The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR Series
Quick Response
Standard Spray
Bu
l
l
e
t
i
n
0
1
4
R
e
v
.
I
Bulletin 014 Rev. I
Model F1FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model F1FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model F1FR56 Concealed Sprinkler Types
Standard Pendent
Model F1FR42, F1FRXLH & F1FR28 Sprinkler
Types
Standard Upright
Standard Pendent
Model F1FR42, F1FRXLH & F1FR28 Recessed
Sprinkler Types
Standard Pendent
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada (cULus).
2. Factory Mutual Approvals (FM)
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverhütung GmbH
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56, F1FR42, F1FRXLH & F1FR28
Series Sprinklers are quick response sprinklers which
combine the durability of a standard sprinkler with the
attractive low profile of a decorative sprinkler.
The Models F1FR56, F1FR42, F1FRXLH & F1FR28
Series Recessed automatic sprinklers utilize a 3.0 mm
frangible glass bulb. These sprinklers have demonstrat-
ed response times in laboratory tests which are five to
ten times faster than standard response sprinklers. This
quick response enables the Model F1FR56, F1FR42,
F1FRXLH & F1FR28 Series sprinklers to apply water to
a fire much faster than standard sprinklers of the same
temperature rating.
The glass bulb consists of an accurately controlled
amount of special fluid hermetically sealed inside a pre-
cisely manufactured glass capsule. This glass bulb is
specially constructed to provide fast thermal response.
PendentConventional
Recessed
Pendent/F1/F2
Upright
Vertical SidewallHorizontal Sidewall
Recessed
Horizontal Sidewall
Recessed
Pendent/FP
Concealed
Pendent
XLH UprightXLH Pendent XLH Recessed
Pendent F1/F2
XLH Recessed
Pendent FP
At normal temperatures, the glass
bulb contains the fluid in both the
liquid and vapor phases. The vapor
phase can be seen as a small bub-
ble. As heat is applied, the liquid
expands, forcing the bubble smaller
and smaller as the liquid pressure
increases. Continued heating forces
the liquid to push out against the bulb, causing the glass
to shatter, opening the waterway and allowing the deflec-
tor to distribute the discharging water.
2.
Technical data:
ModelsDischarge Coeffi cientResponse Thread
Size
Max.
Working
Pressure
Min.
Working
Pressure
Temperature
Rating Finish
F1FR56 K 5.6
Quick
Response
1/2” NPT
(R1/2)175 PSI7 PSI
See
“Temperature
Ratings” Table.
See
“Finish Table”
F1FR42
F1FRXLH K 4.2
F1FR28 K 2.8
Material Data:
FrameDefl ectorLoad ScrewPintleCupWasherBulb
DZR Brass
QM Brass
CDA Alloy 260,
CDA Alloy 220
or
CDA Alloy510
CDA Alloy 360
or
CDA Alloy 544
CDA Alloy 360
or
CDA Alloy 544
CDA Alloy 651
or
CDA Alloy 693
Nickel Alloy 440 or Alloy 360
coated with PTFE Adhesive
Tape
Glass
Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-
sponse sprinklers should not be intermixed.
Model F1FR42, F1FRXLH Upright
Pendent ConventionalUpright
Model F1FR56, F1FRXLH & F1FR28 F1 or F2
Model F1FR56, Upright, Pendent & Conventional Sprinklers
Model F1FR42, F1FRXLH & F1FR28 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifi ce
ThreadNominal K Factor SprinklerApproval Sprinkler Identifi cation Number
(SIN)
SizeUSMetricHeightOrganization Upright Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
1/2” (15mm) (1)1/2” NPT (R1/2)5.6802.25” (57mm)1,2,3,4RA1425(1)(2)(3)RA1414(1)(2)(3)
7/16” (10mm)1/2” NPT (R1/2)4.2602.25” (57mm)1RA1423(1)RA1413
3/8” (10mm)1/2” NPT (R1/2)2.8402.25” (57mm)1RA1421(1)RA1411
Conventional-Install in Upright or Pendent Position
15mm (1)1/2” NPT (R1/2)5.68057mm3, 4RA1475(3)
(1) cULus listed corrosion resistant (Polyester coated) sprinkler.
