HomeMy WebLinkAboutE05-0070 -. _
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ELECTRICAL PERMIT Permit #: E05-0070
Job Address: 1 WILLOW BRIDGE RD VAIL Status . . . : FINAL
Location.....: 1 Willow Bridge Rd Applied . . : OS/10/2005
Parcel No...: 210108284001 Issued . . : OS/11/2005
Legal Description: RESUB OF TRACTK-L Expires . .: 04/24/2008
Project No :
OWNER VAIL DOVER ASSOCIATES LLC 09/10/2004
4148 N ARCADIA DR
PHOENIX
AZ 85018
APPLICANT ENCORE ELECTRIC 05/10/2005 Phone: (970) 949-9277
PO BOX 8849
AVON
CO 81620
License: 331-E
CONTRACTOR ENCORE ELECTRIC 05/10/2005 Phone: (970) 949-9277
PO BOX 8849
AVON
CO 81620
License: 331-E
Desciption: Swiss Haus redevelopment/One Willow Bridge
Valuation: 1,545,351.00 Square feet: 53579
•**************�***********�********+*****��***�*r******r�*+******� FEE SUMMARY *�***s***�*v**r*a****r**r►***►*************+****�►**►**�***�
Electrical---------> $30,779.00 Total Calculated Fees--> $30,782.00
Investigation----> $0.00 Additional Fees----------> $0.00
Will Call---------> $3.00 Total Permit Fee--------> $30,782.00
TOTAL FEES--> 530,782.00 Payments------------------> 530,782.00
BALANCE DUE--------> S0.00
*►*******r**a********�**�*�+******t*****s***�*ssrr*�****�s**************r**r+**►*�r***��**r�*****�*�*r:*�M**++�**+**��**+***+**+»*�*t**►t*r*****+
Approvals:
Item: 06000 ELECTRICAL DEPARTMENT
05/10/2005 JS Action: AP
Item: 05600 FIRE DEPARTMENT
i####�#####f**##*##%t##**#f*#*t**#***#**##I##*t##**#k4####+k**t#R*##*►#!�#*4*#***#**###M####*A#***#*k#**rt*#*�*#I*#**►##*###*##�Ft##4###4ti#►##k####
CONDITIONS OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
.�.,*..*.**�.**..*•..■*:...:.*�..*�.**:*.*.*..**+.*.*:*.*.�...**.+.....«.:.*.**..�..*+.***,...+.*.�.,*.*+.*+*....�.+».*.*....*.,.,:+»..,.*.,......
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 479-2149 OR AT OUR OFFICE FROM 8:00 AM-4 PM.
*********************************************************+**********************************
TOWN OF VAIL, COLORADOCopy Reprinted on 04-12-2013 at 15:23:10 04/12/2013
Statement
******************************************�****�******************************************+*
Statement Number: R050000561 Amount: $30, 782.0005/11/200509:04 AM
Payment Method: Check Init: DDG
Notation: Encore
Electric 015002
--------------------------------------------------------
Permit No: E05-0070 Type: ELECTRICAL PERMIT
Parcel No: 2101-082-8400-1
2101-082-8400-2
2101-082-8400-3
2101-082-8400-5
2101-082-8400-6
2101-082-8400-7
2101-082-8400-9
2101-082-8401-0
2101-082-8401-1
2101-082-8401-2
2101-082-8401-3
2101-082-8401-4
2101-082-8901-5
2101-082-8401-6
2101-082-8401-7
2101-082-8401-8
2101-082-8401-9
2101-082-8402-0
2101-082-8402-1
2101-082-8402-2
2101-082-8402-3
2101-082-8402-7
Site Address: 1 WILLOW BRIDGE RD VAIL
Location: 1 Willow Bridge Rd
Total Fees: $30, 782.00
This Payment: $30,782.00 Total ALL Pmts: $30, 782.00
Balance: $0.00
*****************************************+**********************�***+************+**********
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------
EP 00100003111100 ELECTRICAL PERMIT FEES 30, 779.00
WC 00100003112800 WILL CALL INSPECTION FEE 3.00
----------------------------------------------------------
E05-0070: Entries for Item:190 - ELEC-Final 15:23 04/12/2013
Action Comments By Date Unique_
Ke
PA partial approval for 17 parking spaces required shahn 06/30/2006 A800091
for TCO.Witnessed exit and emergency
li htin .
APPR unit 101 and 102 only eg 12/14/2006 A000096
852
NO inspection cancelled prior to visit. shahn 12/29/2006 A000097
258
PA UNITS 201-202 FINAL APPROVED. SHAHN 01I03/2007 A000097
347
CR UNITS 203 AND 204 WALL SCONCE SMAHN 01/09/2007 A000097
FIXTURES IN BEDROOM#1 DOES NOT 538
WORK. CALL FOR REINSPECT.
PI EXIT SIGNS AND EGRESS LIGHTING SHAHN 01/16/2007 6600097
TESTED FOR EMERGENCY POWER.
EXIT SIGN LOCATIONS ARE CONFUSING
AND SHALL BE REVIEWED.
STAIRWELLS EM POWER FOR
1,2,3,4,5,6,8,9,1 0 OK.
ELEV LOBBY EM POWER FOR 201/202,
301/302,303/304,203/204 OK.
FRONT ENTRY,COMMON RR, 1ST FLOOR
CORRIDOR, DEN, PANTRY WALLS&
CEILING,SUNROOM,CONCIER, ENTRY
VESTIBULE, ELEV#2 AND#3 AND FIRE
COMMAND OK.
PI PARTIAL FOR KITCHENNETTE. shahn 01/18/2007 A230097
STAFF CEILINGS ONLY.
OPERATION OFFICE CEILINGS ONLY.
PA NO ACCESS TO 303&304. SHAHN 02/15I2007 3590098
UNITS 301 AND 302 APPROVED.
PA Units 303&304. Need panel schedule in 304 JEC 02/22/2007 4030098
PA units 205&305 JEC 03/22/2007 A000099
104
CR MECHIBOILER ROOM: LV CONDUITS NOT shahn 04/05/2007 4600099
SUPPORTED WITHIN 3FT OF BOX PER
NEC 300.
APPROVED SPRINKLER RISER ROOM,
MACHINE ROOMS#1,#2,#3,#4,&5,
PHONE/EQUIP ROOM, MAIN ELEC ROOM,
POOL MECH ROOM,&OPERATIONS
OFFICE.
CR inspected rooftop for encore permit only. shahn 04/11/2007 6380099
(marketplace has issues)
UNIT 306 OK.
LOADING DOCK OK.
TRUCKER RR OK.
THE LV CONDUITS FAILED INSPECTION
AGAIN FOR LACK OF SUPORTS AS NOTED
4/5I07.
PA FINAL 207&208 UNITS AND VESTIBULES. shahn 10/19/2007 5500106
NR 403 NOT READY AT 4:OOPM. shahn 10/22/2007 6300106
PA unit 403 including elevator vestibule. shahn 10/24/2007 6990106
PA final 402 elev and unit ok. shahn 11/09/2007 4850107
PA UNIT 308 OK. shahn 12/11/2007 A000109
192
NR UNIT 404 NOT READY FOR INSPECTION. SHAHN 12/17/2007 4850109
AP 404 AND 404 ELEVATOR FINAL OK. shahn 12/19/2007 6560109
PA unit 401 and vestibule approvedt shahn 02/14/2008 A820111
Page 1
E05-0070: Entries for Item:190 - ELEC-Final 15:23 04/12/2013
p�p sgremmer 04/24/2008 A000112
838
Total Rows:21