HomeMy WebLinkAboutB12-0309 REV22 CR1 Test & Balance Report.pdf H-VAC, INC. .
OBSERVATION
DATE: 4/9/2013 REPORT
PROJECT: VAIL FIRE STATION#2
SYSTEM: HVAC
ATTN.:
Phone:
Fax:
SYSTEM OBSERVATION
FC-1-5 COOLING COILS SEASONAL TAB
CHILLER SEASONAL SYSTEM NOT CHARGED TAB
P-1 BOILER-1 LOW GPM 76%ON SPEED 3 CIRCUIT SETTER SET AT 4
ALL OTHER HVAC EQUIPMENT IS WITHIN+OR- 10%PER SPEC 15990
REVIEWED _REVISE AND RESUBMIT
_REJECTED _FURNISH AS CORRECTED
Corrections or comments made on the shop drawings this review do not relieve
contractor from compliance with requirements of the drawings and specifications. This
check is only for review of general conformance with the design concept of the project
and general compliance with the information given in the contract documents. The
contractor is responsible for:confirming and correlating all quantities and dimensions;
selecting fabrication processes and techniques of construction;coordinating his work
with that of all other trades;and performing his work in a satisfactory manner.
Date:04/10/2013 By: Martin Zourek
Architectural Engineering Consultants
�a00
Stanton Humphri
•C
S Gi 4`F
Note: the chiller system needs to be measured when operational in summer
season or the contractor shall override the control to force the system
operating to allow measurements during this season.
i
0
TEST, ADJUST AND BALANCE REPORT
PROJECT
VAIL FIRE STATION #2
#2734
PREPARED FOR
C & C MECHANICAL
REPORT ISSUE DATE
4/9/2013
PREPARED BY
H-VAC, INC.
P.O. BOX 5123
VAIL, CO 81658
PHONE: 970-331-1095
FAX: 970-926-0502
E-MAIL: BTOPPING@HVACTAB.NET
NVVVVW .*
TEST, ADJUST AND BALANCE REPORT
THE DATA I'RE:SI-N TED IN THIS REPORT IS AN EXACT RECORD OF
SYSTEM PERF(.)RMAN('l' kND WAS OBTAINED IN COMPLIANCE WITH NBC
PRACTICAL STANDARDS. ANY VARIANCES S FRONT THE DESIGN REQUIRE-
INIE:NTS ARE NOTED THROUGHOU T T111!S IZEPORT.
THE RESULTS SH0'1'1'N AND INFORMATION PRESENTED IN THIS
REPORT IS CERTIFIED TO BE ACCURATE AND C'OMPL'ETE, TO THE
EXTENT POSSIBLE BY EQUIPMENT AND PROCIA)URES USED THROUGH-
011"L'HIS SURN'll") .
THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN
COMPLIANCE WITH NBC PRACTICAL STANDARDS FOR TESTING, ADJUST-
ING AND BALANCING. OF ENVIRONMENTAL SYS'T'EMS AND THE PROJECT
SPEC'I Flt'ATIONS.
CERTIFIED BY: -__. _ DATE:
THE FINAL HYDRONIC DISTRIBLI110N SYSTEM MEASUREMENTS
ARE IN CONIPI.I.ANC'E: WITH N13C PRAC'TIC'AL STANDARDS FOR TESTING,
ADl .� \'\I) llAl..\\( IN(. OF E:NVIRONNIFNTAI, SYsTENIIS AND THE
PRi),IEX.1 5I'I ('111C A I IONS.
CE:I�'1'IFIEI) I3Y: _�� I)A'I'I+::
H-VAC, INC. W.AIURANTS THAT 'L'IIE AIR AND HYDIZO NIC SYSTEM
1A:1I..I ATFF) D(JRIN(l Tl IIS St II;\ I Y IS OPERATING AT THE SPI-VIFIED LEVELS
AS SHOWN WITHIN HIN TI IIS RFI'()RT. A_F AND ONLY A C THIS TINIF. H-VAC
N,IAKES NO O I'I IFR NVARRA N I II .S. S I VIT"D OR INII'I.11-1). C'0N(.TRN1NCi "6EI
('ONTINI 11.1) e')I'I.RA 110N 0R S.;\I::I-"I YIN I HE' l, ISL OF VI IIS
1't>1 '11'N1I IIII IS 'I'INIL..
►'VA C, E f T i f= l E D v.c i
1t L�►�1�1'14d U�1 i�Rr' Page: I
QA �
NATTONAl W P! (� ISG COUNCIL
` ll_�. lv
H-VA Cr Z INC.
