HomeMy WebLinkAboutPRJ07-0534 LEGALPage I of2 Don Naill From: Sent: To: Gc: Subject: Keith Bartlett Ikbartlett@JGJOHNSON.c em] Thursday, October 30, 2008 1:47 pM Craig BrunE Don Naill; Sykes, David RE: 0705-Lower level fire rating.pdf - gd rbe Acrobat professional Attachments: 0705-Lower level fire rating.pdf Craig, Attached is our response to the corridor issue. Regarding the fire-resistance-rated corridor it is our recon rrcndation lo attempt to accomplish the design asillustrated with the attiached sketch. At the corridor areas in which you have already extended :i/8-inch type X gypsum board to the underside of thefloor deck at the room side of the corridor wall, provide a lr;r'rer of Sl8-incn fiie X gypsum wall board to theunderside of the floor deck at the corridor side of the corrir lrlr wall. At thos6'areaj,'ihe corridor will not require a separate fire-resistance-rated ceiling in the corridor. That oesign will allow the ceiiing to be any construction orassembly, not require a fire-resistance rating, and allow ur,rated access openings to the spacaabove the ceiling. At the corridor areas in which you have not or cannot exte rC 5/8-inch type X gypsum board to the underside ofthe floor deck at the room side of the conidor wall, we req rtnmend tnaf you ui6'tne design shown on the attachedsketch. ln that case, you are assuming the existing cor4dr rr wall is of orie-hour fire-resistive construction and aree)dending a separate one-hour ftre-resistive wall section, < f lset to the conidor side of the existing wall, to the underside of the floor deck. Atthe offuet, the new upper u irll overlaps the existing lower wall a d-istance of at least4 inches, providing one layer of Si8-inch type X gypsum br ,irrd to pr6tect the bottdm of the tack at the new wall,and.sealing.the joint between the new wail and the existinr 1 walt with a listed fire-resistant joint system. That design, again, will allow the ceiling to be any construction ,'assembly, not require a fire-rilsistance rating, and allow unrated access openings to the space above the cei ing. This design is btso the recommended solution forlocations atwhich a structural beam running parallel to the rrorridor wall iiterferes with framing the existing wall to the underside of the floor deck. In all cases the walls must extend to the underside of the r lristing two-hour fire-resistive floor assembly and arr lolnts and penetrations must be fire caulked. Please let me know if you have any questions or need any ildditional information. Thank you. Keith KEITH R BARTLETT Associat€ JC Johnson Architects 730 lTth Street Suite t 10 Denver, CO 80202 www.jgiohnson.com kbartlett@jgiohnson.com Fax: 303.892.7059 Studio: 303.892.7062 * * * * * * * * * * * * ,t * * r. * * * * * * * {r * * * * * * * * * * * i! * * * * * * * * * * * * * * * { !| * * * * * {. * * * * 10/30t2008 /. 1 LAYER OF TYPE'X' GYP BOARD, RE: GA FILE NO WP 1200 EXISTING 5 3/4' CONCRETE ON METAL DECK * FIRE CAULK ALL JOINTS AND PENETRATIONS IN CEILING rAL lE:rILE 340 1 5/8" MI STUDS, GA NO. WP BRING ryPE'X'GYP BOAD TIGHT TO METAL DECK, FIRE CAULK cooRrDoR FINISHED GYP BD CEILING 1 I.AYER OF TYPE X GYP BOARD, RE: GA FILE NO WP 1200 ATAREAS OF EXISTING BEAMS LOWER LEVEL COORIDOR Project # 0705 JG JoHNsot rArcHrrrcrs HOSPTTALTTY ll H0UStltG 0ESlCfl 730|tti St at Suna 110 Dh.. c.lo..do n202 ffijsiorib.m r! 303 39 70.0 ana. ,t a! t,.t SK.O1VAIL CASCADE RENOVATION RE: A01.01 DATE: 10129108 COPYRIGHT BY J G JOHNSON ARCHITECTS, P.C. (JGJA). ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE MODIFIED, 12-18-2008 Inspection Request Reporting Page 12 4:16 pm Vait co'- ciry ol - Requested Inspect Date: Friday, December 19, 2008' Sitd Address: 1300 WESTHAVEN DR VAIL VAIL CASCADE/ARIA SPA A/P,D lnformation Description: Reouested Insoection{s) llem:70 Activiw: 808-0075 TvDe: Const TvpC: Occuoair'cv: OWiier: L-O VAIL HOLDING INC Conlractor: WEll-Z COMPANY, lNC. OHE) A-coMM suu rgg, frcottl Status: ISSUED Insp Area: Phone: 303-860-6600 PORTE COCHERE, NEW POOL AND POOL DECK, MEETING ROOM ^"o",la: Enlered By: #rffil47 DGOLDEN K Item: 533 PLAN-TEMP. C/O Sequeslor: WEITZ COMPANY, lNC. Conimenls: AM reouested Assioned To: NPETERSON- Action: Requested Time: 08:00 AM- Phone: 379-0474 Enlered By: DGOLDEN K (rHE) Time Exp: tfHE) Time Exp: l:3o Item llem Item Item llem llem llem ITH CONDITION BY PLANNING 22 50 OU 11tO4tOB Comment: 12tO2tO8 Comment: 12t1',UOg Comment: BLDG-Misc. 10/31/08 Comment: 11n5t08 Comment: 1A0AO8 Commenl: Action: PA PARTIAL APPROVAL Action: NR NOT READY FOR INSPECTION llt*ty*@ ruttfu'P*,-'ilr/ (ffidf Inspection Historv 1O BLDG-FOOTING20 BLDG-Foundation/Steel21 PLAN-ILC Foundation Plan30 BLDG-Framino ** ADoroved "* 10/31/08 -lnspector: GCD ' Action: PA PARTIAL APPROVAL Commenl: PORTE COCHER UNDER FRAMING FOR CEILING. 12t11tog I : PA PARTIAL VI WEST END ( .S FOR THIS V\ Comment: Action: PA PARTIAL APPROVAL ROOM WEST END OF BREEZEWAY. SEE NOTES ON FRAMING. Action: Pl PARTIAL INSPECTION. COLUMNS. SOFFIT AND FACIA ON 8 LINE 8.5.Action: Pl PARTIAL INSPECTION FROM 13 TO 17 LINEAction: PA PARTIAL APPROVAL S LINE BETWEEN 7 AND 9. ,MN, SOFFIT AND FACIA ON 2 LINE BETWEEN Q AND S. REPT131.Run Id: 8855 N4EEA\I@@tD RESOURCES APPLIGATIONSorbEilrr GoNTROLS, lNC. Mr. Barry Monroe The Weitr Company 965 North Ten Mile Drive, Unit llA-1 P.O. Box 4536 Frisco. CO 80443 3220 E. 59TH STREET LONG BEACH, CA 90805 fel. (562\ 272-7231 Fa)( (562) 529-7513 HilTl"boil";3".1i"".".' RE: RADCO Evaluation of Three Custom Built Decorative Gas Fire Features at Vail Cascade Resort, Vail, CO. Dear Mr. Monroe: This letter is to advise you that RADCO, a testing Laboratory recognized by Inlernational Accreditation Service, Inc. (lAS), has conducted a field evaluation of the three custom built decorative gas fire features installed at the Vail Cascade Resort in Vail, CO. These decorative appliances were manufactured by Colombo Conslruc{ion Corp. of Brooklyn, NY, and include the 'upper branch wall', 'lower branch wall', and 'tree wall' fire fealures. The objective of the evaluation is to determine if the construction, installation, and performance of the unlisted equipment conforms to the applicable portions of the folloring nationally recognized codes and standards: . IAS 4 Outdoor Gas Fireplaces. 221.97 (Drafr) Outdoor Open-Flame Decorative Gas Appliances. The lntemalional Fuel Gas Code,2003 Edition. The lnlemaiional Mechanical Code,2003 Edition At this time, RADCO has completed our third party program, and has found these three fire features to be in compliance with the above referenced codes and standards, with the following exceptions: . The manufacturer is to provide manuals covering the recommended ongoing maintenance procedures for these fire features.. The 'upper branch wall' and 'lorer branch wall'fire features are to be provided with suitable housings for the appliance isolation ball valves and appliance regulators such that adequate means of access and weather protection are provided for these devices. As these outstanding issues periain to the ongoing maintenance of the equipment, F|IADCO recommends that permission to operate these fire features be granted on a lemporary basis. Once RADCO has confirmed that the above issues have been resolved, a formal report complete with the product and installation specifics, test procedures, test results, allowable limits, photographs, and any recommendations and/or requirements will be submitted for your review. Should you have any queslions or concerns, feel free to contiact us. Regards RADCOfu';#&*- Michael Hagan, P.E. Manager Gas Testing Lab & Field Services t*} rry LccnEDrrsD 12-17-2008 Inspection Request Reporting Page 30 5:03 pm veil- co - city ol - Requested Inspect Date: Thursday, December {8, 2008' Inspeclion Area: JRM Site AddreEs: 1300 WESTHAVEN DR VAIL VAIL CASCADE/ARIA SPA FROM FCU INSTRUCTIONS 1A11lOB Insriector: JGG ;CD Action: PA PARTIAL APPROVAL A NEW SNOWMELT. AND PORTE COCHER SUPPLY AND RETURN MAINS Action: NR NOT READY FOR INSPECTION Contractor: IIIJECH MECHANICAL TECHNOLOGIES Phone: (303) 650-4000 GROUP.INC Description: POOL DECK AND FRONT ENTRY MODS TO INCLUDE SNOWMELT/HX ,, - trl Reouesred lnspecrionts) 12 /Y - Cb 4,K Item: 390 MECH-Final Requestea Time: 11:30 AM : ) Requestor: MTECHMECHANICALTECHNOLOGIES Phone: (303)650-4000 -' GROUP.ll.r. , Assisned.ro: dijEtVbltx/J.p - /."#g':";i:;;;ffi rper.roTr\iFr5tfr LeAAN#-E'oRr Commenl: Coov of balance reDort received. date stamDed and filed. Comment: Snb,iv meli systems OK. Fiont entry, pool ddck, existing spa walkway to bike path all OK and in operalion. A/P/D Information Aclivitv: M08-0142 Tvoe: B-MECH Sub Tvpe: ACOM Consl TvD6: Occuoahbv: Use: Ow'rier: L-O VAIL HOLDING INC \r4^^f Inspection Historv llem: 200 MECH-Rouqhu11-Kouo 10to7tog Commenl: 10/08/08 Commenl: 11t12t08 Comment: Item: 310 Item: 315 Comment: MEDIUM PRESSItem: 320 MECH-Exhaust HoodsItem: 330 MECH-Supolv AirItem: 340 MECH-M|6i.' 'l1l11lOB lnspector: GCD 1A11nB Insriector: JGG Action: PAPARTIALAPPROVAL Comment: Ste'am line Bressure tested at 150 psi, OK. Insulalion over pipe is OK Condensale drain to be installed beTore final insDection.lE^C..ltHe^qting ^fJpproVed *MECH-Heatinq * AporoVed * 08/04/08 Insoector: GCD ' Action: CR CORRECTION REQUIRED Comment: UNDERGROUND RETURN FOR SNOWMELT HAS LEAK AT 90 RETEST REQD. UNDERGROUND SUPPLY FOR SNOWMELT 100osi TEST. 11124108 lnsoector: GCD Action: PA PARTIAL APPROVAL Cpmnent: POL DECK SNOWMELT SUPPLY AND RETURN AND SNOWMELT FIELD IOOPS| TEST PLMB-Gas Pioino *' Aooroved "*08/04/08 Insbector: 'GCD Action: PA PARTIAL APPROVAL Comment: UNDERGROUND GASPIPE TRACPIPE ll INSTALLED PER INSTALLATIN INSTRUCTIONS 1Ol23lOB lndoector: GCD Actionr PA PARTIAL APPROVAL Comment: TRACPIPE GASPIPE FROM POOL MECH ROOM TO PLANTER MANIFOLD AND FIRE FEATURES. 40osi TEST 1 1/03/08 Insoector: GCD Action: AP APPROVED Comment: MEDIUM PRESSURE 1 1/4" CSST FROM MAIN TO POOL EQUIP ROOM 40psi TEST. Status: ISSUED Insp Area: JRM ** Aooroved ** lD ' ' Action: DN DENIED ITE FOR INSPECTION REPT].31 Run Id: 8852 12-17-2008 Inspection Request Reporting Page 37 5:03 om Vail- CO'- City Ol - Requested Inspect Date: Thursday, December 18, 2008' Insoeclion Area: JRM Site Addrss: 1300 WESTHAVEN DR VAIL VAIL CASCADE/ARIA SPA A/P/D Information Activitv: P08-0071 Tvoe:ConstTvp6: Occuoahbv:Owrier: L-O VAIL HOLDING INC Contractor: TOTAL PLUMBING *"0*"*{ffir,Item: Requestor: Assiqned To:- Action: B-PLMB Sub Tgne: AcoM Description: VAIL CASCADE REMODEL: PLUMBING TO TWO (2) Requested Inspectionls) Time Exp: ' 1'g^/ Comment: Stalus: ISSUED Insp Area: JRM Phone: 303-39$7271 FLOOR SINKS AND 2" WATER TO POOL ROOM Entered By: 1 M; 303-3 SBEL lnspection Historv REPT131 Run Id: 8852 1t"J?#08 ln"p"$3ll F"duF:t nepo'nng p"g" ''o Requested Inspect Date: lrlday, December 19, 2008- lnspection Arca: Ctr Site Address: 1300 WESTHAVEN DR VAIL VAIL CASCADE/CHAPS & LIBRARY A/P/D Information Activitv: 808-0175 Tvoe: A-COMM Consl TvD6: Occuoahbv:Owrier: L-O VAIL HOLDING INC Contractor: WEITZ COMPANY, lNC. (THE) Descriotion: ADDITION TO CHAPS RESTAURANT Requested Insoection(s) ACOM Status: REVISIONlA Insp Area: CG Phone: 303-860€600 /z'fi-oY Reouested Time:' I l:00 AM' Phone: 379-0474 Entered By: DGOLDEN K Requested Time: 08:15 AM' Phone: 379-0474 Entered By: DGOLDEN K CR CORRECTION REQUIRED GYPSUM WRAP PER DETAILS 12 AND 16 ON IN KITCHEN. : PA PARTIAL APPROVAL : PA PARTIAL APPROVAL NEW ADDITION CEILING, Y APPLIED FIRE PROOFING TO BE APPLIED OHE) Time Exp: OHE) Time Exp: &@ Item: Requestor: Coniments: Assiqned To:- Action: 10 20 21 30 22 50 60 533 PLAN.TEMP, C/O WEITZ COMPANY. INC, AM requesled NPETERSON Wf,n^ Inspection Historv Item Item Item Item Item Item Item Comment: 't2t01tog Commenl: 12!02108 Comment: Item: 70 BLDG-Misc. 12t11t08 Comment: 12t12tO8 Inspector: Lathe on \ Item: 530 BLDG-Tem Requestor: WEITZ COMPATConiments: PM reouesled . AssignedTo: GDENCKLA A- Action: I *" Aooroved "*: GCD' Action: PA PARTIAL APPROVAL\ CEILING INSULATION APPR. "* Approved '": GCD ' Action: CR CORRECTION REQUIREO YERS OF THE CEILING PATCHES IN THE EXISTIN RESTARAUNT ARE REQUIRED : MODERATE CONTACT. THERE ARE LARGE GAPS AT SEAMS. REINSPECTION REPT131. Inspector; Action: PA PARTIAL APPROVAL OK for scratch coat. stucco.Action: PA PARTIAL APPROVAL Run Id: 8855 1z."16-2008 InJpection Request Reporting Page 13 4:26 pm Vail CO - City Of - Requ*ted Inspect Date: Wednesday, December 17, 2008' lnsoeclion Area: JRM Site Addr€ss: 1300 WESTHAVEN DR vAlL CHAPS RESTAURANT A/P/D lnformation Activitv: M08-0306 Tvpe: B-MECh Const TvD6: Occupahbv: Ow?ier: L-O VAIL HOLDING INC Contractor: FIRESIDE OUTFITTERS LLC Description: INSTALL GAS FIREPIACE. (GAS PIPING BY OTHERS). Reouested lnspectionl3) LLC Time Exp: sub rgoe: ACoM r"rflilS:: jt*t#to Phone: (970) 928-7501 *"0"""nd#,S-Ei Entered By: Item: Requestor: Conimenls: Assioned To:- Action: Insoection Historv Item: 200 MECH-Rouoh -12105109 Inspeclor: Comment:Item: 330 MECH-SuDply AirItem: 340 MECH-M|Si. ' -12104108 Inspector: Comment:Item: 390 MECH-Final Action: AP APPROVED Action: NR NOT READY FOR INSPECTION -fu *" ApDroved ** GCD' GCD REPT131 Run Id: 8846 12-18-2008 Inspection Request Reporting Page 35 4:16 pm vait_ co'- city ol - Requ$ted Inspect Dato: Friday, December 19, 2008- Insoeclion Arsa: JRtl ' sire Addrc$: 01ll gfsJIfyEN DR vArL A/P/D lnformation Activitv: M08-0321 Tvoe: B-MECH Sub Tvpe: ACOM Const Tvo6: Occuoah'cv: U'se:Ovrtier: L-O VAIL HOLDING INC Conlraclor: LEADING EDGE MECHANICAL Phone: 3037308494 DescTiption: INSTALL REFRIGERATIONPIPING FOR KITCHEN EOUIPMENT Reouested fmoection(s) ,/r"""/ /Z-Item: 315 PLMB-6r5.F|![tid.