HomeMy WebLinkAboutB12-0451 Rev1-2 Load CalcA-Phase Electric, LLC Load Calculation Lodge at Vail Unit #406
General Lighting and Receptacle Demand Load:
1440 sq.ft. x3VA= 4320 220.3(a)
1,500 VA X 2= 3000 220.16(a)
1,500 VA X 1 = 1500 220.16(b)
Total connected load: 8,820
3,000 VA @ 100% = 3,000 220.11
VA @ 35% = 2,037.0
712.95
Total general lighting and
Receptacle demand load: 3,713
Range demand load:
12,000VA 8,000 220.19
Dryer Load:
0 220.18
Fixed appliance load:
Dishwasher 1.2 kva 1 1,200
Garbage disposal .8 kva 1 800
Sub-Zero 1.2 kva 0 0
Air Condition 3.8 kva 1 3,800
Hot tub 12 kva 0 0
Total flxed appliance load: 5,800
A-Phase Electric, LLC Load Calculation Lodge at Vail Unit #406
Heating load:
Boiler 0.2 0 0
Pump 0.2 0 0
Baseboard heat .25/ft 0 0
Wall heater 1,500 0 0
Total heating load: 0
25% of largest motor: 1,200
Totals:
General lighting and receptacles: 3,713
Range: 8,000
Dryer: 0
Fixed appliance: 5,800
Heating: 0
25% of largest motor: 1,200
Total: VA 18,713
AMPS 77.97
Installed Service Size:
Secondary Conductors:
Distance from vault to meter:
100A single phase 120/240
2/0 Aluminum
150'