HomeMy WebLinkAboutF13-0001 EQUIPMENTThe Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bu l l e t i n 0 0 6 Re v . F Bulletin 006 Rev. F Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features Very low water flow requirements. ½” (13mm) Total adjustment. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. Smooth aesthetic ceiling profile. Available in brass, chrome and black plated or painted finishes. Listings & Approval Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has dem- onstrated, in fire testing, an ability for controlling residen- tial fires, and thereby providing significant evacuation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, concealing 1. 2. 3. 4. 5. 1. 2. the most dependable fire protection available, an automat- ic sprinkler system. The RFC30, RFC43 and RFC49 are UL Listed Residential Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit accurately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Application and Installation The RFC30, RFC43 and RFC49, for residential installa- tions, use a 165°F (74°C) fusible solder link in a tuning fork style sprinkler frame with a drop-down deflector. This as- sembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classification solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to 2. ceiling temperature. The subsequent operation of the sol- der link opens the waterway and causes the deflector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler deflector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The residential distri- bution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces significantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexagonal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe installation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COVERS. Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2” (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final adjust- ment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover removal requires turning in the counter-clockwise direction. In ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or negative pressur- ization but must not be positively pressurized. Inspect all sprinklers after installation to ensure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air flow impediment. Temperature Rating SprinklerCover PlateMax. Ambient Temp. 165°F/74°C 135°F/57°C 100°F/38°C Installation Data: RFC30 (SIN RA0611) Thread Size inch (mm) K Factor Sprinkler Spacing ft. (m) Maximum Distance to Wall ft. (m) Minimum Distance between sprinklers ft. (m) Minimum Required Sprinkler Discharge Flow gpm (Lpm) Press. psi (bar) ½” (15mm) ½” (15mm) 3.0 3.0 12 x 12 (3.6x3.6) 14 x 14 (4.3x4.3) 6 (1.83) 7 (2.13) 8 (2.43) 8 (2.43) 9 (34.1) 10 (37.8) 9.0 (0.62) 11 (0.76) Note: 1 bar = 100 Kpa Installation Data: RFC43 (SIN RA0612) Thread Size inch (mm) K Factor Sprinkler Spacing ft. (m) Maximum Distance to Wall ft. (m) Minimum Distance between sprinklers ft. (m) Minimum Required Sprinkler Discharge Flow gpm (Lpm) Press. psi (bar) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm) 4.3 4.3 4.3 4.3 4.3 12 x 12 (3.6x3.6) 14 x 14 (4.3x4.3) 16 x 16 (4.9x4.9) 18 x 18 (5.5x5.5) 20 x 20 (6.0x6.0) 6 (1.83) 7 (2.13) 8 (2.43) 9 (2.74) 10 (3.05) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43) 12 (45) 13 (49) 13 (49) 18 (68) 21 (79) 7.8 (0.54) 9.1 (0.63) 9.1 (0.63) 17.5 (1.21) 23.8 (1.64) Note: 1 bar = 100 Kpa Installation Data: RFC49 (RA0616) Thread Size inch (mm) K Factor Sprinkler Spacing ft. (m) Maximum Distance to Wall ft. (m) Minimum Distance between sprinklers ft. (m) Minimum Required Sprinkler Discharge Flow gpm (Lpm) Press. psi (bar) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm)½” (15mm) 4.9 4.9 4.9 4.94.9 12 x 12 (3.6x3.6) 14 x 14 (4.3x4.3) 16 x 16 (4.9x4.9) 18 x 18 (5.5x5.5)20 x 20 (6.0x6.0) 6 (1.83) 7 (2.13) 8 (2.43) 9 (2.74)10 (3.05) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43)8 (2.43) 13 (49) 13 (49) 13 (49) 17 (64.3)20 (75.7) 7.0 (0.48) 7.0 (0.48) 7.0 (0.48) 12.0 (0.83)16.7 (1.14) Note: 1 bar = 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 3. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gen- tle vacuuming. Remove any sprinkler cover plate assem- bly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specifi cation Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop-down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K-factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91 (70) having a 5/16”, 3/8” and 7/16” orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a ½” cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). Ordering Information Specify: Sprinkler Model Cover Plate Finish Thread-On or Push-On Feature 1. 2. 3. Cover Plate Finishes (1) Standard Finishes Chrome White Special Application Finishes Bright Brass Black Plating Black Paint Off WhiteSatin Chrome (1) Other colors and finishes avail- able. Consult factory for details. Note: Paint or any other coatings applied over the factory finish will void all approvals and warran-ties. The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A 02/11 P/N 9999970261 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrical sprinkler alarm switches Water flow detectors • • • • • • • • • • • • • • • • Deluge valves Detector check valves Check valves Electrical system Sprinkler emergency cabinets Sprinkler wrenches Sprinkler escutcheons and guards Inspectors test connections Sight drains Ball drips and drum drips Control valve seals Air maintenance devices Air compressors Pressure gaugesIdentification signs Fire department connection • • • • • • • • • • • • • • • Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection TheReliableAutomaticSprinklerCo.,Inc.,103FairviewParkDrive,Elmsford,NewYork10523 Bulletin176 Rev.A Bu l l e t i n 1 7 6 Re v . A ModelF1ResSprinklersengineeredforthelowestflows tomeettheminimumdesigndensityof.05gpm/ft2 Types: 1.F1Res49Pendent 2.F1Res49RecessedPendent/F1 3.F1Res49RecessedPendent/FP 4.F1Res49CCPPendent 5.F1Res58Pendent 6.F1Res58RecessedPendent/F1 7.F1Res58RecessedPendent/FP 8.F1Res58CCPPendent 9.F1Res44&58HSW 10.F1Res44&58HSWRecessedHSW/F2 11.F1Res44SWC 12.F1Res76Pendent 13.F1Res76RecessedPendent/F1 14.F1Res76RecessedPendent/FP 15.F1Res76CCPPendent Listings&Approvals 1.ListedbyUnderwritersLaboratoriesInc.and ULCertifiedforCanada(cULus) 2.NYCMEA258-93-E ProductDescription ModelF1ResPendentsprinklers(Figs.1,2,3&4) combineexcellentdurability,highsensitivityglass-bulb andlowprofiledecorativedesign. The3mmglass-bulbpendentsprinklerspermitthe efficientuseofresidentialwatersuppliesforsprinkler coverageinresidentialfireprotectiondesign. ThelowflowF1Ressprinklersarespecially engineeredforfastthermalresponsetomeetthe sensitivefireprotectionapplicationneedsofthelatest residentialmarketstandards(UL1626Standard * Uponfireconditions,risingheatcausesasprinkler’s heat-sensitiveglass-bulbtoshatter,releasingthe waterwayforwaterflowontothedeflector,evenly distributingthedischargedwatertocontrolafire. F1Res49,58&76 RecessedPendent/F1 F1Res49,58&76 RecessedPendent/FP F1Res49,58&76 CCPPendent ULListingCategory ResidentialAutomaticSprinkler ULGuideNumber VKKW Patents USPatentNo.6,516,893appliestothe ModelF1Res49&58PendentSprinklers TechnicalData: •ThermalSensor:Nominal3mmglass-bulb •SprinklerFrame:BrassCasting •Sprinklers’PressureRating:175psi FactoryHydrostaticallyTestedto500psi •ThreadSize:½”NPT(R1/2) •K-Factor:4.9(Actual)-F1Res49PendentSprinkler 5.8(Actual)-F1Res58Pendent&HSWSprinkler 7.6(Actual)-F1Res76PendentSprinkler 4.4(Actual)-F1Res44HSWSprinkler •Density:Minimum0.10gpm/ft2 Application ModelF1ResSprinklersareusedforResidentialFire ProtectionaccordingtoUL1626Standard*.Besure thatorificesize,temperaturerating,deflectorstyleand sprinklertypeareinaccordancewiththelatest publishedstandardsofTheNationalFireProtection Associationortheapprovingauthorityhaving jurisdiction. WhenusingF1ResidentialSprinklersforsystems designtoNFPA13DorNFPA13R,uselistedareaof coverageandminimumflowandpressurerequirements showninBulletin135. ForsystemsdesignedtoNFPA13,useinformationin thisbulletin.Thenumberofdesignsprinklersshallbethe mosthydraulicallydemandingsprinklersasrequiredby NFPA13.Flowsandpressurescannotbebelowthe baselineflowsandpressurers. NFPA13 ForresidentialsprinklersystemsdesignedtoNFPA13, aminimumdensityof0.1gpm/ft2mustbeprovidedover the“designarea”thatincludesthefour(4)hydraulically mostdemandingsprinklersfortheactualcoverage areasbeingprotectedbythe4sprinklers.Theminimum requireddischargefromeachofthefourmost hydraulicallydemandingsprinklersshallbethe greater ofthefollowing: 1.TheflowratesgivenintheReliableResidential SprinklerTechnicalBulletinsreferencedinTableA forNFPA13Dand13Rasafunctionoftemperature ratingandmaximumallowablecoveragearea(for actualcoverageareaslessthanorbetweenthose indicatedintherespectivetechnicalbulletin,itis requiredtousetheminimumrequiredflowforthe nextlargestcoveragearea);or 2.Aminimumdischargedensityof0.1gpm/ft2 appliedoverthe“designarea”consistingofthefour mosthydraulicallydemandingsprinklersforthe actualcoverageareasbeingprotectedbythefour sprinklers.Themaximumdimensionoftheactual coverageareacannotbeanygreaterthanthe maximumcoverageareaindicatedinthetechnical bulletinsreferencedinTableA. DesignNote:UsingtheAs =SxLmethodto determinethesprinklerprotectionareaofcoverage inaccordancewithNFPA13,applythe0.1gpm/ft2 densitytothisareatodeterminetheminimum requiredflow.Comparethisflowtotheminimum 0.05gpm/ft2 cULusListedflowfortheappropriate coverageareainthetechnicalbulletinforthe specificresidentialsprinkler.Iftheflowstatedinthe technicalbulletinislessthanthecalculated0.1 gpm/ft2 densityflowrequired,the.1densityflow mustthenbeusedintheequationQ=K P,solving forP,toestablishtheminimumrequiredpressure usingthesprinklerK-factor.Note:Inmanycases thelistedflowofindividualresidentialsprinklers mayexceedtherequiredminimum0.05gpm/ft2 density.Reliablehasavailableresidentialsprinklers withlargerK-factors(K=5.8andK=7.6)thatwill providelowerpressuredemandsfor0.1gpm/ft2 densitiesinNFPA13residentialapplications. ExampleNo.1 RoomSize=12ftx20ft(3.6mx6.1m) CoverageArea=12x20=240ft2 (22.3m2) Flow@0.10gpm/ft2 density=240x0.10=24gpm UsinganF1Res49PendentSprinkler,K=4.9 Pressure=(24/4.9)2 =24psi(1.65bar) Thebaselineflowfora20ftx20ft(6.1mx6.1m) coverageareausingthebaselinedensityof0.05 gpm/ft2 willbe20gpm@16.7psi(75.7L/min@1.14 bar).Therefore,theminimumflowrequiredis24gpm@ 24psi(90.8L/min@1.65bar). ExampleNo.2 RoomSize=8ftx20ft(2.4mx6.1m) CoverageArea=8x20=160ft2 (14.9m2) Flow@0.10gpm/ft2 density=160x0.10=16gpm UsinganF1Res49PendentSprinkler,K=4.9 Pressure=(16/4.9)2 =10.7psi(0.74bar) Thebaselineflowfora20ftx20ft(6.1mx6.1m) coverageareausingthebaselinedensityof0.05 gpm/ft2 willbe20gpm@16.7psi(75.7L/min@1.14 bar).Therefore,theminimumflowrequiredis20gpm@ 16.7psi(75.7L/min@1.14bar). ExampleNo.3 RoomSize=10ftx16ft(3.0mx4.91m) CoverageArea=10x16=160ft2 (14.9m2) Flow@0.10gpm/ft2 density=160x0.10=16gpm UsinganF1Res76PendentSprinkler,K=7.6 Thebaselineflowfora16ftx16ftcoverageareais21 gpm@7.6psi(79.5L/min@0.52bar).Therefore,the minimumflowandpressureis21gpm@7.6psi(79.5 L/min@0.52bar). ExampleNo.4 RoomSize=14ftx18ft(4.3mx5.5m) CoverageArea=14x18=252ft2 (23.6m2) Flow@0.10gpm/ft2 density=252x0.10=25.2gpm (94.6L/min) UsinganF1Res76PendentSprinkler,K=7.6 Pressure=(252/7.6)2 =11psi(0.76bar) Thebaselineflowandpressureofan18ftx18ft coverageareais21gpm@7.6psi(79.5L/min@0.52 bar).Therefore,theminimumflowandpressureis25.2 gpm@11psi(94.6L/min@0.76bar). Ingeneralresidentialsprinklersrequireflowsandpressuresaslistedfor0.05 densitiestoachievetheproperspraypatternsotheflowsandpressuresat0.05densityare thebaselineflowsandpressures.Flowsandpressuresbelowthelisted0.05densityshall notbeused. 2. ModelF1Res49,58&76Pendent 4. Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm)F C F C 12 NPT (R12)716"(11)155 175 68 79 175(12)100 150 38 66 4.92.25(57) Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)13(49)7.0(0.48) R3516 14x14(4.3x4.3)13(49)7.0(0.48) 16x16(4.9x4.9)13(49)7.0(0.48) 18x18(5.5x5.5)17(64.3)12.0(0.83) 20x20(6.1x6.1)20(75.7)16.7(1.14) Deflector-to-ceiling Maximum1 (25mm)to4 (100mm) Type Adjustment Inch(mm) “A” Inch(mm) Faceoffittingto ceiling Inch(mm) F1 34 (19.0)Min.=34 (19.1) Max.=112 (38.1)316 -1516 (4.7-24.0) F2 12 (12.7)Min.=1516 (23.8) Max.=112 (38.1)316 -1116 (4.7-17.4) Escutcheon*,F1orF2,Data: *Note: Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)15(57)9.4(0.65) R3516 14x14(4.3x4.3)16(60.5)10.6(0.73) 16x16(4.9x4.9)17(64.3)12.0(0.83) 18x18(5.5x5.5)19(72)15.0(1.0) 20x20(6.1x6.1)22(83.2)20.2(1.4) *Deflector-to-ceiling Maximum4 (100mm)to8 (203mm) *Note:TheF1Res49pendentandrecessedpendent residentialsprinklerscanbeinstalledperNFPA13in beamedceilingsmeetingthefollowingcriteria: 1.Maximumbeamdepth=7 (178mm) 2.Beamspacingatorgreaterthan7.5ft.(2.3m)oncenter. TechnicalData:F1Res49PendentandRecessedPendent Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)F C F C ½NPT (R½)12"(13)155 175 68 79 175(12)100 150 38 66 5.82.25(57) Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Ceiling-to- Deflector Inch(mm) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)16(61)7.6(0.53) 1-4 (25-100)R3513 14x14(4.3x4.3)16(61)7.6(0.53) 16x16(4.9x4.9)16(61)7.6(0.53) 18x18(5.5x5.5)19(72)10.8(0.75) 20x20(6.1x6.1)22(83.3)14.4(1.0) TechnicalData:F1Res58PendentandRecessedPendent **Baselineflowsandpressuresfor0.05density **Baselineflowsandpressuresfor0.05density **Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures 5. ModelF1Res49,58&76 CCPPendent ModelF1Res49,58&76 RecessedPendent/FP FPpush-on/thread-offescutcheon Fig.4Fig.3 NOTE:TheF1Res76willusea1"x¾"reducer. TechnicalData:F1Res76PendentandRecessedPendent Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)F C F C 3 4 NPT (R34)1732"(13.5)155 175 68 79 175(12)100 150 38 66 7.62.25(57) Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)217.6(0.53) R7618 14x14(4.3x4.3)217.6(0.53) 16x16(4.9x4.9)217.6(0.53) 18x18(5.5x5.5)217.6(0.53) 20x20(6.1x6.1)239.2(0.63) Type Adjustment Inch(mm) “A” Inch(mm) Faceoffittingto ceiling Inch(mm) F1 34(19.0)Min.=34 (19.1) Max.=112 (38.1)316 -1516 (4.7-24.0) F2 12 (12.7)Min.=1516 (23.8) Max.=112 (38.1)316 -1116 (4.7-17.4) *Baselineflowsandpressuresfor0.05density *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures 6. Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)F C F°C F C ½NPT (R½)716"(11)1556813557175(12)100384.9 2.25 (57) Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)13(49)7.0(0.48) R3516 14x14(4.3x4.3)13(49)7.0(0.48) 16x16(4.9x4.9)14(53)8.2(0.56) 18x18(5.5x5.5)18(68.1)13.5(0.93) 20x20(6.1x6.1)20(75.7)16.7(1.14) “A” CoverAdjustment Inch(mm) “B” CCPHeight Inch(mm) 12 (12.7)1516 (24) 316 (4.7)3 4 (19) CCPOptionsData: FPPosition “A” Inch(mm) Max.Recessed 716 (11) Min.Recessed 1516 (24) FPData“A”: TechnicalData:F1Res49CCPPendentandRecessedPendent/FP Note:SprinklersshowninFig.3andFig.4arenot suitableforinstallationinceilingswhichhave positivepressureinthespaceabove. Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm)F C F°C F C NPT (R½)½"(13)1556813557175(12)100385.82.25(57) Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)16(61)7.6(0.53) R3513 14x14(4.3x4.3)16(61)7.6(0.53) 16x16(4.9x4.9)16(61)7.6(0.53) 18x18(5.5x5.5)19(72)10.8(0.75) 20x20(6.1x6.1)22(83.3)14.4(1.0) TechnicalData:F1Res58CCPPendentandRecessedPendent/FP Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembl yTemp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)F C F°C F C ¾NPT (R3/4) 1732" (13.5) 155 175 68 79 13557175(12)100 150 38 66 7.6 2.25 (57) Max.Sprinkler Spacing ft(m) Flow gpm(Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6)217.6(0.53) R7618 14x14(4.3x4.3)217.6(0.53) 16x16(4.9x4.9)217.6(0.53) 18x18(5.5x5.5)228.4(0.58) 20x20(6.1x6.1)2510.8(0.74) TechnicalData:F1Res76CCPPendentandRecessedPendent/FP *Baselineflowsandpressuresfor0.05density *Baselineflowsandpressuresfor0.05density *Baselineflowsandpressuresfor0.05density *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures ModelF1Res44&58HSW ModelF1Res44&58 RecessedHSW/F2 8. ModelF1Res44SWC Fig.5 Max.Sprinkler Spacing ft(m) “A” Ceiling-to- Deflector Inch(mm) Flow gpm (Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6) 4-6 (101-152) 13(49.2)8.7(0.60) R3531 14x14(4.3x4.3)14(53.0)10.2(0.71) 16x16(4.9x4.9)17(64.3)15.0(1.1) 16x18(4.9x5.5)19(71.8)18.7(1.13) 16x20(4.9x6.1)23(87.1)27.4(1.89) 12x12(3.6x3.6) 6-12 (152-305) 14(52.9)10.2(0.71) 14x14(4.3x4.3)15(56.7)11.7(0.81) 16x16(4.9x4.9)18(68.1)16.8(1.16) 16x18(4.9x5.5)20(75.6)20.7(1.43) *Baselineflowsandpressuresfor0.05density Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CoverTemp. Rating Max. Pressure psi (bar) Max. AmbientTemp.K Factor Sprinkler Length Inch (mm)F C F°C F C ½NPT (R½)38"(10)1556813557175(12)100384.42.45(62) TechnicalData:F1Res44SWC *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)F C F C ½NPT (R½)12"(13)155 175 68 79 175(12)100 150 38 66 5.82.45(62) Type Adjustment Inch(mm) FaceofFitting towall Inch(mm) F2 12 (13)316 -1116 (4.7-17.4) Escutcheon,F2,Data: TechnicalData:F1Res58HSW&HSW/F2 Max.Sprinkler Spacing ft(m) “A” Ceiling-to- Deflector Inch(mm) SprinklerTemp. Rating F(C) Flow gpm (Lpm) Pressure psi(bar) Sprinkler Identification Number(SIN) 12x12(3.6x3.6) 4-6 (101-152) 155(68)175(79)16(60.6)7.6(0.53) R3533 14x14(4.3x4.3)155(68)175(79)18(68.2)9.7(0.67) 16x16(4.9x4.9)155(68)175(79)21(79.5)13.2(0.91) 16x18(4.9x5.5)155(68)175(79)25(94.7)18.6(1.28) 16x20(4.9x6.1)155(68)175(79)29(109.8)25(1.73) 12x12(3.6x3.6) 6-12 (152-305) 155(68)175(79)22(83.3)14.4(1.0) 14x14(4.3x4.3)155(68)175(79)22(83.3)14.4(1.0) 16x16(4.9x4.9)155(68)175(79)26(98.4)20.1(1.39) 16x18(4.9x5.5)155(68)175(79)31(117.4)28.6(1.97) *Baselineflowsandpressuresfor0.05density 9. *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures OrderingInformation Specify: 1.SprinklerModel 2.SprinklerType 3.TemperatureRating 4.SprinklerFinish 5.EscutcheonFinish StandardFinishes Sprinkler F1,F2,FPEscutcheons Bronze ChromePlated WhitePolyesterCoated Brass BrightChromePlated WhitePainted SpecialApplicationFinishes Sprinkler F1,F2,Escutcheons BrightBrass BlackPlated BlackPaint OffWhite SatinChrome BrightBrass BlackPlated BlackPaint OffWhite SatinChrome Finishes(1) (1)Otherfinishesandcolorsareavailableonspecialorder. Consultfactoryfordetails. 10. Maintenance ModelF1Res49,F1Res58&F1Res76Sprinklers shouldbeinspectedquarterly,andthesprinklersystem maintainedinaccordancewithNFPA25,13,13D,and 13R.Donotcleansprinklerwithsoapandwater,Ammonia oranyothercleaningfluids.Removedustbyusingasoft brushorgentlevacuuming.Removeanysprinklerwhich hasbeenpainted(otherthanfactoryapplied)ordamaged inanyway.Astockofsparesprinklersshouldbe maintainedtoallowquickreplacementofdamagedor operatedsprinklers.Priortoinstallation,sprinklersshould remainintheoriginalcartonsandpackaginguntilused. Thiswillminimizethepotentialfordamagetosprinklersthat couldcauseimproperoperationornon-operation. ModelF1RES49Residential SprinklerSpecifications ModelF1Res49&58Pendent Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialpendent sprinklersengineeredtoprovideaminimumdesign densityof0.10gpm/ft2 overthelistedcoveragearea. Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’s installationguidelinesandtheapplicableinstallation standard.Wherependentresidentialsprinklersare installedunderslopedceilingshavingapitchofupto[4/12] [8/12],thesprinklersshallbelistedforsuchuse. Deflector-to-ceilingdistancelistingshallbe1”to8” maximum.Sprinklerframeanddeflectorshallbeofbronze frameconstructionhavinga½”NPTthread.Waterseal assemblyshallconsistofaTeflon-coatedBellevillespring washerandtop-loadedextrudedcupwith3mmglassbulb containingnoplasticparts,andhavingatemperature ratingof[155 F(68 C)][175 F(79 C)].Sprinklersshall haveanominalK-factorof4.9&5.8.Standardfinish: [Bronze][Chrome-plated][WhitePolyester][Specialfinish– specify].ResidentialpendentsprinklersshallbeReliable ModelF1Res49&58,SINR3516&R3513(Bulletin135). ModelF1Res49&58RecessedPendent/F1, ModelF1Res49&58RecessedPendent/F2, ModelF1Res49&58RecessedPendent/FP Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialrecessed pendentsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft2 overthelistedcoveragearea. Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’sinstallation guidelinesandtheapplicableinstallationstandard.Where pendentresidentialsprinklersareinstalledundersloped ceilingshavingapitchofupto[4/12][8/12],thesprinklers shallbelistedforsuchuse.Deflector-to-ceilingdistance listingshallbe1”to8”maximum.Sprinklerframeand deflectorshallbeofbronzeframeconstructionhavinga½” NPTthread.Watersealassemblyshallconsistofa Teflon-coatedBellevillespringwasherandtop-loaded extrudedcupwith3mmglassbulbcontainingnoplastic parts,andhavingatemperatureratingof[155 F(68 C)] [175 F(79 C)].SprinklersshallhaveanominalK-factorof 4.9(70).Standardfinish:[Bronze][Chrome-plated][White Polyester][Specialfinish–specify].Recessedescutcheon assemblyshallbeasteel,two-pieceescutcheon[with½” adjustment(ModelF2)][with¾”adjustment(ModelF1)][of push-onandthreadoffdesignwith½”adjustment(Model FP)].Standardfinishshallbe[brass][brightchrome][white painted].Residentialrecessedpendentsprinklersshallbe Reliable[ModelF1Res49&58RecessedPendent/F1] [ModelF1Res49&58RecessedPendent/F2][ModelF1 Res49&58RecessedPendent/FP]SINR3516&R3513 (Bulletin135). ModelF1Res49&58CCPPendent(Concealed) Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialconcealed sprinklersengineeredtoprovideaminimumdesign densityof0.10gpm/ft2 overthelistedcoveragearea. Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshall beinstalledinconformancewiththemanufacturer’s installationguidelinesandtheapplicableinstallation standard.Wherependentresidentialsprinklersare installedunderslopedceilingshavingapitchofupto [4/12][8/12],thesprinklersshallbelistedforsuchuse. Sprinklerframeanddeflectorshallbeofbronzeframe constructionhavinga½”NPTthread.Waterseal assemblyshallconsistofaTeflon-coatedBelleville springwasherandtop-loadedextrudedcupwith3mm glassbulbcontainingnoplasticparts,andhavinga temperatureratingof155 F(68 C).Coverplate assemblyshallconsistofabrasscoverplateandcopper alloyretainerflange.Methodofattachingthecoverplate tothesprinklercupshallbeapush-onandthread-off designallowinga½”coverplateadjustment.Cover platetemperatureratingshallbe135 F(57 C).Aplastic protectivecapshallbeprovidedandfactoryinstalled insidethesprinklercuptoprotectthesprinklerfrom damage,whichcouldoccurduringconstructionbefore thecoverplateisinstalled.Standardcoverplatefinish: [White][CustomColor–specify].].Concealedpendent sprinklersshallbeReliableModelF1Res49&58CCP, SINR3516&R3513(Bulletin135). 11. ModelF1Res44&58HorizontalSidewall Sprinkler Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialhorizontal sidewallsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft2 overthelistedcoverage area.Listedflowsasspecifiedbythemanufacturer’s technicaldatasheetsaretobeused.Residential sprinklersshallbeinstalledinconformancewiththe manufacturer’sinstallationguidelinesandtheapplicable installationstandard.Wherehorizontalsidewall residentialsprinklersareinstalledunderslopedceilings havingapitchofupto[4/12][8/12],thesprinklersshall belistedforsuchuse.Sprinklerframeanddeflectorshall beofbronzeframeconstructionhavinga½”NPTthread. WatersealassemblyshallconsistofaTeflon-coated Bellevillespringwasherandtop-loadedextrudedcup with3mmglassbulbcontainingnoplasticparts,and havingatemperatureratingof[155 F(68 C)][175 F (79 C)].SprinklersshallhaveanominalK-factorof5.8. Standardfinish:[Bronze][Chrome-plated][White Polyester][Specialfinish–specify].Residentialhorizontal sidewallsprinklersshallbeReliableModelF1Res58, SINR3513(Bulletin135). ModelF1Res44&58Recessed HorizontalSidewallSprinkler UsedescriptionfortheModelF1Res58horizontal sidewallsprinklerwiththefollowingmodifications: Replace“horizontalsidewallsprinkler”with“recessed horizontalsprinkler.”Add:Recessedescutcheon assemblyshallbeasteel,two-pieceescutcheonwith½” adjustment(ModelF2).Standardfinishshallbe [brass][brightchrome][whitepainted][Specialfinish– specify].Residentialrecessedhorizontalsidewall sprinklersshallbeReliableModelF1Res58/F2,SIN R3513(Bulletin135). ModelF1Res76Pendent Sprinklersshallbe[cULusListed]lowflowresidential pendentsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft2overthelistedcoveragearea. Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’sinstallation guidelinesandtheapplicableinstallationstandard. Sprinklerframeanddeflectorshallbeofbronzeframe constructionhavinga¾”NPTthread.Watersealassembly shallconsistofaTeflon-coatedBellevillespringwasherand machinedcupwith3mmglassbulbcontainingnoplastic parts,andhavingatemperatureratingof[155 F(68 C)] [175 F(79 C)].SprinklersshallhaveanominalK-factorof 7.6.Standardfinish:[Bronze][Chrome-plated][White Polyester][Specialfinish–specify].Residentialpendent sprinklersshallbeReliableModelF1Res76,SINR7618 (Bulletin135). ModelF1Res76RecessedPendent/F1, ModelF1Res76RecessedPendent/F2, ModelF1Res76RecessedPendent/FP Sprinklersshallbe[cULusListed]lowflowresidential recessedpendentsprinklersengineeredtoprovidea minimumdesigndensityof0.10gpm/ft2 overthelisted coveragearea.Listedflowsasspecifiedbythe manufacturer’stechnicaldatasheetsaretobeused. Residentialsprinklersshallbeinstalledinconformance withthemanufacturer’sinstallationguidelinesandthe applicableinstallationstandard.Sprinklerframeand deflectorshallbeofbronzeframeconstructionhavinga ¾”NPTthread.Watersealassemblyshallconsistofa Teflon-coatedBellevillespringwasherandmachined cupwith3mmglassbulbcontainingnoplasticparts,and havingatemperatureratingof[155 F(68 C)][175 F (79 C)].SprinklersshallhaveanominalK-factorof7.6. Standardfinish:[Bronze][Chrome-plated][White Polyester][Specialfinish–specify].Recessed escutcheonassemblyshallbeasteel,two-piece escutcheon[with½”adjustment(ModelF2)][with¾” adjustment(ModelF1)][ofpush-onandthreadoffdesign with½”adjustment(ModelFP)].Standardfinishshallbe [brass][brightchrome][whitepainted].Residential recessedpendentsprinklersshallbeReliable[ModelF1 Res76RecessedPendent/F1][ModelF1Res76 RecessedPendent/F2][ModelF1Res76Recessed Pendent/FP]SINR7618(Bulletin135). ModelF1Res76CCPPendent(Concealed) Sprinklersshallbe[cULusListed]lowflowresidential concealedsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft2 overthelistedcoveragearea. Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’sinstallation guidelinesandtheapplicableinstallationstandard. Sprinklerframeanddeflectorshallbeofbronzeframe constructionhavinga¾”NPTthread.Watersealassembly shallconsistofaTeflon-coatedBellevillespringwasherand machinedcupwith3mmglassbulbcontainingnoplastic parts,andhavingatemperatureratingof155 F(68 C). Coverplateassemblyshallconsistofabrasscoverplate andcopperalloyretainerflange.Methodofattachingthe coverplatetothesprinklercupshallbeapush-onand thread-offdesignallowinga½”coverplateadjustment. Coverplatetemperatureratingshallbe135 F(57 C).A plasticprotectivecapshallbeprovidedandfactoryinstalled insidethesprinklercuptoprotectthesprinklerfrom damage,whichcouldoccurduringconstructionbeforethe coverplateisinstalled.Standardcoverplatefinish:[White] [CustomColor–specify].].Concealedpendentsprinklers shallbeReliableModelF1Res76CCP,SINR7618(Bulletin 135). Reliable...ForCompleteProtection Reliableoffersawideselectionofsprinklercomponents.Followingaresomeofthemany precision-madeReliableproductsthatguardlifeandpropertyfromfirearoundtheclock. •Automaticsprinklers •Flushautomaticsprinklers •Recessedautomaticsprinklers •Concealedautomaticsprinklers •Adjustableautomaticsprinklers •Dryautomaticsprinklers •Intermediatelevelsprinklers •Opensprinklers •Spraynozzles •Alarmvalves •Retardingchambers •Drypipevalves •Acceleratorsfordrypipevalves •Mechanicalsprinkleralarms •Electricalsprinkleralarmswitches •Waterflowdetectors •Delugevalves •Detectorcheckvalves •Checkvalves •Electricalsystem •Sprinkleremergencycabinets •Sprinklerwrenches •Sprinklerescutcheonsandguards •Inspectorstestconnections •Sightdrains •Balldripsanddrumdrips •Controlvalveseals •Airmaintenancedevices •Aircompressors •Pressuregauges •Identificationsigns •Firedepartmentconnection TheequipmentpresentedinthisbulletinistobeinstalledinaccordancewiththelatestpertinentStandardsoftheNationalFireProtectionAssociation,FactoryMutualResearch Corporation,orothersimilarorganizationsandalsowiththeprovisionsofgovernmentalcodesorordinances,wheneverapplicable. ProductsmanufacturedanddistributedbyRELIABLEhavebeenprotectinglifeandpropertyforover80years,andareinstalledandservicedbythemosthighlyqualifiedandreputable sprinklercontractorslocatedthroughouttheUnitedStates,Canadaandforeigncountries. Manufacturedby (800)431-1588 SalesOffices (800)848-6051 SalesFax (914)829-2042 CorporateOffices www.reliablesprinkler.com InternetAddress Revisionlinesindicateupdatedornewdata. EG.PrintedinU.S.A.05/08P/N9999970322 Recycled Paper Nominal or Standard Size, inches Outside Diameter Inside Diameter Cu ftGal Wall Thickness Contents of Tube per linear ft Cross Sectional Area of Bore, sq inches Weight of Tube Only,poundsper linear ft Weight of Tube & Water,poundsper linear ft Nominal Dimensions, inches Calculated Values (based on nominal dimensions) 3/8 .500.450.025.159.145.214.00110.00826 1/2 .625.569.028.254.204.314.00176.0132 3/4 .875.811.032.517.328.551.00359.0269 1 1.1251.055.035.874.465.843.00607.0454 11/4 1.3751.291.0421.31 .6821.25.00910.0681 11/2 1.6251.527.0491.83 .9401.73.0127.0951 2 2.1252.009.0583.171.462.83.0220.165 21/2 2.6252.495.0654.892.034.14.0340.254 3 3.1252.981.0726.982.685.70.0485.363 31/2 3.6253.459.0839.403.587.64.0653.488 4 4.1253.935.09512.2 4.669.83.0847.634 5 5.1254.907.10918.9 6.6614.8.131.982 6 6.1255.881.12227.2 8.9220.7.1891.41 8 8.1257.785.17047.616.537.1.3312.47 10 10.1259.701.21273.925.657.5.5133.84 12 12.12511.617.254106 36.782.5.7365.51 Nominal or Standard Size, inches Outside Diameter Inside Diameter Cu ftGal Wall Thickness Contents of Tube per linear ft Cross Sectional Area of Bore, sq inches Weightof Tube Only, pounds per linear ft Weightof Tube & Water, pounds per linear ft Nominal Dimensions, inches Calculated Values (based on nominal dimensions) 11/4 1.3751.295.0401.32.6501.22.00917.0686 11/2 1.6251.541.0421.87.8091.62.0130.0971 2 2.1252.041.0423.271.072.48.0227.170 3 3.1253.030.0457.211.694.81.0501.375 4 4.1254.009.05811.6 2.877.88.0806.603 5 5.1254.981.07219.5 4.4312.9.1351.01 6 6.1255.959.08327.9 6.1018.2.1941.45 8 8.1257.907.10949.110.631.8.3412.55 22 TABLE 2c.Dimensions and Physical Characteristics of Copper Tube: TYPE M TABLE 2d.Dimensions and Physical Characteristics of Copper Tube: DMV (Drain, Waste and Vent) 32 TABLE 7.Pressure Loss in Fittings and Valves Expressed as Equivalent Length of Tube, feet NOTES: Allowances are for streamlined soldered fittings and recessed threaded fittings. For threaded fittings, double the allowances shown in the table. The equivalent lengths presented above are based upon a C factor of 150 in the Hazen-Williams friction loss formula. The lengths shown are rounded to the nearest half foot. 3/8 .5—1.5—————1.5 1/2 1.52—————2 5/8 1.5.52—————2.5 3/4 2.53—————3 1 2.514.5——.5——4.5 11/4 315.5.5.5.5——5.5 11/2 41.57.5.5.5——6.5 2 5.529.5.5.5.57.59 21/2 72.512.5.5—11011.5 3 93.51511—1.515.514.5 31/2 93.51411—2—12.5 4 12.552111—21618.5 5 166271.51.5—311.523.5 6 1973422—3.513.526.5 8 29115033—512. 539 Nominal or Standard Size, in Standard Ell 90° TeeCoupling Valves BallGateBtflyCheck Side Branch Straight Run90°45° Fittings 36 ➀ ADAPTERS ELBOWS COUPLINGS FIGURE 5. Selected Pressure Fittings GENERAL NOTES: (a) Fittings are designated by size in the order: 1x2x3 (b) Fitting designs and drawings are for illustration only. Fully Listed and FM Approved Sprinkler Pipe When you specify Schedule-10/Schedule-40 – ABFII sprinkler pipe from Allied Tube & Conduit, you get UL listed and FM approved products. Although these products do not require separate approvals, Schedule-10/Schedule-40 – ABFII gives you the extra quality assurance you demand. Our Sch-10 (1-1⁄4” – 8”) pipe and Sch-40 (1” – 2-1⁄2”) pipe have passed the same thorough lab testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. Galvanized Pipe Schedule-10/Schedule-40 – ABFII product can be “hot-dip” galvanized to meet FM requirements. Superior Coating Our advanced formula mill coating offers a clean, durable surface that is also paintready for custom color applications without special preparation. The internal surface of all black Fire Sprinkler pipe up to 4.5000” in diameter shall be coated with Allied Tube & Conduit Antibacterial Formula “ABF”. American Made Able to meet “Buy American” requirements, and is available through distributors in the USA, Canada, Mexico and Latin America. Specifications & Approvals Schedule-10 – ABFII pipe is in compliance with ASTM A135, Type E Grade A, and NFPA 13. Schedule-40 – ABFII pipe is in compliance with ASTM A135/A795, Type E Grade A, and NFPA 13. Both pipe products have a working pressure rating of 300 psi maximum and also meet the stringent requirement for the following tests: Welded Outlets, Hydrostatic Pressure, Side Wall Rupture, Vibration Test. Schedule-10/Schedule-40 – ABFII Submittal Data Sheet Customer Service (800) 882-5543 Fax: (800) 659-7730 www.alliedtube-sprinkler.com • 16100 S Lathrop Ave. • 11350 Norcom Rd. • 2525 N 27th Ave. • 600 Dean Sievers Place Harvey, IL 60426 Philadelphia, PA 19154 Phoenix, AZ 85009 Morrisville, PA 19067 ©2011 Atkore International, Inc. All Rights Reserved. STP-S5-4-1111 Project: Sprinkler Contractor: Date: Engineer: Specification Reference: System Type: Locations: Comments: Sch-40 – ABFII Specifications NPS Nominal I.D.Wt.Wt. (H20 Filled)CRR In; mm In; mm Lbs/Ft; kg/m Lbs/Ft; kg/m – 1”1.049 1.680 2.05 1 25 26.6 2.5 3.05 – 1¼”1.380 2.270 2.93 1 32 35.1 4.36 4.36 – 1½”1.610 2.720 3.61 1 40 40.9 4.0 5.37 – 2”2.067 3.650 5.13 1 50 52.5 5.4 7.63 – 2½”2.469 5.790 7.86 1 65 62.7 8.6 11.73 – Sch-10 – ABFII Specifications NPS Nominal I.D.Wt.Wt. (H20 Filled)CRR In; mm In; mm Lbs/Ft; kg/m Lbs/Ft; kg/m – 1¼”1.442 1.810 2.525 7.0955 32 36.6 2.7 3.75 – 1½”1.682 2.080 3.04 5.6570 40 42.7 3.1 4.52 – 2”2.157 2.640 4.22 4.5827 50 54.8 3.9 6.28 – 2½”2.635 3.530 5.89 3.5196 65 66.9 5.3 8.77 – 3”3.260 4.330 7.94 2.5550 75 82.8 6.4 11.82 – 4”4.260 5.610 11.78 1.6020 100 108.2 8.3 17.53 – 5”5.295 7.77 17.33 1.4874 125 134.5 11.56 25.80 – 6”6.357 9.290 23.03 1.0251 150 161.5 13.8 34.27 – 8”8.249 16.490 40.15 1.8365 200 209.5 24.5 59.75 – Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50% lighter in weight than the Style 77, the Style 75 coupling is recommended for service up to 500 psi/3450 kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. The Victaulic standard flexible coupling offering for grade “EHP” or “T” gaskets is the Style 177 installation-ready flexible coupling. For all available sizes, the Style 177 is the standard flexible coupling Victaulic supplies in North America for piping systems using Grade “EHP” or “T” gaskets. Contact Victaulic for further details. Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: Orange enamel. • Optional: Hot dipped galvanized and others. Gasket: (specify choice*) • Grade “E” EPDM EPDM (Green color code). Temperature range –30°F to +230°F/–34°C to +110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot +180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade “T” nitrile Nitrile (Orange color code). Temperature range –20°F to +180°F/–29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; except hot, dry air over +140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. NOTE: Additional gasket styles are available. Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. MATERIAL SPECIFICATIONS 06.05_1 Flexible Coupling STYLE 75 06.05CARBON STEEL PIPE – GROOVED COUPLINGS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. . REV_M Exaggerated for clarity SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS VNIIPO DIMENSIONS Size Max. Work Pressure *Max. End Load *Allow. Pipe End Sep. †Deflect. Fr. CL†Bolt/Nut@ No – SizeDimensions – Inches/mm Approx. Wgt. Each Nominal Size Inchesmm Actual Outside Diameter Inchesmm psi kPa Lbs.N Inches mm Per Cplg. Deg. Pipe In./Ft.mm/mInches X Y Z Lbs. kg 1 1.3155006800 – 0.06 2˚ – 43’0.57 2 – 3/8 x 2 2.384.271.771.32533.4345030250 – 1.6 48 61108450.6 1 1/4 1.66050010800 – 0.06 2˚ – 10’0.45 2 – 3/8 x 2 2.684.611.771.43242.2345048050 – 1.6 38 68117450.6 1 1/2 1.90050014200 – 0.06 1˚ – 56’0.40 2 – 3/8 x 2 2.914.821.771.54048.3345063200 – 1.6 33 74122450.6 2 2.37550022150 – 0.06 1˚ – 31’0.32 2 – 3/8 x 2 3.435.221.881.75060.3345098600 – 1.6 26 87133480.8 2 1/2 2.87550032450 – 0.06 1˚ – 15’0.26 2 – 3/8 x 2 3.885.681.881.96573.03450144400 – 1.6 22 98144480.9 76.1 mm 3.00050035350 – 0.06 1˚ – 12’0.26 2 – 3/8 x 2 4.005.901.881.976.13450157300 – 1.6 22 102150480.9 3 3.50050048000 – 0.06 1˚ – 2’0.22 2 – 1/2 x 2 3/4 4.507.001.882.98088.93450213600 – 1.6 18 114178481.3 3 1/2 4.00050063000 – 0.06 0˚ – 54’0.19 2 – 1/2 x 2 3/4 5.007.501.882.990101.63450280350 – 1.6 16 127191481.3 4 4.50050079500 – 0.13 1˚ – 36’0.34 2 – 1/2 x 2 3/4 5.808.032.134.1100114.33450353800 – 3.2 28 147204541.9 108.0 mm 4.25045063800 – 0.13 1˚ – 41’0.35 2 – 12 x 70.0 5.557.792.133.7108.03100283950 – 3.2 29 141198541.7 4 1/2 5.00045088200 – 0.13 1˚ – 26’0.25 2 – 5/8 x 3 1/4 6.139.432.135.5120127.03100392500 – 3.2 21 156240542.5 5 5.563450109350 – 0.13 1˚ – 18’0.27 2 – 5/8 x 3 1/4 6.8810.072.135.8125141.33100486600 – 3.2 23 175256542.6 133.0 mm 5.25045097350 – 0.13 1˚ – 21’0.28 2 – 16 x 82.5 6.559.372.136.0133.03100433250 – 3.2 24 166238542.7 139.7 mm 5.500450106650 – 0.13 1˚ – 18’0.28 2 – 5/8 x 3 1/4 6.809.592.136.3139.73100474600 – 3.2 24 173244542.9 152.4 mm 6.000450127350 – 0.13 1˚ – 12’0.21 2 – 5/8 x 3 1/4 7.3810.481.886.2152.43100566700 – 3.2 18 187266482.8 6 6.625450155250 – 0.13 1˚ – 5’0.23 2 – 5/8 x 3 1/4 8.0011.072.137.0150168.33100 690850 – 3.2 18 203281543.2 159.0 mm 6.250450138000 – 0.13 1˚ – 9’0.24 2 – 16 x 82.5 7.6310.492.136.8159.03100614050 – 3.2 20 194266543.1 8 8.625450262800 – 0.13 0˚ – 50’0.18 2 – 3/4 x 4 1/4 10.3413.972.3212.4200219.131001169450 – 3.2 14 263355595.6 Z X Y * Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. † Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be reduced by: 50% for 3/4 – 3 1/2”/20 – 90 mm; 25% for 4”/100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. 06.05_2 Flexible Coupling STYLE 75 06.05CARBON STEEL PIPE – GROOVED COUPLINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. . REV_M WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. 