS Coupling with Dimpled Tube Stop C x C – Wrot APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES 3/16 O.D.0.01 3/32 1/80.01 1/16 5/16 O.D.0.01 3/32 1/40.01 1/16 3/80.01 3/32 1/20.03 3/32 3/40.06 3/32 7/80.09 3/32 10.11 3/32 1 1/40.16 1/8 1 1/20.23 1/8 20.41 1/8 2 1/20.65 1/8 30.93 1/8 3 1/21.45 5/32 41.93 7/32 53.53 7/32 65.63 7/32 814.12 15/32 Wrot and Cast Pressure Fittings NIBCO INC. World Headquarters n 1516 Middlebury St. n Elkhart, IN46516-4714 U.S.A. n www.nibco.com 10 n CAPS continued 717 Tube Cap C – Cast APPROX.DIM.N NOM.SIZENET WT./LBS.INCHES 55.48 7/16 69.07 17/32 717-D Drain Cap – Cast APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES §1/2 0.06 21/32 §3/4 0.10 21/32 §10.16 11/16 n COUPLINGS §Made to Order.Consult price sheet for minimum order quantities. 600 Reducing Coupling C x C – Wrot APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES 1/8 x 3/16 O.D.0.01 5/32 5/16 O.D.x 1/80.01 3/16 1/4 x 5/16 O.D.0.01 3/16 1/4 x 1/80.01 3/16 3/8 x 1/40.02 3/16 §3/8 x 5/16 O.D.0.01 1/4 3/8 x 1/80.01 1/4 1/2 x 3/80.03 3/16 1/2 x 1/40.02 1/4 1/2 x 1/80.03 11/32 5/8 x 1/20.05 3/16 5/8 x 3/80.04 11/32 5/8 x 1/40.03 13/32 3/4 x 5/80.07 3/16 3/4 x 1/20.06 9/32 3/4 x 3/80.06 3/8 3/4 x 1/40.05 11/32 1 x 3/40.11 11/32 1 x 5/80.09 3/8 1 x 1/20.10 11/32 1 x 3/80.10 13/32 1 1/4 x 10.16 5/16 1 1/4 x 3/40.18 17/32 §1 1/4 x 5/80.18 5/8 1 1/4 x 1/20.14 7/16 1 1/2 x 1 1/40.23 5/16 1 1/2 x 10.22 9/16 1 1/2 x 3/40.20 3/8 1 1/2 x 1/20.19 1/2 2 x 1 1/20.41 9/16 2 x 1 1/40.35 11/16 2 x 10.37 7/16 2 x 3/40.34 17/32 2 x 1/20.35 23/32 2 1/2 x 20.59 9/16 2 1/2 x 1 1/20.65 11/16 2 1/2 x 1 1/40.65 13/16 2 1/2 x 10.73 29/32 Continues… APPROX.DIM.ANOM.SIZENET WT./LBS.INCHES 3 x 2 1/20.98 1/2 3 x 21.06 15/16 3 x 1 1/21.0411/32 3 1/2 x 31.52 1/2 §4 x 3 1/22.12 19/32 4 x 32.08 27/32 4 x 2 1/22.111 4 x 22.1611/4 5 x 43.50331/32 5 x 33.18115/32 5 x 2 1/23.50 13/16 5 x 23.0921/32 6 x 55.7011/8 6 x 45.2411/2 6 x 35.042 6 x 2 1/25.1321/4 6 x 24.8921/2 8 x 613.06119/32 8 x 412.22219/32 8 x 311.7933/32 8 x 2 1/212.6433/8 Wrot and Cast Pressure Fittings NIBCO INC. World Headquarters n 1516 Middlebury St. n Elkhart, IN46516-4714 U.S.A. n www.nibco.com 6 n ADAPTERS 603 Adapter C x F – Wrot APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES 1/8 0.03 13/32 1/8 x 1/40.03 1/2 1/40.03 5/8 1/4 x 3/80.05 21/32 3/80.04 11/16 3/8 x 1/20.09 29/32 3/8 x 1/40.03 9/16 1/20.09 27/32 1/2 x 3/40.141 1/2 x 3/80.04 17/32 1/2 x 1/4 0.05 1/2 5/8 x 3/40.12 29/32 5/8 x 1/20.11 3/4 3/40.15 29/32 3/4 x 10.2111/8 3/4 x 1/20.10 5/8 10.24 31/32 1 x 1 1/40.2817/32 1 x 3/40.19 25/32 1 x 1/20.24 5/8 1 1/40.3313/32 1 1/4 x 1 1/20.4011/4 1 1/4 x 10.27 31/32 1 1/20.4411/8 1 1/2 x 20.5011/32 20.6313/32 2 x 1 1/20.7413/16 2 1/21.13– 31.94– 703 Adapter C x F – Cast APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES §1/4 x 1/20.13 27/32 1/2 x 10.301 3/4 x 1 1/40.5511/8 §3/4 x 3/80.17 3/4 1 x 1 1/20.68 13/32 1 1/4 x 20.98 15/32 1 1/4 x 10.27 31/32 1 1/4 x 3/40.29 3/4 §1 1/4 x 1/20.33 3/4 1 1/2 x 20.7811/32 §1 1/2 x 10.37 25/32 1 1/2 x 1 1/40.4711/4 §2 x 1 1/40.76 27/32 2 1/21.6213/8 32.3411/2 44.0519/16 58.20115/16 613.5721/32 603-2 Fitting Adapter Ftg x F – Wrot APPROX.DIM.B NOM.SIZENET WT./LBS.INCHES §1/40.0313/32 §3/80.0613/16 1/20.0917/16 1/2 x 3/80.0511/4 3/4 0.13111/16 10.2721/32 1 1/4 0.3121/8 1 1/2 0.4325/16 20.61217/32 703-2 Fitting Adapter Ftg x F – Cast APPROX.DIM.B NOM.SIZENET WT./LBS.INCHES §1/2 x 3/40.1817/16 1/2 x 1/4 0.1117/32 3/4 x 1/2 0.1219/16 1 x 3/40.38131/32 1 x 1/2 0.1517/16 §2 1/21.65215/16 32.4731/4 §Made to Order.Consult price sheet for minimum order quantities. Call 1-800-345-8207 Fax: 610-524-8965 E-Mail: genairpro@generalairproducts.com Remember - You can find this sheet and more at www.GENERALAIRPRODUCTS.com Magnetic Line Starters - Thermal Overload Protection Single Phase 115V230V SizeModel 1/3 HP1 HP00 MG00A* Maximum 1 HP2 HP0 MGX0A* HP 2 HP3 HP1 MG01A* 3 HP5 HP1PMG15A* The LThe Leading Manufacturer of Air Compressors eading Manufacturer of Air Compressors for the Ffor the F ire Pire P rotection Industryrotection Industry OILLESSTANKMOUNTED COMPRESSORS for DryPipe Sprinkler Systems - Fully Automatic - Direct Drive - Air Intake Filter(s) - Oil Less Piston Compressor - ULListed Pressure Switch - Bubble Tight Air Check Valve - Permanently Lubricated Bearings System Capacity (gallons)** 110† 215† 335 425 610 900 1200‡ 60 Cycle Units - 50 Cycle Available, Consult Factory Model Number OL11016ACT OL21533ACT OL33550ACT OL42575ACT OL610V100ACT OL900V150ACT OL1200V200ACT Average CFM* 1.33 2.61 4.06 5.27 7.40 10.91 14.55 Motor H.P. 1/6 1/3 1/2 3/4 1 1 1/2 2 Min. Wire Size ++ 12 10 8 8 8 6 10 Dimensions L 33 33 33 33 33 38 38 W 11 11 11 14 14 17 17 H 23 23 24 25 25 32 32 Weight (lbs.) 100 102 114 110 124 175 180 Air Maintenance Device Part # AMD-1 The AMD-1 is used when compressed air is supplied through an existing factory air supply or when using tank mounted units. When Ordering a Magnetic Line Starter you must specify HP, Voltage and Phase that is supplied to the motor. Tank Capacity (gallons) 10 10 10 10 10 20 20 - A.S.M.E. Coded Tanks - 1/2” Outlet Connections - Thermal Overload Protection - Fills System to 40 PSI in 30 Minutes (NFPA13) OL SeriesOL Series * Average CFM is the average free air delivery from 0 to 40 PSIG. ++ Based on 100 foot run at weakest voltage. Consult Factory for longer or shorter runs. ** Based on 70 degree F system temp. For other conditions consult factory for pump up times. † - 115 volt only, ‡ - 230 volt only, all other units 115/230 volt. 3 Phase Units available - Consult Factory. BB-SC 100&S02 BBSC100_rev0.CDR MILWAUKEEVALVE 1 2-"/" Approvedby:NYCBoardofStds.&Appeals, Cal.#996-81-SM(175psi) 720-83-SA(350&500psi) D Theinformationpresentedonthissheetiscorrectatthetimeofpublication.Milwaukee Valvereservestherighttochangedesign,and/ormaterialspecificationswithoutnotice. Forthemostcurrentinformationaccess.www.milwaukeevalve.com 1 2- BRONZEBUTTERFLYVALVE ONE-PIECE,FULL-PORT 175PSI THREADEDENDS C US APPROVED MATERIALSLIST butterball SLOWCLOSE 1 2 3 4 5 6 PertainstoBB-SC100only. PertainstoBB-SCS02only. AREDIMENSIONSUSINGSCHEDULE40 PIPE AREDIMENSIONSUSINGSCHEDULE80 PIPE ISFLOWRESISTANCEEXPRESSEDIN EQUIVALENTLENGTHOFSCHEDULE40 PIPE ISTHEWRENCHMAKE-UPLENGTH M-40 M-80 N-40 W FEATURES Slowopeningandclosing -Signalsdiscmovement -FactoryorFieldinstallation -10Amp/115VAC-60Hz -0.5Amp/28VDC Quarterturnoperation WaterHammerelimination Optionalinternaltamperswitch (Indooruseonly). GroovedEndsAvailablein Sizes2”and2-1/2” “M" B “L" BUTTERFLYVALVE 76G2 OPEN R LISTED M L “K” (MAX ENTRY) “C"C 4-1/2” BB-SC100 Sizes1”,1-1/4”,1-1/2”,2”,2-1/2” W A 4-1/2” “C"C BUTTERFLYVALVE 76G2 OPEN R LISTED W A J D BB-SCS02 (IncludesSwitch) DIMENSIONS ALLDIMENSIONS-INCHES 2-1/2” 4.13 3.82 3.19 3.50 4.66 1.18 1.29 2.47 2.32 10.00 1.75 DIM A B C D J K L M-40 M-80 N-40 W 1 2 3 4 5 6 1” 2.13 3.16 1.56 1.72 4.16 .66 .83 1.10 .96 2.25 1.13 1-1/4” 2.63 3.31 1.94 2.11 4.16 .73 .90 1.38 1.28 2.00 1.25 1-1/2” 2.88 3.41 2.19 2.38 4.51 .73 .10 1.61 1.50 2.50 1.41 2” 3.25 3.63 2.75 3.07 4.76 .79 1.41 2.07 1.94 2.25 1.69 ValveSize 5 4 3 6 1 2 7 ITEMPARTMATERIALSASTMSPEC. 