HomeMy WebLinkAboutA13-0016 A13-0017 SPECS.PDF r0ti0 S E G O R I T Y S O L U T i ry w$ 1 II_ _ . _ __ _ 'r'_ i East Vail Duplex Residences Vail, CO Fire Alarm Submittal Manual FTSwww.fireteamsecu ritv.co m INC DF-60601:A1 •Al-60 MS-92000DLS(E) Rev 3 FirellTeALaf ms Intelligent Addressable FACP with Built-In Communicator by Honeywell Addressable Fire Alarm Control Panel General The Fire-Lite MS-92000DLS Rev 3 with Version 5.0 firmware is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact intelligent addressable control panel has an extensive list of powerful features. While the MS-92000DLS Rev 3 may be used with an SLC configured in the CLIP(Classic Loop Interface Protocol)mode, it can also operate in LiteSpeedTM mode—Fire•Lite's latest polling technology—for a quicker device response time. LiteSpeed's patented technology polls 10 devices at a time. This improvement allows a fully loaded panel with up to 198 devices to report an incident and activate the notification cir- cuits in under 10 seconds.With Litespeed polling, devices can be wired on standard twisted, unshielded wire up to a distance of 10,000 feet. - - AIA- The MS-92000DLS Rev 3's quick-remove chassis protects the electronics during construction. The backbox can be installed allowing field wiring to be pulled. When construction is com- pleted, the electronics can be quickly installed with just two bolts. New features for Rev 3 with Version 5.0 firmware include ol removable terminal blocks, improved transient protection, additional secondary ANN-BUS, and increased power for the by Hone"ZI�7 resettable and remote sync outputs. Available accessories include ANN-BUS devices as well as Features ACS LED, graphic and LCD annunciators, and reverse polar Listed to UL standard 864, 9th edition. ity/city box transmitter. The integral DACT transmits system status(alarms,superviso- . On-board DACT. ries, troubles, AC loss, etc.) to a Central Station via the public . Remote site or local USB port upload/download, using PS- switched telephone network. It also allows remote and local Tools. programming of the control panel using the PS-Tools Upload/ • Four(4) Style Y (Class B) NAC circuits, which can be con- Download utility. In addition, the control panel may be pro- verted to four (4) Style Z (Class A) circuits with optional grammed or interrogated off-site via the public switched tele- ZNAC-92 converter module. (Up to 6.0 amps total NAC phone network. Any personal computer with Windows®XP or power when using optional XRM-24B.) greater, a compatible modem, and PS-Tools—the Fire-Lite . Selectable strobe synchronization for System Sensor, Upload/Download software kit—may serve as a Service Termi- Wheelock,and Gentex devices. nal. This allows download of the entire program or upload of Remote Acknowledge,Silence, Reset and Drill via address- the entire program, history file, walktest data, current status able monitor modules or LCD-80F,ANN-80 or Legacy ACS and system voltages. The panel can also be programmed Annunciators. through the FACP's keypad or via a standard PS-2 computer keyboard,which can be plugged directly into the printed circuit ANN BUS for connection to following optional modules(cannot board. This permits easy typing of address labels and other be used if ACS annunciators are used): programming information. –ANN-80(-W) Remote LCD Annunciator Version 5.0 firmware supports the following: Primary and Sec- –ANN-I/O LED Driver ondary ANN-bus devices,AD355(LiteSpeed), USB port, NAC –ANN-S/PG Printer Module circuit diagnostics, a new report has been added to the walk- –ANN-RLY Relay Module test that lists untested devices, new device types added:audio telephone type code for ACC 25/50ZST, Photo Supervisory –ANN LED Annunciator Module and auto-resettable Drill (non-latching). –ANN-BLED Annunciator Module alarms only The Fire Watch Series internet monitoring modules IPDACT-2 –ROME Relay Option Module Enclosure and IPDACT-2UD permit monitoring of alarm signals over the ACS/TERM: Internet saving the monthly cost of two dedicated business –ACS Annunciators: Up to 32 Legacy ACM Series annun- telephone lines. Although not required, the secondary tele- ciators(ACM-16AT or ACM-32 series). Cannot be used if phone line may be retained providing backup communication ANN-BUS devices are used. over the public switched telephone line. –Terminal-mode Annunciators: Up to 32 Legacy LCD-80F NOTE: Unless otherwise specified, the term MS-92000DLS is remote annunciators. used in this document to refer to both the MS-92000DLS and the MS-92000DLS(E)FACPs(Fire Alarm Control Panels). DF-60601:A1•12/07/2010—Page 1 of 6 • EIA-232 printer/PC interface (variable baud rate) on main • Supervisory(yellow) circuit board,for use with optional UL-listed printer PRN-617. . Alarm Silenced(yellow) • Integral 80-character LCD display with backlighting. • System Trouble(yellow) • Real-time clock/calendar with automatic daylight savings • Maintenance/Presignal (yellow) control. • Disabled (yellow) • Detector sensitivity test capability(NFPA 72 compliant). . Battery Fault(yellow) • History file with 1,000-event capacity. • Ground Fault(yellow) • Maintenance alert warns when smoke detector dust accu- mulation is excessive. KEYPAD CONTROLS • Automatic device type-code verification. • Acknowledge/Step • One person audible or silent walk test with walk-test log and • Alarm Silence printout. • Drill • Point trouble identification. • System Reset(lamp test) • Waterflow(nonsilenceable)selection per monitor point. • 16-key alpha-numeric pad(similar to telephone keypad) • System alarm verification selection per detector point. • 4 cursor keys • PAS (Positive Alarm Sequence) and presignal delay per . Enter point(NFPA 72 compliant). NOTE:Only detectors may participate in PAS. Product Line Information SLC LOOP: MS-92000DLS: 198-point addressable Fire Alarm Control • SLC can be configured for NFPA Style 4,6, or 7 operation. Panel, one SLC loop. Includes 80-character LCD display, sin- • SLC supports up to 198 addressable devices per loop (99 gle printed circuit board mounted on chassis,and cabinet. 