HomeMy WebLinkAboutF13-0019 EQUIPMENT.pdf Bulletin 006 Rev. F Model RFC30 (SIN RA0611) °J J CRS Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Rel bi Residential Flat Concealed Sprinklers AO A Residential Flat Concealed Sprinkler engineered fora minimum design density of 0.05 gpm/ft2 with ;\ANT low GPM requirements. ,``i� Features 1. Very low water flow requirements. 2. 112" (13mm) Total adjustment. , A 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4 � 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- the most dependable fire protection available, an automat- tial Sprinklers are fast response residential fusible solder is sprinkler system. link automatic sprinklers. Residential sprinklers differ from The RFC30, RFC43 and RFC49 are UL Listed Residential standard sprinklers primarily in their response time and Sprinklers to be installed in the residential portions of any water distribution patterns. occupancy in accordance with NFPA 13, 13R, & 13D. Model RFC30, RFC43 and RFC49 sprinklers discharge The RFC30, RFC43 and RFC49 can reduce the need for water in a hemispherical pattern below the sprinkler de- precise cutting of drop nipples. The threaded cover plate flector. Residential distribution patterns are higher and assembly can be adjusted without tools to fit accurately generally contain a finer droplet size than standard sprin- against the ceiling. The fire protection system need not be kler patterns. shut down to adjust or remove the cover plate assembly. The combination of speed of operation and high dis- Application and Installation charge pattern required for residential sprinklers has dem- The RFC30, RFC43 and RFC49, for residential installa- onstrated, in fire testing, an ability for controlling residen- tions, use a 165°F(74°C)fusible solder link in a tuning fork tial fires, and thereby providing significant evacuation time style sprinkler frame with a drop-down deflector. This as- for occupants. sembly is recessed into the ceiling and concealed by a flat The RFC30, RFC43 and RFC49 Sprinklers provide the cover plate. The cover plate is attached to the skirt, using best form of fire protection by combining an attractive ap- 135°F (57°C) ordinary temperature classification solder. pearance and 112" (13mm) of cover adjustment for ease of When the ceiling temperature rises, the solder holding installation. The small diameter cover plate is easily and the cover plate releases the cover allowing the deflector positively attached and blends into the ceiling, concealing to drop into position and exposing the sprinkler inside to The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 ceiling temperature. The subsequent operation of the sol- OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, der link opens the waterway and causes the deflector to RFC43 AND RFC49 CONCEALED SPRINKLERS MUST drop into position to distribute the discharging water in a BE INSTALLED ONLY WITH 135°F RATED COVERS. hemispherical pattern below the sprinkler deflector. Any Note: A leak tight'/2" NPT(R1/2) sprinkler joint can be ob- adjustment of thread engagement between the cover tained with a torque of 8-18 ft-lbs (10,8- 24,4 N-m). Do not plate and cup will assure that the drop-down deflector is tighten sprinklers over maximum recommended torque. It properly located below the ceiling. The residential distri- may cause leakage or impairment of the sprinklers. bution pattern contains a finer droplet size than a standard Cover assemblies provide up to 1/2" (13mm) of adjust- sprinkler, and the pattern produces significantly higher ment. Turn the cover clockwise until the flange is in con- wall wetting. tact with the ceiling. For the push-on/thread-off option, the After a 25/8 inch diameter hole is cut in the ceiling, the cover assembly is pushed onto the cup and final adjust- sprinkler is to be installed with the Model FC Wrench. ment is made by turning the cover clockwise until the skirt When installing a sprinkler, the wrench is first positioned flange makes full contact with the ceiling. Cover removal into the sprinkler/cup assembly and around the hexagonal requires turning in the counter-clockwise direction. body of the sprinkler frame. The Wrench must bottom out In ceilings that have a plenum space above the sprinkler, against the cup in order to ensure proper, safe installation. the plenum space may have neutral or negative pressur- The sprinkler is then tightened into the pipe fitting. When ization but must not be positively pressurized. Inspect all inserting or removing the wrench from the sprinkler/cup sprinklers after installation to ensure that the gap between assembly, care should be taken to prevent damage to the cover plate and ceiling and the 4 slots in the cup are the sprinkler. DO NOT WRENCH ON ANY OTHER PART all open and free from any air flow impediment. Temperature Rating Sprinkler Cover Plate Max.Ambient Temp. 165°F/74°C 135°F/57°C 100°F/38°C Installation Data: RFC30 (SIN RA0611) Thread Sprinkler Maximum Minimum Minimum Required Size K Factor Spacing Distance to Distance between Sprinkler Discharge inch (mm) ft. (m) Wall sprinklers Flow Press. ft. (m) ft. (m) gpm (Lpm) psi(bar) 1/2"(15mm) 3.0 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 9(34.1) 9.0(0.62) 1/2"(15mm) 3.0 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 10(37.8) 11 (0.76) Note: 1 bar=100 Kpa Installation Data: RFC43 (SIN RA0612) Maximum Minimum Minimum Required Thread Sprinkler Distance to Distance between Sprinkler Discharge Size K Factor Spacing inch (mm) ft. (m) Wall sprinklers Flow Press. ft. (m) ft. (m) gpm (Lpm) psi (bar) 1/2"(15mm) 4.3 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8(0.54) 1/2"(15mm) 4.3 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63) 1/2"(15mm) 4.3 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 9.1 (0.63) 1/2"(15mm) 4.3 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(l.21) 1/2"(15mm) 4.3 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 21 (79) 23.8(l.64) Note: 1 bar= 100 Kpa Installation Data: RFC49 (RA0616) Maximum Minimum Minimum Required Thread Sprinkler Distance to Distance between Sprinkler Discharge Size K Factor Spacing Wall sprinklers inch (mm) ft. (m) p Flow Press. ft. (m) ft. (m) gpm (Lpm) psi (bar) 1/2"(15mm) 4.9 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 13(49) 7.0(0.48) '/2"(15mm) 4.9 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 7.0(0.48) '/2"(15mm) 4.9 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 7.0(0.48) '/2"(15mm) 4.9 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 17(64.3) 12.0(0.83) '/2"(15mm) 4.9 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 20(75.7) 16.7(l.14) Note: 1 bar= 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 2. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprinklers consist of a brass cover plate and copper alloy retainer should be inspected quarterly and the sprinkler system flange allowing a 112" cover plate adjustment. Any secure maintained in accordance with NFPA 25. Do not clean engagement between the cover plate and the cup will sprinklers with soap and water, ammonia or any other assure that the drop-down deflector is properly located cleaning fluids. Remove dust by using a soft brush or gen- below the ceiling. A plastic protective cap shall be tle vacuuming. Remove any sprinkler cover plate assem- provided and factory installed inside the sprinkler cup bly which has been painted(other than factory applied)or to protect the drop-down sprinkler deflector from dam- damaged in any way. A stock of spare sprinklers should age, which could occur during construction before the be maintained to allow quick replacement of damaged or cover plate is installed. Standard cover finish: [Chrome] operated sprinklers. Prior to installation, sprinklers should [White] [Specialty—specify]. Residential concealed be maintained in the original cartons and packaging until sprinklers shall be Reliable Model RFC30, SIN RA0611 used to minimize the potential for damage to sprinklers (Bulletin 006), Model RFC43, SIN RA0612(Bulletin 006) that would cause improper operation or non-operation. or Model RFC49, SIN RA0616 (Bulletin 006). Model RFC30, RFC43 and RFC49 Residential Ordering Information Cover Plate Finishes Sprinkler Specification Specify: Standard Finishes Concealed S P p 1. Sprinkler Model Sprinklers shall be cULus Listed low flow residential con- 2. Cover Plate Finish Chrome White cealed sprinklers with drop-down deflector and adjust- 3. Thread-On or able flat cover plate engineered for a minimum design Push-On Feature Special Application density of 0.05 gpm/ft2. Sprinkler frame and deflector Finishes shall be of bronze frame construction having a'h" NPT Bright Brass thread. Thermal element shall consist of an approved Black Plating black-painted beryl um-nickel solder n w Black Paint Ili ikl fibl ld link p Y Off White symmetric lever mechanism, maintaining a Teflon-coated Satin Chrome Belleville spring washer and machined brass cap water (1)Other colors and finishes avail- seal assembly containing no plastic parts. Sprinkler able.Consult factory for details. K-factor shall be nominal 3.0(44), 4.3(62.4), and 4.91 Note:Paint or any other coatings (70) having a 5/16", %" and 7/,6" orifice. Temperature rating applied over the factory finish will shall be Ordinary 65°F 74°C ; cover late temperature void all approvals and warran- t ( ) p p ties. rating to be 135°F(57C). Cover plate assembly shall I"x 112"REDUCING TEE OR ELBOW 28"[66.55mml 276'[58.42mm] DIA HOLE IN CEILING J CUP I 2"[50.8mm] MAX. +' FACE OF FITTING TO FACE OF CEILING DIMENSION -- CEILING 2°[12.70mm] MAX. COVER ADJUSTMENT js"[4.96mM [ OCR COVER PLATE 3 5" 84.21 mm] DIA. DO O■ 1 ASSEMBLY 1B SPRINKLER 006FGOIA COVER PLATE: 1,,2" [12.7mm] ADJUSTMENT 3. Reliable . . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges Identification signs • Electrical sprinkler alarm switches • Fire department connection • Water flow detectors The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Prod uctsmanuf actured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. lax Recycled (800)431-1588 Sales Offices Paper ' (800)848-6051 Sales Fax Revision lines indicate updated or new data. (914)829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.s.A 02111 P/N 9999970261 Bulletin 176 Rev.A v Model F1 Residential Sprinklers for Design Density of .10 gpm/ft2 D Model F1 Res Sprinklers engineered for the lowest flows to meet the minimum design density of.05 gpm/ff Types: 1. F1 Res 49 Pendent 2. F1 Res 49 Recessed Pendent/F1 3. F1 Res 49 Recessed Pendent/FP 4. F1 Res 49 CCP Pendent 30 0 5. F1 Res 58 Pendent F1 Res 49,58&76 F1 Res 49,58&76 6. F1 Res 58 Recessed Pendent/F1 Recessed Pendent/F1 Recessed Pendent/FP 7. F1 Res 58 Recessed Pendent/FP 8. F1 Res 58 CCP Pendent 9. F1 Res 44 & 58 HSW 10. F1 Res 44 & 58 HSW Recessed HSW/F2 11. F1 Res 44 SWC 12. F1 Res 76 Pendent 13. F1 Res 76 Recessed Pendent/F 1 14. F1 Res 76 Recessed Pendent/FP 15. F1 Res 76 CCP Pendent F1 Res 49, 58&76 F1 Res 44&58 CCP Pendent Recessed HSW/F2 Listings &Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW F1 Res 44 SWC Patents US Patent No. 6,516,893 applies to the Model F1 Res 49 & 58 Pendent Sprinklers Product Description Technical Data: Model F1 Res Pendent sprinklers (Figs. 1, 2, 3 & 4) • Thermal Sensor: Nominal 3mm glass-bulb combine excellent durability, high sensitivity glass-bulb • Sprinkler Frame : Brass Casting and low profile decorative design. • Sprinklers' Pressure Rating : 175 psi The 3mm glass-bulb pendent sprinklers permit the Factory Hydrostatically Tested to 500 psi efficient use of residential water supplies for sprinkler . Thread Size: 112" NPT(R1/2) coverage in residential fire protection design. • K-Factor.4.9(Actual)-F1 Res 49 Pendent Sprinkler The low flow F1 Res sprinklers are specially 5.8(Ach.ial)-F1 Res 58 Pendent&HSW Sprinkler engineered for fast thermal response to meet the 7.6(Actual)-F1 Res 76 Pendent Sprinkler sensitive fire protection application needs of the latest 4.4(Actual)-F1 Res 44 HSW Sprinkler residential market standards (UL 1626 Standard *). • Density: Minimum 0.10 gpm/ft2 Upon fire conditions, rising heat causes a sprinkler's heat-sensitive glass-bulb to shatter, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire. * Effective date 7/12/02 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application Model F1 Res Sprinklers are used for Residential Fire Example No. 1 Protection according to UL 1626 Standard*. Be sure Room Size= 12 ft x 20 ft(3.6 m x 6.1 m) that orifice size, temperature rating, deflector style and Coverage Area= 12 x 20 = 240 ft2(22.3 m2) sprinkler type are in accordance with the latest Flow @ 0.10 gpm/ft2 density= 240 x 0.10 = 24 gpm published standards of The National Fire Protection Using an F1 Res 49 Pendent Sprinkler, K=4.9 Association or the approving authority having Pressure= (24/4.9)2 = 24 psi (1.65 bar) jurisdiction. The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m) When using F1 Residential Sprinklers for systems coverye area using the baseline density of 0.05 design to NFPA 13D or NFPA 13R, use listed area of gpm/ft will be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 coverage and minimum flow and pressure requirements bar). Therefore,the minimum flow required is 24 gpm @ shown in Bulletin 135. 