Loading...
HomeMy WebLinkAboutB12-0309 REV22 CR1 Test & Balance Report.pdf H-VAC, INC. . OBSERVATION DATE: 4/9/2013 REPORT PROJECT: VAIL FIRE STATION#2 SYSTEM: HVAC ATTN.: Phone: Fax: SYSTEM OBSERVATION FC-1-5 COOLING COILS SEASONAL TAB CHILLER SEASONAL SYSTEM NOT CHARGED TAB P-1 BOILER-1 LOW GPM 76%ON SPEED 3 CIRCUIT SETTER SET AT 4 ALL OTHER HVAC EQUIPMENT IS WITHIN+OR- 10%PER SPEC 15990 REVIEWED _REVISE AND RESUBMIT _REJECTED _FURNISH AS CORRECTED Corrections or comments made on the shop drawings this review do not relieve contractor from compliance with requirements of the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract documents. The contractor is responsible for:confirming and correlating all quantities and dimensions; selecting fabrication processes and techniques of construction;coordinating his work with that of all other trades;and performing his work in a satisfactory manner. Date:04/10/2013 By: Martin Zourek Architectural Engineering Consultants �a00 Stanton Humphri •C S Gi 4`F Note: the chiller system needs to be measured when operational in summer season or the contractor shall override the control to force the system operating to allow measurements during this season. i 0 TEST, ADJUST AND BALANCE REPORT PROJECT VAIL FIRE STATION #2 #2734 PREPARED FOR C & C MECHANICAL REPORT ISSUE DATE 4/9/2013 PREPARED BY H-VAC, INC. P.O. BOX 5123 VAIL, CO 81658 PHONE: 970-331-1095 FAX: 970-926-0502 E-MAIL: BTOPPING@HVACTAB.NET NVVVVW .* TEST, ADJUST AND BALANCE REPORT THE DATA I'RE:SI-N TED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERF(.)RMAN('l' kND WAS OBTAINED IN COMPLIANCE WITH NBC PRACTICAL STANDARDS. ANY VARIANCES S FRONT THE DESIGN REQUIRE- INIE:NTS ARE NOTED THROUGHOU T T111!S IZEPORT. THE RESULTS SH0'1'1'N AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE ACCURATE AND C'OMPL'ETE, TO THE EXTENT POSSIBLE BY EQUIPMENT AND PROCIA)URES USED THROUGH- 011"L'HIS SURN'll") . THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PRACTICAL STANDARDS FOR TESTING, ADJUST- ING AND BALANCING. OF ENVIRONMENTAL SYS'T'EMS AND THE PROJECT SPEC'I Flt'ATIONS. CERTIFIED BY: -__. _ DATE: THE FINAL HYDRONIC DISTRIBLI110N SYSTEM MEASUREMENTS ARE IN CONIPI.I.ANC'E: WITH N13C PRAC'TIC'AL STANDARDS FOR TESTING, ADl .� \'\I) llAl..\\( IN(. OF E:NVIRONNIFNTAI, SYsTENIIS AND THE PRi),IEX.1 5I'I ('111C A I IONS. CE:I�'1'IFIEI) I3Y: _�� I)A'I'I+:: H-VAC, INC. W.AIURANTS THAT 'L'IIE AIR AND HYDIZO NIC SYSTEM 1A:1I..I ATFF) D(JRIN(l Tl IIS St II;\ I Y IS OPERATING AT THE SPI-VIFIED LEVELS AS SHOWN WITHIN HIN TI IIS RFI'()RT. A_F AND ONLY A C THIS TINIF. H-VAC N,IAKES NO O I'I IFR NVARRA N I II .S. S I VIT"D OR INII'I.11-1). C'0N(.TRN1NCi "6EI ('ONTINI 11.1) e')I'I.RA 110N 0R S.;\I::I-"I YIN I HE' l, ISL OF VI IIS 1't>1 '11'N1I IIII IS 'I'INIL.. ►'VA C, E f T i f= l E D v.c i 1t L�►�1�1'14d U�1 i�Rr' Page: I QA � NATTONAl W P! (� ISG COUNCIL ` ll_�. lv H-VA Cr Z INC. IN T M NT ! F W IRW mv 19W qr v PROJECT : VAIL FIRE STATION#2 INSTRUMENT/SERIAL# APPLICATION DATE OF USE CALIBRATION CALIBRATION DATE DUE DATE SHORTRIDGE ADM-870/CP#62913 AIR FLOW READINGS 3/15/2013 1/10/2013 1/10/2014 ALNOR ANEMOTER RVA801 CP#83799 AIR FLOW READINGS 3/15/2013 1/17/2013 1/17/2014 SHORTRIDGE FLOW HOOD AIF FLOW READINGS 3/15/2013 ALNOR HYGRO.TH-720/CP#41551 AIR TEMP/HUMIDITY 3/15/2013 1/12/2013 1/12/2014 PITOT TUBE 18" PRES.READINGS NOT USED N/A N/A PITOT TUBE 24" PRES.READINGS 3/15/2013 N/A N/A PITOT TUBE 36" PRES.READINGS NOT USED N/A N/A SHIMPO TACHOMETER/CP#20213 RPM READINGS NOT USED 1/18/2013 1/18/2014 FLUKE T5-600 CP#41550 VOLT/AMP 3/15/2013 1/10/2013 1/10/2014 