Loading...
HomeMy WebLinkAboutEast Vail Re-Submittal_East Vail Calcs 4-10-13FACP BATTERY CALCULATIONS PROJECT: East Vail Duplex Residences - Unit A Panel 1 HOURS OF SUPERVISION:24 HOURS MINUTES OF ALARM:15 MINUTES FACP:MS-25 LOCATION: Mechanical Device Device Total Total PART Supervisory Alarm Supervisory Alarm ITEM QTY NUMBER DESCRIPTION Current Current Current Current 1 1 MS-25 Addressable FACP w/ Built-in Communicator 0.135000 0.220000 0.135000 0.220000 Mains Totals:0.135000 0.220000 PERIPHERAL:Supervisory Alarm Device Device Total Total ITEM PART Supervisory Alarm Supervisory Alarm #QTY NUMBER DESCRIPTION Current Current Current Current 1 10 S355 Smoke Detector 0.000300 0.000300 0.003000 0.003000 2 5 CO1224T Carbon Monoxide Detector 0.000500 0.005000 0.002500 0.025000 3 3 H355 Heat Detector 0.000300 0.000300 0.000900 0.000900 4 2 MMF-301 Mini Monitor Module 0.000350 0.000600 0.000700 0.001200 5 1 MDF-300 Dual Monitor Module 0.000375 0.000750 0.000375 0.000750 6 2 BY OTHERS Tamper Switch 0.000000 0.025000 0.000000 0.050000 7 1 BY OTHERS Waterflow Switch 0.000000 0.025000 0.000000 0.025000 8 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000 Peripheral Totals: 0.007475 0.281850 Supervisory Alarm SUPERVISORY COMPUTATIONS PANEL:0.135000 AMPS PERIPHERAL 0.007475 AMPS SUB-TOTAL:0.142475 AMPS X HOURS OF SUPERVISORY:24.0000 HOURS SUPERVISORYSUB-TOTAL: 3.419400 AMP HOURS ALARM COMPUTATIONS PANEL:0.220000 AMPS PERIPHERAL:0.281850 AMPS SUB-TOTAL:0.501850 AMPS X MINUTES OF ALARM:0.25000 HOURS ALARM SUB-TOTAL: 0.125463 AMP HOURS BATTERY REQUIREMENT COMPUTATIONS TOTAL SUPERVISORY:3.419400 AMP HOURS TOTAL ALARM:0.125463 AMP HOURS TOTAL:3.544863 AMP HOURS DERATE 25%:4.43108 AMP HOURS MINIMUM BATTERY REQUIREMENT: 4.43108 AMP HOURS BATTERY SUPPLIED: 7.00000 AMP HOURS FACP BATTERY CALCULATIONS PROJECT: East Vail Duplex Residences - Unit B Panel 2 HOURS OF SUPERVISION:24 HOURS MINUTES OF ALARM:15 MINUTES FACP:MS-25 LOCATION: Mechanical Device Device Total Total PART Supervisory Alarm Supervisory Alarm ITEM QTY NUMBER DESCRIPTION Current Current Current Current 1 1 MS-25 Addressable FACP w/ Built-in Communicator 0.135000 0.220000 0.135000 0.220000 Mains Totals:0.135000 0.220000 PERIPHERAL:Supervisory Alarm Device Device Total Total ITEM PART Supervisory Alarm Supervisory Alarm #QTY NUMBER DESCRIPTION Current Current Current Current 1 12 S355 Smoke Detector 0.000300 0.000300 0.003600 0.003600 2 5 CO1224T Carbon Monoxide Detector 0.000500 0.005000 0.002500 0.025000 3 2 H355 Heat Detector 0.000300 0.000300 0.000600 0.000600 4 1 MMF-301 Mini Monitor Module 0.000350 0.000600 0.000350 0.000600 5 0 MDF-300 Dual Monitor Module 0.000375 0.000750 0.000000 0.000000 6 0 BY OTHERS Tamper Switch 0.000000 0.025000 0.000000 0.000000 7 0 BY OTHERS Waterflow Switch 0.000000 0.025000 0.000000 0.000000 8 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000 Peripheral Totals: 0.007050 0.205800 Supervisory Alarm SUPERVISORY COMPUTATIONS PANEL:0.135000 AMPS PERIPHERAL 0.007050 AMPS SUB-TOTAL:0.142050 AMPS X HOURS OF SUPERVISORY:24.0000 HOURS SUPERVISORYSUB-TOTAL: 3.409200 AMP HOURS ALARM COMPUTATIONS PANEL:0.220000 AMPS PERIPHERAL:0.205800 AMPS SUB-TOTAL:0.425800 AMPS X MINUTES OF ALARM:0.25000 HOURS ALARM SUB-TOTAL: 0.106450 AMP HOURS BATTERY REQUIREMENT COMPUTATIONS TOTAL SUPERVISORY:3.409200 AMP HOURS TOTAL ALARM:0.106450 AMP HOURS TOTAL:3.515650 AMP HOURS DERATE 25%:4.39456 