Sequence of operation for Silent Knight 5700 Addressable Fire Alarm Control
System
The Vail Gymnasium will have 2 fire alarm zones - lower floor devices and upper
floor devices.
In the event of a smoke detector, heat detector or pull station activation on the
upper floor, the horns throughout the entire building will sound, the strobes
throughout the entire building will flash, the elevator will recall to the lower floor
and the communicator will communicate an alarm condition to the monitoring
company. All strobes will by synchronized via synchronization module built in the
FACP.
In the event of a smoke detector, heat detector, pull station or sprinkler flow
activation on the lower floor, the horns throughout the entire building will sound,
the strobes throughout the entire building will flash, the elevator will recall to the
upper floor and the communicator will communicate an alarm condition to the
monitoring company. All strobes will by synchronized via synchronization module
built in the FACP.
The fire alarm panel will annunciate the floor and specific detector location and
the horns will be able to be silenced while maintaining strobe operation, All wire
will be 18 - 14 gauge solid copper for the SLC loop and 14 gauge solid copper
for the NAC circuits.
vAtL rlRE DrpAQIdrrox
Srproved as Sutmtttffi '-'-"=
, Rppruv# as Hstatfl/
9.u. { .2 /1',^o ".,--- ,.
AIL
ELECNONICS
LfD.
Vail Gymnasium Device and Address List:
Device
Upper Floor:
SD
SD
SD
PS
PS
SD
SD
SD
SD
SD
SD
Lower Floor:
PS
SD
SD
HD
HD
SD
SD
PS
SD
SD
SD
SD
SD
SD
TS
TS
FS
Location
Storage Room
Top of Elevator Shaft
Outside Elevator
East Stairwell
Gym Stairwell
Gym N. E.
Gym N. Center
Gym N. W.
Gym S. E.
Gym S. C-enter
Gym S. W.
Exercise Room
W side of Exercise Room
E side of Exercise Room
Women's Restroom
Men's Restroom
W end of Corridor
E end of Corridor
Main Exit
Electrical Room
Elevator Equipment Room
Oubide Elevator
Closet
Computer Closet
Outside Offices
Sprinkler Riser Room (Supply side)
Sprinkler Riser Room (House side)
Sprinkler Riser Room
01
02
03
04
05
06
07
OB
09
10
11
Address
t2
13
t4
15
16
t7
18
19
20
2L
22
23
24
25
26
27
28
23698Highway24rP,0.B0x460rMinturn,ColoradoSl645r9701827-9120tFax9701827-9126r1-800-843-2704
IntelliKnighto Model 57OO
Single Loop Addressable Fire
Alarm Gontrol System
The affordable addressable solution.
IntelliKnight Model 5700 is a 50 point class leading single loop addressable fire alarm
control/communicator system that provides you with the revolutionary value and performance of
addressable sensing technology combined with exclusive, built-in digital communication, distributed
intelligent power, that includes an easy to use interface. Powerful features such as drift compensation
and maintenance alert are delivered in this powerful FACP from Silent Knight.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1-800-446-6444, or in Minnesota, call 763-493-6435.
Description
The IntelliKnight 5700 performs dritt
compensalion and calibration dlecks
on each of the sensors in the system.
The basic InlelliKnight 5700 system
can be €nhanced by adding modules
such as lhe Remote Annunciator, the
Serial/Parallel lnlerlace (for printing
system reports), and an Intelligent
Power Module. The Model 5700 also
Jeatures a oow€rful builtin dual line lire
communicator that allows tor reporting
of all sysl€m activily to a remole
monitoring location.
Featurcs
. Up to 50 addressable points.. Upto 125 zones and 125 ouFut
groups.. Uses standard wire-no shielded or
twisted pair required.. Built-in digital communicator.. Central station reporting by Point or
by Zone.. Supports Class B (Style 4) and Class
A (Slyle 6 or 7) configuration lor
JLI,.. Distributed, intelligent power.. Drift comoensation.. 13 pre-programmed outpul
cadences, (including ANSI-3.41), and
4 programmable outputs.. Notilication circuits can be conligured
as 1 Class A (Style Z) or 2 Class B
(Style Y), or auxiliary power lor
resettable, constant. or door holder
DOWer.
. Built-in synchronization for
applianoes from G€nlex@, Faraday,
System Sensop and Wheelock@.. Built-in annuncialor with 8o-character
LCD display.. RS-485 bus provides @mmunication
to syslem accessories.. Up or Download programming, event
history, or det€ctor status via r€mote
or direcl connection.. Built-in RS-232 interlace for
programming via PC.. Built-in Form C trouble relay rat€d at
2.5 amps at 24 VDC.. Two buill-in Form C programmable
relays rated at 2.5 amps at 24 VDC.
Approvals:
UL Listsd / NFPA 72 (Fil€ No. 52766)
-Central Station
.DACT
-Local Protective
Signalling System
-Water D€luge
Releasing Service
CSFM Listed
Speclf lcations
PdmaryAC: 120 VAC,60 Hz, 1.5A
Total Accessory Load: 2.5A al 24 VDC
2.5 amps at 24 VDC ol power-limiled
notification Dower
Standby Current:
Alarm Curr€nt:
160 mA
330 mA
Notiff cation/Aux power circuits:
2.5 amps ol powerlimiled power per
circuit at 24 VDC.
Model 5700
Mechanlcal Specif ications:
Dim€nsions:
12-314'W x 15-1/8"H x 3-3/8'D
(32.39 x 38.42 x 8.57 cm)
Weight: 11.5 lbs. (5.2 kg)
Color: Red
Telephone Requirements:
FCC Part 15 and Pan 68 approv€d
Type of Jac*: RJ31X (two required)
sft"ilf4T
${lri}{i.}:lll'
.;. .j ::: :i:: i:, iH::: I,i:::ri:i::{ :i
SLC Sensor Devlces
sDs05-APS
Addressable ohotoslectric smoke detector.
SDsO5-AHS
Addressable h6at sen6or.
sDs05-6A8
Six inch base designed for use with detector
head models SD505-APS,and SD505-AHS.
sDs056tB
Short circuit isolator base for SD505-AHS.
and SD505-APS detectors.
SD5O5-ADH
Duet Housing, Detects smoke in HVAC
ducts. Use with S0505-APS.
SDsOs.ADHR/DTS
Addressable Duct smoke detector with built
in relay module detects products ot
combustion present in air moving through an
HVAC system. Providss fofm C alarm
contact. The SD505-ADHR is compatible
with the SD505-DTS, which provides remole
annunciation and iesting capabilities lor the
SD505-ADHR. Use wilh SD505-APS.
sDsoo-Ps/PsDA
Addressable Pull Station with visible LED.
Intelligent SLC Modules
SD5OO-AIM
Dry Contact Input Module. Designed to used
with normally open dty contacts- Mounts in a
4 inch square electtical box. lt features an
indicator LED to shovr alarm status and a
coverolate-
SD5OO-MIM
Mini Dry Contact Input Module. A minjature
velsion of the addrgssabls input module
which is designed to be used with pull
stations and other normally open dry contact
inputs where a smaller size is desired.
SD5OO.ARM
Addressable Relay Module. Fealures 2
Form C output relays, designed to mount on
a 4 inch square electrical box. Provides
indicator LEO to show outout status and
comes with a coverplats.
SD5OO.LED
An LEO driver capable ol driving 80 LEDS
through the SLC loop. Up to 40 SD500-
LEDS can be used per system.
SDsOO-LIM
Addr6ssable short circuit isolator module for
SLC devices
S-BUS Accessories
The lollowing it€ms listed are devices that
connected lo the IntelliKniqhts RS-485 Bus
5860 Remote Flre Annunciator
The 5860 features the same 80 character
backlit LCD display keypad and lirefighteis
keyswiich as the 5820. The system can ba
lully programmed and operated from any
remote annunciator.
5880 LED/IO Module
Features 40 LED outputs, I normally open
day contact inputs and one piezo output.
5496 lntelligent Power Module
The 5496 is a 6 amp.notmcation power
expander that provid€s four additional
power-limited noti{ication appliance circuit.
5865-3 and 5865-4
Bemote LED
Annunciator
Features 30
Programmable LEDs (15
red and 15 y6llow) outputs
and Diezo sounder. The
5865-4 adds a silsnce and
reset swibh to the
package.
5883 Relay Board
Feaiures '10 General outoosa Form C
relays. Used with 5880 module.
5824 Serial/Parallel Gateway
Module
Has one parallel and one BS-232 serial pon
for connecting any standard IBM-compatible
printer to the IntelliKnight system. lntertaces
with building control system.
SKSS Silent Knight Software
Suite
5660 Up Download Software
Userfriendly, WindowsTM soltware for
remote programming of lhe IntelliKnight
panel using a PC.
5670 Facility Management
Software
Powerful end-user software allows vrewing
of detector status and evant history via
modem or direct connection,
iN*C:lA
5700
$i!{..tiN"*'
$i\iI{j*.$T
7550 Meridian Circle, Maple Grove, MN 55369-4927
aoo-446-6444 0r in Minnesota 763-493-64i|5
FAX; 763-493-6475
World Wide Web: http://www.silentknight.com
TIADE IN AMERICA
FORM# 350392-Pr€liminary, Rev. 10/03
Copyright @ 2003 Silent Knight
SLC DeYice fnstalfatian
5.4 Heat and Smoke Detector Installation
The iaformation in this section applies to the fotlowing models: SD505-AHS Heat Detector.
and SD505-APS Photoelectric Smoke Detector.
See also Section 5.9 for iaformation on how to address thE detectors.