1 IndicatorIronF0008P 2 Housing 3 Body 4 HandleBrass ASTMB176UNS C85800 5 Disk StainlessSteel ASTMA276, Type304 6 DiskSeal EPDM 7 SwitchHousing (BB-SCS02)Aluminum Bronze ASTM584UNS C8440 Grinnell Grooved Fire Protection Products Grooved Fittings Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 www.tyco-fire.com September 2004 TFP1810Page 1 of 6 The grooved fittings provide an economical and efficient method of changing direction, adding an outlet, reducing, or capping grooved piping systems. Grooved fittings are available in durable ductile iron or fabricated steel as indicated. Note: Figure 510S and 519S fittings are special short radius fittings with smaller center to end dimensions than standard grooved fittings. Depending on the size and coupling used, there may be interferences at the bolt pads that require repositioning of the coupling orientation. The use of flange adapters is not recommended with Figures 510S and 519S fittings. Contact Tyco Fire Products for details. WARNING The Fittings described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of this device. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Approvals: UL, FM, ULC, VdS, and LPCB; Note: See Fire Protection Submittal Sheet for exact Listing / Approval information. General Description When placing an order, indicate the full product name. Please specify the quantity, figure number, wall thickness, and size. Grinnell Grooved Piping Products, valves, accessories and other products are available throughout the U.S., Canada, and internationally, through a network of distribution centers. You may write directly or call 215-362-0700 for the distributor nearest you. Ordering Procedure Care and Maintenance The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in accordance with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The installing contractor or product manufacturer should be contacted relative to any questions. Any impairment must be immediately corrected. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service. Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association (NFPA), and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products’ sole option. Tyco Fire Products neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Limited Warranty See Fire Protection Submittal Sheet for Pressure Rating and Listing/Approval Information LPCB Vd S Material: Cast: Figures: 201, 210, 219, 250, 260, 501, 510, 519, 510DE, 501S, 510S and 519S - Ductile iron conforming to ASTM A-536, Grade 65-45-12 Fabricated Steel: Figures 391, 392, 393, 312, 313, 321, 327, 341 and 350 - Carbon Steel, (Sizes 11/4" - 6" are Schedule 40); (Sizes 8" - 12" are Schedule 30), conforming to ASTM A-53 Grade B Protective Coatings: • Non-lead orange paint • Fire brigade red (optional) non-lead paint • Hot dipped galvanized conforming to ASTM A-153 Technical Data Page 2 of 6 TFP1810 ‡- Available with tapped plugs, contact Tyco Fire & Building Products. Figures 201, 210, 219, and 260 Figure 201Figure 210Figure 219Figure 260‡ 45° Elbow90° ElbowTee End Cap C to EAppx. Wt.C to EAppx. Wt.C to EAppx. Wt.E to EAppx. Wt. InchesLbs.InchesLbs.InchesLbs.InchesLbs. mmKg.mmKg.mmKg.mmKg. 1.750.92.751.02.751.40.880.4 44.50.469.90.569.90.622.40.2 1.751.12.751.22.751.80.880.6 44.50.569.90.569.90.822.40.3 2.001.83.252.03.252.70.880.9 50.80.882.60.982.61.222.40.4 2.252.23.753.03.755.80.880.9 57.21.095.31.495.32.622.40.4 2.252.23.753.03.755.80.941.1 57.21.095.31.495.32.623.90.5 2.503.54.254.54.257.00.881.1 63.51.6108.02.0108.03.222.40.5 2.885.54.758.54.7511.5 73.02.5120.73.9120.75.2 3.005.25.008.55.0011.81.002.6 76.22.4127.03.9127.05.425.41.2 3.257.75.2511.35.2510.6 82.63.5133.45.1133.44.8 3.257.75.5011.35.5015.30.924.7 82.63.5139.75.1139.76.923.42.1 3.258.55.5013.55.5017.01.005.0 82.63.9139.76.1139.77.725.42.3 3.5012.06.0014.66.0013.9 88.95.4152.46.6152.46.3 3.5012.06.5018.56.5026.01.007.5 88.95.4165.18.4165.111.825.43.4 3.5012.06.5018.56.5026.01.007.5 88.95.4165.18.4165.111.825.43.4 4.2523.07.7536.57.7545.0 108.010.4196.916.6196.920.4 4.2523.07.7536.57.7545.01.1912.8 108.010.4196.916.6196.920.430.25.8 4.7531.09.0060.09.0072.11.2520.0 120.714.1228.627.2228.632.731.89.1 5.2540.010.0067.010.0092.51.2536.0 133.418.1254.030.4254.042.031.816.3 Nominal Size 11/4" 11/2" 2" 21/2" 76.1mm 3" 108.0mm-- 4" 133.0mm-- 139.7mm 5" 159.0mm-- 165.1mm 6" 216.3mm-- 8" 10" 12" Friction Resistance* (Expressed as Equivalent Straight Pipe) ElbowTee Size90°45°BranchRun InchesFeetFeetFeetFeet mmMetersMetersMetersMeters 11⁄4 1.91.04.81.9 42.40.60.31.50.6 11⁄2 2.31.25.82.3 48.30.70.41.80.7 2 3.21.68.03.2 60.31.00.52.51.0 21⁄2 3.92.09.83.9 73.01.20.63.01.2 4.12.110.34.1 1.20.63.11.2 3 4.92.412.24.9 88.91.50.73.71.5 6.53.316.36.5 2.01.05.02.0 4 6.53.316.36.5 114.32.01.05.02.0 8.04.020.08.0 2.41.26.12.4 8.04.120.08.0 2.41.36.12.4 5 8.24.120.58.2 141.32.51.36.32.5 9.54.823.89.5 2.91.47.22.9 9.54.823.89.5 2.91.47.22.9 6 9.95.024.89.9 168.33.01.57.63.0 13.16.632.813.1 4.02.010.04.0 8 13.16.632.813.1 219.14.02.010.04.0 1016.58.341.316.5 273.05.02.512.65.0 1219.99.949.719.9 323.46.13.015.16.1 76.1mm 108.0mm 133.0mm 139.7mm 159.0mm 165.1mm 216.3mm Figure 260 E to E Figure 201 C to E C to E Figure 210 C to E C to E Figure 219 C to E C to E For reducing tees and branches, use the value that is corrosponding to the branch size. Example: for 8" x 8" x 2" tee, the branch value 2" is 8.0 feet. *Friction resistance for all elbows and tees except Figures 510S and 519S. Page 3 of 6 TFP1810 Figures 501S, 510S and 519S Figure 501SFigure 510S Figure 519S 45° Elbow90° ElbowTee C to EAppx Wt.C to EAppx. Wt.C to EAppx. Wt. InchesLbs.InchesLbs.InchesLbs. mmKg.mmKg.mmKg. 2.001.82.751.52.752.1 50.80.869.90.769.91.0 2.252.23.002.23.003.0 57.21.076.21.076.21.4 2.252.23.002.33.003.1 