- RequestedTime: Requestor: LEADING EDGE MECFANICAL Phone: Comments: refrioerator oioino. earlv AMAssisnedro: GpExcKycD/) rime Exp: 3o Entered By: Status: ISSUED Insp Area: JRM A/t^t tL 11-0'6 /k 4. 0l:00 Pltl ( | 3037308494 -or 72G98Y 3421 DGOLDEN K bil,f.*t, c77v,r*) f,, l't4'!u'/ttt'<- H 1\,,u,/g r, y,",,a7+' /f; *- lt t, 4 Ufi<-, CJ)r-*p Or;/,-, %', ll^'4' )rt"^,,A - ,6"1w )- &. Jrt#* fng^^." l,;t otbi- /*{ /Yt'44/- Y"- ri t 4-''//tl-/tzr'*-' ,a REPT131 Run Id: 8855 December 16, 2008 Job Name: Materials Testing Summary,Vail Cascades lmprovements, Vail, Colorado Job Number: 08-6546 Weitz Construction 965 North Ten Mile Drive Frisco, Colorado 80443 Attn: Mr. Barry Monroe, This letter summarizes the materials testing services Ground Engineering Consultants, Inc. (GROUND) performed during the improvements to Vail Cascades Building located at 1300 Westhaven Drive in Vail, Colorado. The materials testing services were performed on a part{ime basis at times scheduled by the contractor from June 11 to December 12,2008. During construction, nuclear moisture density testing was periodically performed on the foundation soils and foundation backfill to determine percent compaction and in-place moisture content. ln addition, representatives our office observed reinforcing steel placement and performed periodic testing on the structural concrete placed for the structural elements. The structural concrete was tested to determine physical properties and compressive strength. A Certified Welding Inspector (CWl) was on-site to observe welded and bolted connections. These observations were performed at times scheduled by the contractor during erection of the structural steel. A representative of GROUND also observed the placement of sprayed fire-resistive materials (SFRM). The SFRM was periodically tested for thickness, adhesive strength and density. To the best of our knowledge, based on the test results, field observations, RFI's received and additional comments from the design team, it is our opinion that the materials tested for the foundation soils, structural concrete, reinforcing steel, structural steel and SFRM were in general accordance with project plans and specifications. The observations and materials testing as indicated above were performed periodically to provide data to the Owner, Contractor and Subcontractors to assist them in evaluating the general compliance of the tested materials and/or work with the contract trROTIIII n EN 6 I N EEF IN6 CO N5ULTFI NT5, INC, 'f 0lAAirpark Dr., Unit 9, PO Box 464, Gypsum, CO 81637 Phone (970) 524'0720 Fax (970) 524'0721 office Locations.' Englewood ' commerce city ' Loveland ' Granby www,groundeng.com ' GYPsum M nn ?4r1^ Evan E. Ku vail Cascades Building lmprovements documents at the times of our observation and testing. We did not supervise, direct or have any control over the Contractor's work. We were not responsible for the Contractor's means, methods, procedures, techniques, or sequences of construction, nor responsible for Contractor to carry out the work in accordance with the contract documents. lf you have any questions concerning this letter, please contact our office. Sincerely, Ground Engineering Consultants, Inc. Reviewed by Michael K. Wariner, P.E. Job No. 08-6546 GROUND Engineering Consultants, Inc.Page 2 ol 2 / NOTE: rHrS PERMIT MUST BE POSTED ON JOBSTIE AT ALL TIMES /.-':_'\ f\ \ | ta TWINtrliI&V Town of Vail, Community Oevetopmeni7ffiuth Frontage Road, Vail, Colorado 81657 p. 97 0 -47 9-21 39 f. 97 O.47 9.2452 i nspections. 97 0.47 9.21 49 MECHANICAL PERMIT ACOM JobAddrcss: 1300 WESTHAVEN DR VAILLocation.....: VAIL CASCADE Parcef No...: 210312100012 Mechanical Permit Fee-> S80.00 Will Call------> Plan Check---------> $20.00 Use Tax Fee---> OWNER L-O VAIL HOLDING INC 1211712008 C/O DELOITTE & TOUCHE LLP 555 17TH ST STE 3600 DENVER co 80202 APPLfCANT LEADING EDGE MECHANICAL 1211712008 Phone: 3037308494 PO BOX 2149 LITTLETON co 801612149 License: 415-M CONTRACTOR LEADING EDGE MECI-I,ANICAL'tzt 17 12008 Phone: 3037308494 PO BOX 2149 LITTLETON co 801612149 License: 415-M D,esciption: INSTALL REFRIGERATION PlPlNc FOR KITCHEN EQUTPMENT Valuation: $3.770.00 Permit #: M08-0321 Project #: PRJ07-0534 Status...: ISSUED Appfied.. : 1211712008 fssued. . : 12f1812008 Exoires. .: 06/16/2009 $4.00 Tolal Calculated Fees-->S0.00 Additional Fees-------> $104.00 $0.00 s104.00 $104.00 s0.00 Investigation-------> $0.00 TOTAL PERIUIIT FEE-.> TotalCalculated Fees-> S104.00 Payments-------> BALANCE DUE_--.> APPROVALS Item: 05100 BUILDING DEPARTMENT 1211712008 JLE Action: AP CONDITION OF APPROVAL Cond: 12 (BLDG,): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE. Cond:22 (BLDG.): COMBUSTION AIR lS REQUIRED PER CHAPTER 7 OF THE 2003 IMC AND SECTION 304 OF THE 2OO3 IFGC AS MODIFIED BY TOWN OF VAIL. Cond: 23 (BLDG.): BOIILER INSTALLATION MUST CONFORM TO MANUFACTURER'S INSTRUCTIONS AND CHAPTER 10 OF THE 2OO3 IMC, Cond: 25 (BLDG.): GAS APPLIANCES SHALL BE VENTED ACCORDING TO CHAPTER 5 OF THE 2003 IFGC. Cond: 29 (BLDG.): ACCESS TO MECHANICAL EQUIPMENT MUST COMPLY WITH CHAPTER 3 OF THE 2003 IMC AND CHAPTER 3 OF THE 2OO3 IFGC.. Cond: 3l (BLDG.): BOILERS SHALL BE MOUNTED ON FLOORS OF NONCOMBUSTIBLE CONST. UNLESS LISTED FOR MOUNTING ON COMBUSTIBLE FLOORING. Cond: 32 (BLDG.): PERMIT,PLANS AND CODE ANALYSIS MUST BE POSTED IN MECHANICAL ROOM PRIOR TO AN INSPECTION REQUEST, Cond: 30 (BLDG.): BOILER ROOMS SHALL BE EQUIPPPED WlTtl A FLOOR DRAIN OR OTHER APPROVED MEANS FOR DISPOSING OF LIQUID WASTE PER SECTION ,I004.6. mechcanicaLperm it_o41 908 REQUESTS FOR INSPECTI ignature of Ornqr or Conlrac{or/Zr OECLAMTIONS I hereby acknodedge that I have read this application, filled out in full the infomation required, completed an accurate plot plan, and state that all the infomation as required is conect. I agree to comply with the information and plot plan, to comply with all Town ordinances and stale la\fls, and to build this structure according to lhe towns zoning and subdivision codes, design review approved, Internalional Building and Residential Codes and other ordinances of the Town applicable thet€lo. E MADE TWENW-FOUR HOURS lN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROilI 8:0( /7- /6,-of mechcanicaLpermit_041 908 t**'l * * * * f,* * ** {.,1*'l * ** * * 'l ** ** *l'*ti **'} ********* {r* {* t {' {',t' {' * * *:t *,t 't 't * * * * * * * * * * *,t i * * * * * * '} t 't 't 'l* *t +* * * TOWNOFVAIL, COLORADO Statement****t*********li't*******{r*{r***tri**********'t*****+**t*t*+*+t t * * * * * * * + * * * * * * * * * * * * * * * * rt | * {.** ** * Statement Number: R080002385 Amount: 9L04.00 t2 / 1,8 / 20 081-l- : l-7 AM Pa)ment Method: Check 2263 IniE: DDG Notation: L,eading Edge $104.00 :r*'r*|I*i********|.*|*******:ti**|i**'3*|**************t rt**r*****|*************lt****************** ACCOUNT ITEM LIST: Account Code Current PmtE Permit. No: Parcel No: Site Address: L,ocation: This Pa)ment: M08- 0321 2103-121--0001-2 ].300 WESTHAVEN DR VAIL VAIIJ CASCADE Descript.ion Type: MECHANICAL PERMIT ToEal Fees: Total ALL Pmts : Balance : $104.00 $104.00 $0.00 MP PF 9f,c 00100003111r.00 00100003r.r.2300 00100003112800 MECHANICAL PERMIT FEES PI,AN CHECK FEES WILI, CA].,L TNSPECTION FEE 80.00 20.00 4.00 Dec 16 O8 O6:5?p tAtltauve l|.o r-'s'Lead i nE.. Edge I'lechan i ca I 303?38849?p.1 iffiiuttln rn oud Sa rd toadotr Flw. Vart rnd Grs line Stso rnd Locetlon Hcsi Lott crlculdiont Contncbr Infotrnrllon Comnnf Oclr|lql DelEdFficn ot UkE' CempanYAddce: smp6vdudo^rr*nW n*nanlalg.-...-- € Subdlvirirh: / aoo w6rl#wv'24ua Ynfb' vt&&' M.lllne Addl[t;lEll'$lJii *'rr up.aPutw'G- VltcttChl.: Nw( I Adltcn () Rrncdrl( ) &!g!ldtT llCtypEffine F|nDhcx XltfyPe PtlPocld FittFltc.3: sr.ApP0.'rca( )c$LoE3( )wtglEt!-l Bulldhtry?r: Sirql+Frmily( ) Jt+Femityl ) MsFP"ttilv( I#*"rii# Job Nrms OrnrrNmr A|thlbct ( ) Ordgn* ( t Ehttlccr I I Nama: Phone: F4 FMrll: LAfb/Af/fu,ltts*EwntJ' too uv ar-fi nl _*.Ln xotbl Contsc{P E.MdI; Ftlpcrry|l|lbflmtht Conttacbl Slgnro]l (ttqu?.O I ) LsgrtDccrtptoni wVW#- EollJltcruoll: Inbticr( 1 Ecuior(,,) Odu( ) BEC 1'7 ?ili1il TOWN OF VAIL 4to+ w Drb Rec.hIGd: TOWN OF VAIL FIRE DEPARTMENT 75 S, FRONTAGE ROAD VAIL, CO 81657 970-479-2135 OI^INER L-O VAIIJ HOLDING INC C/O DBLOITTE & TOUCHE LLP 555 r_7TH ST SrE 3600 DENVER co 80202 APPLICANT ACME AI,ARM COMPANY P.O. BOX 883 RIFLE (16 al4qn Li-cense : 154 -S CONTRACTOR ACME ALARM COMPANY NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES VAIL FIRE DEPARTMENT 1J/05/2OO8 1l/05/2008 Phone: 910-525-3398 II/05/2ooe Phone: 9'70-625-3398 3c6-6o-\5- 3pE -o \lS Permit #: A08-0100 -?tf'o1-6t31 Status...: ISSUED Applied..: ll/05/2008 lssued..: ll/ll/2008 Expires. .; 05/10/2009 ALARM PERMIT Job Address: 1300 WESTHAVEN DR VAIL Location.....: CHAPS RESTAURANT ParcefNo...: 210312100012 Project No : P.O. BOX 883 RIFLE co 81550 License : l-54 -S Desciption: INSTALL ALARM DEVICES FOR ADDITION Valuation: $6,000.00 'r *,* 't * *{'t*t*{++ +'t*t '}t*t++++'i+l**rt+* Electrical------> DR8 Fe€-----> Inv€stigation--> Will Call-----> TOTAL FEES.-> s0.00 So. oo s4s?.00 $4s7.00 $457.00 $4s7.00 Total Calculated Fees-> Additional Fee s-----> Total Permit Fee----> Payments-------------> BAIANCE DUE----> 'l * * * t l * + 'l l,t* a a* a + Approvals:rtem: 05600 FIRE DEPARTMENT I1/ 1-0 / 20og drhoades Action: AP Field verify l-ocat ion/ spac j-ng of devices. t****rt'tt*t*t'ttt*'it*'tttt*t'tt****ttt*+*+*++*,ta+*+,at:t*,t+11.+t*i++++,t,t*t***t**++'rl,l**tt*l.l l*'l++a+'l a,t* * t 'l 'l t 'l * * t * * * rt I * *l+ CONDITIONS OF APPROVAL ;ff;*;dj*i**'i**''t*f**+||'****'i'i'|{r'*+*r*r*'i"'|**r*r'*t*"*:}'}*1*****'i'|.*****' I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review approved, Intemational Building and Residential Codes and other ordinances of the Town applicable thereto. REQUESTS FOR INSPECTION SHALL BE MADE SEVENTY-TWO HOURS IN ADVANCE ONE AT 970-479-2252 FROM E:00 AM - 5 PM, SIGNA OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER a+a***+*ta****'lt**'l*l**f'l'l'll'*l************* * * * *** ********lil** * ***{.******i ** *********l * * * | * * TOWNOFVAIL. COLORADO Statement t*** * * tt+t*** ** * * * * * * * * * tt* * * * * * * * * * * * * * | * * ** * ** * * * * * * * * * * * r * 'r 'r * * * * * * * * * * * * *'r***i**i** * * * * * || Statenent Number: R080002164 Amount: $457.00 LL/LL/2OO8O9:11 AItl Paynent Method: Check AI,ARM COMPAT,IY Init: LC Notation: #93 84 /ACME Permit No: Parcel No: Site Address : L,ocation: Thj-s Payment:$4s7.00 A08-0100 1lzpe: AITARM PERMIT 2103 - 121- 0001- 2 13OO WESTHAVEN DR VAII, CHAPS RESTAURANT Total FeeE: Total A].IIJ Pmts : Balance: $4s7.00 $4s7.00 $0.00 ACCOIJNT ITEM LIST: Account Code BP 00100003111100 PF 00100003112300 FIRE AIJARM PERMIT FEES PI.AN CHECK FEES ** * * * * * * * * * * * * * * * * 'l t * 't * * * * *'1.