HomeMy WebLinkAboutM05-0125 inspection 11-20-2006 Inspection Request Reporting Page 29
4:43 pm Vail, CO - Citv Of
� Requested Inspect Date: Tuesday, November 21,2006
Inspection Area: CG
5ite Address: 20 VAIL RD VAIL
SONNENALP HOTEL ADDITION
A/P/D Information
Activity: M05-0125 Type: B-MECH Sub Type: ACOM Status: ISSUED
Const Type: Occu ancy: Use: Insp Area: CG
Owner: SONNENALP PROPERTI�S INC
Applicant: MTECH MECHANICAL TECHNOLOGIES Phone: (303)650-4000
GROUP,INC
Contractor: MTECH MECHANICAL TECHNOLOGIES Phone: (303)650-4000
GROUP,INC
Description: INSTALL ALL NEW HVAC SYSTEMS
Requested Inspection(s)
Item: 390 MECH-Final Requested Time: 08:30 AM
Requestor: MTECH MECHANICAL TECHNOLO I Phone: 401-0077
GROUPINC
Assigned To: JMOND�2AGON Entered By: DGOLDEN K
Action: Time Ex :
Comment: 6.
Comment: Units 319 4�21 &431
Comment: BALANC� REPORT RECEIVED.
UNIT FINALS 320 321 322 323 324 325 327,328 329,330 332 333.
UNDERC(JT.THE�2E dDA(�UA'fE F�ETIJRN AIR�ROM N�ASYER BEDROOM TO FCU WITH 1"DOOR
SPA DUCT WRAP APPROVED.
Comment: 334 MECH FINAL
422 BATH EXHAUST CONNECTED.
430 MECH FINAL
Comment: Unit 422-Exhaust fan is missing the cover. Unit 425-A.)Need access to disconnect at fan coil. B)Need
access to remove fan coil without removing permanent construction. Units 423 and 434 are ok.
Comment: 422I BATH EXHA�ST�OV�3RE�D 1,424,427,428,429
Comment: CORRECTIONS FROM 02-01-06 APPROVED. -
UNIT 529 RETURN AIR FOR FCU IN LIVING ROOM?
Comment: UNIT 535
Comment: 1.CAP ALL DUCTS THRU WALLS ON UNFINISHED SIDE AS NOTED ON 022106.
2.RETURN AIE IS REQD FOR 2 OFFICES.
3.PROVIDE BALANCE REPORT.
4.ALL PENETRATIONS REQD TO BE FIRE STOPPED ON BOTH SIDES OF SEP WALL.
Comment: UNIT 435
Comment: 524 NOT T-STAT
526 COMPLETE FINAL INSTALLATION AND COVERS.
529 NOT READY
525 APPR
Comment: Reinspection Required- 1)supply duct passes through fire-rated wall in office. Needs a damper or be
removed.2.)Comp�ete insulation of oufside air duct above office. First 3-4 feet from outside wall is not
insulated. 3:)Verity with Greg D.-4 blocked off supply ducts which pass through rated walls. Ducts will
need to be sealed at all ends(no openings).
Comment: Back of House
Corrections complete
Comment: Balance report recieved for back of house. See file
Comment: Labels missing from access panels located on level 3,4&5
Obtain engineer approval for fire damper location and installation at the elevator equipment room at
Talisman
�U�O�C�lC,��lS �yVl IF�C��
, � r,�►,� a�'��
��r� �- Dr�-►� � ,
Inspection Historv ����� ��.
Item: 200 MECH-Rou h "`Approved"` V °
08/31/0� Ins ector: GCD ctio � AR IAL INSPECTION
Comment: GA�AGE SNOWMELT& HYDRONI PPLY AND RETURN LINES ON Z LINE FROM 111
TO 0 LINE. 100psi TEST.
09/28/05 Inspector: GCD Action: PI PARTIAL INSPECTION
Comment: HOT AND CHILLED WATER SUPPLY AND RETURN MAINS AND RISERS 100psi TEST. UNITS
323 THRU 329 AND 423 THRU 429
11/02/05 Inspector: GCD Action: PI PARTIAL INSPECTION
Comment: GARAGE SNOWMELT AND HYDRONIC SUPPLY AND RETURN MAINS FROM 111 LINE TO
REPT131 Run Id: 5990