120 detectors and 99 monitor,control,or relay modules). VAC operation. • SLC loop maximum length 10,000 ft. (3,000 m.). MS-92000DLSE: Same as MS-92000DLS, except with 240 See installation manual for wire tables. VAC operation. NOTIFICATION APPLIANCE CIRCUITS(NA CS): 4XTMF Reverse Polarity Transmitter Module: Provides supervised output for local energy municipal box transmitter, • Four onboard NACs with additional NAC capability using alarm,and trouble. output control modules (CMF-300 or CMF-300-6). The four ZNAC-92: Optional converter module which converts four (4) Class B NACs can be converted to four Class A NACs with Style Y(Class B) NAC circuits to four(4) Style Z(Class A)cir- optional ZNAC-92 converter module. cuits. • Silence Inhibit and Auto Silence timer options. Continuous, March Time, Temporal or California code for PK-CD Programming software for Windows® • -based PC com- main circuit board NACs with two-stage capability. puter(cable not included),available on www.firelite.com. • Selectable strobe synchronization per NAC. DP-9692: Optional dress panel for MS-92000DLS Rev 3. • 2.5 amps maximum per each NAC circuit. TR-CE: Optional trim Ring for semi-flush mounting. NOTE: Maximum 24VDC system power output is shared among BB-26: Battery backbox, holds up to two 25 AH batteries and all NAC circuits and 24VDC special-application auxiliary power CHG-75. outputs. Total available output is 3.0 amps. Using the optional BB-55F: Battery box, houses two 55 AH batteries. XRM-24B transformer increases 24VDC output to 6.0 amps. PROGRAMMING AND SOFTWARE: CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. • Autoprogram (learn mode) reduces installation time. CHG-120F: Remote battery charging system for lead-acid bat- • Custom English labels(per point) may be manually entered teries with a rating of 55 to 120 AH. Requires additional BB- or selected from an internal library file. 55F for mounting. • Three Form-C relay outputs(two programmable). BAT Series: Batteries,see data sheet DF-52397. • 99 software zones. XRM-24B(E): Optional transformer. Increases system power • Continuous fire protection during online programming at the output to 6.0 amps. Use XRM-24BE with MS-92000DLS Rev front panel. 3(E). • Program Check automatically catches common errors not PRT/PK-CABLE: Cable printer/personal computer interface linked to any zone or input point. cable; required for printer or for local upload/download pro- • OFFLINE PROGRAMMING: Create the entire program in gramming and updating panel firmware. your office using a Windows®-based software package PRN-6F: UL listed compatible event printer. Uses tractor-fed (order programming kit PS-Tools, separately). Upload/ download system programming locally to the MS- Paper. 92000DLS Rev 3 in less than one minute. IPDACT 2/2UD, IPDACT Internet Monitoring Module: • USB upload/download programming with standard Male-A Mounts in bottom of enclosure with optional mounting kit (PN to Male-B cable. IPBRKT). Connects to primary and secondary DACT tele- phone output ports for internet communications over customer User Interface provided ethernet internet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP LED INDICATORS or static IP. (See data sheet DF-60407 or DF-52424 for more • AC Power(green) information.) • Fire Alarm(red) Page 2 of 6—DF-60601:A1•12/07/2010 IPBRKT: Mounting kit for IPDACT-2/2UD in common enclo- DNRW: Innovair Flex low-flow non-relay duct-detector hous- sure. ing, with NEMA-4 rating. Watertight. (Order SD355R sepa- IPSPLT: Y-adaptor option allows connection of both panel rately.) dialer outputs to one IPDACT-2/2UD cable input. MMF-300: Addressable Monitor Module for one zone of nor- mally-open dry-contact initiating devices. Mounts in standard COMPAT/BLEANNUNCIATORS 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of- ANN-80(-W): LCD Annunciator is a remote LCD annunciator line resistor. Module may be configured for either a Style B that mimics the information displayed on the FACP LCD dis- (Class B)or Style D(Class A) IDC. play. Recommended wire type is un-shielded. (Basic model is MDF-300: Dual Monitor Module. Same as MMF-300 except it red;order-W version for white;see DF-52417.) provides two Style B(Class B)only IDCs. ANN-LED: Annunciator Module provides three LEDs for each MMF-301: Miniature version of MMF-300. Excludes LED and zone: Alarm, Trouble and Supervisory. Ships with red enclo- Style D option. Connects with wire pigtails. May mount in sure(see DF-60241). device backbox. ANN-BLED: Provides alarm (red) indicators for up to 30 input MMF-302: Similar to MMF-300, but may monitor up to 20 con- zones or addressable points. (See DF-60241). ventional two-wire detectors. Requires resettable 24 VDC ANN-RLY: Relay Module, which can be mounted inside the power. Consult factory for compatible smoke detectors. cabinet, provides 10 programmable Form-C relays. (See DF- 52431.) ROME: Relay Option Module Enclosure. Provides one ANN- RLY Relay Module already installed. The ROME Series pro- vides mounting space for one additional Relay Module or one addressable Multi-module. (See Installation Sheet PN 53530.) ANN-S/PG: Serial/Parallel Printer Gateway module provides a connection for a serial or parallel printer. (See DF-52429.) ANN-1/0: LED Driver Module provides connections to a user supplied graphic annunciator. (See DF-52430.) ACM-8RF: Relay module provides 8 Form-C 5.0 amp relays. ACS-LED Zone Series: LED-type fire annunciators capable of providing up to 99 software zones of annunciation.Available in increments of 16 or 32 points to meet a variety of applications. LDM Graphic Series: Lamp Driver Module series for use with custom graphic annunciators. LCD-80F (Liquid Crystal Display) point annunciator: 80-character, backlit LCD-type fire annunciators capable of displaying English-language text. NOTE:For more information on Compatible Annunciators for use with the MS-92000DLS Rev 3,see the following data sheets(doc- ument numbers) ACM-8RF (DF-51555), ACS/ACMSeries (DF- 52378),LDM Series(DF-51384),LCD-80F(DF-52185). LITESPEED COMPATIBLE ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. CP355:Addressable low-profile ionization smoke detector. SD355:Addressable low-profile photoelectric smoke detector. SD355T: Addressable low-profile photoelectric smoke detec- tor with thermal sensor. SD355R: Addressable remote test capable detector for use with D355PL or DNR(W)duct smoke detector housings. H355: Fast-response, low-profile heat detector. H355R: Fast-response, low-profile heat detector with rate-of- rise option. H355HT: Fixed high-temperature detector that activates at 190F/88C. AD355(A): Low-profile, intelligent, "Adapt' multi-sensor detec- tor(B350LP base included). BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitivity test. D355PL: Innovair Flex low-flow non-relay duct-detector hous- ing.SD355R included. DF-60601:A1•12/07/2010—Page 3 of 6 CMF-300: Addressable Control Module for one Style Y/Z (Class B/A) zone of supervised polarized Notification Appli- ances. Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance Circuit option requires external 24 VDC to power notification appliances. CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box,surface mount using ---� the SM13500. BG-12LX:Addressable manual pull station with interface mod- MS-92000DLS Remote ACC-25/50(ZS/T) ule mounted inside. Fire Alarm ; ; Microphone Audio Command Control Panel Center 1300: Fault Isolator Module.This module isolates the SLC loop o from short circuit conditions (required for Style 6 or 7 opera- tion). SPR SMB500: Used to mount all modules except the MMF-301 and Speaker o p ( _ M301. SD355 — SPC MMF-300-10: Ten-input monitor module. Mount one or two Photo Detector s� Series modules in a BB-2F cabinet (optional). Mount up to six mod- Speaker ules on a CHS-6 chassis in a 1313-61F. LCD-80F MMF-302-6: Six-zone interface module for compatible conven- tional two-wire detectors. Mount one or two modules in a BB- 2F cabinet (optional). Mount up to six modules on a CHS-6 AD355 SPS chassis in a BB-6F. Adapt Detector Series Speaker/Strobe CMF-300-6: Six-circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six ANN-80 modules on a CHS-6 chassis in a BB-617. CRF-300-6: Six Form-C relay control module. Mount one or H355/H355R/H355HT two modules in a BB-2F cabinet (optional). Mount up to six Heat Detector Im modules on a CHS-6 chassis in a 1313-6F. P211 NOTE: 1)For more information on Compatible Addressable Strobe Devices for use with the MS-92000DLS Rev 3, see the following MH data sheets (document numbers): AD355 (DF-52324), BG-12LX (DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-60379), MDF-300 CMF/CRF Series (DF-52130), CP355 (DF-52383), D355PL (DF- Dual Monitor Module 52398), H355 Series (DF-52385), 1300 (DF-52389), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF- P211 302-6 (DF-52356), SD355/SD355T (DF-52384). 2)Legacy 300 Strobe Series detection devices such as the CP300 1CP350, SD300(T)/ Power Supply SD350(T) and older modules such as the M300, M301, M302, SD355T FCPS-24FS6 C304,and BG-10LX are not compatible with LiteSpeed polling. If Photo/'rhermal FCPS 24FS8 ti Jp the SLC contains one of these devices, polling must be set for standard LiteSpeed protocol. Please consult factory for further P2R information on previous 300 Series devices. Strobe Wiring Requirements MMF-300 Multi-Modules Monitor Module While shielded wire is not required, it is recommended that all • CRF-300-6 Six-Relay Control Module SLC wiring be twisted-pair to minimize the effects of electrical • CMF-300-6 Six-Circuit Supervised Control Module interference. Wire size should be no smaller than 18 AWG • MMF-302-6 Six-Zone Interface Module (0.78 mm2) and no larger than 12 AWG (3.1 mm2). The wire • MMF-300-10 Ten-Input Monitor Module size depends on the length of the SLC circuit. Refer to the MMF-302 panel manual for wiring details. Wire Detector Monitor Module D355PL Beam Detector/Beam355 Duct Detector mmMS-92000DLS ADDRESSABLE FIRE ALARM BG-1 2LX Addressable CONTROL PANEL Manual Pull Station Page 4 of 6—DF-60601:A1•12/07/2010 DF-60601:A1•12/07/2010—Page 5 of 6 SYSTEM SPECIFICATIONS System Capacity 16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring • Intelligent Signalling Line Circuits.......................................1 (TR-CE): 22.00" (55.88 cm.) high x 19.65"(49.91 cm.)wide. • Addressable device capacity..........................................198 Shipping Specifications • Programmable software zones.........................................99 Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00"(50.80 cm.) • ACS Annunciators............................................................32 high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. • ANN-bus devices..............................................................16 Temperature and Humidity Ranges Electrical Specifications This system meets NFPA requirements for operation at 0 — AC Power: MS-92000DLS Rev 3: 120 VAC, 60 Hz, 3.0 amps. 49°C/32 — 120°F and at a relative humidity 93% ± 2% RH MS-92000DLS Rev 3E:240 VAC,5 0 Hz, 1.5 amps.Wire size: (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the minimum 14 AWG (2.00 mm2)with 600 V insulation. useful life of the system's standby batteries and the electronic Battery charger capacity: 7 AH - 18 AH batteries. Up to two components may be adversely affected by extreme tempera- 18 Ah batteries can be housed in the FACP cabinet. Larger ture ranges and humidity. Therefore, it is recommended that batteries require an external battery charger such as the CHG- this system and its peripherals be installed in an environment 75 or CHG-120, and a separate battery cabinet such as the with a normal room temperature of 15—27°C/60—80°F. BB-26 or NFS-LBB. Communication Loop: Supervised and power-limited. NFPA Standards Notification Appliance Circuits: Each terminal block pro- The MS-92000DLS Rev 3 complies with the following NFPA vides connections for two Style Y (Class B) for a total of four 72 Fire Alarm Systems requirements: Style Y (Class B) or with an optional ZNAC-92 module con- —LOCAL (Automatic, Manual, Waterflow and Sprinkler verts to four