Loading...
HomeMy WebLinkAboutF13-0002 F13-0003 CR1 BATTERY CALCS.PDF FACP BATTERY CALCULATIONS PROJECT: East Vail Duplex Residences-Unit A Panel 1 HOURS OF SUPERVISION: 24 HOURS MINUTES OF ALARM: 1 15 IMINUTES FACP: MS-25 LOCATION: Mechanical Device Device Total Total PART Supervisory Alarm Supervisory Alarm ITEM QTY NUMBER DESCRIPTION Current Current Current Current 1 1 MS-25 Addressable FACP w/Built-in Communicator 0.135000 0.220000 0.135000 0.220000 Mains Totals: 0.135000 0.220000 PERIPHERAL: Supervisory Alarm Device Device Total Total ITEM PART Supervisory Alarm Supervisory Alarm # QTY NUMBER DESCRIPTION Current Current Current Current 1 10 S355 Smoke Detector 0.000300 0.000300 0.003000 0.003000 2 5 C01224T Carbon Monoxide Detector 0.000500 0.005000 0.002500 0.025000 3 3 H355 Heat Detector 0.000300 0.000300 0.000900 0.000900 4 2 MMF-301 Mini Monitor Module 0.000350 0.000600 0.000700 0.001200 5 1 MDF-300 Dual Monitor Module 0.000375 0.000750 0.000375 0.000750 6 2 BY OTHERS Tamper Switch 0.000000 0.025000 0.000000 0.050000 7 1 BY OTHERS Waterflow Switch 0.000000 0.025000 0.000000 0.025000 8 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000 Peripheral Totals: 0.007475 0.281850 Supervisory Alarm SUPERVISORY COMPUTATIONS PANEL: 0.135000 AMPS PERIPHERAL 0.007475 AMPS SUB-TOTAL: 0.142475 AMPS X HOURS OF SUPERVISORY: 24.0000 HOURS SUPERVISORYSUB-TOTAL: 3.419400 AMP HOURS ALARM COMPUTATIONS PANEL: 0.220000 AMPS PERIPHERAL: 0.281850 AMPS SUB-TOTAL: 0.501850 AMPS X MINUTES OF ALARM: 0.25000 HOURS ALARM SUB-TOTAL: 0.125463 AMP HOURS BATTERY REQUIREMENT COMPUTATIONS TOTAL SUPERVISORY: 3.419400 AMP HOURS TOTAL ALARM: 0.125463 AMP HOURS TOTAL: 3.544863 AMP HOURS DERATE 25%: 4.43108 AMP HOURS MINIMUM BATTERY REQUIREMENT: 1 4.43108 JAMPHOUR S BATTERY SUPPLIED: 1 7.00000 1 AMP HOURS FACP BATTERY CALCULATIONS PROJECT: East Vail Duplex Residences-Unit B Panel 2 HOURS OF SUPERVISION: 24 HOURS MINUTES OF ALARM: 1 15 IMINUTES FACP: MS-25 LOCATION: Mechanical Device Device Total Total PART Supervisory Alarm Supervisory Alarm ITEM QTY NUMBER DESCRIPTION Current Current Current Current 1 1 MS-25 Addressable FACP w/Built-in Communicator 0.135000 0.220000 0.135000 0.220000 Mains Totals: 0.135000 0.220000 PERIPHERAL: Supervisory Alarm Device Device Total Total ITEM PART Supervisory Alarm Supervisory Alarm # QTY NUMBER DESCRIPTION Current Current Current Current 1 12 S355 Smoke Detector 0.000300 0.000300 0.003600 0.003600 2 5 C01224T Carbon Monoxide Detector 0.000500 0.005000 0.002500 0.025000 3 2 H355 Heat Detector 0.000300 0.000300 0.000600 0.000600 4 1 MMF-301 Mini Monitor Module 0.000350 0.000600 0.000350 0.000600 5 0 MDF-300 Dual Monitor Module 0.000375 0.000750 0.000000 0.000000 6 0 BY OTHERS Tamper Switch 0.000000 0.025000 0.000000 0.000000 7 0 BY OTHERS Waterflow Switch 0.000000 0.025000 0.000000 0.000000 8 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000 Peripheral Totals: 0.007050 0.205800 Supervisory Alarm SUPERVISORY COMPUTATIONS PANEL: 0.135000 AMPS PERIPHERAL 0.007050 AMPS SUB-TOTAL: 0.142050 AMPS X HOURS OF SUPERVISORY: 24.0000 HOURS SUPERVISORYSUB-TOTAL: 3.409200 AMP HOURS ALARM COMPUTATIONS PANEL: 0.220000 AMPS PERIPHERAL: 0.205800 AMPS SUB-TOTAL: 0.425800 AMPS X MINUTES OF ALARM: 0.25000 HOURS ALARM SUB-TOTAL: 0.106450 AMP HOURS BATTERY REQUIREMENT COMPUTATIONS TOTAL SUPERVISORY: 3.409200 AMP HOURS TOTAL ALARM: 0.106450 AMP HOURS TOTAL: 3.515650 AMP HOURS DERATE 25%: 4.39456 AMP HOURS MINIMUM BATTERY