06.05 Flexible Coupling STYLE 75 CARBON STEEL PIPE – GROOVED COUPLINGS For complete contact information, visit www.victaulic.com 06.05 1470 REV M UPDATED 2/2011 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 06.05 Victaulic offers a broad line of fittings in sizes through 24”/600 mm in a variety of straight and reducing styles. Most standard fittings are cast of durable ductile iron to precise tolerances. Victaulic standard fittings pressure ratings conform to the ratings of Victaulic Style 77 couplings. All fittings are supplied with grooves to permit fast installation without field preparation. The grooved design permits flexibility for easy alignment. These fittings are not intended for use with Victaulic couplings for plain end pipe (refer to Section 14.04 for fittings available for plain end applications). Fittings are provided in various materials including ductile iron, steel or segmentally welded steel depending on styles and size. Fittings are painted orange enamel with a galvanized finish available as an option, contact Victaulic for details. Victaulic fittings are designed specifically for use in grooved piping systems. Fittings are provided grooved conforming to standard steel pipe outside diameters. When connecting wafer or lug-type butterfly valves directly to Victaulic fittings with 741 or 743 Vic-Flange® adapters, check disc clearance dimensions with I.D. dimension of fitting. Note: The following Victaulic fittings are VdS approved: No.10 90º Elbow, No.11 45º Elbow, No.20 Tee and No.60 Cap. Note: The following Victaulic fittings are LPCB approved: No.10 90º Elbow, No.11 45º Elbow, No.12 22 ½º Elbow, No.13 11 ¼º Elbow, No.30 45º Lateral, No.30-R Reducing Lateral, No.100 Long Radius Elbow, No.110 Long Radius Elbow, No.20 Tee, No.35 Cross, No.60 Cap, No.25 Reducing Tee, No.33 True Wye, No.50 Concentric Reducer, No.51 Eccentric Reducer and No.29M Tee with Threaded Branch. Advanced Groove System – For 14 – 24"/350 – 600 mm piping systems, Victaulic now offers the Advanced Groove System (AGS). Refer to Section 20.05 for AGS fitting details. Stainless Steel – Grooved end fittings are available in Schedule 10 Type 316 stainless steel (Schedule 5, 40 and Type 304 available as an option) in various sizes. Fitting center-to-end dimensions will vary depending upon type and schedule. Refer to Section 17.04 and 17.16 for details. Aluminum – Grooved end fittings are available in aluminum alloy 356 T6, in sizes from 1 – 8"/25 – 200 mm. Refer to Section 21.03 or contact Victaulic for details. Fabricated Steel – A full range of fabricated segemtnally welded steel or full flow grooved end fittings are available refer to section 07.04. Fabricated Steel with AGS Vic-Rings – A full range of full flow fabricated fittings with Vic-Rings are also available. AGS – ADVANCED GROOVE SYSTEM ALTERNATE STYLES Extra Heavy EndSeal® “ES” Fittings – EndSeal fittings are available in 2 – 12"/50 – 300 mm for use with “ES” grooved pipe and HP-70ES EndSeal couplings. “ES” fittings are painted black for easy identification. EndSeal (and standard) fittings may be easily internally coated (by others) for severe service requirements. Always specify “ES EndSeal fittings” when ordering. See Section 07.03 for information on EndSeal fittings. Fittings Machined for Rubber or Urethane Lining (MRL) – For severe abrasive services, Victaulic fittings may be rubber or urethane lined (by others). Lining may be inside diameter/end (abrasion resistance) or wrap-around (corrosion and/or abrasion) machined. Refer to Section 25.03 or contact Victaulic for specific details. Note: Fittings are available with a variety of coatings upon request such as hot dip galvanized, epoxy, glass lined and others. 07.01_1 Grooved End Fittings NO. 20 TEE 07.01CARBON STEEL PIPE - GROOVED FITTINGS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q NO. 10 ELBOW SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. tOr: Segmentally welded steel as shown under nipples Nipples: (adapter, swaged & hose) t£ooNN$BSCPOTUFFM 4DIFEVMF DPOGPSNJOHUP"45." 5ZQF' tooNN$BSCPOTUFFM 4DIFEVMF DPOGPSNJOHUP"45." 5ZQF&PS4 (S# tooNN$BSCPOTUFFM 4DIFEVMFPS DPOGPSNJOHUP"45." 5ZQF&PS4  Gr. B Flanged Adapter Nipples: (Nipple – see above) t$MBTT'MBOHF$BTUJSPODPOGPSNJOHUP"/4*# t$MBTT'MBOHF$BSCPOTUFFMDPOGPSNJOHUP"/4*# SBJTFEPSGMBUGBDF t$MBTT'MBOHF$BSCPOTUFFMDPOGPSNJOHUP"/4*# SBJTFEPSGMBUGBDF Fitting Coatings: Orange enamel tOptional: Hot dip galvanized and others. Some fittings supplied electroplated as standard – see product specifications. Flanged Adapter Nipple Coating: None (Unfinished) tOptional: Orange enamel, hot dip galvanized and others. 07.01_2 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q FLOW DATA (Frictional Resistance) The chart expresses the frictional resistance of various Victaulic fittings as equivalent feet of straight pipe. Fittings not listed can be estimated from the data given, for example, a 22½° elbow is approximately one-half the resistance of a 45° elbow. Values of mid-sizes can be interpolated. Size Dimension – Feet/meters Nominal Size In./mm Actual Outside Dia. In./mm Elbows Tees 90° Elbows45° Elbows BranchRun No. 10 Std. Radius No. 100 1 ½ D Long Radius No. 11 Std. Radius No. 110 1 ½ D Long Radius 11.3151.7 —0.8 —4.2 1.7 2533.70.5 0.2 1.3 0.5 22.3753.5 2.5 1.8 1.1 8.5 3.5 5060.31.1 0.8 0.5 0.3 2.6 1.1 76.1 mm 3.0004.3 —2.1 —10.84.3 76.11.3 0.7 3.3 1.3 33.5005.0 3.8 2.6 1.613.05.0 8088.91.5 1.2 0.8 0.5 4.0 1.5 108.0 mm 4.2506.4 —3.2 —15.36.4 108.02.0 0.9 4.7 2.0 44.5006.8 5.0 3.4 2.116.06.8 100114.32.1 1.5 1.0 0.6 4.9 2.1 133.0 mm 5.2508.1 —4.1 —20.08.1 133.02.5 1.2 6.22.5 139.7 mm 5.5008.5 —4.2 —21.08.5 139.72.6 1.3 6.4 2.6 55.5638.5 —4.2 —21.08.5 125141.32.6 1.3 6.4 2.6 159.0 mm 6.2509.4 —4.9 —25.09.6 159.02.9 1.5 7.6 2.9 165.1 mm 6.5009.6 —5.0 —25.010.0 165.12.9 1.5 7.6 3.0 66.62510.07.5 5.0 3.025.010.0 150168.33.0 2.3 1.5 0.9 7.6 3.0 88.62513.09.8 6.5 4.033.013.0 200219.14.0 3.0 2.0 1.210.14.0 1010.75017.012.08.3 5.041.017.0 250273.05.2 3.7 2.5 1.512.55.2 1212.75020.014.510.06.050.020.0 300323.96.1 4.4 3.0 1.815.26.1 1414.00024.5 §15.818.5 §11.070.023.0 350355.6 4.8 5.6 3.421.37.0 1616.00028.0 §18.021.0 §13.080.027.0 400406.4 5.5 6.4 4.024.48.2 1818.00031.0 §20.023.5 §14.090.030.0 450457.0 6.1 7.2 4.327.49.1 2020.00034.0 §22.525.5 §16.0100.033.0 800508.0 6.9 7.8 4.930.510.1 2424.00042.0 §27.029.5 §19.0120.040.0 600610.0 8.2 9.0 5.836.612.2 # Contact Victaulic for details. # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. § Fitting flow data for 14-24”/350-600 mm size No. 10 and No. 11 Elbows is based on fittings for Style 07 and 77 couplings. For flow data on AGS fittings ( No. W10 and No. W11 Elbows), refer to submittal 20.05. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s”. S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_3 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Elbows NO. 10 90º Elbow NO. 11 45º Elbow NO. 12 22½º Elbow NO. 13 11¼º Elbow NO. 100 90º Long Radius NO. 110 45º Long Radius DIMENSIONS Cto E C to E NO. 10 C to E NO. 11 NO. 12 C to E NO. 13 C to E NO. 100 C to E NO. 110 Size No. 10 90º Elbow No. 11 45º Elbow No. 12 22½° Elbow No. 13 11¼° Elbow No. 100† 90° Long Radius Elbow (S) No. 110† 45° Long Radius Elbow (S) Nominal Size Inches mm Actual Outside Dia. Inches mm C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg ¾1.0502.250.51.500.51.63 sw —1.38sw —2.50 sw 64 0.4 0.2 1.81 sw 46 0.3 0.12026.9570.2380.241 35 1 1.3152.250.61.750.6 3.25 0.61.38sw0.3 2.88 sw 73 0.6 0.3 2.25 sw 57 0.5 0.22533.7570.3440.3830.3350.1 1 ¼1.6602.751.01.750.91.750.81.38sw0.5 3.25 sw 83 1.1 0.5 2.38 sw 60 0.7 0.33242.4700.5440.4440.4350.2 1 ½1.9002.751.21.750.91.750.81.38sw0.5 3.63 sw 92 2.2 1.0 2.50 sw 64 1.3 0.64048.3700.5440.4440.4350.2 2 2.3753.251.82.001.33.75 @1.41.381.04.382.52.75 1.8 5060.3830.8510.6950.6350.51111.1700.8 2 ½2.8753.753.22.252.24.00 @2.31.501.15.133.43.002.8 6573.0951.5571.01021.0380.51301.5761.3 76.1 mm 3.0003.753.72.253.42.24 —1.50 —————76.1951.7571.557 38 33.5004.254.52.503.14.50 @3.11.502.15.886.03.384.9 8088.91082.0641.41141.4381.01492.7862.2 3 ½4.0004.505.62.754.32.50 sw4.01.75sw2.7 ————90101.61142.5702.0641.8441.2 44.5005.007.13.005.62.885.61.753.67.5012.34.007.3 100114.31273.2762.5732.5441.61915.61023.3 108.0 mm 4.2505.0011.03.005.6 ————————108.01275.0762.5 4 ½5.0005.25 sw10.03.13 sw6.03.50 sw 6.61.88sw4.2 ————120127.01334.5792.7893.0481.9 55.5635.5011.73.258.32.88sw7.82.00sw5.0 9.25 sw 18.2 4.88 sw 14.8 125141.31405.3833.8733.5512.2 235 8.3 124 6.7 133.0 mm 5.2505.5011.73.258.3 ————————133.01405.3833.8 139.7 mm 5.5005.5011.73.258.32.87 —2.00 —————139.71405.3833.873 51 66.6256.5017.23.5010.86.25 @12.22.007.010.7530.45.5017.4 150168.31657.8894.91595.5513.227313.81407.9 159.0 mm 6.2506.5018.63.5010.8 ————————159.01658.4894.9 165.1 mm 6.5006.5015.53.509.83.1311.42.007.410.75sw 29.05.50sw 19.0 165.11657.0894.4795.2513.427313.21408.6 @ Gooseneck design endtoend dimension fittings in this size contact your nearest Victaulic sales office † Chinese standard sizes Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded C to E NO.12 GSNK E to E 07.01_4 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q C to E C to E NO. 10 C to E NO. 11 NO. 12 C to E NO. 13 C to E NO. 100 C to E NO. 110 Size No. 10 90º Elbow No. 11 45º Elbow No. 12 22½° Elbow No. 13 11¼° Elbow No. 100† 90° Long Radius Elbow (S) No. 110† 45° Long Radius Elbow (S) Nominal Size Inches mm Actual Outside Dia. Inches mm C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg C to E Inches mm Approx. Wgt. Each Lbs. kg 88.6257.7529.94.2520.47.75 @20.02.0010.114.2566.07.2536.0 200219.119713.61089.31979.1514.636230.018416.3 1010.7509.0063.34.7537.54.38sw 30.02.1311.815.00107.06.2557.0 250273.022928.712117.011113.6545.338148.515925.9 1212.75010.0074.05.2566.74.88sw 40.02.2529.318.00156.07.5090.0 300323.925433.613330.312418.15713.345770.819140.8 14 #14.00014.00136.05.7565.05.00sw46.03.50sw32.021.00 s164.08.75 s82.0 350355.6355.661.714629.512720.98914.553374.422237.2 377.0 mm †14.84314.84149.36.1582.0 ————————377.0376.967.7156.237.2 16 #16.00016.00171.06.6388.05.00sw58.04.00sw42.024.00 s210.010.00 s100.0 400406.4406.477.616839.912726.310219.161095.325445.4 426.0 mm †16.77216.77198.66.95101.3 ————————426.0426.090.1176.545.9 18 #18.00018.00228.07.46108.05.50sw65.04.50sw53.227.00 s273.011.25 s135.0 450457.0457.2103.418950.014029.511424.1686123.828661.2 480.0 mm †18.89818.90291.07.83141.7 ————————480.0480.0132.0198.864.3 20 #20.00020.00298.08.28138.06.00sw78.65.00sw65.030.00 s343.012.50 s174.0 500508.0508.0135.221062.615236.012729.5762155.631878.9 530.0 mm †20.86620.87355.08.64179.0 ————————530.0530.0161.0219.481.2 24 #24.00024.00438.09.94221.07.00sw140.06.00sw60.036.00 s516.015.00 s251.0 600610.0609.6198.7252100.217863.515227.2914234.1381113.9 630.0 mm †24.80324.80545.010.27255.2 ————————630.0630.0247.2261.0115.7 14 – 24 350 – 600 TM For AGS fitting information, see publication 20.05 @ Gooseneck design (GSNK), end-to-end dimension fittings in this size, contact your nearest Victaulic sales office. # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. † Chinese standard sizes Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded C to E NO.12 GSNK E to E 07.01_5 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Reducing Base Support Elbow NO. R-10G Grv. × Grv. NO. R-10F Grv. × Flange C to E H B Dia. NO. R-10G C to E H B Dia. NO. R-10F Size No. R-10 Reducing Base Support Elbow Approx. Weight Each Nominal Size Inches mm C to E Inches mm H Inches mm B Diameter Inches mm Grv. × Grv. Lbs. kg Grv. × Flange Lbs. kg 6 × 4 9.00 1.25 1.50 19.0 33.0 150100 229 32 38 8.6 15.0 5 9.00 1.50 1.50 23.0 38.0 125 229 38 38 10.4 17.2 8 × 6 10.50 2.13 1.50 33.0 52.0 200150 267 54 38 15.0 23.6 10 × 8 12.00 2.40 1.50 61.0 88.0 250200 305 61 38 27.7 39.9 Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_6 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Adapter Elbow NO. 18 90º Adapter Elbow NO. 19 45º Adapter Elbow C to TE C toGE NO. 18 C toGE C to TE NO. 19 Size No. 18 90° Adapter Elbow @ No. 19 45° Adapter Elbow @ Nominal Size Inches mm Actual Outside Diameter Inches mm C to GE Inches mm C to TE Inches mm Approx. Weight Each Lbs. kg C to GE Inches mm C to TE Inches mm Approx. Weight Each Lbs. kg ¾1.050 2.25 2.25 0.5 1.50 1.50 0.5 20 26.9 57 57 0.2 38 38 0.2 1 1.315 2.25 2.25 0.5 ———25 33.7 57 57 0.2 1 ¼1.660 2.75 2.75 0.9 ———32 42.4 70 70 0.4 1 ½1.900 2.75 2.75 1.1 1.75 1.75 0.9 40 48.3 70 70 0.5 44 44 0.4 2 2.375 3.25 4.25 2.5 ———50 60.3 83 108 1.1 2 ½2.875 3.75 3.75 3.0 2.25 2.25 2.3 65 73.0 95 95 1.4 57 57 1.0 3 3.500 4.25 6.00 5.8 2.50 4.25 5.0 80 88.9 108 152 2.6 64 108 2.3 3 ½4.000 4.50 6.25 8.0 5.25 5.25 8.8 90 101.6 114 159 3.6 133 133 4.0 6 6.625 6.50 6.50 17.6 3.50 3.50 12.7 150 168.3 165 165 8.0 89 89 5.8 @ Available with British Standard Pipe Threads specify “BSP” clearly on order Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_7 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q C to E C toE NO. 20 C to E NO 35 C to LE C to SE NO. 33 C to GE C to TE NO. 29M Size No. 20 Tee No. 35 Cross (sw) No. 33 True Wye (sw) No. 29M Tee with Threaded Branch Nominal Size Inches mm Actual Outside Dia. Inches mm C to E Inches mm Approx. Weight Each Lbs. kg C to E Inches mm Approx. Weight Each Lbs. kg C to LE Inches mm C to SE Inches mm Approx. Weight Each Lbs. kg C to GE Inches mm C to TE Inches mm Approx. Weight Each Lbs. kg ¾1.0502.250.62.250.9 2.25 57 2.00 51 0.7 0.3 2.252.25 sw 0.6 2026.957 0.3 57 0.4 57 57 0.3 11.3152.251.02.251.32.252.251.12.252.251.0 2533.757 0.5 57 0.6 57 57 0.5 57 57 0.5 1 ¼1.6602.751.52.752.12.752.501.52.752.751.5 3242.470 0.7 70 1.0 70 64 0.7 70 70 0.7 1 ½1.9002.752.02.752.52.752.751.82.752.752.0 4048.370 0.9 70 1.1 70 70 0.8 70 70 0.9 22.3753.253.03.253.83.252.752.53.254.253.00 5060.383 1.4 83 1.7 83 70 1.1 831081.4 2 ½2.8753.754.33.756.13.753.004.33.753.754.3 6573.095 2.0 95 2.8 95 76 2.0 95 95 2.0 76.1 mm 3.0003.755.2 —————3.753.75 sw5.2 76.195 2.4 95 95 2.4 33.5004.256.84.2510.54.253.256.14.256.006.8 8088.91083.01084.810883 2.81081523.1 3 ½4.0004.50 sw 7.94.5011.54.503.509.64.504.50 sw7.9 90101.61143.61145.211489 4.411411473.6 108.0 mm 4.2505.0015.5 —————5.005.00 sw 15.5 108.01277.0 1271277.0 44.5005.0011.95.0015.85.003.7510.05.007.2511.9 100114.31275.41277.212795 4.51271845.4 4 ½5.0005.25 sw 15.05.2518.5 ———5.255.25 sw15.0 120127.01336.81338.4 1331336.8 133.0 mm 5.2505.5017.8 —————5.505.50 sw 17.8 133.01408.1 1401408.1 139.7 mm 5.5005.5017.8 —————5.505.50 sw 17.8 139.7140 8.1 1401408.1 55.5635.5017.85.5020.05.504.0015.05.505.50 sw17.8 125141.31408.11409.11401026.81401408.1 159.0 mm 6.2506.5027.1 —————6.506.50 sw 27.1 159.016512.3 16516512.3 165.1 mm 6.5006.5022.06.5028.0 ———6.506.50 sw 22.0 165.116510.016512.7 16516510.0 66.6256.5025.76.5028.06.504.5022.36.506.50 sw25.7 150168.316511.716512.716511410.116516511.7 8 8.6257.7547.67.7548.07.756.0036.07.757.75 sw47.6 200219.119721.619721.819715216.319719721.6 1010.7509.0099.09.00121.59.006.5069.99.009.00 sw 73.0 250273.022944.922955.122915531.722922933.1 1212.75010.00133.010.00110.010.007.0080.010.0010.00 sw 99.0 300323.925460.325449.925417836.325425444.9 Tees, Crosses and True Wyes NO. 20 Tee NO. 35 Cross NO. 33 True Wye NO. 29M Tee with Threaded Branch Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_8 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q C to E C toE NO. 20 C to E NO 35 C to LE C to SE NO. 33 C to GE C to TE NO. 29M Size No. 20 Tee No. 35 Cross (sw) No. 33 True Wye (sw) No. 29M Tee with Threaded Branch Nominal Size Inches mm Actual Outside Dia. Inches mm C to E Inches mm Approx. Weight Each Lbs. kg C to E Inches mm Approx. Weight Each Lbs. kg C to LE Inches mm C to SE Inches mm Approx. Weight Each Lbs. kg C to GE Inches mm C to TE Inches mm Approx. Weight Each Lbs. kg 14 #14.00011.00 sw 145.011.00198.011.007.50134.2 11.00 sw 279 11.00 279 145.0 65.8350355.627965.827989.827919160.8 377.0 mm 14.000 11.50 145.0 ————————355.6 292 65.8 16 #16.00012.00 sw 186.012.00250.012.008.00167.0 12.00 sw 305 12.00 305 186.0 84.4400406.430584.4305113.430520375.7 426.0 mm †16.000 13.00 186.0 ————————406.4 300 84.4 18 #18.000 15.50 sw260.0 15.50350.015.508.50234.0 15.50 sw 394 15.50 394 117.9450457.0 394117.9 394158.8394216106.1 480.0 mm†18.000 14.57 256.0 ————————457.0 370 116.1 20 #20.000 17.25 sw336.0 17.25452.017.259.00281.0 17.25 sw 438 17.25 438 336.0 152.4500508.0 438152.4 438205.0438229127.5 530.0 mm †20.000 15.39 sw 339.0 ————————508.0 391 153.8 24 #24.000 20.00 sw592.0 20.00795.020.0010.00523.0 20.00 sw 508 20.00 508 592.0 268.5600610.0 508268.5 508360.6508254237.2 630.0 mm †24.000 17.37 sw 473.0 ————————610.0 441 214.5 14 – 24 350 – 600 TM For AGS fitting information, see publication 20.05 # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. † Chinese standard sizes Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded Tees, Crosses and True Wyes NO. 20 Tee NO. 35 Cross NO. 33 True Wye NO. 29M Tee with Threaded Branch (sw) 07.01_9 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q NO. 25 NO. 29 Size No. 25 Std. No. 29T w/ Thd. Branch Approx. Weight Each Nominal Size Inches mm C to E Inches mm C to E Inches mm Lbs. kg 1 × 1 × ¾2.25 sw 57 2.24 sw 57 1.0 25 20 0.5 1 ¼× 1 ¼× 1 2.75 sw 70 2.75 sw 70 1.3 323225 0.6 1 ½× 1 ½× ¾2.75 sw 70 2.75 sw 70 1.5 404020 0.7 1 2.75 sw 70 2.75 sw 70 1.5 25 0.7 1 ¼2.75 sw 70 2.75 sw 70 1.7 32 0.8 2 × 2 × ¾3.25 3.25 2.5 50502083 83 1.1 13.25 3.25 2.7 25 83 83 1.2 1 ¼3.25 sw 83 3.25 sw 83 1.8 32 0.8 1 ½3.25 3.25 sw 3.0 4083 83 1.4 2 ½× 2 ½× ¾3.75 sw 95 3.75 sw 95 3.9 656520 1.8 13.75 3.75 sw 3.8 2595 95 1.7 1 ¼3.75 sw 95 3.75 sw 95 4.2 32 1.7 1 ½3.75 3.75 3.9 4095 95 1.8 23.75 3.75 sw 4.5 5095 95 2.0 3 × 3 × ¾4.25 sw 108 4.25 sw 108 5.7 808020 2.6 14.25 4.25 6.1 25108 108 2.8 1 ¼4.25 sw 108 4.25 sw 108 8.0 32 3.6 1 ½4.25 4.25 sw 6.5 40108 108 2.9 24.25 4.25 sw 6.2 50108 108 2.8 2 ½4.25 4.25 sw 6.4 65108 108 2.9 4 × 4 × ¾5.00 sw 127 5.00 sw 127 8.0 10010020 3.6 15.00 5.00 7.8 25127 127 3.5 Size No. 25 Std. No. 29T w/ Thd. Branch Approx. Weight Each Nominal Size Inches mm C to E Inches mm C to E Inches mm Lbs. kg 4 × 4 × 1 ¼5.00 sw 127 5.00 sw 127 9.6 10010032 4.4 1 ½5.00 5.00 10.2 40127 127 4.6 25.00 5.00 11.2 50127 127 5.1 2 ½5.00 5.00 11.4 65127 127 5.2 35.00 5.00 11.6 80127 127 5.3 5 × 5 × 1 5.50 sw 140 5.50 sw 140 14.0 12512525 6.4 1 ½5.50 sw 140 5.50 sw 140 14.3 40 6.5 25.50 sw 5.50 sw 14.5 50140 140 6.6 2 ½5.50 5.50 sw 15.2 65140 140 6.9 35.50 5.50 sw 16.6 80140 140 7.5 4 5.50 5.50 sw 16.7 100140 140 7.6 6 × 6 × 1 6.50 sw 165 6.50 sw 165 23.0 15015025 10.4 1 ½6.50 sw 165 6.50 sw 165 24.0 40 10.9 26.50 6.50 21.6 50165 165 9.8 2 ½6.50 6.50 21.4 65165 165 11.7 14 – 24 350 – 600 TMFor AGS fitting information, see publication 20.05 + Contact Victaulic for details. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded IMPORTANT NOTE: No. 29T Threaded Outlet Reducing Tees are supplied NPT and are available with British Standard threads. For British Standard specify "BSP" clearly on order. Reducing Tee NO. 25 Grooved Branch NO. 29T Threaded Branch C to E C to E C to E C toE NO. 25 NO. 29T C to E CtoE NO. 25-SW NO. 29T-SW C to E Cto E 07.01_10 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Size No. 25 Std. No. 29T w/ Thd. Branch Approx. Weight Each Nominal Size Inches mm C to E Inches mm C to E Inches mm Lbs. kg 6 × 6 × 3 6.50 6.50 26.5 15015080165 165 12.0 46.50 6.50 25.0 100165 165 11.3 56.50 6.50 23.2 125165 165 10.5 6 ½× 6 ½× 36.50 6.50 sw 24.0 165.1165.180165 165 10.9 46.50 6.50 sw 25.0 100165 165 11.3 8 × 8 × 1 ½7.75 sw 197 7.75 sw 197 33.0 20020040 15.0 27.75 sw 7.75 sw 33.5 50197 197 15.2 2 ½7.75 sw 197 7.75 sw 197 39.0 65 17.7 37.75 sw 7.75 sw 33.6 80197 197 15.2 47.75 7.75 41.8 100197 197 19.0 57.75 sw 7.75 sw 34.0 125197 197 15.4 67.75 7.75 42.3 150197 197 19.2 165.1 7.75 sw 7.75 sw 48.0 197 197 21.8 10 × 10 × 1 ½9.00 229 9.00 229 62.0 25025040 28.1 29.00 sw 9.00 sw 62.0 50229 229 28.1 2 ½9.00 sw 229 9.00 sw 229 62.4 65 28.3 3 9.00 sw 229 9.00 sw 229 60.0 80 27.2 49.00 sw 9.00 sw 61.0 100229 229 27.7 59.00 sw 9.00 sw 52.0 125229 229 23.6 69.00 sw 9.00 sw 59.0 150229 229 26.8 89.00 sw 9.00 sw 64.7 200229 229 29.3 Size No. 25 Std. No. 29T w/ Thd. Branch Approx. Weight Each Nominal Size Inches mm C to E Inches mm C to E Inches mm Lbs. kg 12 × 12 × 1 10.00 sw 254 10.00 sw 254 77.0 30030025 34.9 2 10.00 sw 254 10.00 sw 254 80.0 50 36.3 2 ½10.00 sw 254 10.00 sw 254 78.0 65 35.4 310.00 sw 10.00 sw 82.0 80254 254 37.2 410.00 sw 10.00 sw 80.0 100254 254 36.3 510.00 sw 10.00 sw 75.0 125254 254 34.0 610.00 sw 10.00 sw 75.0 150254 254 34.0 8 10.00 sw 10.00 sw 80.0 200254 254 36.3 1010.00 sw 10.00 sw 84.0 250254 254 38.1 # 14 × 14 × 4 11.00 sw 279 11.00 sw 279 102.0 350350100 46.3 6 11.00 sw 279 11.00 sw 279 108.2 150 49.1 811.00 11.00 112.0 200279 279 50.8 1011.00 11.00 120.0 300279 279 54.4 1211.00 11.00 129.1 300279 279 58.6 # 16 × 16 × 4 ++130.0 400400100 59.0 14 – 24 350 – 600 TMFor AGS fitting information, see publication 20.05 + Contact Victaulic for details. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded IMPORTANT NOTE: No. 29T Threaded Outlet Reducing Tees are supplied NPT and are available with British Standard threads. For British Standard specify "BSP" clearly on order. Reducing Tee NO. 25 Grooved Branch NO. 29T Threaded Branch # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. C to E C toE C to E Cto E NO. 25 NO. 29T C to E CtoE NO. 25-SW NO. 29T-SW C to E C toE 07.01_11 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Size No. 25 Std. No. 29T w/ Thd. Branch Approx. Weight Each Nominal Size Inches mm C to E Inches mm C to E Inches mm Lbs. kg # 16 × 16 × 6 12.00 sw 305 12.00 sw 305 133.5 400400150 60.6 812.00 12.00 145.0 200305 305 65.8 1012.00 12.00 149.5 250305 305 67.8 1212.00 12.00 154.0 300305 305 69.9 14 12.00 sw 305 —167.0 350 75.8 # 18 × 18 × 4 15.50 sw 394 15.50 sw 394 194.0 450450100 88.0 6 15.50 sw 394 15.50 sw 394 200.0 150 90.7 8 15.50 sw 394 15.50 sw 394 202.0 200 91.6 1015.50 15.50 212.0 250394 394 96.2 1215.50 15.50 222.6 300394 394 101.0 1415.50 —230.1 350394 104.4 1615.50 —247.6 400394 112.3 # 20 × 20 × 6 17.25 438 17.25 438 240.0 500500150 108.9 8 17.25 438 17.25 438 244.0 200 110.7 10 17.25 438 17.25 438 256.0 250 116.1 12 17.25 438 17.25 438 264.0 300 119.8 1417.25 —275.0 350438 124.7 Size No. 25 Std. No. 29T w/ Thd. Branch Approx. Weight Each Nominal Size Inches mm C to E Inches mm C to E Inches mm Lbs. kg # 20 × 201617.25 —288.6 500500400438 130.9 1817.25 —297.0 450438 134.7 # 24 × 24 × 820.00 20.00 340.0 600600200508 508 154.2 1020.00 20.00 343.9 250508 508 156.0 1220.00 20.00 352.8 300508 508 160.0 14 §20.00 —360.0 350508 163.3 1620.00 —378.0 400508 171.5 18 §20.00 —380.0 450508 172.4 2020.00 —373.0 500508 169.2 14 – 24 350 – 600 TMFor AGS fitting information, see publication 20.05 + Contact Victaulic for details. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded IMPORTANT NOTE: No. 29T Threaded Outlet Reducing Tees are supplied NPT and are available with British Standard threads. For British Standard specify "BSP" clearly on order. § Cast fitting available. Contact Victaulic for details. Reducing Tee NO. 25 Grooved Branch NO. 29T Threaded Branch # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. NO. 25 NO. 29T C to E C toE C to E C toE 07.01_12 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Bullhead Tee NO. 21 C to EOB C to EOR NO. 21 Size No. 21 Bullhead Tee Nominal Size Inches mm C to EOR Inches mm C to EOB Inches mm Approx. Weight Each Lbs. kg 5 × 5 × 8 7.75 5.50 28.7 125125200197 140 13.0 6 × 6 × 87.75 6.50 37.5 150150200197 165 17.0 Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded Bull Plug NO. 61 E to E NO. 61 Size No. 61 Bull Plug (S) Nominal Size Inches mm Actual Outside Diameter Inches mm E to E Inches mm Approx. Weight Each Lbs. kg 2 2.375 4.00 2.5 50 60.3 102 1.1 2 ½2.875 5.00 3.0 65 73.0 127 1.4 3 3.500 6.00 4.5 80 88.9 152 2.0 4 4.500 7.00 7.5 100 114.3 178 3.4 5 5.563 8.00 12.0 125 141.3 203 5.4 6 6.625 10.00 17.0 150 168.3 254 7.7 IMPORTANT NOTES: Steel dish caps available through 24"/600 mm, contact Victaulic. No. 61 Bull Plugs should be used in vacuum service with Style 72 or 750 couplings Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_13 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q 45° Lateral NO. 30 NO. 30 Size No. 30 45º Lateral (SW) Nominal Size Inches mm Actual Outside Diameter Inches mm C to LE Inches mm C to SE Inches mm Approx. Weight Each Lbs. kg ¾1.050 4.50 2.00 1.0 20 26.9 114 51 0.5 1 1.315 5.00 2.25 1.7 25 33.7 127 57 0.8 1 ¼1.660 5.75 2.502.5 (d) 32 42.4 146 64 1.1 1 ½1.900 6.25 2.75 3.5 40 48.3 159 70 1.6 2 2.375 7.00 2.754.6 (d) 50 60.3 178 70 2.1 2 ½2.875 7.75 3.00 9.0 65 73.0 197 76 94.1 76.1 mm 3.000 8.50 3.25 11.0 76.1 216 83 5.0 3 3.500 8.50 3.2511.7 (d) 80 88.9 216 83 5.4 3 ½4.00010.00 3.50 17.8 90 101.6 254 89 8.1 4 4.50010.50 3.7522.2 (d) 100 114.3 267 95 10.1 5 5.56312.50 4.00 21.8 125 141.3 318 102 9.9 165.1 mm 6.50014.00 4.50 43.6 165.1 356 114 19.8 45° Lateral NO. 30 NO. 30 Size No. 30 45º Lateral (SW) Nominal Size Inches mm Actual Outside Diameter Inches mm C to LE Inches mm C to SE Inches mm Approx. Weight Each Lbs. kg 6 6.62514.00 4.50 43.6 150 168.3 356 114 19.8 8 8.62518.00 6.00 72.0 200 219.1 457 152 32.7 10 10.75020.50 6.50 105.0 250 273.0 521 165 47.6 12 12.75023.00 7.00 165.0 300 323.9 584 178 74.8 14 #14.00026.50 7.50 276.0 350 355.6 673 191 125.2 16 #16.00029.00 8.00 344.2 400 406.4 737 203 156.1 18 #18.00032.00 8.50 429.0 450 457.0 813 216 194.6 20 #20.00035.00 9.00 500.0 500 508.0 889 229 226.8 24 #24.00040.0010.00715.0 600 610.0 1016 254 324.3 14 – 24 350 – 600 TM For AGS fitting information, see publication 20.05 # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. Note: All fittings are segmentally welded steel unless otherwise noted with a (d) for ductile iron. C t o L E C toLE C to SE 07.01_14 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q 45º Reducing Lateral NO. 30-R C t o L E C to LE C toSE NO. 30-R Size No. 30-R 45º Reducing Lateral (SW) Nominal Size Inches mm C to LE Inches mm C to SE Inches mm Approx. Weight Each Lbs. kg 3 x 3 x 2 8.50 3.25 9.8 808050216 83 4.4 2 ½8.50 3.25 9.8 65216 83 4.4 4 x 4 x 210.50 3.75 10.0 10010050267 95 4.5 2 ½10.50 3.75 10.0 65267 95 4.5 310.50 3.75 18.3 80267 95 8.3 5 x 5 x 212.50 4.00 24.0 12512550318 102 10.9 312.50 4.00 27.0 80318 102 212.2 412.50 4.00 26.5 100318 102 12.0 6 x 6 x 314.00 4.50 37.0 15015080356 114 16.8 414.00 4.50 36.0 100356 114 16.3 514.00 4.50 44.7 125356 114 20.3 8 x 8 x 418.00 6.00 62.0 200200100457 152 28.1 518.00 6.00 75.5 125457 152 34.2 618.00 6.00 82.0 150457 152 37.2 10 x 10 x 420.50 6.50 104.8 250250100521 165 147.5 520.50 6.50 99.0 125521 165 44.9 620.50 6.50 105.8 150521 165 48.0 820.50 6.50 118.0 200521 165 53.5 12 x 12 x 523.00 7.00 122.0 300300125584 178 55.3 623.00 7.00 137.0 150584 178 62.1 823.00 7.00 147.0 200584 178 66.7 1023.00 7.00 167.0 250584 178 75.8 45º Reducing Lateral NO. 30-R C t o L E C to LE C toSE NO. 30-R Size No. 30-R 45º Reducing Lateral (SW) Nominal Size Inches mm C to LE Inches mm C to SE Inches mm Approx. Weight Each Lbs. kg # 14 x 14 x 426.50 7.50 172.0 350350100673 191 78.0 626.50 7.50 187.0 150673 191 84.8 826.50 7.50 205.8 200673 191 93.4 1026.50 7.50 235.0 250673 191 106.6 1226.50 7.50 250.0 300673 191 113.4 # 16 x 16 x 629.00 8.00 215.0 400400150737 203 97.5 829.00 8.00 252.5 200737 203 114.5 1029.00 8.00 265.0 250737 203 120.2 1229.00 8.00 295.0 300737 203 133.8 1429.00 8.00 305.0 350737 203 138.3 # 18 x 18 x 632.00 8.50 274.0 450450150813 216 124.3 832.00 8.50 275.0 200813 216 124.7 1232.00 8.50 347.0 300813 216 157.4 1432.00 8.50 350.0 350813 216 158.8 1632.00 8.50 362.0 400813 216 164.2 # 20 x 20 x 1235.00 9.00 415.0 500500300889 229 188.2 1435.00 9.00 420.0 350889 229 190.5 1635.00 9.00 425.0 400889 229 192.8 # 24 x 24 x 1640.00 10.00 425.0 6006004001016 254 192.8 2040.00 10.00 570.0 6001016 254 258.6 14 – 24 350 – 600 TMFor AGS fitting information, see publication 20.05 # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. Note: All fittings are segmentally welded steel unless otherwise noted a (d) for ductile iron. 07.01_15 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Tee Wye NO. 32 NO. 32 Size No. 32 Tee Wye (SW) Nominal Size Inches mm G Inches mm H Inches mm E1 Inches mm E2 Inches mm Approx. Wgt. Each Lbs. kg 2 × 2 × 2 2.757.009.004.636.4 505050701782291182.9 2 ½× 2 ½× 2 ½3.007.7510.505.7511.5 656565761972671465.2 3 × 3 × 33.258.5011.506.5014.3 808080832162921656.5 3 ½× 3 ½× 3 ½3.2510.0013.007.7522.9 9090908925433019710.4 4 × 4 × 43.7510.5013.638.1326.0 1001001009526734620711.8 Tee Wye NO. 32 NO. 32 Size No. 32 Tee Wye (SW) Nominal Size Inches mm G Inches mm H Inches mm E1 Inches mm E2 Inches mm Approx. Wgt. Each Lbs. kg 5 × 5 × 5 4.0012.5016.1310.0048.0 12512512510231841025421.8 6 × 6 × 64.5014.0018.2511.5060.5 15015015011435646429227.4 8 × 8 × 86.0018.0023.2515.25127.1 20020020015245759138757.7 10 × 10 × 106.5020.5027.2518.00190.0 250250250165521692457186.2 12 × 12 × 127.0023.0031.0020.50240.0 300300300178584787521108.9 Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded H G E2 E1 07.01_16 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Adapter Nipple NO. 40 Grv. × Thd. NO. 42 Grv. × Bev. NO. 43 Grv. × Grv. E to E NO. 40 * E to E NO. 42 E to E NO. 43 Size No. 40, 42, 43 Adapter Nipple (s) Nominal Size Inches mm Actual Outside Diameter Inches mm E to E Inches mm Approx. Weight Each Lbs. kg ¾1.050 3.00 0.3 20 26.9 76 0.1 1 1.315 3.00 0.4 25 33.7 76 0.2 1¼1.660 4.00 0.8 32 42.4 102 0.4 1½1.900 4.00 0.9 40 48.3 102 0.4 2 2.375 4.00 1.2 50 60.3 102 0.5 2½2.875 4.00 1.9 65 73.0 102 0.9 3 3.500 4.00 2.5 80 88.9 102 1.1 3½4.000 4.00 2.1 90 101.6 102 0.9 4 4.500 6.00 5.5 100 114.3 152 2.5 5 5.563 6.00 7.4 125 141.3 152 3.4 Adapter Nipple NO. 40 Grv. × Thd. NO. 42 Grv. × Bev. NO. 43 Grv. × Grv. E to E NO. 40 * E to E NO. 42 E to E NO. 43 Size No. 40, 42, 43 Adapter Nipple (s) Nominal Size Inches mm Actual Outside Diameter Inches mm E to E Inches mm Approx. Weight Each Lbs. kg 6 6.625 6.00 9.5 150 168.3 152 4.3 8 8.625 6.00 14.2 200 219.1 152 6.4 10 10.750 8.00 27.0 250 273.0 203 12.2 12 12.750 8.00 33.0 300 323.9 203 15.0 * Available with British Standard Pipe Threads, specify “BSP” clearly on order. IMPORTANT NOTES: For pump package nipples with 1 ½”/40 mm hole cut to receive Style 923 Vic-Let or Style 924 Vic-O-Well request special No. 40, 42 or 43 nipples and specify No. 40-H, 42-H or 43-H on order. NOTE: 4 – 12”/100 – 300 mm diameter – 8”/200 mm minimum length required. # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_17 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Cap NO. 60 T NO. 60 Size No. 60 Cap Nominal Size Inches mm Actual Outside Diameter Inches mm T Thickness Inches mm Approx. Weight Each Lbs. kg ¾1.050 0.88 0.2 20 26.9 22 0.1 1 1.315 0.88 0.3 25 33.7 22 0.1 1 ¼1.660 0.88 0.3 32 42.4 22 0.1 1 ½1.900 0.88 0.5 40 48.3 22 0.2 2 2.375 0.88 0.6 50 60.3 22 0.3 2 ½2.875 0.88 1.0 65 73.0 22 0.5 76.1 mm 3.000 0.88 1.2 76.1 22 0.5 3 3.500 0.88 1.2 80 88.9 22 0.5 3 ½4.000 0.88 2.5 90 101.6 22 1.1 108.0 mm 4.250 1.00 2.3 108.0 25 1.0 4 4.500 1.00 2.5 100 114.3 25 1.1 133.0 mm 5.250 1.00 4.5 133.0 25 2.0 139.7 mm 5.500 1.00 4.5 139.7 25 2.0 5 5.563 1.00 4.6 125 141.3 25 2.1 159.0 mm 6.250 1.00 6.8 159.0 25 3.1 165.1 mm 6.500 1.00 7.3 165.1 25 3.3 Cap NO. 60 T NO. 60 Size No. 60 Cap Nominal Size Inches mm Actual Outside Diameter Inches mm T Thickness Inches mm Approx. Weight Each Lbs. kg 6 6.625 1.00 6.1 150 168.3 25 2.8 8 8.625 1.19 13.1 200 219.1 30 5.9 10 10.750 1.25 21.0 250 273.0 32 9.5 12 12.750 1.25 35.6 300 323.9 32 16.2 14 # (s)14.000 9.50 *350 355.6 241 16 # (s)16.000 10.00 *400 406.4 254 18 # (s)18.000 11.00 *450 457.0 279 20 # (s)20.000 12.00 *500 508.0 305 24 # (s)24.000 13.50 *600 610.0 343 14 – 24 350 – 600 TM For AGS fitting information, see publication 20.05 IMPORTANT NOTES: * Steel dish caps available through 24"/600 mm, contact Victaulic. No. 60 cap is not suitable for use in vacuum service with Style 72 or 750 couplings. No. 61 bull plugs should be used, see pg. 35. # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_18 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Flanged Adapter Nipple NO. 41 ANSI Class 125 (Cast Iron) NO. 45F ANSI Class 150 Flat Face NO. 45R ANSI Class 150 Raised Face NO. 46F ANSI Class 300 Flat Face NO. 46R ANSI Class 300 Raised Face E to E NO. 41 E to E NO. 45F E to E NO. 45R E to E NO. 46F E to E NO. 46R Size No. 41 ANSI 125 Flange Adapter Nipple No. 45F and No. 45R ANSI 150 Flange Adapter Nipple (S) No. 46F and No. 46R ANSI 300 Flange Adapter Nipple (S) Nominal Size Inches mm Actual Outside Diameter Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg ¾1.050 3 —3 2.3 3 3.3 20 26.9 76 76 1.0 76 1.5 1 1.315 3 2.5 3 2.7 3 3.9 25 33.7 76 1.1 76 1.2 76 1.8 1¼1.660 4 3.0 4 3.3 4 4.8 32 42.4 102 1.4 102 1.5 102 2.2 1½1.900 4 3.5 4 3.9 4 6.9 40 48.3 102 1.6 102 1.8 102 3.1 2 2.375 4 5.5 4 6.2 4 8.2 50 60.3 102 2.5 102 2.8 102 3.7 2½2.875 4 8.0 4 9.9 4 11.9 65 73.0 102 3.6 102 4.5 102 5.4 3 3.500 4 9.5 4 11.4 4 16.5 80 88.9 102 4.3 102 5.2 102 7.5 3½4.00 4 12.0 4 15.1 4 20.1 90 101.6 102 5.4 102 6.8 102 9.1 4 4.500 6 16.7 6 18.4 6 27.4 100 114.3 152 7.6 152 8.3 152 12.4 5 5.563 6 21.5 6 21.3 6 35.3 125 141.3 152 9.8 152 9.7 152 16.0 6 6.625 6 26.5 6 27.5 6 47.5 150 168.3 152 12.0 152 12.5 152 21.5 8 8.625 6 39.0 6 41.3 6 70.3 200 219.1 152 17.7 152 18.8 152 31.9 10 10.750 8 57.0 8 59.8 8 100.8 250 273.0 203 25.9 203 27.1 203 45.7 12 12.750 8 41.0 8 88.2 8 146.2 300 323.9 203 18.6 203 40.0 203 66.3 14 #14.000 8 —8 +8 +350 355.6 203 203 203 16 #16.000 8 —8 +8 +400 406.4 203 203 203 18 #18.000 8 —8 +8 +450 457.0 203 203 203 20 #20.000 8 —8 +8 +500 508.0 203 203 203 24 #24.000 8 —8 +8 +600 610.0 203 203 203 14 – 24 350 – 600 TM For AGS fitting information, see publication 20.05 IMPORTANT NOTES: + Contact Victaulic for details. Flanged adapter nipples are supplied with standard rolled grooves. Standard cut grooves or machining for rubber lining are optionally available. Contact Victaulic for details. # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_19 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Swaged Nipple NO. 53 Grv. × Grv. NO. 54 Grv. × Thd. NO. 55 Thd. × Grv. E to E NO. 53 E to E NO. 54 E to E NO. 55 Size No. 53, 54 and 55 Swaged Nipples (S) Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg 2 × 1 6.50 2.0 5025 165 0.9 1 ¼6.50 2.0 32 165 0.9 1 ½ 6.50 2.0 40 165 0.9 2 ½ × 1 7.00 3.0 6525 178 1.4 1 ¼7.00 3.0 32 178 1.4 1 ½7.00 3.0 40 178 1.4 2 7.00 3.0 50 178 1.4 3 ×1 8.00 4.5 8025 203 2.0 1 ¼8.00 4.5 32 203 2.0 1 ½8.00 4.4 40 203 2.0 2 8.00 4.5 50 203 2.0 2 ½ 8.00 4.5 65 203 2.0 3 ½ × 3 8.00 6.8 9080 203 3.1 4 × 1 9.00 7.5 10025 229 3.4 1 ¼9.00 7.5 32 229 3.4 1 ½9.00 7.5 40 229 3.4 2 9.00 7.5 50 229 3.4 4 × 2 ½9.00 7.5 10065 229 3.4 Swaged Nipple NO. 53 Grv. × Grv. NO. 54 Grv. × Thd. NO. 55 Thd. × Grv. E to E NO. 53 E to E NO. 54 E to E NO. 55 Size No. 53, 54 and 55 Swaged Nipples (S) Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg 4 × 3 9.00 7.5 10080 229 3.4 3 ½9.00 7.5 90 229 3.4 5 × 2 11.00 11.5 12550 279 5.2 3 11.00 11.3 80 279 5.1 4 11.00 11.5 100 279 5.2 6 × 1 12.00 17.0 15025 305 7.7 1 ¼ 12.00 17.0 32 305 7.7 1 ½ 12.00 17.2 40 305 7.8 2 12.00 17.4 50 305 7.9 2 ½12.00 17.4 65 305 7.9 3 12.00 17.4 80 305 7.9 3 ½12.00 17.4 90 305 7.9 4 12.00 17.5 100 305 7.9 4 ½ 12.00 17.5 120 305 7.9 5 12.00 17.5 125 305 7.9 8 × 6 +20.0 200150 9.1 + Contact Victaulic for details. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded 07.01_20 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Female Threaded Adapter NO. 80 E to E NO. 80 Size No. 80 Female Threaded Adapter Nominal Size Inches mm Actual Outside Diameter Inches mm E to E Inches mm Approx. Weight Each Lbs. kg ¾1.050 2.00 1.0 20 26.9 51 0.5 1 1.315 2.06 1.0 25 33.7 52 0.5 1 ¼1.660 2.31 (sw)1.5 32 42.4 59 0.7 1 ½1.900 2.31 (sw)1.5 40 48.3 59 0.7 2 2.375 2.50 1.4 50 60.3 64 0.6 2 ½2.875 2.75 1.5 65 73.0 70 0.7 3 3.500 2.75 2.9 80 88.9 70 1.3 4 4.500 3.25 4.5 100 114.3 83 2.0 Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded IMPORTANT NOTE: Available with British Standard Pipe threads, specify “BSP” clearly on order. Hose Nipple NO. 48 Size No. 48 Hose Nipple (s) Nominal Size Inches mm Actual Outside Diameter Inches mm E to E Inches mm Approx. Weight Each Lbs. kg ¾1.050 3.12 0.3 20 26.9 79 0.1 1 1.315 3.38 0.4 25 33.7 86 0.2 1 ¼1.660 3.88 0.6 32 42.4 98 0.3 1 ½1.900 3.88 0.8 40 48.3 98 0.4 2 2.375 4.50 1.1 50 60.3 114 0.5 2 ½2.875 5.38 2.0 65 73.0 137 0.9 3 3.500 5.75 3.2 80 88.9 146 1.5 4 4.500 7.00 4.9 100 114.3 178 2.2 5 5.563 8.75 8.0 125 141.3 222 3.6 6 6.625 10.12 14.3 150 168.3 257 6.5 8 8.625 11.88 24.7 200 219.1 302 11.2 10 10.750 12.50 40.1 250 273.0 318 18.2 12 12.750 14.50 62.0 300 323.9 368 28.1 Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded E to E NO. 48 07.01_21 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Concentric/Eccentric Reducer NO. 50 Concentric NO. 51 Eccentric Size No. 50 Concentric Reducer No. 51 Eccentric Reducer Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg 1 ¼× ¾+1.9 ——3220 0.9 1 +1.9 ——25 0.9 1 ½ × ¾+1.4 — — 4020 0.6 12.50 0.88.50 sw 4.5 2564 0.4 216 2.0 1 ¼2.50 1.0 ——3264 0.5 2 × ¾2.50 0.99.00 sw 2.0 502064 0.3 229 0.9 12.50 0.79.00 sw 2.3 2564 0.3 229 1.0 1 ¼2.50 1.29.00 sw 4.6 3264 0.5 229 2.1 1 ½3.50 1.0 3.50 1.1 4089 0.5 89 0.5 2 ½ × ¾+1.3 +3.3 6520 0.6 1.5 12.50 1.1 9.50 3.5 2564 0.5 241 1.6 1 ¼3.50 3.3 3.50 1.4 3289 1.5 89 1 ½2.50 3.69.50 sw 3.7 4064 1.6 241 1.7 22.50 3.9 3.50 4.3 5064 1.8 89 2.0 3 × ¾+1.5 +4.5 8020 0.7 2.0 12.50 1.39.50 sw 4.8 25241 0.6 241 2.2 1 ¼2.50 1.4 +4.8 3264 0.6 2.2 1 ½2.50 5.19.50 sw 5.1 4064 2.3 241 2.3 2 2.50 1.6 3.50 6.0 5064 0.7 89 2.7 2 ½2.50 1.8 3.50 7.0 6564 0.8 89 3.2 76.1 2.50 2.1 ——64 1.0 Concentric/Eccentric Reducer NO. 50 Concentric NO. 51 Eccentric Size No. 50 Concentric Reducer No. 51 Eccentric Reducer Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg 3 ½× 3 2.50 2.09.50 sw 7.0 908064 0.9 241 3.2 4 × 13.00 3.013.00 sw 6.5 1002576 1.4 330 2.9 1 ¼+4.6 ——32 2.1 1 ½3.00 sw 2.610.00 sw 8.1 4076 1.2 254 3.7 23.00 2.4 4.00 3.3 5076 1.1 102 1.5 2 ½3.00 2.7 4.00 3.4 6576 1.2 102 1.5 33.00 3.2 4.00 3.5 8076 1.4 102 1.6 3 ½3.00 2.910.00 sw 8.0 9076 1.3 254 3.6 5 × 211.00 sw 9.011.00 sw 5.2 12550279 4.1 279 2.4 2 ½4.00 4.311.00 sw 10.8 65102 2.0 279 4.9 34.00 5511.00 sw 11.1 80102 2.5 279 5.0 43.50 4.3 5.00 12.0 10089 1.9 127 5.4 6 × 14.00 5.011.50 sw 14.5 15025102 2.3 292 6.6 1 ½+5.5 ++40 2.5 24.00 6.611.50 sw 14.5 50102 3.0 292 6.6 2 ½4.00 6.411.50 sw 14.2 65102 2.9 292 6.4 34.00 6.4 5.50 15.0 80102 2.9 140 6.8 44.00 6.5 5.50 17.0 100102 2.9 140 7.7 54.00 6.4 5.50 17.0 125102 2.9 140 7.7 8 × 2 ½16.00 7.9 12.00 sw 26.1 20065406 3.6 305 11.8 35.00 9.312.00 sw 22.0 80127 4.2 305 10.0 Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded NO. 50 Fabricated Steel No.50NO. 51 Fabricated Steel No.51 E to E E to EE to E E to E 07.01_22 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Concentric/Eccentric Reducer NO. 50 Concentric NO. 51 Eccentric Size No. 50 Concentric Reducer No. 51 Eccentric Reducer Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg 8 × 4 5.00 10.412.00 sw 23.0 200100127 4.8 305 10.4 55.00 11.612.00 sw 23.0 125127 5.2 305 10.4 65.00 11.9 6.00 24.0 150127 5.4 152 10.9 10 × 46.00 19.713.00 sw 32.0 250100152 8.9 330 14.5 5 +34.3 +34.6 125 15.6 15.7 66.00 20.013.00 sw 36.9 150152 9.1 330 16.7 8 6.00 22.0 7.00 21.6 200152 10.0 178 9.8 12 × 4 +44.014.00 sw 48.0 300100 20.0 356 21.8 67.00 24.614.00 sw 50.0 150178 11.2 356 22.7 87.00 52.014.00 sw 53.5 200178 23.6 356 24.3 10 7.00 39.014.00 sw 57.0 250178 17.7 356 25.9 # 14 × 613.00 65.0 13.0060.0 350150330 29.5 330 27.2 813.00 65.0 13.0060.0 200330 29.5 330 27.2 1013.00 66.0 13.0065.0 250330 29.9 330 29.5 1213.00 68.0 13.0066.0 300330 30.8 330 29.9 # 16 × 814.00 73.0 14.0073.0 400200356 33.1 355 33.1 10 §14.00 73.0 14.0073.0 250356 33.1 355 33.1 1214.00 73.0 14.0073.0 300356 33.1 355 33.1 1414.00 73.0 14.0073.0 350356 33.1 355 33.1 # 18 × 1015.00 91.0 15.00 91.0 450250381 41.3 381 41.3 Concentric/Eccentric Reducer NO. 50 Concentric NO. 51 Eccentric Size No. 50 Concentric Reducer No. 51 Eccentric Reducer Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg # 18x1215.00 91.0 15.00 91.0 450300381 41.3 381 41.3 1415.00 91.0 15.00 91.0 350381 41.3 381 41.3 1615.00 91.0 15.00 91.0 400381 41.3 381 41.3 # 20 × 1020.00110.020.00177.0 500250508 49.9 508 80.3 1220.00120.020.00120.0 300508 54.4 508 54.4 1420.00149.020.00149.0 350508 67.9 508 67.9 1620.00120.020.00120.0 400508 54.4 508 54.4 1820.00136.020.00136.0 450508 61.7 508 61.7 # 24 × 1020.00142.020.00142.0 600250508 64.4 508 64.4 1220.00150.020.00150.0 300508 68.0 508 68.0 1420.00162.020.00162.0 350508 73.5 508 73.5 1620.00162.020.00162.0 400508 73.5 508 73.5 1820.00162.020.00162.0 450508 73.5 508 73.5 2020.00151.020.00190.0 500508 68.5 508 86.2 14 – 24 350 – 600 TM For AGS fitting information, see publication 20.05 + Contact Victaulic for details. * Available with male threaded small end No. 52. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded IMPORTANT NOTE: Steel eccentric reducers available through 30"/750 mm, contact Victaulic for dimensions. # For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). For pricing and availability of cut groove fittings in this size, contact your nearest Victaulic sales office. § Cast fitting available for JIS size. Contact Victaulic for details. NO. 50 Fabricated Steel No.50NO. 51 Fabricated Steel No.51 E to E E to EE to E E to E 07.01_23 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q Small Threaded Reducer NO. 52 Eto E NO. 52 Eto E NO. 52F Size No. 52 Small Threaded Reducer No. 52F Concentric Reducer with BSPT Female Threaded End Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg 1 ½× 1 2.50 0.8 ——402564 0.4 1 ¼2.50 0.9 ——3264 0.4 2 × ¾2.50 0.9 ——502064 0.4 12.50 0.7 ——2564 0.3 1 ¼2.50 1.2 ——3264 0.5 1 ½ 2.50 1.0 ——4064 0.5 2 ½ × 12.50 1.1 ——652564 0.5 1 ¼ 2.50 (sw)1.2 ——3264 0.5 1 ½2.50 (sw)1.3 ——4064 0.6 2 3.00 1.4 ——5076 0.6 76.1× 48.363.5 0.8 63.50.77 60——63.50.85 3 × ¾+ (sw)1.5 ——8020 0.7 12.50 1.3 ——2564 0.6 1 ¼2.50 1.5 ——3264 0.7 1 ½2.50 (sw)1.5 ——4064 0.7 22.50 1.5 ——5064 0.7 2 ½2.50 2.4 ——6564 1.1 88.9× 42.463.5 0.9 63.50.82 48.363.5 0.9 63.50.85 60——63.50.89 4 × 13.00 2.3 ——1002576 1.0 1 ½3.00 2.7 ——4076 1.2 23.00 2.6 ——5076 1.2 Small Threaded Reducer NO. 52 Eto E NO. 52 Eto E NO. 52F Size No. 52 Small Threaded Reducer No. 52F Concentric Reducer with BSPT Female Threaded End Nominal Size Inches mm E to E Inches mm Approx. Weight Each Lbs. kg E to E Inches mm Approx. Weight Each Lbs. kg 4 × 2 ½3.00 2.6 ——1006576 1.2 3 3.00 2.5 ——8076 1.1 108× 42.476.2 1.3 76.21.32 48.376.2 1.3 76.21.35 60——76.21.39 114.3× 42.476.2 1.3 76.21.30 48.376.2 1.3 76.21.34 60——76.21.40 5 × 4 +4.5 ——125100 2.0 133×60——114.32.17 139×60——114.32.26 6 × 14.00 5.5 ——15025102 2.5 2 4.00 5.7 ——50102 2.6 2 ½4.00 5.8 ——65102 2.6 3 4.00 5.8 ——80102 2.6 4 + (sw)6.5 ——100 2.9 5 + (sw)2.0 ——125 0.9 159x 42.4114.3 2.2114.32.45 48.3114.3 2.2114.32.51 60——114.32.60 165.1x 42.4101.6 2.4101.62.90 48.3101.6 2.6101.62.95 60——101.63.00 8 × 216.00 1.5 ——20050406 0.7 2 ½16.00 1.7 ——65406 0.8 + Contact Victaulic for details. Note: All fittings are ductile iron unless otherwise noted with an “sw” or “s” S= Carbon Steel Direct Roll Groove (OGS) SW= Carbon Steel Segmentally Welded IMPORTANT NOTE: Available with British Standard Pipe Threads, specify "BSP" clearly on order 07.01_24 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_Q WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. INSTALLATION 07.01 Grooved End Fittings 07.01CARBON STEEL PIPE - GROOVED FITTINGS UPDATED 12/2011 07.01 1449 REV Q VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. ® Specification: MIFABSeries MI-DE (specify size and connection type) galvanized steel dielectric nipples with plastic liner, designed and tested for use at temperatures up to +225 degrees F and for pressures up to 425 PSI. Function: Used to protect the plumbing system through the steel to plastic design that provided a dielectric waterway in all potable water and appropriate HVAC applications. Dissimilar metals are separated in the waterway eliminating the local galvanic cell. The metal to metal connection design maintains external electrical continuity to prevent stray current corrosion. USA: 1-800-465-2736 www.mifab.com CAN: 1-800-387-3880 ® Job Name Section No: Schedule No: Page No: Contractor Purchase Order No: MIFAB reserves the right to make changes in material and design without formal notice and obligation. DIELECTRIC NIPPLES Page Cl10 MI-DE GALVANIZED STEELNIPPLE PLASTIC LINER A MODEL NUMBER MI-DETT-75 MI-DETT-100MI-DETT-125MI-DETT-150MI-DETT-200 MI-DETT-50 MI-DETT-250 MI-DEGT-100 MI-DEGT-125MI-DEGT-150MI-DEGT-200MI-DEGT-250 MI-DEGG-200 NIPPLE LENGTH 3” (76)4” (102)4” (102)4” (102)4” (102) 3” (76) 6” (152) 4” (102) 4” (102)4” (102)4” (102)6” (152) 4” (102) 6” (152) NIPPLE DIAMETER 3/4” (19)1” (25)1 1/4” (32)1 1/2” (38)2” (52) 1/2” (13) 2 1/2” (65) 1” (25) 1 1/4” (32)1 1/2” (38)2” (52)2 1/2” (65) 2” (52)2 1/2” (65) CONNECTION TYPE THREADED X THREADEDTHREADED X THREADEDTHREADED X THREADEDTHREADED X THREADEDTHREADED X THREADED THREADED X THREADED THREADED X THREADED GROOVED X THREADED GROOVED X THREADEDGROOVED X THREADEDGROOVED X THREADEDGROOVED X THREADED GROOVED X GROOVEDGROOVED X GROOVEDMI-DEGG-250 514 OFFSET C.P.V.C.-STEEL-COPPER HANGER SIZE MATERIAL FINISH PATENTNo.6,648,278. FUNCTION INSTALLATION WOOD #905 STEEL FEATURES #905 ORDERING 906 -3/4"thru2"pipe. -CarbonSteel. -Mil.Galvanized.. - -UseonC.P.V.C.,CopperorSteelpipe. Hangerandrestrainerontop,bottomorsideposition. -PerN.F.P.A13,13Rand13Don top,bottomorsideofbeam.Spacebypipetype. Snapoverpipethensqueezestrapbackallowingpipetoslidefreely. in: CPVCpipe-screw-nopre-drill. Copperpipe- Steelpipe-1/4x11/2lagscrew-nopre-drill. in: *11/2Offset. *3/4and1”pipesizehavecommoncenter-line. *Legdesignproducessuperiorstrength. *Offsetedgeeliminatesabrasion. *Requiredscrewhas5/16"hexhead-included -Part#andpipesize. #soldseparately. AFCON AFCON LISTINGS- EX4231,EX2551 906 FASTENERS #905 On3/8"woodwebuse#backingnuts.-seedrawing. Oncopper-insulatepipe. -ULListedperNFPA13 screw-nopre-drill. "" CPVCpipe-1/4"or#14TekScrew. Copperpipe-1/4"or#14TekScrew. Steelpipe-1/4"or#14TekScrew. " " Hanger,Restrainer andSupport Stabilize-Only Hanger/Restrainer Stabilize-Only a company ® ® DOCUMENT #: REVISION: BF-975XL(LG) 1/11 SPECIFICATION SUBMITTAL SHEET Page 1 of 2 Model 975XL Reduced Pressure Principle Assembly WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 In Canada: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com FEATURES Sizes: 3/4" 1" 1 1/4" 1 1/2" 2" Maximum working water pressure 175 PSI Maximum working water temperature 180°F Hydrostatic test pressure 350 PSI End connections Threaded ANSI B1.20.1 OPTIONS (Suffixes can be combined) - with full port QT ball valves (standard) L - less ball valves U - with union ball valves MS - with integral relief valve monitor switch P - for reclaimed water systems S - with bronze "Y" type strainer BMS - with battery operated monitor switch FDC - with fire hydrant connection; 2" only TCU - with test cocks up V - with union swivel elbows (3/4" & 1") SE - with street elbows FT - with integral male 45 ° flare SAE test fitting ACCESSORIES Air gap (Model AG) Repair kit (rubber only) Thermal expansion tank (Model XT) Soft seated check valve (Model 40XL) Shock arrester (Model 1250) QT-SET Quick Test Fitting Set Ball valve handle locks Test Cock Lock (Model TCL24) DIMENSIONS & WEIGHTS (do not include pkg.) APPLICATION Designed for installation on potable water lines to protect against both backsiphonage and backpressure of contami- nated water into the potable water supply. Assembly shall provide protection where a potential health hazard exists. STANDARDS COMPLIANCE ASSE® Listed 1013 IAPMO® Listed UL® Classified (less shut-off valves or with OS&Y v alves) C-UL® Classified CSA® Certified AWWA Compliant C511 Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California NYC MEA 425-89-M VOL 3 MATERIALS Main valve body Cast Bronze ASTM B 584 Access covers Cast Bronze ASTM B 584 Fasteners Stainless Steel, 300 Series Elastomers Silicone (FDA Approved) Buna Nitrile (FDA Approved) Polymers Noryl™, NSF Listed Springs Stainless steel, 300 series Relief Valve discharge port: 3/4” - 1” - 0.63 sq. in. 1 1/4” - 2” - 1.19 sq. in. MODEL SIZE DIMENSIONS (approximate)WEIGHT A A UNION BALL VALVES B LESS BALL VALVES CDEFG LESS BALL VALVES WITH BALL VALVES in.mmin.mmin.mmin.mmin.mmin.mmin.mmin.mmin.mmlbskglbs.kg 3/4201230513 3/43497 3/41972 1/8543763 1/289512716 1/8410104.5125.5 1251333014 1/23687 3/41972 1/8543763 1/289512717 3/8441104.5146.4 1 1/4321743218 13/1647810 15/162782 3/4703 1/28951276 3/417122 9/1657322102812.7 1 1/24017 3/844119 3/849210 15/162782 3/4703 1/28951276 3/417124 1/1661122102812.7 25018 1/247020 1/252110 15/162782 3/4703 1/28951276 3/417126 1/267322103415.4 A B G CD F E Page 2 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com 0 20 40 60 805 10 15 20 0 50 100 150 200 2505 10 15 20 Rated Flow (Established by approval agencies) FLOW RATES (GPM) PR E S S U R E L O S S ( P S I G ) 69 PR E S S U R E L O S S ( k p a ) FLOW RATES (l/s) MODEL 975XL 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC) 35 3/4" (20mm)1" (25mm)1 1/4" (32mm) 2" (50mm)103 15.812.69.56.33.25.03.82.521.26 1 1/2” (40mm) 137 TYPICAL INSTALLATION Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged. OUTDOOR INSTALLATIONINDOOR INSTALLATION (*Shown w/ optional BMS) SPECIFICATIONS The Reduced Pressure Principle Backflow Preventer shall be ASSE® Listed 1013, rated to 180°F and supplied with full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal polymers shall be NSF® Listed Noryl™ and the seat disc elastomers shall be silicone. The first and second checks shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed indoors, the installation shall be supplied with an air gap adapter and integral monitor switch. The Reduced Pressure Principle Backflow Preventer shall be a WILKINS Model 975XL. Capacity thru Schedule 40 Pipe Pipe size5 ft/sec7.5 ft/sec10 ft/sec15 ft/sec 1/8"1123 1/4"2235 3/8"3469 1/2"57914 3/4"8121725 1"13202740 1 1/4"23354770 1 1/2"32486395 2"5278105167 BATTERY MONITOR SWITCH* AIR GAP FITTING 12" MIN. 30" MAX. FLOOR DRAIN DIRECTION OF FLOW FLOOR CENTRAL STATION ALARM PANEL 12" MIN 30" MAX PROTECTIVE ENCLOSURE OPTIONAL WATER METER INLET SHUT-OFF AIR GAP DRAIN DIRECTION OF FLOW FLOW CHARACTERISTICS General Description TheTyco®2thru8inch(DN50thru DN200)ModelPRV-1PressureRe- ducingValvesarefactoryassembled andfullytrimmedvalvearrangements forpressurecontrol.Theyareusedon waterfilledpipewhereitisnecessary toreduceahigherinletpressureto alowerdeliverypressureunderstatic and/orresidualflowingconditions.The PRV-1isintendedtoautomatically maintaintheoutlet“setpressure” (staticandresidual)withinaclose range,regardlessoffluctuationsinthe higherpressureinletlineorvarying flowrates. ThePRV-1isprovidedwithafactory outlet“setpressure”of125psi(8,6 bar);howeveritmaybefieldsettoa nominaloutlet“setpressure”of80to 225psi(5,5to15,5bar)peritsFM Approvalor80to150psi(5,5to10,3 bar)peritsULListing. Typicalapplicationsareasfollows: •Withinthemainheader(Ref.Figure 1)supplyingwetpipe,drypipe,del- uge,orpreactionsystemrisers, and/orastandpipesystemsupply- inghoseconnections. •Aspartofasectionalfloorcontrol assembly(Ref.Figure2)supplying sprinklersystems,and/orhosesta- tions. Featuresareasfollows: •Canbeinstalledinanyorientation. •Eliminatesanyrequiredbleedingof trappedairfromthediaphragm chamberduringinstallation. •Globeoranglepattern. •Accuratepressurecontrol. •Standardnyloncoatedinternaland external. (continued) ModelPRV-1PressureReducingValve 2thru8Inch(DN50thruDN200),250psi(17,2bar) PilotOperated,GlobeandAngleBodyStyles TechnicalServices:Tel:(800)381-9312/Fax:(800)791-5500 Page1of16 TFP1580NOVEMBER,2007 EndConnection 2Inch (DN50) 3Inch (DN80) 4Inch (DN100) 6Inch (DN150) 8Inch (DN200) NominalValveSize ThreadxThread Groovex GrooveGlobe Flangex Flange AvailableBodyStyles,EndConnections&Sizes N/A N/AN/A N/A N/A N/A N/AN/AThreadxThread Groovex Groove Flangex Flange Angle Body Style =Available N/A N/A N/A=NotAvailable SOUTHAMERICA,CENTRALAMERICA &EASTERNHEMISPHERE EndConnection 2 Inch (DN50) 3Inch (DN80) 4Inch (DN100) 6Inch (DN150) 8Inch (DN200) NominalValveSize AvailableBodyStyles,EndConnections&Sizes Body Style NORTHAMERICA ThreadxThread Groovex GrooveGlobe Flangex Flange N/A N/AN/A N/A =AvailableN/A=NotAvailable N/A N/A N/A N/A •Onepiece,onemovingpartdia- phragm. •In-lineservice. •Onepilotvalvesub-assemblypro- videsforanyoutlet“setpressure”, i.e.,80to225psi(5,5to15,5bar). WARNING TheModelPRV-1PressureReducing Valvesdescribedhereinmustbein- stalledandmaintainedincompliance withthisdocument,aswellaswiththe applicablestandardsoftheNational FireProtectionAssociation,inaddition tothestandardsofanyotherauthori- tieshavingjurisdiction.Failuretodo somayimpairtheperformanceof thesedevices. Theownerisresponsibleformaintain- ingtheirfireprotectionsystemandde- vicesinproperoperatingcondition. Theinstallingcontractororsprinkler manufacturershouldbecontacted withanyquestions. Duetotheflowregulatingcharac- teristicofthisdevice,itsimpacton systemhydraulicsshouldbecarefully considered,especiallywhenretrofit- tedintoexistingsystems. Downstreampressureadjustment isonlytobeperformedbyexperi- encedpersonnelwhounderstand theimpactofadjustingthedown- streampressureandwhotakefull responsibilityofthereadjustment fromthefactorysetting.ThePilot ValveisprovidedwithaTamperCap, whichuponremovalforpurposesof downstreamadjustmentwillprovide anindicationthatthePRV-1mayhave beenalteredfromitsfactorysetting. Page2of16 TFP1580 FIGURE1 TYPICALMAINHEADERAPPLICATION FIGURE2 TYPICALSECTIONALFLOORCONTROLAPPLICATION MAIN HEADER PRV-1 HOSE STATIONS MAIN DRAIN DRYPIPE SPRINKLER RISER WETPIPE SPRINKLER RISER MAIN CONTROL VALVE MAIN DRAIN PRV-1 MAIN CONTROL VALVE RELIEF VALVE HOSE VALVE PRV-1 SECTIONAL CONTROL VALVE SECTIONAL FLOOR CONTROL SECTIONAL FLOOR CONTROL SPRINKLERS HOSE VALVE PRV-1 RELIEF VALVE RELIEF VALVE Z RISER MANIFOLD OR ZONE CHECK SPRINKLERS CHECK VALVE SECTIONAL CONTROL VALVE CHECK VALVE Page3of16TFP1580 FIGURE3 MODELPRV-1PRESSUREREDUCINGVALVE —ASSEMBLY— Referto KitDESCRIPTION Diaphragm HexBolt, 6 InchValve, M16x45 3 &4 InchValves, 6 &8 InchValves,M16 8 InchValve, M16x55 M16x55 2 InchValve, M12x35 HandholeCover Flat Washer, 2 InchValve, M12 3 &4 InchValves,M16 Valve Body HexNut, M16, 4 InchValve Only 6 3 4 5 NO. 2 1 . . .. .. .. .4CH . .8 8 CH CH VALVEPARTS .. .. .. . .. .. .. .. .. . .. .. .. .. .. . 1NR . .. .. . . . . . 4 8 4 CH CH CH QTY. 1 1 (a) NR . .4CH .. .. .. .. .. .. .4CH Diaphragm, .. .. .. .. .. .. . .. .. .. .. .. .. . .. .. .. .. .. .. . REPLACEMENTPARTS .. .. .. .. .. .. . .. .. .. .. .. .. . (a) 2 InchValves 3 InchValves 4 InchValves 8 InchValves 6 InchValves DESCRIPTIONNO. 92-570-2-011 92-570-2-012 92-570-2-013 92-570-2-015 92-570-2-014 P/N CHAMBER DIAPHRAGM INLET CAVITY 4,5,6 23 7 Pilot Valve. .. .. .. .. .. .1 (c) 7 (b)Pilot Valve.. .. .. .. .. .. .. .92-570-2-200 INLET PRESSURE GAUGE PRESSURE GAUGE OUTLET 11 . .Water Pressure Gauge82 (d) Water Pressure Gauge(c)92-570-2-201.. .. . 1 ANGLEBODYSTYLE GLOBEBODYSTYLE 3PRESSURE GAUGE INLET GAUGE PRESSURE 2 4,5,6 OUTLET DIAPHRAGM CHAMBER7 11 Strainer9 . .. .. .. .. .. .. .1 (e) Strainer:(d) 92-570-2-202 8 8 OUTLET CAVITY 8 8 (SEEDETAIL) STRAINER STRAINER (SEEDETAIL) Tubing andFitting Kit,(f) PressureSensorInsert10 . .1 (f) STRAINER ExcludesItems7, 8, 9, and10 Globe StyleValve: 2 InchValve. .. .. .. .. .. .. .92-570-3-001 92-570-3-004 92-570-3-005 92-570-3-003 92-570-3-002 8 InchValve 6 InchValve 4 InchValve 3 InchValve. .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . 2 InchValve 6 InchValve 4 InchValve 3 InchValve Angle StyleValve: . .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . FitsEither BodyStyle, IncludesItem 2 only: GLOBEANGLE OUTLETFLOWOUTLETFLOW TABISORIENTED DIAPHRAGM PERPENDICULAR TO OUTLETFLOW Tubing andFittings11.. .. .1 (e)PressureSensorInsert: 92-571-3-004 92-571-3-003 92-571-3-002 92-571-3-001 PRESSURESENSOR DETAILINSERTDETAIL92-570-2-204 92-570-2-205 92-570-2-207 92-570-2-206 92-570-2-203 . .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . . .. .. .. .. .. .. . 3 InchValve 4 InchValve 6 InchValve 8 InchValve 2 InchValve (SEEDETAIL) SENSOR INSERT PRESSURE (SEEDETAIL) SENSOR INSERT PRESSURE 1 2, 3, &4 InchValves 6 &8 InchValves .. .. .. . . .. .. .. .. .92-570-2-209 (b) NOTES: NR-NotReplaceable CH-CommonHardware 1. 2. DOWNSTREAM UPSTREAM DOWNSTREAM VALVE BODY TO TRIM CAVITY INTERIOR OFOUTLET 10 SENSOR INLET FACES INTERIOR VALVE BODY TO TRIM OFINLET 9 CAVITY DOWNSTREAM OUTLET CAVITY INLET CAVITY UPSTREAM DOWNSTREAMDOWNSTREAM Technical Data Approvals: ULListed.FMApproved. TheULListingisbasedon •Installationrequirementsrefer- encedintheStandardforInstalla- tionofSprinklerSystems,NFPA 13,ortheStandardforInstallation ofStandpipeandHoseValves, NFPA14,asapplicable. •Inspection,testing,andmainte- nancerequirementsreferencedin theStandardforInspection,Test- ing,andMaintenanceofWater- BasedFireProtectionSystems, NFPA25. •TheModelPRV-1beingfieldsetto providetherequiredoutletpres- suresandflowsforthegivenappli- cation. •TheModelPRV-1beingtestedaf- terinstallationinaccordancewith NFPA13and/orNFPA14asappli- cable. •TheModelPRV-1beingtestedpe- riodicallythereafterinaccordance withNFPA25. MaximumInletPressure: 250psi(17,2bar) FactoryOutlet“SetPressure”: 125psi(8,6bar) FieldOutlet“SetPressure”Range: 80to225psi(5,5to15,5bar)perits FMApproval,or80to150psi(5,5to 10,3bar)peritsULListing PressureLossWithInletPressure Above"SetPressure" Theinletpressureminustheoutlet "setpressure"equalspressureloss. Forexample:assumimgthattheinlet flowingpressureis225psi(15,5bar) andthefieldoutlet"setpressure"is 130psi(9,0bar),thepressureloss is95psi(6,5bar). PressureLosswithInletPressure Below“SetPressure” RefertoGraphsAthruE.