57.21.076.21.076.21.4 2.503.53.383.03.384.1 63.51.685.91.385.91.9 3.005.24.005.64.007.7 76.22.4101.62.6101.63.5 3.257.74.888.64.8812.0 82.63.5124.03.9124.05.4 3.258.54.888.84.8812.0 82.63.9124.03.9124.05.4 3.5012.05.5011.005.5015.0 88.95.4139.75.0139.76.8 3.5012.05.5011.25.5015.2 88.95.4139.75.1139.76.9 4.2523.06.8823.46.8831.2 108.010.4174.810.6174.814.2 Nominal Size 2" 21/2" 76.1mm 3" 4" 139.7mm 5" 165.1mm 6" 8" Figure 510S* C to E C to E Figure 519S* C to E C to E *Note: Figure 510S and 519S fittings are special short radius fittings with smaller center to end dimensions than standard grooved fittings. Depending on the size and coupling used, there may be interferences at the bolt pads which requires repositioning of the coupling orientation. The use of flange adapters is not recommended with Figures 510S and 519S fittings. Contact Tyco Fire Products for details. Figures 501, 510, 519 and 510DE Figure 501 C to E C to E Figure 510 C to E C to E Figure 501S C to E C to E Figure 510DE C to E C to E A B Figure 519 C to E C to E Figure 501Figure 510Figure 519 Figure 510DE 45° Elbow90° ElbowTee 90° Drain Elbow C to EAppx. Wt.C to EAppx. Wt.C to EAppx. Wt.C to EABAppx. Wt. InchesLbs.InchesLbs.InchesLbs.InchesInchesInchesLbs. mmKg.mmKg.mmKg.mmmmmmKg. 1.750.92.751.02.751.4 44.50.469.90.569.90.6 1.751.12.751.22.751.8 44.50.569.90.569.90.8 2.001.83.252.03.252.7 50.80.882.60.982.61.2 2.252.23.753.03.755.83.752.002.752.7 57.21.095.31.495.32.695.350.869.91.2 2.503.54.254.54.257.04.252.342.753.7 63.51.6108.02.0108.03.2108.059.469.91.7 3.005.25.008.55.0011.85.002.852.757.0 76.22.4127.03.9127.05.4127.072.469.93.2 3.258.55.5013.55.5017.05.503.382.7513.0 82.63.9139.76.1139.77.7139.785.969.95.9 3.5012.06.5018.56.5026.06.503.922.7513.4 88.95.4165.18.4165.111.8165.199.669.96.1 4.2523.07.7536.57.7545.07.754.952.7526.3 108.010.4196.916.6196.920.4196.9125.769.911.9 Nominal Size 11/4"---- 11/2"---- 2"---- 21/2" 3" 4" 5" 6" 8" Friction Resistance 501S, 510S & 519S (Expressed as Equivalent Straight Pipe) ElbowTee Size90°45°BranchRun InchesFeetFeetFeetFeet mmMetersMetersMetersMeters 2 3.21.68.03.2 60.31.00.52.51.0 21⁄2 3.92.09.83.9 73.01.20.63.01.2 4.12.110.34.1 1.20.63.11.2 3 4.92.412.24.9 88.91.50.73.71.5 4 6.53.316.36.5 114.32.01.05.02.0 8.04.120.08.0 2.41.36.12.4 5 8.24.120.58.2 141.32.51.36.32.5 9.54.823.89.5 2.91.47.22.9 6 9.95.024.89.9 168.33.01.57.63.0 8 13.16.632.813.1 219.14.02.010.04.0 76.1mm 139.7mm 165.1mm Page 4 of 6 TFP1810 Figures 250 and 350 Figure 350 Fabricated Sizes 3” to 6” E to E E to E Figure 350 Fabricated Sizes 8” to 12” E to E Figure 250 Cast Figures 250 and 350 Concentric Reducer - Groove x Groove NominalE to EAppx. Wt.NominalE to EAppx. Wt.NominalE to EAppx. Wt. SizeInchesLbs.SizeInchesLbs.SizeInchesLbs. InchesmmKg.InchesmmKg.InchesmmKg. 2.501.03.504.24.005.8 63.50.588.91.9101.62.6 2.501.33.504.45.0012.2 63.50.688.92.0127.05.5 2.501.23.504.65.0012.1 63.50.588.92.1127.05.5 2.501.53.504.65.0012.0 63.50.788.92.1127.05.5 2.501.63.504.55.0011.9 63.50.888.92.0127.05.4 2.501.33.504.45.0011.3 63.50.688.92.0127.05.1 2.501.33.504.55.0010.8 63.50.688.92.0127.04.9 2.501.34.005.56.0021.9 63.50.6101.62.5152.410.0 3.001.54.006.06.0021.6 76.20.7101.62.7152.49.8 3.002.04.005.66.0021.1 76.20.9101.62.5152.49.6 3.002.24.006.06.0019.5 76.21.0101.62.7152.48.9 3.002.34.006.07.0028.0 76.21.0101.62.7177.812.7 3.002.34.006.07.0030.0 76.21.0101.62.7177.813.6 3.002.34.006.07.0028.0 76.21.0101.62.7177.812.7 3.003.24.005.97.0033.0 76.21.5101.62.7177.815.0 3.002.64.006.3 76.21.2101.62.9 *2 x 11⁄4 *139.7mm x 3*6 x 5 *2 x 11⁄2 *139.7mm x 48 x 2 *21⁄2 x 25 x 11⁄2 8 x 21⁄2 *76.1mm x 11⁄2 5 x 28 x 3 *76.1mm x 25 x 21⁄2 8 x 4 3 x 11⁄4 5 x 38 x 5 3 x 11⁄2 *5 x 48 x 6 *3 x 2*165.1mm x 310 x 4 *3 x 21⁄2 *165.1mm x 410 x 5 *3 x 76.1mm *165.1mm x 139.7mm 10 x 6 4 x 11⁄4 *6 x 210 x 8 4 x 11⁄2 6 x 21⁄2 12 x 4 *4 x 2*6 x 76.1mm 12 x 6 *4 x 21⁄2 6 x 312 x 8 *4 x 76.1mm *6 x 412 x 10 4 x 3*6 x 139.7mm B C A D ADA CAP® Patented Pipe Nominal Dimensions O.D.Takeout Center to End SizeABCD InchesInchesInchesInchesInches mmmmmmmm 1.251.751.890.77 31.844.548.00.3 1.9001.251.751.890.77 48.331.844.548.00.3 1.372.002.020.88 34.850.851.30.4 1.251.751.890.92 31.844.548.00.4 2.3751.251.751.890.92 60.331.844.548.00.4 1.372.002.021.06 34.850.851.30.5 1.471.971.891.28 37.350.048.00.6 2.8751.471.971.891.28 73.037.350.048.00.6 1.372.002.021.50 34.850.851.30.7 Net OutletWt. NPT*Lbs. Inches Kg. 1/2 11/2 3/4 1 1/2 2 3/4 1 1/2 21/2 3/4 1 *ISO-7 threaded outlets are available upon request. Note: Sizes marked with an asterisk (*) are only available in Figure 250 Cast. Sizes without an asterisk are only available in Figure 350 Fabricated. Page 5 of 6 TFP1810 Figures 391, 392, 393, 312 and 313 Figure 341 E to E Figure 327 C to E C to E Figure 393 E to E Figure 392 E to E Figure 391 E to E Figure 313C to E C to E Figure 341 150 lbs. Flange Adapter C to EAppx. Wt.E to EAppx. Wt. nchesLbs.InchesLbs. mmkg.mmkg. 2.752.04.002.8 69.60.9101.61.3 2.752.24.003.2 69.92.0101.61.5 3.252.74.05.2 82.61.2101.62.4 3.755.04.008.0 95.32.3101.63.6 4.257.14.0010.2 108.03.2101.64.6 5.0011.96.0017.2 127.05.4152.47.8 5.5017.16.0021.4 139.77.8152.49.7 6.5027.56.0026.0 165.112.5152.411.8 7.7547.06.0038.4 196.921.3152.417.4 9.0068.08.0065.0 228.630.8203.229.5 10.00107.08.0091.0 254.048.5203.241.3 Nominal Size 11/4" 11/2" 2" 21/2" 3" 4" 5" 6" 8" 10" 12" Figure 327 Cross Figures 391, 392 and 393 Adapter Nipples E to EAppx. Wt.C to EAppx. Wt.C to EAppx. Wt. InchesLbs.InchesLbs.InchesLbs. mmKg.mmKg.mmKg. 4.000.81.750.41.380.4 101.60.444.50.235.10.2 4.000.91.750.51.380.5 101.60.444.50.235.10.2 4.001.21.880.61.380.6 101.60.547.80.335.10.3 4.001.92.000.71.501.1 101.60.950.80.338.10.5 4.002.52.251.41.501.2 101.61.157.20.638.10.5 6.005.52.632.41.752.2 152.42.566.81.144.51.0 6.007.42.884.12.003.3 152.43.473.21.950.81.5 6.009.53.135.62.004.6 152.44.379.52.550.82.1 6.0014.23.8811.12.008.7 152.46.498.65.050.83.9 8.0027.04.3814.02.139.1 203.212.211.36.454.14.1 8.0033.04.8822.02.2516.7 203.215.0124.010.057.27.6 Nominal Size 11/4" 11/2" 2" 21/2" 3" 4" 5" 6" 8" 10" 12" Figure 312Figure 313 221/2° Elbow111/4° Elbow Figures 327 and 341 Figure 312 C to E C to E General Notes: It is the Designer’s responsibility to select products suitable for the intended service and to ensure that pressure ratings and performance data is not exceeded. Always read and understand the installation instructions (IH-1000). Never remove any piping component or correct or modify