* ** * *** * * * ** I't*'f * *****'l*'l Description Currenf Pmtss 225 . O0 232.OO APPIJGATIOT{ WILL NOT BE ACCEPTED IF INCOMPI."ETE OR Commercial &Fire Alarm shop drawings are req Ital and nust include information lisftd on the at time of 75 S. Frontage Rd. Vail, Colorado 81657 1#ri9ti%:rnlg!.tl-tH*i*r.yi:2* page of this form. Application will not be accepted without this information. CONTRACTOR INFORIIATION Fire Alarm @ntractor: l)r*, Alnr (n*,nn.,,, Tontn of Vail Reg. No.: ,54.S Conbct Person and Phone #3: (t;rr+,l4nriel< E-Maif Addresst r lt*d Arrnn rslr-trry.r-rarrt Fax#: q1O Lt.s (19-l(1 Contractor Signature: COMPLETE \ @nbct /Al :UATIOI{S FOR AtARItl PERMIT rI rD) \|t' 6ffi$vc . ... ' {' "lf,:ln rowN oF v4!t FireAlarm: $ GW T aE t/u-tza-60.ru or tt I'# Parcef # 2tOZrV t4,6,6 tL Jobgdrus: l3oo trJesllpverr D. Vall, & g.t661 SuMivision: o"Yl"tgTflJ$tL--SI: j-tb,$Fr*l[$*gj'.?;s*.,f ;U\stst364)Phonel Engineer:Address:Phonel 'ZeAl | &ttes in &tf M)tu, WorkClass: New() Addition0g Remodel(X Repair( ) Refo-fit( ) Other( ) @liilrtrroF^Lrre@rsF E!rO__Igt__) ******************ri********************FOR OFEICE US F:\cdev\FOR[$PERMm\FreFl{mJenn-12{545.doc Page 1 of 5'12/0s/200s NOTE: IHrS PERMIT MUST BE POSTED OA, JOBSITE AT ALL TIMES Town of Vail, Community Development, T5 Soulh Fronlage Road, Vail, Golorado 81657 p. 97 O.47 9.21 39, l. 97 0.47 9.24 52, in psection s 97 O.47 9.21 49 ffi Permit #: 808-0175 Project #: 'fi5 01 -o57 ISSUED 05not2008 09/02/2008 03/01/2009 ADD/ALT COMM BUILD PERMT JobAddress: 1300 WESTHAVEN DR VAIL Location......: VAIL CASCADE/CHAPS & LIBMRY ParcelNo....: 21031?100012 OWNER L-O VAIL HOLDING INC O5I2OI2OO8 C/O DELOITTE & TOUCHE LLP 555 17TH ST STE 3600 DENVER co 80202 APPLICANT WEITZ COMPANY, lNC. (THE) ost2ol290g Phone: 303-860€600 4725 S, MONACO STREET. STE lOO DENVER co 80237 License: 131-A CONTRACTOR WEITZ COMPANY, lNC. (THE) 05/20/2008 Phone: 303-860-6600 4725 S. MONACO STREET. STE lOO DENVER co 80237 License: 131-A Description: ADDITION TO CHAPS RESTAURANT Occupancy: mixed Typo Constructlon:lA Valuation: Total Sq Ft Addad: s1,150,000.00 1415 FEE SUMMARY Building Permit Fee--> $6,156.25 Will Cal Fee---------> $4.00P|ancheck----.-.--->$4'001.56UseTaxFee---..-----...-> Add'l Plan Check Hours-> $0.00 Restuaranl Plan Review--> $0.00Investigation-----_.._.t $0.00 Recreation Fee-._--.---> S353.75 TotatcatculatedFees-> s33.315.56 Total Calculated Fees-------> Additional Fees- TOTAL PERMIT FEES-._--> Paymonts--._-_- BALANCE DUE------------> $33,315.56 249,631.50 282,947.W 282,947.06 s0.00 DECLARATIONS I hereby acknowledge that I have read lhis applicetion, filled out in full the information required, completed an accurate plot plan, and state thal all the informalion as required is correc{. I agree lo comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure according to lhe towns zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town applicable thereto. REQUESTS FOR INSPECTION SHALL BE MADE TWENTY.FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROiI 8:00 AM - 4:00 PM. Print Name bld_a lt_constructionjermit_04 1 908 Permit#: 808-0175 APPROVALS as of 10-15-2008 Status: ISSUED Item: 05100 BUILDING DEPARTMENT 06/10/2008 cgunion Action: CR comments sent to applicant and architect F:\cdev\CHRIS\PERMIT.COMMENTS\B08-0'l 75\808-01 75. DOC 06/30/2008 cgunion Action: CR SECOND CHECK PLAN REVIEW COMMENTS SENT TO APPLICANT AND ARCHITECT FOR OUTSTANDING ITEMS FROM ORIGINAL PLAN REVIEW. ' F:\cdev\CHRIS\PERMIT.COMMENTS\808-0175\808-0lTS.secondcheckDOC.DOC 0711512004 cgunion Action: AP O9t22t2OO8 cgunion Action: CR REVISIONS DENIED, CORRECTIONS REOUIRED F:\cdev\CHRIS\PERMIT.COMMENTS\808-01 75\808-0'l 75.DOC 1OlO7l2O08 cgunion Action: AP APPROVED ADDITIONAL PLAN SET FOR THE INTERIOR WORKAT THE RESTAURANT SPACE. SEE PLAN SET DATED 9-30-08 Item: O54OO PLANNING DEPARTMENT 0612612008 npeterson Action: AP Approved plans dated June25,2008. Ref. DRB08-0081 approval. 09/09/2008 npeterson Action: AP Approved revised plans date stamped September 2, 2008. 1010712008 npeterson Action: AP Approved revised plans date stamped 9/30/08. 'No outdoor barapproved. Item: 05600 FIRE DEPARTMENT 07lO9l2OOB McGee Action: AP Subject to Bldg Dept review and approval of exit stairs. Fire alarm and fire sprinkler permits are required. Item: 05500 PUBLIC WORKS 06/2512008 cdelles Action: AP Contacted contractor regarding access and staging See the Conditions section of this Document for any that may apply. bld_a lt_construction_permit_04 1 908 Permit #: 808-0175 CONDITIONS OF APPROVAL as of 10-1 5-2008 Status: ISSUED Cond: 1 (FIRE): FIRE DEPARTMENT APPROVAL IS REQUIRED BEFORE ANY WORK CAN BE STARTED. Cond: 12 (BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE. Cond: CON0010149 Fire alarm and fire sprinkler permits are required. Cond: 14 (BLDG.):ALL PENETRATIONS lN WALLS, CEILINGS, AND FLOORS TO BE SEALED WITH AN APPROVED FIRE MATERIAL. Cond: 18 (BLDG.): STAIRWAYS ARE REQUIRED TO MEET SECTION R311.s OF THE 2003 rRC OR SECTTON 1009 0F THE 2003 tBC. Cond: 19 (BLDG.): GUARDS ARE REQUIRED TO MEET SECTION R312 OF THE 2003 tRc oR sEcTroN 1012 0F THE 2003 tBC. Cond:CON0010160 SPECIAL INSPECTION REPORTS ARE REQUIRED TO BE SUBMITTED FOR CONCRETE, SOILS, SPRAY APPLIED FIRE RESISTANT MATERIALS AND STEEL CONSTRUCTION. SEE STATEMENT OF SPECIAL INSPECTION FROM THE ARCHITECT. bld_alt_conskuctionJrermil_041 908 ***'tl'l * | * I I I | * **** t * t * * * 'l * l' * | | * * i * * | * * t I't * ** * * * * 't 't 't 't't {' 't 'l,t *** * 't I I * * 'l 'itf * t** 'l* 'l 'l'l * f * 'l f i *'l 1|.'r f 'tt'l TOWNOFVAIL, COLORADO Staternent f3** { fttlt+lllt+a*ta**{'*'} * ll*t*llt*ltll*$taa*aaaal * tl tli 'l * {. * * *lt * l:l' * *t'1.34* * * ***aaattat '}* * I tl Statement Nurber: R080001952 AmounE 3 $9,4?0.87 LO/L5/200810:50 A[l Palment Methodr Check Init: DDG Notation: Vfeitz 13543017 Permit No: 808- 0175 1)4IC: ADD,/ALT COMM BUII,D PERMT ACCOTJNT ITEM LIST: Account Code BP 00100003111100pF 00100003112300 uT 1.1000003105000 Description Parce1 No: 2103-121-0001-2 Sit,e Addregg : 13 0O l{ESfHA'rlEl{ DR VAIL Location: \IAIL CASCADE/CHAPS & IJIBRARY ThiE Palment 3 i9,470 .87 Total FeeE: 282,947 ,06 Total JIIJLf FtntE ! 292,947.OG Balance:$0.00 Current PntE 1,497.50 973.37 7, 000 . 00 BUII,DING PERMIT FEES PIA}I CHECK FEES USE TAX 4* Transmittal Form Revision Submiftals: 1. "Field Set" of approved plans MUST accompany revisions2. No further inspections will be performed until the revisions are approved3. Fees for reviewing revisions are $55.00 per hour (2 hour minimum), and & the permit is re-issued. are due upon issuance. Permit #(s) information applies to: bog - ot15 Attention: ( ) Revisions ("f nesponse to Correction Letter 4'attached copy of correction letter ( ) Deferred Submittal ( ) Other Project Address: , Description / List of Changes: ,too ltggllaVe/ thl{e :: -, ,- .- t ,. .. ,L2rlor'tLL P fL*P | (t'7-! ^',1)V?+2, [c 1,b51 Contact f nformation / ,\ I V {r.l s+].j ) Dconpany: ?oo'r^4 f1o/kd / Ivh+z Company Ph:€?q Aaf {f r, Fax: - e..lr"l N"-o' (^ \ ,,2------\ contact Ph: \'1'Io\ t|'t -oTTtl 'ce : e-r,tatl: brg.noano O W*iT, C;n Town of Vail Contractor Registration No: I? I -A X---Pnl t Signature (required) : .,.'! Revised ADDITIONAL Valuations (Labor & Materials) (DO NOT include original valuation) Building $ Plumbing $ Electrical $ Mechanical $ Fire Sorinkler/Alarm $ (Use additional sheet if necessary) Total $15oL. Date Received: Transmittal Form Revision Submiftals: 1. "Field Set" of approved plans MUST accompany revisions2. No further inspections will be performed until the revisions are approved & the permit is re-issued. 3. Fees for reviewing revisions are $55.00 per hour (2 hour minimum), and are due upon issuance. ,M,Revisions Pemit #(s) information applies to: (1b<- b n5 Project Address: hoo ug9*xual c)r,'-lt VFO.6 6v5a Contact tnformation Company: companyP6,Qtl'r GCS- un* P"r,Q<1.\ [ bb -4yo- conract Ph:(q1J "ul --q.\q a;D g-Vtrit Ut&t5-'l.tat.C\Vilt-ha i Town of Vail Contractor Registration ruo: b-\at-A I i,X fzwq d. rlarl't+ i Signature (required) i"ui""a ADDITIONAL Valuations (Labor & Maieriats) (DO NOT include original valuation) i Building $ Plumbing $ tSolA i :--""-,.-Mechanical $ _ Fire Sorinkler/Alarm $ I Date Total $ ( ) Response to Correction Letter _attached copy of correction letter 'D,{ Deferred Submittal 1 i otn", Description / List of Changes: (/qw+r< 5t(9 Q,rTO ?9Euo,u-{ (Use additional sheet if necessary) De@rfrnent of Co,rrmunity Det/elopment Euilding haty and Insrytion Seruic$ 75 South FronbgE R@d Vail, @lorado 81657 970479-2138 FAX 970479-2452 www.vailgov,com BUILDING SAFETY AND INSPECTION SERVICES PI.AN REVIEW COMMENTS: TO:Contractor/Aoolicant WeiE Company Barry Monroe Architect JG Johnson proj#0705 2 Chris Gunion, Building Plans Examiner 0e12212008 808-0175 L-O Vail Holdings 1300 Westhaven Drive R1 1A e,risting 1887 s.f. addition FAX/Email #: barry.monroe@weiE.com tstrohe@JGJOHNSON.com NUMBER OF PAGES: FROM: DATE: BUITDING PERMIT #: OWNERS NAME: SITE ADDRES!i: OCCUPANCYGROUP: TYPE OF CONSTRUCTION: NUMBER OF STORIES: BUILDING AREA: The documents submitted for this project have been reviewed for compliance with the 2003 International Building Code, 2003 International Residential Code, 2003 International Mechanical Code 2003 Intemational Fuel Gas Code 2003 International Plumbing Code, 2003 International Energy Conservation Code and 2005 National Electrical Code as modified and adopted by the Town of Vail. The following @mmenE will nd to be addres*d prior to isuance of a building permit: For procesing:o Please submit three complete sets of revised construction documents containino the rEuested information with all olan revision items clouded or otherwise identified. Paftial plan sets or loose olan sheets are not aceoted. r Please respond in writing to each comment by marking the attached list or creating a response letter. Indicate which olan sheet. detail. soecification. or calculation shows the requested information. Please send revisions to the attention of the phns examiner with the building oermit applicaUon number noted. o Please be sure to include on the resubmittal the engineer's or architecfs "wet" stamp. signature. reoisbation number and date on the cover oage of any structural calculations. all structural details and structural sheets of the olans. For commercial or multi-family proiects all sheets of the olans must be stamoed. Architectural Comments:1 Revise plans to provide a minimum of 2 exits from the larger Gore Creek Dining Room. The occupant load for this dining space o<ceeds 50. Please note fte exterior folding doors are not permitted for o<it purposes. IBC ch. 10 Sheet A00.02 indicates two exits from the larger dining space as well as the minimum distance requirements behreen the two exits.2 Revise egress plans, sheet 400.02 to show occupant loads, common path of egress travel and the total travel distance for the separate dining spaces as proposed. IBC ch. 10 Sheet 400.02 has been modified to show the requested information. 3 Revise wall types indicated as NM between the restaurant and the fireplace lobby atrium. These are required to be t hour fire barriers. IBC 404.5 The wall types on sheet A02.01 between the restaurant and the fireplace lobby atrium have been revised to be lHR rated walls. Refer to wall type lP on sheet A00.01. 4 Revise plans and door schedule for the Won Door to indicate the pre-determined egress opening width per section 3.2 of the Won Door ICC ES Report. Egress width is calculated per IBC table 1005.1. The door schedule has been revised to call out the required opening requirement for this exit. 3'-0" is the minimum requirement, door type D2 calls out for the door to be programmed to open to a distance of 4'-0". 5 Revise the door schedule to specify he correct Won Door model for a 60 minute fire rating. The door schedule has been revised to call out the required Won Door. Fireguard 60. 5 Include complete section and details for the new ceiling proposed in the existing dining area. Show existing and proposed 2 hour fire resistive floor/ceiling construction in this area. IBC ch. 6 The o<isting lower finished ceiling is going to be partially modified with the new design. The existing rated ceiling, which is above the finished ceiling, is not going to be disturbed and will remain as is. Detail C2A/A00,01 shows how these two ceiling's relate to each other. 