HomeMy WebLinkAboutF12-0095 Stamped approved
AUTOMATIC FIRE SPRINKLER SYSTEM
EQUIPMENT SUBMITTALS
FOR
ONE WILLOW BRIDGE
RETAIL CS3- OAKLEY
VAIL, CO.
mirage® standard and
Qr concealed pendent
sprinkler vk462 and hp
sprinkler vk463 (k5.6)
technical data
January 27, 2012
the viking corporation, 210 n industrial park drive, hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com
1. description
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-pro-file cover assembly that provides up to ½” (12.7 mm) of vertical adjustment. The two-piece design allows installation and testing of the sprinkler prior to installation of the
cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly
allows easy installation of the cover plate after the system has been tested and the
ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler.
2. listings and approvals
cUlus listed: Category VNIV
Fm approval: Class 2015
nYc approved: MEA 89-92-E, Volume 32
vds approved: Certificate G4080021
lpcB approved: Ref. No. 096e/12
ce certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032
Refer to Approval Chart 1 on page 54c and Design Criteria on page 54d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 54e for FM Approval requirements that must be followed.
3. technical data
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
maximum Working pressure: sprinkler vk463 is rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. high-pressure (hp) sprinklers can be identified by locating “250” stamped on the deflector. sprinkler vk462 is rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2” (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metric†)
Glass-bulb fluid temperature rated to -65°F (-55°C)Patents Pending
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimumoperatingpressureforLPC��andCEinimum operating pressure for LPC�� and CE
Approvals ONLY is 5 psi (0.35 bar).
†Metric K-factor measurement shown is when pressure is measured in ��ar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
material standards:
Sprinkler ��ody: ��rass UNS-C84400
Deflector: Copper UNS-C19500 for Sprinkler VK462
Phosphor ��ronze UNS-C51000 for Sprinkler VK463Deflector Pins: Stainless Steel Alloy��ulb: Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel
UNS-S30400
��utton: ��rass UNS-C36000 Screws: 18-8 Stainless Steel��elleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor ��ronze UNS-C51000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Form No. F_103005 Replaces page 54a-f, dated April 8, 2011.
(Revised VdS Approval.)
viking technical data may be found on
the viking corporation’s Web site at
http://www.vikinggroupinc.com.
the Web site may include a more recent
edition of this technical data page.
Sprinkler 54a
technical data
January 27, 2012
the viking corporation, 210 n industrial park drive, hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com
mirage® standard and
Qr concealed pendent
sprinkler vk462 and hp
sprinkler vk463 (k5.6)
cover assembly materials:
Cover: Copper UNS-C11000
��ase: ��rass UNS-C26000 or UNS-C26800Springs: Nickel Alloy
Solder: Eutectic
ordering information: (Also refer to the current Viking price list.)
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
sprinkler: ��ase Part No. 13503A or HP ��ase Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:Temperature Suffix: 155 °F (68 °C) = ��, 175 °F (79 °C) = D, 200 °F (93 °C) = E
For example, sprinkler VK463 with a 155 °F (68 °C) temperature rating = 13667A��.
cover plate assembly: ��ase Part No. 13504 (2-3/4” diameter), ��ase Part No. 13642 (3-5/16“ diameter), or ��ase Part No. 15394
(square cover plate, 3-5/16” diameter)
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, ��rushed Chrome = F-/��, ��right ��rass = ��, Antique ��rass = ��-/A, ��rushed ��rass = ��-/��, ��rushed Copper = E-/��, Painted White = M-/W, Painted Ivory = M-/I, Painted ��lack = M-/��
Temperature Suffix: 135 °F (57 °C) UL (139 °F (59 °C) FM and LPC��) = A, 165 °F (74 °C) = C For example, cover 13504 with a Polished Chrome finish and a 165 °F (74 °C) temperature rating = 13504FC.
Note: Square cover plate 15394 cULus Listing is for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart.
available Finishes and temperature ratings: Refer to Table 1.
accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
sprinkler Wrenches**:
A. Heavy Duty Wrench Part No. 14047W/�� (available since 2006), or��. Head Cabinet Wrench Part No. 14031*** (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover
(available since 2007)
**Requires a ½” ratchet (not available from Viking). ***Optional for removal of the protective cap. Ideal for sprinkler cabinets.
sprinkler cabinet: Part No. 01731A (available since 1971)
4. installation
Refer to appropriate NFPA Installation Standards.
5. operation
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. inspections, tests and maintenance
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. availaBilitY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. gUaranteeFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Sprinkler 54b
mirage® standard and
Qr concealed pendent
sprinkler vk462 and hp
sprinkler vk463 (k5.6)
technical data
January 27, 2012
the viking corporation, 210 n industrial park drive, hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com
taBle 1: availaBle sprinkler temperatUre ratings and Finishes
sprinkler temperature
classification
sprinkler nominal
temperature rating1
maximum ambient
ceiling temperature2
temperature rating of cover
assembly (required)Bulb color
Ordinary 155 °F (68° C)100 °F (38 °C)135 °F (57 °C) cULus
139 °F (59 °C) FM and LPC��Red
Intermediate 175 °F (79 °C)150 °F (65 °C)165 °F (74 °C)Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)165 °F (74 °C)Green
cover plate Finishes: Polished Chrome, ��rushed Chrome, ��right ��rass, Antique ��rass, ��rushed ��rass, ��rushed Copper, Painted White, Painted Ivory, or Painted ��lack
Footnotes
1 The sprinkler temperature rating is stamped on the sprinkler deflector.
2 ��ased on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
approval chart 1 (Ul)
mirage® concealed pendent sprinklers vk462 and vk463
sprinkler
Base part no.1 sin
npt thread
size
nominal
k-Factor maximum
Water Working
pressure
listings and approvals4
(refer also to design criteria on page 54d.)
inch mm U.s.metric2 cUlus5 nYc vds7 lpcB
standard response applications
13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)----AY1, CZ1 AY1, ��Z1 AY1, CZ18
Quick response applications
13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AV1, ��X1 AV1, ��W16 ------
13667A VK463 1/2”15 5.6 80.6 250 psi (17.2 bar)3 AV1, ��X1 AV1, ��W16 ------
sprinkler temperature ratings
A - 155 °F (68 °C)
�� - 175 °F (79 °C) and 200 °F (93 °C)
C - 200 °F (93 °C)
cover plate assembly temperature ratings9
V - 135°F(57°C)cULusListedcover13504135 °F (57 °C) cULus Listed cover 135041, 136421 (large diam-eter), or 153941 (square cover plate)W - 165 °F (74 °C) cover 135041 or 136421 (large diameter) X - 165°F(74°C)cover13504165 °F (74 °C) cover 135041, or 136421 (large diameter)
Y - 135 °F (57 °C) cover 135041 LPCB Approved as 139 °F (59 °C)
Z - 165 °F (74 °C) cover 135041
cover plate assembly Finishes10
1 - Polished Chrome, ��rushed Chrome,
��right ��rass, Antique ��rass,
��rushed ��rass, ��rushed Copper,
Painted White, Painted Ivory, or
Painted ��lack
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in ��ar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3 The Water Working Pressure rating is stamped on the deflector.
4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
5 Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
6 Accepted for use, City of New York Department of ��uildings, MEA Number 89-92-E, Vol. 32.
7 VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021.
8 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032.
9 The 135/139 °F cover has an orange label. The 165 °F (74 °C) cover has a white label.
10Painted finish consists of Polyester ��aked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
note: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Sprinkler 54c
technical data
January 27, 2012
the viking corporation, 210 n industrial park drive, hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com
mirage® standard and
Qr concealed pendent
sprinkler vk462 and hp
sprinkler vk463 (k5.6)
Sprinkler 54d
Figure 1: identification of custom paint color for concealed covers Figure 2: square cover assembly 15394
design criteria - Ul (Also refer to Approval Chart 1 on page 54c.)
cUlus listing requirements:
Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
For hazard occupancies up to and including Ordinary Hazard, Group II.
Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
Minimum distance from walls is 4 in. (102 mm).
Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall.
The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
note:concealedsprinklersmustbeinstalledinneutralornegativepressureplenumsonly.ote: concealed sprinklers mustbeinstalledinneutralornegativepressureplenumsonly.ust be installed in neutral or negative pressure plenums only.
•
•
•
•
•
•
vds approval requirements:
a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials.
b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight.
c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-cies, except in OH4.
notes: Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which the false ceiling space is protected by a water extinguishing system.
Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which during a fire the pressure above the false ceiling may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
Prepare the sprinkler key.
Remove the plastic cover.
Hold the sprinkler with the wrench and fasten it.
Replace the plastic cover and do not remove until the cover is installed.
1.
2.
