B13-0058 LOAD CALCS.pdf
A-Phase Electric, LLC Load Calculation Montaneros Unit 316 General Lighting and Receptacle Demand Load: 1159 sq. ft. x 3VA= 3477 220.3(a) 1,500 VA x 2= 3000 220.16(a) 1,500 VA x 1 = 1500 220.16(b) Total connected load: 7,977 3,000 VA @ 100%= 3,000 220.11 VA @ 35%= 1,742.0 609.683 Total general lighting and Receptacle demand load: 3,610 Range demand load: 12,000VA 8,000 220.19 Dryer Load: 5,000 220.18 Fixed appliance load: 1.2 kva 0 0 .8 kva 0 0 0 0 Steamer 3 kva 1 3,000 0 0 Total fixed appliance load: 3,000 A-Phase Electric, LLC Load Calculation Montaneros Unit 316 Heating load: Boiler 0.2 0 0 Pump 0.2 0 0 Baseboard heat .25/ft 24 6,000 Heat Tape 1.2 kva 0 0 Total heating load: 6,000 25% of largest motor: 1,200 Totals: General lighting and receptacles: 3,610 Range: 8,000 Dryer:. 5,000 Fixed appliance: 3,000 Heating: 6,000 25%of largest motor: 1,200 Total: VA 26,810 AMPS 111.71 Installed Service Size: 125A single phase 120/240 Secondary Conductors: 1/0 Aluminum Distance from vault to meter: 110,