(2) Polyester coated FM approved sprinkler.
(3) Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475.
Model F1FR56, F1FRXLH & F1FR28 FP
Model F1FR56, F1FR42, F1FRXLH & F1FR28 Quick Response Recessed Pendent Sprinkler(1)
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifi ce
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identifi cation Number
(SIN)USMetric
1/2” (15mm)1/2” NPT(R½)5.6802.25” (57mm)RA1414
7/16” (10mm)1/2” NPT (R1/2)4.2602.25” (57mm)RA1413
3/8” (10mm)1/2” NPT (R1/2)2.8402.25” (57mm)RA1411
(1) Refer to escutcheon data table for approvals & dimensions
3.
4.
Model F1FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal
Orifi ce Thread Size
Nominal K Factor Sprinkler
Height
Approval
Organizations
Sprinkler
Identifi cation
Numbers (SIN)USMetric
½” (15mm)½” NPT (R1/2)5.68.02.25” (57mm)1,2,3,4 RA1485(2)
15mm½” NPT (R1/2)5.68.02.25” (57mm)4(1)
(1) LPC Approval is for pendent position only.
(2) cULus Listed corrosion resistant (Polyester coated) sprinkler.
Sprinkler TypeDefl ector to Ceiling Distance
(Min. - Max.)
Upright4” (102mm) - 12” (305mm)
Pendent4” (102mm) - 12” (305mm)
Model F1FR56 Quick Response Horizontal Sidewall Sprinkler
Defl ector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal Orifi ceThread Size
Nominal K Factor Sprinkler
Height
Approval Organizations
and Type of Approval Sprinkler
Identifi cation
Numbers (SIN)USMetricLight Hazard Ordinary
Hazard
½” (15mm)½” NPT (R1/2)5.6802.63” (67mm)1,21RA1435(1)(2)
(1) cULus Listed corrosion resistant (Polyester coated) sprinkler.
(2) Polyester coated FM approved sprinkler.
Horizontal Sidewall
Vertical Sidewall
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
Model F1FR56 Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC1 Sprinkler Wrench
Technical Data:
Nominal
Orifi ce
“K” Factor Thread
Size Model
Temp. RatingMax.
Ambient
Temp
Bulb
Color Approvals
Sprinkler
Identifi cation
Number(SIN)USMetricSprinklerCover
½” (15mm)5.680½” NPTF1FR135°F/57°C135°F/57°C100°F/38°COrange1RA1414
½” (15mm)5.680½” NPTF1FR155°F/68°C135°F/57°C100°F/38°CRed1, 4(1)RA1414
½” (15mm)5.680½” NPTF1FR175°F/79°C165°F/74°C100°F/38°CYellow1RA1414
½” (15mm)5.680½” NPTF1FR200°F/93°C165°F/74°C150°F/65°CGreen1RA1414
(1) For VdS only = 155°F/68°C Norbulb and 1/2” [12,7mm] adjustment.
Figure 1 Figure 2
Installation Aid
A protective cap is included for use during installation.
Important: The F1FR56 Sprinkler with Model CCP cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and standard
response sprinklers should not be intermixed.
The Model F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed
Quick Response Sprinklers are to be installed as shown. The
Model F1 or F2 Escutcheons illustrated are the only recessed
escutcheons to be used with the Model F1FR56, F1FR42,
F1FRXLH & F1FR28 Sprinklers. The use of any other recessed
escutcheon will void all approvals and negate all warranties.
When installing Model F1FR56, F1FR42, F1FRXLH & F1FR28
Sprinklers, use the Model D Sprinkler Wrench. Use the Mod-
el GFR2 Wrench for installing F1FR56, F1FR42, F1FRXLH
& F1FR28 Recessed Pendent Sprinklers. Any other type of
wrench may damage these sprinklers.
NOTE: A leak tight ½” NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It may
cause leakage or impairment of the sprinklers.