7 Specify panic hardware on the door schedule for door 101. Panic hardware has been called out and will be installed on door 101. Refer to door schedule on sheet A10.01. 8 Include construction details for the new ramp and stair from Fireside Lounge area. Non-combustible construction is required. IBC ch. 6 The new ramp and stair in the Fireside Lounge will be constructed out of metal studs with a gypcrete topping slab. Refer to drawing 10/A02.03. Plumbinq Comments:9 Revise plumbing plans to show how piping in the new lower level bar area will be protected from freezing, IPC 305.5 If heat is being provided for this area, indicate on the mechanical plans or electrical plans. The lower level bar area has been removed from his scope of work. Electrical Comments: 10 Revise E-3 sheet where exit signs are shown at the Gore Creek Dining Room areas. Coordinate location of the exit openings with archihectural plans. Ra4sed drawing and added note to refer to Architectural drawing for exact locaUon of door opening. 11 Revise E-3 to indicate locations of emergency lighting for the dining areas. Shaded light shown on sheet E-3 are on emergency drruiL Mded note for Elecfical Gontactor to connect to emeryency circuiL Pleaie rcfer to the cover sheet ior information on rcsubmitting plans. In older to aYoid delays an issuance of a pernit pl'ease check all rcquested information is included with the rcsubmitbd plans. Please submit revised plans as a omplete set Partial plan rcsubmittals w:ll not be rwiewed. F :\cdev\CHRISIPERMIT.COMMEl'lTS\80&0175\808-0175. DOC ,rB RrpoRT'"ESR-I394 Rer'ssued August 1, 2007 This report is subject to re-examination in two years. IGC Evaluation Service, lnc. www.icc-es.orq BrFfEsslReghfEl Ofica . 5360 Worknan Ml Roed, Wtftkr, Cdfqria 90601 t (562) 6S9{tB Reglonal Ofrca r 900 f,ronb&* Road, Suite A Bimingham, Abbdna 35213 . (Z!5) 59998m RegkrEl Of6cs | 4051 Wesl Flossrnoor Road, Cqr|lly Ctb Hills, llllnds 60478 . f08) 7992305 DIVISION: 08---DOORS AND WINDOWS Seclion: 0830G.-Speclalty Doors Section: 08350-Folding Doors and crilles REPORT HOLDER: WON-DOOR CORPORATION 1865 SOUTH 3480 WEST SALT LAKE CITY, UTAH 84104 (801) 973-7500 www.wondoor.com timw@t ondoor.com EVALUATION SUBJECT: WON.DOOR FIREGUARD SERIES SINGLE€IDE AND CENTER BI.PARTING HORIZONTAL FOLDING FIRE DOOR ASSEMBLIES 1.0 EVALUATION SCOPE Compliance with the following codes: t 2O06 Intemational Building Code@ (lBC) . 1997 Unitorm Building Coden (UBC) Properties evaluated: r Fire resistance . Smoke and draft control r Means of egress 2.0 usES The Won-Door FheGuard series single-side and center bi- parting horizontal folding fire door assemblies are used as opening prolection in fire-resistance-rated wall assemblies, as smoke- and draft-control door assemblies. and as means of egress ooors. 3.0 DESCRIPTION 3.1 Won-Door Firecuard Series Horizontal Folding Fire Door Assemblles: Won-Door Firecuard FG-20, -60, -90, and -180 series single- side and center bi-parting horizontal folding fire door assemblies consist of two independently suspended and parallel steel curtains separated by a cavily. An exlruded melal post connects lo and closes offlhe movable end of the door. A gasket of polyvinyl chloride material is riveted along lhe lop and bottom of the door for smoke and draft control. Door construction is similar for all models, except lhat the cavity of doors with the suffix TR is filled with an 8 pcf (64 kg/m3) ceramic fiber liner and the construction of the surrounding assembly, including the pockets, header, and strike wall, is such as to meet the hourly fire-resistance rating reouiremenls. 3.2 Operation: The poweroperating system includes a controller, emergency battery power supply and drive motor assembly. The controller is programmed to automatically move the door to a closed and lalched posilion upon sensing a fire condition. The door assemblies include a manually activated operaling device that allows the doors to open to a predesignated minimum opening width within 10 seconds for egress, afler which the doors automatically close and seal. The predesignated minimum opening width must be approved by the code official. The power operating system includes limit conbols and sensors that detect and control the door position at all times. Logic circuitry in the conlrol unit prevents the door from opening when heal sensors detect a high-temperature (fire) condition on the olher side of the door. Low-vollage battery emergency conditions of the integrated standby poi/er supply cause the fire door to close and seal and signal a low voltage (or low cunenl) alarm condilion. 3.3 Fire-resistance Rating: The numerical designation of the Won-Door FireGuard door assembly conesponds tothe fire-resistance rating in minutes as determined in accordance with UL 108, NFPA 252, and UBc standard 7-2. The Firecuard FG-20S has a 2o-minute fire-resistance rating; the Firecuard FG-60 and FG-60TR have one-hour fire-resistance ralings; the Firecuard FG-90 and FG-9OTR have 1l/.-hour fire-resislance ratings; and lhe Firecuard FG-180 and FG-180TR have three-hour fire- resistive ratings. 3.4 Smoke and Draft Control Assemblies: The Won-Door FireGuard single-side and center bi-parting horizontal fold ing fire door assemblies comply as smoke- and draft-control assemblies in accordance with IBC Sec{ion 715.4.3 and UBC Standard 7-2,Panll. 3.5 OpeningProteciion: 3.5.1 IBC: The Won-Door Firecuard FG-60, Firecuard FG- 90 and Firecuard FG-1 80 door assemblies are recognized for use in fire walls in accordance with IBC Section 705.8, for use in fire barrier walls in accordance with IBC Section 706.7. for use in fire oartition walls in accordance with IBC Section 708.6, for use in smoke banier walls in accordance with IBC Section 709.5, and for use in smoke parlition walls in accordance with IBC Section 710.5. The Won-Door Firecuard FG-60TR, FireGuard FG-goTR and FireGuard FG- 180TR may be used in accordance wiih IBC Section 715.4.4 where maximum transmitted lemperalure is required.' 3.5.2 UBC: The Won-Door FireGuard FG-9OTR and FG- 180TR door systems are recognized for use in up to 50 percenl of the wall length, in each story, of area separation walls in accordance wilh UBC Section 504.6.2, provided the building is protected throughout by an approved sprinkler system complying with Chapter I of the UBC, the door is .S RgpOatS- are nol lo be co|rttn ed ot repres.nling aesthetic, or any other attribtt.r not tpcciJicall! oddretsed, nor are they to bc construed at an endorselhe ofhe rubiect oflhe reporl ora recommendationlor iE use. Therc is no worrantf b! ICC Evallalion Senice, lnc., etpress or implied, os to any .finding or olher natter i4 lhis reporr, or ar rc any product co\crcd by the reporl. Copydght @ 2007 (@ Page 1 ol2 Page 2 oI 2 ESR-1394 activated by an approved smoke detector when the opening exceeds 25 percent of the lengrth of the area separation wall, and each installation is approved by the building official having jurisdiction. The Fire-Guard FG-90TR door system is used in area separation walls of two-hour fire-resistive construction, and the Firecuard 180TR door system is usedin area separation walls of four-hour tire-resistive c,onstruction. 3.6 Means of Egress: 3.6.1 IBC: The Won-Door Firecuard door syslems are recognized for use in a means of egress system in acmrdance with IBC Section 1008.1.3.3 in any occupancy other than Group H. 3.6.2 UBC: The Won-Door Firecuard door systems comply with the special door requirements of Section 1003.3.1.2, Exception 2, of the UBC. 4.0 INSTALLATION 4.'t General: The Won-Door FireGuard Series horizontal folding fire door assemblies must be installed in accordance with applicable code requirements for the characler and location of the wall in which they are silualed. The Firecuard door assemblies are designed to be installed in openings having a finished width of 12 feet (3658 mm) and a finished height of 10 feet (3048 mm), unless installed underoversized door provisions. The FireGuard doors and frames musl be installed in accordance with the manufactureds published instructions and this evaluation reoort. Where there is a conflict between the two, this reporl governs. 4.1.1 IBC: Inslallation of the door systems, including the frame, closing and release deMces, and anchorage musl be in accordance with NFPA 80, as noted in Sections 715.4, 715.4.7.2, and 1008.1.3.3 of the lBC, as applicable. 4.1.2 UBC: Installalion of the door systems, including the frame, closing and release devices, and anchorage must be in accordance with their listing, as noted in Seclion 713.4 of the UBC. 4.2 Oversized Doors: Where a fire-resistance raling is required, doors wilh a length exceeding 12 feet (3658 mm) or a heighl exceeding 10 feet (3048 mm) may be installed when approved by the code official. A cerlificate of inspeclion hom an approved testing agency must be furnished as noted in Section 715.4.5.2 ot the IBC or Seclion 713.3 of the UBC, as applicable. 4.3 Smoke- and Draft-cont.ol Door Assembly: lnstallation instructions indicating lhe proper method of installing the Won-Door FireGuard smoke-and draft-control door assembly must be attached to, or packaged with, each assembly. The inslallalion instructions will cover the size, design, and construction of the door and frame assembly for specific air leakage rates. 5.0 CONDITIONS OF USE The Won-Door FireGuard FG-20, -60, -90, and -180 series single-side and center bi-parting horizontal folding fire door'assemblies described in this report comply wilh, or are suitable altematives lo what is specified in, those codes listed in Section 1 .0 of this report, subject to the following conditions: 5.1 The door assemblies must be installed in accordance with the manufaciurer's published installation instructions, the fire door lisling, and this report. Where a conflict exisls, this report governs. 5.2 Firecuard Door Assemblies are fabricated in Salt Lake City, Utah, under a quality control program with inspections by Enterprise Engineering (AA-617). 6.0 EVIDENCE SUBMITTED 6.1 Reoorts of tests in accordance with NFPA 252; NFPA 80: UL 108: UL 1784; UBC Standard 7-2, Part l; UBC Standard 7-2,Pafl ll; and UBC Standard 7-8. 6.2 A quality control manual. 7.0 IDENTIFICATION The won-Door FireGuard door assemblies and aulomatic closing devices bear a permanently affixed label with the Won-Door Corporation name, lhe name of the inspection agency (Enterprise Engineering), and lhe fire-resistance ralings from UndeMriters Laboratories Inc. The labels for the FireGuard TR Series doors also include lhe temperature fise developed on the u nefposed surface ofthe door afterlhe first 30 minules of fire exposure [450"F (232'C)]. The labels for the Firecuard doors musl also specify the evaluation report number (ESR-1394), and must comply with NFPA 80. All labels must be applied at the factory or other localion where fabricalion and assembly are performed. Won-Door FireGuard smoke- and draft-control door assemblies complying with UL 1784 must be labeled as such, and must show the letler 'S" on the fire rating label of the door. This marking musl indicate that the door and frame assembly are in compliance when listed or labeled gasketing is also installed. Jef GoMcheck software version 3.5.3 t..YJ Envelope Compliance Gertificate 90.1 (2001) Standard Report Dab: 0eO5/08 Data filenamg: C:\Documsnb srd Ssfrlngsvoy\Local S€ttings\Temporary lnt€mol FIo3\OLK59U6O100 Vall Cascade Dlnhg Room - lE@ calcs under ASHRAE,CTk Sectlon {: Project Informatlon Projecl Type: Now Con trucilon ProJ.ct TiU6 : Conslruc{ion Sib:O*n"74gent Sectlon 2: General Informatlon Buildlng Locatlon (bi w€atlor data): Vall, Cob.ado Hefng D€gr.o Days (bm 65 deg[s6 D: 9l4t CoollrB D€grF Dqs (b€r€ 5{, d€gr€6s F): 1102 Bulldng Type br Envelop€ R€quiEmonts: o,n{..ld.ntlrl AcilvltyType(r) Fbo. At€. lbpfily and F6d ServlceFamily Resburent Diniry Ane 3534 Cornmofl Sp6ce TyDoeFood Pr€paratdl 58.1 H6piblity and Food Servlce:8ar Lounge/Lelsure Dinlqg Ars. 1250 Common Spaco TypcsFood Preparaion t 55 Sectlon 3: Requiromentg Gheckllst Doslgn6rrcontractof: Jon Erooks Arddbctml Ens[needng Dad$r G]oup 19m Waz6 Sbo6t Sulb 255 Dsnv.r, CO 8020tt 30+290{m4 Cllmate€peclfl c Roqulrerncnts: componant l{..narDrrcrlptlon Grors A]!r Cevlg . ConL Proporod Audgf,t or P.rllt|.t . R-Vrlua R-V8|l| U+.cfor U.F-la (r) SudgEt Uhch'r e|s usod br 8oftrl€l€ be8elln€ cabulsllons ONLY, fid al€ not oodo ]€quirtnents. lnsulatlon: E 1. Op€ntlorvn a pour€d looGo-fill lnsilatlon has not b€on used ln attb rwf cpeces wfi c6lltq Elope gr€sbroEn 3 in 12. E 2. Wh€levtr vonb ocqr, thoy alo bamd to dofiec'l Incdnlng alr sbo\re lho In€ulaton. O 3. R€c€ss.d llghb, equhm€r and ducb ar€ nct effec'ting Insulatlon thlcl(nesD. E 4. l{o .oot Inqrhton lc lnBblled m a alsp€rd€d c€lllng wih rsnovabb odling p.nsb g 5, All exb|br lrsulafon h aolrer€d with P|o@iye nEbrbl 0 6. CsAo and loading dod( doors aro €qulppod wtfi woath8r s6alt. Fenestratlon and Doort: g 7, Wndom ad slryfighb .rc labeled and codfrod by the rEnufac'lrrtr for U-facbr and SHGC. p 8. Flxed wln<lors and skyllghb unlab€led by th6 manuhdur€r h6ro b€en slte leHed uslng he default U-facior and SHGC, Proj€d Ti!b:R.port deb: 09/0t08 Data ilonarn€: C:Docrmentr .nd S€tfngs\ro)ALocal Scdngs\TefiForary Intari€t Flbr\OLK5S180100 Vall Casced€ DLing RooB - IECC calcc urdsr AgHRAE,cd( Pag. 1 ot e E 9. Ofilr unlab€bd wrfcal fenostraton, opsraue and frxod, thet ar! unlabolod by tho manuhctrrcr haw bocn sito hH€d u3ing tha dofault l..Lhcbr and SHGC. tlo c|€d[ het b€€n {ivan for met6l treniEs wllh th€rmal btaak3, lor$6rdsslvity coatngs, gne fitngs, c ir}Elledng sp.cEr3 Air Leakage and Componont Grtl0calboi e l0.A[ Jolnte End p€fEtrdlms a]6 caJlke4 gad(ebd. n€€f|or-rblpp€d, or olhorwk !.