HomeMy WebLinkAboutF12-0076 Hydraulic Calculations Approved _ _ _ Fire Prakeckian �y Compuker Design Central Fire Protection 10775 E. 51 st Ave. Denver, Colorado 80239 (303) 576-8157 Job Name : Casa Colorado Building : 1042 Eagles Nest Circle Vail, Colorado Location : Third Floor Bedroom 305 System : Calc#1 Contract : 290712 Data File : Casa Colorado Third Floor Bedroom 305 Calc#1.WX1 �. — I attest to the accuracy and MarvinHeath,SET integrity of this document Central Fire Protection Contractors, Inc. NICET LevellV#/079201 Fire Protection Engineering Technology/ 20� 2.� 0.09 11 .O� :09 -06'00' Water-Based Systems Layout Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Central Fire Protection Page 1 Casa Colorado Date 10-06-12 HYDRAULIC DESIGN INFORMATION SHEET Name - Casa Colorado Date - 10-06-2012 Location - Third Floor Bedroom 305 Building - 1042 Eagles Nest Circle Vail, Colorado System No. - Calc #1 Contractor - Central Fire Protection Contractors Inc Contract No. - 290712 Calculated By - Stephanie Pelster Drawing No. - FP2 Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 8 '-1" OCCUPANCY - NFPA 13D Residential S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D Y Number of Sprinklers Flowing: ( ) 1 (X) 2 ( ) 4 ( ) S ( )Other T ( ) Specific Ruling Made by Date E M Listed Flow at Start Point - 23 Gpm System Type Listed Pres. at Start Point - 27 .3 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 18 x 18 O Deluge O PreAction E Domestic Flow Added - N/A Gpm Sprinkler or Nozzle S Additional Flow Added - N/A Gpm Make TYCO Model LF11 HSW I Elevation at Highest Outlet - Feet Size 1/2" K-Factor 4.4 G Note: Temperature Rating 155 N Calculation Gpm Required 47 . 04 Psi Required 73.172 At Pump Outlet Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 10-01-2012 Rated Cap. 50 Cap. T Time of Test - 10:00 AM @ Psi 41 . 6 Elev. E Static (Psi) - 100 Elev. 1' R Residual (Psi) - 95 Other Well Flow (Gpm) - 1318 Proof Flow Gpm S Elevation - 2 ' P Location: 1042 Eagles Nest Circle vail, Colorado 81657 P L Source of Information: Test conducted by Central Fire Protection Contractors Y and witnessed by Vail Fire & Upper Eagle Valley Fire Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Central Fire Protection Page 2 Casa Colorado Date 10-06-12 City Water Supply: Pump Data: Demand: C1 - Static Pressure : 90 P1 - Pump Churn Pressure : 67.5 D1 - Elevation : 14.238 C2 - Residual Pressure: 85.5 P2 - Pump Rated Pressure : 61 D2 - System Flow : 47.04 C2 - Residual Flow : 1318 P2 - Pump Rated Flow : 20 D2 - System Pressure : 73.172 P3 - Pump Pressure @ Max Flow : 41.6 Hose ( Demand ) � City Water Adjusted to Pump Inlet P3 - Pump Max Flow : 50 D3 - System Demand : 47.04 for Pf- Elev- Hose Flow City Residual Flow @ 0 = 6655.41 Safety Margin : 2.535 A1 -Adjusted Static: 72.401 City Residual Flow @ 20 = 5810.02 A2 -Adj Resid : 64 @ 20 City Water @ 150% of Pump = 89.99 A3 -Adj Resid : 26.632 @ 50 180 168 156 P 144 R 132 E 120 S 108 S 96 C2 U 84 D2 R 72 A 2 E 60 48 36 A3 24 12 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Central Fire Protection Page 3 Casa Colorado Date 10-06-12 Fitting Legend Abbrev. Name Yz '/4 