HomeMy WebLinkAboutM05-0179TOWN OF VAIL
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
DEPARTMENT OF COMMUNITY DEVELOPMENT
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
MECHANICAL PERMIT
Job Address: 715 W LIONSHEAD CR VAIL
Location.....: VAIL MARRIOTT SPA
Parcel No...: 210107214001
Project No : �Z _� U � _ L �L�
OWNER VAMHC INC
PO BOX 7
VAIL
CO 81658
APPLICANT DESIGN MECHANICAL, INC.
168 CTC BLVD. STE. D
LOUISVILLE
CO 80027
License: 277-M
CONTR.ACTOR DESIGN MECHANICAL, INC.
168 CTC BLVD. STE. D
LOUISVILLE
CO 80027
License: 277-M
08/09/2005
Permit #:
Status . . . .
Applied . . :
Issued . . .
Expires . ..
MOS-0179
ISSUED
08/09/2005
08/12/2005
02/08/2006
08/09/2005 Phone: (393)449-2092
08/09/2005 Phone: (393)449-2092
Desciption: VAIL MARRIOTT SPA-MODIFY VENTILATION
Valuation: $9,867.00
Fireplace Information: Restricted: Y # of Gas Appliances: 0 /t of Gas Logs: 0 # of Wood Pellet 0
***********************x***x***s******************************�***�* FEE SUMMARY ************************************************************
Mechanical---> $200. 00 Restuarant Plan Review--> $0. 00 Total Calculated Fees---> $253 . o0
Plan Check---> $50.00 DRB Fee---------------------> $0.00 Addirional Fees-----------> $o. o0
Investigation-> $0.00 TOTALFEES--------------> $253.00 Total Permit Fee----------> $253 .00
Will Call----> $3 . 00 Payments-------------------> $253 . 00
BALANCE DUE---------> $0. 00
**�*****************************x****************************************************************************************************************
Item: 05100 BUILDING DEPARTMENT
08/09/2005 JS Action: AP
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 22
(BLDG.): COMBUSTION AIR IS REQUIRED PER CHAPTER 7 OF THE 2003 IMC AND SECTION
304 OF THE 2003 IFGC AS MODIFIED BY TOWN OF VAIL.
Cond: 23
(BLDG.): BOIILER INSTALLATION MUST CONFORM TO MANiJFACTUR.ER'S INSTRUCTIONS AND
CHAPTER 10 OF THE 2003 IMC.
Cond: 25
(BLDG.): GAS APPLIANCES SHALL BE VENTED ACCORDING TO CHAPTER 5 OF THE 2003 IFGC.
Cond: 29
(BLDG.): ACCESS TO MECHANICAL EQUIPMENT MUST COMPLY WITH CHAPTER 3 OF THE 2003
IMC �1ND CHAPTER 3 OF THE 2003 IFGC..
Cond: 31
(BLDG.): BOILERS SHALL BE MOUNTED ON FLOORS OF NONCOMBUSTIBLE CONST. UNLESS
LISTED FOR MOUNTING ON COMBUSTIBLE FLOORING.
Cond: 32
(BLDG.): PERMIT,PLANS AND CODE ANALYSIS MUST BE POSTED IN MECFIANICAL ROOM PRIOR
TO AN INSPECTION REQUEST.
Cond: 30
(BLDG.): BOILER ROOMS SHALL BE EQUIPPPED WITH A FLOOR DR.AIN OR OTHER APPROVED
MEANS FOR DISPOSING OF LIQUID WASTE PER SECTION 1004.6.