The Model F1FR56/ CCP Concealed Sprinkler uses the ½” ori-
fice, ½” NPT (R1/2), 135°F (57°C), 155°F (68°C), 175°F (79°C) or
200°F (93°C) Model F1FR56 Pendent Sprinkler with a threaded
Model CCP cup which is factory attached to the sprinkler. The
assembly is completed by the installation of the attractive, low
profile, 135°F (57°C) or 165°F (74°C) rated Model CCP push
on cover plate assembly. The cover plate and sprinkler cup as-
semblies are joined using a cover plate skirt with flexible tabs for
threaded engagement. A choice of two cover plate assemblies
provide either ½” (13mm) or 5/16” (8mm) of cover adjustment.
Do not install these sprinklers in ceiling which have positive
pressure in the space above.
After a 25/8” (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model RC1 Wrench. A Tef-
lon* based thread sealant should be applied to the sprinkler
threads only. The Model RC1 Wrench is then used to engage
the sprinkler wrenching surfaces and to install the sprinkler in the
fitting. When inserting or removing the wrench from the sprin-
kler/cup assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF
THE SPRINKLER. The cover plate is then pushed onto the cup.
Final adjustment is made by hand turning the cover plate until
the skirt flange makes full contact with the ceiling. Cover plate
removal requires turning in the counter clockwise direction.
5.
*DuPont Registered Trade Mark
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 07/12 P/N 9999970300
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
After installation, inspect all sprinklers to ensure that there is a gap
between the cover plate and ceiling and that the four cup slots are
open and free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for use with
specific sprinklers. The use of any other concealed cover plate/cup
assembly with the Model F1FR56 Pendent Sprinkler or the use of the
Model CCP Concealed cover plate assembly on any sprinkler with
which it is not specifically listed my prevent good fire protection and
will void all guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. REMOVE
THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS
PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the
protectors before this time may leave the bulb vulnerable to dam-
age. RASCO wrenches are designed to install sprinklers when
covers are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.
Temperature Ratings
Classifi cation
Sprinkler
Temperature Max. Ambient
Temp.Bulb Color
°C°F
Ordinary
Ordinary
Intermediate
Intermediate
High (1)
57
68
79
93
141
135
155
175
200
286
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
(1) Not available for recessed sprinklers.
Escutcheon Data (1)
(1) SIN RA1435 – cULus permits use with F1, F2 or FP escutcheons for “light
hazard” only, while FM limits use for same hazard with F2 escutcheon only.
Maintenance
The Model F1FR56, F1FR42, F1FRXLH and Model F1FR56,
F1FR42, F1FRXLH & F1FR28 Recessed Sprinklers should be in-
spected quarterly and the sprinkler system maintained in accor-
dance with NFPA 25. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by using a soft
brush or gentle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation, sprin-
klers should be maintained in the original cartons and packaging
to minimize the potential for damage to sprinklers that would cause
improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes (1)
Standard Finishes
SprinklerEscutcheonCover plate(1)
Bronze
Chrome Plated
Polyester
Coated (4)(5)(6)
Brass
Chrome
Plated
White Painted
Chrome
White
Special Application Finishes
SprinklerEscutcheonCover plate(1)
Bright Brass (3)
Black Plated
Black Paint (2)(6)
Off White (2)(6)
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Satin
Off White
Black Paint
Black Plated
(1) Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
(2) cULus Listed only.
(3) 200°F (93°C) maximum.
(4) cULus listed “corrosion resistance” applies to SIN Numbers RA1435
(HSW), RA1485(VSW), RA1425 (Upright) and RA1414 (Pendent) in
standard black or white. Corrosion resistance in other polyester colors is
available upon request.
(5) FM Approvals finish as “Polyester coated” applies to SIN Number
RA1414 (Pendent) in standard black or white.