(These graphsarearequirementofULand shouldbeusedasreferenceonly.) RatedFlowingRange: 2inch(DN50):0to250GPM (0to946LPM) 3inch(DN80):0to550GPM (0to2080LPM) 4inch(DN100):0to1000GPM (0to3785LPM) 6inch(DN150):0to2200GPM (0to8325LPM) 8inch(DN200):0to4000GPM (0to15140LPM) EndConnections: Threadedendconnectionsareavail- ableNPTthreadedorthreadedper ISO7/1.Flangedendconnections areavailabledrilledperTableA. Groovedendconnectionsareperin- dustrystandardgroovespecifica- tions. Construction(Ref.Figure3): Body.Rilsan*bluecoatedductile ironperASTMA536-77,Grade65- 45-12. HandholeCover.Rilsan*blue coatedductileironperASTMA536- 77,Grade65-45-12. Diaphragm.Nylonfabricreinforced, naturalrubberperASTMD2000. DiaphragmCoverFasteners.Gal- vanizedcarbonsteel. PilotValve.Brassandstainless steelwithnylonfabricreinforced, naturalrubberperASTMD2000dia- phragm. Strainer.Brassandstainlesssteel. PressureGauges.2-1/2inch(65 mm)diameter,stainlesssteelcase, 0to350psi(25bar). Tube,Fittings,andNeedleValve. Copper,brass,andstainlesssteel. *Rilsanisaregisteredtrademarkof ATOFINAChemicals,Inc.(TheRil- sancoatingisapolyamide(Nylon 11)coating.) Page4of16 TFP1580 TABLEA DIMENSIONALSPECIFICATIONFORSELECTIONOFFLANGEDRILLING SamedrillingasforBS4504Section3.2(PN16)andDIN2532(PN16). ANSIB16.1 AS2129ISO7005-2 JISB 2210 (Class125)(TableE)(PN10)(10K)2 A 7.50 9.50 (190,5) (241,3) B 0.75 0.88 (19,0) (22,2) 7.00 9.25 (178,0) (235,0) 0.71 0.87 (18,0) (22,0) 6.89 (175,0) FlangeDrillingSpecification NominalDimensionsinInchesand(mm) 9.45 (240,0) 11.75 (298,5) 0.88 (22,2) 11.50 (292,0) 0.87 (22,0) 11.61 (295,0) 0.75 (19,0) 0.91 (23,0) Valve 4Inch 6Inch (DN100) (DN150) 8Inch (DN200) 3Inch (DN80) N 4 8 8 8 ABN 8 ISO7005-2 (PN16) 7.09 9.45 (180,0) (240,0) 11.61 (295,0) ABN 8 8 8 12 ISO7005-2 (PN16) USE ABN 8 8 ABN 8 8 8 Dim.Dim. Nominal Qty.Dim.Dim.Qty.Dim.Dim.Qty.Dim.Dim.Qty.Dim.Dim.Qty. SamedrillingasforBS4504Section3.2(PN10)andDIN2532(PN10). Dim.A BoltCircle Diameter Dim.B BoltHole Diameter Qty.N Numberof BoltHoles 3 2 3 6.00 (152,4) 6.30 (160,0) Size SamedrillingasforANSIB16.5(Class150)andANSIB16.42(Class150).1 1 0.75 (19,0) 0.75 (19,0) 0.91 (23,0) 0.91 (23,0) 0.59 (15,0)840.71 (18,0) 5.75 (146,0) 5.90 (150,0) 0.75 (19,0) 11.42 (290,0)12 0.75 (19,0) 0.59 (15,0) Operation WithreferencetoFigure4,thesystem watersupplypressurefromtheinlet cavityofthePRV-1enterstheDia- phragmChamberthroughaStrainer andNeedleValve.Thefactoryset NeedleValveprovidestherequired orificesizeforthesupplylinetothe DiaphragmChambertooptimizeper- formance. ExitflowfromtheDiaphragmChamber throughthePilotValveiscontrolledby aregulatingspringthatisfactoryset, andsubsequentlyfieldadjustable,to thedesireddownstream“setpressure” thatistobemaintained.Asensingline connectstheoutletofthePilotValve tothesystempipingdownstreamof thePRV-1viathePressureSensor Insertintheoutletcavity. Whenthedownstreampressurerises abovethe“setpressure”ofthespring, exitflowfromtheDiaphragmChamber throughthePilotValvetothePRV-1 outletcavityisstoppedandpressure increasesintheDiaphragmChamber. Whendownstreampressurefallsbe- lowthe“setpressure”ofthespring, exitflowfromtheDiaphragmChamber throughthePilotValvetothePRV-1 outletcavityresumesandpressurein theDiaphragmChamberdecreases. TheregulatedflowthroughthePilot Valvedecreasesandincreasesthe pressureinthediaphragmchamberto sufficientlyopenandclosethePRV-1, asrequired,toregulatethedown- stream“setpressure”. Theoperationsequenceisasfollows: •Whenthereisnoflowdemand downstreamofthePRV-1,the PRV-1SeatisclosedandthePilot ValveSeatisclosed.WiththePilot ValveSeatclosed,pressureis trappedintheDiaphragmChamber toseattheDiaphragmandthe PRV-1remainsclosed. •Whenthereisaflowdemanddown- streamofthePRV-1andthePRV-1 outletpressuredropsbelowthe“set pressure,thePilotValveSeatopens torelievepressurefromtheDia- phragmChamberallowingthe PRV-1toopen. •Astheflowdemandcontinuesdown- streamofthePRV-1andthe“set pressure”ismet,thePilotValve Seatcloses.AsthePilotValveSeat closestoreducetheopening,pres- sureistrappedintheDiaphragm Chamberatapointthatallowsthe Diaphragmtoremainliftedfromthe PRV-1Seattoretainthedown- stream“setpressure”. •Shouldthedownstreampressure starttofallbelowthe“setpressure”, thePilotValveSeatre-openstoal- lowforadecreaseinpressureinthe DiaphragmChambertoallowthe PRV-1toopenfurtherandthenonce againestablishthedownstream“set pressure”. •Whenthedownstreampressureisat orabovethe“setpressure”andas- sumingthereisaflowdemand downstreamofthePRV-1,thePilot ValveSeatisclosedtotrapasuffi- cientpressureintheDiaphragm ChambertoallowthePRV-1tore- mainopentoprovidethe“setpres- sure”. Page5of16TFP1580 BODY VALVE OFINLET CAVITY INTERIOR STRAINER SUPPLY LINE SPRING REGULATING VALVE PILOT EXITFLOW SYSTEM SUPPLY WATER PRESSURE INLET CAVITYOUTLETCAVITY PRV-1 DIAPHRAGMSEAT PRV-1 SENSING LINE PILOT SEAT VALVE PRESSURE SENSORINSERT DIAPHRAGM CHAMBER LOCKNUT ADJUSTING SCREW (FACTORYSET, DONOT READJUST) NEEDLEVALVE CAP TAMPER BODY VALVE INLETFACES OFOUTLET INTERIOR UPSTREAM SENSORCAVITY TRIM TO TRIM TO PRESSURE GAUGE INLET GAUGE PRESSURE OUTLET FIGURE4 MODELPRV-1PRESSUREREDUCINGVALVE —OPERATION— Design Considerations Thefollowingitemsmustbeconsid- eredandappliedaccordinglyforan installationthatwillbeusingtheModel PRV-1PressureReducingValve: •ThePRV-1maybeinstalledverti- callyorhorizontallyandinanyorien- tationwithoutaffectingitsoperating efficiency.Whenplanningtheposi- tioningofthePRV-1,itisrecom- mendedthatconsiderationbegiven totheviewingofthepressure gauges.Considerationshouldalso begiventopositioningthePRV-1so thatthediaphragmcoverisfacing up.Withthecoverfacingup,internal accessismoreeasilyachieved. •ThePRV-1mustbeinanareathat iseasilyaccessibleformaintenance purposes,notsubjecttofreezing temperatures,andnotsubjectto physicaldamage. •Thevalveisdesignedforfreshwater service.Whencorrosiveatmos- pheresand/orcontaminatedwater suppliesarepresent,itisthe owner’sresponsibilitytoverifycom- patibilitywiththepressurereducing valve,pilotvalve,andtrim. •Thedifferencebetweenthewater supplypressureandthedesiredout- let(downstream)pressuremustbe 25psi(1,7bar)orgreaterperitsFM Approvalor50psi(3,4bar)or greaterperitsULListing.Thediffer- entialmaintainsaccuracycontrolof thedischargingpressureoverthe fullratedflowingrange. •Cavitationmayoccurwhentheinlet pressureisgreaterthantwicethe “setpressure”.Forthiscase,the pressureshouldbereducedintwo stepsbyusingtwoPRV-1’sinse- ries. •Whenreducingpressureforasprin- klersystem,areliefvalveofnotless than1/2inch(DN15)insizeshallbe locateddownstreamofthePRV-1. Thereliefvalveshallbesetata pressureequaltothelowestpres- sureratedcomponentdownstream ofthePRV-1.NOTE:FMApprovalis basedontheuseofthe1/2inch, WattsRegulator,Series530CPres- sureReliefValve. •Whenreducingpressureforasprin- klersystem,alistedindicatingvalve shallbeprovidedontheinletsideof thePRV-1. •Whenreducingpressureforasprin- klersystem,meansshallbepro- videddownstreamofthePRV-1to facilitateaflowtestatthesprinkler systemdemand. Installation TheTyco®ModelPRV-1PressureRe- ducingValvemustbeinstalledwiththe flowarrowlocatedontheDiaphragm Coverpointingintheintendeddirec- tionofflow.Installationdimensionsare providedinFigures5and6. BeforethePRV-1isinstalled,pipe linesshouldbeflushedofallchips, scaleandforeignmatter.Caremustbe exercisedtoassurethatthetrimisnot damagedduringinstallation.DoNot LiftTheValveByItsTrim. NOTES Theinletandoutletconnectionsmust bemadebasedonthedirectionofflow arrowprovidedonthehandholecover. Thevalvecannotoperateifconnected backwards. Donotalterthetrim.Alteringthetrim mayrenderthevalveineffectiveand impairthesystemoperation. PlacingThe ValveInService Steps1through12aretobeper- formedwhenplacingtheModelPRV-1 PressureReducingValveinservice. WARNING Downstreampressureadjustment isonlytobeperformedbyexperi- encedpersonnelwhounderstand theimpactofadjustingthedown- streampressureandwhotakefull responsibilityofthereadjustment fromthefactorysetting.ThePilot ValveisprovidedwithaTamperCap, whichuponremovalforpurposesof downstreamadjustmentwillprovide anindicationthatthePRV-1mayhave beenalteredfromthefactorysetting. AdjustmentoftheNeedleValveis factorysetandmustnotbealtered. TheNeedleValveisprovidedwitha tamperindication,whichuponremoval forpurposesofanyadjustmentwill provideanindicationthatthePRV-1 mayhavebeenalteredfromthefac- torysetting. NOTES PertherequirementsofNFPA13,a meansshallbeprovideddownstream ofthePRV-1tosimulatethesprinkler systemdemand.Inthecaseofhose stations,theopeningofahosevalve ormultiplehosevalves,asrequired, willbenecessarytosimulatehose streamdemand. Forthepurposesofthefollowingin- struction,theopeningofa“flowtest valve”simulateseitherthesprinkler demandorhosestreamdemand,as applicable.Thesprinklerdemandor hosestreamdemandmustbeatleast 50GPM(190LPM)for2to6inch (DN50toDN150)valvesandatleast 100GPM(380LPM)for8inch (DN200)valves. Thereisnoneedtoventanytrapped airfromtheDiaphragmChamber. FillingTheSystem: Step1.Verifythatdownstreamdrain valvesareclosedandthatthereareno leaks. Step2.Partiallyopenavalveorvalves attheendofthesystem(e.g.,anin- spector’stestconnectiononawetpipe system)toallowtrappedairtoescape whenfillingthesystem. Step3.Slowlyandpartiallyopenthe watersupplycontrolvalvefeedingthe PRV-1. Step4.Afterthesystemfillswith water,closethevalveorvalvesthat hadbeenpartiallyopenedinStep2. Step5.Completelyopenthemain watersupplycontrolvalvefeedingthe PRV-1. DownstreamPressureAdjustment: Step6.RemovetheTamperCapfrom thePilotValvebyfirstlooseningitsset screwandthenunscrewingtheTam- perCap. Step7.Openthe“flowtestvalve”to simulateeitherthedesiredsprinkler demandorhosestreamdemand. NOTE Ifsurgingflowoccurs,attempttobleed trappedairfromthesystemviathe inspector’stestvalveandanyother valvethatcanventtrappedair. Step8.Loosenthelocknutonthead- justingscrewofthePilotValve. Step9.Turntheadjustingscrew clockwisetoincreaseoutletpressure orcounterclockwisetodecreaseoutlet pressure. Step10.Afterachievingthedesired performance,tightenthelocknuton theadjustingscrew. Step11.Closethe“flowtestvalve”. Observetheoutletpressuregauge andcomparetotherequired“set pressure”.Iftherequired“setpres- sure”isnotachieved,repeatStep8 andproceedaccordingly. Page6of16 TFP1580 Step12.ReplacetheTamperCapand tightenitssetscrew. Thepressurereducingvalveisnow setforservice. NOTES Duetothespringtolerancewithinthe PilotValve,itmaybenecessaryto alternatebackandforthbetweenre- sidualandstaticconditionstoachieve thedesired“setpressure”forbothre- sidualandstaticconditions. Afteranydownstreampressuread- justment,thefollowingitemsaretobe recordedonatagattachedtothe valve: -Valveinstallationlocation -Inletstaticpressure -Outletstaticpressure -Inletresidualpressure -Outletresidualpressure -Intendedoutletflow Thetagisnottoberemoveduntilafter thesystemhasbeenacceptedbythe AuthorityHavingJurisdiction.Itisrec- ommendedthatthetagnotbere- movedevenafteracceptancebythe AuthorityHavingJurisdictionunless anothermeansofrecordkeepingis maintained. Careand Maintenance Inspection,testing,andmaintenance mustbeperformedinaccordancewith therequirementsoftheNFPA,andany impairmentmustbeimmediatelycor- rected. Theownerisresponsibleforthein- spection,testing,andmaintenanceof theirfireprotectionsystemandde- vicesincompliancewiththisdocu- ment,aswellaswiththeapplicable standardsofanyauthoritieshavingju- risdiction.Theinstallingcontractoror productmanufacturershouldbecon- tactedrelativetoanyquestions. Automaticsprinklersystemsshouldbe inspected,tested,andmaintainedbya qualifiedInspectionServiceinaccord- ancewithlocalrequirementsand/or nationalcodes. NOTE Beforeclosingafireprotectionsystem maincontrolvalveformaintenance workonthefireprotectionsystemthat itcontrols,permissiontoshutdownthe affectedfireprotectionsystemsmust firstbeobtainedfromtheproper authoritiesandallpersonnelwhomay beaffectedbythisdecisionmustbe notified. TheModelPRV-1PressureReducing Valverequiresnolubrication,packing orpreventativemaintenance;how- ever,replacementofthediaphragm everyfiveyearsisrecommended. FlowTests.FlowtestsperNFPAare requiredeveryfiveyears,atwhich pointtheoutletpressureiscompared toprevioustests.Ifnecessarythe PRV-1canbereadjustedfollowingthe PlacingTheValveInServicesection. Ifthedesiredpressurecannotbe achieved,theDiaphragmand/orPilot Valveshouldbereplaced. DiaphragmReplacement.Priortore- placingtheDiaphragm,thePRV-1 mustbetakenoutofserviceandcom- pletelydrained.WithreferencetoFig- ure3,theDiaphragmTabisoriented perpendiculartotheoutletflow.When reinstallingtheDiaphragmCover,the DiaphragmCoverFasteners mustbe uniformlyandsecurelytightened usingacross-drawsequence.After tightening,doublechecktomakecer- tainthatalloftheDiaphragmCover fastenersaresecurelytightened. PilotValveReplacement.Priortore- movingthePilotValve,thePRV-1 mustbetakenoutofserviceandcom- pletelydrained.Wheninstallingthere- placementPilotValve,thetrimcompo- nentsmustbereplacedexactlyasthey were.AfterreinstallingthePilotValve andbeforereturningthePRV-1into service,completelyunscrewtheAd- justingStemofthereplacementPilot Valvesoastoobtainaminimumoutlet “setpressure”.Thenproceedtouse theinstructionsunderPlacingThe ValveInServicesectiontoplacethe PRV-1inservice. NOTES ThePilotValveisnotfieldrepairable. AttemptingtorepairthePilotValve mayrenderthevalveineffectiveand impairthesystemoperation. CompletelyunscrewingtheAdjusting StemofthereplacementPilotValve willhelptoavoidanaccidentalover pressurizationofthesystempiping priortoachievingthedesired“set pressure”. Limited Warranty ProductsmanufacturedbyTycoFire& BuildingProducts(TFBP)arewar- rantedsolelytotheoriginalBuyerfor ten(10)yearsagainstdefectsinmate- rialandworkmanshipwhenpaidfor andproperlyinstalledandmaintained undernormaluseandservice.This warrantywillexpireten(10)years fromdateofshipmentbyTFBP.No warrantyisgivenforproductsorcom- ponentsmanufacturedbycompanies notaffiliatedbyownershipwithTFBP orforproductsandcomponentswhich havebeensubjecttomisuse,improper installation,corrosion,orwhichhave notbeeninstalled,maintained,modi- fiedorrepairedinaccordancewithap- plicableStandardsoftheNationalFire ProtectionAssociation,and/orthe standardsofanyotherAuthorities HavingJurisdiction.Materialsfound byTFBPtobedefectiveshallbeeither repairedorreplaced,atTFBP’ssole option.TFBPneitherassumes,nor authorizesanypersontoassumeforit, anyotherobligationinconnectionwith thesaleofproductsorpartsofprod- ucts.TFBPshallnotberesponsiblefor sprinklersystemdesignerrorsorinac- curateorincompleteinformationsup- pliedbyBuyerorBuyer’srepre- sentatives. InnoeventshallTFBPbeliable,in contract,tort,strictliabilityorunder anyotherlegaltheory,forincidental, indirect,specialorconsequentialdam- ages,includingbutnotlimitedtolabor charges,regardlessofwhetherTFBP wasinformedaboutthepossibilityof suchdamages,andinnoeventshall TFBP’sliabilityexceedanamount equaltothesalesprice. Theforegoingwarrantyismadeinlieu ofanyandallotherwarranties,ex- pressorimplied,includingwarranties ofmerchantabilityandfitnessforapar- ticularpurpose. Thislimitedwarrantysetsforththeex- clusiveremedyforclaimsbasedon failureofordefectinproducts,materi- alsorcomponents,whethertheclaim ismadeincontract,tort,strictliability oranyotherlegaltheory. Thiswarrantywillapplytothefullex- tentpermittedbylaw.Theinvalidity,in wholeorpart,ofanyportionofthis warrantywillnotaffecttheremainder. Page7of16TFP1580 Page8of16 TFP1580 FIGURE5 MODELPRV-1PRESSUREREDUCINGVALVE —GLOBESTYLEINSTALLATIONDIMENSIONS— A B D F E (DN100) 4" (DN150) 6" (DN80) 3" (DN200) 8" A FlangexFlangeEndConnections Valve Nominal Sizes (305) 12.00 (406) 15.98 (283) 11.14 (470) 18.50 B (57) 2.24 (142) 5.59 (100) 3.93 (170) 6.69 CD (201) 7.91 (171) 6.73 (190) 7.48 (182) 7.16 E (246) 9.68 (292) 11.49 (235) 9.25 (319) 12.55 F (115) 4.52 (150) 5.90 (177) 6.96 (DN50) 2" A Threadx Thread EndConnections Valve Nominal Sizes BCDEF (60) 2.36 (DN100) 4" (DN150) 6" (DN80) 3" (DN50) 2" A GroovexGrooveEndConnections Valve Nominal Sizes (346) 13.62 (452) 17.79 (283) 11.14 (191) 7.51 B (111) 4.37 (84) 3.30 (45) 1.77 (38) 1.49 CD (201) 7.91 (171) 6.73 (190) 7.48 (163) 6.41 E (246) 9.68 (292) 11.49 (235) 9.25 (208) 8.18 F (115) 4.52 (150) 5.90 (60) 2.36 (191) 7.51 (38) 1.49 (163) 6.41 (208) 8.18 (DN80) 3" (283) 11.14 (45) 1.77 (190) 7.48 (235) 9.25 (100) 3.93 (186) 7.32 (221) 8.70 (251) 9.88 (208) 8.19 (186) 7.32 (208) 8.19 C (283) 11.14 (221) 8.70 (251) 9.88 (208) 8.19 (100) 3.93 (100) 3.93 NominalInstallationDimensionsinInchesand(mm)Weight NominalInstallationDimensionsinInchesand(mm)Weight NominalInstallationDimensionsinInchesand(mm)Weight (6,9) 15.2 (13,9) 30.6 (kg) lbs. (kg) lbs. (kg) lbs. (20,5) 45.2 (53,5) 118.0 (21,0) 46.3 (29,5) 65.0 (53,5) 118.0 (75,5) 166.5 (6,9) 15.2 (13,9) 30.6 FIGURE6 MODELPRV-1PRESSUREREDUCINGVALVE —ANGLESTYLEINSTALLATIONDIMENSIONS— (DN100) 4" (DN150) 6" (DN80) 3" A NominalInstallationDimensions inInchesand (mm) FlangexFlange EndConnections Valve Nominal Sizes BCDEF (DN50) 2" A NominalInstallationDimensions inInchesand (mm) ThreadxThread End Connections Valve Nominal Sizes BC (186) 7.32 D (163) 6.41 E (208) 8.18 F (61) 2.40 (DN100) 4" (DN150) 6" (DN80) 3" (DN50) 2" A NominalInstallationDimensions inInchesand (mm) GroovexGrooveEndConnections Valve Nominal Sizes (161) 6.33 (226) 8.89 (154) 6.06 B (116) 4.56 (170) 6.69 (115) 4.52 C (221) 8.70 (251) 9.88 D (201) 7.91 (171) 6.73 (190) 7.48 E (246) 9.68 (292) 11.49 (235) 9.25 F (115) 4.52 (150) 5.90 (100) 3.93 (90) 3.54 (81) 3.18 B C A GD F E (7,2) 15.9 (19,9) 44.0 (40,5) 89.3 (163) 6.41 (208) 8.18 (61) 2.40 (90) 3.54 (81) 3.18 (161) 6.33 (226) 8.89 (154) 6.06 (116) 4.56 (170) 6.69 (115) 4.52 (201) 7.91 (171) 6.73 (190) 7.48 (246) 9.68 (292) 11.49 (235) 9.25 (115) 4.52 (150) 5.90 (100) 3.93 (30,5) 67.3 (52,7) 116.2 (15,9) 35.1 (DN80) 3" (154) 6.06 (115) 4.52 (208) 8.19 (190) 7.48 (235) 9.25 (100) 3.93 (15,5) 34.1 (186) 7.32 (208) 8.19 (208) 8.19 (221) 8.70 (251) 9.88 Weight (kg) lbs. G G (61) 2.40 G (115) 4.52 (150) 5.90 (100) 3.93 (61) 2.40 (115) 4.52 (150) 5.90 (100) 3.93 (100) 3.93 Weight (kg) lbs. Weight (kg) lbs. (7,2) 15.9 (15,5) 34.1 Page9of16TFP1580 Page10of16 TFP1580 GRAPHA-1 2INCH(DN50)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF80PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) 1 GPM=3,785 LPM FLOWRATEINGALLONSPERMINUTE(GPM) 0 1 PSI=0,06895 BAR 250255075100125150175200225 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 40 20 0 10 30 130 110 120 90 70 80 100 60 50 140 B =50PSIINLETPRESSURE A=70PSIINLETPRESSURE A B GRAPHA-2 2INCH(DN50)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF150PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) 225200175150125100755025 2500 1 GPM=3,785 LPM1 PSI=0,06895 BAR 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=100PSIINLET PRESSURE A=140PSIINLET PRESSURE C=50PSIINLET PRESSURE FLOWRATEINGALLONSPERMINUTE(GPM) A B C GRAPHB-1 3INCH(DN80)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF80PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) GRAPHB-2 3INCH(DN80)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF150PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) Page11of16TFP1580 1 GPM=3,785LPM 0 1PSI=0,06895BAR 55050100150200250300350400450500 