HomeMy WebLinkAboutB13-0023 BOILER CUT SHEETS.pdfVITODENS100-W Gas-firedwall-mountedcondensingboiler 37to118MBH/10.8to34.6kW Vitodens100-W WB1BSeries Gas-FiredWall-MountedCondensingBoiler withmodulatingstainlesssteelMatriXcylinder burnerandstainlesssteelInox-Radialheatexchanger forroomairindependentoperation (usingadirectventsystem)orroom airdependentoperation TechnicalDataManual ModelNos.andpricing:seePriceList Vitodens100-W,WB1B (withpreinstalledcoaxialventpipeadaptor)  ThistrademarkisregisteredwiththeU.S.PatentandTrademarkOffice. 5369277v1.501/2010 ProductInformation 2 VITODENS100-W EquippedwithaViessmannstainlesssteel heatexchangerforlastingperformanceand reliabilityandamodulatingMatriXcylinder gasburner,theVitodens100-W wall-mountedcondensingboileristheperfect combinationofvalue,qualityandViessmann technology. Thebenefitsataglance: Outstandingefficiency of95.2%A.F.U.E. onallmodels. Lastingperformance withViessmann-madeSA240316Ti stainlesssteelInox-Radialheatexchanger constructedtoASMESectionIVandCSA B51. Low-emission withfully-modulatingstainlesssteel MatriXcylinderburner.Factorycalibration eliminatesadjustmentsinthefield. <29ppmNOx (at3%O2) <40ppmCO(at3%O2) Controlvariety Integratedboilercontrolinterfaceswith anylevelofexternalcontrol-fromroom thermostattooutdoorresetandmore. Compact,lightweightdesign andzeroclearancetocombustiblesmake itagreatchoiceforlimited-space installations. Extremelyquietoperation; quieterthanmostrefrigerators. <50dBA(at1meter/3.3ft.) Easyinstallation,serviceandmaintenance withallpipeconnectionslocatedatthe bottomandserviceablecomponentseasily accessiblefromthefront. Multipleventingoptions -Horizontalorverticalsealedcombustion coaxialventsystem(factorysupplied). -Horizontal,verticalorhybridsealed combustiondouble-pipeventsystem (fieldsupplied). -Horizontalorverticalsingle-wallvent system(fieldsupplied). Suitableforhighaltitudelevels ofupto10,000ft./3,000m without deration. Built-inautomaticfrostprotection allowsboilertobeshutoffforan extendedperiodoftimewhileprotectingit againstfreeze-up. Limitedlifetimewarranty inresidentialapplications. 5369 277 v1.5 ProductInformation Cross-Section 3 Legend StainlesssteelMatriXcylinderburner Inox-Radialstainlesssteelheat exchanger Burnerblower Gasandhydronicconnections Boilercontrol StandardEquipment: Wall-mountboilerandinstallationfittings c/w30psipressurereliefvalve,pressure gage,gasshut-offvalve,twofill/drain valves,allmountinghardware,outdoor temperaturesensor,andLPconversionkit. 5369 277 v1.5 C D E B A Productmaynotlookexactlyasillustrated. TechnicalData 4 TechnicalData Standardheatingboiler BoilerModelModelNo.WB1B26 WB1B35 NaturalgasandLPG CSAinput CSAoutput/DOE*1 heatingcapacity MBH kW MBH kW 37-91 10.8-26.7 34-83 9.9-24.3 37-118 10.8-34.6 34-108 9.9-31.6 NetI=B=Rrating*2 MBH 72 94 Heatexchangersurfacearea ft.2 m2 10.23 0.86 10.23 0.86 Min.gassupplypressure Naturalgas LPG “w.c. “w.c. 4 10 4 10 Max.gassupplypressure*3 NaturalgasandLPG “w.c.14 14 A.F.U.E.%95.2 95.2 Weight lbs kg 78 34.1 78 34.1 Shippingweight lbs kg 95 43 95 43 Boilerwatercontent USG ltr 0.87 3.3 0.87 3.3 Boilermax.flowrate*4 GPM ltr/h 6.2 1400 6.2 1400 Max.operatingpressure at210ºF/99ºC psig bar 45 3 45 3 Boilerwatertemperature –Adjustablehighlimit(AHL)range –spaceheating(steadystate) –DHWproduction(set-point) –Fixedhighlimit(FHL) ºF/ºC ºF/ºC ºF/ºC 86to176/30to80 172/78 210/99 Boilerconnections BoilerheatingsupplyandreturnNPTM(male)“ PressurereliefvalveNPTF(female)“ Drainvalve(malethread) ¾ ¾ ¾ ¾ ¾ ¾ Dimensions Overalldepth Overallwidth Overallheight inches mm inches mm inches mm 141/8 360 15¾ 400 28½ 725 141/8 360 15¾ 400 28½ 725 *1 Outputbasedon140ºF/60ºC,120ºF/49ºCsystemsupply/returntemperature. *2 NetI=B=Rratingbasedonpipingandpick-upallowanceof1.15. *3Ifthegassupplypressureexceedsthemaximumgassupplypressurevalue,aseparategaspressureregulatormustbeinstalledupstreamofthe heatingsystem. *4See“MaximumFlowRates”onpages15to17inthismanual. 5369 277 v1.5 Vitodens100-W 5 Standardheatingboiler BoilerModelModelNo.WB1B10-26 WB1B10-35 Gassupplyconnection NPTF“¾¾ Fluegas*5 Temperature(atboilerreturn temperatureof86ºF/30ºC) –atratedfullload –atratedpartialload Temperature(atboilerreturn temperatureof140ºF/60ºC) ºF/ºC ºF/ºC ºF/ºC 127/53 90/32 167/75 131/55 90/32 172/78 Fluegasvalue Massflowrate(offluegas) –atratedfullload –atratedpartialload Availabledraught lbs/h kg/h lbs/h kg/h Pa mbar 79.2 36.0 33.0 15.0 100 1.0 100.1 45.5 33.0 15.0 100 1.0 Fluegastemperaturesensor limit ºF/ºC 230/110 230/110 Averagecondensate flowrate*6 withnaturalgas –TS/TR =122/86ºF/50/30ºC USG/day ltr/day 1.95-2.3 8-9 2.5-2.8 9.4-10.5 Condensateconnection*7 hose nozzle ∅in 1 1 Boilerfluegasconnection*8 ∅ in/mm 23/8/60 23/8/60 Combustionairsupply connection*8 outer ∅in/mm 4/100 4/100 Noiselevel(at1meter) –atfullload –atpartialload (dB) (dB) 47 40 49 42 Highaltitude(factoryset)*9 ft./m 0-5,000/0-1,500 0-5,000/0-1,500 *5 Measuredfluegastemperaturewithacombustionairtemperatureof68°F/20°C. *6 Basedontypicalboilercycles,includingpartialloadconditions. *7 Requires1”/25mmtubing.SeeVitodens100-WInstallationInstructionsfordetails. *8 Foranoverviewofventingoptionsrefertotheappendixstartingonpage19.FordetailedinformationrefertotheVitodensVenting SystemInstallationInstructions. *9 For5,000to10,000ft/1,500to3,048moperation,acodingaddresschangeisrequired.RefertotheInstallationandService Instructionsfordetails. ForinformationregardingotherViessmannSystemTechnologycomponentry,pleasereferencedocumentationofrespectiveproduct. 