24 psi (90.8 L/min @ 1.65 bar). For systems designed to NFPA 13, use information in this bulletin.The number of design sprinklers shall be the Example No. 2 most hydraulically demanding sprinklers as required by Room Size= 8 ft x 20 ft(2.4 m x 6.1 m) NFPA 13. Flows and pressures can not be below the Coverage Area= 8 x 20 = 160 ft2(14.9 m2) baseline flows and pressurers. Flow @ 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm NFPA 13 Using an F1 Res 49 Pendent Sprinkler, K=4.9 For residential sprinkler systems designed to NFPA 13, Pressure= (16/4.9)2 = 10.7 psi (0.74 bar) a minimum density of 0.1 gpm/ft must be provided over The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m) the "design area"that includes the four(4) hydraulically coverage area using the baseline density of 0.05 most demanding sprinklers for the actual coverage gpm/ft 2 will be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 areas being protected by the 4 sprinklers. The minimum bar). Therefore,the minimum flow required is 20 gpm @ required discharge from each of the four most 16.7 psi (75.7 L/min @ 1.14 bar). hydraulically demanding sprinklers shall be the greater of the following: 1.The flow rates given in the Reliable Residential Example No.-3 Sprinkler Technical Bulletins referenced in Table A Room Size= 10 ft x 16 ft(3.0 m x 4.91 m) for NFPA 13D and 13R as a function of temperature Coverage Area= 10 x 16 = 160 ft2(14.9 m2) rating and maximum allowable coverage area (for Flow @ 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm actual coverage areas less than or between those Using an F1 Res 76 Pendent Sprinkler, K=7.6 indicated in the respective technical bulletin, it is The baseline flow for a 16 ft x 16 ft coverage area is 21 required to use the minimum required flow for the gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Therefore, the next largest coverage area); or minimum flow and pressure is 21 gpm @ 7.6 psi (79.5 2.A minimum discharge density of 0.1 gpm/ft2 L/min @ 0.52 bar). applied over the"design area"consisting of the four most hydraulically demanding sprinklers for the Example No. 4 actual coverage areas being protected by the four Room Size= 14 ft x 18 ft(4.3 m x 5.5 m) sprinklers. The maximum dimension of the actual Coverage Area= 14 x 18 = 252 ft2(23.6 m2) coverage area cannot be any greater than the 2 maximum coverage area indicated in the technical Flow @ 0.10 gpm/ft density= 252 x 0.10 = 25.2 gpm bulletins referenced in Table A. min) Using an F1 Res 76 Design Note: Using the AS - S x L method to Using a endent Sprinkler, K=7.6 determine the sprinkler protection area of coverag Pressure= (252/7.6)2 = 11 psi (0.76 bar) in accordance with NFPA 13, apply the 0.1 gpm/ftc The baseline flow and pressure of an 18 ft x 18 ft density to this area to determine the minimum coverage area is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52 required flow. Compare this flow to the minimum bar). Therefore, the minimum flow and pressure is 25.2 0.05 gpm/ft cULus Listed flow for the appropriate gpm @ 11 psi (94.6 L/min @ 0.76 bar). coverage area in the technical bulletin for the specific residential sprinkler. If the flow stated in the In general residential sprinklers require technical bulletin is less than the calculated 0.1 flows and pressures as listed for 0.05 gpm/ft density flow required, the .1 density flow densities to achieve the proper spray pattern must then be used in the equation Q=K-/P, solving so the flows and pressures at 0.05 density are for P, to establish the minimum required pressure the baseline flows and pressures. Flows and using the sprinkler K-factor. Note: In many cases pressures below the listed 0.05 density shall the listed flow of individual residential sprinkler not be used. may exceed the required minimum 0.05 gpm/ft density. Reliable has available residential sprinklers with larger K-factors (K=5.8 and K=7.6) that wi� provide lower pressure demands for 0.1 gpm/ft densities in NFPA 13 residential applications. 2. Installation Models F1 Res sprinklers are to be installed as use only the Model GFR2 Sprinkler wrench. Use of shown. Model F1, F2 and FP Escutcheons, illustrated wrenches other than those specified may damage herewith,are the only recessed escutcheons to be used these sprinklers. with Model F1 Res sprinklers. Use of any other Note:A'leak tight"sprinkler joint can be obtained with recessed escutcheon will void all approvals and the following torque: warranties. For installing Model F1 Res Pendent • 3/4" NPT(R3/4)— 14-20 ft-Ibs (19- 27.1 N-m) sprinklers use only the Model D sprinkler Wrench; for . 1/2" NPT(R1/2)—8-18 ft-Ibs (10.8—24.4 N-m) installing Models F1 Res Recessed Pendent, CCP Do not tighten sprinklers over maximum sprinklers use only the Model GFR2 sprinkler wrench; recommended torque. It may cause leakage or for installing Model F1 Res recessed HSW sprinklers impairment of the sprinklers. • Model F1 Res 49, 58 & 76 • Model F1 Res 49, 58 & 76 Pendent Recessed Pendent/ F1/F2 4._ F1 escutcheon, /" (19mm) adjustment Note: See escutcheon table for dimensions. 2 114"HOLE D1A. [5Z2­1 1 1 15116"DIA. I [49.2m ] t 1"X 112"REDUCER TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH eoss. I FACE OF FITTING TO CEILING DIMENSION: 3116-15/16(F1 ESCUTCHEON) N/ 311 1/16-16(F2 ESCUTCHEON) AausrMENT 1e [3.2mm] A" 135FG03 i�bFGO2A 2 27/32"DIA. [72.2-1 Fig. 1 Fig. 2 3. Technical Data: F1 Res 49 Pendent and Recessed Pendent Escutcheon*, F1 or F2, Data: Nominal Sprinkler Max Max Sprinkler <' „ Face of fitting to Actual p Adjustment A Thread Orifice Temp. pressure AmbierTt K Length Type Inch(mm) Inch(mm) ceiling Size Inch Rad psi Tem Inch Inch mm (mm) of oC (13210 of oC Factor (mm) %" ( ) a Min.= 19.1 F1 /(19.0) Max.=14 " 38.1 16-'16(4.7-24.0) "NPT 155 68 100 38 �R, %6"01) 175 79 175(12) 150 66 4.9 2.25(57) F2 (12.7) Min.=lyl,"(23.8) _,/ (4.7-17.4) Max.=1' " 38.1) 1s ,s *Note: Escutcheons F1 or F2 may be used with Model F1 Res 49&58 Recessed Pendent Sprinkler **Baseline flows and pressures for 0.05 density Deflector-to- ceiling *Deflector-to-ceiling Maximum 1" (25mm)to 4" (100mm) Maximum 4" (100mm)to 8" (203mm) Max.Sprinkler Sprinkler Max.Sprinkler Sprinkler Flow Pressure Flow Pressure Spacing gpm(Lpm) psi(bar) Identification Spacing gpm(Lpm) psi(bar) Identification ft m Number SIN ft m Number SIN 12 x 12 3.6x3.6) 13(49) 7.0(0.48) 12 x 12(3.6x3.6) 15(57) 9.4 (0.65) 14 x 14 4.3x4.3 13 49 7.0 0.48 14 x 14(4.3x4.3) 16(60.5) 10.6(0.73) 16 x 16 4.9x4.9 13 49 7.0 0.48 R3516 16 x 16 4.9x4.9 17 64.3 12.0 0.83 R3516 18 x 18 5.5x5.5 17 64.3 12.0"(0.83) 18 x 18 5.5x5.5 19 72 15.0 1.0 20 x 20(6.1 x6.1 20(75.7 16.7 20 x 20(6.1 x6.1) 22(83.2) 20.2(l.4) *Note: The F1 Res 49 pendent and recessed pendent residential sprinklers can be installed per NFPA 13 in beamed ceilings meeting the following criteria: 1. Maximum beam depth = 7" (178mm) 2.Beam spacing at or greater than 7.5 ft.(2.3m)on center. Technical Data: 171 Res 58 Pendent and Recessed Pendent Nominal Sprinkler Max. Max. Sprinkler Thread Orifice Temp. Pressure Ambient K Length Size Inch Rai in psi Temp. Factor Inch (mm) -F oC (bar) -F -C (mm) '/z"NPT Y2"(13) 155 68 175(12) 100 38 5.8 2.25(57) (R1/2) 175 79 150 66 **Baseline flows and pressures for 0.05 density Max.Sprinkler Flow Pressure Ceiling-to- Sprinkler Spacing gpm(Lpm) p Deflector Identification ft m psi(bar) Inch mm Number SIN 12 x 12(3.6x3.6) 16(61) 7.6(0.53) 14 x 14(43x4.3) 16(61) 7.6(0.53) 16 x 16 4.9x4.9 16 61 7.6 0.53 (25-100) R3513 18 x 18 5.5x5.5 19 72 10.8 0.75 20 x 20(6.1x6.1) 22(83.3) 14.4(l.0) **Calculate for a.10 density but in no case go below the baseline flows& pressures 4. Technical Data: F1 Res 76 Pendent and Recessed Pendent Nominal Sprinkler Max Max Sprinkler Thread Orifice Temp. Pressure Ambient K Length Size Inch ng psi T Facbr Inch (mm) -F -C (bar) -F -C (mm) %°NPT 1, 155 68 100 38 Adjustmerrt °°q°f Face of fitting to (R%) /2"(13.5) 175 79 175(12) 150 66 7.6 2.25(57) Type Inch(mm) Inch(mm) ceiling Inch mm *Baseline flows and pressures for 0.05 density F1 (19.0) Max_1 "(191)(38.1) �6 '16(4.7 24.0) 2 F2 %(12.7) Min.='Y16"(23.8) _1y (4.7-17.4) Flow Pressure Max.Sprinkler Sprinkler Max.=%"(38.1) 6 6 Spacing gp Identification ft m m(Lpm) psi(bar) Number SIN 12 x 12 3.6x3.6 21 7.6 0.53 14 x 14 43x4.3 21 7.6 0.53 16 x 16 4.9x4.9 21 7.6 0.53 R7618 *Calculate for a .10 density but in no case 18 x 18(5.5x5.5) 21 7.6(0.53) go below the baseline flows & pressures 20 x 20(6.1x6.1) 23 9.2(0.63) • Model F1 Res 49, 58 & 76 Model F1 Res 49, 58 & 76 CCP Pendent Recessed Pendent/ FP FP push-on/thread-off escutcheon 2 518"[66.7mm] DIA. 2 518°DIA.[66.7-]2 5116" DIA, HOLE IN CEILING HOLE IN CEILING [58.7mm] 2 5116"DIA CUP ---�--- [58.7mm] �_ _� CUP 1-------------}-- - i 7"x1/2" REDUCER CUP \ I"X 112°REDUCER CEILING 03 vu 1 114 [31.5mm] �V / ;f MAX. FACE OF FITTING \ / TO FACE OF CEILING DIMENSION L J CEILING B., COVER ADJUSTMENT HEIGHT ® tl� 1 112"[a8.1mm]MAX. FACE OF FITTING �_ - -- - TO FACE (LING DIMENSION 3 5176" DIA. 135FG04C [84.1 mm] A 112"[13mm]MAX. F1 R E S 49, 58 & 76 CCP P E N D. FP ADJUSTMENT +" Fig. 3 Fig. 4 NOTE: The F1 Res 76 will use a 1"x3/4" reducer. 5. Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent / FP CCP Options Data: Nominal Sprinkler CCP k, Mi3c Max "All "B" Thread Orifice Ted T Ross= Ambient K Cover Adjustment CCP Height Size Inch Ong a?�P' psi Temp. Fir Mrch Inch(mm) Inch mm) (mm) of oC of oC (bar) of IC (mm) '>(12.7 ;6(24) i"s(4.7) %(19) h'RN PT Y16"(11) 155 68 135 57 175(12) 100 38 4.9 575 *Baseline flows and pressures for 0.05 density FP Data "A": Max.Sprinkler Sprinkler FP Position "A" Flow Pressure Spacing gpm(Lpm) psi(bar) Identification Inch(mm) ft m Number SIN Max.Recessed 10 12 x 12 3.6x3.6 13 49 7.0 0.48 Min. Recessed '%6(24) 14 x 14 4.3x4.3 13 49 7.0 0.48 Note: Sprinklers shown in Fig. 3 and Fig. 4 are not 16 x 16 4.9x4.9 14 53 8.2 0.56 R3516 suitable for installation in ceilings which have 18 x 18(5.5x5.5) 18(68.1) 13.5(0.93) positive pressure in the space above. 20 x 20 6.1 x6.1 20 75.7 16.7(l.14) Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP Nominal SPrinkler CCP Max Max Sprinkler Thread Orifice TmP Pressue Amtiierrt K Length S¢e Inch Railing lull" psi TQTP Factor Inch (mm) of oC of oC (bar) of oC (mm) NPT (R 1/2) 1/2"(13) 155 68 135 57 175(12) 100 38 5.8 2.25(57) *Baseline flows and pressures for 0.05 density Max.Sprinkler Sprinkler Flow Pressure Spacing Identification ft m gpm(Lpm) psi(bar) Number SIN 12 x 12 3.6x3.6 16 61 7.6 0.53 14 x 14(4.3x4.3) 16(61) 7.6(0.53) 16 x 16 4.9x4.9 16 61 7.6 0.53 R3513 18 x 18 5.5x5.5 19 72 10.8 0.75 20 x 20(6.1 x6.1) 22(83.3) 14.4(l.0) Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP Nominal Sprinkler A bI Max Max Sprinkler' Thread Orifice Temp. YTS Pressure Ambient K Lerxft Size Inch Ong psi T� Factor Inch (mm) of oC of oC ( of oC ( ) 3/a"NPT �2 155 68 135 57 175(12) 100 38 7 6 2.25 (R3/4) (13.5) 175 79 150 66 (57) *Baseline flows and pressures for 0.05 density Max.Sprinkler Sprinkler Flow Pressure Spacing Identification ft m gpm(Lpm) psi(bar) Number SIN 12 x 12(3.6x3.6) 21 7.6(0.53) 14 x 14 4.3x4.3 21 7.6 0.53 16 x 16(4.9x4.9) 21 7.6(0.53) R7618 *Calculate for a .10 density but in no case 18 x 18 5.5x5.5 22 8.4 0.58 go below the baseline flows& pressures 20 x 20(6.1 x6.1) 25 10.8(0.74) 6. • Model F1 Res 44 & 58 HSW Model F1 Res 44 & 58 Recessed HSW/F2 v ,y F2 escutcheon, y" (13mm) adjustment Technical Data: F1 Res 44 HSW & HSW/F2 Escutcheon, F2, Data: Thread Orice Nominal � Pressure Ambient K Sprinkler Type inch(mm) Facto witting Adjustment Sme Inch t� T Factor � Inch(mm) Inch mm (mm) OF QC (bar) `F °C (mm) F2 12(13) 3, -", (4.7-17.4) 1/2"NPT y"',(10) 155 68 175(12) 100 38 4.4 2.45(62) (R/2) 175 79 150 66 *Baseline flows and pressures for 0.05 density Max.Sprinkler «A» Sprinkler Temp. Flow Sprinkler Spacing Ceiling-to- Rating gpm Pressure Identification ft(m) Deflector OF(°C) (Lpm) psi(bar) Number(SIN) Inch mm 12 x 12 3.6x3.6 155 68 175 79 12(45.4) 7.5(0.52) 14 x 14 43x4.3 155 68 175 79 14(53.0) 10.2 0.71 16 x 16 4.9x4.9 4-6 155 68 175 79 16 60.6 13.3 0.92 16 x 18 4.9x5.5 (101-152) 155 68 175 79 18 68.1 16.8(l.16) 18 x 18 5.5x5.5 155 68 175 79 19 72.0 18.7(l.29) 16 x 20(4.9x6.1) 155(68) 175(79) 23(87.1) 27.4(l.89) R3531 12 x 12 3.6x3.6 155 68 175 79 14 53.0 10.2(0.71 14 x 14 43x4.3 155 68 175 79 16 60.6 13.3 0.92 16 x 16 4.9x4.9 6-12 (152-305) 155 6$ 175 79 17 64.4 15.0 1.04 16 x 18 4.9x5.5 155 68 175 79 20 75.7 20.7(l.43) 16 x 20(4.9x6.1) 155(68) 175(79) 23(87.1) 27.4(l.89) *Calculate for a .10 density but in no case go below the baseline flows& pressures 