HomeMy WebLinkAboutB13-0101 LOAD CALCS.pdf ELECTRICAL LOAD SUMMARY (EXISTING DNELLIN6 UNIT CALCULATION)
UNIT: W5
EXIBTMS LOAD GALUUATION
LIGHTING # 6ENERAL RECEPTACLES
AREA(5.F): VA/S.F. LOAD
1,873 3.0 = 5619 VA
SMALL APPLIANCES
2 1500 - 3000 VA
8619 VA
LAUNDRY BRANCH CIRCUIT
1 1500 - 1500 VA
1500 VA
APPLIANCES:
APPLIANCE QTY LOAD
P15HWASHM 1 1200 VA = 1200 VA
REFRIGERATOR 1 1800 VA = 1800 VA
DISPOSAL 1 1200 VA = 1200 VA
MICROWAVE/HOOD COMBO 1 1200 VA = 1200 VA
BATHROOM EF 3 50 VA = 150 VA
JACUZZI TUB 1 1200 VA - 1200 VA
6'750 VA
COOKING EQUIPMENT:
ELECTRIC OVEN/RAN6E 1 8500 VA = 8500 VA
8500 VA
DRYERS:
ELECTRIC DRYER 1 5000 VA = 5000 VA
5000 VA
TOTAL NON-DEMANDED VA: 28869 VA
TOTAL.EXI5TIN6 LOAD
FIRST 8,000 VA AT 100%: 8000 VA X 10096 = 8000 VA
REMAINING VA AT 40%: 20869 VA X 40% = 8348 VA
TOTAL ELECTRICAL LOAD WITH DEMAND FACTORS = 16348 VA
AMPS AT 208V,IPH = '79 AMPS
ADDED LOAD C44XALATION
APPLIANCES:
APPLIANCE QTY LOAD
BATHROOM HEATER 1 500 VA = 500 VA
BATHROOM FLOOR HEATING 46 12 VA/5F = 552 VA
STEAM GENERATOR 1 6000 VA = 6000 VA
WINE COOLER 1 1200 VA - 1200 VA
8252 VA
TOTAL NON-DEMANDED VA: 8252 VA
TOTAL ADDED LOAD
FIRST 8,000 VA AT 100%: 8000 VA X 100% = 8000 VA
REMAINING VA AT 40%: 252 VA X 40% = 101 VA
TOTAL ELECTRICAL LOAD WITH DEMAND FACTORS = 8101 VA 0 RIF
AMPS AT 206V,IPH = 39 AMPS
TOTAL NEW LOAD ON EXI57IN6 PANEL re
TOTAL NON-DEMANDED LOAD: 3'7121 VA r f y r
5837 0
FIRST 8,000 VA AT 100%: 8000 VA X 100% = 8000 VA
REMAINING VA AT 40%: 29121 VA X 40% = 11648 VA a
. •ti .•• '
TOTAL L9.EGTriICAL LOAD wn+DB•IMD PACTORS• a64e VA
AMPS AT 200V,LPN■ 44 AMPS •••
UNIT 640 REMODEL Date: By:
0DISCIGIN 1900 Wazee Street 04-OCI-15 JEM
Suite#350 ELEGTRIGAL LOAD GALGULATION5
Denver,Colorado 80202 �7� Scale: Job#:
303.296.3034 VOICE ILL: UNIT 635 NONE 2445.00
303.296.3035 FA%aedesi Wn @aedesign-in,.,m RIVA RIDGE NORTH CONDOMINIUM.aedesign-inc.com Sheet#:
URAL ENGINEERING UNIT 640 REMODEL E1 . 0
GROUP,INC. 133 WILLOW PLACE, VAIL, CO
LOAD CENTER - UNIT 635
VOLTAGE L—L: 208 LOCATION: UNIT 635
VOLTAGE L-6: 120 BUS RATING: 150A
TYPE: IPH/3W MAIN CB: M.L.O.