Style Z (Class A) NACs. Maximum signaling cur- Supervisory). rent per circuit:2.5 amps. End-of-Line Resistor:4.7K ohm, 1/2 —AUXILIARY (Automatic, Manual and Waterflow) (requires watt(P/N 71252 UL listed)for Style Y(Class B) NAC. Refer to 4XTMF). panel documentation and Fire-Lite Device Compatibility Docu- —REMOTE STATION (Automatic, Manual, Waterflow and ment for listed compatible devices. Sprinkler Supervisory) (Where a DACT is not accepted, Two Programmable Relays and One Fixed Trouble Relay: the alarm, trouble and supervisory relays may be con- Contact rating:2.0 amps @ 30 VDC(resistive),0.5 amps @ 30 nected to UL 864 listed transmitters. For reverse polarity VAC(resistive). Form-C relays. signaling of alarm and trouble,4XTMF is required.) Special Application Non-resettable Power (24 VDC Nomi- —PROPRIETARY (Automatic, Manual, Waterflow and nal): Jumper selectable (JP4) for conversion to resettable Sprinkler Supervisory). power output. Up to 1.0 amp total DC current available from —CENTRAL STATION (Automatic, Manual, Waterflow and each output. Power-limited. Sprinkler Supervisory). Special Application Resettable Power (24 VDC nominal): —OT, PSDN (Other Technologies, Packet-switched Data Jumper selectable (JP6) for conversion to non-resettable Network) power. Up to 1.0 amp total DC current available. Refer to the Fire-Lite Device Compatibility Document for listed compatible Agency Listings and Approvals devices. Remote Sync Output: Remote power supply synchronization The listings and approvals below apply to the basic MS- output. Nominal special application power: 24 VDC. Maximum 92000DLS Rev 3 control panel. In some cases, certain mod- current: 300 mA. End-of-Line Resistor: 4.71K ohm. Output ules may not be listed by certain approval agencies, or listing linked to NAC 1 control.Supervised and power-limited. may be in process.Consult factory for latest listing status. Telephone Interface: Unless used with Teldat VISORALARM, • UL Listed: S624 requires dedicated business telephone number with a mini- • FM approved mum of 5 volts DC (off-hook voltage). Obtain dedicated phone • CSFM:7165-0075:0208 line directly from your local phone company. Do not use shared . MEA: 120-06-E phone lines or PBX(digital)type phone line extensions. For ULC-listed version, see DF-60599. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x FireLiteO Alarms@ is a registered trademark of Honeywell International Inc. 0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x Wheelock@ is a registered trademark of and ExcederTM is a trademark of Cooper Notification. 02010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING&MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 6 of 6—DF-60601:A1•12/07/2010 S YST Em �4 SENSOR" C01224T and C01224TR • • • Carbon Monoxide Detectors with RealTest°Technology The System Sensor CO1224T and CO1224TR(round) Carbon Monoxide(CO)Detectors use a highly accurate and reliable electrochemical sensing cell to provide early warning of dangerous CO levels. Features With RealTest®technology,the CO gas sensing cell used in • RealTest®enables a functional test using canned CO the C01224T and C01224TR CO detectors can be tested using a CO gas agent,fully meeting the requirements of NFPA 720:2009. • Full compliance with UL 2075 Simply put the detector into RealTest mode,spray a small amount • A code-required trouble relay of CO into the detector per the installation instructions,and within • Wiring supervision with SEMS terminals seconds the detector will alarm,indicating successful gas entry.(See the reverse page or the user manual for complete instructions.) • A six-year end-of-life timer • 12/24 VDC When dangerous amounts of CO are detected,the C01224T and • A low current draw of 20 mA in standby and 40 mA in alarm C01224TR detectors alert residents by sounding and flashing a temp 4 signal alarm.With 24/7 central station monitoring, residents • Versatile mounting for wall and ceiling are guaranteed protection whether they are away from home, • Accurate and reliable electrochemical sensing technology sleeping,or already suffering from the effects of CO. • Optional CO-PLATE CO Detector Replacement Plate to upgrade The C01224T and C01224TR are designed for system operation. previously installed competitor detectors to the C01224T These detectors are fully listed to UL 2075 and offer acode- required trouble relay to send a sensor failure or end-of-life signal to the control panel and the central station.The C01224T and C01224TR also use SEMS-type terminal Philips head screws for quicker and more positive wiring connections and code-required wiring supervision.With a low current draw,these detectors enable more devices to be connected to the panel, limiting the need to purchase extra power supplies or more expensive panels.As 12/24 VDC detectors,the C01224T and C01224TR will operate on most industry security and fire alarm control panels. Agency Listings U tigTl L ry LISTED E307195 E304075 5276-1653:0194 C01224T and C01224TR Carbon Monoxide Detector Specifications Carbon monoxide(CO)detector shall be a system-connected System Sensor model number C01224T or C01224TR listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and Sensors.The detector shall be equipped with a sounder and a trouble relay.The detector's base shall be able to mount to a single-gang electrical box or direct(surface)mount to the wall or ceiling.Wiring connections shall be made by means of SEMS screws.The detector shall provide dual-color LED indication that blinks to indicate normal standby,alarm,or end-of-life.When the sensor supervision is in a trouble condition,the detector shall send a trouble signal to the panel.When the detector gives a trouble or end-of-life signal,the detector shall be replaced.The detector shall provide a means to test CO gas entry into the CO sensing cell.The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.The detector shall perform in the detection of CO up to 12,000 feet above sea level and alarm within the time specified by ANSI/UL 2034 for CO concentrations of 70, 150 and 400 parts per