09-04-2009 Inspection Request Reporting Page 4
4:02 pm VaiL, CO - Citv �f
Requested Inspect Date: Tuesday,September 08, 2009
Inspection Area: SH
Site Address: 3996 LUPINE DR VAIL
3996 LUPINE DR
A1PlD Information
Activity: E08-0134 Type: B-ELEC Sub Type: ADUP Status: ISSUED
Const Type: Occupanc�y: Use: Insp Area: SH
Owner: SKARAJUNSKY,VINCENT C. & Phone: 390-1432
HEIDIHANNEMANN
Contractor: DANICI ELECTRIC Phone: 970-390-1173
Description: WIRING FOR ADDITION/REMODEL
Repuested Inspection(s)
Item: 190 ELEC-Final Requested Time: 08:30 AM
Requestor: DANICI EL IC Phone: 970-390-1173
Comments: 390-11
Assigned To: SHAHN Entered By: JMONDRAGON K
Action: Gf- Time Exp:
Comment: CHEDULE.
PROVIDE 30�INCH WIDE MINIMUM FOR ELECTRICAL METER.
Comment: THE EXTERIOR FINISHES HAVE BEEN INSTALLED SINCE THE METER SERVICE WAS APPROVED.
PROVIDE THE REQUIRED 30 INCH CLEARANCE FOR METER/DISCONNECT.
CRAWL SPACE HAS TUBING BLOCKING ACESS, BUT COULD NOT SEE A CRAWL LIGHT FIXTURE.
� 09
Inspection Historv
Item: 120 ELEC-Rough "*Approved "
01/21/09 Inspector: MDENNEY Action: AP APPROVED
Comment: ROUGH-IN COMPLETE AND TAGGED METER(PERMANENT).
Item: 140 ELEC-Misc. '"Approved*`
09/30/08 Ins ector: shahn Action: AP APPROVED
Comment: SI�E B WEST METER APPROVED.
Item: 190 ELEC-Final
08/27/09 Inspector. SHAHN Action: CR CORRECTION REQUIRED
Comment: NO ACCESS, RESCHEDULE.
PROVIDE 30 INCH WIDE MINIMUM FOR ELECTRICAL METER.
09/03/09 Inspector: shahn Action: CR CORRECTION REQUIRED
Comment: THE EXTERIOR FINISHES HAVE BEEN INSTALLED SINCE THE METER SERVICE WAS
APPROVED. PROVIDE THE REQUIRED 30 INCH CLEARANCE FOR METER/DISCONNECT.
CRAWL SPACE HAS TUBING BLOCKING ACESS, BUT COULD NOT SEE A CRAWL LIGHT
FIXTURE.
_ _ _ __
_ - _ _ _ —
REPT131 Run Id: 10249