AMP HOURS MINIMUM BATTERY REQUIREMENT: 4.39456 AMP HOURS BATTERY SUPPLIED: 7.00000 AMP HOURS East Vail Duplex Residences Circuit 1 NAC Voltage Drop Calculator for Audio / Visual devices Project Name East Vail Duplex Residences Date Circuit Number P1:1 Voltage Voltage Voltage Area Covered 5,706 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.176 63 0.07 0.176 63 0.068 0.176 63 0.034 Minimum Device Voltage 18 End of Line Voltage 20.33 End of Line Voltage 20.33 End of Line Voltage 20.37 Total Circuit Current 0.176 Wire Ohm's Percent Drop 0.33%Percent Drop 0.33%Percent Drop 0.17% Gauge Per 1000 Distance from source to 1st device 63 14 3.07 Wire Gauge for balance of circuit 14 3.07 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.176 63 20.33 0.068 0.33%the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.33 0.068 0.33% END 20.33 0.068 0.33%Device Manufacturer System Sensor Device Manufacturer System Sensor END 20.33 0.068 0.33% END 20.33 0.068 0.33%Horn Strobes Strobe Only END 20.33 0.068 0.33%Candela Candela END 20.33 0.068 0.33%P2R 15CD 0.079 SR 15 CD 0.066 END 20.33 0.068 0.33%30CD 0.107 30 CD 0.094 END 20.33 0.068 0.33%15/75 CD 0.09 15/75 CD 0.077 END 20.33 0.068 0.33%75CD 0.176 75CD 0.158 END 20.33 0.068 0.33%110CD 0.212 110CD 0.202 END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% END 20.33 0.068 0.33% Totals 0.176 63 End of Line Voltage 20.33 Totals Model # Current @Rated Voltage Standard Wire Resistance in Ohms per 1000 feet. Current @Rated Voltage TotalsTotals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction .150 = 150 ma Enter current in amps. Point to Point Method Voltage CIRCUIT IS WITHIN LIMITS Load Centering Method CIRCUIT IS WITHIN LIMITS End of Line Method CIRCUIT IS WITHIN LIMITS East Vail Duplex Residences Circuit 2 NAC Voltage Drop Calculator for Audio / Visual devices Project Name East Vail Duplex Residences Date Circuit Number P2:1 Voltage Voltage Voltage Area Covered 4,356 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.176 67 0.07 0.176 67 0.072 0.176 67 0.036 Minimum Device Voltage 18 End of Line Voltage 20.33 End of Line Voltage 20.33 End of Line Voltage 20.36 Total Circuit Current 0.176 Wire Ohm's Percent Drop 0.35%Percent Drop 0.35%Percent Drop 0.18% Gauge Per 1000 Distance from source to 1st device 67 14 3.07 Wire Gauge for balance of circuit 14 3.07 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.176 67 20.33 0.072 0.35%the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.33 0.072 0.35% END 20.33 0.072 0.35%Device Manufacturer System Sensor Device Manufacturer System Sensor END 20.33 0.072 0.35% END 20.33 0.072 0.35%Horn Strobes Strobe Only END 20.33 0.072 0.35%Candela Candela END 20.33 0.072 0.35%P2R 15CD 0.079 SR 15 CD 0.066 END 20.33 0.072 0.35%30CD 0.107 30 CD 0.094 END 20.33 0.072 0.35%15/75 CD 0.09 15/75 CD 0.077 END 20.33 0.072 0.35%75CD 0.176 75CD 0.158 END 20.33 0.072 0.35%110CD 0.212 110CD 0.202 END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% END 20.33 0.072 0.35% Totals 0.176 67 End of Line Voltage 20.33 Totals Model # Current @Rated Voltage Standard Wire Resistance in Ohms per 1000 feet. Current @Rated Voltage TotalsTotals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction .150 = 150 ma Enter current in amps. Point to Point Method Voltage CIRCUIT IS WITHIN LIMITS Load Centering Method CIRCUIT IS WITHIN LIMITS End of Line Method CIRCUIT IS WITHIN LIMITS