5369 277 v1.5 Vitodens100-W 6 Vitodens100-W,WB1B26/35 withoutpipingconnections ConnectionsVitodens100-W, WB1B10-26,10-35 Legend Connections Condensatedrain,plastichose Ø1”/25mm Boilerwatersupply,NPT¾”(male thread) Gasconnection,NPT¾”(malethread) Boilerwaterreturn,NPT¾”(male thread) E Combustionairopeningfordoublepipe system F Combustionairopeningforco-axial system Dimensions aSeefig.2fordimensions b15¾”/400mm c25/8”/68mm d28½”/725mm e47/8”/123mm f61/8”/156mm g141/8”/360mm h5”/125mm j97/8”/250mm k11/4”/31mm m77/8”/200mm n31/8”/80m 5369 277 v1.5 a b ee f g h B A DC n n m EF E j c d k Fig.1Frontview TopviewSideview Vitodens100-W 7 Vitodens100-W,WB1B26/35 withpipingconnections PipingconnectionsforVitodens 100-W,WB1B10-26and10-35 (factorysupplied) Legend BWRBoilerwaterreturn,¾” BWSBoilerwatersupply,¾” BDBoilerdrain BFBoilerfill GCGasconnection,¾”NPTM (malethread) PRVPressurereliefvalve PGPressuregage VCVentingconnection CAICombustionairinletconnection (optional) 5369 277 v1.5 14”/ 355mm 15¾”/ 400mm 27/8”/73mm 12 ” / 3 0 0 m m 2 5/8”/ 68mm 6”/ 152mm 47/8”/ 123mm 47/8”/ 123mm VC CAICAI PG Fig.2 28 ½ ” / 7 2 5 m m 32 ½ ” / 8 2 6 m m PRV BD GCBF BWS BWR Fig.3 Vitodens100-W/TechnicalData 8 RecommendedMinimumServiceClearancesMinimumClearancestoCombustibles Top Front Rear Left Right Ventpipe*1 0 0AL, CL 0 0 0 0 AL=Alcove CL=Closet *1RefertotheInstallationInstructionsofthe VitodensVentingSystemfordetails. Note: TheVitodens100-Wboilerhaspassedthe zeroinchesventclearancetocombustibles testingrequirementsprovidedbytheboiler HarmonizedStandardANSIZ21.13.CSA 4.9.2005andthereforeislistedforzero clearancetocombustibleswhenvented withasinglewallspecialventingsystem (AL-29-4Cmaterial)orUL/ULC-listedCPVC gasventmaterial.Thezeroinchesvent clearancetocombustiblesfortheVitodens 100-Wboilersupercedestheclearanceto combustibleslistingthatappearsonthe specialventingsystemlabel. 5369 277 v1.5 Front 12”/305mm Top 12”/305mm 0”/mm 28”/700mm Side 0”/mm Back SideFig.4 12”/300mm*1 4” / 1 0 0 m m 28”/ 700mm ¼”/5mm¼”/5mm¼”/5mm Fig.5 TechnicalData/HeatingCircuitPumps 9 WatersideFlow(boilercircuit) TheVitodens100-Wisdesignedonlyforclosedloop,forced circulationhotwaterheatingsystems. Pressuredrop(primarycircuit)ofVitodens100-W Usestandardfrictionlossmethodforpipesizing. Observeboilermaximumandminimumflowratelimitations.Ifsystemflowrateexceeds boilermaximumflowrate(asstatedonpage13)orifsystemflowrateisunknown,Viessmannstrongly recommendstheinstallationofalow-lossheader.Seepage13forlow-lossheaderinformation. HeatingCircuitPumps RecommendedheatingpumpswithVitodens100-W,WB1B10-26,10-35: Grundfos15-58(3-speed) Taco00R orequivalent Refertothegraphabovefortheproper watersideboilerfrictionlosscalculations. Pumpselectionmustbebasedonaccurate systemflowandpressuredropcalculations (incl.DHWsizing). 5369 277 v1.5 050010001500 0 1 2 3 4 5 6 0 3.3 6.6 9.8 13.1 16.4 19.7 ft . 2000ltr./hr. 7 8 23 26 Flowrate(USGPM) Su p p l y h e a d p r e s s u r e ( f t . w a t e r ) 02.24.46.68.8GPMm Alow-lossheader must beusedwhenthe system flow rateexceedsthemaximumorfallsbelowtheminimum flowrateoftheVitodens100-Wboiler.Analternative methodmaybeused,suchasprimarysecondarypiping usingcloselyspacedtees.Alow-lossheaderoffers additionalbenefitsnotprovidedbyapairofclosely spacedtees.Viessmannstronglyrecommendsand preferstheuseofalow-lossheaderovercloselyspaced tees. Pleaseseepage13fordetails. IMPORTANT DHWProduction/WallMounting 10 DomesticHotWaterProductionviaDHWStorageTank Vitodens100-Wboilerscanbeusedin conjunctionwiththestand-aloneDHW storagetanksofferedbyViessmann(a separateDHWcontrollershouldbefield supplied).AllViessmannDHWstorage tankssoldinNorthAmericaareavailablein “Vitosilver”finishonly. SizeandselecttheDHWstoragetankbased ontheforecastDHWconsumptionofthe buildinginquestion. ForfurthertechnicalinformationonDHW storagetanks,seetheVitocell-VTechnical DataManuals. WallMountingInformation TheVitodens100-W(modelWB1B10-26 and10-35)comeswithatemplate,which allowsyoutoeasilymarkthelocationofthe screwsforthemountingbracketandthe locationofthefluegaspipeonthewall (ViessmanncoaxialPPSventsystemonly). Theconnectiontotheheatingcircuitsmust bemadeonsite(installationfittingsare suppliedintheInstallationFittingspackage suppliedwiththeboiler). Legend Mountingtemplate 5369 277 v1.5 Fig.6 CondensateConnection/NeutralizationUnit 11 CondensateConnection Installthecondensatedrainpipe(Ø 7/8”/ 22mm)withasuitablegradient(min.2.5%). Dischargecondensatefromtheboilerinto thedrainagesystem,eitherdirectlyor(if required)viaaneutralizationunit (accessory). CondensateconnectionforVitodens100-W modelWB1A8-24,8-30 ThecondensatedrainoftheVitodes100-W boilerisequippedwithabuilt-insiphontrap inordertokeepfluegasesfrombeing dischargedviathecondensatedrain. Dischargetubing Pipeventilationmusttakeplacebetween thesiphontrapandtheneutralizationunit(if applicable). CondensateDrainageandCondensateNeutralization Thecondensateformedbothinthe condensingboilerandinthefluegaspipe mustbedischargedintothepublicsewage systeminaccordancewithallapplicable localregulations.Thecondensateproduced byagas-firedheatingsystemhasapH valuebetween3and4. Somelocalcodesmayrequiretheuseofa