Addressable FACP
With Built-in Communicator by Honeywell
Addressable Fire Alarm Control Panels
General
The Fire-Lite MS-25(E) is a 25 point addressable Fire Alarm
Control Panel(FACP)with built-in Digital Alarm Communicator
Transmitter (DACT). This control panel supports up to 25
addressable devices in any combination of detectors and mod
ules. With simple programming, operation on standard wire,
and features such as drift compensation and maintenance A0,puBwAJUX _
alert, the MS-25(E) is a preferred alternative to conventional
control panels in both new and retrofit applications. orat-At fns
The JumpStart®(or auto-learn) feature and easy-to-set code-
wheel addressing of Honeywell Fire Systems(HFS)or equiva-
lent Fire-Lite detectors and modules enable the system to be
configured for fire protection without a programming utility.The
default programming can be modified using the panels embed-
ded web server.
The integral DACT transmits system status (alarms, troubles,
supervisories, etc.) to a remote monitoring location via the
public switched telephone network. Reporting formats are con-
tact ID, SIA 8 or SIA 20. E
NOTE: Unless otherwise specified, the term MS-25 is used in
this data sheet to refer to the MS-25 and the MS-25E. For el
details on the Canadian version,see DF-60704.
Features
• SBUS supports two ANN-80 Remote Annunciators
• JumpStart® auto-learn feature reduces installation time SLC Communication
and makes programming easy. • Single addressable SLC loop which meets NFPA Style 4
• Built-in digital communicator. (Class B) requirements.
• IP communicator compatible • 25 addressable device capacity (any combination of
• Two programmable Style Y (Class B) notification appliance addressable detectors and modules).
circuits(NACs). • Compatible with Honeywell Fire Systems (HFS) or equiva-
• Selectable strobe synchronization for System Sensor®, lent Fire-Lite detectors and modules.
Gentex®,Wheelock®or AMSECO devices.
Two programmable Form-C relays and one Form-C trouble Notification Appliance Circuits (NAGS)
• relay. Two independently programmable output circuits. Circuits
• Automatic detector sensitivity testing (NFPA 72 compliant). can be configured for the following outputs:
• Point status eliminates calibrated smoke test requirements —Style Y(Class B).
for NFPA 72. —Door Holder Service (cannot be used for notification
• Drift compensation. appliances).
• Alarm verification per zone of detectors. —Aux Power Source (cannot be used for notification appli-
• Walk-test. ances).
• Detectors and modules are code-wheel addressed for • Silence Inhibit and Auto-silence timer options.
faster installation time. • Continuous or Temporal code.
• Maintenance alert region. • Selectable strobe synchronization per NAC.
• Uses standard wire(unshielded or twisted pair). • Up to 2.0 A total output power, 1.0 A for auxiliary power and
•
Central Station reporting up to five zones. door holder. Each circuit can source up to the total system
current 2.0 A.
• Custom programming performed through the control
panel's built-in browser; no programming software is
required.
DF-60702:A1•9/16/2011—Page 1 of 4
Programming and Software • Low Battery Fault(yellow)
• Auto-learn JumpStart® feature for easy programming • Ground Fault(yellow)
reduces installation time. • Walk Test(yellow)
• Two programmable Form-C relay outputs. KEYPAD CONTROLS
• 5 programming zones. • Acknowledge
• Custom programming can be performed through control . Silence
panel's built-in browser.
• Drill
User Interface • System Reset(lamp test)
• 10-key numeric keypad
LED INDICATORS • 5 Zones Disable keypad
• AC Power(green) • 2 NACs Disable keypad
• Fire Alarm (red)
• Supervisory(yellow)
• Alarm Silenced (yellow)
• System Trouble(yellow)
• Disabled (yellow)
BG
Addressable
Pull Station
D355PL or HFS-D
Duct Smoke Detector
MMF-301 or HFS-MM
Miniature
Monitor Module
F
CRF-300 or HFS-MR
Addressable
Relay Module
SD355 or HFS-P
Intelligent
Photoelectric Detector
H355 or HFS-T
Intelligent
Temperature Sensor
E
N
�V E 4
Bells,Strobes,Horns,and NACs
Page 2 of 4—DF-60702:A1•9/16/2011
Product Line Information 005220: City Box Transmitter Module.
MS-25: Combination DACT/Fire Alarm Control Panel with one 007860: DACT Phone Cord(2 required).
SLC loop. Includes main circuit board with display,transformer, IPDACT 2/2UD, IPDACT Internet Monitoring Module:
backbox with door, manual, and required screws, cables, key, Connects to primary and secondary DACT telephone output
etc. Red, 120 VAC. ports for internet communications over customer provided eth-
MS-25E: Same as MS-25, but operates from 220/240 VAC. ernet internet connection. Requires compatible Teldat
VisorALARM Central Station Receiver. Can use DHCP or
MS-25C: Same as MS-25, but listed for Canadian applica- static IP. (See DF-60407 or DF-52424 for more information.)
tions. For details on the Canadian version,see DF-60704.
IPSPLT: Y-adaptor option allows connection of both panel
HONEYWELL FIRE SYSTEMS DEVICES dialer outputs to one IPDACT-2/2UD cable input.
HFS-P: Honeywell Fire Systems addressable photoelectric IPENC: External mounting enclosure consisting of mounting
smoke detector. Includes base. bracket IPBRKT, and screws. When using the supplied phone
HFS-PT: Honeywell Fire Systems addressable photoelectric cables, enclosure must be mounted within 6"(15.24 cm)of the
smoke detector with thermal sensor. Includes base. FACR Red.
