Loading...
HomeMy WebLinkAboutB12-0583 LOAD CALCSA-Phase Electric, LLC Load Calculation Lodge at Vail Unit #248 General Lighting and Receptacle Demand Load: 1440 sq. ft.x3VA= 4320 220.3(a) 1,500 VA X 2= 3000 220.16(a) 1,500 VA X 1 = 1500 220.16(b) Total connected load: 8,820 3,000 VA @ 100% = 3,000 220.11 VA @ 35% = 2,037.0 712.95 Total general lighting and Receptacle demand load: 3,713 Range demand load: 12,000VA 8,000 220.19 Dryer Load: 0 220.18 Fixed appliance load: Dishwasher 1.2 kva 1 1,200 Garbage disposal .8 kva 1 800 Sub-Zero 1.2 kva 0 0 Air Condition 1.8 kva 1 1,800 Hot tub 12 kva 0 0 Total fixed appliance load: 3,800 B12-0583 A-Phase Electric, LLC Load Calculation Lodge at Vail Unit #248 Heating load: Boiler 0.2 0 0 Pump 0.2 0 0 Baseboard heat .25/ft 0 0 Wall heater 1,500 0 0 Total heating load: 0 25% of largest motor: 1,200 Totals: General lighting and receptacles: 3,713 Range: 8,000 Dryer: 0 Fixed appliance: 3,800 Heating: 0 25% of largest motor: 1,200 Total: VA 16,713 Alv'IPS 69.64 Installed Seaice Size: Secondary Conductors: Distance from vault to meter: 100A single phase 120/240 2/0 Aluminum 150'