separateneutralizationunittotreatthe aggressiveandcorrosivecondensate. Withaneutralizationunitinstalled,all condensatefromtheboilerandthefluegas pipeentersintotheneutralizationunit whereitistreatedandreleasedintothe publicsewagesystemwithasafepHvalue ofabove6.5. Theuseofneutralizationgranulate (performingtheneutralizingprocess)is dependentontheoperationoftheheating system.Todeterminetherequiredrefill amount,checkgranulatelevelseveraltimes duringthefirstyearofoperation.Insome casesonegranulatefillmaylastanentire year. ContactViessmanntoorderaneutralization unitfortheVitodens100-Wboiler. SeeViessmannPriceListfororder information. Thecondensatedischargeoutlettothe drainagesystemconnectionmustbeclearly visible.Itmustbeinstalledwithasuitable gradientandprovidedwithastenchtrap. Ifthecondensateoutletofthe Vitodens100-Wboilerislowerthanthe drain,acondensatepumpmustbeused. Onlycorrosion-resistantmaterialsmaybe usedforcondensatedrainagepurposes(e.g. braidedhose).Donotusegalvanized materialsormaterialscontainingcopperfor piping,couplingsetc.Thecondensatedrain musthaveatraptopreventfluegas leakage. Pleasenotethatotherrequirementsmay applydependingonlocalregulationsand/or project-specificdetails. Itisadvisabletocontactyourlocal waterworksoffice(authorityresponsiblefor wastewaterregulations)wellbefore commencingwiththeinstallationofthe neutralizationunitinordertoestablish detailsoflocalregulationsthatapply. Thefollowingtableshowstheconcentration of(effluent)substances(e.g.heavymetals) containedinthewastewaterfromthe Vitodens100-Wcondensingboiler. Condensate (effluent) substances Valuesmeasured inmg/ltr(effluent) substances Vitodens100 Lead Cadmium Chromium Copper Nickel Zinc Tin <0.01 <0.005 <0.01 <0.01 <0.01 <0.05 <0.05 5369 277 v1.5 Fig.7 IMPORTANT VentingOptions/ElectricalConnection 12 Vitodens100-WVentingOptions Foranoverviewofventingoptionsrefertotheappendixstartingonpage19.Fordetailed informationrefertotheVitodensVentingSystemInstallationInstructions. ElectricalConnection Allelectricalconnectionsaremadetothe boiler’sintegratedpowerpumpmodule(120 VAC/60Hz).Usedisconnectmeansand powerserviceswitchasperlocalcode requirements. ControlUnit Functionandconstruction ThecontrolisintegratedintotheVitodens 100-Wboiler. Integrateddiagnosticsystem Forroomtemperature-dependent operation,anexternalcontroloraroom temperaturethermostatmaybeconnected TocontrolDHWtemperature,aseparate DHWcontrollermaybeconnected Externalheatdemand 0-10V(fieldwiring) Viessmannoutdoortemperaturesensor (fieldwiring) OpenTherm(fieldwiring) Thecontrolunitconsistsof: LCDDisplay Selectordialforboilerwatertemperature adjustment Selectordialforservicesetting Temperatureadjustablehighlimit Boilertemperaturesensor Burnerfaultdisplay Burnerfaultreset Pressuregage Fuse Boilertemperaturesensor Theboilertemperaturesensorisconnected tothecontrolunitandbuiltintotheboiler. Frostprotection Frostprotectioniscontinuouslyactive.The burnerisswitchedONwhentheboiler watertemperaturereaches41°F/5°Cand isswitchedOFFagainwhentheboilerwater temperaturereachesatleast59°F/15°C (butnotmorethan68°F/20°C). Fordetailsonthecontrol,please refertotheVitodens100-W OperatingInstructions. 5369 277 v1.5 Vitodens100-WAccessories 13 AccessoriesfortheVitodens100-W NeutralizationUnitforSingle-Boiler Applications withneutralizinggranulate forVitodens100-W,WB1B10-26,10-35 PartNo.7134231 Low-LossHeader –Type80/50 PartNo.7134791 (max.flowrate17.6GPM/4m3/h) –Type120/80 PartNo.7134792 (max.flowrate35.2GPM/8m3/h) Alow-lossheaderoffersadditionalbenefits notprovidedbyapairofcloselyspaced tees.Viessmannstronglyrecommendsand preferstheuseofalow-lossheaderover closelyspacedtees.Whenusedin conjunctionwiththeVitodens100-Wboiler, thelow-lossheaderactsashydraulicbreak, decouplingboilerandsystemcircuitsfrom eachother(nosensorrequired).Itis recommendedtousethelow-lossheaderin applicationsinwhichthetotalsystemflow rateexceedsthemaximumorfallsbelow theminimumflowrateoftheVitodens 100-Wboiler.Formaximumboilerflow rates,seethetableonpage9inthis manual. Viessmannstronglyrecommendstheuseof alow-lossheaderincaseswherethe systemheadandflowratesareunknown. Inaddition,thelow-lossheaderhelps eliminateairanddebris[D]fromtheheating system.SeeFig.10and11foran illustrationoftheprincipleofoperation. Productdoesnotlookexactlyasillustrated. Thelow-lossheaderisavailableinthe followingsizes.Selectthesizebasedonthe maximumsystemflowrateofyour application. ModelNo.Max.systemflowrate Type80/50 17.6GPM/4m3/h Type120/80 35.2GPM/8m3/h Legend ABAirBleed BRBoilerReturn BSBoilerSupply BYBypass(withlaminarflow) DDebrisand/orair DVDrainValve SRSystemReturn SSSystemSupply TSViessmannTemperatureSensor(not used) SWSensorWell T1Boilersupplytemperature T2Boilerreturntemperature T3Systemsupplytemperature T4Systemreturntemperature Vprimary Boilercircuitflowrate Vsecondary Heatingcircuitflowrate Vbypass Bypassflowrate Qprimary Heatsuppliedbyboiler Qsecondary Heatconsumedbysystem Vprimary <Vsecondary T1>T3 T2=T4 Qprimary =Qsecondary T1 ±176°F/80°C Vsecondary=Vprimary+Vbypass Wheninstallingalow-lossheader,system mixedsupplytemperature(T3)mustbe calculatedasfollows: T3=T1× Vprimary+T4Vbypass Vsecondary 5369 277 v1.5 310mm DN40 14 5 m m Fig.8 Fig.9 DV BS SS SR BR TS BY AB D SW Fig.10 Low-lossheaderdesign T1 T2 Vprimary Vsecondary T3 T4 T4Vbypass Fig.11 PrincipleofOperation