HFS-T: Honeywell Fire Systems addressable fixed tempera- Wiring Requirements
ture heat detector. Includes base.
HFS-MM: Honeywell Fire Systems addressable Mini-Monitor While shielded wire is not required, it is recommended that all
module for normally-open contact devices. SLC wiring be twisted-pair to minimize the effects of electrical
HFS-MR: Honeywell Fire Systems addressable relay module. interference. Refer to the panel manual for wiring details.
HFS-D: Honeywell Fire Systems addressable photoelectric
duct smoke detector. Includes detector.
FIRE•LITE EQUIVALENT DEVICES
BG-12LX:Addressable dual-action manual pull station.
SD355:Addressable low-profile photoelectric smoke detector.
SD355T: Addressable low-profile photoelectric smoke detec-
tor with thermal sensor.
H355: Fast-response, low-profile heat detector.
D355PL: InnovairFlex low-flow non-relay duct-detector hous-
ing; includes SD355R.
MMF-301: Miniature version of MMF-300. Excludes LED and
Style D option. Connects with wire pigtails. May mount in
device backbox.
CRF-300: Addressable relay module containing two isolated
sets of Form-C contacts,which operate as a DPDT switch.
1300:This module isolates the SLC loop from short circuit con-
ditions
COMPATIBLE ANNUNCIATORS
ANN-80(-W): Remote LCD annunciator mimics the informa-
tion displayed on the FACP LCD display. Recommended wire
type is un-shielded. (Basic model is red; order-W version for
white;see DF-52417.)
ANN-SB80KIT-R: Red surface mount backbox with angled
wedge.
ANN-SB80KIT W: White surface mount backbox with angled
wedge.
MISCELLANEOUS
SB-1/0: Surface-mount backbox for the BG-12LX, plastic.
BG12TR: Optional trim ring for semi-flush mounting the pull-
station.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
BB-55F: Battery box, houses two 55 AH batteries.
CHG-75: Battery charger for lead-acid batteries with a rating
of 25 to 75 AH.
CHG-120F: Remote battery charging system for lead-acid bat-
teries with a rating of 55 to 120 AH. Requires additional BB-
55F for mounting.
BAT Series: Batteries. See DF-52397.
DF-60702:A1•9/16/2011—Page 3 of 4
SYSTEM SPECIFICATIONS
System Capacity Temperature and Humidity Ranges
• Intelligent Signalling Line Circuits.......................................1 This system meets NFPA requirements for operation at 0 —
• Addressable device capacity............................................25 49°C/32 — 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
• Programmable software zones...........................................5 useful life of the system's standby batteries and the electronic
• Annunciators ......................................................................2 components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
Electrical Specifications this system and its peripherals be installed in an environment
• AC Power: MS-25: 120 VAC, 60 Hz, 1.5 A. MS-25E: 230 with a normal room temperature of 15—27°C/60—80°F.
VAC, 50/60 Hz, 0.75 A. AC wire size is minimum 14 AWG
(2.00 mm2) with 600 V insulation. Nonpower-limited, super- Agency Listings and Approvals
vised. The listings and approvals below apply to the basic MS-25(E)
• Battery: Charging capacity 7-33 AH (18 AH for ULC appli- control panel. In some cases, certain modules may not be
cations). MS-25 cabinet holds maximum of two 7 AH batter- listed by certain approval agencies, or listing may be in pro-
ies. Larger batteries require a separate battery cabinet, cess. Consult factory for latest listing status.
such as the BB-26 or BB-55F. • UL Listed: S624
• Communication Loop: Supervised and power-limited. • CSFM:7165-0075:0217
• Notification Appliance Circuits: For the ULC-listed version, see DN-60641.
—Terminal Strip provides connections for two NACs,Style Y
(Class B). NFPA Standards
—Maximum signaling current:2.0 A.
The MS-25(E)complies with the following NFPA 72 Fire Alarm
—End-of-Line Resistor: 4.7 kOhm, 1/2 watt (P/N 71252 UL Systems requirements:
listed)for Style Y(Class B)NAC. Refer to the MS-25 man-
ual for listed compatible devices. —LOCAL (Automatic, Manual, Waterflow and Sprinkler
• Standby Current: 135 mA Supervisory).
• Alarm Current:220 mA —AUXILIARY (Automatic, Manual and Waterflow) (requires
5220 module).
• Aux Power Circuits: 1.OA @ 24 VDC per circuit, power —REMOTE STATION (Automatic, Manual, Waterflow and
limited Sprinkler Supervisory) (Where a DACT is not accepted,
• Two Programmable Relays and One Fixed Trouble the alarm, trouble and supervisory relays may be con-
Relay: nected to UL 864 listed transmitters.
—Contact rating:2.5 A @ 24 VDC(resistive). —PROPRIETARY(Automatic, Manual and Waterflow).
—Form-C relays, nonpower-limited, nonsupervised. —CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
Physical Specifications
• Dimensions: 15.2" H (38.42 cm) x 12.75" W (32.39 cm) x
3.4"D(8.57 cm)
• Weight: 11.5 lbs. (5.2 kg)
• Color: Red
Fire•Lite@ AlarmsO, JumpStartO, and System Sensor@ are registered
trademarks of Honeywell International Inc.
02011 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
I�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
ENGINEERING 8 MANUFACTURING All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com