(6) LPCB and VdS Approved finish applies only to RA1425, RA1414 and RA1475.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
9. Cover plate Model
10. Cover plate Thread size
11. Cover plate Temperature
12. Cover plate Adjustment
13. Cover plate Finish
Note: When Model F1FR56 Recessed sprinklers are ordered, the sprinklers
and escutcheons are packaged separately.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F3QR
Quick Response
Dry Sprinklers
Bu
l
l
e
t
i
n
1
5
7
Re
v
.
I
Bulletin 157 Rev. I
Features
1. The Model F3QR sprinkler utilizes Belleville Spring
Closure Technology. Reliable is the first in the industry
to produce a Quick Response Dry Concealed sprin-
kler utilizing this technology.
2. Styles available
• Pendent
• Recessed FP Pendent
• Recessed F1 Pendent
• Concealed
• Horizontal Sidewall
• Recessed FP Horizontal Sidewall
• Recessed F1 Horizontal Sidewall
3. 1½” (38mm) escutcheon adjustment on pendent sprinkler.
4. ½” (13mm) escutcheon adjustment on recessed sprin-
kler with push-on/ thread-off FP Model Escutcheon ring.
5. 3/8” (9.5mm) cover plate adjustment on concealed
sprinkler with push-on/ thread-off CCP Cover Plate.
6. 3/4” (19mm) escutcheon adjustment on recessed
sprinkler with F1 Escutcheon.
7. Attractive appearance. Employs 3mm frangible glass
bulb and galvanized nipple.
8. Lengths available to accommodate installation di-
mensions from 2” - to - 48” (51mm - to - 1219mm), in
¼” (6mm) increments. See specific styles for correct
“A” dimension range.
9. Available in a variety of plated and painted finishes.
10. Polyester Coated Corrosion Resistant Sprinklers.
US Patent Numbers 5,775,431 and 5,967,240.
Other US Patents pending.
Approvals
1. Listed by Underwriters Laboratories Inc. and UL
Certified for Canada (cULus)
StyleResponse Sprinkler
System Type Hazard
Pendent
Recessed Pendent
Recessed F1 Pendent
CCP Concealed
(R5714)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
Ordinary
Horizontal Sidewall
Recessed Horizontal Sidewall
(R5734)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
2. Certified by FM Approvals
StyleResponse Sprinkler
System Type Hazard
Pendent
Recessed F1 Pendent
(R5714)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
Ordinary,
Groups
1&2
Horizontal Sidewall
Recessed F1 Horizontal Sidewall
(R5734)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
3. NYC MEA 258-93-E
Concealed
(See Fig. 4)
Recessed FP Pendent
(See Fig. 3)
Recessed F1
Horizontal Sidewall
(See Fig. 9)
Horizontal Sidewall
(See Fig. 6)
Pendent
(See Fig. 1)
Recessed F1 Pendent
(See Fig. 5)
Recessed FP
Horizontal Sidewall
(See Fig. 8)
Pendent / HB
(See Fig. 2)
Horizontal Sidewall / HB
(See Fig. 7)
2.
Model F3QR Dry Pendent Sprinkler
“A” Dim.2” to 48” (51mm to 1219mm) in ¼” (6mm) increments
Finishes(1)
SprinklerEscutcheon
Bronze
Chrome Plated
White Polyester (2)
Brass (3)
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
(3) Not available for HB escutcheons.
Model F3QR Dry Recessed FP Pendent Sprinkler
“A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments
Finishes(1)
SprinklerEscutcheon
Bronze
Chrome Plated
White Polyester (2)
Brass
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details. Cup remainds unfinished.
Only the escutcheon will contain desired finish.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Classifi cation
Sprinkler
Temperature
Rating
Max.
Ambient
Temp.
Bulb Color
Ordinary
Ordinary
Intermediate (1)
Intermediate
High (1)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
Sprinkler cup and FP Escutcheon fabricated of steel and recommended
for interior applications.
(1) Listed and Certifi ed only by cULus.
Note: The sprinkler can protrudes ¼” when escutcheon is in nominal
position. Escutcheon adjustment provides -¼” (-6mm) to +1¼”
(+32mm) “A” dimension adjustment range.