million(ppm),as verified by a Nationally Recognized Test Laboratory. Electrical Specifications Operating Voltage 12/24 VDC Audible Signal 85 dB in alarm Standby Current 20 mA Alarm Current 40 mA(75 mA test) Alarm Contact Ratings 0.5 A @ 30 VDC Trouble Contact Ratings 0.5 A @ 30 VDC Physical Specifications Size:C01224T Length:5.1 in,Width: 3.3 in,Height: 1.3 in C01224TR Diameter:6 in,Height: 1.3 in Approximate Weight CO1224T:7 oz;CO1224TR: 11 oz Operating Temperature Range 32oF to 104°F(0°C to 40°C) Operating Humidity Range 22 to 90%RH Input Terminals 14 to 22 AWG Mounting Single-gang back box;surface mount to wall or ceiling Operation Modes Operation Mode Green LED Red LED Sounder Normal(standby) Blink 1 per minute — — Alarm — Blink in temp 4 pattern Sound in temp 4 pattern RealTest®Feature: The System Sensor C01224T and C01224TR Carbon Monoxide Detectors with RealTest enable evaluation of the functionality of the CO sensing cell using a canned CO test agent. �=a Push and hold the Test/Hush button for Spray canned CO agent into Verify CO sensing at the two seconds to enter RealTest mode.The the detector. control panel.The detector will green LED will flash once every second automatically exit RealTest alarm to indicate RealTest mode has started. mode after about 20-60 seconds. NOTE:Check with local codes and the AHJ to determine if a functional gas test is desired for an installation. Hush Feature: Pushing the Test/Hush button will silence the sounder for 5 minutes(except in RealTest mode). Trouble Feature: When the detector is in a trouble condition, it will send a trouble signal to the panel. �_ End-of-Life Timer: After the detector's internal sensor has reached the end of its life,a trouble signal will be sent to p the panel to indicate it is time to replace the detector.An electrochemical CO detector lifespan is about six years.The detector must be replaced by the date marked on the inside of the product. r CO-PLATE: System Sensor also offers the CO-PLATE CO Detector Replacement Plate to cover the footprint(when �� necessary)of previously installed competitive carbon monoxide detectors that require replacement. Ordering Information CO-PLATE Part No. Description CO1224T 12/24 volt,4-wire system-monitored carbon monoxide detector with RealTest®Technology CO1224TR 12/24 volt,4-wire system-monitored round carbon monoxide detector with RealTest®Technology CO-PLATE CO detector replacement plate to cover the footprint of previously installed competitive detectors as necessary 4� SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 ©2012 System Sensor. Phone:800 SENSOR2•Fax:630-377-6495 Product specifications subject to change without notice.Visit systemsensor.com SENSOR`N or current product information,including the latest version of this data sheet. www.systemsensor.com scosooloo•anz df-52385:A•E-710 H355(A) Series FMIITerALaf ms Intelligent Addressable Thermal Detectors by Honeywell Addressable Devices General The Fire-Lite Alarms H355 Series thermal detectors are addressable sensors that use a state-of-the-art thermistor sensing circuit for fast response. These sensors are designed to provide open-area protection and are intended for use with the Fire•Lite's addresable Fire Alarm Control Panels(FACPs). The H355(A) and H355R(A) sensors provide fixed tempera- ture alarm detection at 135oF (57°C). The H355R(A) sensor 6936pho1.jp also responds to rate-of-rise conditions of greater than 15oF i+ (8.3°C) per minute. The H355HT(A) is a fixed high-tempera- ture detector that activates at 190oF (88°C). These thermal detectors provide cost effective, addressable property protec- tion in a variety of applications. H355 with B350LP base Two LEDs on each sensor light to provide a local, visible sen- sor indication. Remote LED annunciator capability is available as an optional accessory(P/N RA400Z). • 94-5V plastic flammability rating. Features Options: SLC loop: • Remote LED output connection to optional RA40OZ • Two-wire SLC loop connection. remote LED annunciator. • Unit uses base for wiring. • Recessed (RMK400) or surface (SMK400E) base mount- Addressing: ing kits. • Addressable by device. Installation • Direct Decade entry of address:01 —159 with MS-9600,01 —99 with MS-92000D. H355(A) Series plug-in intelligent thermal detectors use a detachable base to simplify installation, service and mainte- Architecture: nance. Installation instructions are shipped with each detector. • Sleek, low-profile,stylish design. Mount base (all base types) on box that is at least 1.5" (3.81 • State-of-the-art thermistor technology for fast response. cm)deep. Suitable boxes include: • Integral communications and built-in device-type identifica- . 4.0" (10.16 cm)square box. tion. • 3.5" (8.89 cm)or 4.0" (10.16 cm)octagonal box. • Built-in tamper resistant feature. Single-gang box(except relay or isolator base). • Built-in functional test switch activated by external magnet. NOTE: Because of the inherent supervision provided by the SLC Operation: loop, end-of-line resistors are not required. Wiring "T-taps" or • Factory preset at 135oF (57°C) for the H355(A) and branches are permitted for Style 4(Class"B")wiring only. H355R(A); 190°F(88°C)for the H355HT(A). • Rate-of-rise triggers at 15oF (8.3°C) per minute for the Applications H355R(A). Use thermal detectors for protection of property. • 360°-field viewing angle of the visual alarm indicators (two bicolor LEDs). LEDs blink green in Normal condition and Construction turn on steady red in Alarm. Visible LEDs"blink"every time the unit is addressed. These detectors are constructed of off-white Bayblend®. The • H355(A) Series plug-in intelligent thermal detectors are Mechanicals: designed to commercial standards and offer an attractive • Sealed against back pressure. appearance. • SEMS screws for wiring of the separate base. • Designed for direct-surface or electrical-box mounting. Operation • Plugs into separate base for ease of installation and main- Each H355(A) Series detector uses one of 159 (MS-9600) or tenance. 