HomeMy WebLinkAboutF13-0002 F13-0003 CR1 BATTERY CALCS.PDF FACP BATTERY CALCULATIONS
PROJECT: East Vail Duplex Residences-Unit A Panel 1
HOURS OF SUPERVISION: 24 HOURS
MINUTES OF ALARM: 1 15 IMINUTES
FACP: MS-25 LOCATION: Mechanical
Device Device Total Total
PART Supervisory Alarm Supervisory Alarm
ITEM QTY NUMBER DESCRIPTION Current Current Current Current
1 1 MS-25 Addressable FACP w/Built-in Communicator 0.135000 0.220000 0.135000 0.220000
Mains Totals: 0.135000 0.220000
PERIPHERAL: Supervisory Alarm
Device Device Total Total
ITEM PART Supervisory Alarm Supervisory Alarm
# QTY NUMBER DESCRIPTION Current Current Current Current
1 10 S355 Smoke Detector 0.000300 0.000300 0.003000 0.003000
2 5 C01224T Carbon Monoxide Detector 0.000500 0.005000 0.002500 0.025000
3 3 H355 Heat Detector 0.000300 0.000300 0.000900 0.000900
4 2 MMF-301 Mini Monitor Module 0.000350 0.000600 0.000700 0.001200
5 1 MDF-300 Dual Monitor Module 0.000375 0.000750 0.000375 0.000750
6 2 BY OTHERS Tamper Switch 0.000000 0.025000 0.000000 0.050000
7 1 BY OTHERS Waterflow Switch 0.000000 0.025000 0.000000 0.025000
8 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000
Peripheral Totals: 0.007475 0.281850
Supervisory Alarm
SUPERVISORY COMPUTATIONS
PANEL: 0.135000 AMPS
PERIPHERAL 0.007475 AMPS
SUB-TOTAL: 0.142475 AMPS
X HOURS OF SUPERVISORY: 24.0000 HOURS
SUPERVISORYSUB-TOTAL: 3.419400 AMP HOURS
ALARM COMPUTATIONS
PANEL: 0.220000 AMPS
PERIPHERAL: 0.281850 AMPS
SUB-TOTAL: 0.501850 AMPS
X MINUTES OF ALARM: 0.25000 HOURS
ALARM SUB-TOTAL: 0.125463 AMP HOURS
BATTERY REQUIREMENT COMPUTATIONS
TOTAL SUPERVISORY: 3.419400 AMP HOURS
TOTAL ALARM: 0.125463 AMP HOURS
TOTAL: 3.544863 AMP HOURS
DERATE 25%: 4.43108 AMP HOURS
MINIMUM BATTERY REQUIREMENT: 1 4.43108 JAMPHOUR S
BATTERY SUPPLIED: 1 7.00000 1 AMP HOURS
FACP BATTERY CALCULATIONS
PROJECT: East Vail Duplex Residences-Unit B Panel 2
HOURS OF SUPERVISION: 24 HOURS
MINUTES OF ALARM: 1 15 IMINUTES
FACP: MS-25 LOCATION: Mechanical
Device Device Total Total
PART Supervisory Alarm Supervisory Alarm
ITEM QTY NUMBER DESCRIPTION Current Current Current Current
1 1 MS-25 Addressable FACP w/Built-in Communicator 0.135000 0.220000 0.135000 0.220000
Mains Totals: 0.135000 0.220000
PERIPHERAL: Supervisory Alarm
Device Device Total Total
ITEM PART Supervisory Alarm Supervisory Alarm
# QTY NUMBER DESCRIPTION Current Current Current Current
1 12 S355 Smoke Detector 0.000300 0.000300 0.003600 0.003600
2 5 C01224T Carbon Monoxide Detector 0.000500 0.005000 0.002500 0.025000
3 2 H355 Heat Detector 0.000300 0.000300 0.000600 0.000600
4 1 MMF-301 Mini Monitor Module 0.000350 0.000600 0.000350 0.000600
5 0 MDF-300 Dual Monitor Module 0.000375 0.000750 0.000000 0.000000
6 0 BY OTHERS Tamper Switch 0.000000 0.025000 0.000000 0.000000
7 0 BY OTHERS Waterflow Switch 0.000000 0.025000 0.000000 0.000000
8 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000
Peripheral Totals: 0.007050 0.205800
Supervisory Alarm
SUPERVISORY COMPUTATIONS
PANEL: 0.135000 AMPS
PERIPHERAL 0.007050 AMPS
SUB-TOTAL: 0.142050 AMPS
X HOURS OF SUPERVISORY: 24.0000 HOURS
SUPERVISORYSUB-TOTAL: 3.409200 AMP HOURS
ALARM COMPUTATIONS
PANEL: 0.220000 AMPS
PERIPHERAL: 0.205800 AMPS
SUB-TOTAL: 0.425800 AMPS
X MINUTES OF ALARM: 0.25000 HOURS
ALARM SUB-TOTAL: 0.106450 AMP HOURS
BATTERY REQUIREMENT COMPUTATIONS
TOTAL SUPERVISORY: 3.409200 AMP HOURS
TOTAL ALARM: 0.106450 AMP HOURS
TOTAL: 3.515650 AMP HOURS
DERATE 25%: 4.39456 AMP HOURS
MINIMUM BATTERY REQUIREMENT: 4.39456 AMP HOURS
BATTERY SUPPLIED: 7.00000 AMP HOURS
East Vail Duplex Residences Circuit 1
NAC Voltage Drop Calculator
for Audio/Visual devices
This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering).
Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction
Point to Point Method End of Line Method Load Centering Method
Project Name East Vail Duplex Residences CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS
Date
Circuit Number P1:1 Totals Voltage Totals Voltage Totals Voltage
Area Covered 5,706 Current Distance Drop Current Distance Drop Current Distance Drop
Nominal System Voltage 20.4 0.176 63 0.07 0.176 63 0.068 0.176 63 0.034
Minimum Device Voltage 181 1 End of Line Voltage 20.33 End of Line Voltage 20.33 End of Line Voltage 20.37
Total Circuit Current 0.176; Wire I Ohm's Percent Drop 0.33% Percent Drop 0.33% Percent Drop 0.17%
Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source
Distance from source to 1st device 63 14 3.07 Standard Wire Resistance in Ohms per 1000 feet.
Wire Gauge for balance of circuit 14 3.07 i 18=7.771 16=4.891 14=3.07; 12=1.981 10=1.241
Enter current in amps. Distance 18-14 Aw = Solid Conductors 12-10 Awg = Stranded Conductors
.150 = 150 ma from Voltage Notes:
Device Device previous At 1 Drop from;1 Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative)
Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then
Device 1 0.176 63 20.33 0.068 0.33% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC).
END 20.33 0.068 0.33%
END 20.33 0.068 0.33% Device Manufacturer System Sensor Device Manufacturer JSystern Sensor
END 20.33 0.068 0.33% Current I I Current
END 20.33 0.068 0.33% Horn Strobes @Rated Strobe Only @Rated
END 20.33 0.068 0.33% Model # Candela Voltage Model # Candela Voltage
END 20.33 0.068 0.33% P2R 15CD 0.079 SR 15 CD 0.066
END 20.33 0.068 0.33% 30CD 0.107 30 CD 0.094
END 20.33 0.068 0.33% 15/75 CD 0.09 15/75 CD 0.077
END 20.33 0.068 0.33% 75CD 0.176 75CD 0.158
END 20.33 0.068 0.33% 110CD 0.212 110CD 0.202
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
END 20.33 0.068 0.33%
Totals 0.176 63 End of Line Voltage 20.33
East Vail Duplex Residences Circuit 2
NAC Voltage Drop Calculator
for Audio/Visual devices
This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering).
Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction
Point to Point Method End of Line Method Load Centering Method
Project Name East Vail Duplex Residences CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS
Date
Circuit Number P2:1 Totals Voltage Totals Voltage Totals Voltage
Area Covered 4,356 Current Distance Drop Current Distance Drop Current Distance Drop
Nominal System Voltage _ 20.4 0.176 67 0.07 0.176 67 0.072 0.176 67 0.036
Minimum Device Voltage 181 End of Line Voltage 20.33 End of Line Voltage 20.33 End of Line Voltage 20.36
Total Circuit Current 0.176; Wire Ohm's Percent Drop 0.35% Percent Drop 0.35% Percent Drop 0.18%
Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source
Distance from source to 1st device 67 14 3.07 Standard Wire Resistance in Ohms per 1000 feet.
Wire Gauge for balance of circuit 14 3.07 i 18=7.771 16=4.891 14=3.07; 12=1.981 10=1.241
Enter current in amps. Distance 18-14 Aw = Solid Conductors 12-10 Awg = Stranded Conductors
.150 = 150 ma from Voltage Notes:
Device Device previous At 1 Drop from;1 Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative)
Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then
Device 1 0.176 67 20.33 0.072 0.35% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC).
END 20.33 0.072 0.35%
END 20.33 0.072 0.35% Device Manufacturer System Sensor Device Manufacturer JSystern Sensor
END 20.33 0.072 0.35% Current I I Current
END 20.33 0.072 0.35% Horn Strobes @Rated Strobe Only @Rated
END 20.33 0.072 0.35% Model # Candela Voltage Model # Candela Voltage
END 20.33 0.072 0.35% P2R 15CD 0.079 SR 15 CD 0.066
END 20.33 0.072 0.35% 30CD 0.107 30 CD 0.094
END 20.33 0.072 0.35% 15/75 CD 0.09 15/75 CD 0.077
END 20.33 0.072 0.35% 75CD 0.176 75CD 0.158
END 20.33 0.072 0.35% 110CD 0.212 110CD 0.202
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
END 20.33 0.072 0.35%
Totals 0.176 67 End of Line Voltage 20.33