IN T M NT !
F W IRW mv 19W qr v
PROJECT : VAIL FIRE STATION#2
INSTRUMENT/SERIAL# APPLICATION DATE OF USE CALIBRATION CALIBRATION
DATE DUE DATE
SHORTRIDGE ADM-870/CP#62913 AIR FLOW READINGS 3/15/2013 1/10/2013 1/10/2014
ALNOR ANEMOTER RVA801 CP#83799 AIR FLOW READINGS 3/15/2013 1/17/2013 1/17/2014
SHORTRIDGE FLOW HOOD AIF FLOW READINGS 3/15/2013
ALNOR HYGRO.TH-720/CP#41551 AIR TEMP/HUMIDITY 3/15/2013 1/12/2013 1/12/2014
PITOT TUBE 18" PRES.READINGS NOT USED N/A N/A
PITOT TUBE 24" PRES.READINGS 3/15/2013 N/A N/A
PITOT TUBE 36" PRES.READINGS NOT USED N/A N/A
SHIMPO TACHOMETER/CP#20213 RPM READINGS NOT USED 1/18/2013 1/18/2014
FLUKE T5-600 CP#41550 VOLT/AMP 3/15/2013 1/10/2013 1/10/2014
SHORTRIDGE HDM-300/#CP83800 WATER PRES.READINGS 3/15/2013 1/10/2013 1/10/2014
ASCROFT/0-100 PSI/#D068332-06 WATER PRES.READINGS NOT USED
FLUKE561 /CP101041 TEMP.READINGS 3/15/2013 1/29/2013 1/29/2014
REFRACTOMETER RHA-100 /#RHA- GLYCOL%READINGS NOT USED N/A N/A
100
*CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR
TEMPERATURE AND ALTITUDE.
PAGE:II
w
H-VAC, INC. I A
TEST REPORT
PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-1
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER ENVIRO TEK MANUFACTURER FASCO
MODEL HLP HP R.P.M. 1/6 -
SERIAL FCU121113-07 PHASE FRAME -
FAN TYPE CENTRIFUGAL S.F. TYPE - -
RATING/OUTLET 330CFM @0.3ESP/500CFM VOLTS AMPS 120 2.1
TOTAL
MIN OSA 0 THERMALLY PROTECTED YES
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE DD
MODEL NONE MOTOR BORE DD
SIZE/THERMAL NO. NONE FAN DRIVE DD
RANGE NONE FAN BORE DD
SET AT(AMPS) NONE NO. BELTS & SIZE DD
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY
CHANGE BELT TENSION SPEED
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 506 FAN R.P.M./ DD DD
MTR RPM
OSA CFM 0 VOLTAGE 122 122
RETURN CFM 506 AMPERAGE 1.4 1.4
F
-0.05 L COIL NA Cw 0.32
J
T ITW
E
NOTES: R
PAGE:
w
H-VAC, INC. I A
TEST REPORT
PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-2
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER ENVIRO TEK MANUFACTURER -
MODEL HLP HP R.P.M. 1/6 -
SERIAL FCU121113-07 PHASE FRAME - -
FAN TYPE CENTRIFUGAL S.F. TYPE - -
RATING/OUTLET 530CFM @0.3ESP/530CFM VOLTS AMPS 115 2.1
TOTAL
MIN OSA 0 THERMALLY PROTECTED -
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE DD
MODEL NONE MOTOR BORE DD
SIZE/THERMAL NO. NONE FAN DRIVE DD
RANGE NONE FAN BORE DD
SET AT(AMPS) NONE NO. BELTS & SIZE DD
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY
CHANGE BELT TENSION SPEED
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 527 FAN R.P.M./ DD DD
MTR RPM
OSA CFM 0 VOLTAGE 122 122
RETURN CFM 527 AMPERAGE 1.6 0.6
F (? ;7 COIL
-O,01 L NA CW 0.08
T
'J HW
E
NOTES: SET AT LOW SPEED R
PAGE:
w
H-VAC, INC. I A
TEST REPORT
PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-3
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER ENVIRO TEK MANUFACTURER -
MODEL HLP HP R.P.M. 1/6 -
