HomeMy WebLinkAboutA12-0068 DETECTORSINTELLIGENT LOW PROFILE SENSORS MIX-200 SERIES
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
CATALOGUE NUMBER
Intelligent Low Profile Ionization Smoke Sensor
(MIX-1251B)
The Intelligent Ionization Smoke Sensor is constantly
monitored to measure any change in its sensitivity due to the
environment (dirt, aging, temperature, humidity, etc.) It can
give an advance indication to the FX-2000 analog control
panel of the need for maintenance and can be specific as
to where the maintenance is needed. It can be mounted in
a number of different bases. See the Ordering Information
for a list of these bases and their descriptions.
Intelligent Low Profile Photoelectronic Smoke
Sensor (MIX- 2251B)
The Intelligent Photoelectronic Smoke Sensor is constantly
monitored to measure any change in its sensitivity due to the
environment (dirt, aging, temperature, humidity, etc.) It can
give an advance indication to the FX-2000 analog control
panel of the need for maintenance and can be specific as
to where the maintenance is needed. It can be mounted in
a number of different bases. See the Ordering Information
for a list of these bases and their descriptions.
Intelligent Thermal Sensors
(MIX-5251B/MIX-5251RB/MIX-5251H)
The Intelligent Thermal Sensors contain a dual thermistor
sensing circuit for fast response. They provide open
area protection with 50 foot spacing. The sensors rapid
response characteristic virtually eliminates the thermal lag
which is characteristic of conventional heat detectors and
insures operation as soon as the temperature reaches its
set point (MIX-5251B), or upon a temperature rise of 15°F
per minute (MIX-5251RB). The MIX-5251H provides fixed
high temperature detection at 190°F. These sensors can be
mounted in a number of different bases. See the Ordering
Information for a list of these bases and their descriptions.
Mircom’s MIX-200 Series intelligent plug-in smoke detectors
with integral communication provide features that surpass
conventional detectors. Detector sensitivity is continuously
monitored and reported to the FX-2000 Fire Alarm Control
Intelligent Low Profile Photoelectronic Smoke
Sensor with Thermal (MIX-2251TB)
The MIX-2251TB has the same features as the MIX-
2251B and includes a 135°F thermal sensor. It can
be mounted in a number of different bases. See the
Ordering Information for a list of these bases and their
descriptions.
5904
NOT TO BE USED FOR INSTALLATION PURPOSES.
S6295
(MIX-1251B,
MIX-2251B &
MIX-2251TB)
S6299
(MIX-5251B/RB/H)
CS920
(MIX-1251B,
MIX-2251B &
MIX-2251TB)
CS717
(MIX-5251B/RB/H)
MEAapproved
7271-1477:122
(MIX-1251B)7271-1477:117
(MIX-2251B/TB)7271-1477:114
(MIX-5251B/RB/H)
205-94-E
(MIX-1251B)
219-02-E
(MIX-2251B/TB)390-02-E
(MIX-5251B/RB/H)APPROVED
3017996
2151
(MIX-1251B)
2131
(MIX-2251B/TB)
Panel. Point ID capability allows each detector’s address
to be set with decade address switches, providing exact
detector locations for selective maintenance when chamber
contamination reaches an unacceptable level.
Ordering Information
Model Description
Intelligent Addressable Analog Sensors
MIX-1251B Intelligent Low Profile Ionization Smoke Sensor
MIX-2251B Intelligent Low Profile Photoelectronic Smoke Sensor
MIX-2251TB Intelligent Low Profile Photoelectronic Smoke Sensor c/w 135°F Fixed Temp. Thermal Sensor
MIX-5251B Intelligent Low Profile Fixed Temp. Thermal Sensor 135°F
MIX-5251RB Intelligent Low Profile Fixed Temp. and Rate of Rise Thermal Sensor 135°F
MIX-5251H Intelligent Low Profile High Temperature Thermal Sensor 190°F
Intelligent Analog Bases
B210LP Intelligent Flanged Mounting Base
B224BI Intelligent Isolator Base
B224RB Intelligent Relay Base*
B501 Intelligent Flangeless Mounting Base
B501BH Intelligent Sounder Base
B501BHT Intelligent Temporal Tone Sounder Base
Accessories
RA-400Z Remote LED Annunciator
Note: For Canadian models add suffix “A”.
* When used with the M500X Fault Isolator Module, the number of relay bases between fault isolators is limited to 12.
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com Email: mail@mircom.com
Distributed by:
CAT. 5904
Rev. 5
Specifications
Height
2.0 inches (51 mm)
Diameter
6.1 inches (155 mm) Installed in B210LP Base
4.1 inches (104 mm) Installed in B501 Base
Shipping Weight
Heat: 4.8 oz. (137 g)
Photo/Photo with Heat: 5.2 oz. (147 g)
Ion: 5.4 oz. (154 g)
Operating Temperature Range
Ion/Photo: 32°F to 120°F (0°C to 49°C)
Photo with Thermal: 32°F to 100°F (0°C to 38°C)
Thermal: -4°F to 100°F (-20°C to 38°C)
High Temperature: -4°F to 100°F (-20°C to 66°C)
UL Listed Velocity Range
Ion: 0 - 1200 fpm (0 - 5.1 m/sec)
Photo/Photo with Thermal: 0 - 4000 fpm (0 - 20 m/sec)
Relative Humidity
10% - 93% noncondensing
Insect Screen Hole Size
Photo: 0.016 inch (0.41mm) nominal
Ion: 0.035 inch (0.89mm) nominal
Thermal Ratings
Fixed Temperature Setpoint: 135°F (57°C)
Rate of Rise Detection: 15°F/min. (8.3°C/min.)
High Temperature: 190°F (88°C)
Voltage Range
15 - 32 volts DC peak
Standby Current
Ion/Thermal:
150 uA @ 24 VDC (without communication, LED off)
200 uA @ 24 VDC (one communication every 5 sec.
with LED enabled)
Photo/Photo with Thermal:
250 uA @ 24 VDC (without communication, LED off)
300 uA @ 24 VDC (one communication every 5 sec.
with LED enabled)
LED Current (max.)
6.5 mA @ 24 VDC (on)
Note: Mounting sensors outside of the specified temperature ranges will cause sensor failures and erratic panel operation.
NOT TO BE USED FOR INSTALLATION PURPOSES.
U.S.A.
60 Industrial Parkway
Cheektowaga, New York 14227
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113