HomeMy WebLinkAboutF12-0065 stamped approvedF1 2 - 0 0 6 5 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Model F1FR Series Quick Response Standard Spray Bu l l e t i n 0 1 4 R e v . I Bulletin 014 Rev. I Model F1FR56 Sprinkler Types Standard Upright Standard Pendent Conventional Vertical Sidewall Horizontal Sidewall Model F1FR56 Recessed Sprinkler Types Standard Pendent/F1/F2/FP Horizontal Sidewall Model F1FR56 Concealed Sprinkler Types Standard Pendent Model F1FR42, F1FRXLH & F1FR28 Sprinkler Types Standard Upright Standard Pendent Model F1FR42, F1FRXLH & F1FR28 Recessed Sprinkler Types Standard Pendent Listing & Approvals 1. Underwriters Laboratories Inc. and Certified for Canada (cULus). 2. Factory Mutual Approvals (FM) 3. Loss Prevention Council (LPCB, UK) 4. VdS Schadenverhütung GmbH UL Listing Category Sprinklers, Automatic & Open (VNIV) Quick Response Sprinkler Product Description Reliable Models F1FR56, F1FR42, F1FRXLH & F1FR28 Series Sprinklers are quick response sprinklers which combine the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler. The Models F1FR56, F1FR42, F1FRXLH & F1FR28 Series Recessed automatic sprinklers utilize a 3.0 mm frangible glass bulb. These sprinklers have demonstrat- ed response times in laboratory tests which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1FR56, F1FR42, F1FRXLH & F1FR28 Series sprinklers to apply water to a fire much faster than standard sprinklers of the same temperature rating. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a pre- cisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response. PendentConventional Recessed Pendent/F1/F2 Upright Vertical SidewallHorizontal Sidewall Recessed Horizontal Sidewall Recessed Pendent/FP Concealed Pendent XLH UprightXLH Pendent XLH Recessed Pendent F1/F2 XLH Recessed Pendent FP At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bub- ble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the liquid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflec- tor to distribute the discharging water. 2. Technical data: ModelsDischarge Coeffi cientResponse Thread Size Max. Working Pressure Min. Working Pressure Temperature Rating Finish F1FR56 K 5.6 Quick Response 1/2” NPT (R1/2)175 PSI7 PSI See “Temperature Ratings” Table. See “Finish Table” F1FR42 F1FRXLH K 4.2 F1FR28 K 2.8 Material Data: FrameDefl ectorLoad ScrewPintleCupWasherBulb DZR Brass QM Brass CDA Alloy 260, CDA Alloy 220 or CDA Alloy510 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 651 or CDA Alloy 693 Nickel Alloy 440 or Alloy 360 coated with PTFE Adhesive Tape Glass Application Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re- sponse sprinklers should not be intermixed. Model F1FR42, F1FRXLH Upright Pendent ConventionalUpright Model F1FR56, F1FRXLH & F1FR28 F1 or F2 Model F1FR56, Upright, Pendent & Conventional Sprinklers Model F1FR42, F1FRXLH & F1FR28 Upright & Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Nominal Orifi ce ThreadNominal K Factor SprinklerApproval Sprinkler Identifi cation Number (SIN) SizeUSMetricHeightOrganization Upright Pendent Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position 1/2” (15mm) (1)1/2” NPT (R1/2)5.6802.25” (57mm)1,2,3,4RA1425(1)(2)(3)RA1414(1)(2)(3) 7/16” (10mm)1/2” NPT (R1/2)4.2602.25” (57mm)1RA1423(1)RA1413 3/8” (10mm)1/2” NPT (R1/2)2.8402.25” (57mm)1RA1421(1)RA1411 Conventional-Install in Upright or Pendent Position 15mm (1)1/2” NPT (R1/2)5.68057mm3, 4RA1475(3) (1) cULus listed corrosion resistant (Polyester coated) sprinkler. (2) Polyester coated FM approved sprinkler. (3) Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475. Model F1FR56, F1FRXLH & F1FR28 FP Model F1FR56, F1FR42, F1FRXLH & F1FR28 Quick Response Recessed Pendent Sprinkler(1) Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Size K Factor Sprinkler Height Sprinkler Identifi cation Number (SIN)USMetric 1/2” (15mm)1/2” NPT(R½)5.6802.25” (57mm)RA1414 7/16” (10mm)1/2” NPT (R1/2)4.2602.25” (57mm)RA1413 3/8” (10mm)1/2” NPT (R1/2)2.8402.25” (57mm)RA1411 (1) Refer to escutcheon data table for approvals & dimensions 3. 