MECHANICAL PERMIT Permit #: M03 -0011
Job Address: 75 S FRONTAGE RD WEST VAIL Status ...: FINAL
Location.....: 75 S FRONTAGE ROAD Applied..: 02/07/2003
Parcel No...: 210108236004 Issued . .. 02/17/2003
Legal Description: Expires. .: 04/04/2006
Project No :
OWNER TOWN OF VAIL
C/O FINANCE DEPT
75 S FRONTAGE RD
VAIL CO 81657
APPLICANT FALCON PLUMBING & HEATING
3187 MESA AVENUE, SUITE A
GRAND JUNCTION CO
81504
CONTRACTOR FALCON PLUMBING & HEATING
3187 MESA AVENUE, SUITE A
GRAND JUNCTION CO
81504
License: 175 —P
02/07/2003
02/07/2003 Phone: 970 - 434 -0556
02/07/2003
Desciption: INSTALL NEW BOILER @ COM DEVELOPMENT
Valuation: $85,000.00
Fireplace Information: Restricted: Y # of Gas Appliances: 0 # of Gas Logs: 0 # of Wood Pellet: 0
FEE SUMMARY
Mechanical - -> $1,700.00 Restuarant Plan Review —> $0.00 Total Calculated Fees - -> $2,128.00
Plan Check —> $425.00 TOTAL FEES------- - - - - -> $2, 128.00 Additional Fees--- - - - - -> $2,128.00)
Investigation -> $0.00 Total Permit Fee -- ------- > $0.00
Will Call —> $3.00 Payments---- - - - - -- $0.00
BALANCE DUE --- - -> $0.00
Item: 05100 BUILDING DEPARTMENT
02/11/2003 cdavis Action: AP
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 22
(BLDG 2003): COMBUSTION AIR IS REQUIRED PER CHAPTER 7 OF THE 2003 IMC AND
SECTION 304 OF THE 2003 IFGC AS MODIFIED BY TOWN OF VAIL.
Cond: 23
(BLDG 2003) : BOILER INSTALLATION MUST CONFORM TO MANUFACTURER'S INSTRUCTIONS
AND CHAPTER 10 OF THE 2003 IMC.
Cond: 25
(BLDG 2003): GAS APPLIANCES SHALL BE VENTED ACCORDING TO CHAPTER 5 OF THE 2003
IFGC.
Cond: 29
(BLDG 2003): ACCESS TO MECHANICAL EQUIPMENT MUST COMPLY WITH CHAPTER 3 OF THE
2003 IMC AND CHAPTER 3 OF THE 2003 IFGC..
Cond: 31
(BLDG.): BOILERS SHALL BE MOUNTED ON FLOORS OF NONCOMBUSTIBLE CONST. UNLESS
LISTED FOR MOUNTING ON COMBUSTIBLE FLOORING.
Cond: 32
(BLDG.): PERMIT,PLANS AND CODE ANALYSIS MUST BE POSTED IN MECHANICAL ROOM PRIOR
TO AN INSPECTION REQUEST.
Cond: 30
(BLDG.): BOILER ROOMS SHALL BE EQUIPPPED WITH A FLOOR DRAIN OR OTHER APPROVED
MEANS FOR DISPOSING OF LIQUID WASTE PER SECTION 1004.6.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 479 -2149 OR AT OUR OFFICE FROM 8:00 AM - 4 PM.
SIGNATURE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
M03 -0011 : Entries for Item:390 - MECH -Final 09:27 02/19/2013
Action
Comments
By
Date
Unique_
Key
CR
1.CAP ALL OPEN COPPER PIPE.
GCD
07/29/2003
A000065
2.SUPPORT GASPIPE AT APPLIANCES.
123
3.PROVIDE BALANCE REPORT.
4.ROUGH AND FINAL ELECTRICAL
INSPECTION READ.
5.PAINT EXTERIOR SHEET METAL TO
MATCH BUILDING
CR
MET WITH STATE BOILER INSPECTOR
GCD
12/29/2003
A000068
TODAY.
932
AN ASME LISTED EXPANSION TANK IS
REQD DUE TO THE OPERATING
PRESSURE OF THE T &PR VALVES. THE
T &PR VALVES CAN BE CHANGED TO 30psi
AND THE EXISTING TANK WOULD BE
APPROVED.
AP
GCD
04/04/2006
A000088
557
Total Rows: 3