7. • Model F1 Res 44 SWC 4"to 12" 7q [101.60mm I. 1 114"[31.75mm]Maximum 304.80-1 t Foce 01 Fitting PUSH ON COVER, THEN 1 To W./I Dimension TURN TO ADJUST UNTIL TIGHT AGAINST WALL. 1"X 112"Reducer + J Recommended Wo/l Hale 2 5116" 2 5/8" [58.74mm)�--x��--- - - ��- [66.68-1 Dia. 3 5116" [84.14mm] Dio 11 Dio. r I TURN COLLAR UNTIL `' 1 TIGHT AGAINST SPRINKLER 1 2132" WRENCH BOSS. [42.07mm) 135FG07 -� 112"[12.70mmJ Adjustment F1 RES 44 SWC Fig. 5 Technical Data: F1 Res 44 SWC Nominal Sprinkler CoverTemp. Max. MIX Sprinkler Thread Orifice TW41 Pressue q�*T K I_englh Sme Inch I psi Factor Inch (mm) OF CC (bar) cF CC (mm) 1/2"NPT ;8''(10) 155 68 135 57 175(12) 100 38 4.4 2.45(62) (R1/2) *Baseline flows and pressures for 0.05 density Max.Sprinkler 6W Flow Sprinkler Ceiling-to- Pressure Spacing gpm Identification ft(m) Inch (fpm) psi(bar) Number(SIN) 12 x 12 3.6x3.6 13 49.2 8.7 0.60 14x144.3x4.3 1453.0 10.20.71 16 x 16 4.9x4.9 (101 6 17 64.3 15.0 1.1 16 x 18 4.9x5.5 19 71.8 18.7(l.13) 16 x 20 4.9x6.1 23 87.1 27.4(l.89) R3531 12 x 12(3.6x3.6) 14(52.9) 10.2(0.71) 14 x 14 4.3x4.3 6-12 15 56.7 11.7 0.81 16 x 16 4.9x4.9 (152-305) 18 68.1 16.8(l.16) 16 x 18(4.9x5.5) 20(75.6) 20.7(l.43) *Calculate for a .10 density but in no case go below the baseline flows& pressures 8. Technical Data: F1 Res 58 HSW & HSW/F2 Escutcheon, F2, Data: Nominal Sprinkler Max. Max. Sprinkler Adjustment Face of Fitting Thread Orifice Temp. Pressure Ambient K Length Type Inch(mm)mm) to wall Size Inch Rating psi Tem • Factor Inch Inch mm (mm) OF OC (bar) OF -C (mm) F2 %(13) %6-''/,6(4.7-17.4) 1/2"NPT Y2"(13) 155 68 175(12) 100 38 5.8 2.45(62) (R/2) 175 79 150 66 *Baseline flows and pressures for 0.05 density Max.Sprinkler Sprinkler Temp. Flow Sprinkler Spacing Ceiling-to- Rating gpm Pressure Identification ft(m) Deflector OF(°C) (Lpm) psi(bar) Number(SIN) Inch mm 12 x 12 3.6x3.6 155 68 175 79 16 60.6 7.6 0.53 14 x 14 43x4.3 155 68 175 79 18 68.2 9.7 0.67 16 x 16 4.9x4.9 (101-4 156 2) 155 68 175 79 21 79.5 13.2 0.91 16 x 18 4.9x5.5 155 68 175 79 25 94.7 18.6(l.28) 16 x 20(4.9x6.1) 155(68) 175 79 29(109.8) 25(1.73) R3533 12 x 12 3.6x3.6 155 68 175 79 22 83.3 14.4(l.0) 14 x 14 43x4.3 6-12 155 68 175 79 22 83.3 14.4(l.0) 16 x 16 4.9x4.9 (152-305) 155 68 175 79 26 98.4 20.1 1.39 16 x 18(4.9x5.5) 155(68) 175(79) 31 (117.4) 28.6(1.97) *Calculate for a .10 density but in no case go below the baseline flows& pressures Finishes(l) Ordering Information Standard Finishes Specify: Sprinkler F1, F2, FP Escutcheons 1. Sprinkler Model Bronze Brass Chrome Plated Bright Chrome Plated 2. Sprinkler Type White Polyester Coated White Painted 3. Temperature Rating Special Application Finishes 4. Sprinkler Finish Sprinkler F1,F2, Escutcheons 5. Escutcheon Finish Bright Brass Bright Brass Black Plated Black Plated Black Paint Black Paint Off White Off White Satin Chrome Satin Chrome Other finishes and colors are available on special order. Consult factory for details. 9. Maintenance Model F1 Res 49, F1 Res 58 & F1 Res 76 Sprinklers Model F1 Res 49 & 58 Recessed Pendent/171, should be inspected quarterly, and the sprinkler system Model F1 Res 49 & 58 Recessed Pendent/172, maintained in accordance with NFPA 25, 13, 13D, and Model F1 Res 49 & 58 Recessed Pendent/FP 13R. Do not clean sprinkler with soap and water,Ammonia Sprinklers shall be [cULus Listed] [New York City MEA or any other cleaning fluids. Remove dust by using a soft Approved (258-93-E)] low flow residential recessed brush or gentle vacuuming. Remove any sprinkler which pendent sprinklers engine red to provide a minimum has been painted(other than factory applied)or damaged design density of 0.10 gpm/fttover the listed coverage area. in any way. A stock of spare sprinklers should be Listed flows as specified by the manufacturer's technical maintained to allow quick replacement of damaged or data sheets are to be used. Residential sprinklers shall be operated sprinklers. Prior to installation, sprinklers should installed in conformance with the manufacturer's installation remain in the original cartons and packaging until used. guidelines and the applicable installation standard. Where This will minimize the potential for damage to sprinklers that pendent residential sprinklers are installed under sloped could cause improper operation or non-operation. ceilings having a pitch of up to [4/12] [8/12], the sprinklers shall be listed for such use. Deflector-to-ceiling distance listing shall be 1" to 8" maximum. Sprinkler frame and Model F1 RES 49 Residential deflector shall be of bronze frame construction having a'/2" Sprinkler Specifications NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer and top-loaded extruded cup with 3 mm glass bulb containing no plastic Model F1 Res 49 & 58 Pendent parts, and having a temperature rating of [155°F (68 0C)] Sprinklers shall be [cULus Listed] [New York City MEA [175°F(79 0C)]. Sprinklers shall have a nominal K-factor of Approved (258-93-E)] low flow residential pendent 4.9(70). Standard finish: [Bronze] [Chrome-plated] [White sprinklers engineered to provide a minimum design Polyester] [Special finish-specify]. Recessed escutcheon density of 0.10 gpm/ft2 over the listed coverage area. assembly shall be a steel, two-piece escutcheon [with 1/2" Listed flows as specified by the manufacturer's technical adjustment(Model F2)] [with 3/4"adjustment(Model F1)] [of data sheets are to be used. Residential sprinklers shall be push-on and thread off design with 112" adjustment(Model installed in conformance with the manufacturer's FP)]. Standard finish shall be [brass][bright chrome] [white installation guidelines and the applicable installation painted]. Residential recessed pendent sprinklers shall be standard. Where pendent residential sprinklers are Reliable [Model F1 Res 49 & 58 Recessed Pendent/F11 installed under sloped ceilings having a pitch of up to[4/12] [Model F1 Res 49 &58 Recessed Pendent/F2] [Model F1 [8/12], the sprinklers shall be listed for such use. Res 49 & 58 Recessed Pendent/FP] SIN R3516 & R3513 Deflector-to-ceiling distance listing shall be 1" to 8" (Bulletin 135). maximum.Sprinkler frame and deflector shall be of bronze Model F1 Res 49&58 CCP Pendent(Concealed) frame construction having a '/2" NPT thread. Water seal Sprinklers shall be[cULus Listed] [New York City MEA assembly shall consist of a Teflon-coated Belleville spring Approved 258-93-E low flow residential concealed washer and top-loaded extruded cup with 3 mm glass bulb sprinklers l engineered] to provide a minimum design containing no plastic parts, and having a temperature density of 0.10 gpm/ft2 over the listed coverage area. rating of [155°F (68 0C)] [175°F (79 0C)]. Sprinklers shall Listed flows as specified by the manufacturer's technical have a nominal K-factor of 4.9 & 5.8. Standard finish: data sheets are to be used. Residential sprinklers shall [Bronze][Chrome-plated][White Polyester][Special finish- be installed in conformance with the manufacturer's specify]. Residential pendent sprinklers shall be Reliable installation guidelines and the applicable installation Model F1 Res 49&58,SIN R3516&R3513(Bulletin 135). standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch of up to [4/12] [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a 1/2" NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer and top-loaded extruded cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of 155°F (68 0C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a 1/2" cover plate adjustment. Cover plate temperature rating shall be 135°F(57 0C). A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color- specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 49& 58 CCP, SIN R3516 & R3513 (Bulletin 135). 10. Model F1 Res 44 & 58 Horizontal Sidewall Model F1 Res 76 Recessed Pendent/F1, Sprinkler Model F1 Res 76 Recessed Pendent/F2, Sprinklers shall be [cULus Listed] [New York City MEA Model 171 Res 76 Recessed Pendent/FP Approved (258-93-E)] low flow residential horizontal Sprinklers shall be [cULus Listed] low flow residential sidewall sprinklers engineered to provide a minimum recessed pendent sprinklers engineered to provide a design density of 0.10 gpm/ft2 over the listed coverage minimum design density of 0.10 gpm/ft over the listed area. Listed flows as specified by the manufacturer's coverage area. Listed flows as specified by the technical data sheets are to be used. Residential manufacturer's technical data sheets are to be used. sprinklers shall be installed in conformance with the Residential sprinklers shall be installed in conformance manufacturer's installation guidelines and the applicable with the manufacturer's installation guidelines and the installation standard. Where horizontal sidewall applicable installation standard. Sprinkler frame and residential sprinklers are installed under sloped ceilings deflector shall be of bronze frame construction having a having a pitch of up to [4/12] [8/12], the sprinklers shall 3/4" NPT thread. Water seal assembly shall consist of a be listed for such use.Sprinkler frame and deflector shall Teflon-coated Belleville spring washer and machined be of bronze frame construction having a'/2" NPT thread. cup with 3 mm glass bulb containing no plastic parts,and Water seal assembly shall consist of a Teflon-coated having a temperature rating of [155°F (68°C)] [175°F Belleville spring washer and top-loaded extruded cup (79 0C)]. Sprinklers shall have a nominal K-factor of 7.6. with 3 mm glass bulb containing no plastic parts, and Standard finish: [Bronze] [Chrome-plated] [White having a temperature rating of [155°F (68 1C)] [175°F Polyester] [Special finish- specify]. Recessed (79 0C)]. Sprinklers shall have a nominal K-factor of 5.8. escutcheon assembly shall be a steel, two-piece Standard finish: [Bronze] [Chrome-plated] [White escutcheon [with 112" adjustment (Model F2)] [with 3/4" Polyester][Special finish-specify].Residential horizontal adjustment(Model F1)] [of push-on and thread off design sidewall sprinklers shall be Reliable Model F1 Res 58, with 112" adjustment(Model FP)]. Standard finish shall be SIN R3513 (Bulletin 135). [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Model F1 Res 44 & 58 Recessed Res 76 Recessed Pendent/Fl] [Model F1 Res 76 Horizontal Sidewall Sprinkler Recessed Pendent/F2] [Model F1 Res 76 Recessed p Pendent/FP] SIN 87618 (Bulletin 135). Use description for the Model F1 Res 58 horizontal sidewall sprinkler with the following modifications: Replace "horizontal sidewall sprinkler" with "recessed Model F1 Res 76 CCP Pendent (Concealed) horizontal sprinkler." Add: Recessed escutcheon Sprinklers shall be [cULus Listed] low flow residential assembly shall be a steel,two-piece escutcheon with'/2" concealed sprinklers engin ered to provide a minimum adjustment (Model F2). Standard finish shall be design densityof0.10gpm/fteoverthe listed coverage area. [brass][bright chrome] [white painted] [Special finish- Listed flows as specified by the manufacturer's technical specify]. Residential recessed horizontal sidewall data sheets are to be used. Residential sprinklers shall be sprinklers shall be Reliable Model F1 Res 58/F2, SIN installed in conformance with the manufacturer's installation R3513 (Bulletin 135). guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame Model F1 Res 76 Pendent construction having a3/4"NPT thread. Water seal assembly Sprinklers shall be [cULus Listed] low flow residential shall consist of a Teflon-coated Belleville spring washer and machined cup with 3 mm glass bulb containing no plastic pendent sprinklers engineered to provide a minimum parts, and having a temperature rating of 155°F (68 0C). design density of 0.10 gpme over the listed coverage area. Cover plate assembly shall consist of a brass cover plate Listed flows as specified by the manufacturer's technical and copper alloy retainer flange. Method of attaching the data sheets are to be used. Residential sprinklers shall be cover plate to the sprinkler cup shall be a push-on and installed in conformance with the manufacturer's installation thread-off design allowing a 1/2" cover plate adjustment. guidelines and the applicable installation standard. Cover plate temperature rating shall be 135°F (57 0C). A Sprinkler frame and deflector shall be of bronze frame plastic protective cap shall be provided and factory installed construction having a3/4"NPT thread. Water seal assembly inside the sprinkler cup to protect the sprinkler from shall consist of a Teflon-coated Belleville spring washer and damage,which could occur during construction before the machined cup with 3 mm glass bulb containing no plastic cover plate is installed. Standard cover plate finish: [White] parts, and having a temperature rating of [155°F (68 0C)] [Custom Color-specify]. ]. Concealed pendent sprinklers [175°F(79 0C)]. Sprinklers shall have a nominal K-factor of shall be Reliable Model F1 Res 76 CCP,SIN R7618(Bulletin 7.6. Standard finish: [Bronze] [Chrome-plated] [White 135). Polyester] [Special finish- specify]. Residential pendent sprinklers shall be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135). 