SHORTRIDGE HDM-300/#CP83800 WATER PRES.READINGS 3/15/2013 1/10/2013 1/10/2014 ASCROFT/0-100 PSI/#D068332-06 WATER PRES.READINGS NOT USED FLUKE561 /CP101041 TEMP.READINGS 3/15/2013 1/29/2013 1/29/2014 REFRACTOMETER RHA-100 /#RHA- GLYCOL%READINGS NOT USED N/A N/A 100 *CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE:II w H-VAC, INC. I A TEST REPORT PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-1 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER ENVIRO TEK MANUFACTURER FASCO MODEL HLP HP R.P.M. 1/6 - SERIAL FCU121113-07 PHASE FRAME - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET 330CFM @0.3ESP/500CFM VOLTS AMPS 120 2.1 TOTAL MIN OSA 0 THERMALLY PROTECTED YES STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE NONE FAN BORE DD SET AT(AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY CHANGE BELT TENSION SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 506 FAN R.P.M./ DD DD MTR RPM OSA CFM 0 VOLTAGE 122 122 RETURN CFM 506 AMPERAGE 1.4 1.4 F -0.05 L COIL NA Cw 0.32 J T ITW E NOTES: R PAGE: w H-VAC, INC. I A TEST REPORT PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-2 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER ENVIRO TEK MANUFACTURER - MODEL HLP HP R.P.M. 1/6 - SERIAL FCU121113-07 PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET 530CFM @0.3ESP/530CFM VOLTS AMPS 115 2.1 TOTAL MIN OSA 0 THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE NONE FAN BORE DD SET AT(AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY CHANGE BELT TENSION SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 527 FAN R.P.M./ DD DD MTR RPM OSA CFM 0 VOLTAGE 122 122 RETURN CFM 527 AMPERAGE 1.6 0.6 F (? ;7 COIL -O,01 L NA CW 0.08 T 'J HW E NOTES: SET AT LOW SPEED R PAGE: w H-VAC, INC. I A TEST REPORT PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-3 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER ENVIRO TEK MANUFACTURER - MODEL HLP HP R.P.M. 1/6 - SERIAL FCU121113-07 PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET 975CFM @0.3ESP/975CFM VOLTS AMPS 115 4.2 TOTAL MIN OSA 0 THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE NONE FAN BORE DD SET AT(AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY CHANGE BELT TENSION SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 978 FAN R.P.M./ DD DD MTR RPM OSA CFM 0 VOLTAGE 123 123 RETURN CFM 978 AMPERAGE 1.0 1.0 F COIL -0.05 L NA O CW 0.29 T 'J HW E NOTES: SET AT LOW SPEED R PAGE: w H-VAC, INC. I A TEST REPORT PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-4 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER ENVIRO TEK MANUFACTURER - MODEL HLP HP R.P.M. 1/6 - SERIAL FCU121113-07 PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET 940CFM @0.3ESP/940CFM VOLTS AMPS 115 4.2 TOTAL MIN OSA 0 THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE NONE FAN BORE DD SET AT(AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY CHANGE BELT TENSION SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 1012 FAN R.P.M./ DD DD MTR RPM OSA CFM 0 VOLTAGE 122 122 RETURN CFM 1012 AMPERAGE 2.8 1.7 F I COIL -0.03 T NA �� CW 0.20 E HW R NOTES: SET AT MEDIUM SPEED PAGE: w H-VAC, INC. I A TEST REPORT PROJECT: VAIL FIRE STATION #2 SYSTEM: FC-5 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER ENVIRO TEK MANUFACTURER - MODEL HLP HP R.P.M. 1/6 - SERIAL FCU121113-07 PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET 520CFM @0.3ESP/510CFM VOLTS AMPS 115 2.1 TOTAL MIN OSA 0 THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE NONE FAN BORE DD SET AT(AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY CHANGE