****************************:***********r****�************�***************�****+***************************************�*************************
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot
plan, and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply
with all Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design
review approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 479-2149 OR AT OUR OFFICE FROM 8:00 AM - 4
PM. _ � . �
SIGNATURE OF OWNER OR CONT�C`I'OR FOR HIMSELF AND OWNEF
********************************************************************************************
TOWN OF VAIL, COLORADO Statement
********************************************************************************************
Statement Number: R050001289 Amount: $253.00 08/12/200508:12 AM
Payment Method: Check Init: DDG
Notation: Design
Mechanical 40082
-----------------------------------------------------------------------------
Permit No: M05-0179 Type: MECHANICAL PERMIT
Parcel No: 2101-072-1400-1
Site Address: 715 W LIONSHEAD CR VAIL
Location: VAIL MARRIOTT SPA
Total Fees: $253.00
This Payment: $253.00 Total ALL Pmts: $253.00
Balance: $0.00
********************************************************************************************
ACCOUNT ITEM LIST:
Account Code
--------------------
MP 00100003111100
PF 00100003112300
WC 00100003112800
Description
------------------------------
MECHANICAL PERMIT FEES
PLAN CHECK FEES
WILL CALL INSPECTION FEE
Current Pmts
2-00.00
50.00
3.00
-----------------------------------------------------------------------------
M05-0179: Entries for Item:390 - MECH-Final 09:11 02/20/2013
Action Comments By Date Unique_
Ke
CR GRILLS AND DIFFUSERS INSTALLED. GCD 11/15/2005 A000085
BALANCE REPORT RECEIVED SUPPLY 341
AND RETURN IS UNDER DESIGN BY 18 TO
48%.
AP jrm 02/20/2013 A000157
858
Total Rows: 2
Page 1
, APPLIC.4TION WIi.L iVOT �E ACCEPTED IF INCOMPLETE OR UNSIGNED�� �`�Z6 �
TOV Project #: h�"~
Building Permit #: 1� 0 5 al�A
Mechanical Permit #: �
� 970-479-2149 (Inspections
710WN UF T'AIL
TOlNN OF VAIL MECHANICAL PERMIT APPLICATION
75 S. Frontage Rd. Permit will not be accepted without the following:
Vail, Colorado 81657
P vide Mechanical Ro m La o draw scale to include:
�R,o,o e o
o ustid�i`Air ct i and
ent and G ize d Lo ion
❑ Heat Loss Calcs.
o Equipment Cut/Spec Shee#s
E-Mail
Contractor:
CONTRACTOR INFORMATION
I Town of Vail Reg. No.: Conta
�
f.1s:.1.
COMPLETE VALUATION FOR MECHANICAL PERMIT
MECHANICAL: $ G� �/'� �, �
Contact Eag/e CountyAssessors O�ce at
Parcel #
Job Name:\ /� � if11�� �
_ 1( Y �i �o �
Legal Description Lot: Block: Filing:
Owners Name: Address:
Engineer:
Address:
40 or visit
Job Address:
rt Person and Phone #'s:
�l�e e.�3 �'16 -`l�6 _ O�,qf,�
� ��� - �a� �1� �
(Labor & Materials)
w, ea4/e-county, com for Parce/ #.
Subdivision:
� Phone:
Phone:
Deta� d description of ork:
� � � � ,3 -�.�
Work Class: New ( ) Addition ( ) Alteration ( ) Repair ( ) �ther ( )
Boiler Location: Interior () Exterior () Other () Does an EHU exist at this location: Yes () No ()
Type of Bldg: Singfe-family () Duplex () Multi-family () Commercial
( ) Restaurant ( ) Other ( )
No. of Existing Dweliing Units in this building:
No, of Accommodation Units in this building:
No/Type of Fireplaces Existinq: Gas Appliances () Gas Loqs () Wood/Pellet () Wood Burninq ()
No/Type of Fireplaces Proposed: Gas Appliances () Gas Logs () Wood/Pellet () Wood Burning (NOT ALLOWED)
Is this a conversion from a wood burning fireplace to an EPA Phase II device? Yes () No ()
****�*****************�*FOR OFFICE USE OIVLY***********m*********�******�
Other Fees:' Plannef'Sien-nff• w,...,,....,..�-e...
F:\cdev�BUILDING�P.PPLICATIONS�Iv1ECHPERM2005.DOC �� (� ' 06/08/2005