11. Reliable . . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances,whenever applicable. Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years,and are installed and serviced bythe most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by o The Reliable Automatic Sprinkler Co., Inc. F71 (800)431-1588 Sales Offices Recycled (800)848-6051 Sales Fax ®Paper (914)829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.05/08 P/N 9999970322 TABLE 2c. Dimensions and Physical Characteristics of Copper Tube:TYPE M Nominal Dimensions, inches Calculated Values(based on nominal dimensions) Nominal or Cross Weight Weight Contents of Tube Standard Outside Inside Wall Sectional of Tube Only, of Tube&Water, per linear ft Size,inches Diameter Diameter Thickness Area of Bore, pounds pounds Cu ft Gal s inches per linear ft per linear ft 3/8 .500 .450 .025 .159 .145 .214 .00110 .00826 '/2 .625 .569 .028 .254 .204 .314 .00176 .0132 8/4 .875 .811 .032 .517 .328 .551 .00359 .0269 1 1.125 1.055 .035 .874 .465 .843 .00607 .0454 11/4 1.375 1.291 .042 1.31 .682 1.25 .00910 .0681 11/2 1.625 1.527 .049 1.83 .940 1.73 .0127 .0951 2 2.125 2.009 .058 3.17 1.46 2.83 .0220 .165 21/2 2.625 2.495 .065 4.89 2.03 4.14 .0340 .254 3 3.125 2.981 .072 6.98 2.68 5.70 .0485 .363 31/2 3.625 3.459 .083 9.40 3.58 7.64 .0653 .488 4 4.125 3.935 .095 12.2 4.66 9.83 .0847 .634 5 5.125 4.907 .109 18.9 6.66 14.8 .131 .982 6 6.125 1 5.881 1 .122 1 27.2 1 8.92 1 20.7 1 .189 1.41 8 8.125 7.785 .170 47.6 16.5 37.1 .331 2.47 10 10.125 9.701 .212 73.9 25.6 57.5 .513 3.84 12 12.125 11.617 .254 106 36.7 82.5 .736 5.51 TABLE 2d. Dimensions and Physical Characteristics of Copper Tube: DMV(Drain, Waste and Vent) Nominal Dimensions,inches Calculated Values(based on nominal dimensions) Nominal or Cross Weight Weight Contents of Tube Standard Outside Inside Wall Sectional of Tube Only, of Tube&Water, per linear ft Size,inches Diameter Diameter Thickness Area of Bore, pounds pounds s inches per linear ft per linear ft Cu ft Gal 1'/4 1.375 1.295 .040 1.32 .650 1.22 .00917 .0686 1'/2 1.625 1.541 .042 1.87 .809 1.62 .0130 .0971 2 2.125 2.041 .042 3.27 1.07 2.48 .0227 .170 3 3.125 3.030 .045 7.21 1.69 4.81 .0501 .375 4 4.125 4.009 .058 11.6 2.87 7.88 .0806 .603 5 5.125 4.981 .072 19.5 4.43 12.9 .135 1.01 6 6.125 5.959 .083 27.9 6.10 18.2 .194 1.45 8 8.125 1 7.907 1 .109 49.1 1 10.6 1 31.8 1 .341 2.55 22 TABLE 7. Pressure Loss in Fittings and Valves Expressed as Equivalent Length of Tube, feet Nominal Fittings Valves or Standard Ell 90°Tee Coupling Standard Side Straight Size, in 90° 45° Branch Run Ball Gate Btfly Check 3/8 .5 1.5 1.5 1/2 1 .5 2 2 5/8 1.5 .5 2 2.5 8/4 2 .5 3 - - - - - 3 1 2.5 1 4.5 - - .5 - - 4.5 1'/4 3 1 5.5 .5 .5 .5 5.5 1'/z 1 4 1.5 7 1 .5 .5 .5 6.5 2 5.5 2 9 .5 .5 .5 .5 7.5 9 21/2 7 2.5 12 .5 .5 - 1 10 11.5 3 9 3.5 15 1 1 - 1.5 15.5 14.5 3'/8 9 3.5 14 1 1 - 2 - 12.5 4 12.5 5 21 1 1 - 2 16 18.5 5 16 6 27 1.5 1.5 - 3 11.5 23.5 6 19 7 34 2 2 - 3.5 13.5 26.5 8 29 11 50 3 3 - 5 12.5 39 NOTES: Allowances are for streamlined soldered fittings and recessed threaded fittings. For threaded fittings,double the allowances shown in the table. The equivalent lengths presented above are based upon a C factor of 150 in the Hazen-Williams friction loss formula.The lengths shown are rounded to the nearest half foot. 32 FIGURE 5. Selected Pressure Fittings ADAPTERS OO OZ ) -, EF- /- lrvvvvv- FTGxM FTGxF C x C Adapter Adapter Union OO OO OO iO C x M C x F C x C x F Adapter Adapter Tee ELBOWS 0 :2D OO 20 iO 10 � C x C C x C C x C x C 45° Elbow 901 Elbow Tee 20 OO OO zO O iO FTGx C FTGxC CxFTGxC 450 Elbow 901 Elbow Tee COUPLINGS OO iO CxC C x C C x C C x C Roll Stop Staked Stop No Stop Reducing GENERAL NOTES: (a) Fittings are designated by size in the order: 1x2x3(b) Fitting designs and drawings are for illustration only. 36 &OAf 7' kYLI '. . Schedule-10/Schedule-40 - ABF11 Submittal Data Sheet f Fully Listed and FM Approved Sprinkler Pipe NIPS Nominal I.D. Wt. Wt.(H20 Filled) CRR When you specify Schedule-10/Schedule-40-ABFII sprinkler pipe from Allied Tube& In;mm In;mm Lbs/Ft;kg/m Lbs/Ft;kg/m - Conduit,you get UL listed and FM approved products.Although these products do not 1" 1.049 1.680 2.05 1 require separate approvals,Schedule-10/Schedule-40-ABFII gives you the extra quality 25 26.6 2.5 3.05 - assurance you demand.Our Sch-10(1-1/4"-8")pipe and Sch-40(1"-2-1/2")pipe 1'A 1.380 2.270 2.93 1 have passed the same thorough lab testing as our other listed pipe products,and receive 32 35.1 4.36 4.36 - periodic mill inspections from both UL and FM agents to ensure consistent quality. 1'12 1.610 2.720 3.61 1 40 40.9 4.0 5.37 - >- Galvanized Pipe Schedule-10/Schedule-40-ABFII product can be "hot-dip" 2" 2.067 3.650 5.13 1 galvanized to meet FM requirements. 50 52.5 5.4 7.63 - 2'/2" 2.469 5.790 7.86 1 >- Superior Coating Our advanced formula mill coating offers a clean,durable 65 62.7 8.6 11.73 - surface that is also paintready for custom color applications without special preparation. The internal surface of all black Fire Sprinkler pipe up to 4.5000" in diameter shall be NIPS Nominal I.D. Wt. Wt.(H20 Filled) CRR coated with Allied Tube&Conduit Antibacterial Formula "ABF". In;mm In;mm Lbs/Ft;kg/m Lbs/Ft;kg/m - 1 Y4" 1.442 1.810 2.525 7.0955 American Made Able to meet"Buy American" requirements,and is available 32 36.6 2.7 3.75 - through distributors in the USA,Canada, Mexico and Latin America. 1Y2 1.682 2.080 3.04 5.6570 40 42.7 3.1 4.52 - >- Specifications & Approvals Schedule-10-ABFII pipe is in compliance 40 42.7 23.1 4.22 4.5827 with ASTM A135,Type E Grade A,and NFPA 13.Schedule-40-ABFII pipe is in compliance 50 54.8 3.9 6.28 - with ASTM Al 35/A795,Type E Grade A,and NFPA 13. Both pipe products have a working 21/2° 2.635 3.530 5.89 3.5196 pressure rating of 300 psi maximum and also meet the stringent requirement for the 65 66.9 5.3 8.77 - following tests:Welded Outlets, Hydrostatic Pressure,Side Wall Rupture,Vibration Test. 3" 3.260 4.330 7.94 2.5550 75 1 82.8 6.4 11.82 1 - 4" 4.260 5.610 11.78 1.6020 100 108.2 8.3 17.53 - 5" 5.295 7.77 17.33 1.4874 125 134.5 11.56 25.80 - 6" 6.357 9.290 23.03 1.0251 150 161.5 13.8 34.27 - 8" 8.249 16.490 40.15 1.8365 200 209.5 24.5 59.75 - L c �L M 4PP•¢v[¢ Project: Sprinkler Contractor: Date: Engineer: Specification Reference: System Type: Locations: Comments: (;/'� ��III�� Customer Service (800) 882-5543 Fax: (800) 659-7730 www.alliedtube-sprinkler.com • 16100 S Lathrop Ave. • 11350 Norcom Rd. •2525 N 27th Ave. •600 Dean Sievers Place TUBE & CONDUIT' Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 Morrisville,PA 19067 A PAPT OP_�atkore 02011 Atkore International,Inc.All Rights Reserved. STP-S5-4-1111 a Xif Rp eilORPI FITTINGS CAST IRON SUBMITTAL SHEET 099.1 MOP t ni visiou a f Star Pipe Produces �s x x A _ - • LISTED LISED APPROVED CAST ■ 1 ■ ELBOW IRON STRAIGHT NOMINAL ITEM MAX. DIMENSIONS WEIGHT NOMINAL ITEM MAX. DIMENSIONS WEIGHT SIZE CODE WORKING EACH SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE (INCH) # P.S.I. A B PIECE 1 CB90033 300 1.50 1.50 4.95 1 CT333 300 1.50 1.60 1.21 1114 CB90W 3U4 1.75 115 1.34 1114 CT444 300 1.75 1.76 1.87 1112 CB90055 300 1.94 1.94 1.80 1112 1 CT555 300 1.94 1.94 2.51 2 CB90066 300 2.25 1 2.26 2.94 2 CT666 300 2.25 2.25 3.96 CAST �d ,G I b I� A IRON RED. COUPLING ' ! DEGREE ELBOW NOMINAL ITEM MAX. DIMENSION WEIGHT NOMINALi ITEM MAX.. DIMENSIONS WEIGHT SIZE CODE WORKING EACH SIZE CODE WORKING EACH (INCH) # P.S.I. A PIECE (INCH) # P.S.I. A B PIECE 1X112 CRC031 300 1.70 0.62 1 CB45033 300 1.12 1.12 0.84 1X314 CRC032 300 130 0.80 1114 C1345044 300 1.29 1.29 1.40 1112 CB45055 300 1.43 1.43 1.80 p� 2 CB45066 300 1.68 1.68 2.79 - = A CAST IRON RED. 90 DEG. ELBOW CAST IRON PLUGS NOMINAL ITEM MAX. DIMENSIONS WEIGHT NOMINAL ITEM MAX. DIMENSION WEIGHT SIZE CODE WORKING EACH SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE (INCH) # P.S.I. A PIECE 1X1/2 CB90031 300 1.26 1.36 0.64 112 CPL001 304 0.94 0.10 1X314 CB90032 300 1.37 1.45 0.87 314 CPI-002 300 1.07 0.17 1114X112 CB90041 300 1.34 1.53 1 0.96 1 CPI-003 300 1.25 '0.28 1114X314 C890042 300 1.45 1.62 1.13 1114 CPI-004 300 1.36 0.44 1114X1 CB90043 300 1.58 167 1.16 1112 CPL005 300 1.45 0.62 1112X1 CB90453 300 1.65 1.80 1.51 2 CPL046 1 300 1.56 0.91 1 112X1114 CB90054 300 1.82 1.88 1.62 2X112 CB90061 300 1.49 1.88 2.00 2x314 cB90062 300 1.60 1.97 2.05 Submitted by: 2X1 CB90063 340 1.73 2.02 2.10 Date_ 2X1114 CB90064 304 1.90 2.10 2.30 2X1112 CB90065 300 2.02 2.16 2.60 - Approved by: Date: For installation on the project By; contractor 4018 WESTHOLLOW PARKWAY HOUSTON,TEXAS 77482 TOLL FREE:888-861-STAR,TEL: 281-558-3000,FAX:281-558-9404 FITTINGS CAST IRON SUBMITTAL SHEET +099.1 �f Division of Scar Pipe Products CAST 1 REDUCING SP NOMINAL ITEM MAX. DIMENSIONS WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.L A 8 C PIECE U jk 1X1X112 CT331 300 -1.26 1.26 1.36 0195 1XIX314 CT332 300 1.37 1.37 1.45 1.10 1X1/2-X1 CT313 300 1.50 1.36 1.50 1.48 1X314X1 CT323 300 1.50 1.4+5 1.50 1.18 i , 1 X 1 X 1 114 CT334 300 1.67 1.67 1.58 1.52 ° ' _ 1X1X1112 CT335 300 1.84 1.80 1.65 1.73 1 114X1X1I2 CT431 300 1.34 1.26 1.53 1.17 1114XiX314 CT432 300 1.45 1.37 1.62 1.38 1114X1X1 CT433 300 1.58 1150 1.57 1.47 1114XiX1114 CT434 300 1.75 1.67 1.75 1.80 I114XIXI112 CT435 1 300 1.88 1.80 1..82 2.05 1 114X1 114X112 CT441 300 1.34 1.34 1.53 1.37 1114XI114X314 CT442 300 1.45 1.45 1.62 1.54 LC UI +FM II► 1 114X1 114X1 CT443 300 1.58 1.58 1,67 1.65 "'1 1 114X1 114X1 112 CT445 300 1.88 1.88 1.82 2.21, 1 114X1 114X2 CT446 300 2.10 2.10 1.90 2.55 LISTED USED APPROVED 1112XV112 CT531 1 300 1.41 1.34 1.66 1.41 1112X1%314 CT532 300 1.52 1.37 1.75 1.65 1112X1X1 CT533 300 1.65 1.50 1.80 1.65 1112XIXI114 CT534 300 1.82 1.67 1.88 1 2.00 1112X1X1112 CT536 300 1.94 1.80 1.94 2.30 CAST IRON THREADED FITTINGS SPECIFICATION: 1 112X1 114X112 CT541 300 1 1.41 1.34 1.66 1.58 1112XI114X314 CTS42 300 1.52 1.45 1.75 1.72 1112X1114X1 CTS43 300 1.65 1.58 1.80 1.85 ASTM A-126 All cast iron screwed fittings meet or exceeds 1 112X1 114X2 CT546 380 2.16 2.10 2.02 2.80 materials conforming to ASTM A-126. 1 112X1 112X112 CT55i 300 1.41 1.41 1.66 1.76 1 112XI VZX314 CT552 300 1.52 1.52 1.75 1.87 1112X1112X1 CT553 300 1 1.65 1.65 1.80 1.94 AN511ASME 516.4 CLASS 125 Cast iron threaded fittings 1 112X1 112X1 114 CT554 300 1.82 1.82 1.88 2.29 dimensions conform to ANSI/ASTM 51X6.4 CLASS 125. 1 112X1 112X2 CT556 300 2.16 2.16 2.02 3.28 2XiX2 CT636 300 2.25 2.42 2.25 3.40 2X1 114X2 CT646 300 2.25 2.10 2.25 2.80 ANSUASME 81.20.1 All cast iron threaded fittings 2X1 112X112 CT651 300 1.49 1.41 1.88 2.09 are NPT standard conforming to ANSIIASME 51.20.1 2X1 112X314 CT652 300 1.60 1.52 1.97 2.40 2X1112XI CT653 300 1.73 1.65 2.02 2.54 2X1112X1 114 C7654 300 1.90 1.82 2.10 2.85 2X1112X1112 CTS55 300 1.49 1 1.41 1.88 2.24 2X1 112X2 CT656 300 2.25 2.161 2.25 3,75 ZXZX 112 CT661 300 1.49 1.49 1.88 Z60 2X2X314 CT662 300 1.60 1.60 1.97 2.71 2X2X1 CT663 300 1.73 1.73 1 2.02 1 2.97 27(2701 114 CT664 300 1.90 1.90 2.10 1 3.32 2X2X11/2 CT665 300 2.02 2.02 2.18 1 3.72 CAST IRON CROSS A A NOMINAL ITEM MAX. --r117rRMZ= WEi{IHT SIZE CODE WORKING EACH ...... s _ _(INCH) # P.S.I. A B PIECE 1 CX033 300 1.50 1.50 1.54 1 114 CX 044 300 1.75 1.75 2.40 1112 0X055 300 1.94 1.94 3.10 e -----r---, 2 CX066 300 2.25 2.25 4.00 1114X1 CX043 340 1.58 1.67 2.05 1112X1 CX053 300 1.65 1.80 2.40 2X1 CX063 1 300 1.73 1 2.02 1 2.75 4018 WESTHOLLOW PARKWAY HOUSTON,TEXAS 77082 TOLL FREE: 888-861-STAR,TEL: 281-558-3000,FAX: 281-558-9000 THREADED FITTINGS SFP[,.98 ►S'TAR FITTIN S A Division of Star Pipe Products,L P. ITEM SIZE LIST QUANTITY WEIGHT ICAPTONS CODE INCH PRICE CARTON PLT. CARTON PLT. PLT. PLUG CI CPI-001 112 1.15 1000 40,000 85 3,400 48 CPL002 314 1.28 600 24,000 102 4,080 48 CPL003 1 1.28 300 12,000 70 2,800 48 CPL004 1114 2.08 180 7,200 75 3,000 48 CPL005 1112 2.93 140 5,600 87 3,480 48 CPL006 2 3.43 80 3,200 64 2,580 48 CROSS Cl CX033 1 13.45 42 1,680 48 1,920 48 CX044 1114 18.97 22 880 50 2,000 48 CX055 1112 25.73 17 680 41 1,540 48 CX066 2 34.06 12 320 35 1,400 48 CX043 1114X1114X1X1 21.08 28 1,120 50 2,000 48 CX053 1112X1112X1X1 25.07 18 720 51 2,040 48 CX063 2X2X1X1 34.32 16 640 42 1,680 48 BULL HEAL?TEE CI CT334 1X1X1114 9.141 42 1,680 62 2,480 48 CT335 1X1X1112 13.55 34 1,360 52 2,080 48 CT435 1 114X1X1 112 14.54 27 1,296 55 2,640 48 CT445 1 114X1 114X1 112 14.54 24 960 48 1,920 48 CT446 1114X1114X2 20.20 20 800 46 1,840 48 CT546 1112X1114X2 22.28 17 680 46 1,844 48 CT556 1112X1112X2 15.91 17 680 47 1,880 48 COUPLING DI DCL033 1 3.65 140 6,720 75 3,600 48 DCL044 1114 4.68 90 4,320 72 3,456 48 DCL055 1112 6.26 56 2,688 59 2,832 48 DOL066 2 9.22 36 1,728 65 3,120 48 CAP L)I DCP003 1 2.50 200 9.600 64 3,072 48 DCP004 1 '114 3.22 130 6,240 65 3,120 48 DCP005 1112 4.42 96 4,608 65 3,120 48 DCP006 2 6.59 72 3,456 75 3,600 48 NOTE: ON ORDERS RECEIVED FOR THREADED PRODUCTS IN LESS THAN CARTON QUANTITIES, WE RESERVE THE RIGHT TO ADJUST TO THE NEXT CARTON QUANTITY ABOVE THE NUMBER OF PIECES SHOWN ON THE ORDER. Tel: (800) 999-3009, (281) 558-3000, Fax: (281) 558-9000 Pale 20 PpAble Coupling LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS VNIIP0 STYLE 75 Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50% lighter in weight than the Style 77, the Style 75 coupling is recommended for service up to 500psi/345OkPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. The Victaulic standard flexible coupling offering for grade"EHP"or"T"gaskets is the Style 177 installation-ready flexible coupling. For all available sizes,the Style 177 is the standard flexible coupling Victaulic supplies in North America for piping systems using Grade"EHP"or"T"gaskets. Contact Victaulic for further details. Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel. • Optional: Hot dipped galvanized and others. Gasket: (specify choice*) • Grade"E"EPDM EPDM (Green color code).Temperature range—30°F to+230°F/-340C to+110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+820C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T" nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. NOTE:Additional gasket styles are available.Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.. X. I Iic REV_M 06.05_1 CARBON STEEL PIPE-GROOVED COUPLINGS 06.05 Flexible Coupling STYLE 75 DIMENSIONS Deflect.Max.Work Allow.Pipe Bolt/Nut@ Approx. Size Pressure Max.End Load End Sep.f Actual NoTinal Outside Size Diameter Per Pipe Inches Inches psi Lbs. Inches Deg.� mm mm kPa N mm 1 1.315 500 680 0-0.06 0.57 2.38 4.27 1.77 1.3 25 33.4 3450 3025 0-1.6 2°-43' 48 2-3/8 x 2 61 108 45 0.6 1 1/4 1.660 500 1080 0-0.06 0.45 2.68 4.61 1.77 1.4 32 42.2 3450 4805 0-1.6 2 -10 38 2 '/a x 2 68 117 45 0.6 11/2 1.900 500 1420 0-0'06 . 1 0.40 2.91 4.82 1.77 1.5 40 48.3 3450 6320 0-1.6 1 -56 33 2-3/8 x 2 74 122 45 0.6 2 2.375 500 2215 0-0.06 1'-31' 2-3/6 x 2 0.32 3.43 5.22 1.88 1.7 50 60.3 3450 9860 0-1.6 26 87 133 48 0.8 21/2 2.875 500 3245 0-0.06 0.26 3.88 5.68 1.88 1.9 65 73.0 3450 14440 0-1.6 1 -15 Z2 2-'/e x 2 98 144 48 0.9 3.000 500 3535 0-006 0.26 4.00 5.90 1.88 1.9 76.1 mm 76.1 3450 15730 0-1.6 1 -12 22 2-3/e x 2 102 150 48 0.9 3 3.500 500 4800 0-0'06 0.22 4.50 7.00 1.88 2.9 80 88.9 3450 21360 0-1.6 1 -2 18 2-h x 2?/a 114 178 48 1.3 31/2 4.000 500 6300 0-0.06 0°-54 1 0.19 2_'/i x 2 3/a I 5.00 7.50 1.88 2.9 90 101.6 3450 28035 0-1.6 16 127 191 48 1.3 4 4.500 500 7950 0-0.13 1' 0.34 5.80 8.03 2.13 4.1 100 114.3 3450 35380 0-3.2 -36 28 2-/z x 2 3/a 147 204 54 1.9 4.250 450 6380 0-0.13 1°-41' 0.35 5.55 7.79 2.13 3.7 108.0 m m 108.0 3100 28395 0-3.2 29 2-12 x 70.0 141 198 54 1.7 41/2 5.000 450 8820 0-0.13 1°-26, 0.25 2_5/8 x 31/4 6.13 9.43 2.13 5.5 120 127.0 3100 39250 0-3.2 21 156 240 54 2.5 5 5.563 450 10935 0-0.13 1'-181 2 5/ 0.27 6.88 10.07 2.13 5.8 125 141.3 3100 48660 0-3.2 23 - a x 3 1/a 175 256 54 2.6 5.250 450 9735 0-0.13 0.28 6.55 9.37 2.13 6.0 33.0 mm 133.0 3100 43325 0-3.2 1°-21' 24 2-16 x 82.5 166 238 54 2.7 5.500 450 10665 0-0.13 1°-18' 2-5/e x 31/4 0.28 6.80 9.59 2.13 6.3 139.7 m m 139.7 3100 47460 0-3.2 24 173 244 54 2.9 6.000 450 12735 0-0.13 0.21 7.38 10.48 1.88 6.2 152.4 m m 152.4 3100 56670 0-3.2 1°-12' 18 2-5/e x 3 1/4 187 266 48 2.8 6 6.625 450 15525 0-0.13 1°-5, 0.23 2-5/a x 31/4 8.00 11.07 2.13 7.0 150 168.3 3100 69085 0-3.2 18 203 281 54 3,2 6.250 450 13800 0-0.13 2-16 x 82.5 0.24 1 7.63 10.49 2.13 6.8 159.0 mm 159.0 3100 61405 0-3.2 1°-9' 20 194 266 54 3.1 8 8.625 450 26280 0-0.13 0°-50' 0'18 2-3/4 x 41/4 10.34 13.97 2.32 12.4 200 219.1 3100 116945 0-3.2 14 263 355 59 5.6 * Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONETIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-31/2'%20-90 mm;25%for 47100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. �Y K-Z- I X www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.. ICtaUI1C® 06.05_2 REV_M Flexible Coupling STYLE 75 WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. For complete contact information,visit www.victaulic.com 06.05 1470 REV M UPDATED 2/2011 ✓ccitauIi VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. \V/ 06.05 CARBON -•• • FITTINGS 07.01 Grooved End Fittings FM ��� ids LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS Victaulic offers a broad line of fittings in sizes through 24"/600 mm in a variety of straight and reducing styles. Most standard fittings are cast of durable ductile iron to precise tolerances. Victaulic standard fittings pressure ratings conform to the ratings of Victaulic Style 77 couplings. All fittings are supplied with grooves to permit fast installation without field preparation.The grooved slip design permits flexibility for easy alignment. These fittings are not intended for use with Victaulic couplings for plain end pipe(refer to Section 14.04 for fittings available for plain end applications). Fittings are provided in various materials including ductile iron,steel or segmentally welded steel NO.20 TEE depending on styles and size.Fittings are painted orange enamel with a galvanized finish available as an option,contact Victaulic for details. Victaulic fittings are designed specifically for use in grooved piping systems. Fittings are provided grooved conforming to standard steel pipe outside diameters.When connecting wafer or lug-type butterfly valves directly to Victaulic fittings with 741 or 743 Vic-Flanges adapters,check disc clearance dimensions with I.D.dimension of fitting. W& Note:The following Victaulic fittings are VdS approved: No.10 90°Elbow, Noll 45°Elbow, No.20 Tee and No.60 Cap. Note:The following Victaulic fittings are LPCB approved: No.10 90°Elbow, Noll 45°Elbow, No.12 NO.10 ELBOW 221/2°Elbow, No.13 111/a°Elbow, No.30 45°Lateral, No.30-R Reducing Lateral,No.100 Long Radius Elbow, No.110 Long Radius Elbow, No.20 Tee,No.35 Cross, No.60 Cap,No.25 Reducing Tee, No.33 True Wye, No.50 Concentric Reducer, No.51 Eccentric Reducer and No.29M Tee with Threaded Branch. Advanced Groove System—For 14-247350—600mm piping systems,Victaulic now offers the Advanced Groove System(AGS). Refer to Section 20.05 for AGS fitting details. Stainless Steel—Grooved end fittings are available in Schedule 10 Type 316 stainless steel(Schedule 5,40 and Type 304 available as an option)in various sizes. Fitting center-to-end dimensions will vary qr depending upon type and schedule.Refer to Section 17.04 and 17.16 for details. Aluminum—Grooved end fittings are available in aluminum alloy 356 T6, in sizes from 1—8"725—200 mm. Refer to Section 21.03 or contact Victaulic for details. Fabricated Steel—A full range of fabricated segemtnally welded steel or full flow grooved end fittings are available refer to section 07.04. 4P Fabricated Steel with AGS Vic-Rings—A full range of full flow fabricated fittings with Vic-Rings are also available. AGS-ADVANCED GROOVE SYSTEM ALTERNATE STYLES Extra Heavy EndSeal®"ES"Fittings—EndSeal fittings are available in 2—12"/50—300 mm for use with"ES"grooved pipe and HP-70ES EndSeal couplings."ES"fittings are painted black for easy identification. EndSeal(and standard)fittings may be easily internally coated(by others)for severe service requirements.Always specify"ES EndSeal fittings"when ordering.See Section 07.03 for information on EndSeal fittings. Fittings Machined for Rubber or Urethane Lining(MRL)—For severe abrasive services,Victaulic fittings may be rubber or urethane lined(by others).Lining may be inside diameter/end(abrasion resistance)or wrap-around(corrosion and/or abrasion)machined.Refer to Section 25.03 or contact Victaulic for specific details. Note:Fittings are available with a variety of coatings upon request such as hot dip galvanized,epoxy, glass lined and others. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. X.AC_t UIiR: REV_Q 07.01_1 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. • Or:Segmentally welded steel as shown under nipples Nipples: (adapter,swaged&hose) • 3/—4720—100 mm: Carbon steel, Schedule 40,conforming to ASTM A-53,Type F • 5—67125—150mm:Carbon steel,Schedule 40,conforming to ASTM A-53,Type E or S, Gr. B • 8—127200—300 mm:Carbon steel,Schedule 30 or 40,conforming to ASTM A-53,Type E or S, G r. B Flanged Adapter Nipples: (Nipple—see above) • Class 125 Flange: Cast iron conforming to ANSI B-16.1 • Class 150 Flange:Carbon steel conforming to ANSI B-16.5, raised or flat face • Class 300 Flange:Carbon steel conforming to ANSI B-16.5, raised or flat face Fitting Coatings: Orange enamel • Optional: Hot dip galvanized and others.Some fittings supplied electroplated as standard—see product specifications. Flanged Adapter Nipple Coating: None(Unfinished) • Optional: Orange enamel, hot dip galvanized and others. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_2 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings FLOW DATA The chart expresses the frictional resistance of various Victaulic fittings as equivalent feet of straight pipe. Fittings not listed can be estimated from the data given,for example,a 221/2°elbow is (Frictional Resistance) approximately one-half the resistance of a 45°elbow.Values of mid-sizes can be interpolated. Size Dimension-Feet/meters Tees .0.Elbows 4 Elbows Actual No. 0. No.110 Si e Dia. Std. Long Std. Long in./mml In./mm Radius Radius Radius Radius Branch Run 1 1.315 1.7 0.8 4.2 1.7 25 33.7 0.5 0.2 1.3 0.5 2 2.375 3.5 2.5 1.8 1.1 8.5 3.5 50 60.3 1.1 0.8 0.5 0.3 2.6 1.1 76.1 mm 3.000 4.3 _ 2.1 _ 10.8 4.3 76.1 1.3 0.7 3.3 1.3 3 3.500 5.0 3.8 2.6 1.6 13.0 5.0 80 88.9 j 1.5 1.2 0.8 0.5 4.0 1.5 108.0 mm 4.250 6.4 _ 3.2 _ 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 5.0 3.4 2.1 16.0 6.8 100 114.3 2.1 1.5 1.0 0.6 4.9 2.1 133.0 mm 5.250 8.1 _ 4.1 20.0 8.1 133.0 2.5 1.2 6.2 2.5 139.7 mm 5.500 8.5 _ 4.2 21.0 8.5 139.7 2.6 1.3 6.4 2.6 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 159.0 mm 6.250 9.4 _ 4.9 _ 25.0 9.6 159.0 2.9 1.5 7.6 2.9 165.1 mm 6.500 9.6 _ 5.0 _ 25.0 10.0 165.1 2.9 1.5 7.6 3.0 6 6.625 10.0 7.5 5.0 3.0 25.0 10.0 150 168.3 3.0 2.3 1.5 0.9 7.6 3.0 8 8.625 13.0 9.8 6.5 4.0 33.0 13.0 200 219.1 4.0 3.0 2.0 1.2 10.1 4.0 10 10.750 17.0 12.0 8.3 5.0 41.0 17.0 250 273.0 5.2 3.7 2.5 1.5 12.5 5.2 12 12.750 1 20.0 14.5 10.0 6.0 50.0 20.0 300 323.9 6.1 4.4 3.0 1.8 15.2 6.1 14 14.000 24.5§ 15.8 18.5§ 11.0 70.0 23.0 350 355.6 JS 4.8 5.6 3.4 213 7.0 16 16.000 28.0§ 18.0 21.0§ 13.0 80.0 27.0 400 406.4 8.5 5.5 6.4 4.0 24.4 8.2 18 18.000 31.0§ 20.0 23.5§ 14.0 90.0 30.0 450 457.0 9.5 6.1 7.2 4.3 27.4 9.1 20 20.000 34.0§ 22.5 25.5§ 16.0 100.0 33.0 800 508.0 104 6.9 7.8 4.9 30.5 10.1 24 24.000 42.0§ 27.0 29.5§ 19.0 120.0 40.0 600 610.0 12.8 8.2 9.0 5.8 36.6 112 #Contact Victaulic for details. #For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. §Fitting flow data for 14-247350-600 mm size No.10 and No.11 Elbows is based on fittings for Style 07 and 77 couplings.For flow data on AGS fittings(No.W10 and No.W11 Elbows),refer to submittal 20.05. Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s". S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded WWW.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IlCtal- REV_Q 07.01_3 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings DIMENSIONS Elbows NO. 10 90°Elbow NO. 11 45°Elbow NO. 12 221/2°Elbow (Iri E .-cto E� NO. 13 111/a°Elbow NO. 100 90°Long Radius N0. 110 45°Long Radius C to E+I NO.12 GSNK j I I nE C_ - CtoCto to E �'O L Lj NO.10 NO.11 NO.12 NO.13 NO.100 NO.110 Size 90'� Nominal Actual A 0.- Approx. Approx. AP rox. Size Outside D. Inches Inches Lbs. nc es Lbs. Inches Lbs. Inches Lbs. kg mm mm kg mm kg mm �-,r mm kg 3/4 1.050 2.25 0.5 1.50 0.5 1.63 sw _ 1.38sw _ 2.50sw 0.4 1.81 sw 0.3 20 26.9 57 0.2 38 0.2 1 41 35 64 0.2 46 0.1 1 1.315 2.25 0.6 1.75 0.6 3.25 0.6 1.38sw 0.3 2.88 sw 0.6 2.25 sw 0.5 25 33.7 57 0.3 44 0.3 83 0.3 35 0.1 73 0.3 57 0.2 1'/4 1.660 2.75 1.0 1.75 0.9 1.75 0.8 1.38sw 0.5 3.25 sw 1.1 2.38sw 0.7 32 42.4 70 0.5 44 0.4 44 0.4 35 0.2 83 0.5 60 0.3 1 1/2 1.900 2.75 1.2 1.75 0.9 1.75 0.8 1.38sw 0.5 3.63sw 2.2 2.50sw 1.3 40 48.3 70 0.5 44 0.4 44 0.4 35 0.2 92 1.0 64 0.6 2 2.375 50 60.3 3835 0.8 2. 