5,4-l Wiring
1- Wire device bases ds*own iu Figrur 54,
2. Set the address for each device as described in Section 5.9.
3. Connect the device as shown in Figure 5-4.
I
I
I
I
I
I
I
I
Sli. 4 {c).8s a}
I ocffi3&L
Figure 54 Heat or Smoke lletector Gonncction to the FACP
I t";i...-
r51N5 tr-
A.1 1 N otifi cati on Appli an ceJAuxilia ry Pover C i reuits
be Programmed to be used as NACs
*" **o aseb+ilt-in * lf.t]:::^CPwhich
c&11 D€ pru6.'""---
fi:*a'iildili-,'Jt'-,1-H$T:'l-,T:"entionalnotificationappliarruesand
hori' .,bese ternrriuals can
4.11.1 Gonventional Notificaticn Appliance
rhis $rb-sesrion :ll"fi:l$r rHi:Tr1"r*"ffi:*'entionat
notification applianses for
class A (Sryle Z) ano t-
i.*tJj "ffi:liaTf::ffi*'::H*'"
appriances in the Appendix A ar tlre
back of tbis manuat'
Tsin'S411 aClass B notrfication appliaace cireuit:
1. Wire Class B Notificatlon appliances as
;hown
in Figure 4-29'
,r,L-^rr.r:h ff.sr&1n11111rg {see Secdon 7'4)'
Shown in alarm conditon
Claes B
SuPervised
Notiflcition Circuits i'-\Y+
UL Listed 4'7k EOL
Model7628
Figllre lF29 GlasE B Notilication Appllance Clrc$lt Wtring
i:t;:f:iffi i,*""'1fil:.''l,T:::i"**appriancesintheAppendix*'n.01:xn
151295
,.-.,.. !,-tt...r,,..=".. , . :,.,...,,.r.'' . ' .''tt.r'r;i:;iffiffi
Addressoble Heot Defeclor
lntellilhighto oddressoble heot delectoru combine
occurole heot debction wift pin-point locotion lD.
An essentiol tombinotion for ony instollotion.
InielliKnight heat detectors are an essential component in virtualty any IntelliKnight installation. The IntelliKnight
panel recognizes each detector by its specific address, so precious seconds are not wasted in determining
location of an alarm.
Like other IntelliKnight detector models, the SD505-AHS ofiers a low profile for pleasing aesthetics.
The lntelliKnight family of detectors has been designed to use a @mmon base, Model SD505-6A8, allowing
complete application and placement flexibility. Combine all this with the features you've come to expect from
Silent Knight detectors-easy installation, stable operation, RF/transient proteetion, and vandal-resistant
locking-and it adds up to a flexible solution for all your fire protection needs.
hdclSDs0llllS
lldrsbloHxl D.h.for
The SDS0$AHS is a heat detec{or
suited to virtually any commercial
setting. The SD505-AHS is an
absolute temperature device. This
means that it resoonds in alarm if
the temperature goes above the
trip point (programmed at the
panel).
The SD505-AHS orovides accurate
temperature measurement data to
the fire alarm conlrol panel. This
heat detector is particularly suited
to environments rfiere smoke
detectors cannot be used because
of the presence of steam or
cooking fumes, such as in a
kitchen.
The SD505-AHS unit is made up of
an extemally mounted thermistor
with a specially designed cover that
protecis the thermistor while
allowing maximum air flow. The
thermislor reads the temperature
ftom the air it takes in. lt then
transmits a signal representing the
temperature to the lntelliKnight
panel.
lf the t€mperafure exceeds the trip
point (programmed at the panel),
an alarm occurs. The status LED
lights continuously during the alarm
period.
Under normal conditions, the stiatus
LED blinks approximately every 15
seconds, indicating that the head is
communicating with the loop.
Foolu€t. Low profile, 2 inches, including
oase
. Absolute temperature device
Simple and reliable addressing
Uses digilal communication
protocol
The SD505-AHS is UL Listed
and meets the requiremenb
outlined in NFPA 72 Inspection
Testing and Maintenance,
Chapter 7.
CFSM listed
MEA listed
FM approved
SILENT
KNIGHT
Heat Detector
17 to 41 VBC
Cunenl Consu mption:
$andbl/: .55 mAAlarm: .55 mA
Detection TemDerature
Range: 135"F to 150"F
(57'C TO 65"C)
Ambienl Temperature: 32'F to l00oF
(0"C to 37"c)
Mounting:4' SOR, 4' OCT
Single gang mud
flng
Rated Sacing:
sD505-AHS
SeeCncttom
Operaung Voltage:
70'between
sensors on smooth
cailings.
Comoatible Base6: SD505{AB
(SoldSeparately) (6'Base)
sD50$4AB
(4' Base)
lhdel SD505-AHS
Addresssble Heot Deleclor
tgfemg $edfrollorr
The conkactor shall furnish and install where indicaf€d on the plans, dressable heat detector Silent Knight
SD505-AHS. The combination detector head, and hrisuock base, straH be ULo listred compeiible with Silent
Knighfs IntelliKnight fire alarm control panels.
The base shall pennit clirect interchange udth Silent SD5O5-APS Photodectric Smoke Detec-tor, s SD505-AIS
lonization Smoke Detector. Base shall be the appropriate twist-tock base SD5056AB.
The srnoke detector shall have a flashirg status LED for visual supeffision. When the detector is actuat€d, fie
fiashing LED will tatcfr on steady at full brilliance. The detector may be reset by ac.tuating the control panel reset
switcfi.
The vandal-resistant, sectrity locking featur€ shall be used in those areas as indicated on the drawing. The
locking feature shall be field removable when not required.
\troltage and RFltransient suppression t€chniques shall be emptoyed to nrinimize false alarm potrential.
Dbmeter = 3-15/16"
Height = 2 inches,
including base
ilodel SD505-GAB Detector Base
(F ront Vrew)
ilodel SD505-AHS Detector}led
(Front View)
.- tfsmeter = $.15/16"F
/"\
r',,fN%t\\w
\ iGlffil
----:
i/-'
?FT SILENTll\l KMGrrr
7550 Meridian Circle, Maple Grove, MN 55369-4927
80lt 4{F6444 or in Minnesota 763-493-6435
FAX: 763-493-6475
World Wide Web: http:/ M,r/w.silentknight.com
TADE IH AII'ERIGA
FORM# 350229, Rev 01/01
Copyright @ 2001 Silent lciight
Addressoble
PhotoeleCric lype
Smoke Delecfor
Detect smoldedng fires quickly ond gel help fost
with I nhllil(nighto photoeledric smole deteclon.
lntelliKnight addressable photoelectric smoke detec{ors are the clear choice for commercial settings $here
smoldering fires are a threat. ln addition to accurately detec{ing a smoldering ftre, each SD505-APS
photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds
ete wasted in determining location of an alarm.
The SD505-APS compensates automatically for contamination in the environment" And detector testing ig
simpl*even from a remote site. Like other IntelliKnight deteclor models, the SD505"APS offers a low profile for
pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model
SD505€AB, allowing complete application and placement flexibility. Combine all this with the featrres you've
come to expecrt from Silent Knight smoke detec{ors-easy installation, stable operation, RFftransient protection,
and vandal*esistanl locking--and it adds up to a tlexible solution for all your fire protection needs.
lod.lSEEllS
ldog/ldtocaHe
Plolorluldclype
hob Df,dol
The SD505-APS is particularly
suited to detec{ing dense smoke
typical of fires involving materials
such es soft fumishings, plastic,
foam or oiher similar materials
which tend to smolder and produce
large visible particles.
The detector fealures automatic
compensation for contamination
and a simple detec{or calibration
tcst procedure that can be run from
the panel or remotely (using the
WindowsrM based dornloading
sofiYvare).
The SD505-APS units made up of
an LED light source and a silicon
photo diode receiving element. ln a
normal standby condition, the
receiving element receives no light
from the pulsing light source. ln the
event or lire, smoke enter the
delector and light is reflecied from
the smoke particles to the receiving
element.
The light received is converted into
an electronic signal. Under normal
conditions, the slatus LED blinks
approximately every 15 seconds,
indicating that the head is
communicating with the loop. The
LED lighb continuously during the
alarm period.
Hrru. Low profile, 2 inches, including
base
Simple and reliable addressing
without mechanical switches
Automatic compensation for
sensor contamination
Built-in fire test feeture
Simple detec'tor calibration
testing through the control panel
or remotely through a
WindowsrM based computer
sotware.
Vandal-resistance locking
features
Field cleanable
UL listed, meeG NFPA72 Ch 7
requirements
CSFM approved
MEA approved
FM Approved
SrobDfldol
1741 VDC
Curent Consumption:
$andby: -55 mA
Alarm: .55 mA
Ambienl Temperaturc: 32oF to 100PF
(oec to 5rC)
Mounting:
tD50sils
SpoCnonor
Operathg Votiage:
,|: Squars, 4" OCI
Single gang mud
dng
Relative Hurnidity: 85%
noncondensing
Air Vdocity:0 - 300 FPM
Cornpalible Bases: SD5O54!\B
(Sdd Separately) (€i Base)
sD505-4AB
(4' Base)
SILENT
KNIGHT
lhodelSD505-APS
Addressoble Phobelectric Type Smoke
Defecfol
Erglneedng Spodfr olloilr
The conlractor shall furnish and install wtrere indicated on the plans, addressable photoelectric smoke detector
Silent Knight SD505-APS. The cornbination detector head, and twist-lock base, shall be ULo listed compatible
with Silent Knight's IntelliKnight fire control panels.
The base shall permil direcl interchange with Silent Knight SD505-AIS lonization Smoke Detec'tor, or SD505-
AHS Heat Detector. Base shall be the appropriate twist-lock base SD5056AB.
The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the
flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch.
The calibration of the detector shall be capable of being selected and measured by the c,ontrol panel without the
need for external test apparatus.
The vandal-resistant, security lod<ing feature shall be used in those arreas as indicated on the drawing. The
locking feature shall be field selectable as required.
The SD505-APS shall aulomatically perform a functional test of the detector. The test method shall simulate
effects of products of combustion in the chamber lo ensure testing of detector circuits.
.- Diameter = $15/16"
Height = 2 inches,
including base
hd.lSDffilD*ftrEolc
tfnnldnl
haelSD505{lt D€b.lorllcod
(frortdd
Diameter = 3-15/16"
/"'-
6N
\\
ril srLENrI\\A KMGHTT"
7550 Meridian Circle, Maple Grove, MN 55369-4927
EOG44&6444 or in Minnesota 763-49&6435
FAX: 763-493-6475
World Wide Web: http:/rflwrrr.silentknight.com
TADE IT{ ATERICA
FORM# 350225. Rev. 12y01
Copyright @ 2001 Silcnt Knight
SD500-PS and SDS00-PSDA
Addressable Pull-Station
IntelliKnight's addressable pull stations
combine fast response with pin-point
location lD.