BELT TENSION SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 491 FAN R.P.M./ DD DD MTR RPM OSA CFM 0 VOLTAGE 122 122 RETURN CFM 491 AMPERAGE 1.5 0.6 F -0.05 L NA O CW COIL 0.09 T HW E NOTES: SET AT LOW SPEED R PAGE: i f. 7 H-VAC, INC. TEST REPORT PROJECT: VAIL FIRE STATION#2 SYSTEM: FC-1,2,3,4,5 SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-1 1 SR 9/9 170 204 172 2 SR 9/9 330 224 334 500 428 506 TOTAL FC-2 1 SR 6/16 330 1045 337 2 SR 11/3 200 - 195 530 1045 532 TOTAL FC-3 1 SR - 575 1065 577 2 SR 200 38 197 3 SR 200 22 204 975 1125 978 TOTAL FC-4 1 SR 21/5 540 779 591 2 SR 1515 400 427 421 940 1206 1012 TOTAL FC-5 1 SR 7/3 140 134 131 2 SR 7/3 120 122 115 3 SR 515 50 0 47 4 SR 7/3 100 130 97 5 SR 7/3 l00 134 101 510 520 491 TOTAL NOTES: PAGE: w H-VAC, INC. I A TEST REPORT PROJECT: VAIL FIRE STATION #2 SYSTEM: HRV-1 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER AMERICAN ALDES MANUFACTURER - MODEL 50ODDD HP R.P.M. - - SERIAL NEBB 120312004398 PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET 300CFM @0.8ESP/300CFM VOLTS AMPS 120 6.2 TOTAL THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE NONE FAN BORE DD SET AT(AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE DRIVE MOTOR ADJ PULLEY CHANGE BELT TENSION SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 273 FAN R.P.M./ DD DD MTR RPM VOLTAGE 121 121 AMPERAGE 4.4 2.3 F -0..20 L NA 0.16 T \J, E NOTES: R SET AT LOW SPEED PAGE: H-VAC, INC. L- TEST REPORT PROJECT: VAIL FIRE STATION#2 SYSTEM: HRV-1 , EF-1 , EF-2 SYSTEM TERMINAL DESIGN INITIAL FINAL 746;TES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM HRV-1 1 SR 11/7 150 232 140 2 SR 11/7 150 250 133 300 482 273 TOTAL EF-1 A 91 - 97 B 91 131 131 C 91 131 131 D 91 136 136 E 91 108 108 F 91 94 94 G 91 87 87 H 91 73 73 EF-2 1 257 234 234 't--77J NOTES: PAGE: H-VAC, INC. BALANCE VALVE TEST REPORT PROJECT: VAIL FIRE STATION#2 SYSTEM:P-1-2-3-4-5-6-7 FLOW METER DESIGN MEASURED DESIGN DESIGN VALVE LOCATION TYPE SIZE GPM AP FINALA P POSITION FINAL GPM /o OPEN P-1 BL-1 TA 1" 8.0 9.5 .89' 4 6.1 P-2 BL-2 TA 1" 5.5 9.3 .81 4 5.6 P-1 BL-1 GRUNDFOS _ 8.0 9.5 .89' SPD-3 6.1 UPS15-58FC P-2 BL-2 GPRUNDFOS _ 5.5 9.3 .81' SPD-2 5.6 P-3 WH-1 GRUNDFOS _ 8.0 12.0 10.8' SPD-3 8.4 UPS15-58FC P-4 BLDG HEAT GRUNDFOS _ 8.7 9.5 - - *1 UPS 15-55F P-5 HX-1 GRUNDFOS _ 11.0 5.0 3.6' SPD-2 10.9 UPS15-58FC P-6 (SPD1) SM GRUNDFOS _ 13.0 18.0 21.8' SPD-1 12 P 4 -1 OS P-7 CHILLER - - 8.8 20.0 - - *4 DOM HW RECIRC TB4ACO 006- _ *1 FC-1 HW TA 3/4 1.0 1.07 1.5 1.0 FC-2 HW TA 3/4 0.9 1.53 2.0 1.1 FC-3 HW TA 3/4 1.3 1.45 1.5 1.2 FC-4 HW TA 3/4 1.3 1.19 1.5 1.1 FC-5 HW TA 3/4 0.9 1.14 1.5 1.0 FC-1 CW TA _ _ *4 FC-2 CW TA *4 FC-3 CW TA _ *4 FC-4 CW TA _ *4 FC-5 CW TA *4 HC-1 - EAT-67 AT-1 13 *1 . DEGREES DEGREES CH-1 10 - - *4 NOTES: *1 DENOTES NO PIETIES PLUGS/NO CIRCUIT SETTER *4 DENOTES SEASONAL TESTING PAGE: i I• �. w �' � Vii" r.a H-VAC, INC. BALANCE VALVE TEST REPORT PROJECT: VAIL FIRE STATION#2 SYSTEM:SM MANIFOLDS/ RFZ FLOW METER DESIGN MEASURED DESIGN DESIGN VALVE LOCATION TYPE SIZE GPM AP FINALA P POSITION FINAL GPM /o OPEN SM MANIFOLD 1-1 7.2 5.6 *1 SM MANIFOLD 1-2 2.7 4.5 *1 SM MANIFOLD 2-3 2.6 4.0 *1 RFZ-1-1 MIENS 0.6 2.0 *1 BATH RFZ-1-2 WOMENS 0.8 4.5 *1 BATH NOTES: *1 DENOTES NO PIETIES PLUGS/NO CIRCUIT SETTER PAGE: vlv,- - � U �E U 2 a � L—Y—� I r•c 7 (� d . \u' 4 m �. � � ,�V� o •� I —` f � nom.}' .� ^�}r �'- .\ El I � W", O . vo �U — 1 n L , 3>S4 a ap'Z is ~-•� R ��� 1 '�. ii r g ar [x� m y �uai f" casj3 `i S - p '3W x� w�� i iy �°`�,` '� x C m ' w ' t� LL' G # a rr�oa ✓i�c } nl It n I7 oil Al -��� , G7 (D oil iO 15 AH 4 12