IMPORTANT StandardEquipment/HowtheVitodens100-WOperates.../ InstallationExamples 14 StandardEquipment TheVitodens100-Wgas-firedcondensing boilerwithInox-Radialheatexchanger surfaces,modulatingstainlesssteelMatriX cylindergasburner c/w installationfittingswith30psig pressurereliefvalve,airventand pressuregauge twofill/drainvalves allmountinghardware Theboilercomesfullypipedandprewired. Ventingmaterial(coaxial)istobe suppliedbyViessmannonly.Sidewall ventinstallationsmustincludeViessmann protectivescreen! Wallmountingcomponentry Thefollowingwallmountingcomponents aresuppliedwiththeVitodens100-W boiler: Mountingbracket Mountingbolts Installationfittings Screwsformountingbracketon –woodstuds(2”x4”) –metalstuds –brick/concretewall HowtheVitodens100-Wboiler operates... TheVitodens100-Wboilerusesapremix combustionsystem,whichisdesignedto deliveracertainair-gasmixturetothe burnerforcompletecombustion.Thegas isinjectedupstreamoftheblower.The burnerandheatexchangerarepartofa forced-draftdesign.Thebenefitsof forced-draftsystemsarelower componenttemperatures,directair-fuel connection(premix)forimprovedmixing, andlongerservicelifeoftheboilerdueto mildtomoderateambientconditions. TheMatriXcylinderburner,blowerand thecombinationgasvalvearefactory calibratedandpre-adjusted.Apneumatic linkbetweencombustionairandgas flowsguaranteesoptimalboiler performanceatallfiringrates.Blower speedisautomaticallyincreasedor decreasedbasedonheatdemand, therebyregulatingtheamountof combustionairdrawn.Thepneumaticlink betweenairandgasintroducesthe requiredamountofgasforoptimal combustiontomeetthecurrentheat demand,basedonalinearrelationship between Pairand Pgas. InstallationExamples Theexamplesonthefollowingpages depictpossiblepipinglayoutsofthe Vitodens100-Wboiler. Pleasenotethatthefollowingexamples aresimplifiedconceptualdrawingsonly! Pipingandnecessarycomponentrymust befieldverified.Alowwatercut-off (LWCO)mustbeinstalledwhererequired bylocalcodes.Properinstallationand functionalityinthefieldisthe responsibilityoftheheatingcontractor. 5369 277 v1.5 IMPORTANT InstallationExamples 15 SystemLayout1 Vitodens100-W,WB1B10-26,10-35withoneheatingcircuit SystemLayout1-AlternateOption Legend AVAirvent PRVPressurereliefvalve Vitodens100-W Roomthermostat Heatingcircuit Heatingcircuitpump(field supplied) Expansiontank PressureActivatedBy-Pass Pleasenote: Heatingcircuit C intheexamplesshould bedesignedto30ºFto40ºF/16.7ºCto 22.2ºC.ForlesserdeltaTdesign,system layoutdesignermustuseoneofthe examples(3or4)onthefollowingpages. Ensurethatapressureactivated by-passisinstallediftherearesystem component(s)in C thatmayisolate theflowtothepump D. Pleasenote! Theuseofalow-lossheaderis recommendedifthewaterflowrateis lessthan1.7GPM/400ltr/hormore than6.2GPM/1400ltr/h. Thelow-lossheaderisavailableas accessorypart. MaximumFlowRates ModelWB1B 10-26 10-35 t Output Btu/h 83,000 108,000 30ºFrise(GPM)5.5 ---- 35ºFrise(GPM)4.7 6.2 40ºFrise(GPM)4.2 5.4 5369 277 v1.5 PRV AV * Fig.12 F T--T PRV AV * Fig.13 F T--T IMPORTANT InstallationExamples 16 SystemLayout2 Vitodens100-W,WB1B10-26,10-35with... –DHWstoragetank –low-lossheader –oneheatingcircuit Primarypump mustpumpinto theboiler(asillustrated). AVAirvent PRVPressurereliefvalve TPVTemperatureandpressurerelief valve Vitodens100-Wgas-fired condensingboiler Externalboiler/DHWcontroller(field supplied) Heatingcircuit Heatingcircuitpump(fieldsupplied) DHWstoragetank DHWtanktemperatureaquastator sensor DHWcirculatingpump(field supplied) Low-lossheader Expansiontank Primarypump(boilercircuit,field supplied)withlow-lossheaderonly Pleasenote! Theuseofalow-lossheaderis recommendedifthewaterflowrateis lessthan1.7GPM/400ltr/hormore than6.2GPM/1400ltr/h. Thelow-lossheaderisavailableas accessorypart. MaximumFlowRates ModelWB1B 10-26 10-35 t Output Btu/h 83,000 108,000 30ºFrise(GPM)5.5 ---- 35ºFrise(GPM)4.7 6.2 40ºFrise(GPM)4.2 5.4 DHWsupplyandreturnpipingbetweenboilerDHWconnections andtheViessmannDHWtankconnections,shallbeaminimumof 1”nominalpipediameter(irrespectiveofthe¾”DHWconnectionoutletsizesprovidedontheboilerandtheDHWtank).This ensuresthattheheadofthepumpisfullyutilizedtoovercometheresistanceoftheDHWheatexchangercoilandtoprovide sufficientwaterflowtotheboilerheatexchanger.Innon-ViessmannDHWtankapplications,perform,inadditiontothe above, accuratecalculationsforDHWtankcoilpressuredropversusboilerpumpheadtoensuresufficientwaterflowtotheboilerheat exchanger.Failuretoheedtheaboveinstructionsmaycause boilershort-cyclingandinadequateDHWsupply. 5369 277 v1.5 AV PRV TPV Y Y Fig.14 IMPORTANT IMPORTANT InstallationExamples 17 SystemLayout3 Vitodens100-W,WB1B10-26,10-35withDHWstoragetankandoneheatingcircuit Primarypump mustpumpinto theboiler(asillustrated). AVAirvent PRVPressurereliefvalve TPVTemperatureandpressurerelief valve Vitodens100-Wgas-fired condensingboiler Externalboiler/DHWcontroller(field supplied) Heatingcircuit Heatingcircuitpump(fieldsupplied) DHWstoragetank DHWtanktemperatureaquastator sensor DHWcirculatingpump(field supplied) Closelyspacedtees,4xpipeØ or12”/305mm* Expansiontank Primarypump(boilercircuit,field supplied)withlow-lossheaderonly *Alow-lossheaderoffersadditional benefitsnotprovidedbyapairof closelyspacedtees.Viessmannstrongly recommendsandpreferstheuseofa low-lossheaderovercloselyspacedtees. Pleaseseepage13fordetails. Pleasenote! Theuseofalow-lossheaderis