The SD500-PS and SDS0trPSDA are a single action or dual action addr€ssable manual lire alarm puil sation
for uso with Silent Knight's IntelliKnight fir€ control panel. Extremely easy to operat6, the SDSoo-PS/PSDA
provides a fast and practical means of manr.rally initiating a fire alarm signal. Th€ IntelliKnight panel recognizes
sach manual pull stration by its specific address saving precious seconds in detemining the location of an alarm.
The SDS@-PS/FSDA mounts to a single gang box and teaturos a rugg€cl metal construc'tion that lasts and
lasts.
Combine all this with ths features you've come to expect trom Silent Knight - easy installalion and stable
oporation - and it adds up to a flexible solution for all your fire proteclion ne€ds.
Model SD500-PS &
SD5OO.PSDA
Addressable Pull
Station
The SDSOGPS is a single action
addrassable fire pull station, and
the SD500-P$DA is a dual action
addles€able fire pull station. The
SDsoFPS/PSDA feature rugg€d
metal construciion A terminal strip
on back of the pull stafion allows
interconnec{ion of the pull station to
the SLC ot an IntelliKnight control
panel. The SDsOo-PS/PSDA is
designed for indoor use in non-
explosive environments. The
nomally open initiating point
cDntacts are gold-plated to avoid
risk of coffosion. The SD500-
PS,/PSDA has been tested by UL
for compliance to ths l€quirements
of the Ameficans with Disabilitios
ACT (ADA).
Features. UL Listed. CSFM listed. ADA compliant. Key reset (Same key as Silent
Knight enclosures)
Surface mount back box
available
Terminals - acc€pt up to 14
gauge wire
Extremely easy to operate
Conosion-resistent gold" plated
contacts.
Reflec'tive label makes it easier
to locale in low light
Specifications
Operating Voltaqo:
Sbndby Cun€nt:
Alam Cua€nt:
sD500-PS
Ambier Temperaturo: 32"F to 120'F
(0"C to 49"C)
Mounting: Single gsng
box -
Ootonal Red Surlac€ Mount Box PS-SMBB
SITENT
KNIGTTT
e r xo.qiiaqFFrt
Operation
The SD5oo-PS/PSDA single aclion
pull stations are operaled by a pull
on th€ front pull cover ol the
station. A plunger switch, wired to
a selt contained addressabl€
module, is released as the pull
station opens to initiate the alarm.
Once operated, the cover hangs
down and can be seen up lo 100
feet away. The pull station is ros€t
by returning the tront cover to the
normal upright position and
relocking the station with a reset
key. The reset keys are the same
keys used on Silenl Knight
enclosures.
The SD50o-PS/PSDA includos a
status LED which blinks, indicating
that lhe addrossable modulo is
communicating with lho loop. The
status LED lights continuously
during an alarm. A dlp switch on
the addressable module is used to
set the unique address.
,55.n4
.55.n4
SD500-PS and SDSOO-PSDA
Addressable Pull-Station
Engineering Speciflcations
Manual pull station shall be addressable Module SD50GPS/SD500-PSDA. Equipment shall be made of 14
gauge C.R.S.(Cold Rolled Steel), painted with a red €namel . The labsl shall contain tho words Fire Alarm and
be made of a reflective material embossed lext 3/8 inches tall. Operating instruction shall be clearly visible on
the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, th€
key shall match the control pan€|.
Manual station shall contain four terminal blocks with two connected to the addressable module and two connect
to the SLC loop. Manual station shall provide data to the control panel with an lD address programmed by dip
swltch settings .
Manual stations shall be Unden ,riters Laboratories lnc. listed and installed within the limits defined in the
American Disabilities Act.
Wiring
tt
\
llounting to Single
Gang Electrical Box
Mounting to Optlonal
Surlace ilount Box
Installing SDSm-LK
FIEP
SD5IXFPSDA
SILENT
KNIGHT
A l$qlil'a CCT'$rlt
7550 Meddian Circle, Maple Grove, MN 5536S-4927
8OG44G€444 or in Minnesola 763-4936435
FAX' 763-493-6475
World Wide Web: http:/Arww.silentknight.com
TADE IN ATERICA
FORM# 35q342. Flev. 09/G3
Copyrighr @ 2O0O Silenl Knigt
frlodel SD5(l0-AltIl
Addressqble Input ltlodule
And
Iflodel SD500-il1il
illinioture I nput l[odule
lntelliKnigh's oddresoble contocl nonitor modules
combine lost response with pin.point locolion lD.
A combinotion thot mves lives ond plopefi
The SDSOGAIM and SD500-M|M are addressable input modules for use with Silent Knight's
IntelliKnight fire control panel. The SD500-AIM and SD500-MIM are designed to be used with pull
stations, water flow switches, and other applications requiring dry contact alarm initiation devices.
The SD500-A|M addressable input module mounb to a 4"-square box. The SD500-M|M mini input
module fits inside a single gang box. The modules are supervised, single input contact monitors.
Using an EOL resisier, they monitor for alarm contact closures and for open circuit wiring fault
conditions.
The SD500-A|M and SD500-MIM ofier a compact design for adaptability and pleasing aesthetics as
well as easy installation and stable operation*a flexible solution for all your fire protection needs.
todolSDS0Giltord
SD50illt lryltodd6
The addressable inpul modules
elgand the flexibility of the
IntelliKnight system by allowing the
use of contac,t type inputs. Typical
applications include manual pull
stations and water flow switches.
;.olmu
Operates on Class A {Style 6 & $yle
7) or Class B (Style 4)SLC Loop,
Single contact monitor.
Up to 127 modules per SLC loop.
SD500-M|M mounts in a single gang
box.
SD500-A|M mounts in a
4"-square or double gang electrical
box, and has an attractive ivory
cov€r date.
SD50GAIM/M|M are DIP switch
programmable-
Accepls up to 14 gauge wire.
Bolh modules UL 864 listed; comply
with NFPA 72
2500 ft max. wiring distance from
input module to contact.
CSFM listed.
MEA42992-E, Vol. 9
FM approvcd
slxtoo.Atfl
Each addressable input module is
programmed with a unique SLC
loop address. The module
supervises the wiring to the contact
with an End Of Line (EOL) resistor.
lf a fault occurs in the wiring, the
module alerts the FACP.
Ambi€nt Temperaturc: 32oF to 120oF
(oqc b 49oc)
Mounting:
SCmmor
Operating Volkcge:
sD6@{tr
21VD,C
S€ndby Cunent:
Alarm Cuncnt:
0.55 mA
0.55 mA
SDsOGAIM
double gang box or
4'-square electrical
DOX
SDsOO.MIM
single gang box
SITENT
KNIGHT
Illodel SDS0O.Alfrl qnd SDs00.Irllftl
Addressqble Input cnd lllini lnput Modules
Engineering Specificolions
The contractor shall furnish and install where indicated on the plans, addressable input
modules Silent Knight SD500-A|M or SD500-MlM. The modules shall be UL listed and
compatible with Silent Knight's IntelliKnight FACPs.
The SD500-M|M shallfit inside a single gang electrical box. The SD500-A|M shall be supplied
with a plastic cover and shall be suitable for mounting to a 4"-square or double gang electrical
box. The SD500-AIM addressable input module must provide a monitor LED that is visible
from outside the cover plate.
Iodel3D500{lt
FROt|l UEYT
+18
rod.l SD500{lm
ffiJ"^*
sroE Ytg|t
rll
llln
ilI
iui
iit?i i*il
m
rFl srLENr
IitrKMGHT
7550 Meridian Circle, Maple Grove, MN 55369-4927
EOO-.14F6444 or in Minnesota 7634936435
FAX: 763-493-6475
World Wde Web: http:/ vww.silentknight.com
UADE IH ATERIGA
FORM# 350231. Rev- 11/0t
Copydghl O 2001 Silent Knight
sD500-AtM
Installation
SILENT
KI\UGHT
and SD500-M|M
Instructions
The following instructions are a quick reference
guide, refer to the confiol panel installation
insffuction lnle lliKnight 5 8 2 0 Analog/
Addressable Fire Systern P N 15097 2 fot
detailed system information.
Wiring the SD500-A|M / MIM
Nole: Installotion and wlring of these devices must be
done in accorfurrce with NFPA 72 and local
otdinances.
Tefidnate the wiring as shown in Table L See
also Figure l.
Speclfications
Table 2 lists the operating specifications for the
SD500-AIM and the SD500-MIM.
Table 2: SD300.All, and gDsoo-tlll{ Speclflcations
Figure l: Wring the SD500-Alt and SOsm.Hil
Setting the Device Address
The range ofvalid addresses is I - 127 (0 is an
invalid address). Refer to Figwe 2 to set the dip
switches to the desired address.
Table l: Wre Connestlons
sD500.AtM
so5txt-iltt
Terminals
To:
5820 or 58{5
Termlnals Contac-t
sLc sLc
ouT
sc-..
+s+
Contac{
A :,t..:-' ' -..-:-,i
t- . . ,tt.
To N.O. Coftact
B To N,O. Contact
Specltlcadons
Mar Line resistaace 5Oft
lvhL Alarm
Cunent
One device in alarm
23mA. 46 mA for two
devices in alarm.
.5 mA for each addi-
tional device in alam.
Max. Voltage 33V
Operating Temperature 0o to 49o C
(32" to 120" F)
Indoor use onlv
P/N 151071
' 5D500-A\M and SD50ID-M\M lnstalhtion lnstructions
StatuE LEI'
Mounting the SD500-A|M
Mount the SD500-AM into a double gang box
as shown in Figure 3.