#. E 1l.Wndow8, dooE. and Cqllghb c€rtfiod r modryL*e0rrrybrnr E l2.Componont R-valuea E U-bcb.r labded as cedflod. E l3.Bulldng €ntsarrc. doo6 haw e wstbule and squlpp.d trvnt doslng dorrlcar. Excap/do/|,s: Buldirq! l€ss lhan bur slofts above grad€. Eulldlng onEancas wlh rsrrDlvlng doo.s. D@r! hat oFn dlr€cdy from a epace locl thsn 3000 sq. lL ln d€a. E l4.Insula0on Insbll€d aocodhg b manufaduB/s Insuuc0on3, in substar alcont!.iwlth tho 6uihce belng lmubtad, ard Ina mannerthat ad fl€slho rel€d R-vafuo wft|qjt compGsslng tho lnruhtlon. hdod Tlt6: Rc9ort dsb: @/0t08 oeta lllonaflio: C:\Doflm€nls fid Sefinglvolilocel Settirgs\Tqnporary Inhmel Fllee\OLK68\1601 00 Vail Caecado Dlnlng Room - IECC calc6 under ASHRAE.Cd( PagB 2 ot I itt coMcheck software version 3.5.3 t V I Interior Lighting and PowerlJ-l Compliance Gertificate 90.1 (2001) Standard ReDort Date; 0gio500 Clata filonamo: CtDocuments and SetlingsVoy\Local Setdngs\Temporery Iniomet F|I6\OLK59U60100 VaU Cascade Dining Room - IECC calca urd€r ASHRAE.Cd( Section 1: Prolect Information PrQect Type: Nou Gonrtruc-tlon Projsc{ Titl€ : Construction Siib: Own€r/Agent Deslgner/Contractor: Jon Brooks Archtteclural Engin€odng Daslgn Grcup 1$0 Wazoo Ske€t Sufte 256 3#;T6S.:o'o' Section 2: General Information Bulldlng Use Ooscrlptlon b!,r Actlylty lyp. Acllvl$ Ilrp.l|! Flor ArB. HoEplblity and Food Servico:Family Restaurant Olnir€ Ar€€ 3531 Commm Spa Typos:Food Pr€peratm 58a Hcpitallty '|d Food Servlca:8r Lo(Jnge/Lobul€ t)|nlng Ar€a 125{, Common Spaco Typ€s:Food PFpar8lion 156 Sectlon 3: Requlrcments Checklist lnt€rior Llghtlng: O 1. Totel propcad yvalts mud be l€ls than or equal to lotal allorrr€d wslte Allowd lv.tt3 P.opo$d W.tt Compller 15749 15376 YES Exterlor Lightlng: E 2. Mlnimum encacy of 60 lumon/hElt fur lamps gr€ater th8n 10O/Y. tr 3, Lighuno pou\tor fu. canoplot €ntran€8, and oxlt8 me€tr tho followlng crttoda (lrad&otrB allo\r/€d ammg lh6!€ tpdicalions): (l) Llght'lg po$l8 br froe-Etandlng canopy arEs or butldlng onbarrss wllh canopl€s is l€ss lhd| or €qu€l b 3 watF por squaE lbot. (ii) LlgtrthrS poutgr br bulldlng srfenes withdrt a campy b lese than or equal b 33 watts p€. lino€r bot of door wldth. (lll) LbhffE porr/sr fu bulldlng ertr b lo53 than or oqu6l b 20 ryatts p€r tlnear bot of e)dl door wldth. g 4. tightng potysr for buiHirp facades ir hss lhsn or equal b 0.25 watB par squsr. foot ol th€ llluflrhalrd ar€a. Exc:spllotp: Contmll€d by motlon sanror, slgnal or advsrtslng slgnaga, hlghllgh{ng tbatur€! of hisbrlc mdrumonb ard bulldhgF, or roqulrod for sabty r seqJn.ty. Gontrole, 9witchlng, and Wrlng: E 5. Indspondont manuald occupsrrl s.rtslng contrclr br €ach spacc (rsnob $iyibh with indlcabr allo €d for solbty or soqJrfry). E 0. Auiomdlo shubfr control for lightlng In >5000 sq.fr buildlng8 by tme-of.day devlc., occupant r€nsor, or cfflgr automadc control. Exaptbn; 24 hour Wratbn lighdng. Pnclcct Tlte: R€port datB: 09,05,'08 Oete il€name: C:\Doc m€ntr end Soningr\ro$Looal Sotlings\Ter?orry tnbmt Flhs\OLK39U6O100 Vall Cascad€ Dinir€ Room - IECC calcs under ASHRAE.Gd( PrgE 3 oto E 7. Marler 8wibh al sntry b hoteltmtol guost room. [] 8. Sopaab contol dovico for dl8play/sccont llghdng, cale ligMng, bsk ligh(ng, nonvisual lgMng, llghting fDr sale, and dq|Dnsfatdl [gt'tinS. U 9. Phobcoluasbonorlcal dme sv/ltch on dedof gttB. Exc€fflu7a: covsFd \r€hlde ontrancdedt ereas requldng lightng for $af€ty, s€cu ty and 6y€ adaptadon. O lo.Tsdem wl]sd orFlamp and thrco+mp ballae{ed tumhdres (ltlb slngblamp ba as!3r, Ee€Nons: Electomic hlgh-fEqu€ncy ballasb; LumhaftE! nol on s€mo snltdr: Roce6€€d fumlnah€! 10 fr. apa or surfaco/pendant not con[nuous; Lumlnales on ameryency ckwlts, Voltage Drop: O I l. Feadsr oo.duc{q! hav€ boan deslgrEd tor a maximum ,roltag6 drcp d 2 porcont. E 12,Brancj| ol|lull oonducbG hsv6 b€on deslgnod br a madmum voltEgo drop of 3 p€rcenl. Section 4: Compllanco Stat€ment Compratrce Slalbnont' Tho prcpGsd llghdng da3ign r€p|€sardod In lhb documor i! consistent wilh lha buildlng dsm, spedficalbns and other calcrrFdon! submitbd witr tHs pemlt appllcs[d. The propossd llghtlng system h6 beon dosignod b m€et lha 90.1 (2001) Stsndad In @Mdrad(Volsbn 35.3 srd to conply wl|h the ]rqulrsmg|b In 0|o R€qull€rffib Ch€cHisl. Sectlon 5: Post Gonstruction Compliance Statement Record Orewlnge and Operatlng and llaintenance l[anuals: E l. Constuc{on dooJm€nb wllh racod drawlng! dd op€ralng and mainbnsnco mfiudE prwid€d lo lh€ ovrna.. LlgMng oGlgnor d Conbacbr NanF Shnatura Dob Prctecl Tlte:R€port dab: 09/05/08 Dats filonam€: C:\Dodrmsnts and Selongs\lol^Local Seltlngs\Tompors.y Intsmst Filss\OLK59\'160100 Vsll Cascade Olnlng Room - IECC c€lcs urder ASHRAE.cck Pagf, 4 of 6 COMcfieck Software Version 3.5.3 Interior Lighting Application Worksheet 90.1 (2001) Standard Roport Date: Data filgname: C:\Documonts and S€flingsvoyLocsl Ssttngs\T€mpomry Intsm.t FitostoLK5g\'l00100 Vall Cascde Dinlng Room - IECC calcs undtr ASHME.Gd( Sectlon l: Allowed Lightlng Power Galculatlon A&t cabgory g Floo. Atta 1fl2) c Allo!v.d Wrttr , fi2 D Allow.dHtr (BrG) tloopllalily end Food S6.vlc.:Family RoEbrrar Dining &6s Allowanc€: Dscoradv€ Appoaranco / Fir, lD: T1 Common Spaca Typ6:Food Pr€pcatiort Alolvancs: Docorelhra App€arance / Fh. lD: L-04 Allos|ancs: Oocoraliv€ Appearance / Fh. lD: \ItP Hosplta[ty and Food S6rvlcs:Bar Loungo/Lolsuro Dlnlng Ar€e Alorvance: Dacoratvo App€oranca / Flx. lD: l{o 3534 1754(al 5&f 5E4(e) 10(a) 1250 150(a' 2.2 1 22 I 1 1.2 1 n75 1754(b) 1286 s&flb) 1o(bl 't 500 7m&l Totd Albwed Watts = (r) Area clalm€d mugt nol qxcoad lho lllumlnatGd a]€a pamltbd br hb allowsnca tyF, (b) Allorflance b (B x C) or he sctual $/Ettag. of ths lLlur€s gtwn In Sodion 2, wtrlchsv€r b l€$. Section 2: Proposed Llghtlng Power Calculatlon A Fmr,tt D: D.|crlplbn / t mp,W.tt!g. P.r t mpf Bdb.t BCtrmpd : d FbduE Flxtur€ o Flxtura W.tt E (GxD) H6pitdity ard Food Sarvlo.:F6mlv Rsstauranl Dining Area (3534 dq.lL) Incardescana e Ol: Olh€r Halogen 3: D2: O,lhsr l-lalogon 4: 03: Olh€l Incandescar 3: L{1: Incerdosc€nt 00\iY Incandelcenl 4: L{2: lncand$c€nt 40W lncandoscsnl 6: L-03: Ofior Hdog€n 6: Cl: Oth€t Hdogen 7: C2: Othe. Incand€scont 7: T1: Incards8cent 160W Incandoscent 11: T2: Inc€ndes€oni 4{i!y Flalog€n l0: W3: HalogF MR-16 351fl Comnnn Sgaoe Typea:Food Prepsratlon (541 sq.tl) HelogFn 2: D4: Olhsr lncandGcent 10: D5: Incand6c6nl 45W Halogen 8: D8: 0{her Lln6 Fluoclcont 3: UCl: 46' T5 28lrv / ElectDnlc Incandesce 6: L.04: Oth.t H6pltaliiy and Food Sol.lca:8ar Loungo/Lalalm Dhlng Arec (1250 sq.lt) Incand€lent 8: L{16: Othar Incard€sc€nt 9: Wl: Othor Halogen 9: D7: Halog€n MR-16 35W Linoar Fluorcsc€nt l; Fl: 22' T5 14W / Eladronic Halog€n 10: Pl: Flalogen MR-l6 35W Comrmn SFe Typ6:Food Pleparaton (155 sq.n ) 45 0t 13 9 3 4 7 4 2 I 2 45 2025 x7 2267 50 650 60 540 80 240 450 1800 321 20 80 1440 2880 240 240 3f 74 37 666.l!t 405 12 32?56 400 2000 118 19 12 18 15 1 5 4 1 I I I I 1 1 7m 20 'l/|8 16m 7m 4 37 16 s7 Pr{ed Tlfe:Roport dab 0005/08 Dab flenanp: C:\Doomenb ard Sdnge@Local Se$rBe\Tenpoory Intcnet Fihr\Ol-K5S\160100 Vall Cstcado Dlnlm Roorn - IECC calcr urdor ASHRAE.cck Page 5 of 6 ,har.lEt1&wlfrxtmr0UU|AE/(} $rdlon 3l Compllancr Gelculrtlon ltlh.Tdd Alq!-l,US- |r|||||h.T# Prcsordlilt l,gr!*!!|r.qdhaD'.0t bulflrg6n?l!a ItttlhrJlllbr Tobl RoF|.d tlhlf . ErCOF|tCryr lfapraTt E7D ffi guqg'ilrrnrcr*lnrrgr.d lorrrrtrlnollrrhrilrFr.dqxnlrrorov{ cnor*ffifr|Ttr* c|hf uttuA8l{ila6* Fgtade t NOTE: THIS PERMIT MUST BE POSTED ON JOBSTTE AT ALL TIMES -.,.-..\ l\\\tlt WNEl{/,LV Town of Vail, community oevetopmeniTffiuth Frontage Road, Vail, Colorado 8'1657 p. 970-479-21 39 l. 970.479.2452 inspections. 97 0.479.2149 MECHANICAL PERMIT ACOM Job Address: 1300 WESTHAVEN DR VAIL Location.....: VAILCASCADE/ARIASPA Parcel No...: 2103121000'12 OWNER L.O VAIL HOLDING INC O6/26/2OOE C/O DELOITTE & TOUCHE LLP 555 17TH ST STE 3600 DENVERco 80202 APPLICANT MTECH MECHANICAL TECHNOLOGIE 06/26/2008 Phone: (303) 650-4000 7535 HILLTOP CIRCLE. STE 2OO DENVERco 802?13452 License:281-M CONTRACTOR MTECH MECHANICAL TECHNOLOGIE 06/26/2008 Phone: (303) 650-4000 7535 HILLTOP CIRCLE, STE 2OO DENVER co 802213452 License:281-M Desciption: POOL DECK AND FRONT ENTRY MODS TO INCLUDE SNOWMELT/HX Valuation: $230,225.00 Permit #: M08-0142 [@-oors -Project#: PRJ07-0534 GoS ot-15 Status...: ISSUEDApplied..: 06/2612008 lssued. . : 08/01/2008 ExDires. .: 01l28n009 Mechanical Permit Fee--> $4.620.00 Will Call-----> Plan Check---------> $ 1, 155.00 Use Tax Fee--->Investigation---------> $0.00 S4.00 Tolal Calculated Fees--> 00.00 Addilional Fees------> TOTAL PERMIT FEE---> Total Calculaled Fees-> S5,779.00 Payments-------1 BALANCE DUE---_> $5,779.00 $0.00 i5,779.00 $5,779.00 $0.00 APPROVALS Item: 05100 BUILDING DEPARTMENT 06/26/2008 caunion Action: AP CONDITION OF APPROVAL Cond: 12 (BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE. Cond'.22 (BLDG.): COMBUSTION AIR lS REQUIRED PER CHAPTER 7 OF THE 2003 IMC AND SECTION 304 OF THE 2OO3 IFGC AS MOOIFIED BY TOWN OF VAIL. Cond: 23 (BLDG.): BOIILER INSTALLATION MUST CONFORM TO MANUFACTURER'S INSTRUCTIONS AND CHAPTER 1O OF THE 2OO3 IMC. Cond: 25 (BLDG.): GAS APPLIANCES SHALL BE VENTED ACCORDING TO CHAPTER 5 OF THE 2003 IFGC. Cond: 29 (BLDG.): ACCESS TO MECHANICAL EQUIPMENT MUST COMPLY WITH CHAPTER 3 OF THE 2003 IMC AND CHAPTER 3 OF THE 2OO3 IFGC,, Cond: 31 (BLDG.): BOILERS SHALL BE MOUNTED ON FLOORS OF NONCOMBUSTIBLE CONST. UNLESS LISTED FOR MOUNTING ON COMBUSTIBLE FLOORING. Cond; 32 (BLDG.): PERMIT,PLANS AND CODE ANALYSIS MUST BE POSTED lN MECHANICAL ROOM PRIOR TO AN INSPECTION REQUEST. Cond: 30 (BLDG.): BOILER ROOMS SHALL BE EQUIPPPED WITH A FLOOR DRAIN OR OTHER APPROVED MEANS FOR DISPOSING OF LIQUID WASTE PER SECTION 1004,6, mechcanicaLpermiL04l 908 DECLARATIOilS I hereby acknordedge that I have read thiE epplication, filled out in full lhe infomation r€quired, compleled an accurate plot plan, and slate lhat all lhe infomation as EquitEd F corEci. I agr€o to comply with th€ informalion and plot plan, to comply with all Torvn ordinances and slate laws, and to build lhis glrucluro according to the toflns zoning and subdivision codes, design review approved, Int€mational Building and Residential Codes and olher ordinances of lhe Town applicable thereto. mechcanicalJrormit_il1 908 ;( * * * | * | * r * i * I | * * | * * I * * * * * * * * t t t * 't * * * * * * t*** * * * * * * l' * 't * * | | t | | t *t t'ittt|tt't't |} a I lll**llll|t'l't*f a*lal TOWN OF VAIL, COLORADO Statement i I | *l** ** * * * * * * I'tt * I *t * I * * *ttt* tt I ttl*t* I t{ I I t* I I I 'l * 't 'l 'l 'l 'l * 'l:t ir I {' {' {' { * {' 'l I l' {r'l * t * 'l 'l 'l *{' * * {' * t t t t t { { Statement, lnmber: R080001289 Anount,: i5,179.o0 08/0L/200802:11 PM Pa:ment Method: Check Init 3 sAB NoEauion: 020314 MTECH Pennit No: Parce1 No: Site Address: IJocaEion: Tn*i s PalnnenE : M08 - 0142 2103-121-0001-2 13OO WESTIIAVEN DR VAIIJ VAII., CASCADE/ARIA SPA $5, 779. 