99 (MS-92000D) possible addresses on a control panel SLC • Separate base allows interchange of photoelectric, ioniza- loop. It responds to regular polls from the control panel and tion and thermal sensors. reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its elec- Other system features: tronics and reports an alarm. It blinks its LEDs when polled • Remote test feature from the panel. and turns the LEDs on when commanded by the panel. The • Walk test with address display. H355(A) Series offers features and performance that repre- • Low standby current. sent the latest in thermal detector technology. df-52385:A•12/17/08—Page 1 of 2 Specifations Product Line Information Diameter:6.1" (15.5 cm) installed in B350LP(A). NOTE:"A"suffix indicates ULC-Listed model. Height:2.1"(5.33 cm). H355: Intelligent thermal sensor; B350LP base included. Weight:4.8 oz. (137 g). H355A: Same as H355 but with ULC Listing (13350LPA base Installation temperature: -4°F to 100°F(-20°C to 38°C). included). Humidity range: 10% to 93% relative humidity (noncon- H355R: Same as H355 with rate-of-rise feature; B35OLP base densing). included. Voltage range: 15 to 32 VDC peak. H355RA: Same as H355R but with ULC Listing (13350LPA base included). Standby current: 300 pA @ 24 VDC (one communication H355HT: Intelligent fixed high-temperature thermal detector; every five seconds with LED blink enabled). B350LP base included. LED current:6.5 mA @ 24 VDC. H355HTA: Same as H355HT but with ULC Listing (13350LPA Mounting: B350LP(A)flanged base, included. base included). Fixed-temperature setpoint: 135°F (57°C) for the H355(A) B350LP(A): Plug-in detector base (included). Dimensions: and H355R(A); 190°F(88°C)for the H355HT(A). 6.1" (15.5 cm). Mounting: 4.0" (10.16 cm) square box with or Rate-of-rise detection: responds to greater than 15°F(8.3°C) without plaster ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 per minute. cm) octagonal box, or single-gang box. All mounting boxes have a minimum depth of 1.5" (3.81 cm). Listings and Approvals B224RB(A): Plug-in System Sensor relay detector base. Diameter:6.2" (15.75 cm). Mounting:4.0" (10.16 cm)square Listings and approvals below apply to the H355(A) Series box with or without plaster ring,4.0" (10.16 cm)octagonal box, detectors. In some cases, certain modules may not be listed or 3.5" (8.89 cm) octagonal box. All mounting boxes have a by certain approval agencies, or listing may be in process. minimum depth of 1.5"(3.81 cm). Consult factory for latest listing status. B224BI(A): Plug-in System Sensor isolator detector base. • MEA approved:file 387-02-E Maximum 25 devices between isolator bases(see DF-52389). • UL Listed,file S2517 Diameter:6.2" (15.75 cm). Mounting:4.0" (10.16 cm)square • ULC Listed(models H355A, H355RA, H355HTA) box with or without plaster ring,4.0" (10.16 cm)octagonal box, • CSFM approved:file 7270-0075:195 or 3.5" (8.89 cm) octagonal box. All mounting boxes have a • FM approved minimum depth of 1.5" (3.81 cm). B501 BH-2(A): Plug-in System Sensor standard sounder base. Diameter: 6.0" (15.24 cm). Mounting: 4.0" (10.16 cm) square box with or without plaster ring. Mounting boxes have a minimum depth of 1.5" (3.81 cm). B501 BHT 2(A): Plug-in System Sensor temporal tone sounder base. ACCESSORIES: RA400Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and B350LP(A) bases only. SMK400E: Surface mounting kit provides for entry of surface wiring conduit. For use with B501(A) base only. RMK400: Recessed mounting kit. For use with B501(A) base only. M02-04-00:Test magnet. M02-09-00:Test magnet with telescoping handle. XR2B: Detector removal tool.Allows installation and/or removal of detector heads from bases in high ceiling applications. XP-4: Extension pole for XR213. Comes in three 5-foot (1.524 m)sections. Fire•LiteO Alarms is a registered trademark of Honeywell International Inc. Bayblend0 is a registered trademark of Bayer Corporation. 02008 by Honeywell International Inc. All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING 8 MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 2 of 2-df-52385:A•12/17/08 SYSTEM �4 SEIVSORI"" A, Outdoor Selectablem Output Horns, Strobes, and Horn Strobes for Wall Applications SPECTRQUert SpectrAlert®Advance outdoor audible visible products �► ova IIIV c E are rich with features that cut installation times and maximize profits. Features SpectrAlert Advance offers the broadest line of outdoor horns, • Weatherproof per NEMA 4X, IP56 strobes,and horn strobes in the industry.With white or red plastic housings,wall or ceiling mounting options,and plain or FIRE-printed • Listed to UL 1638(strobe)and UL 464(horn) devices,SpectrAlert Advance can meet virtually any application • Compatible with System Sensor synchronization protocol and requirement, including indoor,outdoor,wet,and dry applications in legacy SpectrAlert products temperatures from—40cF to 151°F. • Field-selectable candela settings: 15, 15/75,30,75,95, 110, 115, Like the entire SpectrAlert Advance line,outdoor horns,strobes, 135, 150, 177,and 185 and horn strobes for wall applications include a variety of features • Automatic selection of 12-or 24-volt operation at 15 and that increase application flexibility and simplify installation. First, 15/75 candela field-selectable settings, including candela,automatic selection of • Rotary switch for horn tone and three volume selections 12-or 24-volt operation,horn tones,and three volume options enable • Horn rated at 88+dBA at 16 volts installers to easily adapt devices to meet requirements. • Rated from—40°F to 151°F Next,SpectrAlert Advance devices use a universal mounting plate • Universal mounting plate with an onboard shorting spring that for both wall and ceiling applications.This mounting plate includes tests wiring continuity before devices are installed an onboard shorting spring that ensures wiring continuity before • Plug-in design with minimal intrusion into the back box devices are installed,so installers can verify proper wiring without mounting the devices and exposing them to potential construction • Tamper-resistant construction damage.Once the plates are mounted,all