Mounting the SD500-M|M
Use the adhesive-backed velcro pad to mount
the SD500-MM into a single gang box as
shown in Figure 3.
t ++I Addrsilsrs I Lr,*t 3 ,l g t€ 1l 6il i.hfll
ftld lh6 rElriEE d tlE dS E|rlEhEE h fi* 'dltt' j
tE*filr|lltfrldarian |.liffi.Ib j. rddm* intb rIr|dr ir *?. ef,drF t. + 5 ,ril $rd 6 rE q'r hsNtn! rdK d /
\r.rrfna:p;$ /-.,. /t.., t"
Figure 2: Setting the Device Address.
Nole: The dip switch settings shown in Figwe 2 apply to
the 5D500-MIM also.
7550 Meridian Circle
Maple Grove, MN 553694927
6r2493-64ss
800-328-0r03
Fax: 612-493-6475
@ 1997 SilentKnight
P/N 15l07l, Rev. A, lll97
SILENT
KI\IGHT
P/N 151071
at
GiEIUTEX
Gommander3 Series Selectable
Gandela Evacuation
Applications
The Commander3 Series is a low
orofile slrobe or horn/strobe
combination that offers dependable
audible and visual alarms and the
lowest current available.
The GE3 Series offers field
selectable candela options of 15, 30,
60,75, and 110 can{ela.
The Commanderr Series horns
offer a new synchable chime and
whoop tone and provide a selection
of high or low dBA as well as a
selection of a 2400 Hz (remote
signaling) or a low frequency broad
band 1500-3000H2 mechanical
sounding (evacuation) tone where
doors could be a problem.
The GE3 Series are easily field
changeable from temporal 3 to a
conlinuous tone by simply removing a
jumper. The GEC3 is shipped from
Signals
the factory on the temporal lower
frequency mode and it comes
standard with a rugged cast metal
mounting plate.
The Commanderr has a minimal
ooeration current and has a minimum
flash rate of 1Hz regardless of input
voltage,
The Commanderr Series comes
standard with the 4" mounting plate
which incorporates the popular
"Superslideru" feature that allows you
to easily test for supervision. Also
included is a locking mechanism
which secures the product to the
bracket without any pcrews showing
The Commanded (GE3 Series)
appliances are UL 464 and UL 1971,
listed for use with fire protective
systems and are wananted for three
years from date of purchase.
GES3 GEC3
Standard Features
. Field selectable candela options of 15, 30, 60, 75,
and 110 candela
. Prewire Entire System, Then Install Your Signals. Ease of Supervision Testing (Super SlideJ. Lower Installation and Operating Costs. Input Terminals 12 to 18 AWG. Switch Selection for Hlgh or Low dBA
. Switch Selection for High or Low Frequency
(1500-3000 Hz). Switch for Temporal 3, Chime, orWhoop Tones. Tamperproof Re-entrant Grill
. Surface Mount with the GSB (Gentex Surface
Mount Box)
Synchronize Strobe and/or Horn by Using the
AVS-44 Control Module
Silence Horn While Strobes Remain Flashing
Rugged Die Cast Metal Mounting Bracket
True Evacuation Tone
. Wide Voltage Range 16-33 VDC or FWR
' Seoarate Hom and Strobe Functions. Available in Red or Off-White
Approvals
'@"ffiIHE
Americans with Disabililies Act (ADA 4.28.3)
BFP (City of Chicago)
BS+A/MEA #285-9.|-E
CSFM 7.|35-0569:l 22 (GEC3)
712s-0569:.|23 (GES3)
NFPA 72
UL ULC Dual Listsd 464. l97l
i
GES3 24 VDC Selectable Gandela Low Profile Evacuation Strobe Wall Mount
Model Number Part Number Nominal Gandela
Voltaqe (uL 1971)
GES3-24WR 90+1321-002 24VDC 15.30. 60.75. 110
GES3-24WW 90+1319-002 24VDC 15.30. 60.75. 110
GES3-24PWR 90+1322-OO2 24]/DC 15.30. 60. 75.'t10
GES3-24PWW 904-1320,002 24VDC 15.30. 60,75. 110
GEC3 24VDC Selectable Candela Low Profile Evacuation Horn/Strobe Wall
Model Number Part Number Nominal Gandela dBA@
Voltase (uL 1971)10 Ft
GG€g*lrlu{R..90+1317402 24 VDC 15.30. 60.75. 110 100
GEC3-24WW 90+1315-002 24VDC 15.30. 60.75. 110 100
GEC3-24PWR 90+1318-002 24VDC 15. 30. 60. 75. 110 100
GEC3-24PWW 904-1316402 24VDC 15, 30, 60, 75, 110 100
Notes:
The GE3 Series is not listed for outdoor use. Operating temperature: 32"to 120'F (0'to 49" C)
Model designations:
"W" = Wall Mount
"R" = Red Faceolate
"W" = Off-White Faceolate
"P" = Plain (no lettering) Available with all models. These units are non-returnable.
"Agent" bezel also available.
Operatinq Strobe Current @ 24VDC
15 Candela 55mA
30 Candela 63mA
60 Candela 88mA
75 Candela 1zmA
1 10 Candela 136mA
Note: For nominal and peak current across UL regulated voltage range for filtered DC
power and unfiltered (FWR [Full Wave Rectilied]) power, see installation manual.
DBA @ 10 ft. per
UL454 (Hichl
DBA @ 10 ft. per
111464 (Lowl
Dc (mA)
Horn Mode 16v 2$t 33v 16v 24v 33v 16Y 24v 33v
Temo 3 2400H2 7A 83 84 71'75 77 13 19 24
Temo 3 Mechanical 76 81 82 70'73-/b 16 22
Tcmn 3 Chime 70*7't).7'1,66.68.70'I 12 .15
.g€nfirr6&$:ltlgis.:81 86 87 78 80 '14 21 28
Continuous Mechanical 80 84 85 72*76 78 13 18 25
Continuous Chime 70'7l',73.66"68.70-10 15
Whoon 82 6.1 83 6S*72"/5 43 51 56
.Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level required
for public mode fire protection service. These settings are acceptable only for private mode Jire alarm use. Use the high
dBA sotting for public rnode application (not applicable when using the chime tone. The chime tone is always private
mode).
Notes: The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound
output rating.
While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous
mooe,
*...-.._-...::.:.......... Ir' 'l ti..t.--.-----.--.-.\, | |:il,iiil
il lr ilrit::ll:. it I
i"i. .... r' ;
i..,i;lil.$i$,,. I
iiq$iiit[llif . Iii'"'"'ll
ii..4if#**iii.ri :l.. . "l::':":'::-'" " ., I
1
Dlmensions
Switch Locations
Mounting Super Slide"
Die Casl Metal Mounting Plate: Mounts to single gang,
double gang 4" square boxes or GSB box.
Gandela
Selection
Candela sel€dion s1!d€.
snilch D€pr€ss c€dtr
and slide silch lo desied
Br€ak ofi pin andins€d inta
hol. al th. botrom ofthe
sel.clor to lo.& candela s€lting
Sagnal musl be remov€d rdn
bGck€r d pin grshed foNard
frbm ba.*sid€ o|r of hole
Gonventional GES3/GEG3 Series Wiring Diagrams
UL L|bd
Cqltdhl
&f.tthd{l|rl Clrqdf
Sl,\4ICl-l POSTION
Hiconl
Swr'tch Position 6
ON > HIGH dB
OFF> LOW dB
as Switch pollllons 1 rnd 2
lh lhe off porition lo 3€l€ct
isolat d horn afld Elrobd
pourer hputs.
HEHEEH123456
Removing Bezel
UL Lbbd
Contsol
Prt|el
Sryrnrked
thnrl Clreuit
Wiri4g Diagram GE3 Series with AVS44 Synchronizatlon Module
rEtft*fitr
r|glatctt
Architect & Engineering Specifications:
The audible and/or visible signal shall be Gentex GE3 Series or approved equal and shall be listed by Underwriters
Laboratories Inc. per UL 1971and/or UL 464. The notification appliance shallalso be listed with the California State Fire
Marshall (CSFMi and the Bureau of Standards and Appeals (NYC).
The notification appliance (combination audible/visible) shall produce a peak sound outpul of 100dBA or greater at 24V
as measured in an anechoic chamber. The signaling appliance shallalso have the capability lo silence the audible signal
while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to
select either continuous or temporaltone output with the temporalsignalhaving the ability to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a
trouble signalatthe fire alarm controlpanel.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or greater regardless
ofpowerinputvoltage. Theapplianceshallhaveanoperatingcunentof 55mAorlessal24VDCforthelSCdsirobecircuit.
The appliance shall be polarized to allow for electricalsupervision ofthe system wiring. The unit shallbe provided with a
mounting bracket with terminals with barriers for input/output wiring and be able to mount l0 a single gang or double gang
box or double workbox withoutthe use of an adapter plate. The unitshall have an input voltage range of 16-33 volts with
either direct cunent of full wave rectified power.
The appliance shall be capable oftesting supervision without disconnecting wires. Also the appliance shallbe capable of
mounting to a surface back box,
GiENTE)(EclFIFCIFIATIclN
Fire Prot c{on Producb: www.gentsx.@rn
10985 Chicago Dr., Box 310, Zeeland, Ml 49441
616892-7195 1€00/436€391 FAX 616892-4219
centex @rporation reserves rhe nghl 13 rnake chang* to tie pbduct dda sheets at their dbcretio". *) Prhted on Recyoled PaP€t
24 units per carton
27 pounds per carton
GE30201-3
GiEl\lTE)(
Commander+ Series Selectable
Ceiling Mount Strobe and Horn Strobe
Applicationa
The GCS/GCC Series b a ceiling
mount strobe or hom/strobe
cornbination that offers dependable
zudible and visual ahrms and the
lorcsl cunentarrailable.
The GCS/GCC offers field
seledable candela options of 15, 30,
75, 95, and 115 candela.
The models are easily field
dtatg€able fiorn temporal 3 to a
continuous tone by simply removing
a dip switch. The models are
shipped from the factory in the
tesnponal alarm mode.