recommendedifthewaterflowrateis lessthan1.7GPM/400ltr/hormore than6.2GPM/1400ltr/h. Thelow-lossheaderisavailableasan accessorypart. MaximumFlowRates ModelWB1B 10-26 10-35 t Output Btu/h 83,000 108,000 30ºFrise(GPM)5.5 ---- 35ºFrise(GPM)4.7 6.2 40ºFrise(GPM)4.2 5.4 DHWsupplyandreturnpipingbetweenboilerDHWconnectionsandtheViessmannDHWtankconnections,shallbeaminimumof 1”nominalpipediameter(irrespectiveofthe¾”DHWconnectionoutletsizesprovidedontheboilerandtheDHWtank).This ensuresthattheheadofthepumpisfullyutilizedtoovercometheresistanceoftheDHWheatexchangercoilandtoprovide sufficientwaterflowtotheboilerheatexchanger.Innon-ViessmannDHWtankapplications,perform,inadditiontothe above, accuratecalculationsforDHWtankcoilpressuredropversusboilerpumpheadtoensuresufficientwaterflowtotheboilerheat exchanger.Failuretoheedtheaboveinstructionsmaycause boilershort-cyclingandinadequateDHWsupply. 5369 277 v1.5 AV PRV TPV Y Y 4xpipeØ or12”/305mm Fig.15 IMPORTANT IMPORTANT 18 SystemDesignConsiderations INTHECOMMONWEALTHOFMASSACHUSETTS... -thisproductshallbeinstalledbyalicensedplumberorgas fitter. -theflexibleconnector(ifused)maynotexceed36”. -anyleveltypeshutoffusedmustbeofteehandletype. Boilerlocation Asadirectventappliance,the Vitodens100-Wmaybeinstalledforroom airindependentoperation(sealed combustion)regardless ofsizeandventilation methodoftheroominwhichitislocated. TheVitodens100-Wmaybeinstalled,for example,inthemainlivingareaofahouse, innon-ventilatedutilityrooms,cupboards, closetsandalcoveswithnoclearance requiredfromcombustiblematerials,aswell asinatticswithadirectoutletfortheflue gas/freshairsystem.Followalllocaland nationalcodes. Fluegassystem ViessmanncoaxialPPS(Polypropylene- flameretardent)concentricfluegas/freshair systemsandtwo-pipestainlesssteel/CPVC systemsforroomairindependentoperation (sealedcombustion)andsidewallventing aretestedtoANSIZ21.13-CSA4.9- 2007standardsandarecertifiedtogether withtheVitodens100-Wboilerasa constructionalunit.TheVitodens100-W boilermayalsobeventedverticallyor horizontally,usingametallicAL29-4C® specialstainlesssteel,ornon-metallicCPVC single-wall,roomairdependentventing system(UL/ULClistedforcategoryIV). Foramoredetaileddescriptionofthedirect ventandsingle-wallventsystem,please refertotheVitodensVentingSystem InstallationInstructions. Fluegastemperatureprotection ViessmanncoaxialPPS(Polypropylene- flameretardent)fluepipesusedforthe Vitodens100-Wareratedformax.fluegas temperaturesofupto248°F/120°C. Fluegastemperatureprotectionisalso includedalthoughthemaximumpermissible fluegastemperaturewillnotbeexceededin anyoperatingconditionorintheeventof malfunctioning. Lowwatercut-off Alowwatercut-offmayberequiredby localcodes.Iftheboilerisinstalledabove theradiationlevel,alowwatercut-off deviceofapprovedtypemustbeinstalledin allinstances.Anapprovedlowwatercut-off devicethatmeetsgovernmentandlocal regulationsmustbeprovidedbytheheating contractor.Donotinstallanisolationvalve betweentheboilerandthelowwater cut-off.TheVitodens100-Wboilerhasa built-inflowswitch,whichmaybeaccepted bylocalcodesinlieuofalowwatercut-off. Systemlayout Themax.boilerwatertemperaturefor... –spaceheatingis180°F/82°C. –DHWproductionis172°F/78°C. Tominimizedistributionlosses, Viessmannrecommendsthattheheating anddomestichotwatersystemsbebased onamaximumboilersupplytemperature of158°F/70°C. Duetothelowreturntemperatures requiredforgascondensing,avoidtheuse ofmixingvalvesintheheatingcircuit wheneverpossible.Ifmixingvalvesare required,e.g.formulti-circuitsystemsor underfloorheatingsystems,only3-way mixingvalvesmaybeused. Donotuse4-waymixingvalvesina systemwithcondensingboilers. Waterconnections Vitodens100-Wboilerscanbeusedinany fullypumpedhotwaterheatingsystem. Minimumsystempressureis0.8bar/12psig. Chemicalcorrosionprotectionproducts Corrosiondoesnottypicallyoccurinsealed heatingsystemswhichhavebeencorrectly installedandarecorrectlyoperated. Manymanufacturersofplasticpipes recommendtheuseofchemicaladditives. Inthiscase,onlycommerciallyavailable corrosionprotectionproductsthathave beenapprovedforboilerswithdomestichot waterheatingviasingle-wallheat exchangers(instantaneousplateheat exchangersorDHWtanks)maybeused. Underfloorheatingsystems ForunderfloorheatingsystemsViessmann recommendstheuseofplastictubingwith anoxygendiffusionbarrierinorderto preventthediffusionofoxygenthrough tubing.Ifplastictubingwithoutanoxygen diffusionbarrierisusedinunderfloor heatingsystems,Viessmannrecommends thatsuchsystemsbeseparatedfromthe boilerwithaheatexchanger. Oxygendiffusionbarrier underfloortubing Theboilerwarrantydoesnotcoverleaks resultingfromcorrosioncausedbytheuse ofunderfloorplastictubingwithoutan oxygendiffusionbarrier.Suchsystemsmust havethenon-oxygendiffusionbarriertubing separatedfromtheboilerwithaheat exchanger.Viessmannrecommendstheuse ofunderfloorplastictubingwithanoxygen diffusionbarrier. Waterquality Treatmentforboilerfeedwatershouldbe consideredinareasofknownproblems, suchaswhereahighmineralcontentand hardnessexist.Inareaswherefreezing mightoccur,anantifreezemaybeaddedto thesystemwatertoprotectthesystem. Pleaseadheretothespecificationsgivenby theantifreezemanufacturer.Donotuse automotivesilicatebasedantifreeze.Please observethatanantifreeze/watermixture mayrequireabackflowpreventerwithinthe automaticwaterfeedandinfluence componentssuchasdiaphragmexpansion tanks,radiation,etc.Maximumantifreeze contentis50%fortheVitodens100-W boiler.Do not useantifreezeotherthan specificallymadeforhotwaterheating systems.Thesystemmayalsocontain componentswhichmightbenegatively affectedbyantifreeze.Checktotalsystem frequentlywhenfilledwithantifreeze. Advisesystemoperator/ultimateownerthat systemisfilledwithaglycolmix. Theheatingcontractormustprovidea MSDS(MaterialSafetyDataSheet)forthe antifreezeusedtothesystem operator/ultimateowner. Warranty Ourwarrantydoesnotcoverdamages resultingfromthefollowing: –installationorservicebyunqualifiedand unlicensedpersonnel. –attemptingtoperformanyrepairworkon theboilerotherthanthatmentionedinthe boilerliterature. –tamperingwithorattemptingtoreadjust thefactorysettingsofthecombination gasvalve –leaksresultingfromcorrosioncausedby theuseofunderfloorplastictubing withoutanoxygendiffusionbarrier. Fordetailedwarrantyinformation,please readwarrantysheetsuppliedwithproduct. 53 6 9 2 7 7 v 1 . 5 Appendix 19 Vitodens100-WVentingAlternatives VentingAlternatives VentSystemDiameter ViessmannCoaxialPPsVent 1 StainlessSteelVent 2 CPVCVent 3 Type Max.EquivalentLength(EqL)60/100 80/125 100/150 3”4”2”3”4”Diameter HorizontallyVented EqL 82/25 98/30 118/36 164/50 200/61 86/26 164/50 200/61 ft./m VerticallyVented EqL 82/25 98/30 118/36 164/50 200/61 86/26 164/50 200/61 ft./m SeePage(s)20-21 22-23 24-25 Page HorizontalIntake/ VerticallyVented EqL ———164/50 200/61 —164/50 200/61 ft./m SeePage(s)26 26 Page Selectventmaterialbasedonventconfiguration,preferredmaterial,andnecessary maximumequivalentlength. AlwaysfollowViessmannventinginstallationinstructions. -Do not commonventVitodens100-Wwithanyotherappliance. -Layoutsonthefollowingpagesarefor illustrative purposes only. -Do not usePriceListforinstallationpurposes.Thisis not adesigntool. 1 Sealedcombustion,coaxialventmaterialtobesuppliedbyViessmann only. 2 Stainlesssteelventmaterial must beULC/ULlisted,stainlesssteelAL29-4C®forCategoryIVboilers. Suggestedsources:FlexmasterCanadaLtd./Z-Flex(US)Inc.,Heat-fab,ProTechSystemsInc.,orSecurityChimneysInt’l. 3 CPVCventmaterial must beULC/ULlisted,forCategoryIVboilers.Suggestedsource:IPEXInc. Boilerstandardworkingpressure:30psig;maximum:45psig.For45psig,orderoptionalPRV9549944. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). StandardEquipment: Wall-mountboilerandinstallationfittingsc/w30psig pressurereliefvalve,pressuregage,gasshut-off valve,twofill/drainvalves,allmountinghardware, outdoortemperaturesensor,andLPconversionkit. 5369 277 v1.5 Appendix 20 CoaxialPPsVentSystem VentSystem 1 VentSystemDiameterVentSystem 60/100 80/125 100/150 Diameter HorizontallyVented MaximumEquivalent Length(EqL) 82/25 98/30 118/36 ft./m RoomAir IndependentOperation BasicHorizontalVentKit Ventingpiecescanbeordered individually,orasaconvenient kitusingtheOrderNo.tothe right;BasicVentKitincludes one ofeachoftheitemsnum- bered 2 to 5,and two MountingClips 6. 7424119 ——OrderNo. 1 BoilerVentPipeAdaptor 60/100 includedwithboiler B A A Adaptor,coaxial 60/100to80/125 (notshown) Adaptor,coaxial 60/100to100/150 (notshown) — — 7424112 — — 7424113 OrderNo. OrderNo. 2 90°Elbow EqL=1.6ft./0.5m 7424094 7424095 7424096 OrderNo. Combustion Air IntakeA 3 StraightPipe 2 3.3ft./1m 7424091 7424092 7424093 OrderNo. Combustion Air Intake FlueGasOutletB A 4 VentTermination 2.6ft./0.8m 7424100 7424101 7424102 OrderNo. 5 ProtectiveScreen 1 7134237 OrderNo. 6 MountingClip 2 (each)7424109 7424110 7424111 OrderNo. OtherAvailableVentPieces notshowninillustrationabove SlidingCoupling 1.25ft./0.4m 7424106 7424107 7424108 OrderNo. StraightPipe 2 1.6ft./0.5m 7424088 7424089 7424090 OrderNo. 45°Elbow (Setof2) EqL=1.0ft./0.3m 7424097 7424098 7424099 OrderNo. 1 PPscoaxialventmaterial must beULCS-636certifiedforCategoryIVboilers.Do not mixnon-ULCS-636withULCS-636venting. Sidewallventinginstallation must includeViessmannProtectiveScreen! 2 Order 1 MountingClipfor each straightlengthofventpipeinstalled. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 elbowsmaybeinstalledintheventsystem;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815.5369 277 v1.5 Appendix 21 CoaxialPPsVentSystem(continued) VentSystem 1 VentSystemDiameterVentSystem 60/100 80/125 100/150 Diameter VerticallyVented MaximumEquivalent Length(EqL) 82/25 98/30 118/36 ft./m RoomAir IndependentOperation BB 1 BoilerVentPipeAdaptor 60/100 includedwithboiler AA Adaptor,coaxial 60/100to80/125 (notshown) Adaptor,coaxial 60/100to100/150 (notshown) — — 7424112 — — 7424113 OrderNo. OrderNo. 2 90°Elbow EqL=1.6ft./0.5m 7424094 7424095 7424096 OrderNo. 6 MountingClip 2 (each)7424109 7424110 7424111 OrderNo. 8 SlidingCoupling 1.25ft./0.4m 7424106 7424107 7424108 OrderNo. 9 StraightPipe 2 1.6ft./0.5m StraightPipe 2 3.3ft./1m 7424088 or 7424091 7424089 or 7424092 7424090 or 7424093 OrderNo. OrderNo. 45°Elbow (Setof2) EqL=1ft./0.3m 7424097 7424098 7424099 OrderNo. CombustionAirIntake FlueGasOutletB A VentTermination 3.9ft./1.2m 7424103 7424104 7424105 OrderNo. RoofFlashing andStormCollar (B-Ventmaterialorbetter) field supplied 1 PPscoaxialventmaterial must beULCS-636certifiedforCategoryIVboilers.Do not mixnon-ULCS-636withULCS-636venting. 2 Order 1 MountingClipfor each straightlengthofventpipeinstalled. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 elbowsmaybeinstalledintheventsystem;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815. 