00 T)4)EI MECHANICAI, PERMIT * * * * * * * ** i' * * * **t * * t * * **l*** * | r I * * * * t t 'tr t * * * t * * t 't r I i I rr** * r i *{t* r r {' * 't 't i' * 't * * r* r i * * t* i t* r l' l':l * * * * t Total Feea : Total ALL Pmts : Balance : $s, ??9. 00 $5, ?79. 00 $0.00 CurrenC PmcE---....----- 4,620.00 1, 155 . 00 4.00 ACCOT'NT ITEM LIST: Account Code 00100003111100 00100003112300 00100003112800 Deacriptsion UP PF vfc MECITANICAJ, PERMIT FEES PI.AN CHECK FEES TIILI, CAJ.,L INSPECTION FEB V'o'tt* lwa*ta,*a F:\cdev\FoRr,lS\Permlts\Brrlldlng\medrankalJrem Lr t-23-2m5.DOC APPLICATION WILL NOT BE ACCEPTED IF INCOMPLETE OR UNSIGNED TOV Project #: Building Permit #: mr 75 S. Frontage Rd. Vail, Colorado 81657 Permit will not be accepted without Provide Mechanical Room tayout drawn too Mechanical Room Dimensions o Combustion Air Duct Size and Location o Flue, Vent and Gas Line Size and locationo Heat Loss Calcs. o Equipment Cut/Spec Sheets CONTRACTOR INFORMATION COMPTETE VALUATION FOR MECHANICAT PERMIT & Materials *****x********x***x****xFoR OFFICE USE oNLy****x*xx*x*******x****xx***** Mechanical Permit #: lAh*,-?|*L s7 o-47 g-2:4s (rnspectioi]j--"--' Other Fees:Date Receivedl Accepted By: lnl iltl at ,4 \v- 2008 VAtr- 2A OF Mechanical Contractor: HreU Herl,a^ icalTethJub b ( Town of Vail Reg. No.: raul) 261- A Contact Person and Phone #'s: -l<'l Opcc qno q.E- til^l-q E-Mail Address: J C-r"oss 6 ft^k&q , corv\Fax#: qtt et/4 1ZZZ Contractor Signature:SJ MECHANICAL: $+ Lb, A25' 6 Contact Assessorc Office at orvisit for Parcel # Parcel # robName Y-l Q-'-scadu P*L Job Address: lZoa nl es[!v"wn \'vi ve.-' Legal Description ll Loe ll Btock: ll riling:Subdivision: oflsE V[S'ttt*'.- lu"-Address.jqT /7 th <l- * 46*Phone: Ensiner:24 beJ.; t{d+To-Iz r-r-l. ll Maress:Phone: Detailed descripfron d*4_ I!-^r4, (_,s goZo>WF l-<m,tt 6 t'^-l"tdZ *-,*rltltlx Work Class: New ( )ldditnn M itteration (p Repair ( )Other( ) Boilerl.ocaUon: Interior( ) Exterior( ) OUrer( )Does an EHU o<ist at this location: Yes ( ) No ( ) Type of Bldg: Single-family ( ) Duptex ( ) Mutd-famiv ( ) Commercial ([) Restaunnt ( ) Other ( ) No. of Existing Dwelling Units In thls building:No. of Accommodation UniB in thls building: Nofl-JpeofFireplacesExisting: GasAppliances( ) GasLoqq( ) wood/pellet( ) wmdBuming( ) No/fype of Fireplaces Proposed; Gas Appliances ( ) Gas LoSs ( ) Wood/Pellet ( ) wood Burnlng (NOT ALLoWED) Is this a @nversion from a wood burning fireplace to an rFlPhase@ tuzSr2oos 11-07-2008 Inspection Request Reporting Page2 4:20 om Vait- Co'- CiV of - Requested Inspect Date: Monday, November 10, 2008 Inspection Area: CG Site Address: 1000 S FRONTAGE RD WEST VAIL VAIL CASCADE ARIA SPA ArPrD Information Activitv: 807-0284 Tvoe: A-COMM Const Tvo6: Occuoahbv: OWrier: L-O VAIL HOLDING Conlractor: WEITZ COMPANY, lNC. (THE) Sub Tvoe: ACOM U'se: l-A Status: ISSUED Insp Area: CG Phone: 303-860-6600 Description: ARIA SPA REMODEL MENS AND WOMENS LOCKER ROOMS Requested Inspectionlsl Item: 540 BLDG-Final C/O Requestor: WEITZ COMPANY, lNC. CIHE) / STEVE /t- t,t// /(J Reouested'Time: 03:30 PM' Phone: 303-842-4899. STEVE Entered By: LCAMPBELL K Comments: ARIA MENS LqCKER ROOM / --Assioned To: GDENCKLA /-.L/--. / .--'-- " Action: - '- nf Time Exp: / J Inspection Historv Item: 30 BLDG-F 06/1 Comment: 06/18/08 Comment: 07l08/08 Comment: 09/19/08 Action: DN DENIED /INSPECTION.Action: DN DENIED oermit is aooroved and has rouqh insDection.' Action: PA PARTIAL APPROVAL COMPLYWITH Comment: frame09/26/08 InsoecComment: ALL Fl BLDG-lnsulation BLDG-Sheetrock Nail 06/24108 InsDec Action: AP APPROVED IN MENS LOCKER ROOMItem: 50llem: 60 Item: 70 liem: 90 Dc-Sheetrock Nail "* Aooroved * 0612410A InsDector: JRM Action: PA PARTIAL APPROVALComment: WALLS ONLY 07122108 InsDector: JRM Action: APAPPROVEDComment: COMPLETE10n2rc8 lnsoector: JGG Action: AP APPROVED10102t08 Insoector: JGG Action: AP APPROVED _. Qqnr.nenl: Drywall screws Ok, waterproofing applied to showers. BLDG-Misc. 08/20/08 Inspector: GCD Action: NO NOTIFIEDCommenl: SEE BUILD FINALBLDG-Final "" Aporoved ** 08l2OlOB Inspector: GCD Action: NO NOTIFIED Comment: COURTESY WALKTHRU FOR REMODELED RESTROOM. CHECK SHOWER OFR SEAT REOUIREMENTS. OBn2lOS Inspector: GCD Action: PA PARTIAL APPROVALCommenl: WOMENS LOCKER ROOM APPROVED FOR OCCUPANCY. PROVIDE SIGNAGE TO NEAREST ACCESSABLE TOILET, PROVIDE WRITTEN POLICY FOR ASSISTANCE. PROVIDE TOE CLEARANCE AT PRIVACY PARTITION.llem: 532Item: 533Item: 530 PW- walls REPT131 PLAN-' BLDG- Run Id: 8673 TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT 75 S.FRONTAGEROAD vArL,90 81657 970479-2t35 NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES SPRINKLERPERMIT Permit #: F08-0075 &-l-oLV'[ tfs61-6!(z I Job Address: 1000 S FRONTAGE RD WEST VAIL Status . . . : ISSUED Location.....: ARIA SPA: MEN'S LOCKER ROOM Applied . . : 09124/2008 Parcel No...: 210312115002 Issued. .: 09/26/2008 Project No : Expires . .: ohlNER L-O VArL HOLDTNG O9/24/2OO8 C/O DEI,OITTE & TOUCHE I-,LP 555 17TH ST STE 3500 DENVER co 80202 APPLICANT WESTERN STATES FrRE PROTECTT 09/24/2008 Phone: 3O3-792-0022 7026 SOUTH TUCSON WAY ENGLEWOOD co 80112 License: 338-S CONTRACTOR WESTERN STATES FIRE PROTECTI 09/24/2008 Phone: 303-792-0022 7026 SOUTH TUCSON WAY ENGLEWOOD co 80112 License:338-S Desciption: ADD ONE SPRINKLER HEAD, RELOCATE TWO HEADS Valuation: $2,050.00 .t*|1|:t*'l:}*t*tt*|'|:}*,l*.**.*.*.**.t,||'|':|*tt'+.+|'ttl.'t|*.,l||||***|| Mechanical---> 90. oo Restuarant Plan Review--> So. oo Tolal Calculated Fees--> $43?.13 Plan Check--> g3so.oo DRB Fee------*-----> $0.00 Additional Fees-----> 90.00 lnyestigation-> $0. OO TOTAL FEES------> 943?. 13 Total Permil Fee-----> 943?.13 Will Call--> $0.00 Payments--__-.._-1 543?.13 BALANCE DUE--> S0 . 00 Item: 05100 BUILDING DEPARTMENT Item: 05600 FIRE DEPARTMENT O9/25/2OOB Mccee Act.ion: APCR 1. The reterenced code standard shouLd be 1 edit.ion of NFPA 13. 2. There is a sectr-on ot the plans that. is cross hatched tor botlr area included al excluded, No heads are shown. 3. The hydrauLic cover sheet indicates area ot coverage is 100 sq tt / head at .1 gpn/sq/ft. Nodes 129, 217, and 205 do not meet the minimum flow reguj.rements. Plans indicate the relocated heads were being ted by ! 1-/4 or larger pipe. The an 1 inch. Recommend usins the same size arm-over as the teeder branch line to resol. Cond:12 (BLDG. ) : of minimum flow. 4. The street address on the permit application is j-ncorrect. Please revise. Resubmittal is required. I t/2 x L1 format is acceptable if changes are so noted. CONDITION OF APPROVAL FIEIJD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPI-,'IANCE. DECLARATIONS I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information as required is conect. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review approved, lntemational Building and Residential Codes and other ordinances of the Town applicable thereto. REQUESTS FOR INSPECTION SHALL BE MADE, SEVENTY-TWO IN ADV BY TELEPHONE AT 970.479.2252 FROM 8:00 AM - 5 PM. ATURE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER lrllll'|'|lrr|***tflt'tt*:tr:t | *all'lllr*r*rl *t I * I ** * *{ * * * *t**+**** *ll**i'{'*l'l* i *l+*** +t * *l' *tatl'lat TOWNOFVAIL, COLORADO Statement t'll I I I * * {rtlt*** *'l * 'l * 'l * lr i:} t t 't{.t 't' * 't tr*{' * 'f* 't * 't 't {' 'a 't f't 't 'a 't t rt * t t t*{' t * {' t**tt't*{i't't | * t***{'!r * { 'l' t * 'l * *'l***** Statement Number: R080001773 Anount: $437.13 09/26/200908:54 A!{ Palment Method: Check STATES FIRE Init: SAB Notation: L07744 WESTERN $437.13 * * t * * * * ** | * * * * a* i ** t***r*tr* r*rri****t*******ttt***tr't*'t * r *:t*'t *:t * * * $ * ** * * * * * * * * *'t' * 't 't' * * a * * 'r * * * ACCOUNT ITEM LIST: Account Code DeEcrl.pt.lon Current PmtsE Penrit No: Parcel No: Site Address : tocaEion: This PaymenE: BP 001.00003111100 PF 00100003112300 F08- 0075 2103 -121-1500-2 1OOO S FRONTAGE ARIA SPA: MENIS Tlrye: SPRINKITER PER"I,IIT RD WEST VATI, LOCKER ROOM Total Feeg: Total ALL Pmts : Balance: 943?.13 $437.13 $0.00 SPRINKLER PERMIT FEES PI.AN CHECK FEES 87.1.3 3s0.00 75 S. Frontage Rd. Vail, Colorado 81657 APPLICATION wlLL NOT BE ACCEPTED IF INCOMPLETE OR Project #: Building Permit #: Sprinkler Permit #: Fire Sprlnkler shop drawings are required at time of permit submittal and must include the following. Permit application will not be accepted without this information:. A Golorado Registered Engineer's stamp or N.|.C.E,T. Level lll (min) stamp,. Equipment cut sheets of materials.r Hydrauliccalculations.. A State of Colorado Plan Registration form.o Plans must be submitted by a Registered Fire Protection Contractor. COMPLETE VALUATIONS FOR ALARM PERMIT (Labor & Materials) Fire Spdnklen $ ArO 5'g -OO **********************ri&?iJ*****iii*ri*pqp CONTRACTOR INFORMATION Fire Sprinkler Contractor: \^)cst"',. S-{^tr "tT'ilii:i::, 'i ]; i-o t - Contact Eagle Counly Asses sors Office at g 76328-8640 orvisit for # Parcef # Jl o 3/J.i t 5' d O )- JobName: Aviq 7pa1 P1 <nt Lr-kcn"""ta;I;; ' to|t);;r;;,;-+Job Ad*ess: Legal Description ll Lot ll Btoctc ll riting:Subdivision: o*TIr-tU."a_. -6 ve,-t, ll td{22:)s'ffi[pnone: Engineer: a Address:Phone: Detailed Location-of work: (i.e., floor, unit #, bldg. #) A. i, t p, n ,,, Cq s,aLcs rt3to-* + Iro", Lozk ot- ,(ao>tj o*'l1o ro:*l'otion of work: 7$ o{ dL ta SY<4?*t o Workclass: New( ) Add,figll_l_ tg.g99!;| f,€pair( ) Rerro-frt( ) Other( ) Type of Bldg.: Single-family ( ) TwGfamily ( ) Multi-family ( ) Commerciaff{ Restaurant ( ) other( ) No. of Existing Dwelling Units in this building:No. of Accommodation Units in this building: Does a Fire Alarm Exist: Y"-*!. No L)Dqgg q.li1e Sprinkler System Exist: VeFfi No ( ) trr-,-t FTi :irll t\: ji 12412002TOYfll *JF ,iA;'. \WAiNdAIA\CdCV\FORMS\PERMITS\SPRKPERM.DOC usE oN LY** **** *** ** ** ******* *** **** ******* *** TOWNOF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT 75 S.FRONTAGEROAD VAIL. CO 81657 970-479-2135 NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES SPRINKLERPERMIT Permit #: F08-0044 GO?-oZ8{ Job Address: 1000 S FRONTAGE RD WEST VAIL Status . . . : ISSUED Location.....: VAILL CASCADE ARIA SPA Applied. . : 07115/2008 Parcel No...: 210312115002 Issued . . : 0'111712008 Project No : -lRS c)1 - o t{Z -l Expires . .: OWNER L-O VAIL HOLDING O7/L5/2008 C/O DELOITTE & TOUCHE LIJP 555 17TH ST STE 3500 DENVER co 80202 APPLICANT WESTERN STATES FIRE PROTECTT 07/]-5/2008 Phone: 3O3-792-0022 7026 SOUTH TUCSON WAY ENGLEWOOD co 80112 L,icense: 338 -S CONTRACTOR WESTERN STATES FIRE PROTECTI 07/75/2008 Phone: 303-792-0022 7026 SOUTH TUCSON WAY ENGLEWOOD co 80112 License:338-S Desciption: ARIA LOCKER ROOM REMODEL: ADD & REPLACE HEADS, INSTALLNEW PUPING FOR HYDRAULICS Valuation: $6,800.00 ,i 'r t t r +:| t 'i *,1'l' *.t l l l * * a t * i * r * 't r * t * * i,t Mechanical--> Plan Check--> lnYestigation-> Will Call---> $639.00 $s8. o0 $69?.00 $69?.00 90.00 $0.00 Restuaranl Plan Review-> 93 50 . oo DRB Fee-----------> s0.00 ToTAI-FEES-----.._--> 90.00 go. oo Total Calculaled Fees--> So. oo Additional Fees----------> $ 63 9 . oo Tolal Permit Fee-----> PaYments----'-"--'-;' BALANCE DUE------> Item: 05100 BUILDING DEPARTMENT Item: 05500 FIRE DEPARTMENT 07 /17 /2008 mvaughan Action: AP CONDITION OF APPROVALCond: 12 (BLDG.): FIELD INSPECTTONS ARE REQUIRED TO CHECK FOR CODE COMPI-.,IANCE. r **r+*+*at+t++ **r DECLARATIONS I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town applicable thereto. REQUESTS FOR INSPECTION SHALL BE MADE SEVENTY-TWO HOURS rN ADVANCE BY TELEPHONE AT 910-479-2252 FROM 8:00 AM - 5 PM. OR CONTMCTOR FOR HIMSELF AND OWNER * *+* * | * * t * * * * + * * t * * * * * * * * * * * **r * | * * **t*'t *:t t * I t't * * 't * tt't*'t{.