The Commandef Series homs
prwide a seledion of high or low
dBA c well as a sdedion of a 24fl)
Hz (remote signaling) or a low
frequency bmad band 1500-3000F12
mechanieal sounding (evacuation)
tone where doors could be a
prcblem.
The GCS/GCC Series comes
standard with he 4" mounting plate
which incorporates the popudar
"Superslideru' bracket that allortrs
yor to easily test for supeMsion.
The GCS/GCC Series has a
minimal operating ornent and has a
minimum flash rate of 1Hz
regadless of input voltage.
Commandef Series appliances are
VL6411971 listed for use wih fire
protective systems and are
wananted for hree years ftorn the
date of purchase.
GCS24 GCG24
Standard Featurce
. Fidd selectable candda options of 15, 30, 75, 95 and
't15 candda. Plavirc Entire Syslem, Then Inshll Your S[nals. Eaecf $nervhiulTe$irg (Super Sllde). Lorver Installation and Openating Costs. Inp* Teminals 12 to 18 A!\G. Switch Sdec{ion tur HQh or Lorv dBA. Srrlldr Selecfion for High or Lot Frequency
{150o3m0l-ts). Tatperymf Re-entnant Gdll. Synchronize Strobe and/or Hom by Using the
AVS44 Control Module. Silence Hom \Mtile Strobes Remain Flashing. Rugged Die Cast Metal Mornting Bnacket. TrueEvrcudionTone. VUde Volhge Rarge 1&33 VDC q F\,1/R. SepraeHom ad Strobe Fundions
. Avail$le in Red or Ofi-Vlhite
Approvals
.nSr"Er=:ffii
. Americans with Disabilities AEt (A0A 4,28.31. BFP (Clty of Chlcago). B9+4,[EA#285.91.E .Pending. CSF|| 7136-0669:122
7125{559r123. NFPA 72. UL tlLC Dual Lbted tl6a, 1971
GGS 24 VDG Ceiling llount Selectable Strobe
ilodel Gentex
Part
Number
Gandela
(uL r97r)Number
GCSa4CR 9(X-1213{X}2 't5, 3{r. 75, 95. 115
GCS24C1^/9,J4..1215{f}2 15.30. 75.95. 115
GCS24PCR s121ffiz 15.30. 75.95. 115
GCS24PCW 9/u{--121ffi2 15.30. 75.95. 115
GCC 24 VDC Geiling Mount Selectable Horn/Strobe
l{obs:
The GC Series is not listed for outdoor use. Operating temperature: 32'to 120.F (0" to 49. C)
Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe
products. See lechnical bulletin number 014 for more information.
fiodel designations:
"C" = Ceiling Mount
"R" - Red Faceplate
'w' = Off-White Faceplate
"P" = Plain (no lettering) Available with all models. These units are non-returnable.
Gandela Operating Strobe
Current @ 24VDC
15 72mA
30 88mA
75 176mA
s 200mA
115 214MA.
ilodel
Number
Gentex-
Part
Number
Gandela
(uL r97r)
In Anechoic
RoomdBA
@r0Ft
GCC24CR 9o+1209002 21mA '15. 30.75.95. 115 100
GCC24CW 9'U,{--1211{0,2 21mA 15. 30.75.95. 115 100
GCC24PCR 90+1210{X}2 21mA 15.30.75.95. 115 1m
GCC24PCW #.1212{tr2 21mA 15, 30,75,95, 115 100
DBA @ r0 fr. per
Ul-48it Glidhl
EA g 10 fr. per
uLl6t fl-owl
Dc(mA)
Ho.n bde l6v 2N 33Y l8v 24,3:Dv tBv 21v 3:tv
TemD 3 2400H2 7A 83 a1 71'75 77 13 19 21
Temp 3 Medranical 76 81 a2 70.73.76 16 22
Conlinuous 2400H2 81 86 a7 74.7A 80 14 21 2A
ConUnuous Meohanical 80 84 85 72.76 7A 13 18 25
'Operating the horn in this mode al this voltag€ will result in nol meeting the minimum UL reverberant sound level
required for public mode fire protection seryice. These setlings are acceptable only for private mode fire alarm use. Use
the high dBA setting for public mode application.
ilotla: Tho sound oulput for lhe temporal 3 tone is rated lower since tho time lhe hom is off is averaged into the sound
ouFui rating.
While the horn is producing a tone in the temporal 3 mode its sound prossure ig lhe eame as the @ntinuous
mode.
tounting 3- SI,|AP COVER OVERASSEMBLY
2. INSERT L@KING SCREW li
I
I
I
Ii
1. SLIDE ONTO BMCKET
DIMENSIONS:6"X 2.6"
Dip Switch Locations Hlhl-rr-rht aa-EIrIEr{.tta
Fb*.
.ntdlblh-
L!lrrtd.
NOTE: To prewnt aacidanlal
cendela seloclion change,
remow the scr€w from lh€
wrlock posilioo ard dace in lie
lod( poe'tio{ sfr€r lhe d€atod
Intlorly ls l€l€dgd.
F"rE €H
o
Gonventional Wiring Diagrams GCSTGCC Series
ffinfl
ttF.ttr|fiIdClfiit
1@-\ '.,-
Eimagltfil
f||nHJ${Cratil
Wiring Diagram GCSTGCC Series Using the AVS44 Synchronization Module
IIIfiT.art
[anI5
Architect & Engineering Specificatlons
The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by
Underrriters Laboralories lnc. per UL 1971 for the GCS and also UL 464 for the GCC. The notification appliance shall also
be lisled with the California State Fire Marshal (CSFM) and lhe Bureau of Standards and Appeals (NYC).
The notification appliance (combination audible/visible units only) shall produce a peak sound output of 90dBA or
gteater as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible
signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be
able to select either conlinuous or temporal lone output with the temporal signal having the ability to be synchronized.
The visible signaling appliance shall also maintain a minimum flash rate of 1Hz or greater regardless of power
input voltage. The appliance shall have an operating curent of 73mA or less at 21 VDC for the 15 Cd.
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided
with teminals with barriers for inpuUoutput wiring and be able to mount t0 a single gang or double gang box or double
wo*box with lhe use of an adapter plate. The unit shall have an input voltage range of l6-33 volts wilh either direct
cunent or full wave rectified power.
GiENTEXcc'rrFtrttATroN
Fire Pmtedion Produds: ur/w,gentex.com
10985 Chicego Dr., Box 310, Zeeland, Ml 49464
616f,192-7195 l-8m/,4i}G8391 FAX: 616/3924219
Ga|b. sFdin r€oftEr 0|€ ritn b rEka dranCra b $e Fodu.t detr d|.ab at lret dloUori.
24 units per carton
29 pounds per cadon
fil *-*"*.0""-
GC010102€
tukdel 5700 tnstallation and .Qperatian Manual
5.2 frllaxirnurn Number of Devices
A total of 50 addressable devices can be used with tlre syttem'
5,3 Wiring Requirements for SLC Bevices
The following information applies to all sLC devices. Refer to the section drat describes the
tlope of devise you ar€ ia*talli+g for details.
5.3,1 Wiring $LC devices in Style tl{Class B}
No speeial wire is reqlire.d fer eddrcssabl,e loopr The wire ean be untwiste4 unshielded' solid
or siranded as long as it rneets lhe Natisnal Eiecttic Code ?6G51 re-grrirements for power
timited fire prctective sigrraling cables.
Maximunr wiring resistancs is 5O ohms.
Maximum loop iength depends on the wire gauge'
lMre Gauge ller. Disbnc.
22 AWG 1500 fEet
18 AWC 3900 feet
16 AWG 6200 feet
14 A\l/c 10,000 ftet
Figwe 5-l and Pigr:re 5*2 show how wire length is determined for out-and-back tap and T-tap
style wiring.
, SLC Circuit i
I $LC devi':€
Dottad tine.f6lh sfiows how
wire disiatlce is calcuhted
tuf the SLC device al tf'e Ead
cf ltre run. The wire dBtance
alusl b€ less than ihe
tnaxirnum per wire g8uge.
<-_-_.----l
I
S,LC device !
I
i
SIC devke
l0aximum loop resistanc€ = 50 ohm$ II
Figure 5.1 Galculatlng wtre run fengthtorasfficost and ba€*
15'!295
Voltage Drop Cabulations
1. Gentex GECS horn strobes have a voltage operating range of 16-33
volts D.C.
2. Silent Knight 5700 NAC Circuit can provide up to 2.5 amps
3. Voltage Drop is 6.35 rrofts for 1000 ft. of 14 gauge wire at 2.5 amps
6.35 volts = 1000 ft. x 2.54 ohms x 2.5 amps
1000 ft.f = RxI
4. 24 volts - 6.35 volts = 17.65 volts
ttrldlat s7O0 lnsiafafiar a*d.Oper*#e* t***ual
3..6.2 Cutrer* {}rffi Wor*slrsgt
(Copy tbe page if additional sparc is requircd')
Trble $2: CslTtnt Calcuffi'r
**
C
B
tl
v
ri
?f
I
J
Aefnr€ Yot Eegfm tnstaffine
fiachd?g8bls BsrY Strs IIrr-,Isd lor 2i[ ]r+.
8fixrdfu, i*tkt-.Alea*
'11s,t{rdncr$hft.StarS$5616"llEtm
7 AT{-"---Zi,?ti
gS $i[
23S *A{E TJ{675 toA
13 AH L-t,{450 nA
'+r $re itEr:' ri&e 6*ery wltt capaaiiy -q2'eater 'thg.a te4xird'
*** f$si?tg rdi paner eni5 llb .rtdndby *r alwtn 6ar7€r2t fer.b#r*l eelculatio* d*iag 24 y-4t, l21l IUC s
249 rac.