5369 277 v1.5 Appendix 22 StainlessSteelVentSystem VentSystem 1 VentSystemDiameterVentSystem 3”4”Diameter HorizontallyVented MaximumEquivalent Length(EqL) a+b 164/50 200/61 ft./m RoomAir Independent Operation 1 BoilerVentAdaptor includedwithboiler b Independent Operation 2 Adaptor,forstainlesssteel 60/100to80/125 (outershellremoved) 7424112 OrderNo. a A B 3 Adaptor(s),stainlesssteel 80mmto3” 3”to4” (notshown) field supplied — field supplied and field suppliedA 4 VentingSupport 2 fieldsupplied 5 ULC/ULlistedStainlessSteelVent Material 1forEqLcalculations,use: 45°Elbow EqL=2ft./0.6m 90°Elbow EqL=3ft./0.9m fieldsupplied Combustion Air IntakeA 6 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. Combustion Air Intake Flue Gas OutletB A 7 2”to3”or 2”to4”fieldsuppliedFlueGasOutletB 8 CombustionAirIntakeVentMaterial Allowablematerials:seenotebelow 3 fieldsupplied 9 BirdScreenc/wTermination forstainlesssteel fieldsupplied RoomAir DependentOperation 1 BoilerVentAdaptor includedwithboiler b Dependent Operation B 2 Adaptor,forstainlesssteel 60/100to80/125 (outershellremoved) 7424112 OrderNo. AA B 3 Adaptor(s),stainlesssteel 80mmto3” 3”to4” (notshown) field supplied — field supplied and field supplied 4 VentingSupport 2 fieldsupplied CombustionAirIntake Flue Gas OutletB AC 5 ULC/ULlistedStainlessSteelVent Material 1forEqLcalculations,use: 45°Elbow EqL=2ft./0.6m 90°Elbow EqL=3ft./0.9m fieldsupplied a=zero Flue Gas Outlet AirOpening B C 9 BirdScreenc/wTermination forstainlesssteel fieldsupplied 1 Stainlesssteelventmaterial must beULC/ULlisted,stainlesssteelAL29-4C®forCategoryIVboilers. Suggestedsources:FlexmasterCanadaLtd./Z-Flex(US)Inc.,Heat-fab,ProTechSystemsInc.,orSecurityChimneysInt’l. 2 Boilercannotsupportweightofventsystem.Supportventingasprescribedinventmanufacturer’sinstallationinstructions. 3 Combustionairsupplypipemaybemadeofthefollowingmaterials:ABS,CPVC,PVC,orstainlesssteel. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 x90°elbowsmaybeinstalledintheairintakeandflueoutlet combined;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815.5369 277 v1.5 Appendix 23 StainlessSteelVentSystem (continued) VentSystem 1 VentSystemDiameterVentSystem 3”4”Diameter VerticallyVented MaximumEquivalent Length(EqL) a+b 164/50 200/61 ft./m ARoomAir Independent Operation B 1 BoilerVentAdaptor includedwithboilerAIndependentOperationB 2 Adaptor,forstainlesssteel 60/100to80/125 (outershellremoved) 7424112 OrderNo. b 3 Adaptor(s),stainlesssteel 80mmto3” 3”to4” (notshown) field supplied — field supplied and field supplied a 4 VentingSupport 2 fieldsupplied a 5 ULC/ULlistedStainlessSteelVent Material 1forEqLcalculations,use: 45°Elbow EqL=2ft./0.6m 90°Elbow EqL=3ft./0.9m fieldsupplied 6 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. 7 2”to3”or 2”to4”fieldsupplied Combustion Air IntakeA 8 CombustionAirIntakeVentMaterial 3 fieldsupplied Combustion Air Intake Flue Gas OutletB A 9 BirdScreenc/wTermination fieldsupplied RoomAir DependentOperation B 1 BoilerVentAdaptor includedwithboiler 2 Adaptor,forstainlesssteel 60/100to80/125 (outershellremoved) 7424112 OrderNo. AA b 3 Adaptor(s),stainlesssteel 80mmto3” 3”to4” (notshown) field supplied — field supplied and field supplied 4 VentingSupport 2 fieldsupplied Combustion Air IntakeA C 5 ULC/ULlistedStainlessSteelVent Material 1forEqLcalculations,use: 45°Elbow EqL=2ft./0.6m 90°Elbow EqL=3ft./0.9m fieldsupplied Combustion Air Intake FlueGasOutlet AirOpening a=zero B A C 9 BirdScreenc/wTermination forstainlesssteel fieldsupplied 1 Stainlesssteelventmaterial must beULC/ULlisted,stainlesssteelAL29-4C®forCategoryIVboilers. Suggestedsources:FlexmasterCanadaLtd./Z-Flex(US)Inc.,Heat-fab,ProTechSystemsInc.,orSecurityChimneysInt’l. 2 Boilercannotsupportweightofventsystem.Supportventingasprescribedinventmanufacturer’sinstallationinstructions. 3 Combustionairsupplypipemaybemadeofthefollowingmaterials:ABS,CPVC,PVC,orstainlesssteel. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 x90°elbowsmaybeinstalledintheairintakeandflueoutlet combined;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815. 5369 277 v1.5 IMPORTANT: DonotuseanyDWVplumbing pipestoventthisboiler. Appendix 24 CPVCVentSystem VentSystem 1 VentSystemDiameterVentSystem 2”3”4”Diameter HorizontallyVented MaximumEquivalenta+b Length(EqL) 86/26 164/50 200/61 ft./m RoomAir Independent Operation 1 BoilerVentAdaptor includedwithboiler b Independent Operation 2 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. a A B 3 Adaptor(s),CPVC 2”to3” 3”to4” (notshown) — — field supplied — field supplied and field supplied A 4 VentingSupport 2 fieldsupplied 5 ULC/ULlistedCPVCVentMaterial 1 forEqLcalculations,use: 45°Elbow EqL=3ft./0.9m 90°Elbow EqL=5ft./1.5m fieldsupplied 6 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. CombustionAirIntake Flue Gas OutletB A 7 2”to3”or 2”to4”fieldsupplied FlueGasOutletB 8 CombustionAirIntakeVentMaterial Allowablematerials:seenotebelow 3 fieldsupplied 9 BirdScreen (Setof2) forCPVC 7134780 7134781 7134782 OrderNo. b RoomAir DependentOperation 1 BoilerVentAdaptor includedwithboiler b AA B 2 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. AA B 3 Adaptor(s),CPVC 2”to3” 3”to4” (notshown) — — field supplied — field supplied and field supplied 4 VentingSupport 2 fieldsupplied C CombustionAirIntake Flue Gas OutletB A 5 ULC/ULlistedCPVCVentMaterial 1 forEqLcalculations,use: 45°Elbow EqL=3ft./0.9m 90°Elbow EqL=5ft./1.5m fieldsupplied a=zero Flue Gas Outlet AirOpening B C 9 BirdScreen (Setof2) forCPVC 7134780 7134781 7134782 OrderNo. 