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=50PSIINLETPRESSURE A=70PSIINLETPRESSURE A B FLOWRATEINGALLONSPERMINUTE(GPM) 550500450400350300250200150100500 1 GPM=3,785LPM1PSI=0,06895BAR 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=100PSIINLETPRESSURE A=140PSIINLETPRESSURE C=50PSIINLETPRESSURE B A C FLOWRATEINGALLONSPERMINUTE(GPM) GRAPHC-1 4INCH(DN100)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF80PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) GRAPHC-2 4INCH(DN100)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF150PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) Page12of16 TFP1580 0 1000 1 GPM=3,785LPM1PSI=0,06895BAR 100200300400500600700800900 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=50PSIINLETPRESSURE A=70PSIINLETPRESSURE B A FLOWRATEINGALLONSPERMINUTE(GPM) 1PSI=0,06895BAR 4003002001000 900800700600500 1000 1 GPM=3,785LPM 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 A=140PSIINLETPRESSURE B=100PSIINLETPRESSURE C=50PSIINLETPRESSURE C B A FLOWRATEINGALLONSPERMINUTE(GPM) GRAPHD-1 6INCH(DN150)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF80PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) GRAPHD-2 6INCH(DN150)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF150PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) Page13of16TFP1580 225020001750150012501000750500250 25000 1 GPM=3,785LPM1PSI=0,06895BAR 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=50PSIINLETPRESSURE A=70PSIINLETPRESSURE A B FLOWRATEINGALLONSPERMINUTE(GPM) 25002250200017501500125010007505002500 1 GPM=3,785LPM1PSI=0,06895BAR 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=100PSIINLETPRESSURE A=140PSIINLETPRESSURE C=50PSIINLETPRESSURE C B A FLOWRATEINGALLONSPERMINUTE(GPM) GRAPHE-1 8INCH(DN200)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF80PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) GRAPHE-2 8INCH(DN200)PRESSUREREDUCINGVALVE OUTLETPRESSUREVERSESFLOW SHOULDINLETPRESSUREFALLBELOWASETPRESSUREOF150PSI (ThisgraphisarequirementofULandshouldbeusedasreferenceonly.) Page14of16 TFP1580 10005000 150020002500300035004000 1 GPM=3,785LPM1PSI=0,06895BAR 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=50PSIINLETPRESSURE A=70PSIINLETPRESSURE B A FLOWRATEINGALLONSPERMINUTE(GPM) 1 GPM=3,785LPM 0 1PSI=0,06895BAR 4000500100015002000250030003500 40 OU T L E T P R E S S U R E I N P O U N D S P E R S Q U A R E I N C H ( P S I ) 0 10 20 30 50 60 70 80 90 100 110 120 130 140 B=100PSIINLETPRESSURE A=140PSIINLETPRESSURE C=50PSIINLETPRESSURE B A C FLOWRATEINGALLONSPERMINUTE(GPM) Ordering Procedure NorthAmerica PressureReducingValve: Specify:GlobeType,(specifysize), 125psiOutlet“SetPressure”with(T xT,GxG,orFxF)Connection,P/N (specifyfrombelow). P/N’sforGLOBEBODYSTYLE AVAILABLEINAMERICAS 2InchTxT NPT................P/N52-570-8-060 2InchGxG 2.37inch(60,3mm) GrooveO.D...........P/N52-570-8-920 3InchGxG 3.50inch(88,9mm) GrooveO.D..........P/N52-570-8-922 4InchGxG 4.50inch(114,3mm) GrooveO.D..........P/N52-570-8-923 4InchFxF ANSIFlange.........P/N52-570-8-023 6InchGxG 6.62inch(168,3mm) GrooveO.D..........P/N52-570-8-925 6InchFxF ANSIFlange.........P/N52-570-8-025 8InchFxF ANSIFlange.........P/N52-570-8-026 PressureReliefValve: Specify:1/2inch(DN15)WattsRegu- lator,Series530CPressureRelief ValveforusedownstreamofaPRV-1 beingusedforreducingpressurein sprinklersystem,P/N92-570-2-208. ReplacementValveParts: Specify:(description)forusewith (specify)sizeModelPRV-1Pressure ReducingValve,P/N(seeFigure3). Ordering Procedure SouthAmerica, CentralAmerica& EasternHemisphere PressureReducingValve: Specify:(GlobeorAngle)Type,(spec- ifysize),125psiOutlet“SetPressure” with(specify)Connection(andfor flangedvalvesspecifyflangedrilling), P/N(specifyfromcompletelistingon Page16). •ValveType&Size (Globe,2,3,4,6,or8Inch) (Angle,2,3,4,or6Inch •125psiOutlet“SetPressure” Pressure •ConnectionType (Threaded,Grooved,Flanged) Forthreaded,specifyNPTorISO Forgrooved,specifyO.D.PipeSize -2inch(DN50): 2.88inch(60,3mm)O.D. -3inch(DN80): 3.50inch(88,9mm)O.D. -4inch(DN100): 4.50inch(114,3mm)O.D. -6inch(DN150): 6.62inch(168,3mm)O.D.or 6.50inch(165,1mm)O.D. -8inch(DN200): 8.62inch(219,1mm)O.D. Forflanged,specifyflangedrilling per -ANSIB16-1(Class125) -ISO7005-2(PN16) -ISO7005-2(PN10), 8inchvalveonly -JISB2210(10K) -AS2129(TableE) NOTES RefertoTableAforflangedrillingdi- mensionalspecifications. PressureReliefValve: Specify:1/2inch(DN15)WattsRegu- lator,Series530CPressureRelief ValveforusedownstreamofaPRV-1 beingusedforreducingpressurein sprinklersystem,P/N92-570-2-208. ReplacementValveParts: Specify:(description)forusewith (specify)sizeModelPRV-1Pressure ReducingValve,P/N(seeFigure3). Page15of16TFP1580 P/N’sforGLOBEBODYSTYLE 2InchTxT NPT................P/N52-570-8-060 2InchTxT ISO................P/N52-570-8-160 2InchGxG 2.37inch(60,3mm) GrooveO.D...........P/N52-570-8-920 3InchTxT NPT................P/N52-570-8-062 3InchTxT ISO................P/N52-570-8-162 3InchGxG 3.50inch(88,9mm) GrooveO.D..........P/N52-570-8-922 3InchFxF ANSIFlange.........P/N52-570-8-022 3InchFxF ISO(PN16)Flange....P/N52-570-8-112 3InchFxF JISFlange...........P/N52-570-8-722 3InchFxF ASFlange...........P/N52-570-8-522 4InchGxG 4.50inch(114,3mm) GrooveO.D..........P/N52-570-8-923 4InchFxF ANSIFlange.........P/N52-570-8-023 4InchFxF ISO(PN16)Flange....P/N52-570-8-113 4InchFxF JISFlange...........P/N52-570-8-723 4InchFxF ASFlange...........P/N52-570-8-523 6InchGxG 6.62inch(168,3mm) GrooveO.D..........P/N52-570-8-925 6InchGxG 6.50inch(165,1mm) GrooveO.D..........P/N52-570-8-945 6InchFxF ANSIFlange.........P/N52-570-8-025 6InchFxF ISO(PN16)Flange....P/N52-570-8-115 6InchFxF JISFlange...........P/N52-570-8-725 6InchFxF ASFlange...........P/N52-570-8-525 8InchFxF ANSIFlange.........P/N52-570-8-026 8InchFxF ISO(PN10)Flange....P/N52-570-8-116 8InchFxF ISO(PN16)Flange....P/N52-570-8-126 8InchFxF JISFlange...........P/N52-570-8-726 8InchFxF ASFlange...........P/N52-570-8-526 P/N’sforANGLEBODYSTYLE 2InchTxT NPT................P/N52-571-8-060 2InchTxT ISO................P/N52-571-8-160 2InchGxG 2.37inch(60,3mm) GrooveO.D..........P/N52-571-8-920 3InchTxT NPT................P/N52-571-8-062 3InchTxT ISO................P/N52-571-8-162 3InchGxG 3.50inch(88,9mm) GrooveO.D..........P/N52-571-8-922 3InchFxF ANSIFlange.........P/N52-571-8-022 3InchFxF ISO(PN16)Flange...P/N52-571-8-112 3InchFxF JISFlange..........P/N52-571-8-722 3InchFxF ASFlange...........P/N52-571-8-522 4InchGxG 4.50inch(114,3mm) GrooveO.D.........P/N52-571-8-923 4InchFxF ANSIFlange........P/N52-571-8-023 4InchFxF ISO(PN16)Flange...P/N52-571-8-113 4InchFxF JISFlange..........P/N52-571-8-723 4InchFxF ASFlange...........P/N52-571-8-523 6InchGxG 6.62inch(168,3mm) GrooveO.D.........P/N52-571-8-925 6InchGxG 6.50inch(165,1mm) GrooveO.D.........P/N52-571-8-945 6InchFxF ANSIFlange........P/N52-571-8-025 6InchFxF ISO(PN16)Flange...P/N52-571-8-115 6InchFxF JISFlange..........P/N52-571-8-725 6InchFxF ASFlange...........P/N52-571-8-525 Page16of16 TFP1580 ©2007TYCOFIRE&BUILDINGPRODUCTS,451NorthCannonAvenue,Lansdale,Pennsylvania19446 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.336.4226 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 17 AHEAD OF THE FLOW® www.nibco.com Revision 8/3/2010 300 PSI WWP Bronze Ball Valves Fire Protection Valve • Two-Piece Body • Chrome Plated Ball • Blowout-Proof Stem • Reinforced PTFE Seats MATeRIAL LIST PART SPeCIFICATION 1. Handle Nut Zinc Plated Steel 2. Handle Zinc Plated Steel Clear Chromate with Plastisol Grip 3. Threaded Pack Gland Brass ASTM B16 4. Packing PTFE 5. Stem Silicon Bronze ASTM B371 Alloy C69430 or ASTM B99 Alloy C65100 6. Thrust Washer Reinforced PTFE 7. Ball Brass ASTM B124 Alloy C37700 or ASTM B16 Alloy C36000 with Hard Chrome Plate 8. Seat Ring (2) Reinforced PTFE 9. Body Cast Red Bronze ASTM B584 Alloy C84400 10. Body End Piece Cast Red Bronze ASTM B584 Alloy C84400 ¹⁄₄" and ³⁄₈" size only has A304 stainless steel grounding washer . 300 PSI/20 .7 Bar Non-Shock Cold Water CONFORMS TO MSS SP-110 • UL LISTED† • FM APPROVED† DIMeNSIONS—WeIGHTS—QUANTITIeS KT-585-70-UL Dimensions Size A B C D Port Weight Box Master In . mm . In . mm . In . mm . In . mm . In . mm . Lbs . Kg . Qty . Ctn . Qty . ¹⁄₄ 8 2.00 51 1.75 44 5.00 127 .38 10 .45 .20 10 100 ³⁄₈ 10 2.00 51 1.75 44 5.00 127 .38 10 .45 .20 10 100 ¹⁄₂ 15 2.44 62 1.88 48 5.19 132 .50 13 .64 .29 10 100 ³⁄4 20 2.94 75 2.25 57 6.25 159 .75 19 1.33 .60 5 50 1 25 3.34 85 2.38 59 6.44 164 1.00 25 1.79 .81 5 20 KT-580-70-UL Dimensions Size A B C D Port Weight Box Master In . mm . In . mm . In . mm . In . mm . In . mm . Lbs . Kg . Qty . Ctn . Qty . 1 ¹⁄₄ 32 3.94 100 2.63 67 6.75 171 1.00 25 2.17 .99 5 20 1 ¹⁄₂ 40 4.31 110 3.00 76 8.91 228 1.25 32 3.27 1.49 5 20 2 50 4.63 117 3.25 83 9.06 230 1.50 38 5.09 2.31 5 10 2 ¹⁄₂ 65 5.84 148 3.53 90 9.66 245 2.00 51 8.25 3.79 2 6 3 80 7.09 202 4.41 112 11.53 293 2.50 64 15.65 7.11 1 4 † UL Listed, FM Approved for trim and drain use (UL Subject 285) – Sizes ¹⁄₄" thru 2" . KT-585-70-ULFull PortNPT x NPT KT-580-70-ULStandard PortNPT x NPT KT-585-70-UL ¹⁄₄" - 1" Full Port Threaded KT-580-70-UL 1¹⁄₄" - 3" Standard Port Threaded DezincificationResistant NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.336.4226 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 14 AHEAD OF THE FLOW® www.nibco.com Revision 8/3/2010 200 PSI WWP Bronze Check Valves Fire Protection Valve • Horizontal Swing • Rubber Disc MATeRIAL LIST PART SPeCIFICATION 1. Bonnet Bronze ASTM B62 or B584 Alloy C84400 2. Body Bronze ASTM B62 or B584 Alloy C84400 3. Hinge Pin Bronze ASTM B140 Alloy C31400 or B134 Alloy C23000 4. Disc Hanger Bronze ASTM B62 5. Hanger Nut Bronze ASTM B97 Alloy C65500 or Brass ASTM B16 6. Disc Holder Bronze ASTM B62 7. Seat Disc Nitrile (W) PTFE (Y)‡ 8. Seat Disc Nut Brass ASTM B16 or B97 Alloy C65500 9. Hinge Pin Plug Bronze ASTM B140 Alloy C32000 (Not Shown) *10. Seat Disc Washer Stainless Steel * Sizes ³⁄₄" , 1" , 1¹⁄₄" and 1¹⁄₂" only . ‡ 2¹⁄₂" and 3" size only . 200 PSI/13 .8 Bar Non-Shock Cold Water CONFORMS TO MSS SP-80 NIBCO check valves may be installed in both horizontal and vertical lines with upward flow or in any intermediate position . WARNING - Valve must be installed downstream of receiver tank if used in line with reciprocating air compressor . DIMeNSIONS—WeIGHTS—QUANTITIeS Dimensions Size A B Weight Box Master . In . mm . In . mm . In . mm . Lbs . Kg . Qty . Ctn . Qty . ¹⁄₂ 15 2.44 62 1.69 43 .58 .26 10 50 3⁄₄ 20 2.94 75 1.88 48 .92 .42 10 50 1 25 3.56 90 2.31 59 1.55 .70 5 30 1¹⁄₄ 32 4.19 106 2.69 68 2.32 1.05 5 20 1¹⁄₂ 40 4.50 114 2.94 75 3.00 1.36 2 10 2 50 5.25 133 3.81 97 4.87 2.21 2 10 2¹⁄₂ 65 8.00 203 5.06 129 11.48 5.22 1 5 3 80 9.25 235 6.25 159 17.53 7.97 1 4 Sizes 2¹⁄₂" and 3" supplied as T-433-Y with PTFe seat disc . KT-403-W NPT x NPT KT-403-W Threaded DezincificationResistant ❏TheAGFManufacturingInc.Model1000 TES TANDRAIN ProvidesBothTheTest FunctionAndTheExpressDrainFunctionForAWetFireSprinklerSystem. ❏TheModel1000CompliesWithAllRequirementsOfNFPA-13,NFPA-13R, And NFPA-13D. ❏TheModel1000 TESTANDRAIN Is ASingleHandleBallValveThatIsLightWeightAnd Compact,IncludesATamperResistantTestOrifice,IntegralTamperResistantSight Glasses,AndIs300PSIRated. ❏AvailableInAFullRangeOfSizesFrom3/4"To2"NPT&BSPT,WithAllSpecifiable O rificeSizes3/8",7/16",1/2",17/32",5/8"(ELO),&3/4"(ESFR). ❏TheOrificeSizeIsNotedOnTheIndicatorPlateAndTheValveIsTappedFor A PressureGauge. ❏LockingKitAvailableWhichProvidesSuperiorVandalResistanceAndPrevents Unintentional AlarmActivation. MODEL1000 10/00 Che ck O u t O u r N e w A u to C A D Site! *Availableon11/4"to2"sizeunitsonly.**3/4"ULListedonly. APPROVALS: ❏ ULandULCListed ❏ FMApprovedexcept3/4" ❏ NYC-BSANO.720-87-SM ❏ CA.StateFireMarshall 5 1 /16 "128mm 3 /4 " 1" 1 1 /4 " 1 1 /2 " 2" 1 1 /2 "37.58mm 2 3 /16 "55.65mm 3 5 /8 "93.23mm 3 3 /8 "85.88mm 1 13 /16 "45.30mm 4 9 /16 "117.12mm 6 3 /8 "162.42mm 5 1 /16 " 128mm 1 1 /2 " 37.58mm 2 3 /16 " 55.65mm 3 5 /8 " 93.23mm 3 3 /8 " 85.88mm 1 13 /16 " 45.30mm 4 9 /16 " 117.12mm 6 3 /8 " 162.42mm 5 7 /16 "137.70mm 1 11 /16 "42.70mm 2 9 /16 "65.36mm 4 1 /4 "108.36mm 3 5 /16 "82.84mm 1 15 /16 "50.89mm 5 9 /16 "141.39mm 5 1 /2 "192.28mm 6 7 /16 "163.38mm 1 13 /16 "45.50mm 3 1 /4 "81.50mm 5 1 /16 "127mm 3 7 /8 "99.18mm 2 5 /8 "66.97mm 8 1 /4 "206.63mm 10 7 /8 "273.60mm 6 7 /16 " 163.38mm 1 13 /16 " 45.50mm 3 1 /4 " 81.50mm 5 1 /16 " 127mm 3 7 /8 " 99.18mm 2 5 /8 " 66.97mm 8 1 /4 " 206.63mm 10 7 /8 " 273.60mm AGFMANUFACTURINGINC. 100QuakerLane Malv ern,PA19355USA Telephone:(610)240-4900 Fax:(610)240-4906 www.testandrain.com PRINTED IN USA MFG. #5401206 - REV G 12/08 VSR-S VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 1 OF 3 Stock No. 1144440 The Model VSR-S is a vane type waterfl ow switch for use on wet sprinkler systems that use 1" (25mm), 1¼" (32mm), 1½" (38mm) or 2" (50mm) pipe size. The unit may also be used as a sectional waterfl ow detector on large systems. The unit contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a fl ow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The fl ow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR-S switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A fi eld installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Installation These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" (15cm) of a valve, drain or fi tting which changes the direction of the waterfl ow. Select the proper paddle for the pipe size and type of TEE used see Fig. 1 for instructions on changing paddle. The unit has a 1" NPT bushing for threading into a non-corrosive TEE. See Fig. 2 for proper TEE size, type and installation. Use no more than three wraps of tefl on tape. Screw the device into the TEE fi tting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterfl ow. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. The device can also be used in copper or plastic pipe installations with the proper adapters so that the specifi ed TEE fi tting may be installed on the pipe run. Note: Do not leave cover off for an extended period of time. Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com UL, ULC, CSFM Listed and NYMEA Accepted Service Pressure: Up to 300 PSI (20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) UL Maximum Surge: 18 FPS (5,5 m/s) Enclosure: Die-cast, red enamel fi nish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT (Form C) 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive 10mAmps min. at 24 VDC Conduit Entrances: Two openings provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic, copper and schedule 40 iron pipe. Fits pipe sizes - 1" (25mm), 1 1/4" (32mm), 1 1/2" (38mm) and 2" (50mm) Note: 12 paddles are furnished with each unit, one for each pipe size of threaded and sweat TEE, one for 1" (25mm) CPVC, one for 1" (25mm) CPVC (Central), one for 1" threaded Nibco CPVC, and one for 1 1/2" (38mm) threaded (Japan). Environmental Specifi cations: • NEMA-4/IP54 Rated enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fi tting.• Temperature range: 40° F to 120° F, (4,5° C to 49° C) UL Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090148 (See Fig. 7 for terminations) Replaceable Components: Retard/Switch Assembly, stock no. 1029030 Installation must be perfomed by qualifi ed personnel and in accordance with all national and local codes and ordinances. Shock hazard. Disconnect power source before servicing. Serious injury or death could result. Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. 4440 PRINTED IN USA MFG. #5401206 - REV G 12/08 VSR-S VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 2 OF 3 COVER TAMPER SWITCH MOUNT SO ARROW ON BUSHING POINTS IN DIRECTION OF WATERFLOW 1” NPT THREADED FITTING ON ALL SIZES RUN OF THE TEE MAY BE THREADED OR SWEAT PIPE DIRECTION OF WATERFLOW DWG# 802-30A Fig. 1 Fig. 2 Notes: 1. The Model VSR-S has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other is used to operate a local audible or visual annunciator. 2. For supervised circuits see “Switch Terminal Connections” drawing and caution note (Fig. 3). Retard Adjustment The time delay is factory set at 30 ± 10 seconds. The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60- 90 seconds). The time delay should be set at the minimum required to prevent false alarms. Fig. 3 Switch Terminal Connections Clamping Plate Terminal OUTG O I N G INCO M I N G DWG# 923-3 To remove knockouts: Place screwdriver at edge of knockouts, not in the center. Screw the device into the tee fi tting as shown. Care must be taken to properly orient the device for the direction of waterfl ow. On sweat tees, no threaded bushings, inserts, or adapters are permitted, unless they comply with the dimensions listed in the chart below. Important - The depth to the inside bottom of the tee should have the following dimensions: DIRECTION OF WATER FLOW DWG# 737-31 Shown with optional Cover Tamper Switch Kit. DWG# 1146-4 DWG# 8810018-2 C (WHT) N.O. (RED) N.C. (BLK) Fig. 7 Cover Tamper Switch Wiring (Shown with cover in place) DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME 4,3MM (1 11/16”)APPROX. DEPTH DWG# 735-33 Approximate Depth Requirement Tee SizeThreadedSweatCPVC 1" x 1" x 1"2 1/16"1 3/4"2 7/16" 1 1/4" x 1 1/4" x 1"2 7/16"2 7/16"N/A 1 1/2" x 1 1/2" x 1"2 11/16"2 1/4"N/A 2" x 2" x 1"3 3/16"2 3/4"N/A DWG# 1146-3A POSITIVE DC OR HOT AC NEGATIVE DC OR NEUTRAL AC WATERFLOW ZONE ON FIRE PANEL BELL EOLR CO M NC NO NO N C CO M Break out thin section of cover when wiring both switches from one conduit entrance. DWG# 1206-2 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. Fig. 4 Typical Electrical Connections Fig. 5 Fig. 6 There are 12 paddles furnished with each unit. One for each size of threaded, sweat or plastic TEE as described in Fig. 2. These paddles have raised lettering that shows the pipe size and type of TEE that they are to be used with. The proper paddle must be used. The paddle must be properly attached (see drawing) and the screw that holds the paddle must be securely tightened.Do not use more than three wraps of tefl on tape. PRINTED IN USA MFG. #5401206 - REV G 12/08 VSR-S VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 3 OF 3 Testing The frequency of inspection and testing for the Model VSR-S and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently.) An inspector's test valve (usually located at the end of the most remote branch line) should always be used for test purposes. If there are no provisions for testing the operation of the fl ow detection device on the system, application of the VSR-S is not recommended or advisable. A minimum fl ow of 10 gpm (38 Lpm) is required to activate this device. Please advise the person responsible for testing of the fi re protection system that this system must be tested in accordance with the testing instructions. Maintenance Inspect detectors monthly for leaks. If leaks are found, replace the detector. The VSR-S waterfl ow switch should provide years of trouble- free service. The retard and switch assembly are easily fi eld replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030. There is no maintenance required, only periodic testing and inspection. DWG# 1206-5 GROUND SCREWS 3.50"5.56" (89.0 mm) (59.4 mm) 2.34" (141.2 mm) (52.3 mm) 4.89" 2.00" (50.8 mm) 1"-11 1/2 NPT Mounting Dimensions Waterfl ow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterfl ow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. Removal • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterfl ow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Use a wrench on the fl ats of the bushing. Turn the switch counterclockwise to disengage the pipe threads. • Gently lift with your fi ngers, roll the vane so it will fi t through the hole while continuing to lift the waterfl ow detector. • Lift detector clear of pipe. PRINTED IN USA RBVS UNIVERSAL BALL VALVE SWITCH PAGE 1 OF 2MFG.