Fig. 1
Note: Do not install the Model F3QR Dry Recessed FP Pendent Sprin-
kler in ceilings which have positive pressure in space above.
Fig. 3
Note: The sprinkler can protrudes 1¼” when escutcheon is in nomi-
nal position. Escutcheon adjustment provides -½” (-12.7mm) to
+½” (+12.7mm) “A” dimension adjustment range.
Fig. 2
Model F3QR Dry Pendent w/HB Escutcheon
“A” Dim.3½” to 48” (89mm to 1219mm) in ¼” (6mm) increments
Standard Temperature Ratings
Classifi cation
Sprinkler
Temperature
Rating
Max.
Ambient
Temp.
Bulb Color
Ordinary
Ordinary
Intermediate (1)
Intermediate
High (1)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications.
(1) Listed and Certifi ed only by cULus.
Sprinkler Guard: Model C-2
Sprinkler Installation Wrench: Model G3 Sprinkler Wrench
Sprinkler Identifi cation Number (SIN): R5714
Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench
Sprinkler Identifi cation Number (SIN): R5714
3.
Model F3QR Dry Pendent Concealed Sprinkler
“A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments
CCP Cover Plate (1) Finishes (2)
Standard FinishesSpecial Application Finishes
Chrome Plated
White
Bright Brass Plated
Black Plated
Black Paint
Off White
Satin Chrome
(1) Utilizes the 1/2” cover plate with 3/8” total adjustment.
(2) Other finishes and colors are available on special order.
Consult factory for details.
Standard Temperature Ratings
Classifi cation
Sprinkler
Temperature
Rating
Cover Plate
Temp. Rating
Max.
Ambient
Temp.
Ordinary
Ordinary
Intermediate (1)
Intermediate
High (1)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
135°F (57°C)
165°F (74°C)
165°F (74°C)
165°F (74°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
150°F (66°C)
Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of
brass and recommended for interior applications.
(1) Listed and Certifi ed only by cULus.
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identifi cation Number (SIN): R5714
Note: Do not install the Model F3QR Dry Concealed Pendent Sprinkler
in ceilings which have positive pressure in the space above.
Fig. 4
Model F3QR Dry Recessed F1 Pendent Sprinkler
“A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments
Finishes (1)
SprinklerEscutcheonCollar
Chrome Plated
White Polyester (2)
Chrome Plated
White
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Classifi cation
Sprinkler
Temperature
Rating
Max.
Ambient
Temp.
Bulb Color
Ordinary
Ordinary
Intermediate (1)
Intermediate
High (1)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
(1) Listed and Certifi ed only by cULus.
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identifi cation Number (SIN): R5714
Fig. 5
4.
Model F3QR Dry Recessed FP Horizontal Sidewall Sprinkler
• Listed by cULus for Quick Response. Approved by FM for
Standard Response.
• Recessed Horizontal sidewall sprinklers are listed with cULus
for installation of min. 4” (100mm) - to - max. 6” (150mm) below
ceiling and approved by FM for installation of min. 4” (100mm)
- to - max. 12” (300mm) below ceiling.
“A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments
Finishes (1)
SprinklerEscutcheon
Bronze
Chrome Plated
White Polyester (2)
Brass
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details. Cup remainds unfinished. “See page 2”
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Classifi cation Sprinkler Tem-
perature Rating
Max.
Ambient Temp.Bulb Color
Ordinary
Ordinary
Intermediate (1)
Intermediate
High (1)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
(1) Listed and Certifi ed only by cULus.
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identifi cation Number (SIN): R5734
Notes: Do not install the Model F3QR Dry Recessed FP Horizontal
Sidewall Sprinkler in walls which have positive pressure in their
side space.
Fig. 8
Model F3QR Dry Horizontal Sidewall Sprinkler
“A” Dim.2” to 48” (51mm to 1219mm) in ¼” (6mm) increments
Finishes(1)
SprinklerEscutcheon
Bronze
Chrome Plated
White Polyester (2)
Brass (3)
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
(3) Not available for HB escutcheons.