SpectrAlert Advance • Listed for ceiling or wall mounting devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes(metal back boxes are available separately)that accommodate in-and- Agency Listings out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater SIGNALING t corrosion. Knock-outs located on the back eliminate the need to drill U s _ holes for screw-in mounting. Plastic and metal weatherproof back O boxes come with 3/4-inch top and bottom conduit entries and 3/4-inch LISTED F M MEA 7300-1653:187(outdoor strobes) ( 7125-1653:188 chime snob s) knock-outs at the back.A screw-in NPT plug with an 0-ring gasket S4011 chimes,horn strobes,horns) APPROVED approved S3593(outdoor and alert strobes) 3023572 MEA452-05-E 7135-1653:189(horns,chimes) for a watertight seal is included with each back box. SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns,strobes,and horn strobes shall mount to a weatherproof back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit'"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.Outdoor SpectrAlert Advance products shall operate between—40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL.The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options shall be set by a multiple position switch. On four-wire products,the strobe shall be powered independently of the sounder.The horn or horn strobe models shall operate on a coded or non-coded power supply.The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature —40°F to 151°F(-40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6-L x 4.7-W x 2.5-D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6-L x 4.7-W x 1.3-D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Weatherproof Back Box Dimensions(SA-WBB) 5.7-L x 5.1-W x 2.0-D(145 mm L x 130 mm W x 51 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-Temporal High 57 56 69 75 95 NA NA 181 176 Non-Temporal Medium 42 50 60 69 110 NA NA 202 195 Non-Temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures,listed Horn and Horn Strobe Output candela ratings must be reduced in accordance with 8-17.5 16-33 24-Volt Nominal this table. Switch Sound Volts Volts Reverberant Anechoic Output Strobe Position Pattern dB DC FWR DC FWR DC FWR DC FWR Listed Candela Candela rating at—40°F 1 Temporal High 78 78 84 84 88 88 99 98 15 2 Temporal Medium 74 74 80 80 86 86 96 96 15/75 Do not use below 32°F 3 Temporal Low 71 73 76 76 83 80 94 89 30 4 Non- High 75 44 Temporal 82 82 88 88 93 92 100 100 95 70 5 Non- Medium 110 110 Temporal 78 78 85 85 90 90 98 98 115 115 6 Non- Low 75 75 81 81 88 84 96 92 135 135 Temporal 150 150 7t Coded High 82 82 88 88 93 92 101 101 177 177 8t Coded Medium 78 78 85 85 90 90 97 98 185 1185 9t Coded Low 75 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobe. AVDS01201 SpectrAlert Advance Diagrams �4.7" 2.5" 5.6" ° O 0 Wall-Mount Horn Strobes ® ® Wall Plastic Weatherproof Back Box LIP Wall-Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Model Description Wall Horn Strobes P2RK*t 2-Wire Horn Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) P2RHK*t 2-Wire Horn Strobe,High cd,Red,Outdoor(includes plastic weatherproof back box) P2WK*t 2-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2WHK*t 2-Wire Horn Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) P4RKt 4-Wire Horn Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe,High cd,Red,Outdoor, 120 V(includes plastic weatherproof back box) Wall Strobes SRK*t Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) SRHK*t Strobe,High cd,Red,Outdoor(includes plastic weatherproof back box) SWK*t Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) SWHK*t Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) Horns HRKt Horn,Red,Outdoor(includes plastic weatherproof back box) Accessories SA-WBB Red,Metal Weatherproof Back Box SA-WBBW White,Metal Weatherproof Back Box Notes: *Add '-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2RK-P. t Add"-R"to model number for weatherproof replacement device(no back box included),only for use with weatherproof outdoor flush mounting plate,WfP and WTPW. "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings.When replacing standard outdoor units both the device and back box must be replaced. 4� SYSTEM ©2012 System Sensor. JJJ 3825 Ohio Avenue•St.Charles, IL 60174 Product specifications subject to change mSenwithout onotice.Visit systemsensoccom SE/VSOR Phone:800-SENSOR2•Fax:630-377-6495 or current product information,including AVDS01201-elatestversionothisdaasheet. 3/12 SD355(A), SD355T(A), df-52384:b•E-160 SD355R(A) Flre•LITe®ALarms Addressable Photoelectric Smoke Detectors by Honeywell Addressable Devices General The SD355(A) and SD355T(A) addressable, low-profile plug- in photoelectric detectors use a state-of-the-art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with Fire-Lite's Address- able Fire Alarm Control Panels(FACPs).The SD355T(A)adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help < ) emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annun- ciator capability is available as an optional accessory (P/N RA100Z(A)). The SD355R is a remote test capable detector for use with D355PL or DNR(W) duct smoke detector hous- SD355 with B35OLP base ings. Features SLC loop: • Two-wire loop connection. • Unit uses base for wiring. Addressing: • Addressable by device. • Direct Decade entry of address: 01 – 99 with MS-9200 series,and 01 –159 with MS-9600 series. Architecture: • Unique single-source, dual-chamber design to respond SD355T with B350LP base quickly and dependably to a broad range of fires. • Sleek, low-profile design. • Integral communications and built-in type identification. Applications • Built-in tamper-resistant feature. Use photoelectric detectors in life-safety applications to pro- • Removable cover and insect-resistant screen for simple vide a broad range of fire-sensing capability, especially where field cleaning. smoldering fires are anticipated. Ionization detectors are often Operation: better than photoelectric detectors at sensing fast, flaming fires. • Withstands air velocities up to 