HomeMy WebLinkAboutB12-0523 ComCheck2009 IECC
. �
!, � � � �
-
Envelope Compliance Certificate
Section 1: Project Information
Project Type: Alteration
Project Title : CRAZY SHIRTS
Construction Site:
286 BRIDGE STREET
VAIL, CO 81657
Owner/Agent:
MARK HOLLANDER
CRAZY SHIRTS
VAIL, CO 81657
Section 2: General Information
Building Location (for weather data): Rifle, Colorado
Climate Zone: 5b
Building Type for Envefope Requirements: Non-Residential
Activ� Tvoe(s)
Retail
Section 3: Requirements Checklist
Floor Area
953
Desig ner/Contractor:
TOM LESTER
LESTERDEVELOPMENT
P O BOX 11347
ASPEN, CO
970 379 4655
�°��'��l :'�.,'�'�'�`�'�{ '�"� � � _ _
.� '. .�.�u�.c.: e �^ co
,� ux�a 4.4A 5 wrr.; un.�f a� . - .�,���:i.::.'� ��,
Climate-Specific Requirements:
R-Value Proposed Max. Allowed
Post-Alteration Assembly Cavity Cont. U-Factor SHGC U-Factor SHGC
Air Leakage, Component Certification, and Vapor Retarder Requirements:
� 1. All joints and penetrations are caulked, gasketed or covered with a moisture vapor-permeable wrapping material installed in accordance
with the manufacturer's installation instructions.
❑ 2.
� 3.
� 4.
� 5.
0 6.
❑�
Windows, doors, and skylights certified as meeting leakage requirements.
Component R-values & U-factors labeled as certified.
No roof insulation is installed on a suspended ceiling with removable ceiling panels.
'Other' components have supporting documentation for proposed U-Factors.
Insulation installed according to manufacturers instructions, in substantial contact with the surface being insulated, and in a manner that
achieves the rated R-value without compressing the insulation.
Stair, elevator shaft vents, and other outdoor air intake and exhaust openings in the building envelope are equipped with motorized
dampers.
� 8. Cargo doors and loading dock doors are weather sealed.
� 9. Recessed lighting fixtures installed in the building envelope are Type �C rated as meeting ASTM E283, are sealed with gasket or caulk.
� 10. Building entrance doors have a vestibule equipped with self-closing devices.
Exceptions:
❑ Building entrances with revolving doors.
❑ Doors not intended to be used as a building entrance.
� Doors that open directly from a space less than 3000 sq. ft. in area.
� Doors used primarily to facilitate vehicular movement or materials handling and adjacent personnel doors.
� Doors opening directly from a sleeping/dwelling unit.
Project Title: CRAZY SHIRTS Report date: 10/05/12
Data filename: C:\Users\BEST ELECTRIC1DocumentslCOMchedclCRAZY SHIRTS 7WO.cck Page 1 of 6
� Alteration projects that replace an existing door, provided, however, that existing vestibules (i.e., pre-alteration) are not removed.
Project Title: CRAZY SHIRTS Report date: 10/05/12
Data filename: C:1Usersl6EST ELECTR�C1Documents\COMchecklCRAZY SHIRTS TWO.cck Page 2 of 6
2009 IECC
COMcheck Software Version 3.9.0
Interior Lighting Compliance
Certificate
Section 1: Project Information
Project Type: Alteration
Project Title : CRAZY SHIRTS
Construction Site:
286 BRIDGE STREET
VAIL, CO 81657
Owner/Agent:
MARK HOLLANDER
CRAZY SHIRTS
VAIL, CO 81657
Section 2: Interior Lighting and Power Calculation
DesignerlContractor:
TOM LESTER
LESTERDEVELOPMENT
P O BOX 11347
ASPEN, CO
970 379 4655
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts / ft2 (B x C)
Retail 953 1.5 1430
Allowance: Other retail highlighting / Fix. ID: F1 50(a) 0.6 30(b)
Allowance: Other retail highlighting / Fix. ID: F3 27(a) 0.6 16(b)
Allowance: Other retail highlighting / Fix. ID: F4 33(a) 0.6 20(b)
Supplemental Allowed Watts(c) = 385
Total Allowed Watts = 1880
(a) Area claimed may exceed total floor area when Retail Merchandise Highlighting allowance(s) are speafied.
(b) Allowance is (B x C) or the actual wattage of the fixtures given in Section 2, whichever is less.
(c) Supplemental watts must be associated with retail merchandise highlighting fixtures.
(e) Additional controls/switching allowances are based on number of fixtures or wattage controlled, not floor area of allowance.
Section 3: Interior Lighting Fixture Schedule
A
Fi�cture ID : Description / Lamp / Wattage Per Lamp / Ballast
Retail (953 sq.ft.)
Linear Fluorescent 1: F1: 2X2 EQUATION / 22" T5 HO 24W / Electronic
Track lighting 1: F2: Wattage based on circuit breaker capacity (1 amps x 120 volts)
Exemption:Retail Display Window
Track lighting 2: F2: Wattage based on circuit breaker capacity (1 amps x 120 volts)
Exemption:Retail Display Window
Track lighting 3: F2: Wattage based on circuit breaker capacity (1 amps x 120 volts)
Track lighting 4: F2: Wattage based on circuit breaker capacity (1 amps x 120 volts)
Track lighting 5: F3: Wattage based on circuit breaker capacity (3 amps x 120 volts)
Track lighting 6: F4: Wattage based on circuit breaker capacity (4 amps x 120 volts)
Incandescent 1: F5: LOW VOLT PENDANTS / Incandescent 50W
Compact Fluorescent 1: F6: LED DOWN LIGHT / Other / Electronic
Compact Ftuorescent 2: F7: WALL MOUNT / BIAX 24W / Dimming
Compact Fluorescent 3: F8: EXIT / Other / Electronic
Exemption:Exit Signs, Safety or Emergency Lighting
Incandescent 2: F9: FROG EYE EM LIGHT / Incandescent 20W
Exemption:Exit Signs, Safety or Emergency Lighting
Linear Fluorescent 2: F10: 2x4 / 48" T8 32W (Super T8) / Electronic
Exemption:Lighting Integral to Equipment
Incandescent 3: F11: BAR LIGHT / Inqndescent 40W
B C D E
Lamps/ # of Fixture (C X D)
Fbcture Fi�ctures Watt.
2 9 40
0 0 0
0 0 0
0
0
0
0
1
1
1
1
0
0
0
0
3
6
2
1
0
0
0
0
50
15
40
17
2 2 40
4 1 128
3 1 120
360
Exempt
Exempt
120
120
360
480
150
90
80
Exempt
Exempt
Exempt
120
Project Title: CRAZY SHIRTS Report date: 10/05/12
Data filename: C:\Usersl6EST ELECTRIC\Documents\COMchecklCRAZY SH�RTS TWO.cck Page 3 of 6
Total Proposed Watts = 1880
Section 4: Requirements Checklist
Lighting Wattage:
� 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies
1880 1880 Passes with merchandise highlighting allowance
Controls, Switching, and Wiring:
� 2. Daylight zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to
vertical fenestration.
� 3. Daylight zones have individual lighting controls independent from that of the general area lighting.
Exceptions:
� Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device.
� Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a
separate switch for general area tighting.
� 4. Independent controls for each space (switch/occupancy sensor).
Exceptions:
� Areas designated as security or emergency areas that must be continuously illuminated.
� Lighting in stairways or corridors that are elements of tfie means of egress.
0 5. Master switch at entry to hoteUmotel guest room.
� 6. Individual dwelling units separately metered.
� 7. Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
� 8. Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either
controlli�g all luminaires, dual switching of altemate rows of luminaires, altemate luminaires, or altemate lamps, switching the middle
lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
� Only one luminaire in space.
� An occupant-sensing device controls the area.
� The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
❑ Areas that use less than 0.6 Watts/sq.ft.
� 9. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
❑ Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
� 10. PhotocelUastronomical time switch on exterior lights.
Exceptions:
� Lighting intended for 24 hour use.
� 11.Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
p Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
. . . ,� r� i ��� i6h'��"I�fl��l � I �I , �� r ii .
. . . . . . .. � 1 ��i,�:IJk.eu� 4� ,�1�_:`f Poi FlM��t�i.:,�+Y . A:^:;�i i�'M.L.�a. �;!r^,�Atirw .. .. a � � -
Section 5: Compliance Statement
Compliance Statement: The proposed lighting alteration project represented in this document is consistent with the building plans,
specifications and other calcufations submitted with this permit application. The proposed tig ' g aReration project has been designed to meet
the 2009 IECC, Chapter 8, requirements in COMcheck Version 3.9.0 and to comply with andatory requirements in the Requirements
Checklist. . �'
� ��- � Q �� " ,�
ame - Title /i,�/� �� Sig at � Date
C�
/ 5 l �%P� l � �
`�7G> 3�� G�% ��
Project Title: CRAZY SHIRTS Report date: 10/05/12
Data filename: C:\UsersIBEST ELECTRIC1Documents\COMchecklCRAZY SHIRTS TWO.cck Page 4 of 6
2009 IECC
COIVlcheck Software Version 3.9.0
Exterior Lighting Compliance
Certificate
Section 1: Project Information
Project Type: Alteration
Project Title : CRAZY SHIRTS
Exterior Lighting Zone: 2(Neighborhood business district)
Construction Site: OwneNAgent:
286 BRIDGE STREET MARK HOLWNDER
VAIL, CO 81657 CRAZY SHIRTS
VAIL, CO 81657
Desig ner/Contractor:
TOM LESTER
LESTERDEVELOPMENT
P O BOX 11347
ASPEN, CO
970 379 4655
Section 2: Exterior Lighting Area/Surface Power Calculation
A
Exterior ArealSurface
B C D E F
Quantity Allowed Tradable Allowed Proposed
Watts Wattage Watts Watts
/ Unit (B x C)
Free standing/attached sales canopy 2 ft2 0.6 Yes 1 0
Total Tradable Watts` = 1 0
Total Allowed Watts =
Total Allowed Supplemental Watts" = 600
' Wattage tradeoffs are only allowed between tradable areas/surfaces.
•* A supplemental allowance equal to 600 watts may be applied toward compliance of both non-Vadable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
p B C D E
Fixture ID : Description / Lamp I Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
Free standinglattached sales canopy (2 ft2): Tradable Wattage
Incandescent 1: Incandescent 50W 1 2 65 Exempt
Exemption:Advertising or directional signage
Total Tradable Proposed Watts = 0
Section 4: Requirements Checklist
Lighting Wattage:
� 1. Within each non-tradable arealsurface, tota{ proposed watts must be less than or equal to tota{ allowed watts. Across all tradable
areas/surfaces, total proposed watts must be less than or equal to total allowed watts.
Compliance: Passes.
Controls, Switching, and Wiring:
� 2. All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting.
� 3. Lighting not designated for dusk-to-dawn operation is control�ed by either a a photosensor (with time switch), or an astronomical time
switch.
� 4. Lighting designated fw dusk-to-dawn operation is controlled by an astronomical time switch or photosensor.
� 5. All time switches are capable of retaining programming and the time setting during loss of power for a period of at least 10 hours.
Project Title: CRAZY SHIRTS Report date: 10I05/12
Data filename: C:\Users\BEST ELECTRIC\Documents\COMcheck\CRAZY SHIRTS TWO.cck Page 5 of 6
Exterior Lighting Efficacy:
0 6. All exterior building grounds luminaires that operate at greater than 100W have minimum efficacy of 60 lumen/watt.
Exceptions:
� Lighting that has been claimed as exempt and is identified as such in Section 3 table above.
� Lighting that is specifically designated as required by a health or life safety statue, ordinance, or regulation.
� Emergency lighting that is automatically off during normal building operation.
� Lighting that is controlled by motion sensor.
�� i� h! . i P i�is h tl� s d� 199� � � f n��i � a i i�
� * �` �' ia����� r� ���������� '�I� � 16 F
� _ � � i�.� �,�ami,� ���,��'� i i G, i. ��,. � ,
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consisten with the building plans, specifications
and other calculations submitted wit this permit application. The proposed lighting system has signed to meet the 2009 IECC
requirements in check Versi 3.9. and to comply with the mandatory irements i quirements Checklist.
� TS -��
Name - ' Si rra Date
/
7�,� �7 � ���p��
�°wn -tyw � �1 7�,�'/�� �,� �
� �� 3�� G���
Project Title: CRAZY SHIRTS Report date: 10/05/12
Data filename: C:\Users\BEST ELECTR�C\Documents\COMchecklCRAZ1' SHIRTS TWO.cdc Page 6 of 6