Note: The sprinkler can protrudes ¼” when escutcheon is in nominal
position. Escutcheon adjustment provides -¼” (-6mm) to +1¼”
(+32mm) “A” dimension adjustment range.
Fig. 6
Note: The sprinkler can protrudes 1¼” when escutcheon is in nomi-
nal position. Escutcheon adjustment provides -½” (-12.7mm) to
+½” (+12.7mm) “A” dimension adjustment range.
Fig. 7
Model F3QR Dry HSW w/HB Escutcheon
“A” Dim.2” to 48” (51mm to 1219mm) in ¼” (6mm) increments
Standard Temperature Ratings
Classifi cation
Sprinkler
Temperature
Rating
Max.
Ambient
Temp.
Bulb Color
Ordinary
Ordinary
Intermediate (1)
Intermediate
High
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications.
(1) Listed and Certifi ed only by cULus.
Sprinkler Installation Wrench: Model G3 Sprinkler Wrench
prinkler Identifi cation Number (SIN): R5734
5.
Model F3QR Dry Recessed F1 Horizontal Sidewall Sprinkler
• Listed by cULus for Quick Response. Approved by
FM for Standard Response.
• Recessed Horizontal sidewall sprinklers are listed
with cULus for installation of min. 4” (100mm) - to
- max. 6” (150mm) below ceiling and approved by
FM for installation of min. 4” (100mm) - to - max. 12”
(300mm) below ceiling.
“A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments
Finishes (1)
SprinklerEscutcheonCollar
Chrome Plated
White Polyester (2)
Chrome Plated
White
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Classifi cation
Sprinkler
Temperature
Rating
Max.
Ambient
Temp.
Bulb Color
Ordinary
Ordinary
Intermediate (1)
Intermediate
High (1)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
(1) Listed and Certifi ed only by cULus.
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identifi cation Number (SIN): R5734
Technical Data:
Orifice Size: ½” (15mm)
Thread Size: 1” NPT per ANSI B2.1
Working Pressure: 175 psi (12 bar)
Nominal K Factor - US / (Metric): 5.6 / (80)
Product Description
Reliable Model F3QR Dry Sprinklers are quick response sprinklers
utilizing a durable 3mm frangible glass bulb. This quick response
enables these sprinklers to apply water to a fire much sooner than
standard response sprinklers of the similar temperature rating.
Model F3QR Dry Sprinklers are intended for use in dry and preac-
tion systems and in areas subjected to freezing temperatures, such
as freezers and unheated portions inside and outside buildings.
Environments wherein dry sprinklers are employed can be cor-
rosive. For this reason, Model F3 Sprinklers have a special wax fillet
placed in the gap between the cup that supports the bulb and the
wrenching boss. This wax will not interfere with the operation of the
sprinkler, and it prevents contaminents from entering the internal
portion of the drop nipple. The wax must not be removed.
Operation
The glass bulb consists of an accurately controlled amount of
special fluid hermetically sealed inside a precisely manufactured
glass capsule. This glass bulb is specially constructed to provide
fast thermal response. When the temperature increases sufficiently,
due to a fire, the bulb shatters allowing operating parts to clear the
waterway. This enables the inlet seal to release air or water and
subsequently, cause water flow over the deflector in a uniform
spray pattern, controlling or extinguishing the fire.
Ordering Information
Specify:
1. Sprinkler Type (select one):
(a) Model F3QR Dry Pendent
(b) Model F3QR Dry Pendent/HB
(c) Model F3QR Dry Recessed FP Pendent
(d) Model F3QR Dry Recessed F1 Pendent
(e) Model F3QR Dry Concealed Pendent
(f) Model F3QR Dry Horizontal Sidewall
(g) Model F3QR Dry Horizontal Sidewall/HB
(h) Model F3QR Dry Recessed FP Horizontal Sidewall
(i) Model F3QR Dry Recessed F1 Horizontal Sidewall
2. Sprinkler Temperature Rating.
3. Sprinkler Finish.
4. Escutcheon type (F1 or FP).
5. Cover Plate/Escutcheon Finish.
6. Length:
“A” Dimension (face of tee to face of ceiling or wall) in ¼”
(6mm) increments.