SERIAL FCU121113-07 PHASE FRAME - -
FAN TYPE CENTRIFUGAL S.F. TYPE - -
RATING/OUTLET 975CFM @0.3ESP/975CFM VOLTS AMPS 115 4.2
TOTAL
MIN OSA 0 THERMALLY PROTECTED -
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE DD
MODEL NONE MOTOR BORE DD
SIZE/THERMAL NO. NONE FAN DRIVE DD
RANGE NONE FAN BORE DD
SET AT(AMPS) NONE NO. BELTS & SIZE DD
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY
CHANGE BELT TENSION SPEED
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 978 FAN R.P.M./ DD DD
MTR RPM
OSA CFM 0 VOLTAGE 123 123
RETURN CFM 978 AMPERAGE 1.0 1.0
F
COIL
-0.05 L NA O CW 0.29
T
'J HW
E
NOTES: SET AT LOW SPEED R
PAGE:
w
H-VAC, INC. I A
TEST REPORT
PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-4
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER ENVIRO TEK MANUFACTURER -
MODEL HLP HP R.P.M. 1/6 -
SERIAL FCU121113-07 PHASE FRAME - -
FAN TYPE CENTRIFUGAL S.F. TYPE - -
RATING/OUTLET 940CFM @0.3ESP/940CFM VOLTS AMPS 115 4.2
TOTAL
MIN OSA 0 THERMALLY PROTECTED -
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE DD
MODEL NONE MOTOR BORE DD
SIZE/THERMAL NO. NONE FAN DRIVE DD
RANGE NONE FAN BORE DD
SET AT(AMPS) NONE NO. BELTS & SIZE DD
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY
CHANGE BELT TENSION SPEED
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 1012 FAN R.P.M./ DD DD
MTR RPM
OSA CFM 0 VOLTAGE 122 122
RETURN CFM 1012 AMPERAGE 2.8 1.7
F
I
COIL
-0.03 T NA �� CW 0.20
E HW
R
NOTES: SET AT MEDIUM SPEED
PAGE:
w
H-VAC, INC. I A
TEST REPORT
PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-5
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER ENVIRO TEK MANUFACTURER -
MODEL HLP HP R.P.M. 1/6 -
SERIAL FCU121113-07 PHASE FRAME - -
FAN TYPE CENTRIFUGAL S.F. TYPE - -
RATING/OUTLET 520CFM @0.3ESP/510CFM VOLTS AMPS 115 2.1
TOTAL
MIN OSA 0 THERMALLY PROTECTED -
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE DD
MODEL NONE MOTOR BORE DD
SIZE/THERMAL NO. NONE FAN DRIVE DD
RANGE NONE FAN BORE DD
SET AT(AMPS) NONE NO. BELTS & SIZE DD
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY
CHANGE BELT TENSION SPEED
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 491 FAN R.P.M./ DD DD
MTR RPM
OSA CFM 0 VOLTAGE 122 122
RETURN CFM 491 AMPERAGE 1.5 0.6
F
-0.05 L NA O CW COIL 0.09
T
HW
E
NOTES: SET AT LOW SPEED R
PAGE:
i
f. 7
H-VAC, INC.
TEST REPORT
PROJECT: VAIL FIRE STATION#2 SYSTEM: FC-1,2,3,4,5
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
FC-1 1 SR 9/9 170 204 172
2 SR 9/9 330 224 334
500 428 506 TOTAL
FC-2 1 SR 6/16 330 1045 337
2 SR 11/3 200 - 195
530 1045 532 TOTAL
FC-3 1 SR - 575 1065 577
2 SR 200 38 197
3 SR 200 22 204
975 1125 978 TOTAL
FC-4 1 SR 21/5 540 779 591
2 SR 1515 400 427 421
940 1206 1012 TOTAL
FC-5 1 SR 7/3 140 134 131
2 SR 7/3 120 122 115
3 SR 515 50 0 47
4 SR 7/3 100 130 97
5 SR 7/3 l00 134 101
510 520 491 TOTAL
NOTES:
PAGE:
w
H-VAC, INC. I A
TEST REPORT