*.*i{cxrbwtarnnm&gr refo n t}c aazi*um untbert rhat the coatol pazel ctft contmunicate wilh. In santa dases
iii{ffi ir*i f"i tU" ii& ry4q ai*et,,ay m*it *. tott SB tt S eunstt' k thac ewt m
;:;rilJ"ip"*;'iippty'uwt t"*"i*"Vi-iri"i-itn sflcd,,a+Jar tl* corres ctnfgurstt^n'
3.6*2-t lglaxlrnum tsattery $tandby Load
The table below shows ltc mffiiIlIlII r. tattcry standbylsad for ttrc 5?s- based ol1 24 and tr
brsesf#a*ey. Trr€ *aodby }o4d sslsuletioa$ of liue E.is &s currcnt Fras' ca*eutatisa
Wbrksheei tTable 3-?) must be lq.ss than the nunber slrswn in the table below for thel battery
cirrJ ussl asd stg.rdby h$ss.reqsilpd,
. &e4trlrd fur NFp,a ? Z Al,'(,iliary Pr$.tcc&d F'Ee Alttn system for Fire AI*m fusifB {$$ ea$ ad naow
ffi;#;;A^riitffi*-tyitiiiiffliioiity E#iit1' *a"aisi*t,Etarm conntuaicarar.;Fr*ttnrfttgr
Table 3-?: Surent Galeulr$on Worl(|hest
;ffi;hffi1;;"ffi;;;'w ,;;;;;: i;;; ao.i'E tw'tnat operation' doot twldox **ve Nlat
ond. n&it be incla'ded in the 2'5 A lotat csrent that cal be drgvett Jrom me Wnet
ffiffi tt' tel" e6*e'*rroeitse *$qi&Silat:K&lF.el{s- mt sqpp{nt tfte-Es&"€f'ldHiqs r[Esl{Ert0i[ t!# r$8€o ul Ers:r r|eER€f t* ra4
oowiH.sbrt6" in6i{iis* rlr€ syse-m,6qd4f,ld*4*F}$eryne#i-gia{be.ist5Bsi@tavi**les*'$
fu reeirad lC hmas .ran6l pe*L U,u fat*c, i+ ln c*c.ttoC. &c co.'tc{ beitlry ampereslhour r6ing ae*&d
*61as 3.7
\
CONTRACTOR INFORMATION
Contact
c*/- 0oct z
MVNOEYAIL
75 S. Frontage Rd.
Vail, Coloradg 57 without this informatlon:
Fire Sprinklei Jnop Orawings are requlred at time of permit submittal and
must'include the iollowing-. Permit application will nolpe accepted
Auti t,6 Ttii}i
VALUATIONS FOR ALARM PERMIT
Fire Sprinkfer: $-ffi
Assessors Office at 970-328-8640 or
TION WILL NOT BE ACCEPTED IF INCOMPLETE OR U}
Project #:
Building Permit #;
Sprinkler Permit #:
IC.E.T. Level lll (min) stamp.
Contractor.
(Labor & Materials)
=42 Soq- BO
for Parcel #
ent c
Contact and Phone #'s: q10Town of Vail Reg, No.:
Address: 55/ Nprtll +y-onbes-Maili,
Detailed Location of work: (i.e., floor, unit #, bldg. #)
Workclass: Newpf Addition( ) Remodel ( ) Repair( ) Retrefit( ) Other( )
Type of Bldg.: Single-family ( ) Two-family ( ) MultFfamily ( ) Commercial ( ) Restaurant ( ) Other (r,{
No. of Accommodation Units in this bullding: <)No. of Existing Dwelling Units in this building: O
Does a Fire Sprinkler System Exist: Yes ( ) No WDoes a Flre Alarm Exist: Yes ( ) No (
.HEUEltf gghrr*******ri**rr***********FoR OFFICE USE ONLY****************** fr*****!t***** 't** ****
/
\VAiM8IS\CdCV\FORMS\PERMITS\SPRKPERM.DOC o't t24t2002
,aL:i3--
FdL.' €l flrg
IotecUon,lnc.
04-1808
SUBMITTAL MANUAL
VAIL GYMNASTICS FACILITY
Vail, CO
536 31 % Road Grtnd Juncllonr CO 8'l5l)4 Phone: (97O) 434{AO3 F.x! (97O).134{aO2
EXGEL FIRE
PROTEGTIOil lJrlG,
Vail G1 nma.*ics tr'{cilit}'
Vail, Colorado
tr'ire Protection Product Data Inrler
I
I
t
t
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
EXCEL JOB NUMBER O+T808
Item
l.
r.
3.
.t.
6.
7.
8.
0
lo.
ll.
12.
13.
ll.
15.
t6.
17.
18.
Description
Hldraulic Calcs
Baclflow Preventer
Tanper Sritch
Water florr slitch
Alarn/Strobe
O$erhead fue protectior sprfukler piping per
NFPA 13
Or erlread fire pmtection sprirliler piping per
NFPA 13
O|erhead fire protection theaded fittirrgs
Oterhead fire protection Groored frttings
Check. Globe. & Ball lahes
UpngAt Sprinklers
Pendant Sprinlilers
Sidervall Sprhklers
Siderrall Sprillilers
Upriglrt Sprtuklers
Head Guards
Sprhkler Escutcheols
2%-' Siugle Fire Dept. Corurection
[Iangers
Sprre head cabinet
Identifica tiol Sig:ns
Model
U 72" Febco tvtoctel 850 DC Bacl{lor Assemblr
Potter OSYSU-2
Potter Electric Model VSR-F
Sprhli-Lanu 2+ VDC
Dllaflow Sizes per Hldraulic Calculations
Dl mtlread Sizes per Hldraulic Calculations
Ward. sized per lndraulic calcs.
Central. sized per h1'drau.lic calcs.
United brass
Viking M QR. SSU. Broue. VK 300
VikingMQR. SSP. White. Wi 302
Viking M QR. HSW. Brorue. VK 30+
Viking M QR. D4'HSW. Bronze. VK I78
Tpo EC-ll. SSU. Bronze. TY5l37
Tvco G2
Model 89. Wlite
Croker Model 63-t I
Tolco
As Required
As Required
19.
20
2t.
I
I
I
T
I
t
I
I
I
I
I
t
I
I
I
I
I
t
T
i**tr Job Number: 041808
Remote Area 1 -
150
135
120
'105
*90
8-gt-
o
(D ^^tL '-
45
30
,t(
Waso 600 7so 9oo l oso 12oo 1350
Water flow, gpm
00.@;tatflc Fres sure J
.r z ro-r J(y !F.\Jt J
w
,1 .i
t.m
n@
I
I
with hose st
70.67
I
tt
ftEMS
Syste
I
mdc tman(curve
rt#$Job Number: 0+1806 I
I
I
I
I
I
t
I
I
T
T
I
I
t
T
t
I
t
t
Remote Area 1 -
041808 LMF
Vail Gymnastics Facility
sr.a. c€rti.tbr^i:.e llurlrr
N.t.c.E,T.# 90020
551 N. Frontage Road Vail FD
city ]$b lztpc".Vail iCO | 81657 0+18@'lA.cad
System |aEIn(,I€s)
M.d ttuEd.g SFiJC.. 0*
11-2 K-Factor 30.00 at 7.175 Light Hazard
H@AltusA€om.
100.00 0.1ogprnfft'z I 504.00ft' (Aclual 1 505.40ft'?)
Addltdd H@ 54&4.6
Node Fbw(ooml
&,r*s Ol Spild.r CdclhEd
2s6.00ft'
100.00
q*..n Fb{, D.Ddd I t.iJ $er ii.qdld (m|nil! rio6 $t!c)19'1.20 , ?91.n
M&in6 PE*m Ui6dru In L.aDs
0.000
Muine v.h€ny AboE Gdnd
16.09 b€tween nodes 93 and 49
i.dnnffi
Volutu ..D.city oMr.t Piodr l VduD 6pciy o. Dry FiF.189.79ga1 | 0.01tr
Supplies
i Hose Flow I Static Residual B Flow
Node I (gpm) | (psi) (psi) !" (qpm)
Available @ Total Dennand(psi) (oom)
Required I Safety Margin(Dsi) | (bsi)
1oo.oo_ | l oo.ooo gb.ooo I rzrsoo 99.646 | zgt .zo 70.667 | 28.979
Contractor
0+o71 codtl|ff lcdulrt
Ray Segura I
Excel Fire Protection, Inc.
Fh6. I e*ooo
(e7o) 434-4s03 I
536 31% Road (97O) 4s4O802
rays@excelflre.mm
Grand Junction 81504 excelfire. cotn
Job Numben 0+1808
Description: Remote Area 1 -
+ lrost Demandlng Sprinkler Data
if;*ff
J1^Jr.,'r^ .f
(o .t-.
S
t
I
I
I
T
t
I
I
I
I
I
I
T
I
I
I
I
I
.;iltr
-
r ilBll Job Number 0+1808
l'1
Rernoie Area 1 - Gvm
PipeTvpe Diameter Flow !'elgg8t HWC Friction Loss Lengt'tr
Eq. Length
Total Lenoth
Ptessure
SurmaryDownstream Elevation Discharge K+actor pt pn FittingG
Up{CCtrt
-,.....Route1...BLr I
-,
Q=30.0O 4.10 .\\-\ 0.024238 16'-C
16'-C
Pf 0.388
Pe
Pv
ls \ 29514 -295-
q=30.0o ' X=t12 y z.sogBL
-F
o=6o.eo 832 c=12t \ 0.089544 to-L
16'-C
Pf 1 .qs3
Pe
Pv
14 N-5
29',-5
q:30.80 K=11.? .. 7.563 Sp(-7.563)
w 8.995BL 1.72ffi / O=9 .91 C=120 Y 0.:36'-l
s',-7vl
4'l'-11v,
Pt 8.479
Pe
Pv.
15
19
29'-5
29',-5
q=33.59 K=11.2 8.995
17.474
Spr(c3Gj-
E6|7'A\
N a=94.39 2.91 C=124 \ 0.202041
11',-311
17-8/,
PI t;2.567
Pe 0.614
Pv -*
19
18
295-
28L0 1P QP
17.474
20.655 PO(11'-3%l
-K 0=9a.39 1 .94 C=120 v 0.061915 16 -C
16'-C
Pf 0.991
Pe
Pvt
1E #.3 n 20.655\ 21 .646
-.'.