any piping deficiencies without first depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the specific application.Certified Company TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A. Page 6 of 6 TFP1810 Figure 321 Figure 321 C to E C to E 11⁄2 x 11⁄2 x 11⁄4 6 x 6 x 4 2 x 2 x 11⁄2 6 x 6 x 5 21⁄2 x 21⁄2 x 11⁄4 8 x 8 x 2 21⁄2 x 21⁄2 x 11⁄2 8 x 8 x 3 21⁄2 x 21⁄2 x 28 x 8 x 4 3 x 3 x 11⁄2 8 x 8 x 5 3 x 3 x 28 x 8 x 6 3 x 3 x 21⁄2 10 x 10 x 2 4 x 4 x 11⁄4 10 x 10 x 3 4 x 4 x 11⁄2 10 x 10 x 4 4 x 4 x 210 x 10 x 5 4 x 4 x 21⁄2 10 x 10 x 6 4 x 4 x 310 x 10 x 8 5 x 5 x 212 x 12 x 3 5 x 5 x 21⁄2 12 x 12 x 4 5 x 5 x 312 x 12 x 5 5 x 5 x 412 x 12 x 6 6 x 6 x 212 x 12 x 8 6 x 6 x 21⁄2 12 x 12 x 10 6 x 6 x 3 Figure 321 Reducing Tee NominalC to EAppx. Wt.NominalC to EAppx. Wt. SizeInchesLbs.SizeInchesLbs. Inches mmKg.Inches mmKg. 3.252.06.5026.6 82.60.9165.112.1 3.252.76.5027.0 82.61.2165.112.2 3.754.27.7536.2 95.31.9196.916.4 3.754.27.7536.5 95.31.9196.916.6 3.754.37.7536.6 95.32.0196.916.6 4.255.37.7536.8 108.02.4196.916.7 4.255.57.7537.0 108.02.5196.916.8 4.255.89.0057.1 108.02.6228.625.9 5.009.89.0057.4 127.04.4228.626.0 5.009.99.0057.6 127.04.5228.626.1 5.0010.19.0057.8 127.04.6228.626.2 5.0010.39.0058.0 127.04.7228.626.3 5.0010.59.0058.4 127.04.8228.626.5 5.5014.510.0080.2 139.76.6254.036.4 5.5014.810.0080.5 139.76.7254.036.5 5.5015.210.0080.7 139.76.9254.036.6 5.5015.810.0080.9 139.77.2254.036.7 6.5026.510.0091.4 165.111.9254.041.5 6.5026.510.0091.8 165.112.0254.041.6 6.5026.5 165.112.0 PRINTED IN USAMKT. #8800003 - REV AA MFG. #5400802 - 11/02 VSR-SF VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 1 OF 2 UL, ULC, CSFM Listed and NYMEA Accepted, CE Marked Service Pressure: Up to 250 PSI (17,2 BAR) Minimum Flow Rate for Alarm: 8-10 GPM (30-38 LPM) Maximum Surge: 18 FPS (5,5 m/s) Enclosure: Die-cast, red enamel fi nish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Usage: Listed plastic, copper and schedule 40 iron pipe. Fits pipe sizes - 1" (25mm), 1 1/4" (32mm), 1 1/2" (38mm) and 2" (50mm) Note: 12 paddles are furnished with each unit, one for each pipe size of threaded and sweat TEE, one for 1" (25mm) CPVC, one for 1" (25mm) CPVC (Central), one for 1 1/2" (38mm) polybutylene and one for 1 1/2" (38mm) threaded (Japan). (CTS-Copper tubing size) Environmental Specifi cations: • Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. • NEMA 4/IP55 rated enclosure - use with appropriate conduit fi tting. • Temperature range: 40° F to 120° F, 4,5° C to 49° C) Caution: This device is not intended for applications in explosive environments. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090018 Stock No. 1113000 U.S. Pat. No. 3921989, Canadian Pat. No. 1009680 Other Patents Pending The Model VSR-SF is a vane type waterfl ow switch for use on wet sprinkler systems that use 1" (25mm), 1 1/4" (32mm), 1 1/2" (38mm) or 2" (50mm) pipe size. The unit may also be used as a sectional waterfl ow detector on large systems. The unit contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a fl ow of 8-10 gallons per minute (30-38 LPM) or more occurs downstream of the device. The fl ow condition must exist for a period of time necessary to overcome the selected retard period. INSTALLATION: These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" (15cm) of a valve, drain or fi tting which changes the direction of the waterfl ow. Select the proper paddle for the pipe size and type of TEE used see Fig. 1 for instructions on changing paddle. The unit has a 1" NPT bushing for threading into a non-corrosive TEE. See Fig. 2 for proper TEE size, type and installation. Use no more than three wraps of tefl on tape. Screw the device into the TEE fi tting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterfl ow. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. The device can also be used in copper or plastic pipe installations with the proper adapters so that the specifi ed TEE fi tting may be installed on the pipe run. INSPECTION AND TESTING: Check the operation of the unit by opening the inspector’s test valve at the end of the sprinkler line or the drain and test connection, if an inspector’s test valve is not provided. If there are no provisions for testing the operation of the fl ow detection device on the system, application of the VSR-SF is not recommended or advisable The frequency of the inspection and testing and its associated protective monitoring system should be in accordance with the applicable NFPA Codes and Standards and/or authority having jurisdiction (manufacturer recommends quarterly or more frequently). Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USAMKT. #8800003 - REV AA MFG. #5400802 - 11/02 VSR-SF VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 2 OF 2 1 11/16” (4,3MM)APPROX. DEPTH DWG# 735-33 CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. FIG. 1 Important: There are 12 paddles furnished with each unit. One for each size of threaded, sweat or plastic TEE as described in Fig. 2. These paddles have raised lettering that shows the pipe size and type of TEE that they are to be used with. The proper paddle must be used. The paddle must be properly attached (see drawing) and the screw that holds the paddle must be securely tightened. FIG. 2 NOTES: 1. The model VSR-SF has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other is used to operate a local audible or visual annunciator. 2. For supervised circuits see “Switch Terminal Connections” drawing and caution note (Fig. 3). FIG. 4 TYPICAL ELECTRICAL CONNECTIONS Retard Adjustment: To change time, turn knob (either direction) for desired time delay. Use the minimum amount of retard necessary to prevent false alarms. A “B” setting is usually adequate for this. Factory set at “B”. FIG. 3 SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL OUTG O I N G INCO M I NG DWG# 923-3 FIG. 5 To remove knockouts: Place screwdriver at edge of knockouts, not in the center. APPLICATION WARNING! Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterfl ow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Screw the device into the tee fi tting as shown. Care must be taken to properly orient the device for the direction of waterfl ow. On sweat tees, no threaded bushings, inserts, or adapters are permitted, unless they comply with the dimensions listed in the chart below. Important - The depth to the inside bottom of the tee should have the following dimensions: DIRECTION OF WATER FLOW DWG# 737-31 2 SETS OF NORMALLY OPEN CONTACTS CLOSE ON ALARM THE N.C. AND N.O. MARKINGS ON THE SWITCH ARE FOR AN ALARM CONDITION. THE CONTACTS ARE REVERSED WHEN THE DEVICE IS IN THE NORMAL CONDITION. WATERFLOW ZONE ON FIRE PANEL EOLR FROM FIRE PANEL POSITIVE DC OR HOT AC NEGATIVE DC OR NEUTRAL AC DWG# 761-2 BELL COM NONC COM NONC COM NONC COM NONC EOLR Warning: Do not use more than three wraps of tefl on tape. Shown with optional Cover Tamper Switch Kit. 709 OSY ES-709L Ball Valve Test Cock Check Assembly Module Bolted Cover Replaceable Resilient Disc Replaceable SeatLower Stem Guide Job Name______________________________________________Contractor______________________________________________ Job Location____________________________________________Approval______________________________________________ Engineer________________________________________________Contractor’s P.O.No.______________________________________ Approval________________________________________________Representative__________________________________________ For Non-Health Hazard Applications Now Available WattsBox Insulated Enclosures. For more information, send for literature ES-WB. Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with- out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. IMPORTANT:INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS Series 709 Double Check Valve Assemblies Sizes: 21⁄2" – 10" (65 – 250mm) Series 709 Double Check Valve Assemblies are designed to prevent the reverse flow of polluted water from entering into the potable water system. This series can be applied,where approved by the local authority having juris- diction,on non-health hazard installations.Series 709 features a modular check design concept to facilitate easy maintenance.Check with local juris- dictional authority as to installation requirements. Features •Replaceable bronze seats •Maximum flow at low pressure drop •Design simplicity for easy maintenance •No special tools required for servicing •Captured spring assemblies for safety •Approved for vertical flow up installation Models Suffix: NRS – non-rising stem resilient seated gate valves OSY – UL/FM outside stem and yoke resilient seated gate valves S-FDA – FDA epoxy coated strainer BB – bronze body - 21⁄2" – 3" (64 – 76mm) QT – quarter-turn ball valves QT-FDA – FDA epoxy coated ball valve shutoffs LF – without shutoff valves Specifications A Double Check Valve Assembly shall be installed at referenced cross-connec- tionsto prevent the backflow of polluted water into the potable water supply. The cross-connections shall be determined by local inspection authority for use where a high hazard situation does not exist.Valve shall feature modular check assemblies with center stem guiding.Each check module shall have a captured spring and be accessible through a bolted cover plate.Seats shall be replaceable without special tools.It shall be a complete assembly including tight-closing resilient seated shutoff valves,test cocks,and a strainer is rec- ommended.The assembly shall meet the requirements of ASSE No.1015; AWWA C510-92; CSA B64.5 and UL Classified File No.EX3185.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be a Watts Regulator Company Series 709. Check Assembly Module Series 709 features a modular design concept which facilitates complete maintenance and assembly by retaining the spring load.Also,the first and second check module are identical and can be interchanged. Approvals Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Sizes 4" – 10" (100 – 250mm) approved horizontal and vertical “flow up”.Size 21⁄2" and 3" (65 – 80mm) approved horizontal only. Factory Mutual approved 4" – 10" (80 – 250mm) vertical “flow up”with OSY gate valves only. Note: Model "S" not listed Dimensions — Weights D C (open) Ñ L A N1 Materials Check Valve Bodies:Epoxy coated cast iron Seats:Bronze Pressure — Temperature Temperatures Range:33°F – 110°F (5°C – 43°C) continuous, 140°F (60°C) intermittent Maximum Working Pressure:175psi (12.06 bar) Standards AWWA C510-92 IAPMO PA 31 USC Manual for Cross-Connection Control,8th Edition SIZE (DN)DIMENSIONS AC (OSY)C (NRS)DLU*MN in.mmin.mmin.mmin.mmin.mmin.mmin.mmin.mmin.mm 21⁄2 65393⁄8 1000163⁄8 41693⁄8 23831⁄2 89241⁄8 613112791025461⁄2 165 380403⁄8 1025187⁄8 479101⁄4 26033⁄4 95241⁄8 61314356101⁄8 2577178 4 100523⁄8 1330223⁄4 578123⁄16 31041⁄2 114341⁄8 86714356121⁄8 30881⁄4 210 6 150627⁄8 1597301⁄8 7651640651⁄2 140415⁄8 105716406181⁄2 470131⁄2 343 8 200751905373⁄4 9591915⁄16 50661⁄2 16552132121533215⁄8 549151⁄2 394 10250902286453⁄4 11622313⁄16 60582036416262563526660181⁄2 470 SIZE (DN)DIMENSIONSWEIGHTSTRAINER N1†RR TNRSOSYQTWeight in.mmin.mmin.mmin.mmin.mmlbs.kgs.lbs.kgs.lbs.kgs.lbs.kgs. 21⁄2 65 102544102164063761677617077154702813 380102545127164063761677617077162733415 4 100123056152193⁄4 50261523681673831742751256027 6 15020508112792666071⁄2 19162728470732161127712255 8 200223⁄4 578111⁄4 286111⁄4 2869229120154513075931419644247112 1025028711121⁄2 318121⁄2 318101⁄4 2602003909207394024661119370168 † - Dimension required for screen removal.Quarter-turn (QT) valve dimensions. *Service clearance for check assembly from center. M R T 2 U 1015 B64.5 050100150200250300350400gpm 0 190380570760950114013301520lpm 5 7.51015fps 1.52.33.04.6mps 21⁄2" (65mm) 6" (150mm) 3" (80mm) 8" (200mm) 4" (100mm) Pr e s s u r e L o s s Pr e s s u r e L o s s Flow Rate Flow Rate 10" (250mm) Capacity *Typical maximum system flow rate (7.5 feet/sec.) **UL rated flow kPapsi 10315 8312 629 416 213 00050100150200250300gpm 0 1903805707609501140lpm 5 7.5101520fps 1.52.33.04.66.1mps kPapsi 10315 8312 629 416 213 00 050100200300400500600gpm 0 1903807601140152019002280lpm 5 7.51015fps 1.52.33.04.6mps Pr e s s u r e L o s s Flow Rate kPapsi 10315 8312 629 416 213 00 0 100250500750100012501500gpm 0 38095019002850380047505700lpm 5 7.51015fps 1.52.33.04.6mps Pr e s s u r e L o s s Flow Rate kPapsi 10315 8312 629 416 213 00 0 25050010001500200025003000gpm 0 9501900380057007600950011400lpm 5 7.51015fps 1.52.33.04.6mps Pr e s s u r e L o s s Flow Rate kPapsi 10315 8312 629 416 213 00 0 5001000150020002500300035004000gpm 0 19003800570076009500114001330015200lpm 5 7.51015fps 1.52.33.04.6mps Pr e s s u r e L o s s Flow Rate kPapsi 10315 8312 629 416 213 00 *** ** ** ** ** ** * * * * * 3 ES-709L 0510© Watts Regulator Co., 2005 HEADQUARTERS:Watts Regulator Company815 Chestnut St.,North Andover,MA 01845-6098 U.S.A.978 688-1811978 794-1848 Edwards,Platt & Deely,Inc.271 Royal Ave.,Hawthorne,NJ 07506973 427-2898973 427-4246 Edwards,Platt & Deely,Inc.368 Wyandanch Ave.,North Babylon,NY 11703631 253-0600631 253-0303 W.P.Haney Co.,Inc.51 Norfolk Ave.,South Easton,MA 02375508 238-2030508 238-8353 J.B.O’Connor Company,Inc.P.O.Box 12927,Pittsburgh,PA 15241724 745-5300724 745-7420 RMIGlenfield Bus.Ctr.,2535 Mechanicsville Tpk.,Richmond,VA 23223804 643-7355804 643-7380 The Joyce Agency,Inc.8442 Alban Rd.,Springfield,VA 22150703 866-3111703 866-2332 Vernon Bitzer Associates,Inc.980 Thomas Drive,Warminster,PA 18974215 443-7500215 443-7573 WMS Sales,Inc.