* t*t1| '11{ * * +* * {* 'l:l' a' a' {' i' * * I' t * t + { *{'{'*t* TOWNOFVAIL, COLORADO Statement rt**ttt*rttttti*t*i**it***********'t*at******t*tttt* *f*'ti*t{'*{' {'****{"r:t{,*{'* **l'****{'ii'{"1*****lt statement Number: R080001175 Amount: $59?,00 01 /L7/200809:54 AII Payment Method: Check STATE FIRE INit: SAB NotaCion: L0?444 WESTERN Perniit No: Parcel No3 Site Addregs : L,ocation: This Payment: F08-0044 2103-121-1500-2 10 OO S FRONTAGE RD VAIIJJ CASCADE ASIA $597.00 T14>e: SPRINKIJER PERUIT WEST VAIIJ SPA ' Total Fees: TOTAI AIJJ PMtS : Balance 3 $697.00 $697.00 90. o0 ACCOUNTITEM LIST: Account Code BP 00100003111100 PF 00100003112300 De Ecrlpt ion * * * t * * * a * I I * I I * * * * * * * * i 'i | * 't * * * * * * * tf* *'f*i Current PnCB SPRINXI,ER PERMIT FEES PLA}T CHECK FEES 289.00 {08.00 NMNW 75 S. Frontage Vail, Colorado 81657 ApplrcAnoN l,rfrLL Nor BE AccEprED rF rNcoMpLErSi3S Hf 'u*ro P_B.to l.- c te1 Building Permlt #: Sprinkler Permit #: 97b17 9-21 35 (l ns Pectlon s) Fire Sprinkter strop drawings are required at time of permit submittal and must'include the ?ollowing-. Permit application will not be accepted without this information:r A Colorado Registered Enginee/s stamp or N.l.c.E.T. Level lll (min) stamp. o Equipment cut sheets of materials.o Hydrauliccalculations.r A State of Golorado Plan Registration form. r Plans must be submitted by a Registered Fire Protection Gontractot' CONTRACTOR INFORMATION COMPLETE VALUATIONS FOR ALARM PERMIT (Labor & Materials) Fire Sprinkler: $ {o.8 for Parcel # Fire Sprinkler Contractor: \^Jeah.n J{./es F'-e Town of Vail Reg. No.: izq,-1 ContaCt and Phone #'s: Bni"'', Woxr (Y^Aqq4gtt E-Maif Address: frrt",r,. lr.,.r,lefr @wt${+, O3 Contact Assessorc at 970-328-8640 or visit Parcel #olt?ilq6,0 Job Job Address: lo@ 5. F*L4R Legal Description ll t-ot: ll Block ll Filing:Subdivision: W*llnooress: fM Engineer:Address:Phone: Detailed Location of work: (i.e., floor, unit #, bldg. #) Qff H*. ( ^f.rr,,eo9 L*bt Detailed description of work:fi{ tP"LJ Er,e 4;a1elr6 E l.}. I WorkClass: New() Addition( ) Remodel 1!t Repair( ) Retro-fit( ) Other( ) rypeof Blds.: single-family( ) rwofamily( ) "untf".M.9gtREB'JK.FflT$If?lFi ) No. of Existing Dwellins Units in this ouilOingivAdF I 1 llff,rnll6fibffi ffiffiii,tt"risbuildins: Xl/A Does a Fire Alarm Exist: Yes (fi No ( )irlllf{Sn exlst Yesp) No ( ) R-of,Us'Eo1t1y-'***jl===ga=.- WaiMata\cdeV\FORMS\PERMITS\SPRKPERM.DOC NOTE: THIS PERMIT MUST BE POSTED ON JOBSTTE AT ALL TIMES /.-:"\fi\t\AL-\.vZtqgryiz Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657 p. 97 0.47 9.2139 t. 97 0.479.2452 inspection s 97 0.47 9.21 49 Permit #: E0s-011g f sol-o?8Y Project #: PRJ07-0427 Status...: ISSUED Applied..: 06/042008 lssued. .: 06/10/2008 Exoires. .: 1210712OQ8 Desciption: ARIA SPA REPAIRS: REPLACE RECESSED CANS WITH SURFACE FIXTURESValuation: $15,000.00 Square feet: 0 FEE SUMMARY Electrical Permit Fee-----> Invesligation Fee------------> Will Call Fee--------------> Use Tax Fee-------------------> Total Calculated Fees----> Item: 06000 ELECTRICAL DEPARTMENT 06/09/2008 shahn Action: AP Item: 05600 FIRE DEPARTMENT ELECTRICAL PERMIT ACOM Job Address: 1OOO S FRONTAGE RD WEST VAIL Location.....: VAILL CASCADE ARIA SPA Parcel No...: 210312115002 OWNER L.O VAIL HOLDING 06/04/2008 C/O DELOITTE & TOUCHE LLP 555 17TH ST STE 3600 DENVER co 80202 APPLICANT PATTERSON ELECTRIC CO 0610412008 Phone: 970-468-6166 P O BOX 483 DILLON co 80435 License: 208-E CONTRACTOR PATTERSON ELECTRIC CO 06/04/2008 Phone: 970-468-6166 P O BOX 483 DILLON co 80435 License: 208-E $327.75 $0.00 $4.00 $0.00 $331.75 Total Calculated Fees-> Additional Fees---------> TOTAL PERMIT FEE-.> Paymenb---- BALANCE DUE-----> APPROVALS $331.75 $0.00 $331.75 $331.75 $0.00 CONDMONS OF APPROVAL Cond:12 (BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE. DECLARATIONS I hereby acknowledge that I have read this application, filled out in full the information required, compleled an accurate plot plan, and state that all the information as required is conect. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review approved, Inlemational Building and Residential Codes and other ordinances of the Town applicable thereto. REQUESTS FOR INSPECTION SHALL BE MADE TWENTY.FOUR HOURS IN ADVANCE BY TELEPHONE AT 970,479.2149 OR AT OUR OFFICE FROM 8:00 AM - elec_prm_041908 bf Owner or Contractor b-/a-/ * * * * * | * * * * * * * * | | | | * * | | I * | t | * t * | * | * * * | | i | | t I t l*t * t * t* 'irt * * * * * * t * * * t * t r' * * * * * * * | * t I r * i {' * * f 't{r'iltrr TOWNOFVAIL, COI,oRADO Statement *att{'{"a1*a*a{{{{t*+lt*r{{' { { tt+{'*rr+tt*ta*aaa**+'| +*at*aata*a*af * | * * *** ** I tl | | * * * ** * '}i I lllt*la Statement Nuriber: R080000923 Anount: 9331.75 06/lo/zooeo2z23 VM Payment Method: Check Electric 5325 Init: DDG Notation: Patterson 9331.75 tt*aalt*t***aataaataaatataatttataa***aa * ft i t*** t r * I't I t ****t 'tr * ***lr'|** t * t * | ** * * * * *'t t * t * * {' * l' * * ACCOIJNTITEM LIST: Account Code Description Current Pmts Permit No: Parcel No: Slte Address: IJocaClon 3 This Palments: EP 00100003111100 9rc 00100003112800 808 - 0118 r)T)e: ELECTRICAL PEF.IIIT 2103 - 121- 15 00 - 2 1000 S FRONTAGE P.D I{EST VAIIJ VAIIJIJ CASCADE ARIA SPA Total Fees: TOTAI AIJIJ PMts : Balance ! ELECTRICAL PER"PIIT FEES WII,trJ CSI.,L INSPECTION FEE $331.7s $331.7s $0.00 327 .15 4.00 75 S. flontage Rd. Vail, Golorado 81657 APPUCATION WILL NOT BE ACCEPTED IF INCOMPLETE OR UNSIGNED ., Project #, 7&J014+)1 Buitding Permit g' Bo-7- oz84 Electricaf Permit *= €08 -0119 97 O- 47 9 -2149 (Inspections) TOWN OF VAII ELECTRICAL PERMIT APPTICATION CONTRACTOR IN FORMATION [^.--fZteor- 2 Contact Person and Phone #5: ^4O?'t t t"d Po,{.#eaS Fax#= Q7t -46[. - 56 COMPLETE SQ. FOOTAGE FOR AREA OF WORK AND VAIUATIOil OF WORK (labor & Materials) AMOUNT OF SQ FT IN STRUCTURE:ELECTRICALVALUATION: $ i5, 6"Od ConEct Asgsglrc Offie at 970-328-8Ant or visit for Patel # q- Parel # Job Narne: YA'J. , <A:'A'\.-l Job Address: ilq W ' l}l{llErl \)ru I rr1 work p.ruo od Pzc-<>se< C'.r7\) t'-' Add a-a/a:e /,r;{r.tt<\ Wo* Class: New ( ) Additlon ( ) Remodel (Repair( ) TempPower( ) Other( ) Does an EHU orist at this location: Yes ( ) No ( )WorkType: Interior Sf Extedor ( ) Both ( ) Typeof Bldg.: Single.family( ) Dupler( ) Multi-family( ) Commercial M) Restaurant( ) Other( ) No. of Aaommodation Units in this building:No. of Exi$ing Dwelling Units in thls building: for a hot tub: Y Does a FIre Sprinkler Sy*c0Exist: Yes ( ) No ( ) F:\ode\ArcRilS\PERMITS\Bullding\elecfl caljermilil-23-2m5. DoC Page 1 of 2 tll23lzms o o Amendment to the 2002 N.E.C. Town of Vail Ordinance 4, Series of 20Os Overhead seruices are not allowed in the Town of Vail. Underground services shall be in conduit (PVC) from lhe uffility transformer to the electric meter, main disconnect switch, and to the first electrical distribuUon circuit breaker panel. The main disconnect switch shall be tedilIy arcible, andloated next to the meter on the exterlor wall of the structure. All underground conduits are required to be inspected before back-filling the trench. In multi-family dwelling units, no electical wiring or feeder cables shall pass from one unit to another. Common waffs and spaoes are exempt NM Cable (Rome><) an E u*d only in singb and mufti-hmtf dwellings net uding 3 turfrElyretUannotb ued ln anybuilding mlxdwiil, Type+B.EF,H,4M &Soeupncie. Alumlnum onduclorcsmaller than size #8 are not permitted with the Town of Vail. , TOWN OF VAII ELECTRICAL PERMIT GUIDELINES All installations of exterior hot tubs or spa's require a DRB approval from planning. This application will not be accepted without a copy of the DRB approval form attached (if applicable). If this permit is for installation of an exterior hot tub or spa on a new elevated platform or deck over 30" above grade, you must also obtain a building permit. If this permit is for installation of an exterior hot tub or spa on any existing deck or elevated platform, a structural engineer must review the existing condition and veriff that it will suppoft the added concenbated load. Please provide a copy of the structural engineers wet stamped letter or drawing with this application. If this is a remodel in a multi-family building wih a homeowners association, a letter of permission from the association is required, If this permit is for a commercial space, two (2) sets of stamped drawings are required. Elstrial one4ine and panel *hedulu arc rcguircd if load is added or distribution is alhrcd, I have read and understand the above. Signature Date Signed If you have any questions regarding the above information or have addiUonal questions, please contact the Town of Vail Electrical lnspector at970-479-2147. The inspector can be rcached on Mondpy thru Friday mornings between the hours of 8am and 9am. You may also leave a voice mail and the inspector will call you back F:\cda/VORMS\PERMm\Building\electicaur€rmllu-23- 2005.DOC Page 2 ol 2 rLl23lzffiS NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES /.":--\ F\\t zrl lumftrvt[,|z---i Toryn of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657 p, 97 0. 47 9.21 39 1. 97 0.47 9.2452 inspections 97 0.47 9.?1 49 PLUMBING PERMIT ACOM Job AddFss: 1000 S FRONTAGE RD WEST VAIL Location.....: VAILL CASCADE ARIA SPA Parcel No...: 2103'12115002 OWNER L.O VAIL HOLDING 06/09/2008 CiO DELOITTE & TOUCHE LLP 555 17TH ST STE 3600 DENVERco 80202 APPLICANT AVON PLUMBING & HEATING 06/09/2008 Phone: 970-926-1608 PO BOX 2051 EDWARDS co 81632 License:314-P CONTMCTOR AVON PLUMBING & HEATING 06/09/2008 Phone: 970-926-1608 PO BOX 2051 EDWARDS co 81632 License:314-P D*ciption: ARIA SPA REPAIRS- INTERIOR REMODEL OF MEN'S AND WOMEN'S LOCKERS. REPLACE LAV FAUCETS, SHOWER FAUCETS AND RELOCATE ROUGH PLUMBING ACCORDING TO PLANS Valuation: $40.000.00 FEE SUMMARY Permit #: Po8-0052 (tot -o K\ Project #: PRJ07-0427 ISSUED 06/09/2008 06/09/2008 12106/2008 Plumbing Permit Fes--> Plan Check-------> I nveStigation--------> $600.00 WillCalF------> $150.00 Use Tax Fee------> 00.00 Total Calculaled Fees-> $4.00 $0.00 $754.00 Total Calculated Fees-> Additional Fees--------> TOTAL PERMIT FEES--> Payments-----------> BALANCE DUE._.*> $754.00 $0.00 $754.00 $754.00 $0.00 APPROVALS Item: 05100 BUILDING DEPARTMENT 06/09/2008 RLF Actionr AP Item: 05600 FIRE DEPARTMENT CONDITION OF APPROVAL Cond: 12 (BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE. OECLARATIONS I hereby acknowledge that I have read this application, filled out in full the intormation required, completed an accurate plol plan, and state thal allthe informalion as required is corect. I agree lo comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structur€ according to the towns zoning and subdivision codes, design review approved, Inlernational Building and Residential Codes and other ordinances ol the Town applicable thersto. REQUESTS FOR INSP AM .4 PM. HOURS lN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM 8:0( 6''l-oE Signature of Owner or V,ta,,t^-l O&)DDOS phbpermtl_041908 Print Name Date ****f**{.**********t t' {.**t *******{.{.**{.{.****************'i't{'**'r*'t'l***'t*'trt{'*'l*********rt*t'f {'****** TOWNOFVAIL, COLORADO Statement *'tr{' | { f ':*{.***** * * * ** ******* * * * *t**** * * * * * * l' * * * * * * t * + * * + * * * * * * * ****** * * * * **** * * * * tt + * * **ltl*t* Statement Number: ROSOOOOgO5 Amount: $754.OO 06/09/200812:40 PM Payment Method: PLTJMBING Init: SAB NoEation; 1278 AVON Permit No: P08-0052 T\TDE: PLUMBING PERMIT ParceL No: 2103-121-1500-2 SiLe Address: 1000 S FRONTAGE RD WEST VAIL, IJOCAEION: VAII,I, CASCADE ARIA SPA $7s4.00 ** **** **** * * * * ******** * * * * * *'t* t 'r * * * * * {*:f ***,r**'r.