4. Model F1FR56 Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: Nominal Orifi ce Thread Size Nominal K Factor Sprinkler Height Approval Organizations Sprinkler Identifi cation Numbers (SIN)USMetric ½” (15mm)½” NPT (R1/2)5.68.02.25” (57mm)1,2,3,4 RA1485(2) 15mm½” NPT (R1/2)5.68.02.25” (57mm)4(1) (1) LPC Approval is for pendent position only. (2) cULus Listed corrosion resistant (Polyester coated) sprinkler. Sprinkler TypeDefl ector to Ceiling Distance (Min. - Max.) Upright4” (102mm) - 12” (305mm) Pendent4” (102mm) - 12” (305mm) Model F1FR56 Quick Response Horizontal Sidewall Sprinkler Defl ector: HSW Installation Wrench: Model D Sprinkler Wrench Installation Data: Horizontal Sidewall Nominal Orifi ceThread Size Nominal K Factor Sprinkler Height Approval Organizations and Type of Approval Sprinkler Identifi cation Numbers (SIN)USMetricLight Hazard Ordinary Hazard ½” (15mm)½” NPT (R1/2)5.6802.63” (67mm)1,21RA1435(1)(2) (1) cULus Listed corrosion resistant (Polyester coated) sprinkler. (2) Polyester coated FM approved sprinkler. Horizontal Sidewall Vertical Sidewall Note: For Recessed HSW Sprinklers use installation wrench GFR2. Model F1FR56 Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: Nominal Orifi ce “K” Factor Thread Size Model Temp. RatingMax. Ambient Temp Bulb Color Approvals Sprinkler Identifi cation Number(SIN)USMetricSprinklerCover ½” (15mm)5.680½” NPTF1FR135°F/57°C135°F/57°C100°F/38°COrange1RA1414 ½” (15mm)5.680½” NPTF1FR155°F/68°C135°F/57°C100°F/38°CRed1, 4(1)RA1414 ½” (15mm)5.680½” NPTF1FR175°F/79°C165°F/74°C100°F/38°CYellow1RA1414 ½” (15mm)5.680½” NPTF1FR200°F/93°C165°F/74°C150°F/65°CGreen1RA1414 (1) For VdS only = 155°F/68°C Norbulb and 1/2” [12,7mm] adjustment. Figure 1 Figure 2 Installation Aid A protective cap is included for use during installation. Important: The F1FR56 Sprinkler with Model CCP cover plate is not an FM Approved combination. Installation Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard response sprinklers should not be intermixed. The Model F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed Quick Response Sprinklers are to be installed as shown. The Model F1 or F2 Escutcheons illustrated are the only recessed escutcheons to be used with the Model F1FR56, F1FR42, F1FRXLH & F1FR28 Sprinklers. The use of any other recessed escutcheon will void all approvals and negate all warranties. When installing Model F1FR56, F1FR42, F1FRXLH & F1FR28 Sprinklers, use the Model D Sprinkler Wrench. Use the Mod- el GFR2 Wrench for installing F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed Pendent Sprinklers. Any other type of wrench may damage these sprinklers. NOTE: A leak tight ½” NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. The Model F1FR56/ CCP Concealed Sprinkler uses the ½” ori- fice, ½” NPT (R1/2), 135°F (57°C), 155°F (68°C), 175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent Sprinkler with a threaded Model CCP cup which is factory attached to the sprinkler. The assembly is completed by the installation of the attractive, low profile, 135°F (57°C) or 165°F (74°C) rated Model CCP push on cover plate assembly. The cover plate and sprinkler cup as- semblies are joined using a cover plate skirt with flexible tabs for threaded engagement. A choice of two cover plate assemblies provide either ½” (13mm) or 5/16” (8mm) of cover adjustment. Do not install these sprinklers in ceiling which have positive pressure in the space above. After a 25/8” (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model RC1 Wrench. A Tef- lon* based thread sealant should be applied to the sprinkler threads only. The Model RC1 Wrench is then used to engage the sprinkler wrenching surfaces and to install the sprinkler in the fitting. When inserting or removing the wrench from the sprin- kler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. The cover plate is then pushed onto the cup. Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning in the counter clockwise direction. 5. *DuPont Registered Trade Mark The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 07/12 P/N 9999970300 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impediment to the space above. Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any other concealed cover plate/cup assembly with the Model F1FR56 Pendent Sprinkler or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to dam- age. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO- TECTORS. Temperature Ratings Classifi cation Sprinkler Temperature Max. Ambient Temp.Bulb Color °C°F Ordinary Ordinary Intermediate Intermediate High (1) 57 68 79 93 141 135 155 175 200 286 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue (1) Not available for recessed sprinklers. Escutcheon Data (1) (1) SIN RA1435 – cULus permits use with F1, F2 or FP escutcheons for “light hazard” only, while FM limits use for same hazard with F2 escutcheon only. Maintenance The Model F1FR56, F1FR42, F1FRXLH and Model F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed Sprinklers should be in- spected quarterly and the sprinkler system maintained in accor- dance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replace- ment of damaged or operated sprinklers. Prior to installation, sprin- klers should be maintained in the original cartons and packaging to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Sprinkler Types Standard Upright Standard Pendent Conventional Recessed Pendent Vertical Sidewall Horizontal Sidewall Recessed Horizontal sidewall Concealed pendent Maximum Working Pressure 175 psi (12 bar) 100% Factory tested hydrostatically to 500 psi (34.5 bar) Finishes (1) Standard Finishes SprinklerEscutcheonCover plate(1) Bronze Chrome Plated Polyester Coated (4)(5)(6) Brass Chrome Plated White Painted Chrome White Special Application Finishes SprinklerEscutcheonCover plate(1) Bright Brass (3) Black Plated Black Paint (2)(6) Off White (2)(6) Satin Chrome Bright Brass Black Plated Black Paint Off White Satin Chrome Bright Brass Satin Off White Black Paint Black Plated (1) Other finishes and colors are available on special order. Consult the factory for details. Custom color painted sprinklers may not retain their UL Corrosion resistance listing. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) cULus Listed only. (3) 200°F (93°C) maximum. (4) cULus listed “corrosion resistance” applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright) and RA1414 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request. (5) FM Approvals finish as “Polyester coated” applies to SIN Number RA1414 (Pendent) in standard black or white. (6) LPCB and VdS Approved finish applies only to RA1425, RA1414 and RA1475. Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Orifice Size 4. Deflector Type 5. Temperature Rating 6. Sprinkler Finish 7. Escutcheon Type 8. Escutcheon Finish (where applicable) 9. Cover plate Model 10. Cover plate Thread size 11. Cover plate Temperature 12. Cover plate Adjustment 13. Cover plate Finish Note: When Model F1FR56 Recessed sprinklers are ordered, the sprinklers and escutcheons are packaged separately. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Model F3QR Quick Response Dry Sprinklers Bu l l e t i n 1 5 7 Re v . I Bulletin 157 Rev. I Features 1. The Model F3QR sprinkler utilizes Belleville Spring Closure Technology. Reliable is the first in the industry to produce a Quick Response Dry Concealed sprin- kler utilizing this technology. 2. Styles available • Pendent • Recessed FP Pendent • Recessed F1 Pendent • Concealed • Horizontal Sidewall • Recessed FP Horizontal Sidewall • Recessed F1 Horizontal Sidewall 3. 1½” (38mm) escutcheon adjustment on pendent sprinkler. 4. ½” (13mm) escutcheon adjustment on recessed sprin- kler with push-on/ thread-off FP Model Escutcheon ring. 5. 3/8” (9.5mm) cover plate adjustment on concealed sprinkler with push-on/ thread-off CCP Cover Plate. 6. 3/4” (19mm) escutcheon adjustment on recessed sprinkler with F1 Escutcheon. 7. Attractive appearance. Employs 3mm frangible glass bulb and galvanized nipple. 8. Lengths available to accommodate installation di- mensions from 2” - to - 48” (51mm - to - 1219mm), in ¼” (6mm) increments. See specific styles for correct “A” dimension range. 9. Available in a variety of plated and painted finishes. 10. Polyester Coated Corrosion Resistant Sprinklers. US Patent Numbers 5,775,431 and 5,967,240. Other US Patents pending. Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) StyleResponse Sprinkler System Type Hazard Pendent Recessed Pendent Recessed F1 Pendent CCP Concealed (R5714) Quick Wet Pipe Dry Pipe All Preaction Light Ordinary Horizontal Sidewall Recessed Horizontal Sidewall (R5734) Quick Wet Pipe Dry Pipe All Preaction Light 2. Certified by FM Approvals StyleResponse Sprinkler System Type Hazard Pendent Recessed F1 Pendent (R5714) Quick Wet Pipe Dry Pipe All Preaction Light Ordinary, Groups 1&2 Horizontal Sidewall Recessed F1 Horizontal Sidewall (R5734) Quick Wet Pipe Dry Pipe All Preaction Light 3. NYC MEA 258-93-E Concealed (See Fig. 4) Recessed FP Pendent (See Fig. 3) Recessed F1 Horizontal Sidewall (See Fig. 9) Horizontal Sidewall (See Fig. 6) Pendent (See Fig. 1) Recessed F1 Pendent (See Fig. 5) Recessed FP Horizontal Sidewall (See Fig. 8) Pendent / HB (See Fig. 2) Horizontal Sidewall / HB (See Fig. 7) 2. Model F3QR Dry Pendent Sprinkler “A” Dim.2” to 48” (51mm to 1219mm) in ¼” (6mm) increments Finishes(1) SprinklerEscutcheon