0.6 3.75 95 @ 0.6 13 8 1 1 8 2 0.0 11 1.1 70 0.8 21/2 2.875 3.75 3.2 2.25 2.2 4.00 @ 2.3 1.50 1.1 5.13 3.4 3.00 2.8 65 73.0 95 1.5 57 1.0 102 1.0 38 0.5 130 1.5 76 1.3 3.000 3.75 3.7 2.25 3.4 2.24 _ 1.50 _ _ _ I _ 76.1 mm 76.1 95 1.7 57 1.5 57 38 3 3.500 4.25 4.5 2.50 3.1 4.50 @ 3.1 1.50 2.1 5.88 6.0 3.38 41, 80 88.9 108 2.0 64 1.4 114 1.4 38 1.0 149 2.7 86 2.2 31/2 4.000 4.50 5.6 2.75 4.3 2.50 sw 4.0 1.75sw 2.7 90 101.6 114 2.5 70 2.0 64 1.8 44 1.2 4 4.500 5.00 71 3.00 5.6 2.88 5.6 1.75 3.6 7.50 12.3 4.00 73 100 114.3 127 3.2 76 2.5 73 2.5 44 1.6 191 5.6 102 108.0 mm 4.250 5.00 11.0 3.00 5.6 08.0 127 5.0 76 2.5 42/0 120000 5.25 133 w 4.5 3.179 w 6.0 3.50 89 w 3 0 L 48sw 4.9 5 5.563 5.50 11.7 3.25 8.3 2.88sw 7.8 2.00sw 5.0 9.25 sw 18.2 4.88s:,v 4.8 125 141.3 140 5.3 83 3.8 73 3.5 1 51 2.2 235 8.3 124 6J 133.0 mm 5.250 5.50 11.7 3.25 8.3 133.0 140 5.3 83 3.8 139.7 mm 5.500 5.50 11.7 3.25 8.3 2.87 _ 2.00 139.7 140 5.3 83 3.8 73 51 6 6.625 6.50 17.2 3.50 10.8 6.25 @ 12.2 2.00 7.0 10.75 30.4 5.50 17.4 150 168.3 165 7.8 89 4.9 159 5.5 51 3.2 273 `13.8 40 79 159.0 mm 6.250 6.50 18.6 3.50 106 159.0 165 8.4 89 4.9 165.1 mm 6.500 6.50 15.5 3.50 9.8 3.13 11.4 2.00 7.4 10 75S 29.0 5.50sw 19.0 165.1 165 7.0 89 4.4 79 5.2 51 3.4 273 13.2 40 8.6 @ Gooseneck design,end-to-end dimension fittings in this size-contact your nearest Victaulic sales office t Chinese standard sizes Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove (OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_4 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings j E -CtoE� I r CtoEj �\ NO.12 GSNK C to E � Cto E j tC Cto E j L NO.10 NO.11 NO.12 NO.13 NO.100 NO.110 � No. 6 Size 0. . . . . Approx. Approx. Nominal Size Outside D. . .. .. Inches Inches Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. mm mm mm kg mm kg mm kg mm kg mm kg mm kg 8 8.625 7.75 29.9 4.25 20.4 7.75 @ 1 20.0 2.00 10.1 14.25 66.0 7.25 36.0 200 219.1 197 13.6 108 9.3 197 9.1 51 4.6 362 30.0 184 16.3 10 10.750 9.00 63.3 4.75 37.5 4.38sw 30.0 2.13 11.8 15.00 107.0 6.25 57.0 250 1 273.0 229 28.7 121 17.0 111 13.6 54 5.3 381 48.5 159 25.9 12 12.750 10.00 74.0 5.25 66.7 4.88sw 40.0 2.25 29.3 18.00 156.0 7.50 90.0 300 323.9 254 33.6 133 30.3 124 18.1 57 13.3 457 70.8 191 40.8 14# 14.000 14.00 136.0 5.75 65.0 5.00sw 46.0 3.50sw 32.0 21.00s 164.0 8.75s 82.0 350 355.6 355.6 61.7 146 29.5 127 20.9 89 14.5 533 74.4 222 37.2 377.Ommt 14.843 14.84 149.3 6.15 82.0 377.0 376.9 67.7 156.2 37.2 16# 16.000 16.00 171.0 6.63 88.0 5,00sw 58.0 4.O0sw 42.0 24.00s 210.0 10.00S 100.0 400 406.4 406.4 77.6 168 39.9 127 26.3 1 102 19.1 610 95.3 254 45.4 426.0 mm t 16.772 16.77 198.6 6.95 101.3 426.0 426.0 90.1 176.5 45.9 18# 18.000 18:00 228:0 7.46 108.0 5.50sw 65.0 4.50sw 53.2 27.00s 273.0 11.25s 135.0 450 457.0 457.2 103.4 189 50.0 140 29.5 114 24.1 686 123.8 286 61.2 480.Omm t 18.898 18.90 291.0 7.83 J 141.7 480.0 480.0 132.0 198.8 64.3 20# 20.000 20.00 298.0 8.28 62.6 6.002w 36.0 5.00sw 659.0 30.62 s 155.6 1 .50 s 7 9 500 508.0 508.0 135.2 210 530.0mmt 20.866 20.87 355.0 8.64 179.0 _ - - - - _ - 530.0 530.0 161.0 219.4 81.2 24# 24.000 24.00 438.0 9.94 221.0 7.00sw 140.0 6.00sw 60.0 36.00s 516.0 15.00S 251.0 600 610.0 609.6 198.7 252 100.2 178 63.5 152 27.2 914 234.1 381 113.9 630.0 mm t 24.803 24.80 545.0 10.27 255.2 630.0 630.0 247.2 261.0 115.7 14-24 A68- For AGS fitting information,see publication 20.05 350-600 v @ Gooseneck design(GSNK),end-to-end dimension fittings in this size,contact your nearest Victaulic sales office. #For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. t Chinese standard sizes Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IlCtalJI1C REV_Q 07.01_5 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Reducing Base Support Elbow CtoE CtoE-1 NO. R-10G Grv. x Grv. NO. R-10F Grv. x Flange �— — H H ,4 I.- B Dia. B Dia, NO.R-10G NO.R-10F No.R-10 Approx. Size Reducing Base Support Elbow Weight Each Nominal B Size C to E H Diameter Grv.x Grv. Grv.x Flange Inches Inches Inches Inches Los. Lbs. mm mm mm mm kg kg 6 4 9.00 1.25 1.50 19.0 33.0 150 X 100 229 32 38 8.6 15.0 5 9.00 1.50 1.50 23.0 38.0 125 229 38 38 10.4 17.2 8 6 10.50 2.13 1.50 33.0 52.0 200 X 150 267 54 38 15.0 23.6 10 8 12.00 2.40 1.50 61.0 88.0 250 X 200 305 i 61 1 38 277 39.9 Note:All fittings are ductile iron unless otherwise noted with an"sw°or"s" S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_6 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Adapter Elbow r-t GE NO. 18 900 Adapter Elbow GE C NO. 19 45°Adapter Elbow C to TE C to TES NO.18 NO.19 Size 0.Adapter Elbow @ 45'Adapter Elbow @ Nominal Actual Appr x. sizes Outside Diameter C to GE77 TEr Weight Each C to GE to Inche Inches Inches Inches Lbs. Inches mr mm mm mm nm kg mm 3/4 1.050 2.25 2.25 0.5 1.50 0 03 20 26.9 57 57 0.2 38 38 0 2 1 1.315 2.25 1 2.25 0.5 25 33.7 57 1 57 0.2 1'/4 1.660 2.75 2.75 0.9 _ 32 42.4 l 70 70 0.4 1 1/2 1.900 2.75 2.75 1.1 1.75 1.75 0.9 40 48.3 70 70 0.5 44 44 0.4 2 2.375 3.25 4.25 2.5 50 60.3 83 f 108 1.1 21/2 2.875 3.75 3.75 3.0 2.25 2.25 2.3 65 710 95 95 1.4 57 57 1.0 3 3.500 4.25 6.00 5.8 2.50 4.25 5.0 80 88.9 108 152 2.6 64 108 2.3 31/2 4.000 4.50 6.25 8.0 5.25 5.25 8.8 90 101.6 114 159 3.6 133 133 4.0 6 6.625 6.50 6.50 17.6 3.50 3.50 12.7 150 168.3 165 165 8.0 89 89 5.8 @ Available with British Standard Pipe Threads-specify"BSP"clearly on order Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IC_t-QUIT REV_Q 07.01_7 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Tees, Crosses and True Wyes � CtoE Cto L N0. 20 Tee h-CtoE- � ' -�E NO. 35 Cross j NO. 33 True Wye -- + - f - -j NO. 29M Tee with C - Threaded Branch E SE ctoTE E NO.20 NO 35 NO.33 NO.29M i Size Tee Cross(sw) True Wye(sw) Tee with Threaded Branch Nominal Actual Approx. Approx. Approx. Approx. Size Outside Dia. C to E Weight Each C to E Weight Each C to LE C to SE Weight Each C to GE C to TE Weight Ea.1 Inches Inches Inches Lbs. Inches Lbs. Inches Inches Lbs. Inches Inches 's. mm mm mm kg mm kg mm mm kg mm mm 3/4 1.050 2.25 0.6 2.25 0.9 2.25 2.00 0.7 2.25 2.25 sw 0.6 20 26.9 57 0.3 57 0.4 57 51 0.3 57 57 0.3 1 1.315 2.25 1.0 2.25 13 2.25 2.25 1.1 2.25 2.25 1.0 25 33.7 57 0.5 57 0.6 57 57 0.5 57 57 0.5 1'/4 1.660 2.75 1.5 2.75 2.1 2.75 2.50 1.5 2.75 2.75 1 1.5 32 42.4 70 0.7 70 1 1.0 70 64 0.7 70 70 0.7 1'/z 1.900 2.75 2.0 2.75 2.5 2.75 2.75 1.8 2.75 2.75 2.0 40 48.3 70 0.9 70 1.1 70 70 0.8 70 70 0.9 2 2.375 3.25 3.0 3.25 3.8 3.25 2.75 2.5 3.25 4.25 3.00 50 60.3 83 1.4 83 1.7 83 70 1.1 83 108 1.4 21/2 2.875 3.75 4.3 3.75 6.1 3.75 3.00 4.3 3.75 3.75 4.3 65 73.0 95 2.0 95 2.8 95 76 2.0 95 95 2.0 76.1 mm 3.000 3.75 5.2 3.75 3.75 sw 5.2 76.1 95 2.4 95 95 2.4 3 3.500 4.25 6.8 4.25 10.5 4.25 3.25 6.1 4.25 6.00 6.8 80 88.9 108 3.0 108 4.8 108 83 2.8 108 152 3.1 31/2 4.000 4.50 sw 7.9 4.50 11.5 4.50 3.50 9.6 4.50 4.50 sw 79 90 101.6 114 3.6 114 5.2 114 1 89 4.4 114 114 73.6 108.0 mm 4.250 5.00 15.5 _ 5.00 5.00 sw 15.5 108.0 127 7.0 127 127 7.0 4 4.500 5.00 11.9 5.00 15.8 5.00 3.75 10.0 5.00 7.25 11.9 100 114.3 127 5.4 127 7.2 127 95 4.5 127 184 5.4 41/2 5.000 5.25 sw 15.0 5.25 18.5 _ _ _ 5.25 5.25 sw 15.0 120 127.0 133 6.8 133 8.4 133 133 6.8 133.Omm 5.250 5.50 17.8 _ _ _ 5.50 5.50sw 17.8 133.0 140 8.1 14_0 140 8.1 139.7mm 5.500 5.50 17.8 _ _ _ 5.50 5.50sw 17.8 139.7 140 8.1 140 140 8.1 5 5.563 5.50 17.8 5.50 20.0 5.50 4.00 15.0 5.50 5.50 sw 17.8 125 141.3 140 8.1 140 9.1 140 102 6.8 140 140 8.1 159.0 m m 6.250 6.50 27.1 6.50 6.50sw 27.1 159.0 165 12.3 165 165 12.3 165.1 mm 6.500 6.50 22.0 6.50 28.0 6.50 6.50sw 22.0 165.1 165 10.0 165 12.7 165 165 10.0 6 6.625 6.50 25.7 6.50 28.0 6.50 4.50 22.3 6.50 6.50sw 25.7 150 168.3 165 11.7 165 12.7 165 114 10.1 165 165 11.7 8 8.625 7.75 47.6 7.75 48.0 7.75 6.00 36.0 7.75 7.75 sw 476 200 219.1 197 21.6 197 21.8 197 152 16.3 197 197 21.6 10 10.750 9.00 99.0 9.00 121.5 9.00 6.50 69.9 9.00 9.00sw 73.0 250 273.0 229 44.9 229 55.1 229 155 31.7 229 229 33.1 12 12.750 10.00 133.0 10.00 110.0 10.00 7.00 80.0 10.00 10.00sw 99.0 300 323.9 254 60.3 254 49.9 254 178 36.3 254 254 44.9 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded WWW.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_8 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Tees, Crosses and True Wyes -CtoE N0. 20 Tee <C to Ej C to LE GE C to NO. 35 Cross j NO. 33 True Wye --+--- -f --- NO. 29M Tee with C - Threaded Branch tE SE ctoTE E NO.20 NO 35 NO.33 NO.29M r Size Tee Cross(sw) True Wye(sw) Tee with Threaded Branch(sw) Nominal A tual Approx. Approx. Approx. Approx. Size Outside Dia. C to E Weight Each C to E Weight Each C to LE C to SE eight Each C to GE C to TE Weight Each Inches Inches Inches Lbs. Inches Lbs. Inches Inches Lbs. Inches Inches Lbs. mm mm mm kg mm kg mm mm kg mm mm kg 14# 14.000 11.00 sw 145.0 11.00 198.0 11.00 7.50 134.2 11.00 sw 11.00 145.0 350 355.6 279 65.8 279 89.8 279 191 60.8 279 279 65.8 377.0 mm 14.000 11.50 145.0 355.6 292 65.8 16# 16.000 12.00sw 186.0 12.00 250.0 12.00 8.00 167.0 12.00 sw 12.00 186.0 400 406.4 305 84.4 305 113.4 305 203 75.7 305 305 84.4 1126.0mmt 16.000 13.00 186.0 406.4 300 84.4 18# 18.000 15.50 sw 260.0 15.50 350.0 15.50 8.50 234.0 15.50 sw 15.50 117.9 450 457.0 394 117.9 394 158.8 394 216 106.1 394 394 480.Ommt 18.000 14.57 256.0 457.0 370 116.1 20# 20.000 17.25 sw 336.0 17.25 452.0 17.25 9.00 281.0 17.25 sw 17.25 336.0 500 508.0 438 152.4 438 205.0 438 229 127.5 438 438 152.4 530.0 mm t 20.000 15.39 sw 339.0 508.0 391 153.8 24# 24.000 20.00 sw 592.0 20.00 795.0 20.00 10.00 523.0 20.00 sw 20.00 592.0 600 610.0 508 268.5 1 508 360.6 508 254 237.2 508 508 268.5 630.0 m m t 24.000 17.37 sw 473.0 610.0 441 214.5 14-24 AGS" For AGS fitting information,see publication 20.05 350-600 v #For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. t Chinese standard sizes Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IlCtalJI1C REV_Q 07.01_9 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Reducing Tee CtoEl -CtoE- F CtoE j CtoEi NO. 25 Grooved Branch NO. 29T Threaded Branch T T C T c C c C to to to to E E E NO.25 NO.29T NO.25-SW NO.29T-SW No.25 No.29T Approx. No'25 No.29T Approx. Size Std. W/Thd.Branch Weight Each_ Size Std. w/Thd.Branch Weight Each Nominal finall LW Inches Inches Inches Lbs. rk,mlci,�es In Inches s Lk Ig mm mm mm kg mm mm m 1 1 /a 2.25 sw 2.24 sw 0 4 4 Ya 5.00sw 5.00sw 9.6 25 X X 20 57 57 0.5 100 X 100 X 32 127 - 127 4.4 1'A 1'/a 1 2.75 sw 2.75 sw 1.3 11/2 5.00 5.00 10.2 32 X 32 X 25 70 70 40 27 127 4.6 1 1/2 Pk 3/a 2.75 sw 275 sw w 1 1.5 5 2 5.00 5.00 11.2 40 X 40 X 20 70 70 0.7 50 127 127 5.1 1 2.75 sw 2.75 sw 1.5 2'/z 5.00 5.00 11.4 25 70 70 0.7 65 127 127 5.2 1 Y4 2.75 sw 2.75 sw 1.7 3 5.00 5.00 11.6 32 70 70 0.8 80 127 127 5.3 2 2 3/a 3.25 3.25 2.5 5 5 1 5.50sw 5.50sw 14.0 50 X 50 X 20 83 83 1.1 125 X 125 X 25 140 140 6.4 1 3.25 3.25 2.7 1 1/2 5.50sw 5.50sw 14.3 25 83 83 12 40 140 140 6.5 1 Ya 3.25sw 3.25 sw 1.8 2 5.50sw 5.50sw 14.5 32 83 83 0.8 50 140 140 6.6 1 1/2 3.25 3.25 sw 3.0 2'/z 5.50 5.50sw 15.2 40 83 83 1.4 65 140 140 6.9 21112 2Yz 3/4 3.75 sw 3.75 sw 3.9 3 5.50 5.50sw 16.6 65 X 65 X 20 95 95 1.8 80 140 140 7.5 1 3.75 3.75 sw 3.8 4 5.50 5.50sw 16.7 25 95 95 1.7 100 140 140 7.6 1 Y4 3.75 sw 3.75sw 4.2 6 6 1 6.50sw 6.50sw 23.0 32 95 95 1.7 150 X 150 X 25 165 165 10.4 1'h 3.75 3.75 3.9 1'/z 6.50sw 6.50sw 24.0 40 95 95 1.8 40 165 165 10.9 2 3.75 3.75 sw 4.5 2 6.50 6.50 21.6 50 95 95 2.0 50 165 165 9.8 3 3 3/4 4.25 sw 4.25 sw 5.7 2'/z 6.50 6.50 21.4 80 X 80 X 20 108 108 2.6 65 165 165 11.7 1 4.25 4.25 6.1 14-24 AG$"For AGS fitting information,see publication 20.05 25 108 108 2.8 350-600 v 1 Y4 4.25 sw 4.25sw 8.0 +Contact Victaulic for details. 32 108 108 3.6 1 1/2 4.25 425sw 6.5 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s" 40 108 108 2.9 S=Carbon Steel Direct Roll Groove(OGS) 2 4.25 4.25 sw 6.2 SW=Carbon Steel Segmentally Welded 50 108 108 2.8 IMPORTANT NOTE: 2'/z 4.25 4.25 sw 6.4 65 108 108 2.9 No.29T Threaded Outlet Reducing Tees are supplied NPT and are available 4 4 3/4 5.00sw 5.00 sw 8.0 with British Standard threads.For British Standard specify 'BSP"clearly 100 X 100 X 20 127 127 3.6 on order. 1 5.00 5.00 7.8 25 127 127 3.5 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt.'alUI1C® 07.01_10 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Reducing Tee CtoE CtoE F CtoE 4-CtoE I NO. 25 Grooved Branch ---- - � NO. 29T Threaded Branch C C C C to to to to E E i � NO.25 NO.29T NO.25-SW NO.29T-SW No.25 No.29T Approx. No.25 No.29T Approx. size Std. w/Thd.Branch Weight Each Size SU w/Thd.Branchjw�eight Each Nominal No Inches Inches Inches Inches Inches L's. mm mm M mm mm mm kg 6 6 3 6.50 6.50 26.5 12 12 1 10.00sw 10.00sw 77.0 150 X 150 X 80 165 165 12.0 300 X 300 X 25 254 254 34.9 4 6.50 6.50 25.0 2 10.00sw 10.00sw 80.0 100 165 j 165 113 50 254 254 36.3 5 6.50 6.50 23.2 2'/2 10.00sw 10.00sw 78.0 125 165 165 10.5 65 254 254 35.4 61/2 6'/2 3 6.50 6.50sw 24.0 3 10.00sw 10.00sw 82.0 165.1 X 165.1 X 80 165 165 10.9 80 254 254 37.2 4 6.50 6.50sw 25.0 4 10.00sw 10.00sw 80.0 100 165 165 11.3 loo 254 254 36.3 8 8 1 1/2 7.75 sw 7.75 sw 33.0 5 10.00 sw 10.00sw 75.0 200 X 200 X 40 197 197 15.0 125 254 254 34.0 2 775 sw 7.75 sw 33.5 6 10.00sw 10.00sw 75.0 50 197 197 15.2 150 254 254 34.0 21/2 7.75 sw 7.75 sw 39.0 8 10.00sw 10.00sw 80.0 65 197 197 17.7_ 200 254 254 36.3 3 7.75 sw 7.75 sw 33.6 10 10.00 sw 10.00 sw 84.0 80 197 197 15.2 250 254 254 38.1 4 7.75 7.75 41.8 #14 14 4 11.00sw 11.00Sw 102.0 100 197 197 19.0 350 X 350 X 100 279 279 46.3 5 7.75 sw 7.75 sw 34.0 6 11.00sw 11.00Sw 108.2 125 197 197 15.4 150 279 279 49.1 6 7.75 7.75 42.3 8 11.00 11.00 112.0 150 197 197 19.2 200 279 279 50.8 165.1 775sw 7.75 sw 48.0 10 11.00 11.00 120.0 197 197 21.8 300 279 279 54.4 10 10 1'/2 9.00 9.00 62.0 12 11.00 11.00 129.1 250 X 250 X 40 229 229 28.1_ 300 279 279 58.6 2 9.00 SW 9.00sw 62.0 #16 16 4 130.0 50 229 229 28.1 400 X 400 X 100 + 59.0 2'/2 9.00 SW 9.00sw 62.4 14-24 AGS"For AGS fitting information,see publication 20.05 65 229 229 283 350-600 v 3 9.00 SW 9.00sw 60.0 +Contact Victaulic for details. 