HomeMy WebLinkAboutB05-0026 inspection B05-0026: Entries for Item:90 - BLDG-Final 14:20 04/25/2013
Action Comments By Date Unique_
Ke
PI CORRECTIONS: FOR ALL UNITS GUARDS GCD 12/20/2005 A000086
EXCEED MAX 4"SPACING. UNIT 320 DOOR 626
SMOKE SEAL REQD, REUSED DOOR NO
SAFETY GLAZING BUG. UNIT 323 REUSED
DOOR GLAZING BROKEN NO SAFETY
GLAZING BUG. UNIT 332 DOOR DOESN'T
LATC H.
2nd FLOOR UNITS
322,324,325,326,327,328,329,330,331,332,
333,334.
3rd FLOOR UNITS 423,424,425,427,428.
RECEIVED LETTER REGARDING SAFETY
_ GLAZING IN FILE
PI Unit 320-Safety Glazing issue still remains on MROYER 12/21/2005 A000086
exterior doors.Smoke seal installed. Unit 323 642
and 332-ok. Looked at 4 other units on the 4th
floor that were not read for ins ection.
PA UNIT FINALS 323,422,422,429,430. GCD 12/22/2005 A000086
UNIT 321 694
1.32"MIN @ BATHROOM DOOR.
2.SOAP DISH OVER 48"MAX
3.SHOWER CONTROL SHOULD NOT REQ
TIGHT GRASP OR TWISTING.
PA Units finals for 319,421,431 cdavis 12/27/2005 A000086
761
PI UNIT 419 CORRECTIONS NO SAFETY GCD 12/30l2005 A000086
GLAZING AT BALCONY DOOR AND 843
SHOWER, FIRE ALARM NOT COMPLETE
UNIT 420 NO SAFETY GLAZING AT
BALCONY DOOR.
UNITS 432,433 APPR FIRE ALARM MAY
NOT BE COMPLETE.
CR CORRECTIONS FROM 12-30-05 NO GCD 01/03/2006 A000086
COMPLETED. 885
NOTED DOORS BEING MOVED TO 5th
FLOOR IN EXISTING SOUTH STAIR.
CONFIRMED ELEVATOR IS NOT
OPERATIONAL.
NO ALL UNITS REQUIRE VFES APPROVAL GCD 01/04/2006 A000086
PRIOR TO OCCUPANCY 886
PA UNITS 419,420,432,433,336 BEDROOM GCD 01/10/2006 A000086
WINDOW REQD TO MEET 20"MIN 999
EGRESS,426 APPR.
PI UNITS 335,436 GCD 01/11/2006 A000087
034
PA UNIT 435 GCD 01/18/2006 A000087
208
PI UNITS 519,524,525,529.APPROVED GCD 02/02/2006 A000087
LETTER FROM KONNEN GLASHAUS 480
REGARDING SAFETY GLAZING RECEIVED
AND IN FILE.
PI ADA REQUIREMENTS NOT MET: INSTALL GCD 02/15/2006 A000087
GRAB BARS, LAV APRON REQD TO BE 27" 683
MIN, INSULATE TRAP AND HOT SUPPLY.
PA UNIT 535 IS APPROVED FOR GCD 02/16/2006 A000087
OCCUPANCY. REINSPECTION IS REQD 719
WHEN DROP DOWN GRAB BAR IS
___ INSTALLED.
PA UNIT 535 GCD 02/17/2006 A000087
739
DN 1.EXTERIOR/ACCESS NOT COMPLETE. GCD 02/27/2006 A000087
2.FIRE ALARM FINAL REQD. 864
3.BALANCE REPORT AND MECH ITEMS
REQ FINAL.
FIRE STOPPING AND ADA INSIDE
APPROVED.
Page 1
_ _
B05-0026: Entries for Item:90 - BLDG-Final 14:20 04/25/2013
CR TALISMAN STAIRS HANDRAILS DO NOT GCD 11/16/2006 A000095
MEET CODE FOR HEIGHT.ADD HANDRAIL 809
ON ONE SIDE SHORT FLIGHT.
EXHAUST FOR ELEVATOR EQUIPMENT
REQUIRES REVIEW BY ENGINEER FOR
FIRE DAMPER LOCATION. FIRESTOP
HEAD OF WALL.
ITEMS APPROVED GATE INSTALLED
(NEED PERMENANT SIGN).
BENCHES DO NOT OBSTRUCT EXIT
DISCHARGE.
HANDRAIL IN BREEZEWAY RAMP
INSTALLED.
DOWN SPOUTS APPROVED.
TRANSFORMER AND DOGHOUSE
PAINTED.
AP All Corrections identifed are completed cdavis 11/21/2006 A000095
See TCO ent 11/21/06 945
Total Rows: 17