# 5401086 - REV U 5/08 US Patent No. 6,945,509 General The Model RBVS is designed to monitor the fully open position of a ball valve installed in a sprinkler system. The unit will fi t on most ball valves installed on back-fl ow-preventers and alarm trim lines of dry, alarm, and deluge sprinkler valves. The switch operates if the ball valve handle is moved from the open position. However, the switch does not track the position of the handle or ball. When the ball valve handle is in the open position, a spring-loaded switch button will contact the valve handle. When the handle is moved from the open position, this switch button extends to the tripped position, and the RBVS contacts change state, thereby opening or closing a circuit. A cover tamper switch is available and is activated by the removal of the RBVS housing cover. If an attempt is made to remove the RBVS by the removal of the mounting brackets, the unit will be set into the tripped mode by this action. The RBVS can be mounted to the hex portion of the ball valve or back-fl ow- preventer or to the adjoining pipe via two clamps. The RBVS is shipped with two sets of mounting clamps to accommodate various pipe and valve sizes, refer to Table 1. An "L" shaped and offset bracket for mounting the switch enclosure and an extension bracket add to the mounting fl exibility of the RBVS. See "Typical Mounting Diagram" and "Installation and Operation" on following page. Testing The RBVS and its associated protective monitoring system should be tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). UL and cUL Listed, FM, CSFM Approved Dimensions: (including mounting clamps) Large Clamps: 6" L x 5" W x 5.2" H 15,2 cm L x 12,7 cm W x 13,2 cm H Small Clamps: 6" L x 4" W x 5.2" H 15,2 cm L x 10,2 cm W x 13,2 cm H Weight: With Large Clamps: 13.6 oz. (386,9 g.) With Small Clamps: 11.0 oz. (311,2 g.) Enclosure: Non-Corrosive Composite Material Environmental Limitations: • NEMA 4 rated enclosure when proper electrical fi ttings are used. (IP67) • Temperature range: -40°F to 150°F (-40°C to 65°C) • Not for use in hazardous locations Housing Cover Tamper: Activated by housing cover removal (Stock No. 1000035 only) Contact Ratings: SPDT Contacts: 10A at 125/250 VAC 2A at 30 VDC SPDT Cover Tamper: 3A at 250 VAC Fig.1 Internal Components Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com RBVS Stock No. 1000040 (w/o Cover Tamper) RBVS-T Stock No. 1000035 (w/Cover Tamper) Installation On Lever Handle (See Fig. 2) 1. Select clamps and clamping bolts based upon pipe/valve size, see Table 1. 2. Insert rubber clamp grippers into clamps, see Fig. 2. 3. Place one clamp on top of pipe/ball valve near the valve handle and insert clamping bolts through it.4. Place other clamp over clamping bolts from beneath the installation and thread hex nuts onto the clamping bolts, but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses). (NOTE: Some installations may require one of the mounting bolts to be inserted from the bottom of the brackets and then trimmed to allow the extension bracket to clear. See Fig. 4) 5. Attach extension bracket (if necessary to use for positioning) to top clamp using ¼-20 X ¾" Hex bolt and washer, but do not fully tighten. 6. Attach "L" bracket (RBVS switch enclosure is loosely attached to "L" bracket) to extension bracket using ¼-20 X ¾" Hex bolt and washer, but do not fully tighten. 7. Be sure ball valve is in the fully open position. 8. Slide loosely assembled RBVS switch enclosure to a position that permits the switch button to contact the valve handle approximately 1" from its inside end. See Fig. 1 for approximate location. Cut and remove the plastic coating from the ball valve handle to allow the RBVS switch button to contact (and be activated by) the metal of the handle. 9. Tighten clamping screws alternately to an eventual 30 in-lbs. (minimum) of torque. 10. Maintain position of switch enclosure over valve handle and secure bolt that holds the extension bracket to the clamping assembly. It may be necessary to close valve to access this bolt. 11. Position "L" bracket so that it contacts the back edge of the valve handle, and secure its bolt. It may be necessary to close valve to access this bolt. 12. With the actuator fully retracted, position RBVS switch enclosure to contact the valve handle squarely, see Fig. 1. 13. With RBVS switch enclosure held squarely in contact with valve handle, securely tighten the two tamper resistant screws on the backside of the enclosure. 14. Close and open the valve to verify operation. The actuator should easily retract when the valve handle is in the open position. 15. Fully open the valve. 16. Remove the cover and wire main switch and tamper switch if applicable. Carefully route tamper switch wires through strain relief channel in switch enclosure. Fully seat the wires into the bottom of the channel. See Fig. 1.17. Replace RBVS switch enclosure cover and securely tighten cover screw. PRINTED IN USA RBVS UNIVERSAL BALL VALVE SWITCH MFG.# 5401086 - REV U 5/08 PAGE 2 OF 2 OUTG O I N G INCO M I N G DWG# 923-3 Installation on Tee Handle (See Fig. 3)1. Select clamps and clamping bolts based upon pipe/valve size, see Table 1. 2. Insert rubber clamp grippers into clamps, See Fig. 3.3. Place one clamp on top of pipe/ball valve near the valve handle and insert clamping bolts through it.4. Place other clamp over clamping bolts from beneath the installation and thread hex nuts onto the clamping bolts, but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses). 5. Loosely attach "L" bracket to the "offset" bracket and "offset" bracket to the RBVS housing. 6. Be sure ball valve is in the fully open position.7. Slide loosely assembled RBVS switch enclosure to a position that permits the switch button to contact the valve handle approximately 1/2" from the end of the handle. Cut and remove the plastic coating from the ball valve handle to allow the RBVS switch button to contact (and be activated by) the metal of the handle. 8. Tighten clamping screws alternately and ¼-20 X ¾" bolt to 30 in-lbs. (minimum) of torque. 9. With the valve handle fully open, slide the RBVS housing down until the switch operates plus 1/8 inch. Tighten the screws holding the RBVS to the "offset" bracket.10. Remove the RBVS switch enclosure cover. 11. Close and open the valve to verify operation. The actuator should easily retract up when the valve handle is in the open position. 12. Fully open the valve.13. Wire main switch and tamper switch (if applicable). Carefully route tamper switch wires through strain relief channel in switch enclosure. Fully seat the wires into the bottom of the channel. See Fig. 1. 14. Replace RBVS switch enclosure cover and securely tighten cover screw. Fig. 3 Typical Electrical Connections Fig. 2 Typical Mounting Diagram Tamper Switch Connections Switch Terminal Connections, Clamping Plate Terminal Table 1 Clamp Sizing Fig. 4 SOME INSTALLATIONS MAY CAUSE INTERFERENCE BETWEEN MOUNTING BOLT AND OFFSET BRACKET. INSTALL BOLT FROM BOTTOM AND TRIM AS NEEDED TO CORRECT. RBVS PIPE DWG# 1086-6 Pipe Valve/SizeClampClamping Bolts 1/2" to 3/4" (12,5 to 19mm)Small10-32 x 2 1/2 1" to 2" (25 to 50mm)Large1/4-20 x 4" An uninsulated section of single conductor should not be looped around the terminal and serve as two seperate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. Features •One alarm appliance with (8) eight selective signals to provide superior sound penetration for various ambient and wall conditions with two field selectable sound output levels. •Code-3 Horn and Tone meet NFPA/ANSI/ISO temporal pattern for standard emergency evacuation signaling. •Audible and strobe can operate from a single signaling circuit. •Designed to meet or exceed NFPA/ANSI Standards and ADA Accessibility Guidelines. 110 VAC model does not meet ADA requirements. •Low current draw with low temperature compensation to reduce power consumption and wiring costs. •Low cost installation via standard electrical boxes. Attractive flush or surface mounting options available. Wheelock’s MT and MT Strobe Series Multitone Electronic Signals offer a choice of eight (8) nationally and internationally recognized alerting sounds: Horn, Bell, March Time Horn, Code-3 Tone, Code-3 Horn, Slow Whoop, Siren or Hi/Lo Tone. Wheelock’s Code-3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications without requiring additional coding means. With MT and MT Strobe Signals, one alarm appliance meets most of your signaling needs. Wheelock’s MT and MT Strobe Signals are UL Listed, FM, CSFM and NYMEA Approved. WHEELOCK SERIES MT AND MT STROBE MULTITONE ELECTRONIC SIGNALS *For outdoor installation use MTWP-2475W-FR with IOB-R backbox. **See next page for mounting options. PRINTED IN USA PAGE 1 OF 2MKT. #8850002 - REV H 2/03 Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com MT-24-1575W-FR SHOWN ledoM RF-W575121-TM )nroH/ebortS( 1290161.oNkcotS **snoitpOgnitnuoM R,P,O,M,L,F,E,D 42/21TM )nroH( 4190161.oNkcotS **snoitpOgnitnuoM R,P,O,M,L,F,E,D *RF-W5751-42-TM roodnI)nroH/ebortS( 5190161.oNkcotS **snoitpOgnitnuoM R,P,O,M,L,F,E,D RFV-HW-511-4TM )nroH/ebortS( 6120161.oNkcotS **snoitpOgnitnuoM R,O,N,K,J,E,D sgnitaRtnerruCdnaABd enoT )spmA(sgnitaRtnerruCegarevA sgnitaRtnarebreveRABd 464LUreP sgnitaRciohcenAABd CDV42@ CDV21@ CDV42@ CDV21@ CDV42dna21@ IH DTS IH DTS IH DTS IH DTS IH DTS nroH 830.0 420.0 590.0 910.0 29 78 09 77 99 39 lleB 910.0 210.0 030.0 010.0 68 08 58 96 29 78 nroHemiThcraM830.0 420.0 590.0 910.0 98 48 98 47 99 39 nroH3-edoC 830.0 420.0 590.0 910.0 88 38 88 37 99 39 enoT3-edoC 720.0 610.0 750.0 410.0 58 08 48 07 59 09 poohWwolS 740.0 520.0 590.0 420.0 09 98 98 57 99 49 neriS 430.0 220.0 870.0 910.0 98 48 98 57 89 39 oL/iH 020.0 310.0 240.0 110.0 68 18 68 17 39 88 WHEELOCK SERIES MT AND MT STROBE MULTITONE ELECTRONIC SIGNALS PRINTED IN USA PAGE 2 OF 2MKT. #8850002 - REV H 2/03 MOUNTING ACCESSORIES (D) 4" SQUARE, FLUSH (BO)(F) DOUBLE-GANG, FLUSH (BO) (J) BB BACKBOX (Order Code: 2830) Standard steel backbox with knockouts for interior surface mounting, concealed conduit mounting or semi-flush applications. It is painted to match the signal. (K) WBB WEATHER RESISTANT BACKBOX (Order Code: 2959) Sturdy die-cast housing, threaded conduit hole and knockout for outdoor applications. It is painted to match the signal. (L) ISP SURFACE ADAPTER (Order Code: 5306) Indoor use. (M) IOB BACKBOX (Order Code: 5046) For surface mounting MT products. (O) RP-R RETROFIT PLATE (Order Code: 5042) (R) SFP SEMI-FLUSH PLATE (Order Code: 2957) Stamped aluminum surface wall plate which mounts behind the basic unit and serves to cover recessed backboxes in semi-flush mounting applications. It is painted to match the signal. MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 4 4 4 4 MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 4 4 4 4 MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 4 4 4 4 MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 8 8 8 4 MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 8 8 8 4 (E) 4" SQUARE, DEEP, FLUSH (BO) MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 8 8 8 4 MAXIMUM NUMBER OF CONDUCTORS AWG. #18AWG. #16AWG. #14AWG. #12 4 4 4 4 MOUNTING NOTES CAUTION: The mounting options figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. Although the limits shown for each mounting option comply with the National Electrical code (NEC), Wheelock recommends use of the largest backbox option and the use of approved stranded field wires whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring. CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. 1.Mounting hardware for each mounting option is supplied. 2.Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. When extension rings are required, conduit should enter through the backbox, not the extension ring. Use Steel City #53151 (1-1/2" deep) or #53171 (2-1/8" deep) extension rings (as noted in the mounting options) or equivalent with the same cut-out area. 3.When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the appliance. 4.Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 5.Do not pass additional wires (used for other than the appliance) through the backbox. Such additional wires could result in insufficient wiring space for the appliance. Page 1 of 2 a company DOCUMENT #:REVISION: WXT-WXTP4/05 Model WXTP Water Thermal Expansion Tank SPECIFICATION SUBMITTAL SHEET FEATURES DIMENSIONS & WEIGHTS (do not include pkg.) MATERIALS APPLICATION ACCESSORIES STANDARDS COMPLIANCE Designed for installation on potable water lines between the backflow preventer or pressure reducing valve and the water heater to protect against water thermal expansion. When system pressure increases, water enters the tank’s bladder which expands into the pre-charged air chamber, keeping system pressure below the relief valve setting. y IAPMO® Listed y NSF® Listed Outer shellHigh Grade Steel CoatingsEpoxy finish (outer shell) ConnectionBrass (sizes: 8 thru 32) Stainless Steel (sizes: 50V thru 320V) Bladder Butyl Rubber (FDA approved) A B B C A C WXTP 50V-320VWXTP 8-32 BR4-water pressure reducing valve TP1100A-temperature & pressure relief valve P1000A-pressure relief valve 975XL-reduced pressure backflow preventer Sizes (liters): 8 18 32 50V 75V 120V 165V 320V (V = vertical, free-standing) Maximum working water pressure150 PSI End connections Threaded NPT ANSI B1.20.1 Precharge (adjustable)40 PSI 5 year warranty R UPC NSFR Certified to ANSI/NSF 61 NOTE: Model WXTP tanks are certified to NSF Standard 61 cold, but are suitable for temperatures up to 200°F. in.mmin.mm lbs.kg WXTP-8150 PSIG2.10.84 408 1/221611 1/22923/4" MNPT73.2 WXTP-18150 PSIG4.51.8 4010254153813/4" MNPT104.5 WXTP-32150 PSIG8.53.4 4012 1/231819 3/164873/4" MNPT156.8 WXTP-50V150 PSIG145.6 401640621 11/165511" FNPT3214.5 WXTP-75V150 PSIG208.0 401640628 13/167321" FNPT3917.7 WXTP-120V150 PSIG3212.8 402153327 13/167061" FNPT6027.2 WXTP-165V150 PSIG4417.6 402153336 3/16919 1 1/4" FNPT7232.7 WXTP-320V150 PSIG8534.0 402666044 7/161129 1 1/4" FNPT14063.4 TANK SPECIFICATIONS MODEL NUMBER MAXIMUM WORKING PRESSURE TOTAL VOLUME GALLON S ACCEPTANCE VOLUME WEIGHTSYSTEM CONNECTION HEIGHT DIMENSIONS DIAMETER FACTORY PRECHARGE (PSI) NOTE: RELIEF VALVE MUST BE SET AT 150 PSIG MAXIMUM Page 2 of 2 WILKINS a Zurn Company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) · Website: http://www.zurn.com SIZING CHART TYPICAL INSTALLATION Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted on the cold water supply and at least 18” from the cold water inlet to the heater. Note: If incoming water pressure is above 40 psi, the precharge pressure of the expansion tank should be adjusted to equal the incoming water pressure, not to exceed 80 psi. MODEL WXTP INSTALLATION MODEL WXTP INSTALLATION “V” SERIES T&P VALVE DIRECTION OF FLOW HOT WATER HEATER MODEL WXTP HOSE BIBB MODEL BR4 WATER PRESSUREREDUCING VALVE DRAIN MODEL 975XL T&P VALVE DIRECTION OF FLOW HOT WATER HEATER MODELWXTP HOSE BIBB MODEL BR4WATER PRESSUREREDUCING VALVE DRAIN MODEL 975XL The Water Thermal Expansion Tank shall be IAPMO® and NSF® Listed. The outer shell shall be high grade steel with exterior coating. The bladder shall be FDA approved butyl rubber and prevent water from contact with shell interior. The assembly shall incorporate a shrader valve for adjustable air precharge and a lead free bronze system connection. The Water Thermal Expansion Tank shall be a WILKINS Model WXTP. SPECIFICATIONS Based upon 100° F temperature rise (40° F to 140° F)X=multiple tanks required (contact your WILKINS Rep) Supply Pressure (psig)203040506080100120150175200 40 88888181818323232 50 88888181818323232 55 88888181818323232 60 888818181818323232 70 888818181818323232 80 888818181832323232 90 88818181832323250V50V 100 8818181832323250V50V50V 110 818181832323250V50V75V75V 120 181832323250V50V50V120V120V120V WATER HEATER CAPACITY (U.S. gal) Supply WATER HEATER CAPACITY (U.S. gal) Pressure (psig)2402602803003504004505006008001000 40 50V50V50V50V50V75V75V75V120V120V165V 50 50V50V50V50V50V75V75V75V120V120V165V 55 50V50V50V50V50V75V75V75V120V120V165V 60 50V50V50V50V50V75V75V75V120V120V165V 70 50V50V50V50V50V75V75V75V120V120V165V 80 50V50V50V50V75V75V75V120V120V165V165V 90 50V50V50V75V75V75V120V120V120V165V320V 100 75V75V75V75V120V120V120V165V165V320V320V 110 120V120V120V120V120V165V165V320V320V320VX 120 165V165V165V320V320V320V320V320VXXX DETAIL AND SUBMITTAL SHEETGUARDIAN FIRE EQUIPMENT, INC.MIAMI, FL Ph. 800.327.6584 • Fax 800.827.3869 Project/Location: 6000 Series - Flush Fire Dept. Inlet Connections Architect/Engineer: Date: Contractor: 31/2” or 41/8” Dia. Swivel Inlet Plug 21/2” or 3”Nipple(by others) Plate 7” 7” Swivel Inlet Plug 31/2” 31/2” or 41/8” Dia. 7” 21/2” or 3”Nipple(by others) Plate 6014/6015 11/2”Nipple (by others) Swivel Inlet Plug 3”43/8” Plate 6002 SwivelInlet 21/2” Nipple(by others) B A A B C Plate 31/2” Dia. 9” 23”D Plug 31/2” Appropriate Selectionoü 6016/6017 Used as auxiliary connections through which the fire department can pump water to supplement existing water supplies. Provides 250 GPM flow (mini- mum), per 21/2” inlet. Single - inlet connections incorporate a straight-thru, non-clappered de- sign with female NPT outlets. Two and three-way inlet connections feature brass bodies (angle or straight pattern), with integral drop-clapper inlets and female NPT outlets. Standard components, all connections: Female hose thread swivel inlets, plugs with chains and identification plate. Cast brass construction, standard. Two and Three-Way Connections Model No.OutletSizeClappersABCD 6024 Back4” x 21/2” x 21/2”2115/8”77/8”---75/8” 6025 Bottom4” x 21/2” x 21/2”2121/8”67/8”71/8”75/8” 6026 Top4” x 21/2” x 21/2”2121/8”67/8”71/8”75/8” 6027 Back6” x 21/2” x 21/2”2115/8”77/8”---75/8” 6028 Bottom6” x 21/2” x 21/2”2121/8”75/8”71/8”75/8” 6029Top6” x 21/2” x 21/2”2121/8”8”9”7” 6034 Back4” x 21/2” x 21/2” x 21/2”3173/8”61/8”---65/8” 6037 Back6” x 21/2” x 21/2” x 21/2”3173/8”61/8”---65/8” 6038 Bottom6” x 21/2” x 21/2” x 21/2”3173/8”75/8”71/8”65/8” 6039Top6” x 21/2” x 21/2” x 21/2”3173/8”75/8”71/8”65/8” Indentification Plate Lettering AUTO SPKR AUTO SPKR & STANDPIPE STANDPIPE DRY STANDPIPE ooooo Single Inlet Connections Model No.60026014601560166017 Outlet 11/2”21/2”3”21/2”3” Inlet 11/2”21/2”21/2”21/2”21/2” Plate 41/2” O.D.7” O.D.7” O.D.7” SQ7” SQ Indentification Plate Lettering: AUTO SPKR ooooo ooooo o o o o 6034-6039 SwivelInlet 21/2” Nipple(by others) B A A B C Plate 31/2” Dia. 9” 15” D 31/2”Plug 6024-6029 Optional Finish: o-C Rough Chrome Plated o-D Polished Chrome Plated -B Polished Brasso 31/2” Contact factory for current listings and approvals Threads: oNST oOther __________