80 229 229 272 4 9.00sw 9.o0 sw 61.0 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s" 10o 229 229 27.7 S=Carbon Steel Direct Roll Groove(OGS) 5 9.00sw 9.00sw 52.0 SW=Carbon Steel Segmentally Welded 125 229 229 23.6 6 9.00Sw 9.00 SW 59.0 IMPORTANT NOTE: 150 229 229 26.8 No.29TThreaded Outlet Reducing Tees are supplied NPT and are available 8 9.00 SW 9.00sw 64.7 with British Standard threads.For British Standard specify"BSP"clearly 200 229 229 29.3 on order. #For roll grooved systems,Victaulic offers the Advanced Groove System(AGS). For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. WWW.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtal- REV_Q 07.01_11 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Reducing Tee rCtoEl 4-CtoE� NO. 25 Grooved Branch NO. 29T Threaded Branch � T � T C LL c to to E E NO.25 NO.29T No 25 No.29T Approx. No.25 No.29T Approx. Size Std. W/Thd.Branch Weight Each Size Std. w/Thcl.Branch Weight Each LNominal inal Inches Inches Inches Lbs. ff"I nc h e s Inches Inches nLbs #16 16 6 12.00 sw 12.00 sw 133.5 #20 20 16 17.25 _ 288.6 400 X 400 X 150 305 305 60.6 500 X 500 400 438 130.9 8 12.00 12.00 145.0 18 17.25 297.0 200 305 305 65.8 450 438 134.7 10 12.00 12.00 149.5 #24 24 8 20.00 20.00 340.0 250 305 305 67.8 600 X 600 X 200 508 508 154.2 12 12.00 12.00 154.0 10 20.00 20.00 343.9 300 305 305 69.9 250 508 508 156.0 14 12.00sw 167.0 12 20.00 20.00 352.8 350 305 75.8 300 508 508 160.0 #18 18 4 15.50sw 15.50sw 194.0 14§ 20.00 360.0 450 X 450 X 100 394 394 88.0 350 508 163.3 6 15.50sw 15.50sw 200.0 16 20.00 378.0 150 394 394 90.7 400 508 171.5 8 15.50sw 15.50sw 202.0 18§ 20.00 380.0 200 394 394 91.6 450 508 172.4 10 15.50 15.50 212.0 20 20.00 373.0 250 394 394 96.2 500 508 169.2 12 15.50 15.50 222.6 14-24 A6S°For AGS fitting information,see publication 20.05 300 394 394 101.0 350-600 v 14 15.50 _ 230.1 +Contact Victaulic for details. 350 394 104.4 16 15.50 247.6 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s" 400 394 - 112.3 S=Carbon Steel Direct Roll Groove(OGS) #20 20 6 1725 17.25 240.0 SW=Carbon Steel Segmentally Welded 500 X 500 X 150 438 438 108.9 8 17.25 17.25 244.0 IMPORTANT NOTE: 200 438 438 110.7 No.29TThreaded Outlet Reducing Tees are supplied NPT and are available 10 17.25 1725 256.0 with British Standard threads.For British Standard specify 'BSP"clearly 250 438 438 116.1 on order. 12 17.25 1725 264.0 #For roll grooved systems,Victaulic offers the Advanced Groove System(AGS). 300 438 438 1198 For pricing and availability of cut groove fittings in this size,contact your 14 17.25 275.0 nearest Victaulic sales office. 350 438 1 124.7 1 §Cast fitting available.Contact Victaulic for details. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IICt.'c�UI1C® 07.01_12 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Bullhead Tee Cto Bull Plug FOR NO. 21 NO. 61 �-EtoE C to EOM NO.21 NO.61 No.21 Size Bullhead Tee No.61 Size Bull Plug(S) Nominal Approx- Siz C to EOR C to EOB Weight Ewhj Nominal Actual Approx. Inches Inches Inches Lbs. Size Outside Diameter E to E Weight Each mm mm mm kg Inches Inches Inches Lbs. 5 5 8 7.75 5.50 28.7 mm mm mm kg X x 2 2.375 4.00 2.5 125 125 200 197 140 13.0 50 60.3 102 1.1 6 x 6 x 8 7.75 6.50 3775 150 150 200 197 165 17 2 Yz 2.875 5.00 3.0 0 65 73.0 .0 1.4 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s 3 3.500 6.00 4.5 S=Carbon Steel Direct Roll Groove(OGS) 80 88.9 152 2.0 SW=Carbon Steel Segmentally Welded 4 4 1 7.5 g y 100 1114.3 4.3 178 78 3.4 5 5.563 8.00 12.0 125 141.3 203 5.4 6 6.625 10.00 170 SO 168.3 254 7.7 IMPORTANT NOTES: Steel dish caps available through 247600mm,contact Victaulic. No.61 Bull Plugs should be used in vacuum service with Style 72 or 750 couplings Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s" S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IC_t-QUIT REV_Q 07.01_13 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings 45° Lateral NO. 30 Cto LE SE NO.30 r No.30 Size 45*Lateral(SW) Size 45*Lateral(SW) to Nominal Actual Approx. Nominal Actua I -7S Appr X. Size Outside Diameter C to LE C to SE Weight Each Size Outside Diameter C to LE to Weight Each Inches Inches Inches Inches Los. Inches Inches Inches Inche Lbs. mm mm mm mm mm kg mm mm mm m7 kg 3/4 1.050 4.50 2.00 1.0 6 6.625 14.00 4.50 43.6 20 26.9 114 51 0.5 150 168.3 356 114 19.8 _ 1 1.315 5.00 2.25 1.7 8 8.625 18.00 6.00 72.0 25 33.7 127 57 0.8 200 219.1 457 152 32.7 1 Y4 1.660 5.75 2.50 2.5(d) 10 10.750 20.50 6.50 105.0 32 42.4 146 64 1.1 250 273.0 521 165 476 11/2 1.900 6.25 2.75 3.5 12 12.750 23.00 7.00 165.0 40 48.3 159 70 6 300 323.9 584 178 74.8 2 2.375 7.00 2.75 4.6(d) 14# 14.000 26.50 7.50 276.0 50 60.3 178 70 2.1 350 355.6 673 191 125.2_ 2'/2 2.875 7.75 3.00 9.0 16# 16.000 29.00 8.00 344.2 65 73.0 197 76 94.1 400 406.4 737 203 156.1 76.1 mm 3.000 8.50 3.25 11.0 18# 18.000 32.00 8.50 429.0 76.1 216 83 5.0 450 457.0 813 216 194.6 3 3.500 8.50 3.25 11.7(d) 20# 20.000 35.00 9.00 500.0 80 88.9 216 83 5.4 500 508.0 889 229 226.8 3'/2 4.000 10.00 3.50 17.8 24# 24.000 40.00 10.00 715.0 90 101.6 254 89 8.1 600 610.0 1016 254 324.3 4 4.500 10.50 3.75 22.2(d) 14-24 AGS" For AGS fitting information,see publication 20.05 100 114.3 267 95 10.1 350-600 v 5 5.563 12.50 4.00 21.8 #For roll grooved systems,Victaulic offers the Advanced Groove System 125 141.3 318 102 9.9 (AGS).For pricing and availability of cut groove fittings in this size,contact 6.500 14.00 4.50 43.6 165.1 mm 165.1 .356 114 19.8 your nearest Victaulic sales office. Note.All fittings are segmentally welded steel unless otherwise noted with a(d)for ductile iron. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_14 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings 45° Reducing Lateral NO. 30-R C to LE I/ SE o�F, -� o r NO.30-R c0 Size 45*Reducing Lateral(SW) Size 45'Reducing Lateral(SW) Size 77SE Nominal Approx. Nominal Approx. Siz C to LIE C to SE Weight Each C to LIE Weight Each Inches Inches Inches Lbs. Inches Inches Inches Lbs. mm mm mm kg mm mm mm kg 3 3 2 8.50 3.25 9.8 #14 14 4 26.50 7.50 172.0 80 X 80 X 50 216 83 4.4 350 X 350 x 100 673 191 78.0 21/2 8.50 3.25 9.8 6 26.50 7.50 187.0 65 216 83 4.4 150 673 191 84.8 4 4 2 10.50 3.75 10.0 8 26.50 7.50 205.8 100 X 100 X 50 267 95 4.5 200 673 191 93.4 21/2 10.50 3.75 10.0 10 26.50 7.50 235.0 65 267 95 4.5 250 673 191 106.6 3 10.50 3.75 18.3 12 26.50 7.50 250.0 80 267 95 8.3 300 673 191 113.4 5 5 2 12.50 4.00 24.0 #16 16 6 29.00 8.00 215.0 125 X 125 X 50 318 102 10.9 400 X 400 X 150 737 203 97.5 3 12.50 4.00 27.0 8 29.00 8.00 252.5 80 318 102 212.2 200 737 203 114.5 4 12.50 4.00 26.5 10 29.00 8.00 265.0 100 318 102 12.0 250 737 203 120.2 6 6 3 14.00 4.50 370 12 29.00 8.00 295.0 150 X 150 X 80 356 114 16.8 300 737 203 133.8 4 14.00 4.50 36.0 14 29.00 8.00 305.0 100 356 114 16.3 350 737 203 138.3 5 14.00 4.50 44.7 #18 18 6 32.00 8.50 274.0 125 356 114 20.3 450 X 450 X 150 813 216 124.3 8 8 4 18.00 6.00 62.0 8 32.00 8.50 275.0 200 X 200 X 100 457 152 28.1 200 813 216 124.7 5 18.00 6.00 75.5 12 32.00 8.50 347.0 125 457 152 34.2 300 813 216 157.4 6 18.00 6.00 82.0 14 32.00 8.50 350.0 150 457 152 37.2 350 813 216 158.8 10 10 4 20.50 6.50 104.8 16 32.00 8.50 362.0 250 X 250 X 100 521 165 147.5 400 813 216 164.2 5 20.50 6.50 99.0 #20 20 12 35.00 9.00 415.0 125 521 165 44.9 500 X 500 X 300 889 229 188.2 6 20.50 6.50 105.8 14 35.00 9.00 420.0 150 521 165 48.0 350 889 229 190.5 8 20.50 6.50 118.0 16 35.00 9.00 425.0 200 521 165 53.5 400 889 229 192.8 12 12 5 23.00 7.00 122.0 #24 24 16 40.00 10.00 425.0 300 X 300 X 125 584 178 55.3_ 600 X 600 X 400 1016 2_54 192.8 6 23.00 7.00 137.0 20 40.00 10.00 570.0 150 584 178 62.1 600 1016 254 258.6 8 23.00 7.00 147.0 14-24 AGSTor AGS fitting information,see publication 20.05 200 584 178 66.7 350-600 v 5 23.00 178 75.8 # For roll grooved systems,Victaulic offers the Advanced Groove System 250 584 178 75.8 9 Y Y (AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. Note:All fittings are segmentally welded steel unless otherwise noted a(d) for ductile iron. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt.'diL- REV_Q 07.01_15 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Tee Wye NO. 32 i H �' E2 -- ------- -� G E, NO.32 Size Tee Wye(SW) Size Tee Wye(SW) Inches Inches Inches Inche s Inches Lbs. Inches inches I nches Inches I riche S Lbs. mm mm RIM mm mm kg mm mm mm mm mm kg 2 2 2 2.75 7.00 9.00 4.63 6.4 5 5 5 4.00 12.50 16.13 10.00 48.0 50 X 50 X 50 70 178 229 118 2.9 125 X 125 X 125 102 318 410 254 21.8 21/2 21/2 21/2 3.00 775 10.50 5.75 1 11.5 6 6 6 4.50 14.00 18.25 11.50 60.5 65 X 65 X 65 76 197 267 146 5.2 150 X 150 X 150 114 356 464 292 27.4 3 3 3 3.25 8.50 11.50 6.50 14.3 8 8 8 6.00 18.00 23.25 15.25 127.1 80 X 80 X 80 83 216 292 165 6.5 200 X 200 X 200 152 457 591 387 57.7 31/2 X 31/2 3.25 10.00 13.00 7.75 22.9 10 10 10 6.50 20.50 27.25 18.00 190.0 90 X 90 X 90 89 254 330 197 10.4 250 X 250 X 250 165 521 692 457 186.2 4 4 4 3.75 10.50 13.63 8.13 26.0 12 12 12 700 23.00 31.00 20.50 240.0 100 X 100 X 100 95 267 346 207 11.8 300 X 300 X 300 178 584 787 521 108.9 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s" S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_16 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Adapter Nipple .-EtoE -. I.-EtoE N . 40 Grv.x NO. Bev.. 42 Grv:x Bev. NO.43 Grv.x Grv. [E] NO.40* NO.43 I-EtoE ID NO.42 I .1 .r ,c Size Adapter Nipple(s) Size Adapter Nipple(s) Nominal Actual Approx. Nominal Actual Approx. Size Outside Diameter E to E Weight Each Size Outside Diameter E I Weight Each Inche s Inches Inches Lbs. Inches Inches Inches Lbs. mm mm mm kg mm mm mm kg 3/4 1.050 3.00 0.3 6 6.625 6.00 9.5 20 26.9 76 0.1 150 168.3 152 4.3 1 1.315 3.00 0.4 8 8.625 6.00 14.2 25 33.7 76 0.2 200 219.1 152 6.4 11/4 1.660 4.00 0.8 10 10.750 8.00 27.0 32 42.4 102 0.4 250 273.0 203 12.2 11/2 1.900 4.00 0.9 12 12.750 8.00 33.0 40 48.3 102 0.4 300 323.9 203 15.0 2 2.375 4.00 1.2 *Available with British Standard Pipe Threads,specify"BSP"clearly on order. 50 60.3 102 0.5 IMPORTANT NOTES: 21/2 2.875 4.00 1.9 65 73.0 102 0.9 For pump package nipples with 1112'740 mm hole cut to receive Style 923 3 3.500 j 4.00 2.5 Vic-Let or Style 924 Vic-O-Well request special No.40,42 or 43 nipples 80 88.9 102 1.1 and specify No.40-H,42-H or 43-H on order.NOTE:4-127100-300 mm 3'/z 4.000 j 4.00 2.1 diameter-87200 mm minimum length required. 90 101.6 102 0.9 #For roll grooved systems,Victaulic offers the Advanced Groove System 4 4.500 6.00 5.5 (AGS).For pricing and availability of cut groove fittings in this size,contact loo 114.3 1S2 2.5 your nearest Victaulic sales office. 5 5.563 6.00 7.4 Note:All fittings are ductile iron unless otherwise noted with an"sw°or"s' 125 141.3 152 3.4 S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtal- REV_Q 07.01_17 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Cap _T NO. 60 lb NO.60601 Size Cap Size Cap Nominal Actual T Ap"x. Nominal Actual T Approx.. Size Outside Diameter Thicknes Wei ghl a. Size Outside Diameter Thicknes Weight Eac Inche s Inches Inches Inche s Inches Inches Lbs. mm mm mm mm mm mm s7 3/4 1.050 0.88 0.2 6 6.625 1.00 6.1 20 26.9 22 0.1 150 168.3 25 2.8 1 1.315 0.88 0.3 8 8.625 1.19 13.1 25 33.7 22 0.1 200 219.1 30 5.9 1 Y4 1.660 0.88 0.3 10 10.750 1.25 21.0 32 42.4 22 0.1 250 273.0 32 9.5 P/2 1.900 0.88 0.5 12 12.750 1.25 35.6 40 48.3 22 0.2 300 323.9 1 32 16.2 2 2.375 0.88 0.6 14#(s) 14.000 9.50 50 60.3 22 0.3 350 355.6 241 2'/z 2.875 0.88 1 1.0 16#(s) 16.000 10.00 65 73.0 22 0.5 400 406.4 254 76.1 mm 3.000 0.88 1.2 18#(s) 18.000 11.00 76.1 22 0.5 450 457.0 279 3 3.500 0.88 1.2 20#(s) 20.000 12.00 80 88.9 22 0.5 500 508.0 305 31/2 4.000 0.88 2.5 24#(s) 24.000 13.50 90 101.6 22 1.1 600 610.0 343 108.Omm 4.250 1.00 2.3 14-24 AGS" For AGS fitting information,see publication 20.05 108.0 25 1.0 350-600 v 4 4.500 1.00 2.5 100 114.3 25 1.1 IMPORTANT NOTES: 133.Omm 5.250 1.00 4.5 *Steel dish caps available through 247600mm,contact Victaulic. 133.0 25 2.0 No.60 cap is not suitable for use in vacuum service with Style 72 or 750 couplings. 139.7mm 5.500 1.00 4.5 No.61 bull plugs should be used,see pg.35. 139.7 25 2.0 5 5.563 1.00 4.6 #For roll grooved systems,Victaulic offers the Advanced Groove System 125 141.3 25 2.1 (AGS).For pricing and availability of cut groove fittings in this size,contact 6.250 1.00 6.8 your nearest Victaulic sales office. 159.Omm 159.0 25 3.1 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s 165.1 mm 6.500 1.00 7.3 S=Carbon Steel Direct Roll Groove(OGS) 165.1 25 3.3 SW=Carbon Steel Segmentally Welded WWW.