(Main office)9580 County Rd.,Clarence Center,NY 14032716 741-9575716 741-4810 Billingsley & Associates,Inc.2728 Crestview Ave.,Kenner,LA 70062-4829504 602-8100504 602-8106 Billingsley & Associates,Inc.478 Cheyenne Lane,Madison,MS 39110601 856-7565601 856-8390 Francisco J.Ortiz & Co.,Inc.Charlyn Industrial Pk.,Road 190 KM1.9 - Lot #8,Carolina,Puerto Rico 00983 787 769-0085787 750-5120 Mid-America Marketing,Inc.203 Industrial Drive,Birmingham,AL 35211205 879-3469205 870-5027 Mid-America Marketing,Inc.1364 Foster Avenue,Nashville,TN 37210615 259-9944615 259-5111 Mid-America Marketing,Inc.5466 Old Hwy.78,Memphis,TN 38118901 795-0045901 795-0394 Smith & Stevenson Co.,Inc.4935 Chastain Ave.,Charlotte,NC 28217704 525-3388704 525-6749 Watts2861-B Bankers Industrial Drive,Atlanta,GA 30360770 209-3310770 447-4583 Aspinall Associates,Inc.6840 Hillsdale Court,Indianapolis,IN 46250317 849-5757317 845-7967 Dave Watson Associates1325 West Beecher,Adrian,MI 49221517 263-8988517 263-2328 Disney McLane & Associates428 McGregor Ave.,Cincinnati,OH 45206800 542-1682877 476-1682 BWA Company17610 S.Waterloo Rd.,Cleveland,OH 44119216 486-1010216 486-2860 Mid-Continent Marketing Services Ltd.1724 Armitage Ct.,Addison,IL 60101630 953-1211630 953-1067 Soderholm & Associates,Inc.7150 143rd Ave.N.W.,Anoka,MN 55303763 427-9635763 427-5665 Stickler & Associates333 North 121 St.,Milwaukee,WI 53226414 771-0400414 771-3607 Hugh M.Cunningham,Inc.13755 Benchmark,Dallas,TX 75234972 888-3808972 888-3838 Mack McClain & Associates11132 South Towne Square,Suite 202,St.Louis,MO 63123314 894-8188314 894-8388 Mack McClain & Associates,Inc.1450 NE 69th Place,Ste.56 Ankeny,IA 50021515 288-0184515 288-5049 Mack McClain & Associates,Inc.15090 West 116th St.,Olathe,KS 66062913 339-6677913 339-9518 OK! Sales,Inc.2200 Blue Creek Dr.,Norman,OK 73026405 360-6161405 360-0092 Phoenix Marketing,Ltd.2416 Candelaria N.E.,Albuquerque,NM 87107505 883-7100505 883-7101 Delco Sales,Inc.1930 Raymer Ave.,Fullerton,CA 92833714 888-2444714 888-2448 Delco Sales,Inc.111 Sand Island Access Rd.,Unit I-10,Honolulu,HI 96819808 842-7900808 842-9625 Fanning & Associates,Inc.6765 Franklin St.,Denver,CO 80229-7111303 289-4191303 286-9069 Hollabaugh Brothers & Associates6915 South 194th St.,Kent,WA 98032253 867-5040253 867-5055 Hollabaugh Brothers & Associates3028 S.E.17th Ave.,Portland,OR 97202503 238-0313503 235-2824 P I R Sales,Inc.3050 North San Marcos Place,Chandler,AZ 85225480 892-6000480 892-6096 Preferred Sales31177 Wiegman Road,Hayward,CA 94544510 487-9755510 476-1595 R.E.Fitzpatrick Sales,Inc.4109 West Nike Dr.(8250 South),West Jordan,UT 84088801 282-0700801 282-0600 Watts Industries (Canada) Inc. (Watts Regulator Co.Division)5435 North Service Road,Burlington,Ontario L7L 5H7905 332-4090905 332-7068 Con-Cur West Marketing,Inc.71B Clipper Street,Coquitlam,British Columbia V3K 6X2604 540-5088604 540-5084 D.C.Sales Corporation Inc.#10-6130 4th St.S.E.,Calgary,Alberta T2H 2A6403 253-6808403 259-8331 D.C.Sales Corporation Inc.11420 142 Street,Edmonton,Alberta T5M 1V1780 496-9495780 496-9621 GTA Sales Team.Greater Toronto Area888 208-8927888 479-2887 Hydro-Mechanical Sales,Ltd.3700 Joseph Howe Drive,Suite 1,Halifax,Nova Scotia B3L 4H7902 443-2274902 443-2275 Hydro-Mechanical Sales,Ltd.P.O.Box 1445 (Mailing),297 Collishaw St.,Suite 7 (shipping) Moncton,New Brunswick E1C 9R2506 859-1107506 859-2424 J.D.S.Sales Ltd.4 Lancaster Street,St.John’s,Newfoundland A1A 5P7709 579-5771709 579-1558 Le Groupe B.G.T.,Inc.23 du Buisson,Pont Rouge,Quebec G3H 1X9418 873-2500418 873-2505 Le Groupe B.G.T.,Inc.86 des Enterprises #208,Boisbriand,Quebec J7G 2T3450 434-9010450 434-9848 Mar-Win Agencies,Ltd.1333 Clifton St.,Winnipeg,Manitoba R3E 2V1204 775-8194204 786-8016 Northern Mechanical SalesP.O.Box 280 (mailing) 163 Pine St.(shipping),Garson,Ontario P3L 1S6705 693-2715705 693-4394 Palser Enterprises,Ltd.P.O.Box 28136 (mailing),1885 Blue Heron Dr.,#4, London,Ontario N6H 5L9519 471-9382519 471-1049 RAM Mechanical Marketing Inc.1401 St.John Street,Regina,Saskatchewan S4R 1S5306 525-1986306 525-0809 RAM Mechanical Marketing Inc.510 Ave M South,Saskatoon,Saskatchewan S7M 2K9306 244-6622306 244-0807 Walmar Mechanical Sales24 Gurdwara Rd.,Nepean,Ontario K2E 8B5613 225-9774613 225-0673 EXPORT Hdqtrs.:Watts Regulator Co.815 Chestnut St.,North Andover,MA 01845-6098 U.S.A.978 688-1811978 794-1848 Fax # For Technical Assistance Call Your Authorized Watts Agent. Ca n a d a Telephone # So u t h Ce n t r a l 0510 No r t h Ea s t So u t h Ea s t Watts USA website: www.wattsreg.com Watts Canada website: www.wattscanada.ca Mi d At l a n t i c No r t h Ce n t r a l Wes t e r n Fire Protection Basic Deluge Valve 700E Typical Applications Features and Benefits • Minimized pressure loss • Unobstructed flow path • Advanced globe "Y", or angle, pattern • Wide-body design • Automatic reset – "hands free" return to stand-by • Double-chambered actuator – reliable drip-tight seal • Only one moving assembly • Hydraulically-powered positive closure • Replaceable stainless steel valve seat – lifetime valve Optional Features A wide variety of control trim components, including: • Latched open – manual reset to close •Alarm pressure-switch • Explosion-proof for hazardous zones • Seawater service • Pressure-reducing add-on trim • Electric,Hydraulic or Pneumatic UL-listed trim • Fail-safe open (upon electrical failure) energized to close main valve ®UL LISTED EX5092 • Petrochemical facilities • Tunnels • Power plants & Transformers • Off-shore platforms • Flammable materials storage • Aviation & Airports • Marine environments • Gas & Oil storage tanks Fire Protection Basic Deluge Valve700E Tender Specifications The deluge valve shall be a hydraulically-operated, diaphragm-actuated, globe "Y" pattern (or angle) valve. Valve actuation shall be accomplished