MOUNTING: RECESSED AIG RATING: I0,000AMPS FULLY RATED
NOTES: EXISTING RELOCATED FED FROM: EXTERIOR METER STACK
(SEE NOTE: 00000)
GIR. LOAD DESCRIPTION CIRCUIT BRKR BUS CIRCUIT BRKR LOAD DESCRIPTION GIR
NO POLE TRIP TRIP POLE NO
I RANGE 2 50 A 50 2 DRYER 2
3 -- -- -- B -- -- -- 4
5 STEAM 6E ERATOR 2 4000 A 20 1 WASHER 6
l -- -- -- B 2016M I JACUZZI TUB 8
q DI5HWA5ER 1 20 A 20 1 MICROWAVE 10
II DISPOSAL 1 20 B 20 1 NORTH BATH 12
15 REFRIGERATOR/KITCHEN REGP 1 20 A 15 1 Popom ROOM0000 14
00 KITCHEN RECEP 1 200 B 20 1 MASTER BATH REGEP 160
15b VINE GOOIER 1 150 B 15 1 *MASTER BATH LTSA9.R HT/1EA
Ila KITCHEN LIGHTS 1 15 A 15 1 HALL LIGHTS + REGEPS 180
Ilb DINING REGEP 1 20 A 15 1 WEST BED 18b
14a LIVING ROOM LIGHTS 1 15 B 20000 1 LMN6 ROOM REGEP 20a
Icib LOFT LIGHTS 1 15 B 15 1 NORTH BATH 20b
NOTES:
0 REPLACE STANDARD 20A/IP CIRCUIT BREAKER WITH "TWIN STYLE" CIRCUIT BREAKER WITH
AMPERAGE RATIN65 AS INDICATED AND MATCH EXISTING MANUFACTURERE AND AIG RATIN65.
** EXISTING PANEL DIRECTORY INDICATES THIS EXISTING 4OA/2P CIRCUIT BREAKER AS "SPARE"
THE ELECTRICAL CONTRACTOR TO FIELD VERIFY AND NOTIFY ARHITECT IF CIRCUIT BREAKER
IS IN USE.
000 REPLACE EXISTING 15A/IP CIRCUIT BREAKER WITH NOW 20AAP CIRCUIT BREAKER.
0000 RE—USE EXISTING COMMON AREA BATHROOM CIRCUIT FOR NEW POWDER ROOM.
*****EXISTIN6 PANEL TO BE RELOCATED AS INDICATED ON THE ARCHITECTURAL PLANS. THE
ELECTRICAL CONTRACTOR TO FIELD COORDINATE EXTENSION OF EXISTING BRANCH CIRCUITS AND
FEEDER.
.0 RE / '=
5837 ;
{ L
UNIT 640 REMODEL Date: By,
OAICHITECTURAL 1900 Wazee Street 03.Iq.13 ._IET"T Suite#350 ELECTRICAL PANEL SCHEDULE
Denver,Colorado 80202 �7� Scale: t,� t�I Job#:
303.296.3034 VOICE RE: UNIT 635 NONE 2445.00
303.296.3035 FAX
aedesign.aedesign-inc.com RIVA RIDGE NORTH CONDOMINIUM www.aedesign-inccorn Sheet#:
ENGINEERING UNIT 640 REMODEL E2 . 0
N GROUP, NC. 133 WILLOW PLACE, VAIL, CO
ELECTRICAL LOAD SUMMARY (EXI5TINCG DWELLING UNIT CALCULATION)
UNIT, 640
9D05T**WAD GA XALATION
LIGHTING b GENERAL RECEPTACLES
AREA(S.F): VA/S.F. LOAD
1,573 3.0 = WWI VA
SMALL APPLIANCES
2 1500 - 3000 VA
"1'719 VA
LAUNDRY BRANCH CIRCUIT
1 1500 - 1500 VA
1500 VA
APPLIANCES:
APPLIANCE QTY LOAD
DISHNIA5HER 1 1200 VA = 1200 VA
REFRIGERATOR 1 1800 VA = 1800 VA
DISP05AL 1 1200 VA = 1200 VA
MICROWAVE/HOOD COMBO 1 1200 VA = 1200 VA
JACUZZI TUB 2 1200 VA = 2400 VA
BATHROOM HEAT LAMP 3 500 VA = 1500 VA
BATHROOM EF 2 50 VA - 100 VA
9400 VA
GOOKING EQUIPMENT:
ELECTRIC OVEN/RANGE 1 8500 VA - 8500 VA
8500 VA
DRYERS:
ELECTRIC DRYER 1 5000 VA - 5000 VA
5000 VA
TOTAL NON-DEMANDED VA: 30619 VA
TOTAL EMT**LOAD
FIRST 8,000 VA AT 10096. 8000 VA X 100% = 5000 VA
REMAINING VA AT 40%: 22619 VA X 40% = 9048 VA
TOTAL ELECTRICAL LOAD WITH DEMAND FACTORS = 1'7045 VA
AMPS AT 205V,IPH = 82 AMPS
AVVW WAD CALCALATION
APPLIANCE5:
APPLIANCE QTY LOAD
BATHROOM HEATER 1 500 VA = 500 VA
BATHROOM EF 1 15 VA - 15 VA
515 VA
TOTAL NON-DEMANDED VA. 515 VA
TOTAL ADVW WAD
FIRST 8,000 VA AT 100%, 515 VA X 100% = 515 VA
REMAINING VA AT 40%: O VA X 40% = O VA
TOTAL ELECTRICAL LOAD WITH DEMAND FACTORS = 515 VA R IF
AMPS AT 206V,IPH = 2 AMPS
TOTAL NEW LOAD ON EXI5TIN6 PANEL '
TOTAL NON-DEMANDED LOAD: 31134 VA II _
FIRST 8000 VA AT 100%: 8000 VA X 100% = 8000 VA
f 5837
REMAINING VA AT 40%: 23134 VA X 40% = 9254 VA I
TOTAL M.WTRKo4L WAD NM DMAND PAGTORS- rr&4 VA
AMF'@i AT 200V,IPH- w A ...
