HomeMy WebLinkAboutA12-0068 DETECTOR BASESMOUNTING BASES 200 SERIES
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
5906NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom’s mounting bases and kits provide a variety
of ways to install detectors in any application.
B501 Flangeless Mounting Base
The B501 is standard base with no flange.
B210LP Flanged Mounting Base
The B210LP is a low profile mounting base with a
flange.
B501BH Sounder Base
The B501BH Sounder Base provides a built-
in sounder which can be used for evacuation
purposes.
B224RB Relay Base
The B224RB Relay Base provides one form C relay
contact for control of auxiliary functions such as
damper control and elevator recall.
B224BI Isolator Base
The B224BI Isolator Base allows loops to continue
to operate under fault conditions and automatically
restore when the fault is removed.
The MIX-200 Series detectors can be mounted in
either flanged or flangeless bases depending on the
junction box selection.
APPROVED
CATALOG NUMBER
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com Email: mail@mircom.com
Distributed by:
CAT. 5906
Rev. 4
NOT TO BE USED FOR INSTALLATION PURPOSES.
Ordering Information
Model Description Agency Listing
B501 Flangeless Mounting Base UL, ULC, FM, CSFM, MEA
B210LP Flanged Mounting Base UL, ULC, FM, CSFM, MEA
B501BH Sounder Base UL, ULC, CSFM, MEA, SSL
B501BHT Temporal Tone Sounder Base UL
B224RB Relay Base UL, ULC, CSFM, MEA
B224BI Isolator Base UL, ULC, CSFM, FM, MEA
RA400Z Remote LED Annunciator
Note: For Canadian models add suffix “A”.
Specifications
Base Specifications
Diameter
4.0” (102 mm);flangeless
6.1” (155 mm);flange
Height
1.2” (31 mm)
Wire Gauge
12 - 22 AWG
Temperature Range
32°F to 120°F (0°C to 49°C)
Humidity Range
10% to 93% RH noncondensing
B224RB/B224BI Electrical Ratings
Operating Voltage
15 to 32 VDC
Standby Ratings
<500 µA maximum @24 VDC
Set Time
4 sec.minimum,20 sec.maximum
Reset Time
1 sec.minimum, 8 sec.maximum
Relay Characteristics (relay base only)
2 coil latching relay
1 Form C contact
Resistive contact rating: 2 A @ 30 VDC
Inductive contact rating:
0.3 A @ 110 VDC (with .35 pF or greater),
0.3 A @ 120 VAC (with .35 pF or greater),
1.0 A @ 30 VDC (with .6 pF or greater)
B501BH/B501BHT Electrical Ratings
External Supply Voltage
17 to 32 VDC
Standby Current
1.0 mA max.
Alarm Current
15 mA max.
Maximum Ripple Voltage
10% of supply voltage
Start-up Capacitance
200 µF
Sound Output
Greater than 90 dBA measured in anechoic room
at 10 feet, 24 volts. 85 dBA minimum in
UL reverberant room.
200 Series Junction Box Selection Guide
*with 3.0 .mud ring
Drywall or
suspended ceiling
Standard junction boxes
Aesthetically pleasing
Used with B501,the RMK400 provides a
simple installation solution in applications that
demand a lower profile smoke detector.
Uses. Kit is suitable for use with 4”octagon,
50mm, and 60mm junction boxes connected
to flexible conduit.
Junction boxes are not included in kit.
Note: Not listed for use with MIX-1251(A).
Recessed Mounting Kit Product Overview
Note: Box depth contingent on base and wire size. Refer to National Electric Code or applicable local codes for appropriate recommendations.
U.S.A.
60 Industrial Parkway, PMB 278
Cheektowaga, New York 14227
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
Model Single
Gang 3.5" Oct.4" Oct.4" Sq.4" Sq.*50 mm 60 mm 70 mm 75 mm
B501 No Yes No No Yes Yes Yes Yes No
B210LP Yes Yes Yes Yes Yes No No No No
B224RB No Yes Yes Yes No No Yes Yes Yes
B224BI No Yes Yes Yes No No No Yes Yes
B501BH No No No Yes No No No No No
B501BHT No No No Yes No No No No No