7. Model F3QR Dry Pendent (a) is available without
sprinkler can and escutcheon.
Note:
1. The “A” dimension is based on a nominally gauged
pipe thread “make-up” of 0.600” (15mm) per ANSI
B2.1 [7½ threads approximately].
2. All platings and paintings are decorative and intend-
ed for interior use.
Fig. 9
General Installation Instructions
Model F3QR dry sprinklers must be installed only in stan-
dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125)
pipe tees in the horizontal position, even at branch line ends.
They should not be installed into elbows or pipe couplings
located on drop nipples to the sprinklers. For these and
other fittings including CPVC*, the dry sprinkler should be
installed into a fitting to allow protrusion into the fitting in ac-
cordance with the diagrams. The “A” dimension of the dry
sprinkler, which extends into the freezers or a freezing zone
from wet pipe systems, should be selected to provide, as a
minimum, the specified lengths in inches shown in Fig. 10.
Caution:
Do not install Model F3QR Dry sprinklers into CPVC
adapter fittings or tees that have an internal obstruction.
This will damage the sprinkler and /or the fitting. Refer to
Fig. 11.
During installation, the following steps must be followed:
1. Cut the specified size hole (see illustrations) for the sprin-
kler in the ceiling or wall directly in line with the tee.
2. Apply pipe joint compound to the 1” (25mm) pipe
threads and install sprinkler using the Model G3 or
G3 R/C Sprinkler Wrench as specified.
3. Install the Model FP push-on / thread-off escutcheon
or CCP cover plate if required.
Note: Installation of the Model F3QR Sprinklers is not rec-
ommended in copper pipe systems, as this may reduce
the life expectancy of the sprinklers.
Model F3QR Concealed and Recessed In-
stallation Instructions
• The Model G3 R/C wrench (Fig. 12) is designed to
locate on the wrenching pads of the recessed sprin-
kler while centering in the cup. A standard ½” drive
ratchet may be used to drive this wrench. Fig. 13 and
Fig. 14 show sequentially the insertion of the wrench.
First the wrench, with its jaws above the sprinkler de-
flector, is moved laterally until centered with the cup.
Then raise the wrench inside of the cup until its jaws
engage the sprinkler’s square wrenching pads (Fig.
14). To remove the wrench, follow this procedure in
reverse order. Care should be taken to avoid striking
the deflector, with the wrench.
• Model G3 Wrench (Fig. 15) is used for installation of
Pendent and Horizontal Sidewall sprinklers.
• Glass bulb sprinklers have orange bulb protectors
to minimize bulb damage during shipping, handling
and installation. REMOVE THIS PROTECTION AT THE
TIME THE SPRINKLER SYSTEM IS PLACED IN SER-
VICE FOR FIRE PROTECTION. Removal of the pro-
tectors before this time may leave the bulb vulnerable
to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PRO-
TECTORS BY UNDOING THE CLASP BY HAND. DO
NOT USE TOOLS TO REMOVE THE PROTECTORS.
Maintenance
The Model F3QR Quick Response Dry Sprinklers should
be inspected quarterly and the sprinkler system maintained
in accordance with NFPA 25. Do not remove the factory
applied thermally sensitive wax fillet between the bulb sup-
porting cup and the wrenching boss. Do not replace this
wax with a substitute substance. An Alternate substance
may interfere with proper operation of the sprinkler. Do not
clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gently
vacuuming. Remove any sprinkler which has been painted
(other than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non-operation.
Caution:
Use specified by RASCO wrenches only, which are
designed to engage sprinkler’s wrenching pad. (Fig. 15,
page 9)
6.
Fig. 10
7.
8.
Fig. 11
Fig. 13 - G3 R/C Wrench
Fig. 15 - G3 Wrench
Fig. 14 - G3 R/C WrenchFig. 12 - G3 R/C Wrench
9.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 05/12 P/N 9999970175
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water fl ow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identifi cation signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection