HomeMy WebLinkAboutB12-0576 CR2 LOAD CALCSLoad Calculation for 2560 Kinnikinnick Rd Building F unit #1
Main Breaker Size 175Amp Panel Board Size 200Amp
General lighting load
Total SF Ft VA 2340
Small Appliance 3000
Laundry 1500
Total 6840
Minus -3000
Total 3840 x .35=1344
3000 + 1344= 4344va /240v=18 amp
Appliance load
Range 8000
Dryer 6720
Jacuzzi 800
Base Board Heater 19000
Water Heater 6240
Dishwasher 660
Disposal 960
25% of largest motor 240
Total 36380va /240v=151amps
New Load 750va/120=6.25amp
Total House load 41474va/240v=173amps