Bronze Chrome Plated White Polyester (2) Brass (3) Chrome Plated White (1) Other finishes and colors are available on special order. Consult factory for details. (2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or White. (3) Not available for HB escutcheons. Model F3QR Dry Recessed FP Pendent Sprinkler “A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments Finishes(1) SprinklerEscutcheon Bronze Chrome Plated White Polyester (2) Brass Chrome Plated White (1) Other finishes and colors are available on special order. Consult factory for details. Cup remainds unfinished. Only the escutcheon will contain desired finish. (2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or White. Standard Temperature Ratings Classifi cation Sprinkler Temperature Rating Max. Ambient Temp. Bulb Color Ordinary Ordinary Intermediate (1) Intermediate High (1) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue Sprinkler cup and FP Escutcheon fabricated of steel and recommended for interior applications. (1) Listed and Certifi ed only by cULus. Note: The sprinkler can protrudes ¼” when escutcheon is in nominal position. Escutcheon adjustment provides -¼” (-6mm) to +1¼” (+32mm) “A” dimension adjustment range. Fig. 1 Note: Do not install the Model F3QR Dry Recessed FP Pendent Sprin- kler in ceilings which have positive pressure in space above. Fig. 3 Note: The sprinkler can protrudes 1¼” when escutcheon is in nomi- nal position. Escutcheon adjustment provides -½” (-12.7mm) to +½” (+12.7mm) “A” dimension adjustment range. Fig. 2 Model F3QR Dry Pendent w/HB Escutcheon “A” Dim.3½” to 48” (89mm to 1219mm) in ¼” (6mm) increments Standard Temperature Ratings Classifi cation Sprinkler Temperature Rating Max. Ambient Temp. Bulb Color Ordinary Ordinary Intermediate (1) Intermediate High (1) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue Sprinkler can and escutcheon fabricated of brass for better weather resistance in exterior applications. (1) Listed and Certifi ed only by cULus. Sprinkler Guard: Model C-2 Sprinkler Installation Wrench: Model G3 Sprinkler Wrench Sprinkler Identifi cation Number (SIN): R5714 Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identifi cation Number (SIN): R5714 3. Model F3QR Dry Pendent Concealed Sprinkler “A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments CCP Cover Plate (1) Finishes (2) Standard FinishesSpecial Application Finishes Chrome Plated White Bright Brass Plated Black Plated Black Paint Off White Satin Chrome (1) Utilizes the 1/2” cover plate with 3/8” total adjustment. (2) Other finishes and colors are available on special order. Consult factory for details. Standard Temperature Ratings Classifi cation Sprinkler Temperature Rating Cover Plate Temp. Rating Max. Ambient Temp. Ordinary Ordinary Intermediate (1) Intermediate High (1) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 135°F (57°C) 165°F (74°C) 165°F (74°C) 165°F (74°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 150°F (66°C) Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of brass and recommended for interior applications. (1) Listed and Certifi ed only by cULus. Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identifi cation Number (SIN): R5714 Note: Do not install the Model F3QR Dry Concealed Pendent Sprinkler in ceilings which have positive pressure in the space above. Fig. 4 Model F3QR Dry Recessed F1 Pendent Sprinkler “A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments Finishes (1) SprinklerEscutcheonCollar Chrome Plated White Polyester (2) Chrome Plated White Chrome Plated White (1) Other finishes and colors are available on special order. Consult factory for details. (2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or White. Standard Temperature Ratings Classifi cation Sprinkler Temperature Rating Max. Ambient Temp. Bulb Color Ordinary Ordinary Intermediate (1) Intermediate High (1) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue (1) Listed and Certifi ed only by cULus. Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identifi cation Number (SIN): R5714 Fig. 5 4. Model F3QR Dry Recessed FP Horizontal Sidewall Sprinkler • Listed by cULus for Quick Response. Approved by FM for Standard Response. • Recessed Horizontal sidewall sprinklers are listed with cULus for installation of min. 4” (100mm) - to - max. 6” (150mm) below ceiling and approved by FM for installation of min. 4” (100mm) - to - max. 12” (300mm) below ceiling. “A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments Finishes (1) SprinklerEscutcheon Bronze Chrome Plated White Polyester (2) Brass Chrome Plated White (1) Other finishes and colors are available on special order. Consult factory for details. Cup remainds unfinished. “See page 2” (2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or White. Standard Temperature Ratings Classifi cation Sprinkler Tem- perature Rating Max. Ambient Temp.Bulb Color Ordinary Ordinary Intermediate (1) Intermediate High (1) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue (1) Listed and Certifi ed only by cULus. Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identifi cation Number (SIN): R5734 Notes: Do not install the Model F3QR Dry Recessed FP Horizontal Sidewall Sprinkler in walls which have positive pressure in their side space. Fig. 8 Model F3QR Dry Horizontal Sidewall Sprinkler “A” Dim.2” to 48” (51mm to 1219mm) in ¼” (6mm) increments Finishes(1) SprinklerEscutcheon Bronze Chrome Plated White Polyester (2) Brass (3) Chrome Plated White (1) Other finishes and colors are available on special order. Consult factory for details. (2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or White. (3) Not available for HB escutcheons. Note: The sprinkler can protrudes ¼” when escutcheon is in nominal position. Escutcheon adjustment provides -¼” (-6mm) to +1¼” (+32mm) “A” dimension adjustment range. Fig. 6 Note: The sprinkler can protrudes 1¼” when escutcheon is in nomi- nal position. Escutcheon adjustment provides -½” (-12.7mm) to +½” (+12.7mm) “A” dimension adjustment range. Fig. 7 Model F3QR Dry HSW w/HB Escutcheon “A” Dim.2” to 48” (51mm to 1219mm) in ¼” (6mm) increments Standard Temperature Ratings Classifi cation Sprinkler Temperature Rating Max. Ambient Temp. Bulb Color Ordinary Ordinary Intermediate (1) Intermediate High 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue Sprinkler can and escutcheon fabricated of brass for better weather resistance in exterior applications. (1) Listed and Certifi ed only by cULus. Sprinkler Installation Wrench: Model G3 Sprinkler Wrench prinkler Identifi cation Number (SIN): R5734 5. Model F3QR Dry Recessed F1 Horizontal Sidewall Sprinkler • Listed by cULus for Quick Response. Approved by FM for Standard Response. • Recessed Horizontal sidewall sprinklers are listed with cULus for installation of min. 4” (100mm) - to - max. 6” (150mm) below ceiling and approved by FM for installation of min. 4” (100mm) - to - max. 12” (300mm) below ceiling. “A” Dim.31/2” to 48” (89mm to 1219mm) in ¼” (6mm) increments Finishes (1) SprinklerEscutcheonCollar Chrome Plated White Polyester (2) Chrome Plated White Chrome Plated White (1) Other finishes and colors are available on special order. Consult factory for details. (2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or White. Standard Temperature Ratings Classifi cation Sprinkler Temperature Rating Max. Ambient Temp. Bulb Color Ordinary Ordinary Intermediate (1) Intermediate High (1) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue (1) Listed and Certifi ed only by cULus. Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identifi cation Number (SIN): R5734 Technical Data: Orifice Size: ½” (15mm) Thread Size: 1” NPT per ANSI B2.1 Working Pressure: 175 psi (12 bar) Nominal K Factor - US / (Metric): 5.6 / (80) Product Description Reliable Model F3QR Dry Sprinklers are quick response sprinklers utilizing a durable 3mm frangible glass bulb. This quick response enables these sprinklers to apply water to a fire much sooner than standard response sprinklers of the similar temperature rating. Model F3QR Dry Sprinklers are intended for use in dry and preac- tion systems and in areas subjected to freezing temperatures, such as freezers and unheated portions inside and outside buildings. Environments wherein dry sprinklers are employed can be cor- rosive. For this reason, Model F3 Sprinklers have a special wax fillet placed in the gap between the cup that supports the bulb and the wrenching boss. This wax will not interfere with the operation of the sprinkler, and it prevents contaminents from entering the internal portion of the drop nipple. The wax must not be removed. Operation The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response. When the temperature increases sufficiently, due to a fire, the bulb shatters allowing operating parts to clear the waterway. This enables the inlet seal to release air or water and subsequently, cause water flow over the deflector in a uniform spray pattern, controlling or extinguishing the fire. Ordering Information Specify: 1. Sprinkler Type (select one): (a) Model F3QR Dry Pendent (b) Model F3QR Dry Pendent/HB (c) Model F3QR Dry Recessed FP Pendent (d) Model F3QR Dry Recessed F1 Pendent (e) Model F3QR Dry Concealed Pendent (f) Model F3QR Dry Horizontal Sidewall (g) Model F3QR Dry Horizontal Sidewall/HB (h) Model F3QR Dry Recessed FP Horizontal Sidewall (i) Model F3QR Dry Recessed F1 Horizontal Sidewall 2. Sprinkler Temperature Rating. 