{' `YAL
UNIT 640 REMODEL Date: By,
RAICECTURAL 1900 Wazee Street 03.Iq.1 3 ._IET"T Suite#350 ELEGTRIGAL LOAD GALGULATION
enver,Colorado 80202 �7� Scale: Job#:
303.296.3034 VOICE RE: UNIT 640 NONE 2445.00
303.296.3035 FA%esi Wn @aedesign-in,.— RIVA RIDGE NORTH CONDOMINIUM.aedesign-inc.com Sheet#:
ENGINEERING UNIT 640 REMODEL E3 . 0
ROUP,INC. 133 WILLOW PLACE, VAIL, CO
LOAD CENTER - UNIT 640
VOLTAGE L—L: 208 LOCATION: UNIT 640
VOLTAGE L—G: 120 BUS RATING: 150A
TYPE: IPH/3W MAIN GB: 15OA/2P M.G.B.
MOUNTING: REGESSED AIG RATING: I0,000AMPS FULLY RATED
NOTES: EXISTING FED FROM: EXTERIOR METER STACK
GIR. LOAD DESCRIPTION CIRCUIT BRKR BUS CIRCUIT BRKR LOAD DESCRIPTION GIR
NO POLE TRIP TRIP POLE NO
I RANGE 2 50 A 30 2 DRYER 2
3 -- -- -- B -- -- -- 4
5 WASHER 1 20 A 20 1 NORTH BATH 6
'1 BATHROOM HEAT LIGHT 1 20 B 20 1 49ATFROOM TWO FWEP 8
4 DISHWASHER 1 20 A 20 1 NORTH BATHROOM HEAT LIGHT 10
II DISPOSAL 1 20 B 15 1 BEDROOM 2 12
13 KITCHEN REGEPS I 20/GFI A 15 1 OBATFRiOOM FEATM 14
15 KITCHEN REGEPS 1 20 B 15 1 BEDROOM LIGHTS AND REGEPS 16
17 REFRIGERATOR 1 20 A 15 1 +BATHROOM TWO LWITAF 18
Mal LIVING ROOM LIGHTS 1 15 B 15 1 ENTRY HALL LIGHTS 20
19b BED ROOM 1 20 B
21a LIVING ROOM RECEP5 1 15 A 15/61FI I SPA TUB 22
21b BATHROOM REGEP 1 15 A
23 BEDROOM LIGHTS AND REGEPS 1 15 B 15 1 KITCHEN UG LIGHTS 24
25 A 26
NOTES:
* RE-UTILIZE EXISTING "MASTER BATHROOM" GIRGUITS THAT HAVE BEEN MADE SPARE DURING
PREVIOUS REMODEL. THE ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH BREAKERS ARE
NOT BEING UTILIZED. NOTIFY ARCHITECT IF CIRCUIT BREAKER IS IN USE.
.0 RE
r f
5
5837 ;
{ L
UNIT 640 REMODEL Date: By:
OARCHITECTURAL 1900 Wazee Stre et 03.Iq.13 ._IET"T Suite#350 ELECTRICAL PANEL SCHEDULE
Denver,Colorado 80202 �7� Scale: t,� t�I Job#:
303.296.3034 VOICE RE: UNIT 640 NONE 2445.00
303.296.3035 FAX
aedesign.aedesign-inc.com RIVA RIDGE NORTH CONDOMINIUM www.aedesign-inccorn Sheet#:
ENGINEERING UNIT 640 REMODEL E4 . 0
N GROUP, NC. 133 WILLOW PLACE, VAIL, CO