3.
4.
important: always refer to Bulletin Form no. F_091699 - care and handling of sprinklers. also refer to page sr1-3 or Qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in accordance with the latest edition of viking technical data, the appropriate standards of nFpa, lpcB, apsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-dards, whenever applicable.
mirage® standard and
Qr concealed pendent
sprinkler vk462 and hp
sprinkler vk463 (k5.6)
technical data
January 27, 2012
the viking corporation, 210 n industrial park drive, hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com
Sprinkler 54e
design criteria - Fm
(Also refer to Approval Chart 2 above.)
Fm approval requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response non-storage concealed pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
note: the Fm installation guidelines may differ from cUlus and/or nFpa criteria.
important: always refer to Bulletin Form no. F_091699 - care and handling of sprinklers. also refer to page sr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in ac-cordance with the latest edition of viking technical data, the appropriate standards of nFpa, Fm global, lpcB, apsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
approval chart 2 (Fm)
mirage® standard response concealed pendent sprinkler vk462
sprinkler Base
part no.1 sin npt thread size nominal k-Factor maximum
Water Working
pressure
Fm approvals3
(refer also to design criteria below.)inch mm U.s.metric2
13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AW1, ��X1
sprinkler temperature ratings
A - 155 °F (68 °C)
�� - 175 °F (79 °C) and 200 °F (93 °C)
cover plate assembly temperature ratings4
W - 139°F(59°C)cover13504139 °F (59 °C) cover 135041, 136421 (large diameter),
or 153941 (square cover plate)
X - 165°F(74°C)cover13504165 °F (74 °C) cover 135041, 136421 (large diameter), or
153941 (square cover plate)
cover plate assembly Finishes5
1 - Polished Chrome, ��rushed Chrome, ��right
��rass, Antique ��rass, ��rushed ��rass,
��rushed Copper, Painted White, Painted
Ivory, or Painted ��lack
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in ��ar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
4 The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
5 Painted finish consists of Polyester ��aked Enamel. Otherpaintcolorsareavailableonrequestwiththesamelistingsasthestandardpaintcolors.Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
note: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
technical data
January 27, 2012
the viking corporation, 210 n industrial park drive, hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com
mirage® standard and
Qr concealed pendent
sprinkler vk462 and hp
sprinkler vk463 (k5.6)
Form No. F_103005
Sprinkler 54f
Figure 4: sprinkler dimensions and cover installation
Figure 3: sprinkler installation and correct Use of Wrenches
Replaces page 54a-f, dated April 8, 2011.
(Revised VdS Approval.)
Wheatland’s Schedule 40 Sprinkler Pipe is a high quality sprinkler pipe offering you the
full range of assurances you require. Schedule 40 Sprinkler Pipe has passed some of the
toughest lab tests ever created for sprinkler pipe.
Wheatland’s schedule 40 Sprinkler Pipe is
made from the highest quality steel in one of
the nation’s most modern and most complete
pipe manufacturing plants. Our proprietary mill
coating offers you a clean, corrosion and heat
resistant surface that outlasts and outperforms
standard lacquer coatings. Plus, this coating
can be quickly and easily painted without special
preparation. Or it may be hot-dipped galvanized
to meet FM requirements for dry systems in
accordance with the zinc coating specifi cation of
ASTM A795. Schedule 40 is also available as
ASTM A 53 in NPS 1 - 6 and is UL & C-UL Listed
and FM Approved.
Wheatland’s Schedule 40 Standard
Wall Sprinkler Pipe meets or
exceeds the following:
UL & C-UL Listed•
FM Approved•
ASTM A795, Type E, Grade A•
Sprinkler Pipe
Specifi cations
NPS
Nominal O.DNominal I.DNominal WallNominal Weight
UL CRR*Pieces
Lift
in.mmin.mmin.mmlbs./ft.kg/m
1”1.31533.41.04926.6.1333.381.682.501.0070
1 1/4”1.66042.21.38035.1.1403.562.273.391.0051
1 1/2”1.90048.31.61040.9.1453.682.724.051.0044
2”2.37560.32.06752.5.1543.913.665.451.0030
* Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY
* The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is
used as the benchmark (value of 1.0).
Please refer to appropriate documentation for
up-to-date listing and approval information.
Specifi cations and descriptions are accurate as
known at time of publication and are subject to
change without notice.
Wheatland’s
Made in the U.S.A. by Wheatland Tube
Company means made to the highest
standards for consistant quality.