1 1'/< 1'/z 2 2Yz 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 Bv B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Cpe" CPVC 90'EII Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 Cpt` CPVC Tee-Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Cue" Copper 90'EII 1 1 2 2 2.5 3.5 4 5 6 7 9 10 0 0 0 0 0 0 0 0 Cut` Copper Tee-Branch 1.5 2 2 3 3.5 5 6 7.5 9 10.5 13 15 0 0 0 0 0 0 0 0 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Central Fire Protection Page 4 Casa Colorado Date 10-06-12 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. S1 27.875 4.4 29.84 na 24.04 0.071 324 27.3 S2 27.875 4.4 27.33 na 23.0 0.071 324 27.3 L1A 27.875 30.34 na L2A 27.875 27.98 na L1B 19.71 35.33 na L2B 19.71 32.85 na L3 19.71 34.98 na L4 27.875 33.72 na L5 19.04 39.2 na L6 8.21 49.8 na L9 8.21 57.96 na TOR 8.21 60.94 na PMPO 1.0 73.17 na PMPI 1.0 31.52 na BFO 2.0 34.35 na BFI 2.0 43.82 na BOR 1.0 52.9 na TEST -5.0 89.99 na The maximum velocity is 19.41 and it occurs in the pipe between nodes BOR and TEST Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 5 Casa Colorado Date 10-06-12 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn *THIRD FLOOR S1 24.04 1.101 1 Cpt 5.0 0.250 29.841 K Factor=4.40 to 150.0 0.0 5.000 0.0 L1A 24.04 0.0954 0.0 5.250 0.501 Vel = 8.10 0.0 24.04 30.342 K Factor= 4.36 S2 23.00 1.101 1 Cpe 7.0 0.333 27.334 K Factor=4.40 to 150.0 0.0 7.000 0.0 L2A 23.0 0.0881 0.0 7.333 0.646 Vel = 7.75 0.0 23.00 27.980 K Factor= 4.35 *VERTICAL RISERS FROM 2ND TO 3RD L1A 24.04 1.101 1Cpe 7.0 8.170 30.342 to 150.0 0.0 7.000 3.536 L1 B 24.04 0.0956 0.0 15.170 1.451 Vel = 8.10 0.0 24.04 35.329 K Factor= 4.04 L2A 23.00 1.101 1 Cpe 7.0 8.170 27.980 to 150.0 0.0 7.000 3.536 L2B 23.0 0.0882 0.0 15.170 1.338 Vel = 7.75 0.0 23.00 32.854 K Factor= 4.01 *2ND FLOOR PIPING L1 B 24.04 1.101 1 Cpe 7.0 20.500 35.329 to 150.0 2Cpt 10.0 17.000 0.290 L5 24.04 0.0956 0.0 37.500 3.585 Vel = 8.10 0.0 24.04 39.204 K Factor= 3.84 L2B 23.00 1.101 2Cpt 10.0 14.170 32.854 to 150.0 0.0 10.000 0.0 L3 23.0 0.0881 0.0 24.170 2.130 Vel = 7.75 L3 0.0 1.101 2Cpe 14.0 11.833 34.984 to 150.0 0.0 14.000 -3.536 L4 23.0 0.0881 0.0 25.833 2.277 Vel = 7.75 L4 0.0 1.101 1 Cpe 7.0 6.750 33.725 to 150.0 1 Cpt 5.0 12.000 3.826 L5 23.0 0.0882 0.0 18.750 1.653 Vel = 7.75 0.0 23.00 39.204 K Factor= 3.67 *VERTICAL RISER FROM 1 ST TO 2ND L5 47.04 1.101 1 Cpe 7.0 10.830 39.204 to 150.0 0.0 7.000 4.690 L6 47.04 0.3311 0.0 17.830 5.904 Vel = 15.85 0.0 47.04 49.798 K Factor= 6.67 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 6 Casa Colorado Date 10-06-12 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn *FIRST FLOOR PIPING L6 47.04 1.101 1 Cpe 7.0 7.670 49.798 to 150.0 2Cpt 10.0 17.000 0.0 L9 47.04 0.3310 0.0 24.670 8.167 Vel = 15.85 L9 0.0 1.101 1 Cpe 7.0 2.000 57.965 to 150.0 0.0 7.000 0.0 TOR 47.04 0.3311 0.0 9.000 2.980 Vel = 15.85 TOR 0.0 1.055 1 Fsp 0.0 7.210 60.945 to 150.0 1 S 7.768 7.768 6.123 * Fixed loss = 3 PMPO 47.04 0.4075 0.0 14.978 6.104 Vel = 17.26 0.0 47.04 73.172 K Factor= 5.50 System Demand Pressure 73.172 Safety Margin 2.535 Continuation Pressure 75.707 Pressure @ Pump Outlet 75.707 Pressure From Pump Curve -44.189 Pressure @ Pump Inlet 31.518 PMPI 0.0 1.055 2Cue 4.0 4.000 31.518 to 150.0 0.0 4.000 -0.433 BFO 47.04 0.4076 0.0 8.000 3.261 Vel = 17.26 BFO 0.0 1.055 0.0 1.170 34.346 to 150.0 0.0 0.0 9.000 * Fixed loss = 9 BFI 47.04 0.4077 0.0 1.170 0.477 Vel = 17.26 BFI 0.0 1.055 1 Cue 2.0 1.000 43.823 to 150.0 1 Bv 3.496 5.496 6.433 * Fixed loss = 6 BOR 47.04 0.4075 0.0 6.496 2.647 Vel = 17.26 BOR 0.0 0.995 2Cue 4.0 55.000 52.903 to 150.0 1 Cut 2.0 8.628 2.599 TEST 47.04 0.5420 1 Bv 2.628 63.628 34.489 Vel = 19.41 0.0 47.04 89.991 K Factor= 4.96 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 _ _ _ Fire Prakeckian �y Compuker Design Central Fire Protection 10775 E. 51 st Ave. Denver, Colorado 80239 (303) 576-8157 Job Name : Casa Colorado Building : 1042 Eagles Nest Circle Vail, Colorado Location : Second Floor Living Room System : Calc#2 Contract : 290712 Data File : Casa Colorado Second Floor Living Room Calc#2.WX1 � I attest to the accuracy and MarvinHeath,SET integrity of this document Central Fire Protection Contractors, Inc. NICET LevellV#079201 Fire Protection Engineering Technology/ 2012 10 09 11 �O� •36 -06'00' Water-Based Systems Layout • • • • Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Central Fire Protection Page 1 Casa Colorado Date 10-06-12 HYDRAULIC DESIGN INFORMATION SHEET Name - Casa Colorado Date - 10-06-2012 Location - Second Floor Living Room Building - 1042 Eagles Nest Circle Vail, Colorado System No. - Calc #2 Contractor - Central Fire Protection Contractors Inc Contract No. - 290712 Calculated By - Stephanie Pelster Drawing No. - FP1 Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9'-11" OCCUPANCY - NFPA 13D Residential S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D Y Number of Sprinklers Flowing: ( ) 1 (X) 2 ( ) 4 ( ) S ( )Other T ( ) Specific Ruling Made by Date E M Listed Flow at Start Point - 20 Gpm System Type Listed Pres. at Start Point - 23. 8 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 20 x 20 O Deluge O PreAction E Domestic Flow Added - N/A Gpm Sprinkler or Nozzle S Additional Flow Added - N/A Gpm Make GLOBE Model MILLENNIUM I Elevation at Highest Outlet - Feet Size 1/2" K-Factor 4 .1 G Note: Temperature Rating 155 N Calculation Gpm Required 42 . 992 Psi Required 62.847 pump outlet Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 10-01-2012 Rated Cap. 50 Cap. T Time of Test - 10:00 AM @ Psi 41 . 6 Elev. E Static (Psi) - 100 Elev. 1' R Residual (Psi) - 95 Other Well Flow (Gpm) - 1318 Proof Flow Gpm S Elevation - 2 ' P Location: 1042 Eagles Nest Circle vail, Colorado 81657 P L Source of Information: Test conducted by Central Fire Protection Contractors Y and witnessed by Vail Fire & Upper Eagle Valley Fire Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Central Fire Protection Page 2 Casa Colorado Date 10-06-12 City Water Supply: Pump Data: Demand: C1 - Static Pressure : 90 P1 - Pump Churn Pressure : 67.5 D1 - Elevation : 10.468 C2 - Residual Pressure: 85.5 P2 - Pump Rated Pressure : 61 D2 - System Flow : 42.992 C2 - Residual Flow : 1318 P2 - Pump Rated Flow : 20 D2 - System Pressure : 62.847 P3 - Pump Pressure @ Max Flow : 41.6 Hose ( Demand ) � City Water Adjusted to Pump Inlet P3 - Pump Max Flow : 50 D3 - System Demand : 42.992 for Pf- Elev- Hose Flow City Residual Flow @ 0 = 6655.41 Safety Margin : 22.450 A1 -Adjusted Static: 72.401 City Residual Flow @ 20 = 5810.02 A2 -Adj Resid : 64 @ 20 City Water @ 150% of Pump = 89.99 A3 -Adj Resid : 26.632 @ 50 180 168 156 P 144 R 132 E 120 S 108 S 96 C2 � 84 R 72 A � E 60 48 36 A3 24 12 D1 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Central Fire Protection Page 3 Casa Colorado Date 10-06-12 Fitting Legend Abbrev. Name Yz '/4 1 1'/< 1'/z 2 2Yz 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 Bv B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Cpe" CPVC 90'EII Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 Cpt` CPVC Tee-Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Cue" Copper 90'EII 1 1 2 2 2.5 3.5 4 5 6 7 9 10 0 0 0 0 0 0 0 0 Cut` Copper Tee-Branch 1.5 2 2 3 3.5 5 6 7.5 9 10.5 13 15 0 0 0 0 0 0 0 0 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Central Fire Protection Page 4 Casa Colorado Date 10-06-12 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. S001 19.29 4.1 27.24 na 21.4 0.0535 400 23.8 S3 19.17 K=K@ EQ01 24.1 na 21.4 L3 19.71 24.89 na S4 19.71 K=K@ EQ01 24.53 na 21.59 L4 19.04 27.17 na L5 19.04 32.43 na L6 8.21 42.12 na L9 8.21 49.03 na TOR 8.21 51.56 na PMPO 1.0 62.85 na PMPI 1.0 37.79 na BFO 2.0 40.11 na BFI 2.0 49.52 na BOR 1.0 58.19 na TEST -5.0 89.99 na The maximum velocity is 17.74 and it occurs in the pipe between nodes BOR and TEST Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 5 Casa Colorado Date 10-06-12 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn *SPRINKLER EQUIV K-FACTORS S001 21.40 1.101 1 Cpe 7.0 0.420 27.243 K Factor=4.10 to 150.0 0.0 7.000 -3.718 EQ01 21.4 0.0771 0.0 7.420 0.572 Vel = 7.21 0.0 21.40 24.097 K Factor= 4.36 *2ND FLOOR PIPING S3 21.40 1.101 1 Cpt 5.0 8.333 24.097 K Factor @ node EQ01 to 150.0 0.0 5.000 -0.234 L3 21.4 0.0772 0.0 13.333 1.029 Vel = 7.21 L3 0.0 1.101 2Cpe 14.0 11.833 24.892 to 150.0 0.0 14.000 0.290 L4 21.4 0.0771 0.0 25.833 1.992 Vel = 7.21 0.0 21.40 27.174 K Factor= 4.11 S4 21.59 1.101 2Cpe 14.0 11.000 24.532 K Factor @ node EQ01 to 150.0 1 Cpt 5.0 19.000 0.290 L4 21.59 0.0784 0.0 30.000 2.352 Vel = 7.28 L4 21.40 1.101 1 Cpe 7.0 6.750 27.174 to 150.0 1 Cpt 5.0 12.000 0.0 L5 42.99 0.2803 0.0 18.750 5.256 Vel = 14.49 0.0 42.99 32.430 K Factor= 7.55 *VERTICAL RISER FROM 1 ST TO 2ND L5 42.99 1.101 1 Cpe 7.0 10.830 32.430 to 150.0 0.0 7.000 4.690 L6 42.99 0.2803 0.0 17.830 4.998 Vel = 14.49 0.0 42.99 42.118 K Factor= 6.62 "FIRST FLOOR PIPING L6 42.99 1.101 1 Cpe 7.0 7.670 42.118 to 150.0 2Cpt 10.0 17.000 0.0 L9 42.99 0.2803 0.0 24.670 6.915 Vel = 14.49 L9 0.0 1.101 1 Cpe 7.0 2.000 49.033 to 150.0 0.0 7.000 0.0 TOR 42.99 0.2803 0.0 9.000 2.523 Vel = 14.49 TOR 0.0 1.055 1 Fsp 0.0 7.210 51.556 to 150.0 1 S 7.768 7.768 6.123 * Fixed loss = 3 PMPO 42.99 0.3450 0.0 14.978 5.168 Vel = 15.78 0.0 42.99 62.847 K Factor= 5.42 System Demand Pressure 62.847 Safety Margin 22.450 Continuation Pressure 85.297 Pressure @ Pump Outlet 85.297 Pressure From Pump Curve -47.510 Pressure @ Pump Inlet 37.787 