REQUIREMENT: 4.39456 AMP HOURS BATTERY SUPPLIED: 7.00000 AMP HOURS East Vail Duplex Residences Circuit 1 NAC Voltage Drop Calculator for Audio/Visual devices This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name East Vail Duplex Residences CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date Circuit Number P1:1 Totals Voltage Totals Voltage Totals Voltage Area Covered 5,706 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.176 63 0.07 0.176 63 0.068 0.176 63 0.034 Minimum Device Voltage 181 1 End of Line Voltage 20.33 End of Line Voltage 20.33 End of Line Voltage 20.37 Total Circuit Current 0.176; Wire I Ohm's Percent Drop 0.33% Percent Drop 0.33% Percent Drop 0.17% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device 63 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 i 18=7.771 16=4.891 14=3.07; 12=1.981 10=1.241 Enter current in amps. Distance 18-14 Aw = Solid Conductors 12-10 Awg = Stranded Conductors .150 = 150 ma from Voltage Notes: Device Device previous At 1 Drop from;1 Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.176 63 20.33 0.068 0.33% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.33 0.068 0.33% END 20.33 0.068 0.33% Device Manufacturer System Sensor Device Manufacturer JSystern Sensor END 20.33 0.068 0.33% Current I I Current END 20.33 0.068 0.33% Horn Strobes @Rated Strobe Only @Rated END 20.33 0.068 0.33% Model # Candela Voltage Model # Candela Voltage END 20.33 0.068 0.33% P2R 15CD 0.079 SR 15 CD 0.066 END 20.33 0.068 0.33% 30CD 0.107 30 CD 0.094 END 20.33 0.068 0.33% 15/75 CD 0.09 15/75 CD 0.077 END 20.33 0.068 0.33% 75CD 0.176 75CD 0.158 END 20.33 0.068 0.33% 110CD 0.212 110CD 0.202 END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% Totals 0.176 63 End of Line Voltage 20.33 East Vail Duplex Residences Circuit 2 NAC Voltage Drop Calculator for Audio/Visual devices This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name East Vail Duplex Residences CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date Circuit Number P2:1 Totals Voltage Totals Voltage Totals Voltage Area Covered 4,356 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage _ 20.4 0.176 67 0.07 0.176 67 0.072 0.176 67 0.036 Minimum Device Voltage 181 End of Line Voltage 20.33 End of Line Voltage 20.33 End of Line Voltage 20.36 Total Circuit Current 0.176; Wire Ohm's Percent Drop 0.35% Percent Drop 0.35% Percent Drop 0.18% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device 67 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 i 18=7.771 16=4.891 14=3.07; 12=1.981 10=1.241 Enter current in amps. Distance 18-14 Aw = Solid Conductors 12-10 Awg = Stranded Conductors .150 = 150 ma from Voltage Notes: Device Device previous At 1 Drop from;1 Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.176 67 20.33 0.072 0.35% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.33 0.072 0.35% END 20.33 0.072 0.35% Device Manufacturer System Sensor Device Manufacturer JSystern Sensor END 20.33 0.072 0.35% Current I I Current END 20.33 0.072 0.35% Horn Strobes @Rated Strobe Only @Rated END 20.33 0.072 0.35% Model # Candela Voltage Model # Candela Voltage END 20.33 0.072 0.35% P2R 15CD 0.079 SR 15 CD 0.066 END 20.33 0.072 0.35% 30CD 0.107 30 CD 0.094 END 20.33 0.072 0.35% 15/75 CD 0.09 15/75 CD 0.077 END 20.33 0.072 0.35% 75CD 0.176 75CD 0.158 END 20.33 0.072 0.35% 110CD 0.212 110CD 0.202 END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% Totals 0.176 67 End of Line Voltage 20.33