Specifi cations and Approvals
700 South Dock Street, Sharon, PA 16146
Ph 800.257.8182 Fax 724.346.7260
www.wheatland.com
Wheatland Tube Company
0309 1.0Mrev02
Effective February 23, 2009 Coated Black Sprinkler Pipe
Page 40
D.I. THREADED FITTINGS
For fire protection services request submittal GRS 1.3
DUCTILE IRON 90 DEG. ELBOW
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1DB900335001.501.500.62
1 1/4DB900445001.751.750.90
1 1/2DB900555001.941.941.20
2DB900665002.252.251.85
DIMENSIONS
DUCTILE IRON STRAIGHT TEE
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1DT3335001.501.500.85
1 1/4DT4445001.751.751.22
1 1/2DT5555001.941.941.55
2DT6665002.252.252.45
DIMENSIONS
DUCTILE IRON RED.90 DEG. ELBOW
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1X1/2DB900315001.261.360.44
1X3/4DB900325001.371.450.52
1 1/4X1/2DB900415001.341.530.64
1 1/4X3/4DB900425001.451.620.72
1 1/4X1DB900435001.581.670.75
1 1/2X1DB900535001.651.800.92
1 1/2X1 1/4DB900545001.821.881.08
2X1/2DB900615001.491.881.08
2X3/4DB900625001.601.971.24
2X1DB900635001.732.021.40
2X1 1/4DB900645001.902.101.52
2X1 1/2DB900655002.022.161.65
DIMENSIONS
DUCTILE IRON COUPLING
NOMINALITEMMAX.DIMENSIONWEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.APIECE
1DCL0335001.670.40
1 1/4DCL0445001.930.57
1 1/2DCL0555002.150.75
2DCL0665002.531.15
DUCTILE IRON RED. COUPLING
NOMINALITEMMAX.DIMENSIONWEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.APIECE
1X1/2DRC0315001.690.39
1X3/4DRC0325001.690.53
DUCTILE IRON 45 DEG. ELBOW
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1DB450335001.121.120.46
1 1/4DB450445001.291.290.73
1 1/2DB450555001.431.430.92
2DB450665001.681.681.50
DIMENSIONS
DUCTILE IRON THREADED FITTINGS ARE UL, ULC LISTED AND FACTORY MUTUAL
APPROVED FOR 500 PSI SERVICE. DUCTILE IRON PER ASTM A 536 GRADE 65-45-
12. DIMENSIONS CONFORM TO ANSI B16.3 CLASS 150. THREADS ARE NPT PER
ANSI/ASME B1.20.1
NOTICE: DUCTILE IRON FITTINGS HAVE HIGHER TENSILE STRENGTH THEN THAT
OF STEEL PIPE. THEREFORE, OVER TIGHTENING CAN CAUSE DAMAGE TO PIPE
THREADS WHICH MAY CAUSE LEAKAGE. DUCTILE IRON
FITTINGS SHOULD BE TIGHTENED THREE TURNS BEYOND
HAND TIGHT, BUT NO MORE THAN FOUR TURNS.
A
Page 41
DUCTILE IRON REDUCING TEE
NOMINALITEMMAX.WEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.ABCPIECE
1X1X1/2DT3315001.261.261.360.64
1X1X3/4DT3325001.371.371.450.73
1X1/2X1DT3135001.501.361.500.71
1X3/4X1DT3235001.501.451.500.76
1X1X1 1/4DT3345001.671.671.580.98
1X1X1 1/2DT3355001.801.801.651.16
1 1/4X1X1/2DT4315001.341.261.530.82
1 1/4X1X3/4DT4325001.451.371.620.90
1 1/4X1X1DT4335001.581.501.671.00
1 1/4X1X1 1/4DT4345001.751.671.751.08
1 1/4X1X1 1/2DT4355001.881.801.821.42
1 1/4X1 1/4X1/2DT4415001.341.341.530.86
1 1/4X1 1/4X3/4DT4425001.451.451.620.92
1 1/4X1 1/4X1DT4435001.581.581.670.95
1 1/4X1 1/4X1 1/2DT4455001.881.881.821.45
1 1/4X1 1/4X2DT4465002.102.101.901.75
1 1/2X1X1/2DT5315001.411.341.660.95
1 1/2X1X3/4DT5325001.521.371.751.14
1 1/2X1X1DT5335001.651.501.801.17
1 1/2X1X1 1/4DT5345001.821.671.881.34
1 1/2X1X1 1/2DT5355001.941.801.941.45
1 1/2X1 1/4X1/2DT5415001.411.341.661.05
1 1/2X1 1/4X3/4DT5425001.521.451.751.15
1 1/2X1 1/4X1DT5435001.651.581.801.25
1 1/2X1 1/4X2DT5465002.162.102.021.90
1 1/2X1 1/2X1/2DT5515001.411.411.161.15
1 1/2X1 1/2X3/4DT5525001.521.521.751.24
1 1/2X1 1/2X1DT5535001.651.651.801.30
1 1/2X1 1/2X1 1/4DT5545001.821.821.881.48
1 1/2X1 1/2X2DT5565002.162.162.021.98
2X1X2DT6365002.252.022.252.15
2X1 1/4X2DT6465002.252.102.252.30
2X1 1/2X1/2DT6515001.491.411.881.50
2X1 1/2X3/4DT6525001.601.521.971.62
2X1 1/2X1DT6535001.731.652.021.64
2X1 1/2X1 1/4DT6545001.901.822.101.80
2X1 1/2X1 1/2DT6555002.021.942.162.00
2X1 1/2X2DT6565002.252.162.252.35
2X2X1/2DT6615001.491.491.881.60
2X2X3/4DT6625001.601.601.971.68
2X2X1DT6635001.731.732.021.85
2X2X1 1/4DT6645001.901.902.102.04
2X2X1 1/2DT6655002.022.022.162.18
2X2X2 1/2DT5565002.602.602.393.61
2 1/2X2X3/4DT7625001.741.602.322.28
DIMENSIONS
DUCTILE IRON CAP
NOMINALITEMMAX.DIMENSIONWEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.APIECE
1DCP0035001.160.32
1 1/4DCP0045001.280.43
1 1/2DCP0055001.330.60
2DCP0065001.450.91
DUCTILE IRON CROSS
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.IABPIECE
1DX0335001.501.500.98
1 1/4DX0445001.751.751.50
1 1/2DX0555001.941.941.90
2DX0665002.252.252.95
1 1/4X1DX0435001.581.671.27
1 1/2X1DX0535001.651.801.48
2X1DX0635001.732.022.10
DIMENSIONS
DT667
DUCTILE IRON BUSHINGS
NOMINALITEM
SIZECODE
(INCH)#
DIMENSIONS
1x1/2DBUSH310.750.251.42OUT
1x3/4DBUSH320.750.251.42OUT
1 1/4x1DBUSH430.800.281.76OUT
1 1/2x1DBUSH530.830.312.00OUT
1 1/2x1 1/4DBUSH540.830.312.00OUT
2x1DBUSH630.880.411.95IN
2x1 1/4DBUSH640.880.342.48OUT
2x1 1/2DBUSH650.880.342.48OUT
0.22
0.17
0.28
0.44
0.30
0.66
0.72
0.61
DIMENSIONS
ABCSTYLE
WT.
EACH
D.I. THREADED FITTINGS
For fire protection services request submittal GRS 1.3
OUTSIDE HEADINSIDE HEAD
Main Office/Manufacturing Facility•1375 Sampson Ave. •Corona, CA 92879 •Ph: 909.737.5599 •Fax: 909.737.0330
Customer Service•800.786.5266
www.tolco.com
86
wwwwww..ttoollccoo..ccoomm
Revision 5/24/2001
™
®a brand of
Fig.200 - “Trimline”Adjustable Band Hanger
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel, Mil.Galvanized to G90
specifications
Function — For fire sprinkler and other general piping
purposes.Knurled swivel nut design permits hanger
adjustment after installation.
Features —
•(1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion.Captured design keeps adjusting nut
from separating with hanger.Hanger is easily
installed around pipe.
•(21/2" thru 8" Spring tension on nut holds it
securely in hanger before installation.Adjusting
nut is easily removed.
Approvals — Underwriters’Laboratories listed (1/2"
thru 8") in the USA (UL)and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8").Conforms to Federal
Specifications WW-H-171E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Maximum Temperature — 650°F
Finish — Mil.Galvanized.For Stainless Steel materi-
als, order TOLCO™ Fig.200WON.
Order By — Figure number and pipe size
Dimensions • Weights
Pipe Rod SizeMax.Rec.Approx.
