Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutB12-0355 Radar eng report on air balancing
12/17/12 Mountain Standard p 1 of 1
PO BOX 8610 • AVON, CO 81620 • Telephone 970-845-7910
Fax 970-845-7522 • E-mail drader@raderengineering.com
MEMO
TO: Mark Hallenbeck, Rocky Mountain Construction Group
FROM: Bryan Houle, Rader Engineering
DATE: 12/17/12
RE: Grease Duct Clean-outs and Test, Adjust & Balance Report
Items:
1. Section 506.3.8.2 of the 2009 IMC requires inline fans to have clean-outs at both the inlet
and outlet of the fan. Each kitchen exhaust fan (KEF-1 & KEF-2) has two built-in access
doors which can serve as clean-outs. Because the doors are located on the upstream side
of the impeller, these can count as clean-outs for the inlet side of the fan. There are field
installed clean-outs at the outlet side of each fan. Therefore, the installation meets the
intent of the cited code section.
2. We have reviewed the TAB Report (dated 12/15/12) and have the following comments:
a. All fan airflow is within 10% of design (industry standard) and we take no
exception to the restaurant opening to the public tomorrow, as planned.
b. MAU-1 make-up air unit is at 91% of design airflow. Please have the TAB
contractor adjust the drive system to achieve 100%. It is my understanding
that a pulley is on order and once installed, 100% will be possible. Looking at the
current amp draw as compared to the max amp rating of the motor, there is
sufficient capacity to achieve 100%.
c. KEF-1 kitchen exhaust fan is at 90% of design airflow. Please have the TAB
contractor adjust the drive system to achieve 100%. Looking at the current
amp draw as compared to the max amp rating of the motor, there is sufficient
capacity to achieve 100%.
d. Please submit a final TAB Report to Rader Engineering for our records.
Sincerely,
Bryan J. Houle, PE
12/17/12