by one moving assembly containing a double-chambered actuator, which shall include a stainless steel stem and a resilient elastomeric seal held by a flat seal-disk and creating a drip- tight seal against the seat. The valve seat shall be removable and made of stainless steel.The seat bore net area shall be no less than that of the valve nominal diameter, and shall have an unobstructed flow path with no stem guide or supporting ribs. All necessary inspection and servicing shall be possible in-line. The valve shall be UL-listed as a water control valve - deluge type. The manufacturer shall be certified according to ISO 9001 standards. Operation Deluge valves are required to operate independently, regardless of failures in other systems or other sources of energy.In emergency situations, these valves should be driven by the line water pressure. In the closed, SET condition, the Bermad 700E Deluge Valves are held closed by line pressure applied and trapped in the upper chamber .This water pressure, multiplied by the surface area of the diaphragm , creates a closing force resulting in the valve remaining sealed drip-tight until a control device activates.The greater the pipeline water pressure ❹, the greater the effective closing force.The closed valve prevents the water (or foam) from entering the system. During a FIRE or TEST condition, the water pressure is released from the upper control-chamber.Line water pressure, without assistance from any outside source, forces the seal-disk open, enabling full, unobstructed, full- bore clear flow. For RESET, line pressure is re-introduced into the upper chamber, closing the valve. Valve Open (operating condition) Valve Closed (set condition) Fire Protection Basic Deluge Valve 700E UL-Listed The BERMAD Model 700E Deluge Valve is UL-listed, as a unit, when installed with specific components and accessories. Models 700E Type 5: Hydraulically-Controlled, PORV-Activated,Deluge Valve Local release compensates for long release lines with adjustablepilot sensing trip point 700E Type 4: Pneumatically-Controlled Deluge Valve Dry pilot line, suited for freezing environments and corrosive media Notes 1.Photos show typical orientation. 2.All models can be installed vertically or horizontally. 3.Angle valves are also available. 700E Type 5D: Hydraulically-Controlled Deluge Valve with HRV Hydraulic-relay local release for long release lines and quick opening 700E Type 6: Dry Pilot & Electrically- Controlled Deluge Valve Combination of solenoid activation and dry pilot line for dual-redundant systems 700E Type 1: Hydraulically-Controlled Deluge Valve For wet pilot line sprinkler systems, simplest and least costly of deluge actuation systems 700E Type 2: Electrically-Controlled Deluge Valve Quick-opening, large-bore servo-solenoid activated, optimized for industrial applications, offers the greatest number of features and design flexibility 700E Type 3: Electrically-Controlled, PORV-Activated,Deluge Valve Ideal for corrosive water. Pneumatic actuator isolates corrosive media from the solenoid valve, keeps solenoid dry 700E Type 3D: Solenoid-Controlled Valve Smooth acting, on/off cycling, combines hydraulic relay and solenoid pilot valve for added system design alternatives Fire Protection Basic Deluge Valve700E Water Temperature • 0.5 - 80°C (33 - 180°F) Working pressure • Max working pressure #150:250 psi (17 bar) #300:400 psi (27 bar) • UL-rated working pressure 175 psi (12 bar) Notes: 1.Ly1, La1 & h1 are for flanged ANSI #150 and ISO PN16 2.Ly2, La2 & h2 are for threaded female, NPT or BSP 3.Ly3, La3 & h3 are for flanged ANSI #300 and ISO PN25 4.Dv is for threaded female NPT or BSP 5.kg is maximum shipping weight (ANSI # 300 - "Y") 6.Dimensions are maximum 7.Provide adequate clearance around valve for maintenance ©Copyright 1999 by BERMAD Control Valves Cat # PC7PE10 ver 4/00 The information contained in this document is subject to change without notice.BERMAD shall not be liable for any errors contained herein.All rights reserved. www.bermad.com E-mail:info@bermad.comEnglish Connection Standard • Flanged:ANSI B16.42 (Ductile iron), B16.5 (Steel & Stainless), B16.24 (Bronze), ISO PN16 & PN25 • Threaded:NPT or BSP 2, 21/2 & 3" Sizes ("Y" & Angle") • Available:11/2, 2, 21/2, 3, 4, 6, 8, 10, 12, 14 & 16" • UL-listed:2, 21/2, 3, 4, 6, 8 & 10" Specifications Materials Manufacturers Standard Materials Valve body and cover • Ductile iron ASTM 536(1) • Carbon steel ASTM A216-WCB(1) Valve wetted parts (internals) • Stainless steel 304 and coated steel Elastomers • NBR Optional Materials Valve body • Stainless steel 316 • Marine bronze • NiAl-bronze • Titanium • Duplex and Super-duplex Valve wetted parts (internals) • Stainless steel 316 • Bronze • Titanium • Copper-nickel • Hastalloy Control Trim System • Brass ASTM B21 • Forged brass fittings & copper tubing • Stainless steel 316 • Copper-nickel Notes: 1.Epoxy coated, fusion bonded - standard. Other coatings available on request. 2.For seawater service see BERMAD publication "Seawater and Corrosive Media". Valve Size11/2"2"21/2"3"4"6"8"10"12"14"16" mminchmminchmminchmminchmminchmminchmminchmminchmminchmminchmminch (1)Ly1 20581/16 20581/16 20981/4 25097/8 320125/8 415163/8 5001911/16 6052313/16 725289/16 733287/8 99039 (2)Ly2 15561/8 15561/8 21283/8 250913/16 N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A (3)Ly3 21081/4 21081/4 21283/8 264107/16 335131/4 433171/16 524205/8 6372576230767303/16 1024403/4 (1)La1 12143/4 12143/4 14051/2 152619071/2 22587/8 265107/16 320125/8 396159/16 400153/4 450173/4 (2)La2 12043/4 12043/4 14051/2 15961/4 N/AN/A N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A (3)La3 1275127514957/8 15961/4 20077/8 23493/16 277107/8 336131/4 415165/16 419161/2 467183/8 Hy 15763/16 15763/16 15763/16 209913/16 250913/16 3501313/16 411163/16 48419580227/8 580227/8 798315/16 Ha 14653/4 14653/4 153618171/16 227815/16 301117/8 375143/4 436171/8 537211/8 515201/4 783303/4 (1)h1 8231/4 8231/4 1024102412751526203821985/8 2751013/16 2751013/16 369141/2 (2)h2 8231/4 8231/4 102411441/2 N/AN/A N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A (3)h3 8931/2 8931/2 10945/16 10841/4 13555/16 16561/2 21681/2 23591/4 294111/2 294111/2 38653/16 W 16561/2 16561/2 18575/16 20781/8 25097/8 320125/8 390153/8 480187/8 550215/8 570227/16 740291/8 a N/AN/A5925/16 6725/8 70.523/4 8533/8 100315/16 100315/16 11745/8 148513/16 N/AN/AN/AN/A (4)Dv 3/8"3/4"11/2"11/2"2"2"2"2"2"N/AN/A (5)kg 12.212.2152543 85146245410434900 Di m e n s i o n s W WW Dv a H Ly Hy La1,La2,La3Ly1,Ly2,Ly3 h1 h2 h3 Ha Wrot and Cast Pressure Fittings NIBCO INC. World Headquarters n 1516 Middlebury St. n Elkhart, IN46516-4714 U.S.A. n www.nibco.com 21 n TEES continued §Made to Order.Consult price sheet for minimum order quantities. APPROX.DIMENSIONS NET WT.INCHES NOM.SIZELBS.CFG 1 x 1/2 x 10.29 11/16 1 21/32 1 x 1/2 x 3/40.27 9/16 13/16 3/4 1 x 1/2 x 1/20.22 15/32 25/32 23/32 1 1/40.43 7/8 7/8 29/32 1 1/4 x 1 1/4 x 21.19129/32 129/32 11/32 1 1/4 x 1 1/4 x 1 1/20.6013/16 13/16 29/32 1 1/4 x 1 1/4 x 10.45 25/32 25/32 29/32 1 1/4 x 1 1/4 x 3/40.37 21/32 21/32 3/4 1 1/4 x 1 1/4 x 1/20.30 1/2 1/2 25/32 §1 1/4 x 1 1/4 x 3/80.34 23/32 23/32 29/32 1 1/4 x 1 x 1 1/40.43 7/8 1 29/32 1 1/4 x 1 x 10.47 25/32 7/8 29/32 1 1/4 x 1 x 3/40.35 21/32 25/32 7/8 1 1/4 x 1 x 1/20.30 1/2 5/8 29/32 1 1/4 x 3/4 x 1 1/40.42 7/8 15/32 29/32 1 1/4 x 3/4 x 10.45 25/32 11/32 29/32 1 1/4 x 3/4 x 3/40.37 21/32 15/16 7/8 §1 1/4 x 3/4 x 1/20.30 1/2 3/4 29/32 1 1/4 x 1/2 x 1 1/40.41 7/8 13/16 29/32 1 1/20.61 31/32 31/32 29/32 1 1/2 x 1 1/2 x 21.2713/4 13/4 11/32 1 1/2 x 1 1/2 x 1 1/40.62 29/32 29/32 11/16 1 1/2 x 1 1/2 x 10.55 11/16 11/16 7/8 1 1/2 x 1 1/2 x 3/40.45 11/16 11/16 11/32 1 1/2 x 1 1/2 x 1/20.40 1/2 1/2 11/32 1 1/2 x 1 1/4 x 1 1/20.6211/32 13/16 29/32 1 1/2 x 1 1/4 x 1 1/40.62 31/32 13/32 31/32 1 1/2 x 1 1/4 x 10.51 25/32 111/32 1 1/2 x 1 1/4 x 3/40.49 11/16 13/16 11/32 1 1/2 x 1 1/4 x 1/20.41 1/2 25/32 11/32 1 1/2 x 1 x 1 1/20.5911/32 111/32 29/32 1 1/2 x 1 x 1 1/40.63 29/32 11/8 11/16 1 1/2 x 1 x 10.54 25/32 11/16 11/32 1 1/2 x 1 x 3/40.44 11/16 31/32 15/16 1 1/2 x 1 x 1/20.39 1/2 25/32 11/32 Continues… APPROX.DIMENSIONS NET WT.INCHES NOM.SIZELBS.CFG 1 1/2 x 3/4 x 1 1/20.6211/32 17/16 11/16 §1 1/2 x 3/4 x 1 1/40.58 29/32 111/32 11/16 1 1/2 x 3/4 x 10.54 25/32 11/4 11/32 1 1/2 x 3/4 x 3/40.47 11/16 13/32 29/32 §1 1/2 x 3/4 x 1/20.39 1/2 29/32 31/32 1 1/2 x 1/2 x 1 1/20.6211/32 113/32 31/32 21.3019/32 19/32 11/32 2 x 2 x 2 1/22.3422121/32 2 x 2 x 1 1/21.2113/32 13/32 13/8 2 x 2 x 1 1/41.12 15/16 15/16 111/32 2 x 2 x 10.90 27/32 27/32 11/4 2 x 2 x 3/40.88 19/32 19/32 11/4 2 x 2 x 1/20.77 19/32 19/32 15/16 2 x 1 1/2 x 21.2719/32 15/8 111/32 2 x 1 1/2 x 1 1/21.1813/32 115/32 13/8 2 x 1 1/2 x 1 1/41.12 15/16 19/32 111/32 2 x 1 1/2 x 3/40.83 21/32 15/16 17/32 2 x 1 1/2 x 1/20.79 11/16 29/32 15/16 2 x 1 1/4 x 21.3319/32 17/8 19/32 2 x 1 1/4 x 1 1/21.1413/32 17/16 111/32 2 x 1 1/4 x 1 1/41.19 15/16 111/32 111/32 2 x 1 1/4 x 10.90 27/32 19/32 111/32 §2 x 1 1/4 x 3/40.85 21/32 115/16 2 x 1 x 21.3211/8 125/32 111/32 2 x 1 x 10.89 27/32 19/32 111/32 2 x 3/4 x 21.3119/32 23/16 19/32 2 x 1/2 x 21.3519/32 23/8 11/32 2 1/22.4015/8 15/8 15/8 2 1/2 x 2 1/2 x 21.9715/16 15/16 121/32 2 1/2 x 2 1/2 x 1 1/21.5313/32 13/32 121/32 2 1/2 x 2 1/2 x 1 1/41.7213/32 13/32 127/32 2 1/2 x 2 1/2 x 11.34 25/32 25/32 111/16 2 1/2 x 2 1/2 x 3/41.34 25/32 25/32 113/16 2 1/2 x 2 1/2 x 1/21.34 25/32 25/32 21/8 2 1/2 x 2 x 2 1/21.99121/32 23/32 121/32 2 1/2 x 2 x 21.95111/32 15/8 123/32 2 1/2 x 2 x 1 1/21.5713/32 213/32 121/32 2 1/2 x 2 x 1 1/41.5713/32 119/32 127/32 2 1/2 x 2 x 11.40 25/32 19/32 13/4 2 1/2 x 2 x 3/41.35 25/32 19/32 127/32 Continues… APPROX.DIMENSIONS NET WT.INCHES NOM.SIZELBS.CFG 2 1/2 x 1 1/2 x 1 1/21.7613/32 113/32 13/8 2 1/2 x 1 1/4 x 2 1/22.40121/32 27/16 121/32 2 1/2 x 1 x 2 1/22.04121/32 223/32 121/32 2 1/2 x 3/4 x 2 1/22.00121/32 211/16 121/32 2 1/2 x 1/2 x 2 1/22.4611/2 27/32 11/2 33.1517/8 17/8 21/32 3 x 3 x 2 1/23.55129/32 129/32 23/8 3 x 3 x 23.19115/32 115/32 131/32 3 x 3 x 1 1/23.08115/32 115/32 29/32 3 x 3 x 1 1/43.10115/32 115/32 27/16 3 x 3 x 12.12 27/32 27/32 131/32 3 x 3 x 3/42.39 27/32 27/32 23/16 3 x 3 x 1/21.82 27/32 27/32 23/8 3 x 2 1/2 x 33.0817/8 23/8 131/32 3 x 2 1/2 x 2 1/23.12129/32 211/32 25/32 3 x 2 1/2 x 22.28115/32 127/32 131/32 3 x 2 x 33.62129/32 217/32 115/16 3 x 2 x 2 1/23.56129/32 29/16 25/16 3 x 2 x 23.22115/32 131/32 131/32 3 x 1 1/2 x 33.13129/32 225/32 23/32 3 x 1 1/4 x 33.63129/32 225/32 115/16 3 x 1 x 33.20131/32 219/32 23/16 3 x 3/4 x 33.55131/32 229/32 23/16 3 1/25.20217/32 217/32 217/32 48.12213/32 213/32 217/32 4 x 4 x 36.7021/32 21/32 221/32 4 x 4 x 2 1/26.6521/32 21/32 35/32 4 x 4 x 25.82115/32 115/32 27/16 4 x 4 x 1 1/23.94111/32 111/32 217/32 4 x 4 x 1 1/44.04111/32 111/32 229/32 4 x 4 x 13.721129/16 4 x 4 x 3/43.7011211/16 4 x 4 x 1/23.58113 4 x 3 x 47.05225/32 37/32 217/32 4 x 3 x 35.0321/32 215/32 215/32 §4 x 3 x 2 1/25.0421/32 215/32 229/32 4 x 3 x 25.87115/32 131/32 27/16 4 x 2 1/2 x 47.19225/32 315/32 227/32 4 x 2 x 47.08225/32 319/32 227/32 Continued on next page. NOTE:Tee sizes are readRun x Run x Outlet. 611 Tee C x C x C – Wrot continued 735 Cross C x C x C x C – Cast APPROX.DIM.A NOM.SIZENET WT./LBS.INCHES §3/80.09 3/8 1/20.15 7/16 3/40.30 9/16 10.54 23/32 1 1/40.78 7/8 1 1/21.051 22.0011/4 §2 1/22.9611/2 Wrot and Cast Pressure Fittings NIBCO INC. World Headquarters n 1516 Middlebury St. n Elkhart, IN46516-4714 U.S.A. n www.nibco.com 13 n CROSSES n ELBOWS §Made to Order.Consult price sheet for minimum order quantities. 606 45°Elbow C x C – Wrot APPROX.DIM.CDIM.D NOM.SIZENET WT./LBS.INCHESINCHES 1/80.01 1/4 1/4 §1/40.02 9/32 9/32 3/80.03 3/16 3/16 1/20.04 9/32 9/32 5/80.09 15/32 15/32 3/40.10 11/32 11/32 §7/80.20 11/16 11/16 10.16 3/8 3/8 1 1/40.25 17/32 17/32 1 1/20.35 19/32 19/32 20.65 25/32 25/32 2 1/21.07 29/32 29/32 31.5811/8 11/8 43.3517/16 17/16 511.0519/16 19/16 616.9522 823.0029/32 29/32 606-2 45° Fitting Elbow Ftg x C – Wrot APPROX.DIM.BDIM.C NOM.SIZENET WT./LBS.INCHESINCHES 1/40.02 9/16 1/4 1/20.04 3/4 7/32 5/80.0811/8 13/32 3/40.1011/16 5/16 10.1617/32 15/32 1 1/40.25119/32 17/32 1 1/20.35125/32 19/32 20.6523/16 25/32 2 1/21.0723/16 29/32 31.55219/32 15/32 706-2 45° Fitting Elbow Ftg x C – Cast APPROX.DIM.BDIM.C NOM.SIZENET WT./LBS.INCHESINCHES 44.31311/32 15/16 607 90° Elbow – Close Rough C x C – Wrot APPROX.DIM.CDIM.D NOM.SIZENET WT./LBS.INCHESINCHES 1/80.01 13/32 13/32 1/40.02 9/32 9/32 3/80.03 1/2 1/2 1/20.04 3/8 3/8 1/2 x 3/80.04 9/16 21/32 3/40.10 17/32 17/32 3/4 x 5/80.12 29/32 7/8 3/4 x 1/20.10 17/32 3/4 10.21 23/32 23/32 1 x 3/40.16 23/32 5/8 1 1/40.3111/32 11/32 1 1/4 x 10.3115/8 115/32 1 1/20.4617/32 17/32 1 1/2 x 1 1/40.3515/32 13/32 20.8411/2 11/2 2 x 1 1/20.5817/16 11/4 2 1/21.41127/32 127/32 32.0723/32 23/32 3 1/22.9423/8 23/8 44.23225/32 225/32 5 7.7427/8 27/8 610.9537/16 37/16 8 29.50423/32 423/32