**r i' * * * * + * * * t * l' * * {. f {. {. * 'r * * * * * * * * * ii i( * {. {. * * * * * * * * ACCOUNT ITEM LIST: Account Code Current Pmts This Payment: PF 00100003112300 PP 00r-00003r-1r.r-00 wc 00100003LL2800 Total Fees: Total- AL,L Pmts : Balance; $7s4.00 $7s4.00 cn nn De script ion PLAN CHECK FEES PLUMB ING PERMIT FEES WILL CALL INSPECTION FEE 1s0.00 500.00 4 .00 APPUCATION WILL NOT BE ACCEPTED IF INCOMPLETE OR UNSIGNED Proiect #: PeJoT - o4z-i 75 S. Frontage Vail, Colorado Building Permit t. @-/ - ozg Plumorng PermIt # # 970-47 9-2L49 (Inspections) W-oosL {t*t CONTRACTOR INFORMATION Plumbing Contracton A\jOrJ PLuf,tBlr\3, lc'a Town of Vail Reg. No.: 3i4-P Contact Person and Phone #'s7 F{AerD qz6- 16c,A / qo4-ocFl I E-Mail Address: rnariO @auoeoLumberc. Cofn Fax#t <\ZQ- t6CA C-ontractor Signature: // ,4i 2--'""'-'-{zr. /hry'a / r/ ) COMPLETE VALUATION FOR PLUMBING PERMIT (Labor & Materials) PLUMBING: E 4O. @ntact Aswrs Office at 97O-328-8640 or visit forPatel# Parcel # 2\O3 \Z ll5oo2 Job Name: vAlL cF6cADe. AprA sp^lob Address: tooo o fe.o^5TAeE PD, l^t L Legal DescripUon I LoB I Block:Flllng:Subdivlslon: il,gtn$e$ie oA rrr..rrte ) | Address: *= t7'h 51s. ---,11.4r{ Phone: Engineer:-ioi$FlAddress: I4N'iEe,c-o 8o2oe[ Phone: Detaileddescriptionof work; usTEPrcta Penouetcf [-{E-rS 4 tpooerss tDc.rEe5 - Uetr'ncE tA\r.i^{rc-'g-tri 3{q^}E8t^t!cte-f5 &Ars PgLoc^-re. Petoa -ff-DHEIAJc: +c4oe-E,sG -Zo-tt€ tr4/\S. WorkClass: New() AddiUon( ) Alteration(r{ Repair( ) Other( ) Type of Bldg.: Single.famif ( ) Duplex ( ) MulU-family ( ) commercld 1'f nestaunnt ( ) Other ( ) No. of Existing Druelling Units in this building:No. of Accommodation Units in this building: ***************************************FOR OFFICE USE ONLY**rt********************************** JUN 06 2008 TOWN OF VAIL F: \cdev\FORMS\PERMITS\Building\plumbingJDermit_1 1-23-2005. doc Page 1 of 1 7t/23120Os *m HOW DID WE RATE WITH YOU? j;)r-;," 1. What Sercices did you Check all that apply Planning _ P.W.Admin _ Building _ Environment _ Fire_ Housing 2- Was your visit today as a: Homeowner_ Contractor Architect Other 3. Please rate your satisfaction with the following aspects of the Community Development Department Use a scale from 1 to 5 where 1 means 'not at all satistied' and 5 means "very satisfied' to rate each of the following items. Please use DK (Don't Know/No Opinion) as appropriate. Please circle your response. Director of Community Development use at Community Development today? very Satisfied 45 Not Satisfied Friendfy and Courteous I 2 3Knowledgeable 1 2 3 Timely Response/Calls Returned 1 2 3OveratlExperience 1 2 3 454545 DK DK DK DK 4. Was the review pnocess clearly exptained to you? (i.e., howthe Design Review Board and/or 'Planning and Environmental Commission works, when they meet, what you need to have when you apply for the planning and/or the building process, how long review times generally take, housing and/or environmental health policy, etc.) YES NO lf NO, what additional information would have been helpful? 5. 6. 7. 8. Did the planning process meetyour expectations? Did the building permit review process meet your expectations? Did the inspection process meetyour expectations? Did you feel the process was fair and efficient? Please explain your response(s). YES YES YES YES NO NO NO NO 9. lf you were looking for information (i.e., legal address file, plat map, plans, etc.) was the information in a format that was helpful / user frlendly?YES NO 10. Are you aware of the Community Development Dept. information available athttp://rvww.vailoov.com? YES NO Thank you for taking the time to complete this evaluation. lf indicated below, we will personally contact you on specific con@rns. lf it is your desire, you may contact the director by telephoning,970479-2145. Please feel free to use the back for additional comments. Name:Company: Address:Telephone: Date:City:_ State:_ Zip Code: F:\cdev\FORMS\SURVEYSbomdev_survey_o91 907.doc BUrLD rN GooD coMpANy. gFjiX?3j#i - " 0/l/' /-r i'iv /Zrl/t /y'/^t-,,4: / 're"**#'-Yff"T:?fft/r'-aK ,,o,/ Vail,colorado81658' -r/"6 /4J - (l,a's -' May 6, 2008 9*1-02€7 --3-dT6'l -6v.21 L-o The intent of this lefter is to formalize our plan for comfleting tre Locker Room Renovation upgrades at the Aria Spa in Vail, Colorado - per Building Permit 807-284. We have been hired by the owner (Deslinalion Hotels and Resorts) to perform this renovation project. The project essentially congsts of 2 locker room cosmetic upgrades - nal tile, new plumbing fixtures, new lockers, carpet paint and some neu/ light fixtures. The exisling room layouts are modified very slighdy - we will provide a sprinkler and fire alarm layout document for review and approval - but we expect the existing layouts of these systems to meet code as is. The Aria Spa wilt remain in use throughout the project. In conjunction with the Spa - we have developed a plan lhat allows us to complete our work In one of the locker rooms while temporarily dividing the other locker room into 3 sections - one section for the men, one for the women, and one uni-sex section where both the men and women can use the steam room and hot tub. This plan addresses the 'partitioning' of the Men's locker room to allow work in the Women's locker room. Exiting: Please see attached temporary egress plan from JG Johnson Architects. The locker room curren0y has an exit door ttat will serve both the 'Mens' side and the Womens' side. The Men's side can exit direcUy into the conidor, while the Women's side can exit to the adjacent spa locker roorn and then into ihe conidor. In an emergency condition - where second means of egress may be required - the way to provide the second means of egress would be through the other guest's side of the space - that is the Men would have to exit through lhe Women's side and vice versa. Signage will be placed above each door that states this clearly. Based on square footage of the space - the total occupant load is 42. Llfe Safety: The space is cunently equipped with notification devices and heat devices to meet code. With the partitioning of the space, and after speaklng with Clint Barthets with Acme Alarm, Acme will add notification devices in the two temporarily partitioned spaces (see notes on drawing). One additional heat device will be added to the Women's side - as all of the cunent heat devices in this space are in the locker area which will be the Men's slde. The temporary partition walls will be constructed so as not to interfere with sprinkler coverage. w-@gI ) (. l/tYz44 RE: lmpairment Plan - Building Permit 807-284 Mike, HOI{ESTY AND II,ITEGRITY. RESPEC' FOR PEOPLE. PERFORMAI{CE $'ITH AASOLUIE REL|AAIUTV. LO1'IG.TERM PERSPECTIVC ' NUF?UBING PERSONAI CNOWTH ![@| BU'LD rN GooD ..''PA.'Y. Work Parameters - Life Safety: When the partitioned space is complete in the existing Men's locker room, we intend to start wo* in the Women's locker room. The Life Safety systems in the 'construction' space are intended to be kept oniine and fully functional while work is ongoing in the space. The existing devices appear lo be heat only devices - if they are smoke/heat combinations - Acrne Alarm will switch these over lo heat only devices prior to demo start. Our work is for the most part limited to the locker rooms, however lhere are a few times when it will be required to access the floor below the locker rooms lo complete plumbing rough in items. The life safety devices in these areas will need to be taken off line during these time frames - as drywall demo and patch will be required. These time frames will be coordinated with TOV and Acme Alarm and notification will be given. Schedule: Our anticipated duration for each locker room renovation is approximately 13 weeks - for an approximate 26 week project overall duration. We have crews and subcontractors ready to start the project once this phasing plan is reviewed and approved by the TOV. We are anxious to get started - as we would like to get the project completed prior to the Spa 'high season' which starts around Thanksgiving. Personnel: Project personnel and contact information are as follows: The Weitz Company Pdect Manager Barry Monroe 970-379{474 The Weitz Company Project Superintendent Glen Musefter 303-2254286 Aria Spa General Manager Dan Timm 970479-5942 Please let me know if lhere are any additional questions regarding this plan or how we plan to complete the wo*. lt may be easier to walk the sile with yourself or your staff to review and address any additional concems - and we can follow up with an amended plan accordingly. Respectfully, brq {. ytttttr Barry Monroe Project Manager CC: Glen Musetter - The Weitz Company Keith Bartleft - JG Johnson Dan Tlmm - Aria Spa Clint Barthels - Acme Alarm "r,'4 .iqp .i6 .'9 ,t L .Rg $rs t$'jtr \--rr ? - rt+ffit [-lI#F tt9 .H\J 3E*r$*$'etq--\ t' R €\ 3 + rLs'z 'q \)s q .g\,sc- Eltrtrtr |GfoHNsoNAncHrrEcrs t!tarta(rt? | H0irttta Dttttl t |'ttrr t-na h*.aia rlh- t Dllt r.a. at E ta VAtt, cA4nPg?ztuK 4 e?A qfuvctw+>t4lY 'r".'?Nb coFYRrG}|r BY J O JO$IXrfl ARc|{]IEC[S, P.C, (JC.A] ^rt DR^W AT|o WRITIEN tNFORtt noaa APFEARS|O t{EREtt| 8t{ Lt }bT EE ll(DlREO. OIJPIJCATED, 9CLO6ED. USED FOR ^IIOIIGR PRbIE T, (N OIHERVUISE USED W[T'(X'T THE U'RITTE{ OOiISENT AM) If,)EUXFEANO OF JG'^. TOWNOF VAIL DEPARTMENTOF COMMI.INITYDEVELOPMENT 75 S.FRONTAGEROAD VAIL. CO 81657 970479-2t38 NOTE: TItrS PERMIT MUST BE POSTED ON JOBSM AT ALL TMES ADD/ALTCOMMBIJILDPERMT Permit # 807-0284 Proiect# PRJ07-0427 Job Address: 1000 S FRONTAGE RD WEST VAIL Status . . . : ISSUED [.ocation.......: VAIL CASCADE ARIA SPA Applied.. . : 08/30/2007 ParcelNo....: 210312115002 Issued...: 02/07/2008 Expires.,..,: 08/05/2008 OVINER IJ-O VAII' HOI'DING C/O DEIJOfTTE & TOUCHE I.JIJP 555 17TH ST STE 3600 DENVER co 80202 APPI-,ICANI AIJPINE MOITNIAIII BUIIJDERS INC 08/30/2007 Phone: 925-8703 PO BOX 69 EDWARDS colroRADO 81632 License:335-A coMrRAcToR WEITZ COMPAT{Y 05/06/2008 Phone: 970-668-4700 x113 PO BOX 4536 FRISCO co 80443 Desciption: ARIA SPAREMODELMENS AND WOMENS LOCKERROOMS Occupancy: mixed Tlpe Construction: I-A Valuation: $187,000.00 Revision Valuation: $0.00 Total Sq Ft Added: 0 *.**tti+*+tttt|at|t|:l:ttt*.**'|*l.*r:r**''|*.*i*!t!t'|*t|t|l||!tit|*|1*+t*|*r*EsRY Building-----> $1,480.95 Restuamm Plan Review-> 90.00 Total Calculated Fecs-> 12,446.57 Plan Check--> 5962,62 Rec'earion Fc€*--> S0.00 Additional Fees---> $0.00 Lrvcstigation> S0.oo TOTAL FEES > i2,446.57 Total Permit Fee-----> 52,446.s7 will Ca[----> $3.00 Payrnents > 52,446.s7 BAI-ANCE DUE ------+ So. oo Approvals:Item: 05L00 BUIIJDING DEPARTMENT 09/12/2007 cAunion Action: col[D see notes on Field set of plans Item: 05400 PL'ANNING DEPARTMEMr 09/07/2007 SH Action: AP IIEM: O55OO FIRE DEPARTMEMT IEen: 05500 PIIBL,,IC WORKS See the Conditions section of this Document for any conditions that may apply to this perrrit. DECLARATIONS I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state tlnt all the information as required is correct. I agree to comply with the information and plot plan, to corryly with all Town ordinances and state laws, and to build this stuchre according to the towns zoning and suMivision codes, desigrr rwiew approvod, International Building and Residential Codes and other ordinances ofthe Town applicable thereto. RDQUESTS FOR INSPECTION SHALL BE MADf, TWENry-FOIIR HOURSI IN ADVANCf, BY TELEPHONE AT 479-?l{9 OR AT OUR OFFICE FROM 8:00 AM 4 PM. 5'6'ot I Wr^l {, l,tortrL OR CONTRACTOR FOR HIMSELF AND OWNET '**|{.***'t**:t*!i**'.'}*'l*'}!3'***,i*'|.*'}*{t,*'tt**,k*****,t*!****!t*.**!**:}:}{t****!*l''|.{.{'||t,|t+,******** CONDITIONS OF APPROVAL Permit #: 807-0284 as of 0546-2008 Status: ISSUED *:*{.|t,|*,f*:i:}*:*{.'t*'t'l*'t***'t'|.*'lt***'}*'tti*'f*'i,t*:|*'f:t*:*,t{.,t*'t't*'t'tf{.'t***!tl.l.'t************ PemftType ADD/ALTCOMMBIJILDPERMT Applied: 08130/2007 Applicant ALPINE MOLTNTAIN BIILDERS INC. Issuer 02t07/2008 926-8703 To Expire: 08/05/2008 Job Address: 1000 S FRONTAGE RD WEST VAIL Iocation: VAILCASCADEARIASPA ParcelNo: 210312115002 Description: ARIA SPAREMODELMENS AND WOMENS LOCKERROOMS ***'t'f*******'*'},}l.***'}'}***'|**'t***'******{.'**'r'*rt**'|.:$conditions.***{.***!r**{t*:r!'}***'**{.:F{(*********** Cond: I (FIRE): FIRE DEPARTMENT APPROVAL IS REQI.]IRED BEFORE ANY WORK CANBE STARTED. Cond: 12 @LDG.): FIELD INSPECTIONS ARE REQLIIRED TO CHECK FOR CODE COMPLIANCE. Cond: CON0009343 SEE NOTES ON AO4.O2 AND AO4.O3 NON COMBUSTIBLE CONSTRUCTION REQUIRED ..\I,PINE I\fOUN'I'AIN BI-TI, I,DERS. ]NC, May 6, 2008 Rachel Friede TOV Community Development Vail, CO 81657 47 9.2452 Mriede@vailgov.com. Re: BP07-0284 Aria Spa Dear Rachel, Alpine Mountain Builders currently holds the permit #BP-0284 for the Aria Spa Renovation. Please hansfer that permit to the Weitz Company attn: Barry J Monroe Pnoject Managen The Weltz Company 955 Nonth Ten Mile Drive Unit # A-1 PO Box 4535 Frisco, Colorado 89443 Phone: 970-668-4700 xt 113 Fax: 970-668-9409 t'lobile: 970-379-0474 ba rrv . mon roe@ure itz . com Thank You, Craig Bruntz Vice Pres Cc David Sykes TOWN OFT VAIL ''.Iil;i ')'r"?o$3'ij' Ro?-n8l PO BOX 69.IiDWARl)S, {.1()l.ORAl)() ' 8lr'.1: PIit-)NE: t)7$ ,26-8i(.t3 . F AX: 9?(j 926 8i05