SizeInchMetric ABLoad Lbs.Length
1/23/88mm or 10mm31/8 25/8 40011
3/43/88mm or 10mm31/8 21/2 40011
13/88mm or 10mm33/8 25/8 40012
11/4 3/88mm or 10mm33/4 27/8 40013
11/2 3/88mm or 10mm37/8 27/8 40014
23/88mm or 10mm41/2 340015
21/2 3/810mm55/8 41/8 60027
33/810mm57/8 460029
31/2 3/810mm73/8 51/4 60034
43/810mm73/8 5100035
51/212mm91/8 61/4 125066
61/212mm101/8 63/4 125073
81/212mm131/8 83/4 1250136
OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE. •CORONA, CA 92879 •PH: 951.737.5599 •FAX: 951.737.0330
CUSTOMER SERVICE•800.786.5266
www.tolco.com
66
wwwwww..ttoollccoo..ccoomm™
®a brand of Revision 9/22/2001
Fig.65 andFig.66
ReversibleC-TypeBeamClamps 3/4" and11/4" ThroatOpenings
Size Range — (Fig.65 and Fig.66) 3/8", 1/2" and 5/8" rod
Material — Carbon Steel with hardened cup point set screw and
jam nut
Function — Recommended for hanging from steel beam where flange
thickness does not exceed 3/4" (Fig.65) or 11/4" (Fig.66).
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps.May be used on top or bot-
tom flange of the beam.(Beveled lip allows hanging from top flange
where clearance is limited.) May be installed with set screw in up or
down position.Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through the clamp.Open
design permits inspection of thread engagement.
Approvals — Underwriters’Laboratories Listed in the USA (UL)and
Canada (cUL).Factory Mutual Engineering approved.Conforms to
Federal Specification WW-H-171E, Type 23 and Manufacturers
Standardization Society SP-69, Type 19.Exceeds requirements of the
National Fire Protection Association (NFPA), Pamphlet 13, 3/8" rod will
support 1/2" thru 4" pipe, 1/2" rod will support 1/2" thru 8" pipe.
Included in our Seismic Restraints Catalog approved by the State of
California Office of Statewide Health Planning and Development
(OSHPD).For additional load, spacing and placement relating to
OSHPD projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish
Fig.65 Patent #4,570,885
Dimensions • Weights
Rod Size Max.Rec.Approx.A B CDEFLoad Lbs.*Wt./100
3/813/16 3/417/16161028
1/211/2 3/419/1611/4 113055
5/811/2 3/419/1611/4 113055
* Max.loads for clamp with set screw in up or down position.
Fig.65
Dimensions • Weights
Rod Size Max.Rec.Approx.A B CDEFLoad Lbs.*Wt./100
3/813/16 11/4 17/16161028
1/211/2 11/4 19/1611/4 113055
5/811/2 11/4 19/1611/4 113055
* Max.loads for clamp with set screw in up or down position.
Fig.66
Component of State of
California OSHPD Approved
Seismic Restraints System
OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE. •CORONA, CA 92879 •PH: 951.737.5599 •FAX: 951.737.0330
CUSTOMER SERVICE•800.786.5266
www.tolco.com
70
wwwwww..ttoollccoo..ccoomm™
®a brand of Revision 8/15/2005
Size Range — Secures 3/8" thru 7/8" hanger rod
Material — Carbon Steel
Function — Secures channel to hanger rod for vertical seismic bracing.
Approvals — Underwriters Laboratories Listed in the USA(UL) and
Canada (cUL).Included in our Seismic Restraints Catalog approved by
the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines
Finish — Electro Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number
Fig.98 - Rod Stiffener
Fig.99 - All ThreadRodCut to Length
Size Range — Secures 3/8" thru 7/8" rod in
1" increments
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter, rod
length and finish
Fig.100 - All ThreadRodFullLengths
Size Range — Secures 3/8" thru 7/8" rod in
10’lengths
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter
and finish
Dimensions • Weights
RodMax.Rec.Load Lbs.
SizeFor Service Temps
650°F750°F
3/8610540
1/211301010
5/818101610
3/427102420
7/837703360
Dimensions • Weights
Max Rec.Load Lbs.
RodFor Service TempsApprox.
Size650°F750°FWt./100
1/424021512
3/861054029
1/21130101053
5/81810161084
3/427102420123
7/837703360169
149604420222
11/4 80007140360
11/2 1163010370510
Component of State of
California OSHPD Approved