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 6 Casa Colorado Date 10-06-12 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn PMPI 0.0 1.055 2Cue 4.0 4.000 37.787 to 150.0 0.0 4.000 -0.433 BFO 42.99 0.3451 0.0 8.000 2.761 Vel = 15.78 BFO 0.0 1.055 0.0 1.170 40.115 to 150.0 0.0 0.0 9.000 * Fixed loss = 9 BFI 42.99 0.3444 0.0 1.170 0.403 Vel = 15.78 BFI 0.0 1.055 1 Cue 2.0 1.000 49.518 to 150.0 1 Bv 3.496 5.496 6.433 * Fixed loss = 6 BOR 42.99 0.3451 0.0 6.496 2.242 Vel = 15.78 BOR 0.0 0.995 2Cue 4.0 55.000 58.193 to 150.0 1 Cut 2.0 8.628 2.599 TEST 42.99 0.4589 1 Bv 2.628 63.628 29.200 Vel = 17.74 0.0 42.99 89.992 K Factor= 4.53 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 _ _ _ Fire Prakeckian �y Compuker Design Central Fire Protection 10775 E. 51 st Ave. Denver, Colorado 80239 (303) 576-8157 Job Name : Casa Colorado Building : 1042 Eagles Nest Circle Vail, Colorado Location : First Floor Garage 107 System : Calc#3 Contract : 290712 Data File : Casa Colorado First Floor Garage 107 Calc#3.WX1 � I attest to the accuracy and MarvinHeath,SET integrity of this document Central Fire Protection Contractors,Inc. NICET Level IV#079201 Fire Protection Engineering Technology/ �0 1 2.� 0.09 11 .O�.O� —O�'oo' Water-Based Systems Layout Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Central Fire Protection Page 1 Casa Colorado Date 10-06-12 HYDRAULIC DESIGN INFORMATION SHEET Name - Casa Colorado Date - 10-06-2012 Location - First Floor Garage 107 Building - 1042 Eagles Nest Circle Vail, Colorado System No. - Calc #3 Contractor - Central Fire Protection Contractors Inc Contract No. - 290712 Calculated By - Stephanie Pelster Drawing No. - FP1 Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9' OCCUPANCY - NFPA 13D Residential S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D Y Number of Sprinklers Flowing: ( ) 1 (X) 2 ( ) 4 ( ) S ( )Other T ( ) Specific Ruling Made by Date E M Listed Flow at Start Point - 25 Gpm System Type Listed Pres. at Start Point - 32 .3 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 20 O Deluge O PreAction E Domestic Flow Added - N/A Gpm Sprinkler or Nozzle S Additional Flow Added - N/A Gpm Make TYCO Model LFII DRY I Elevation at Highest Outlet - Feet Size 1/2" K-Factor 4 .4 G Note: Temperature Rating 155 N Calculation Gpm Required 50.387 Psi Required 77 . 937 At Pump Outlet Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 10-01-2012 Rated Cap. 50 Cap. T Time of Test - 10:00 AM @ Psi 41 . 6 Elev. E Static (Psi) - 100 Elev. 1' R Residual (Psi) - 95 Other Well Flow (Gpm) - 1318 Proof Flow Gpm S Elevation - 2 ' P Location: 1042 Eagles Nest Circle vail, Colorado 81657 P L Source of Information: Test conducted by Central Fire Protection Contractors Y and witnessed by Vail Fire & Upper Eagle Valley Fire Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Central Fire Protection Page 2 Casa Colorado Date 10-06-12 City Water Supply: Pump Data: Demand: C1 - Static Pressure : 90 P1 - Pump Churn Pressure : 67.5 D1 - Elevation : 5.721 C2 - Residual Pressure: 85.5 P2 - Pump Rated Pressure : 61 D2 - System Flow : 50.387 C2 - Residual Flow : 1318 P2 - Pump Rated Flow : 20 D2 - System Pressure : 55.174 P3 - Pump Pressure @ Max Flow : 41.6 Hose ( Demand ) � City Water Adjusted to Pump Inlet P3 - Pump Max Flow : 50 D3 - System Demand : 50.387 for Pf- Elev- Hose Flow City Residual Flow @ 0 = 6655.41 Safety Margin : 12.052 A1 -Adjusted Static: 72.401 City Residual Flow @ 20 = 5810.02 A2 -Adj Resid : 64 @ 20 City Water @ 150% of Pump = 89.99 A3 -Adj Resid : 26.632 @ 50 180 168 156 P 144 R 132 E 120 S 108 S 96 C2 � 84 R 72 A 2 E 60 48 36 A3 24 12 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Central Fire Protection Page 3 Casa Colorado Date 10-06-12 Fitting Legend Abbrev. Name Yz '/4 1 1'/< 1'/z 2 2Yz 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 Bv B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Cpe" CPVC 90'EII Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 Cpt` CPVC Tee-Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Cue" Copper 90'EII 1 1 2 2 2.5 3.5 4 5 6 7 9 10 0 0 0 0 0 0 0 0 Cut` Copper Tee-Branch 1.5 2 2 3 3.5 5 6 7.5 9 10.5 13 15 0 0 0 0 0 0 0 0 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Central Fire Protection Page 4 Casa Colorado Date 10-06-12 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. S1 8.21 4.4 32.3 na 25.01 0.078 320 32.3 L7 8.21 32.89 na S2 8.21 4.4 33.27 na 25.38 0.078 320 32.3 L8 8.21 33.88 na L9 8.21 38.74 na TOR 8.21 42.12 na PMPO 1.0 55.17 na PMPI 1.0 25.97 na BFO 2.0 29.24 na BFI 2.0 38.78 na BOR 1.0 48.22 na TEST -5.0 89.99 na The maximum velocity is 20.79 and it occurs in the pipe between nodes BOR and TEST Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 5 Casa Colorado Date 10-06-12 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn *FIRST FLOOR PIPING S1 25.01 1.101 1 Cpt 5.0 0.708 32.300 K Factor=4.40 to 150.0 0.0 5.000 0.0 L7 25.01 0.1028 0.0 5.708 0.587 Vel = 8.43 L7 0.0 1.101 0.0 9.625 32.887 to 150.0 0.0 0.0 0.0 L8 25.01 0.1029 0.0 9.625 0.990 Vel = 8.43 0.0 25.01 33.877 K Factor= 4.30 S2 25.38 1.101 1 Cpt 5.0 0.708 33.274 K Factor=4.40 to 150.0 0.0 5.000 0.0 L8 25.38 0.1056 0.0 5.708 0.603 Vel = 8.55 L8 25.01 1.101 1 Cpt 5.0 7.920 33.877 to 150.0 0.0 5.000 0.0 L9 50.39 0.3760 0.0 12.920 4.858 Vel = 16.98 L9 0.0 1.101 1 Cpe 7.0 2.000 38.735 to 150.0 0.0 7.000 0.0 TOR 50.39 0.3759 0.0 9.000 3.383 Vel = 16.98 TOR 0.0 1.055 1 Fsp 0.0 7.210 42.118 to 150.0 1 S 7.768 7.768 6.123 * Fixed loss = 3 PMPO 50.39 0.4629 0.0 14.978 6.933 Vel = 18.49 0.0 50.39 55.174 K Factor= 6.78 System Demand Pressure 55.174 Safety Margin 12.052 Continuation Pressure 67.226 Pressure @ Pump Outlet 67.226 Pressure From Pump Curve -41.252 Pressure @ Pump Inlet 25.974 PMPI 0.0 1.055 2Cue 4.0 4.000 25.974 to 150.0 0.0 4.000 -0.433 BFO 50.39 0.4629 0.0 8.000 3.703 Vel = 18.49 BFO 0.0 1.055 0.0 1.170 29.244 to 150.0 0.0 0.0 9.000 * Fixed loss = 9 BFI 50.39 0.4624 0.0 1.170 0.541 Vel = 18.49 BFI 0.0 1.055 1 Cue 2.0 1.000 38.785 to 150.0 1 Bv 3.496 5.496 6.433 * Fixed loss = 6 BOR 50.39 0.4629 0.0 6.496 3.007 Vel = 18.49 BOR 0.0 0.995 2Cue 4.0 55.000 48.225 to 150.0 1 Cut 2.0 8.628 2.599 TEST 50.39 0.6155 1 Bv 2.628 63.628 39.165 Vel = 20.79 0.0 50.39 89.989 K Factor= 5.31 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087