3. Sprinkler Finish. 4. Escutcheon type (F1 or FP). 5. Cover Plate/Escutcheon Finish. 6. Length: “A” Dimension (face of tee to face of ceiling or wall) in ¼” (6mm) increments. 7. Model F3QR Dry Pendent (a) is available without sprinkler can and escutcheon. Note: 1. The “A” dimension is based on a nominally gauged pipe thread “make-up” of 0.600” (15mm) per ANSI B2.1 [7½ threads approximately]. 2. All platings and paintings are decorative and intend- ed for interior use. Fig. 9 General Installation Instructions Model F3QR dry sprinklers must be installed only in stan- dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) pipe tees in the horizontal position, even at branch line ends. They should not be installed into elbows or pipe couplings located on drop nipples to the sprinklers. For these and other fittings including CPVC*, the dry sprinkler should be installed into a fitting to allow protrusion into the fitting in ac- cordance with the diagrams. The “A” dimension of the dry sprinkler, which extends into the freezers or a freezing zone from wet pipe systems, should be selected to provide, as a minimum, the specified lengths in inches shown in Fig. 10. Caution: Do not install Model F3QR Dry sprinklers into CPVC adapter fittings or tees that have an internal obstruction. This will damage the sprinkler and /or the fitting. Refer to Fig. 11. During installation, the following steps must be followed: 1. Cut the specified size hole (see illustrations) for the sprin- kler in the ceiling or wall directly in line with the tee. 2. Apply pipe joint compound to the 1” (25mm) pipe threads and install sprinkler using the Model G3 or G3 R/C Sprinkler Wrench as specified. 3. Install the Model FP push-on / thread-off escutcheon or CCP cover plate if required. Note: Installation of the Model F3QR Sprinklers is not rec- ommended in copper pipe systems, as this may reduce the life expectancy of the sprinklers. Model F3QR Concealed and Recessed In- stallation Instructions • The Model G3 R/C wrench (Fig. 12) is designed to locate on the wrenching pads of the recessed sprin- kler while centering in the cup. A standard ½” drive ratchet may be used to drive this wrench. Fig. 13 and Fig. 14 show sequentially the insertion of the wrench. First the wrench, with its jaws above the sprinkler de- flector, is moved laterally until centered with the cup. Then raise the wrench inside of the cup until its jaws engage the sprinkler’s square wrenching pads (Fig. 14). To remove the wrench, follow this procedure in reverse order. Care should be taken to avoid striking the deflector, with the wrench. • Model G3 Wrench (Fig. 15) is used for installation of Pendent and Horizontal Sidewall sprinklers. • Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SER- VICE FOR FIRE PROTECTION. Removal of the pro- tectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PRO- TECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. Maintenance The Model F3QR Quick Response Dry Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not remove the factory applied thermally sensitive wax fillet between the bulb sup- porting cup and the wrenching boss. Do not replace this wax with a substitute substance. An Alternate substance may interfere with proper operation of the sprinkler. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gently vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non-operation. Caution: Use specified by RASCO wrenches only, which are designed to engage sprinkler’s wrenching pad. (Fig. 15, page 9) 6. Fig. 10 7. 8. Fig. 11 Fig. 13 - G3 R/C Wrench Fig. 15 - G3 Wrench Fig. 14 - G3 R/C WrenchFig. 12 - G3 R/C Wrench 9. The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 05/12 P/N 9999970175 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles • Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water fl ow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals • Air maintenance devices • Air compressors • Pressure gauges • Identifi cation signs • Fire department connection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection