HomeMy WebLinkAboutA12-0063 stamped approved PO Box 1073, Frisco, CO 80443
970.409.9082; fax 970.797.1898
October 10, 2012
Mike Vaughan
Vail Fire & Emergency Services
Vail, Colorado
Re: Millrace Condominiums
Dear Mike,
This letter outlines a scope of work to be performed at the Millrace Condominiums. The work will be
completed by Vail Electronics. Buildings #1, 2, 4, 5, 6 & 7 will be affected by this project. There will
be 4 fire alarm control panels installed. See the attached spreadsheet and site plan. We will install the
following:
• 4 Honeywell, Vista 128FPB fire alarm panels with wireless capabilities and dialers
• 4 Honeywell 6160CR wireless keypads in heated enclosures
• 74 5800WAVE wireless sounders
• 116 5808W3 wireless smoke detectors
• 45 5800CO wireless carbon monoxide detectors
Panel and keypad locations have been discussed on site during our recent walkthrough with Don
Anderson from Vail Electronics. Hand drawn typical plans of each unit type are attached. I have also
provided battery calculations. The attached spreadsheet outlines the number of devices per unit, per
building and per panel. Of course, a zone list will be produced as installation progresses and will be
provided to you at the final inspection. The attached site plan shows notations for panel locations and
building numbers.
The panels will be partitioned per unit. Each unit will operate independently of others. A smoke
detector or carbon monoxide detector activation will activate all sounders within a unit. There is no
General Alarm condition – each unit will operate separately.
If you have any questions or need any additional information for issuance of a permit, please let me
know.
Sincerely,
Deborah L. Shaner, P.E.
Fire Protection Engineer
Cc: Don Anderson, Vail Electronics
10/10/2012
A12-0063
Millrace Condominiums Fire Alarm Installation
Device/FACP Summary
FACP #1, Building #1
Located in Building #1, Covers Units 1A-1H
Unit Type
# of Smoke
Detectors
# of CO
Detectors
# of
Sounders
1A 2 bedroom 3 1 2
1B 2 bedroom 3 1 2
1C 2 bedroom 3 1 2
1D 2 bedroom 3 1 2
1E 3 bedroom 5 2 3
1F 3 bedroom 5 2 3
1G 3 bedroom 5 2 3
1H 3 bedroom 5 2 3
Totals 32 12 20
FACP #2, Building #2
Located in Building #2, Covers Units 2A-2F
Unit Type
# of Smoke
Detectors
# of CO
Detectors
# of
Sounders
2A 1 bedroom 2 1 1
2B 1 bedroom 2 1 1
2C 1 bedroom 2 1 1
2D 2 bedroom + loft 4 2 3
2E 2 bedroom + loft 4 2 3
2F 2 bedroom + loft 4 2 3
Totals 18 9 12
FACP #3, Buildings #4 & 5
Located in Building #5, Covers Units 4A-4D & 5A-5D
Unit Type
# of Smoke
Detectors
# of CO
Detectors
# of
Sounders
4A 2 bedroom 3 1 2
4B 2 bedroom 3 1 2
4C 3 bedroom + loft 6 2 4
4D 3 bedroom + loft 6 2 4
5A 2 bedroom 3 1 2
5B 2 bedroom 3 1 2
5C 3 bedroom 5 2 3
5D 3 bedroom 5 2 3
Totals 34 12 22
FACP #4, Buildings #6 & 7
Located in Building #7, Covers Units 6A-6D & 7A-7D
Unit Type
# of Smoke
Detectors
# of CO
Detectors
# of
Sounders
6A 2 bedroom 3 1 2
6B 2 bedroom 3 1 2
6C 3 bedroom 5 2 3
6D 3 bedroom 5 2 3
7A 2 bedroom 3 1 2
7B 2 bedroom 3 1 2
7C 3 bedroom 5 2 3
7D 3 bedroom 5 2 3
Totals 32 12 20
Grand Totals 116 45 74
~MILLRACECONDOMINIUMS 970.476.6106
TO HOTEL &SPA/CLUB •.
••North C>NM o
BLDG.2
GARAGEr---'r""""I
DlelBIA
Millrace
1&2
BUILDING #4:PARK IN ASSIGNED
GARAGE ATTACHED TO YOUR BUILDING.
BUILDINGS #5,#6,#7:GARAGE IS LOCATED
UNDER YOUR SPECIFIC CONDOMINIUM.
~
VAIL CASCADE
RESORT·SPA·CONDOMINIUMS
OJ STAIRS
TO HOTELnm
K1l-iA-
t -~tb.Jr\...
Standby
Number of Current Total Current
Device Type Devices (Amps)(Amps)
Main FACP CPU 1 X 0.032 =0.032
Wireless Interface 1 X 0.025 =0.025
Keypad 1 X 0.04 =0.04
SUM COLUMN FOR STANDBY LOAD 0.097 =AMPS
Alarm Load
Number of Current Total Current
Device Type Devices (Amps)(Amps)
Main FACP CPU 1 X 0.032 =0.032
Wireless Interface 1 X 0.025 =0.025
Keypad 1 X 0.1 =0.1
Sounder 22 X 0.066 =1.452
SUM COLUMN FOR STANDBY LOAD 1.609 =AMPS
Standby Load Required Standby Time in Hours
Current (Amps)
0.097 X 24 =2.33
Alarm Load Required Alarm Time in Hours
Current (Amps)(15 MINUTES)
1.609 X 0.25 =0.40
Add Standby and Alarm Load for Required
Ampere Hour Battery 2.73
Multiply by the Derating Factor of 1.2
Total Ampere Hours Required =3.28
Batteries Provided:4AH Minimum
Panel calculations is worst case of 4 panels. All battery sizes will be 4AH.
Ademco Vista 128 FACP
Millrace Condominiums
r\'-
4.-r '--
I l".~1dtr)JjJ
\,AA\Jll
~)-+.J~
I 1 I\Il J \
.}~I ~f(J @.@ ~~I.I
r 1~>{2lo{VVl ~1 '-!1l?Q (9
-'
'••,\0.
rv '
;--
J-.~
~»M
~'---"
-
@
~~--I.....--
.----t -..-:-_.-L-_