-- -,
*-'.,.-- ,6.09 c=1V \.0.228516 I J.L
1J-71/'
z0-|71
Pf" 6.087
Pe
Pv
34 28.-0
2A-0
21.ffi
PO(13-7%\
'tt I 6.09 C =2g-2
27-3y
PT
Pe
Fvl
12.670
8.67143
49
28'-0
8'-0
27.733! 49.074 r 4E(6-10)
.20 v0 7'-10
34-1
41'-11%
Pf v 9.585
Pe
Pv,
49
93 *U'e 3:3
49.074\ 58.659 E(6-1 0), PO(1 s'-7%\, C(13-7%:".I 20 16.09 C='l2O I 5'-C Pt v 5.943
Pe 2.1ffi
Pv
93 I 8:0 \ 58.659\ 66.769 BFp(r4.8oo)FR '--
-
a=191.20 io,qg c=tz I V o.oB43J3 o-!
J-{
Pf 0.253
Pe 1.3O1
Pv91
3'-0-
o'-0
. 66.769\ oe.szg
)M I .26 C=14 132',-5y
cJ-!
1ffi',-2y
PT 1 .260
1 .084Pe
Pv
91
'I
0'-0
-24
oo.JzJ
70.667 3E(17-11). S.|..Route2..
fL ;t v Q=30.r/ 4.21 C=1 06
16'-(
Pf r0.406
Pe
PV
29'-5
29'-5
q=30.77 ri11 .2 7.549
\'7.956
Sp(-7.s4s))
t-YQ=8.5i t 6'-c
't 6'-c
Pf w 1 .502
Pe
Pv31
-B'-5
29'-5
q=31.59 K=11 .2 / .vco
r 9.457
sp(-7.s56)
--E!
A'- ._
-
!1f90-er 3.?4 C=120 0.211709 36'r
S-7Y'
41',-111/,
Pf 8.864
Pe
Pv
31
35 zs'-5
q=u.44 K=11 .2 v..F/
14.U2
Sp(-9,457)
e6|7%\RNI I0 0=96.81 13.24 C=124 ' 0.211709
11'-31/t
12-8v.
Pf 2.690
0.614Pe
Pv
35v ZJ -J
28'-0
14.342\ 21 .646 PO61'-3y2\
lEquivatent Pipe Lengtns ot vatffi Lc vatue wti.rttiptier I
| 1 eaua rnsioe oiam*er \ o ut -| \@l =t"ao'Value Of C 10O 130 14O 150
Multiplyrng F3ctol __*_9J1q_____ __ 1.33 1 .51
L=9tv
7c,zg
l;. * yW
:i;tt
-
,i*ff Job Number: 0+1808 I
I
I
t
I
t
t
I
t
I
t
I
I
I
I
t
T
I
I
Description: Remote Area I -PipeTvpe Diameter Flow V"ffiort Length
Eq. Length
Total Lenqth
Pressute
Surmary'Downstream Elevation Discharge K-Faam
Upsteam
AO Arm-OverBL Branch LinegM Cro6s Main
DN Drain
DR Drop
DY Dynamic
FM Feed i/hinFR Feed Riser
MS Miscellaneous
OR Oubigger
RN Riser Nipple
SP SprigST Stard Pipe
UG Underground
Diameter lnch
Elevation FooiFlor gpm
Discharge gpmVelocity fps
Pressure psl
Length Foot
Frbtion Loss pr#Footl-lWC Haen-Willbms ComtaniPt Total pressure al a point in a pipePn Normal pressure at a point in a pipePf Pr6surc lo€s due b ftiction betvreen pdntsPe Pressure due to ele\Etion difiererEe bet^€en indicated pointsPv Velocity pressure at a point in a pipe
ALV
AnSV
D
Balv
BFP
BV
c
opls
Cr
cv
DelV
DPV
E
EE
Ee1
Ee2
t
FDG
'EfEE
Rg
FN
fT
g
Glov
He
HV
Hvd
LtE
Alarm Valve
Angle Valve
BushirE
Ball Valve
Backflot| Preventer
Bufterfly Vatue
Cross Flory Tum 90'
Coupling
Crcs Run
Check Valve
Deluge Valve
Dry Pipe Valvegff Elborv
45" Elbo\.v
111/: EltuN2EElbr!
Flo Device
Fire Departrnent Connection
90' FireLod<CrM) Elbor
45' FareLock(IM) Elborv
Flange
Floating Node
FireLod(CTM) Tee
Gauge
Globe Vah,e
Gate Val\re
Ho€e
Hose Valve
Hydrant
Long Tum Elbo\rv
MeclEnical Tee
Nozre
Pump ln
Pump Out
Post Indicating Valve
Pipe Ouuet
Pressure Relief Valve
Pressure Reducing Valve
Reducer/Adapter
Supply
Swirg Check Valve
Sprinkler
Strainer
Tee Flow Tum 90'
Tee Run
Union
Wifsbo
Water Meter Valve
cap
mecT
Noz
P1
P2
PIV
PO
PrV
PRV
reo
s
sCV
spr
St
T
Tr
U
\MrF
WMV
z
I
t
I
t
I
I
I
I
I
I
I
t
I
I
I
t
I
I
I
Job Number: 04-18O8
RemoteArea l -Gvm
Supply at Node
150
'6
gtu
aoo
60
si
tl
atic Pres€ure 100.000
-1218.00 @ 95.m0
I"
i291.20 r
n@71
f,ith hose s).667 l
lr€ms
iyste m dema
I
nd curue
15
9so 3m 1050
Water tlorv, gpm
1350 1500
Supply at Node 1
100.000
1218.00 @ 95.m0ffi
99.el6 @ 291.20
"'r-t *r*"
191.n@70.67
6!ir.|n D.Ed (l.d|cro lb. st ft)
291 .2o @ 70.667
Job Numb€r: 0+1808
futY t\a
-b -'b (9 Up
-\--=--(ll (:, (:)
t:]
-
E-udv__t L
-1 tr ''| t-----1
.s llll uJ -! llrA EI'E o E
;EEED;1 ?o
o
Job Number: 041808
Rernde Area 2 - Exercise Room
150
135
105
on
gru
Soo
,45
30
15
0
Waso mo zso 9ffi 1o5o 12oo 1350
Water flow, gpm
St.Iic Pres sute 00.00 J
.1218.00 @ 95,000
l-l*].o,lnnJ*o*
10p.51 @ 31.3e3-
System demand curve
ramS
Job Number: 0+1808 I
I
I
I
T
I
T
I
t
I
t
t
t
I
t
I
t
I
I
Rernote Area 2 - E(ercis€ Room
041808 LMF
Vail Gymnastics Facility
$A CrtfEinnAi:.@ tlh!.r
N.t.c-E.T.# 90020
551 N. Frontage Road Vail FD
Vall co 81657 0+18O&1A.cad
llod D.MdiE sFi't.f Dd
5.6 K-Factor 17.34 at 9.592 Light Hazard
H6AffiAtSdF.
1m.00 0.10gpmn3 1075.00ff (Ac{ual 1 080.24n:)
ArEodHEs|dl.
Node Flo/rr(oorn)
t{nb.r Ol Sp.i*Lri C.lc{5<l
b 173.4/.fF
100.00
SFt m fim D..i$! I T.bl t /ii.r R.q.hd (lEldlng fb.. StleG)108.s4 I 208.54
iadin[n Pntu t$.tuE€ h Loop.
0.000
nhitrh\/.bdrAhd Gorn
9.14 between nodes 92 and S
lhitrm \r.&.ry LHrr qond
Vo{Jd c.Drcrly .fl4€t PiF.
189.869a1
V6lE ceclv ot Dry PI6
0.01fl:
Supplies
Node
Hose Flow
{opm}
Static I Residual Fr Flow(psi)l(osi)e{oom}Available @ Total Demand
{DSl} {ODm}
Required I Safety Margin{Dsi) I (Dsi}
1 100.00 | 100.000 1218.00 9S.809 208.54 31.393 | 68.416
Contractor
| 04071
cdldta.n I corctra.
Ray Segura I
Excel Fire Protection. lnc.
Pnm I Ed..rt.
(970) 4314803 |
536 31% Road (970) 4311-0802
rays@excellire.csm
clv Jb
Grand Junction I CO 81504 excelfire-csm
,1il$Job Number: 04'|808
: Remote Area 2 - Exercise Room
t.l) irod Defl|andirE Sprinlder Data
Job Number: 04-1808
: Remote Area 2 - E)€rcise Room
Jn'fuJ,y ' ^l'6t'/+ 6to
wf,b
\- t%"t"ry
\ _
d**r,;
f V 8qs {a ?psi
6
11s,tl
.l
05123/04 TIIU 16:51 $AX
Job Numbs: O'4"1808
DescnPtion. Re{nde Area 2
ff '7o
8 -Fvf r5oo?
t7
2S-6
o'f rzJ_g_______-y.,po ;;&\4.\ 31 878
\ il.Azq 3E(17'11)'S
THU 16:52 FAx
Job Number 0+1808
Remote Arm 2
09/23/04 lgu 10:52 FAX
Job Numbet: 04-188
R€mote Ar€a 2
'.l) ltlcl OerE]dln! Sptrnf'|€r Deb
I
I
t
t
I
I
I
T
T
I
I
I
I
I
t
I
I
I
I
:iii!l
-
.iIff Job Number: 0+1808
Report D6criplbn: Rernote Area 2 - E)(ercis€ Room
9'-0
9'-0
12.8ffi
8'-0
a-0
8'-0
8',-0
a4
8',{
31.393 3E(17-11). S
ga
9{11.115
102
54 1 t .826
12.%4
.6 10.316 SDrG1o
9-0
94
12.268
13.rt31
9'-0 1 1.007
1 1 .115
239 8',-2103 9'-0
)
o"
= '"oo'Schedule tlo Steel Pipe Inside Diarneter
Vafue Of C 100 130 '14o 150
Fac{or 0.713 1.16 1 .33 1.51
Fitinge Legend
ALV
AngV
b
BalV
BFP
BV
cplg
Gr
cv
Delv
DPV
E
EE
Eel
Eez
FDC
fE
fEE
nS
FN
'Tg
Glov
GV
Ho€e
HV
Hyd
LtE
mecT
Notr
P1
P2
PIV
PO
PrV
PRV
red
o
sCV
spr
St
T
tr
U
WirF
WMV
z
Alarm Valve
Angle Vahre
Bushing
Ball Valve
Backflotiv Preventer
Buuerny Valve
Cross Flo,t/ Tum 90'
Coupling
Cross Run
Ch€ck Vahre
Deluge Valve
Dry Pipe Valve9f Elbdiv
45" Elbo{,\,
11./." Elb6!