4,000 feet-per-minute(20 m/ sec.)without triggering a false alarm. Construction • Factory preset at 1.5% nominal sensitivity for panel alarm These detectors are constructed of off-white LEXANO. threshold level. SD355(T)plug-in, low-profile smoke detectors are designed to • Visible LED "blinks"when the unit is addressed (communi- commercial standards and offer an attractive appearance. cating with the fire panel)and latches on in alarm. Mechanicals: Installation • Sealed against back pressure. SD355(T) plug-in detectors use a detachable mounting base • Direct surface mounting or electrical box mounting. to simplify installation, service and maintenance. Mount base • Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 on box which is at least 1.5 inches (3.81 cm) deep. Suitable cm)octagonal box, or 4.0" (10.16 cm) square electrical box boxes include: (using a plaster ring—included). • 4.0" (10.16 cm)square box with plaster ring. Other system features: • 4.0" (10.16 cm)octagonal box. • Fully coated circuit boards and superior RF/transient pro- • 3.5" (8.89 cm)octagonal box. tection. • Single-gang box. • 94-VO plastic flammability rating. NOTE: Because of the inherent supervision provided by the SLC • Low standby current. loop, end-of-line resistors are not required. Wiring "T-taps" or Options: branches are permitted for Style 4 (Class B) wiring. SD355R Remote LED output connection (P/N RA100Z). mounts in a D355PL or DNR(W)duct detector housing. • df-52384:b•3/12/10—Page 1 of 2 Operation Product Line Information Each SD355/T/R uses one of 99 possible addresses on the NOTE:"A"suffix indicates ULC-Listed model. MS-9200 series and up to 318 (159 on each loop) on the MS- SD355: Adressable photoelectric detector; B350LP base 9600 series Signaling Line Circuit(SLC). It responds to regular included. polls from the system and reports its type and status. The SD355/T/R addressable photoelectric sensor's unique SD355A: Sames as SD355 with ULC Listing (B350LPA base included). unipolar chamber responds quickly and uniformly to a broad range of smoke conditions and can withstand wind gusts up to SD355T: Same as SD355 but with thermal element; B350LP 4,000 feet-per-minute (20 m/sec.) without sending an alarm base included. level signal. Because of its unipolar chamber, the SD355/T/R SD355TA: Same as SD355T with ULC Listing (B350LPA base is approximately two times more responsive than most photo- included). electric sensors.This makes it a more stable detector. SD355R: Remote test capable addressable photoelectric Detector Sensitivity Test detector for use with a D355PL or DNR(W)duct detector hous- 9 Each detector can have its sensitivity tested (required per B350LP(A): Plug-in detector base. Dimensions: 6.1" (15.5 NFPA 72,Chapter 14 on Inspection,Testing and Maintenance) cm). Mounting: 4.0" (10.16 cm) square box with or without when installed/connected to a MS-9200 series or MS-9600 plaster ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 cm) series addressable fire alarm control panel. The results of the octagonal box, or single-gang box. All mounting boxes have a sensitivity test can be printed off the MS-9200 series or MS- minimum depth of 1.5" (3.81 cm). 9600 series for record keeping. B224R6(A): Plug-in System Sensor relay detector base. Diameter:6.2" (15.75 cm). Mounting:4.0" (10.16 cm)square Specification box with or without plaster ring,4.0" (10.16 cm)octagonal box, Voltage range: 15-32 VDC(peak). or 3.5" (8.89 cm) octagonal box. All mounting boxes have a Standby current:300 pA @ 24 VDC. minimum depth of 1.5"(3.81 cm). LED current:6.5 mA @ 24 VDC (latched"ON"). B224BI(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases(see DF-52389). Air velocity:4,000 ft./min. (20 m/sec.) maximum. Diameter:6.2" (15.75 cm). Mounting:4.0" (10.16 cm)square Diameter: 6.1" (15.5 cm) installed in B350LP base. box with or without plaster ring,4.0" (10.16 cm)octagonal box, or 3.5" (8.89 cm) octagonal box. All mounting boxes have a Height:2.1" (5.33 cm) installed in B350LP base. minimum depth of 1.5" (3.81 cm). Weight:3.6 oz. (102 g). B200SR: Sounder base capable of producing temporal-3 or Operating temperature range: for SD355(A): 0°C to 49°C steady sound output. (32°F to 120°F); for SD355T(A): 0°C to 38°C (32°F to 100°F). ACCESSORIES: SD355R(A): installed in a DNR(W) -20°C to 70°C (-4°F to 158°F). RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to Temperature: 0°C-49°C(32°F-120°F). a U.S. single-gang electrical box. For use with B501(A) and B350LP(A) bases only. Relative humidity: 10%-93%, non-condensing. SMK400E: Surface mounting kit provides for entry of surface wiring conduit. For use with B501(A) base only. Listings RMK400: Recessed mounting kit. For use with B501(A) base Listings and approvals below apply to the SD355(A) and only. SD355T(A) detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in M02-04-OO:Test magnet. process.Consult factory for latest listing status. M02-09-00:Test magnet with telescoping handle. • UL Listed,file S1059. XR2113: Detector removal tool.Allows installation and/or removal • ULC Listed,file S1059. of detector heads from bases in high ceiling applications. • CSFM approved:file 7272-0075:194. XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 • MEA approved:file 243-02-E. m)sections. • FM approved. T55-127-010:Detector removal tool without pole. BCK-20OB: Black detector covers, box of 10. WCK-20OB:White detector covers, box of 10. FlashScan@ registered trademark of Honeywell International Inc. Bay- blend@ is a registered trademark of Bayer Corporation. @2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. 1S0 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING U MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 2 of 2-df-52384:b•3/12/10 Protecti.6 11� on SECU q ITY S OL UTI4#I L_11L•t _ r.r_r'r 4 Project East Vail Duplex Residences 4017 Lupine Drive, Lot 7 Units A & B Vail, CO 81620 Installer/Contractor Protection 1 —Security Solutions 7100 N. Broadway, Building 8A Denver, CO 80221 Design/CAD Fire Team Security, Inc. 516 Juniper Street Fruita, CO 81521 FTS INC