HomeMy WebLinkAboutB10-0105Department of Community Development 5 South Frontage Road Vail, Colorado 81657 970-479-2138 FAX 970-479-2452 www.vailgov.com ______________________________________________________________________ PROJECT REVIEW COMMENTS DATE: TO: PERMIT APPLICATION #: B10-0105 PROJECT ADDRESS: 2399 N Frontage Road OCCUPANCY GROUP: B/ R-2 TYPE OF CONSTRUCTION: VB NUMBER OF STORIES: 2 BUILDING AREA: 15,300 ● Submit four complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. Special Inspection Agreement to be completed prior to permit issuance BUILDING DEPARTMENT COMMENTS Architectural Comments: Sheet A-2.0 Landscape plan to be coordinated with architectural plans Sheet A-2.2 Provide a door/ window schedule indicating on the architectural plans safety glazing and u value locations. Sheet A-2.8 Revise toilet paper dispenser location to comply with ANSI A117.1 2003 Provide accessible shower details at accessible toilet room to include maneuvering clearances per ANSI A117.1 2003 ed. Sheet A-4.1 Provide a detail showing thermal envelope and counter flashing. Referenced detail appears to be the wrong reference. Sheet A- 4.2 Provide R values on plans for purposes of inspection. Sheet A- 4.3 Thermal break appears on stair section B. Revise plans Sheet A4.7 Clearly Identify handrails to be on both sides of the stairs Sheet A-4.9 Indicate R-value of concrete wall Sheet A -6.2 Provide a detail of how windows and doors are to be counter flashed Structural Comments: Sheet S-1 Include statement that shop drawings are to be submitted to the Town of Vail for approval after reviewed and accepted by the engineer of record and prior to work being performed. Plumbing Comments: Sheet P-3.0 1. Indicate on plans the required vent terminations above roof per Town of Vail amendments Mechanical Comments: Clearly identify vent terminations above roof per Town of Vail amendments. Sheet M-3.2 1. Indicate on plans boilers to be 92% or better efficiency per Town of Vail amendments Electrical Comments: Sheet E2.1 and E3.1Arc-Fault Protection required in R-2 Occupancies per 2008 NEC 210.12 and/ or 210.18. Sheet E2.1 Upper level R-2 occupancy shall meet the receptacle requirements of 2008 NEC 210.52. Sheet E2.1 Tamper resistant receptacles required in R-2 Occupancies per 2008 NEC 406.11. PLANNING DEPARTMENT COMMENTS Denied pending PEC and DRB approval of Changes to Approved Plans addressing changes in development standards (setbacks, site coverage %, landscape area %, parking space locations, etc.) due to inaccurate land surveying. FIRE DEPARTMENT COMMENTS PUBLIC WORKS COMMENTS 1.Construction plans will be required to be submitted to CDOT in order to receive a Notice to proceed for all work within the ROW. 2. Provide all utility signature approvals for Building Permit set. 3. Provide a tree protection detail. 4. Show all the trees intended to be removed on the Demo Plan. 5. A striped cross walk is not necessary across the Fire exit driveway. 6. An ADA ramp (truncated domes ) is still required at the east side of the Fire exit driveway, even thought the walk is at grade. 7. A minimum 2’ asphalt patchback is required along the new curb and gutter, unless a clean cut is made and the asphalt can be used as a clean edge form. 8. A maximum of a 4’ wide patchback along the curb and gutter is aloud unless a full width overlay is provided. 9. The storm sewer crossing must have a perpendicular asphalt patch/cut with infrared seams. 10. All concrete removals must be sawcut at existing joints. 11. The proposed MSE wall “by others” along the south PL must be contained on site. A different type of wall that does not have geogrid lengths would be better suited for this location. Please provide final design for this wall. The final design is not included in the retaining wall and shoring plans. 12. Confirm that all storm sewer has a minimum 18” cover from the outside diameter of the pipe, specfically the one running West to East along the Frontage Rd. 13. Change the Frontage Rd storm sewer crossing to have a minimum slope of 1% as discussed. Update drainage report as necessary. 14. The storm sewer along the north side of the property enters into the east inlet at a tight angle and is subject to backflow from water that is anticipated from the Chamonix site. If this pipe is raised 18” this will not be an issue. This section of pipe should also be increased to have a minimum slope of 1%. 15. The inlet on the north side calls out a 3”/4”/6” pipe. There is no 4” pipe shown. 16. Check scale of Sanitary Sewer profile, the dimensions and invert call outs do not scale correctly. 17. Show proposed and existing utilities on Landscape plan. Do not plant trees over any utilities for future maintenance. A minimum of 3’ clear should be maintained from expected drip line of tree and the center of the utility. This may be reduced to 2’ for shallow dry utilities. These clearances are subject to utility agency review and approval. 18. The shoring and retaining walls submitted separately have the following comments; a. The shoring wall at the SW corner of the site impacts the existing waterline and possibly an existing private sanitary sewer service. The water line and sewer shall be potholed and shown on the cross sections. Additional cross section will need to be provided showing the water line is not impacted by the soil nails or wall. Suggested cross sections at 0', 10', 25', 40',65', 115'. (Assuming the south edge is 0', the existing section is cut at 90'). Sections should show location of water line and actual hillside slope based on existing/future topo. b. ERWSD will have to approve the proximity of the shoring wall to the waterline. c. The E-W wall along the south property line is noted as "Wall by others", who is designing this wall. The BP set also says "Wall by others".