2%"Elbor,
Fhru Device
Fire Departmenl Connection
90' FireLock(TM) Elbot /
its' FireLock(TM) Elbo,v
Flange
Floating Node
FireLock(TM) Tee
Gauge
Globe Valve
Gate Valve
Hose
Ho€e Valve
Hydrant
Long Turn Elbolfi
Mechankxl Tee
Nozle
Pump In
Pump Out
Post Indliatlng Valr/e
Pipe Outlet
Pressure Relief Valve
Pressure ReducirE Valve
Reducer/Adaprter
Supply
Swing Check Vah,e
Sprinlder
Strainer
Tee Flow Tum g0'
Tee Run
Union
Wirsbo
Water lider Valve
Job Number: 04-18{E
Report Description: RerEte Atea 2 - Exercise Rmm I
I
I
I
I
I
I
I
I
l
t
I
T
I
I
I
I
t
I
Pipe Type Leg€nd ,.
AO Arm-OverBL Eranch Line
CM Cro6s l\rain
DN Drain
DR DropDY Dynamic
FM Feed MainFR Feed Riser
MS Miscellaneous
OR Odrigger
RN Riser Nipple
SP SprigST Stand Plpe
UG
Units Legend
Dhr"t", l*h
Elevation FmtFldiv gpm
DischargE gpm
Valocrty fps
Pressure 6lLength Foot
Frldbn Loqs D6ilFmtHWG Hazen-Williams ConsianiPt Tdal pressure at a point in a pipePn Normal pressure at a point in a pipePf PresBure loss due to fdction betlveen pintsPe Pressure due to ebvaton ditference bet reen indicaled points
Pv Vebcity pr€€sure at a point in a
I
I
I
I
I
I
T
I
I
I
I
I
I
I
I
t
I
I
I
Job Number: 0+1E08
: Remote Area 2 - E(ercise Roorn
Supply at Node
1(F
90
-aD
o-
E/t
a
Eo-
45
15
9so ru 600 900 1050
Water florr, gpm
1m0
I atic F rreaaur€100.000
1218.00 @ 95.000
08.3
)rsten
t.54 wit
+@31r
r derrEr
I
t frse s{rei393-
I
I
I
d cun€
lllls
I
Supply d Node 1
100.000
1218.00 @ 95.000
*& FattriD df T..l
99.809 @ 20ri.54
q-- o.,-td
108.54@31.3S
WnD.n:i(n bd.rs no.r S!..rb)
208.54 @ 31 .3S
Job Number: 0+1808
At€a2-E)(ercbeRoom
E}
I-o!
$
t:l
c:
Dn
E rr ft] EIE
/FEA€A,
&$uaLE Gf{ ECK ASS6Jtds{"y@
EACKFLOW PHEVENfTION
t
I
t
I
I
Characterist!cs
Fhysical Frape#ies
Size of Maintine
Max. Working pre$$ure
Hydrostatic Iest press.
Temperature Range
End Connections
Materials
Main Valve tsody
Coatlng
Shut Of Valves
Trim
Elastomer Discs
Spring
Application
Non-Health Hazard
2 1t2, 3,4" 6', s"
175 PSI {1200 Kpa)
350 PSI (2400 KFa)
324 F to 1400 F (0o C to 600 C)
Flanged ANS| 816.1 Ctass 12S
Ductile iron Grade 65-45-12
Fusion epoxy coaied intemal
and extemal, AWWA CS50-90
NRS resilieni wedge gate valves
AW\4A C509
Sronze
EPDM
Stainless steel
U.S. Fatent No. 4,989,635
MODEL 850 DOUBLE CFIECK ASSEMBI-Y
Agency Con'lpiiance
?1/z* -8" {l-forizontal and VerticeN l,Jp}
" Approveci by the Foundaticn for Cross Connection
Control and Flydraulic Research at the r-.,niversiiv of
Southern California.
. ASSE i Sid. 101s)
" ANS|/AWWA (C510-89)
. 0AN/CSA {864.s). FM Approved"
. UL Listed"
" L€ss gates noi FM apprcved. Les6 gaie6 not UL llstcd unleEB instalsd wlttr
Ll L iisted gaia vaives.
t
t
t
T
I
Options
E uurrra.osay RW Gate vatves
E Wye- Strainer
ffiodel 850 Flow Calnves 6" Minimum
Refer to Lo6al CodesItlE
IA
{t
-E
r!-F
4OO GPM
F
zOCO GPM
MOfiEi- 85e
VERTICAL IhSSfALtATISftt
! l/2* anci 3"
=15an
th 10
q
J
!43
o
4
5000 GFi*
Dirvlems lon'ls arnd Weights
NETWT.HETWf,
"'= o r r o u "thlti!?i*21t2" 403t4 25112 12gA $ 4 418 71t8 199 m417t& 255ft 127tA 101t4 4 1E 7 3tE n1 n3461t4 Z 14318 10114 51t2 81t8 zu 312
' Wlh NRS GatB Vatues
Note: Dime.Eions ar€ nominal.
Alo.,l|ancs must be rnade fornornal manuiadurjng trie.6ncas.
ftfiodel 850
Materlais of Constnl.!ction
850 Top View
iF*FE,i $ffiS EcldustrBes" 6me"iElvt& li i A Unit€d Oominion Comlanv
I
I
I
I
I
I
I
t
I
I
I
t
I
T
t
t
t
T
I
ITEftI DESCRIPTION !,A'ERIAL6 ITEM DESCRIPTION i,TATER|ALS rTEff pESCRtPTtOi{ UATFFTALS'I Body
2 Cor€r
2,1 BRing
2.2 Cap Scr€w
2,3 ilsx Nut
2.4 Erpansion Pin
3 S6at Ring
3.." Gasket
4 Arm
4,1 Bushing€wing Pin
1.2 Swing Pin
5 R€iaining Cllp
5.1 Rolaining CIip
6 Chack Dsk Assy
/ LO6,at Ptn
3 L$/r Spring R6in.
4536 GR 6545-1 2
A536 GR 65-4S12
=PDM
ASTM DzOOO
Plat€d Ste€l
Plated St€El
420 SS
8584 Alloy C83600
EPDM ASTM O2OOO
8584 Alloy Ca3600
Acstal R€sin
304 SS
302 SS
EPDM Coatod GR. 45
Dudile lron with typ6
304 SS Etern
304 SS
8584 Alloy C83600
e Spdng Srem 304 SS9.1 Elastic Sbp Jam Nut 1g€ SS'10 Sp.ing A313 Typ€ 631 SS10,2 Spring Shim A3t3 Type 631 SS10.3 Sprihg Shim Acatat RBEin
{8. oNLY)1l Spring Guids Bt30 A[oy C2000'12 Uprspnng Retnr 8584 A[oy CS360012.1 Bu6hing-Spr. Slsm Acoial Resin13 PivotBeanng B5BS A oyCggBOO14 Flan06 casket Rubber.Fabric'15 BEanng Sock€t Ac€ial R66in16 HexJam Nui i&B SS17 Washer 302 SS18 Flange Nui ptatod Si€ett8.': Flsng6 Nui plated St6d1e c5\B BsE4 A oy c8360o24 golt pht€d Stasl
25 Bolt Ptated Sle€l26 G6sk€t EPDM ASTM DZ0O035 GRins EPDM ASTM D200035.1 Back.UpRlng Acotat Rssin
36 Colief 8584 A oy C8360040 Eall\blv€ 8584 A oy CB440O41 NipplE Bras6
42 Gate Vahe (OS&Y) AVvwA C5O9
43 Bullfi6ed Filtin! 8584 A og Ct360O43.1 Bulkhead Fitting BS&t A$oy CB36O045 Gask€t EPDM ASTM 0200045.1 Gask€t EPDM ASTM D200046 WashBr 896 Altoy A6046.1 Washer 836 A oy 26047 Nut 8584 A oy C836OO47.1 N'rt 8584 A[oy C836OO
P.O. Fox SS70 . Fresno, CA 93747-807c
Ya>|: ZCQ 25?-879'i . wu,!v.cmbjnc.con:
59850 i!E? Al;rndte.iatr. copr*gtdod. prinrad ln UGi i lrl i Ce irtio ! Div ls i tt,i
I
t ePoTrEFr OSYSU-tr, .2
OI,.ITSIDE SCREW AND VOKE VALVE
SUPERVISORY SWTCI{
DIMENSIONSI
t
t
I
I
I
T
I
I
I
I
TYPICAL ELECTRIOAt- COf{I.JECT'IONS
PARTS
,vG, s979-6
TYPTCA!_ SWITCT-| ACT'ION
CLOSED VALV'POS]TiON
JI;N.0.
N.C.
OFEN VAI-VE
coM.
sw #:
TC SUPERVISORY CTRCUII
OF CONTROL PANEi-
II.i DICATING
0€vlcE
END CF
:-lNg
RESISTOR
i o*". ,yrrn-,
N.O.
N.C.
Contacts shown in normal (valve open) condition.DWG. #97e-2
LOCAT CIRCUIT
t
I
I
I
ORDERING IhIFORMAT'IOrT
MODEL D=SCRIPTIONOSYSU-1 Ourside Screw a yoke_supervisory Switch (Singte switch)osYSU'z
ruru.*r;:::.,"=ff:ri:*ff::::t'Optional Cover Tamper Switch Kit
I For pressure reducer type valve installation kits (if required) contaci valve manuiacturer.
T
STK. NO.
1 010106
101 0206
5490233
czcuubz
0090131
I