PROJECT: VAIL FIRE STATION #2 SYSTEM: HRV-1
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER AMERICAN ALDES MANUFACTURER -
MODEL 50ODDD HP R.P.M. - -
SERIAL NEBB 120312004398 PHASE FRAME - -
FAN TYPE CENTRIFUGAL S.F. TYPE - -
RATING/OUTLET 300CFM @0.8ESP/300CFM VOLTS AMPS 120 6.2
TOTAL
THERMALLY PROTECTED -
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE DD
MODEL NONE MOTOR BORE DD
SIZE/THERMAL NO. NONE FAN DRIVE DD
RANGE NONE FAN BORE DD
SET AT(AMPS) NONE NO. BELTS & SIZE DD
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY
CHANGE BELT TENSION SPEED
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 273 FAN R.P.M./ DD DD
MTR RPM
VOLTAGE 121 121
AMPERAGE 4.4 2.3
F
-0..20 L NA 0.16
T \J,
E
NOTES: R
SET AT LOW SPEED
PAGE:
H-VAC, INC. L-
TEST REPORT
PROJECT: VAIL FIRE STATION#2 SYSTEM: HRV-1 , EF-1 , EF-2
SYSTEM TERMINAL DESIGN INITIAL FINAL 746;TES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
HRV-1 1 SR 11/7 150 232 140
2 SR 11/7 150 250 133
300 482 273 TOTAL
EF-1 A 91 - 97
B 91 131 131
C 91 131 131
D 91 136 136
E 91 108 108
F 91 94 94
G 91 87 87
H 91 73 73
EF-2 1 257 234 234
't--77J
NOTES:
PAGE:
H-VAC, INC. BALANCE VALVE
TEST REPORT
PROJECT: VAIL FIRE STATION#2 SYSTEM:P-1-2-3-4-5-6-7
FLOW METER DESIGN MEASURED
DESIGN DESIGN VALVE
LOCATION TYPE SIZE GPM AP FINALA P POSITION FINAL GPM
/o OPEN
P-1 BL-1 TA 1" 8.0 9.5 .89' 4 6.1
P-2 BL-2 TA 1" 5.5 9.3 .81 4 5.6
P-1 BL-1 GRUNDFOS _ 8.0 9.5 .89' SPD-3 6.1
UPS15-58FC
P-2 BL-2 GPRUNDFOS _ 5.5 9.3 .81' SPD-2 5.6
P-3 WH-1 GRUNDFOS _ 8.0 12.0 10.8' SPD-3 8.4
UPS15-58FC
P-4 BLDG HEAT GRUNDFOS _ 8.7 9.5 - - *1
UPS 15-55F
P-5 HX-1 GRUNDFOS _ 11.0 5.0 3.6' SPD-2 10.9
UPS15-58FC
P-6 (SPD1) SM GRUNDFOS _ 13.0 18.0 21.8' SPD-1 12
P 4 -1 OS
P-7 CHILLER - - 8.8 20.0 - - *4
DOM HW RECIRC TB4ACO 006- _ *1
FC-1 HW TA 3/4 1.0 1.07 1.5 1.0
FC-2 HW TA 3/4 0.9 1.53 2.0 1.1
FC-3 HW TA 3/4 1.3 1.45 1.5 1.2
FC-4 HW TA 3/4 1.3 1.19 1.5 1.1
FC-5 HW TA 3/4 0.9 1.14 1.5 1.0
FC-1 CW TA _ _ *4
FC-2 CW TA *4
FC-3 CW TA _ *4
FC-4 CW TA _ *4
FC-5 CW TA *4
HC-1 - EAT-67 AT-1 13 *1
. DEGREES DEGREES
CH-1 10 - -
*4
NOTES:
*1 DENOTES NO PIETIES PLUGS/NO CIRCUIT SETTER
*4 DENOTES SEASONAL TESTING PAGE:
i
I• �. w �' � Vii" r.a
H-VAC, INC. BALANCE VALVE
TEST REPORT
PROJECT: VAIL FIRE STATION#2 SYSTEM:SM MANIFOLDS/ RFZ
FLOW METER DESIGN MEASURED
DESIGN DESIGN VALVE
LOCATION TYPE SIZE GPM AP FINALA P POSITION FINAL GPM
/o OPEN
SM MANIFOLD 1-1 7.2 5.6 *1
SM MANIFOLD 1-2 2.7 4.5 *1
SM MANIFOLD 2-3 2.6 4.0 *1
RFZ-1-1 MIENS 0.6 2.0 *1
BATH
RFZ-1-2 WOMENS 0.8 4.5 *1
BATH
NOTES:
*1 DENOTES NO PIETIES PLUGS/NO CIRCUIT SETTER
PAGE:
vlv,-
- � U
�E
U 2
a �
L—Y—�
I r•c
7
(� d .
\u'
4 m
�. � � ,�V� o •� I —` f � nom.}' .� ^�}r �'- .\
El
I � W",
O .
vo
�U
— 1
n
L ,
3>S4 a ap'Z is ~-•� R ��� 1 '�.
ii r g
ar [x� m y �uai f" casj3 `i S - p '3W x�
w��
i iy �°`�,` '� x C m ' w ' t� LL' G # a rr�oa ✓i�c
} nl
It
n I7
oil
Al
-��� , G7
(D oil iO 15 AH 4
12