1 CPVCventmaterial must beULC/ULlisted,forCategoryIVboilers.Suggestedsource:IPEXInc. 2 Boilercannotsupportweightofventsystem.Supportventingasprescribedinventmanufacturer’sinstallationinstructions. 3 Combustionairsupplypipemaybemadeofthefollowingmaterials:ABS,CPVC,PVC,orstainlesssteel. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 x90°elbowsmaybeinstalledintheairintakeandflueoutlet combined;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815. 5369 277 v1.5 IMPORTANT: DonotuseanyDWVplumbing pipestoventthisboiler. Appendix 25 CPVCVentSystem(continued) VentSystem 1 VentSystemDiameterVentSystem 2”3”4”Diameter VerticallyVented MaximumEquivalenta+b Length(EqL) 86/26 164/50 200/61 ft./m ARoomAir Independent Operation B 1 BoilerVentAdaptor includedwithboilerAIndependentOperationB 2 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. b 3 Adaptor(s),CPVC 2”to3” 3”to4” (notshown) — — field supplied — field supplied and field supplied 4 VentingSupport 2 fieldsupplied a 5 ULC/ULlistedCPVCVentMaterial 1 forEqLcalculations,use: 45°Elbow EqL=3ft./0.9m 90°Elbow EqL=5ft./1.5m fieldsupplied 6 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. 7 2”to3”or 2”to4”fieldsupplied Combustion Air IntakeA 8 CombustionAirIntakeVentMaterial Allowablematerials:seenotebelow 3 fieldsupplied Combustion Air Intake FlueGasOutletB A 9 BirdScreen (Setof2) forCPVC 7134780 7134781 7134782 OrderNo. RoomAir DependentOperation B 1 BoilerVentAdaptor includedwithboiler 2 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. AA b 3 Adaptor(s),CPVC 2”to3” 3”to4” (notshown) — — field supplied — field supplied and field supplied 4 VentingSupport 2 fieldsupplied Combustion Air IntakeA C 5 ULC/ULlistedCPVCVentMaterial 1 forEqLcalculations,use: 45°Elbow EqL=3ft./0.9m 90°Elbow EqL=5ft./1.5m fieldsupplied Combustion Air Intake FlueGasOutlet AirOpening B A C a=zero 9 BirdScreen (Setof2) forCPVC 7134780 7134781 7134782 OrderNo. 1 CPVCventmaterial must beULC/ULlisted,forCategoryIVboilers.Suggestedsource:IPEXInc. 2 Boilercannotsupportweightofventsystem.Supportventingasprescribedinventmanufacturer’sinstallationinstructions. 3 Combustionairsupplypipemaybemadeofthefollowingmaterials:ABS,CPVC,PVC,orstainlesssteel. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 x90°elbowsmaybeinstalledintheairintakeandflueoutlet combined;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815.5369 277 v1.5 IMPORTANT: DonotuseanyDWVplumbing pipestoventthisboiler. Appendix 26 CPVCorStainlessSteelVentSystem VentSystem 1 VentSystemDiameterVentSystem 2”3”4”Diameter HybridVentSystem HorizontalIntake/VerticallyVented MaximumEquivalenta+b Length(EqL) 86/26 164/50 200/61 ft./m RoomAir Independent Operation 1 BoilerVentAdaptor includedwithboilerIndependentOperation B 2 Adaptor,forstainlesssteel 60/100to80/125 (outershellremoved) —7424112 OrderNo. 2 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. 3 Adaptor(s),stainlesssteel 80mmto3” 3”to4” (notshown) — — field supplied — field supplied and field supplied b 3 Adaptor(s),CPVC 2”to3” 3”to4” (notshown) — — field supplied — field supplied and field supplied a 4 VentingSupport 2 fieldsupplied a A 5 ULC/ULlisted StainlessSteelVentMaterial 1a forEqLcalculations,use: 45°Elbow EqL=2ft./0.6m 90°Elbow EqL=3ft./0.9m or fieldsupplied CombustionAirIntake FlueGasOutletB A 5 ULC/ULlisted CPVCVentMaterial 1b forEqLcalculations,use: 45°Elbow EqL=3ft./0.9m 90°Elbow EqL=5ft./1.5m fieldsupplied 6 Adaptor(s),CPVC 60mmto2” 7134769 OrderNo. 7 2”to3”or 2”to4”fieldsupplied 8 CombustionAirIntakeVentMaterial Allowablematerials:seenotebelow 3 fieldsupplied 9 BirdScreenc/w Termination forstainlesssteel or fieldsupplied 9 BirdScreen (Setof2) forCPVC 7134780 7134781 7134782 OrderNo. 1aStainlesssteelventmaterial must beULC/ULlisted,stainlesssteelAL29-4C®forCategoryIVboilers. Suggestedsources:FlexmasterCanadaLtd./Z-Flex(US)Inc.,Heat-fab,ProTechSystemsInc.,orSecurityChimneysInt’l. 1bCPVCventmaterial must beULC/ULlisted,forCategoryIVboilers.Suggestedsource:IPEXInc. 2 Boilercannotsupportweightofventsystem.Supportventingasprescribedinventmanufacturer’sinstallationinstructions. 3 Combustionairsupplypipemaybemadeofthefollowingmaterials:ABS,CPVC,PVC,orstainlesssteel. Do not includefirst90°elbowinequivalentventlengthcalculations(thisappliestoallventmaterials). A maximum of 5 x90°elbowsmaybeinstalledintheairintakeandflueoutlet combined;do not exceedmaximumequivalentventlength. AlwaysfollowViessmannventinginstallationinstructions5368815.5369 277 v1.5 27 5369 277 v1.5 ViessmannManufacturingCompanyInc. 750McMurrayRoad Waterloo,Ontario N2V2G5 Canada 1-800-387-7373 Fax(519)885-0887 www.viessmann.ca info@viessmann.ca ViessmannManufacturingCompany(U.S.)Inc. 45AccessRoad Warwick,RhodeIsland 02886 USA 1-800-288-0667 Fax(401)732-0590 www.viessmann-us.com info@viessmann-us.com 28 5369 277 v1.5 Te c h n i c a l i n f o r m a t i o n s u b j e c t t o c h a n g e w i t h o u t n o t i c e . Pr i n t e d o n e n v i r o n m e n t a l l y f r i e n d l y (r e c y c l e d a n d r e c y c l a b l e ) p a p e r .