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_18 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Flanged Adapter Nipple EtoE EtoE �- EtoE EtoE EtoE NO.41 ANSI Class 125(Cast Iron) NO.45F ANSI Class 150 Flat Face NO.45R ANSI Class 150 Raised Face NO.46F ANSI Class 300 Flat Face NO.46R ANSI Class 300 Raised Face N0.41 N0.45F N0.46F NO,45R NO.46R 'I' Size Flange Adapter Nipple Flange Adapter Nipple(S) Flange Adapter Nipple(S) Nominal Outside Diameter TMEOghl c - all t ua mm mm kg 7 'g mm kg 3/4 1.050 3 _ 3 2.3 3 3.3 20 26.9 76 76 1.0 76 1.5 1 1.315 3 2.5 3 2.7 3 3.9 25 33.7 76 1.1 76 1.2 76 1.8 11/4 1.660 4 3.0 4 3.3 4 4.8 32 42.4 102 1.4 102 1.5 102 2.2 1Y2 1.900 4 3.5 4 3.9 4 6.9 40 48.3 102 1.6 102 1.8 102 3.1 2 2.375 4 5.5 4 6.2 4 8.2 50 60.3 102 2.5 102 _ 2.8 102 3.7 21/2 2.875 4 8.0 4 9.9 4 11.9 65 73.0 102 3.6 102 4.5 102 5.4 3 3.500 4 9.5 4 11.4 4 16.5 80 88.9 102 4,3 102 5.2 102 7.5 3/z 4.00 4 12.0 4 15.1 4 20.1 90 101.6 102 5.4 102 6.8 102 9.1 4 4.500 6 16.7 6 18.4 6 27.4 100 114.3 152 7.6 152 8.3 152 12.4 5 5.563 6 21.5 6 21.3 6 35.3 125 141.3 152 9.8 152 9.7 152 16.0 6 6.625 6 26.5 6 27.5 6 47.5 150 168.3 152 12.0 152 12.5 152 21.5 8 8.625 6 39.0 6 41.3 6 70.3 200 219.1 152 17.7 152 18.8 152 31.9 10 10.750 8 57.0 8 59.8 8 100.8 250 273.0 203 25.9 203 27.1 203 45.7 12 12.750 8 41.0 8 88.2 8 146.2 300 323.9 203 18.6 203 40.0 203 66.3 14# 14.000 8 _ 8 8 350 355.6 203 203 + 203 + 16# 16.000 8 _ 8 8 400 406.4 203 203 + 203 + 18# 18.000 8 _ 8 8 450 457.0 203 203 + 203 + 20# 20.000 8 8 8 500 508.0 203 203 + 203 + 24# 24.000 8 8 8 600 610.0 203 203 + 203 + 314-600 v For AGS fitting information,see publication 20.05 IMPORTANT NOTES: +Contact Victaulic for details. Flanged adapter nipples are supplied with standard rolled grooves. Standard cut grooves or machining for rubber lining are optionally available.Contact Victaulic for details. #For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IC_t-QUIT REV_Q 07.01_19 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Swaged Nipple NO. 53 Grv. x Grv. EtoF� EtoE� NO. 54 Grv.x Thd. N0. 55 Thd. x Grv. NO.53 NO.55 r-EtoE� NO.54 Nominal Size Swaged Nipples(S) Size Swaged Nipples(S) _ _ .. .Weight Each Siz E to E Weight Each Size Inches Inches Lbs. Inches Inches Lbs mm mm kg mm mm kg 2 1 6.50 2.0 4 3 9.00 7.5 50 X 25 J 165 0.9 100 X 80 229 3.4 11/4 6.50 2.0 31/2 9.00 7.5 32 165 0.9 90 229 3.4 152 6.50 2.0 5 2 11.00 11.5 40 165 0.9 125 X 50 279 5.2 252 1 7.00 3.0 3 11.00 11.3 65 X 25 178 1.4 80 279 5.1 154 7.00 3.0 4 11.00 11.5 32 178 1.4 100 279 5.2 152 7.00 3.0 6 1 12.00 17.0 40 178 1.4 150 X 25 305 7.7 2 7.00 3.0 1'/4 12.00 17.0 50 178 1.4 32 305 7.7 3 x 1 8.00 4.5 11/2 12.00 17.2 80 25 203 2.0 40 305 7.8 1'A 8.00 4.5 2 12.00 17.4 32 203 2.0 50 305 7.9 152 8.00 4.4 21/2 12.00 17.4 40 203 2.0 65 305 7.9 2 8.00 4.5 3 12.00 17.4 50 203 2.0 80 305 7.9 21/2 8.00 4.5 31/2 12.00 17.4 65 203 2.0 90 305 7.9 31/2 3 8.00 6.8 4 12.00 17.5 90 X 80 203 3.1 100 305 7.9 4 1 9.00 7.5 41k 12.00 17.5 100 X 25 229 3.4 120 305 7.9 11/4 9.00 7.5 5 12.00 17.5 32 229 3.4 125 305 7.9 11/2 9.00 7.5 8 6 20.0 40 229 3.4 200 X 150 + 9.1 2 9.00 7.5 +Contact Victaulic for details. 50 229 3.4 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s 4 252 229 3.4 75 100 X 65 229 S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_20 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Female Threaded Adapter Hose Nipple NO. 80 E to E NO. 48 .-E to E NO.80 NO. 48 :0 +No.48 Size Female Threaded Adapter Size Hose Nipple(s) Size Outside Diameter E to E Weigh Ea Size Outside Diameter E to E Weight Each Inches Inches Inches Lb$- Inches Inches Inches Lbs. mm Mm mm k(jg mm mm rnm kg 3/4 1.050 2.00 1.0 3/4 1.050 3.12 0.3 20 26.9 51 0.5 20 26.9 79 0.1 1 1.315 2.06 1.0 1 1.315 3.38 0.4 25 33.7 52 0.5 25 33.7 86 0.2 1 Y4 1.660 2.31(sw) 1.5 1 Y4 1.660 3.88 0.6 32 42.4 59 0.7 32 42.4 98 0.3 1 1/2 1.900 2.31(sw) 1.5 1 1/2 1.900 3.88 0.8 40 48.3 59 0.7 40 48.3 98 0.4 2 2.375 2.50 1.4 2 2.375 4.50 1.1 50 60.3 64 0.6 50 60.3 114 0.5 21/2 2.875 2.75 1.5 21/2 2.875 5.38 2.0 65 73.0 70 0.7 65 73.0 137 0.9 3 3.500 2.75 2.9 3 3.500 5.75 3.2 80 88.9 70 1.3 80 88.9 146 1.5 4 4.500 3.25 4.5 4 4.500 7.00 4.9 100 114.3 83 2.0 100 114.3 178 2.2 5 5.563 8.75 8.0 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s 125 141.3 222 3.6 S=Carbon Steel Direct Roll Groove(OGS) 6 6.625 10.12 14.3 SW=Carbon Steel Segmentally Welded 150 168.3 257 6.5 IMPORTANT NOTE: 8 8.625 11.88 24.7 200 219.1 302 11.2 Available with British Standard Pipe threads,specify"BSP"clearly on order. 10 10.750 12.50 40.1 250 273.0 318 18.2 12 12.750 14.50 62.0 300 323.9 368 28.1 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IlCtait- REV_Q 07.01_21 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Concentric/Eccentric Reducer NO. 50 Concentric E NO. 51 Eccentric I�toE' EtoE EtoE� r-EtoE �ED EA Fabricated Steel Fabricated Steel NO.50 NO.51 No.50 No.51 I. .0 Size Concentric Reducer Eccentric Reducer Size Concentric Reducer Eccentric Reducer Nominal Approx. App,.,4 'n.1 Appr x. Siz E to E Weight Each E to E W�,ght E.1 �ze E to E Weight Each E to E W Inches Inches Lbs. Inches Lbs. r11nmhes Inches Lbs. Inches mm mm kg mm kg mm mm kg mm �11 11/a 3/a 1.9 _ 311 3 2.50 2.0 9.50sw 7.0 32 X 20 ± 0.9 90 X 80 64 0.9 241 3.2 1 1.9 _ 4 1 3.00 3.0 13.00 sw 6.5 25 + 0.9 100 X 25 76 1.4 330 2.9 11/2 3/a + 1.4 - 1 Ya + 4.6 X - 40 20 0.6 32 2.1 1 2.50 0.8 8.50sw 5 1112 3.00sw 2.6 10.00sw 8.1 25 64 0.4 216 1 2.0 40 76 1.2 254 3.7 11/a 2.50 1.0 1 2 3.00 2.4 4.00 3.3 32 64 0.5 50 76 1.1 102 1.5 2 3/a 2.50 0.9 9.005w 1 2.0 21/2 3.00 2.7 4.00 3.4 50 X 20 64 0.3 229 0.9 65 76 1.2 102 1.5 1 2.50 0.7 9.00sw 1 2.3 3 3.00 3.2 4.00 3.5 25 64 0.3 229 1.0 80 76 1.4 102 1.6 1114 2.50 1.2 9.00 5W 4.6 31/2 3.00 2.9 10.005w 8.0 32 64 0.5 229 I 2.1 90 76 1.3 254 3.6 11/2 3.50 1.0 3.50 1 1.1 5 2 11.00sw 9.0 11.00sw 5.2 40 89 0.5 I 89 0.5 125 X 50 279 4.1 279 2.4 2'/z 3/a 1.3 3.3 2112 4.00 4.3 11.00sw 10.8 65 X 20 + 0.6 + 1.5 65 102 2.0 279 4.9 1 2.50 1.1 9.50 3.5 3 4.00 55 11.005w 11.1 25 64 0.5 241 1.6 80 102 2.5 279 5.0 1 Ya 3.50 3.3 3.50 1.4 4 3.50 4.3 5.00 12.0 32 89 1.5 89 a6 100 89 1.9 127 5.4 11/2 2.50 3.6 9.50sw 3.7 6 1 4.00 5.0 11.50sw 14.5 40 64 1.6 241 1.7 150 X 25 102 2.3 292 6.6 2 2.50 3.9 3.50 4.3 1112 5.5 50 64 _ 1.8 89 2.0 40 + 2.5 + + 3 3/a 1.5 4.5 2 4.00 6.6 11.50sw 14.5 80 X 20 0.7 + 2.0 50 102 3.0 292 6.6 1 2.50 1.3 9.50sw 4.8 2112 4.00 6.4 11.50sw 14.2 25 241 0.6 241 2.2 65 102 2.9 292 6.4 1 Ya 2.50 1.4 4.8 3 4.00 6.4 5.50 15.0 32 64 0.6 + 2.2 80 102 2.9 140 6.8 1 1/2 2.50 5.1 9.50sw 5.1 4 4.00 6.5 5.50 17.0 40 64 2.3 241 2.3 100 102 2.9 140 7.7 2 2.50 1.6 3.50 6.0 5 4.00 6.4 5.50 17.0 50 64 0.7 89 2.7 125 102 2.9 140 77 21/2 2.50 1.8 3.50 7.0 8 2Yz 16.00 7.9 12.00sw 26.1 65 64 0.8 89 3.2 200 X 65 406 3.6 305 11.8 76.1 2.50 2.1 _ _ 3 5.00 9.3 12.00 sw 22.0 64 1.0 80 127 4.2 305 10.0 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s S=Carbon Steel Direct Roll Groove(OGS) SW=Carbon Steel Segmentally Welded www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt.'alUI1C® 07.01_22 REV_Q CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Concentric/Eccentric Reducer NO. 50 Concentric E I�toE � r- � N0. 51 Eccentric [4--E to E �EtoE EtoE -F_-j E]d Fabricated Steel Fabricated Steel NO.50 NO.51 No.50 No.51 5 Size Concentric Reducer Eccentric Reducer Size Concentric Reducer Eccentric Reducer Nominal Appr x. A P" Nominal Approx. Appr x. Siz E to E Weight Eac h E to E We ih t Size E to E Weight Each E to E Weight Each Inches Inches Lbs. Inches Lbsq Inches Inches Lbs. Inches Lbs. mm mm kg mm g mm mm kg mm kg 8 4 5.00 10.4 12.00 sw 23.0 #18 x 12 15.00 91.0 15.00 91.0 200 X 100 127 4.8 305 10.4 450 300 381 41.3 381 41.3 5 5.00 11.6 12.00sw 23.0 14 15.00 91.0 15.00 91.0 125 127 5.2 305 10.4 350 381 41.3 381 41.3 6 5.00 11.9 6.00 24.0 16 15.00 91.0 15.00 91.0 150 127 5.4 152 10.9 400 381 41.3 381 41.3 10 4 6.00 19.7 13.00 sw 32.0 #20 10 20.00 110.0 20.00 177.0 250 X 100 152 8.9 330 14.5 500 X 250 508 49.9 508 80.3 5 34.3 34.6 12 20.00 120.0 20.00 120.0 125 + 15.6 + 15.7 300 508 54.4 508 54.4 6 6.00 20.0 13.00 sw 36.9 14 20.00 149.0 20.00 149.0 150 152 9.1 330 16.7 350 508 67.9 508 67.9 8 6.00 22.0 7.00 21.6 16 20.00 120.0 20.00 120.0 200 152 10.0 178 9.8 400 508 54.4 508 54.4 12 4 44.0 14.00 sw 48.0 18 20.00 136.0 20.00 136.0 300 X 100 + 20.0 356 21.8 450 508 61.7 508 61.7 6 7.00 24.6 14.00 sw 50.0 #24 10 20.00 142.0 20.00 142.0 150 178 11.2 356 22.7 600 X 250 508 64.4 508 64.4 8 7.00 52.0 14.00sw 53.5 12 20.00 150.0 20.00 150.0 200 178 23.6 356 24.3 300 508 68.0 508 68.0 10 7.00 39.0 14.00 sw 57.0 14 20.00 162.0 20.00 162.0 250 178 17.7 356 25.9 350 508 73.5 508 73.5 #14 6 13.00 65.0 13.00 60.0 16 20.00 162.0 20.00 162.0 350 X 150 330 29.5 330 27.2 400 508 73.5 508 73.5 8 13.00 65.0 13.00 60.0 18 20.00 162.0 20.00 162.0 200 330 29.5 330 27.2 450 508 73.5 508 73.5 10 13.00 66.0 13.00 65.0 20 20.00 151.0 20.00 190.0 250 330 29.9 330 29.5 500 508 68.5 508 86.2 12 13.00 68.0 13.00 66.0 14 vn For AGS fitting information,see publication 20.05 300 330 30.8 330___] 29.9 350-600 600 #16 8 14.00 73.0 14.00 73.0 400 X 200 356 33.1 355 33.1 + Contact Victaulic for details. to§ 14.00 73.0 14.00 73.0 Available with male threaded small end No.52. 250 356 33.1 355 33.1 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s 12 14.00 73.0 14.00 73.0 S=Carbon Steel Direct Roll Groove(OGS) 300 356 33.1 355 33.1 SW=Carbon Steel Segmentally Welded 14 14.00 73.0 14.00 73.0 350 356 33.1 355 33.1 IMPORTANT NOTE: #18 10 15.00 91.0 15.00 9i.0 Steel eccentric reducers available through 307750 mm,contact Victaulic for 450 X 250 381 41.3 381 41.3 dimensions. #For roll grooved systems,Victaulic offers the Advanced Groove System (AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. §Cast fitting available for JIS size.Contact Victaulic for details. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtal- REV_Q 07.01_23 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings Small Threaded Reducer NO. 52 E E N 5 N0.52 N0.52F No.52F No.52 Concentric Reducer with BSPT Size Small Threaded Reducer Female Threaded End IIIIIIIIIII�=- M6 WOMEM23S6 Nominal Inches Inches Lbs. mm mm kg 11/2 1 2.50 0.8 4 21/2 3.00 2.6 40 x 25 64 0.4 100 x 65 76 1 1.2 1'/4 2.50 0.9 3 3.00 2.5 32 64 0.4 80 76 1.1 2 3/4 2.50 0.9 108 x 42.4 76.2 1.3 76.2 1.32 50 x 20 64 0.4 48.3 76.2 1.3 76.2 1.35 1 2.50 0.7 60 - - 76.2 1.39 25 64 0.3 114.3 x 42.4 76.2 1.3 76.2 1.30 11/4 2.50 1.2 48.3 76.2 1.3 76.2 _ 1.34 32 64 0.5 60 - 76.2 1.40 1'/z 2.50 1.0 5 4 4.5 40 64 0.5 125 x 100 + 2.0 21/2 1 2.50 1.1 133 x 60 - - 114.3 2.17 65 x 25 64 0.5 139 x 60 - - 114.3 2.26 1 Y4 2.50(sw) 1.2 6 1 4.00 5.5 32 64 0.5 150 x 25 102 2.5 1 Y2 2.50(sw) 1.3 2 4.00 5.7 40 64 0.6 50 102 2.6 2 3.00 1.4 21/2 4.00 5.8 _ 50 76 0.6 65 102 2.6 76.1 x 48.3 63.5 0.8 63.51 0.77 3 4.00 5.8 60 - - 63.5 0.85 80 102 2.6 3 x 3/4 +(sw) 1.5 4 +(sw) 6.5 - 80 20 0.7 100 2.9 1 2.50 1.3 5 2.0 25 64 0.6 125 +(sw) 0.9 - - 1'/4 2.50 1.5 159 x 42.4 114.3 2.2 114.3 2.45 32 64 0.7 48.3 114.3 2.2 114.3 2.51 1'/2 2.50(sw) 1.5 60 - - 114.3 2.60 40 64 0.7 165.1 x 42.4 101.6 2.4 101.6 2.90 2 2.50 1.5 48.3 101.6 2.6 101.6 295 50 64 0.7 60 - - 101.6 3.00 2'/2 2.50 2.4 _ 8 2 16.00 1.5 65 64 1.1 200 x 50 406 0.7 88.9 x 414 1 63.5 0.9 633 0.82 21/2 16.00 j 1.7 48.3 63.5 0.9 63.5 0.85 1 65 406 0.8 60 63.5 1 0.89 4 1 3.00 2.3 + Contact Victaulic for details. too x 25 76 1.0 - - Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s" 11/2 3.00 2.7 S=Carbon Steel Direct Roll Groove(OGS) 40 76 1.2 SW=Carbon Steel Segmentally Welded 2 3 2.6 50 76 6 1.2 IMPORTANT NOTE: Available with British Standard Pipe Threads,specify"BSP"clearly on order www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1C® 07.01_24 REV_Q CARBON GROOVED FITTINGS 07.01 IA Grooved End Fittings INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. UPDATED 12/2011 07.01 1449 REV Q 1 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 07.01 4 M 1 FAB° 1 DIELECTRIC NIPPLES Specification: MIFAB®Series MI-DE (specify size and connection type) galvanized steel dielectric nipples with plastic liner, designed and tested for use at temperatures up to +225 degrees F and for pressures up to 425 PSI. Function: Used to protect the plumbing system through the steel to plastic design that provided a dielectric waterway in all potable water and appropriate HVAC applications. Dissimilar metals are separated in the waterway eliminating the local galvanic cell. The metal to metal connection design maintains external electrical continuity to prevent stray current corrosion. GALVANIZED STEEL NIPPLE PLASTIC LINER MODEL NIPPLE NIPPLE CONNECTION NUMBER LENGTH DIAMETER TYPE MI-DETT-50 3" 76 1/2" 13 THREADED X THREADED MI-DETT75 3" 76 3/4" 19 THREADED XTHREADED MI-DETT-100 4" 102 1" 25 THREADED X THREADED MI-DETT-125 4" 102 1 1/4" 32 THREADED X THREADED MI-DETT-150 4" 102 1 1/2" 38 THREADED XTHREADED MI-DETT-200 4" 102 2" 52 THREADED X THREADED MI-DETT-250 6" 152 21/2" 65 THREADED XTHREADED MI-DEGT-100 4" 102 1" 25 GROOVED XTHREADED MI-DEGT-125 4" 102 1 1/4" 32 GROOVED XTHREADED MI-DEGT-150 4" 102 1 1/2" 38 GROOVED XTHREADED MI-DEGT-200 4" 102 2" 52 GROOVED XTHREADED MI-DEGT-250 6" 152 2 1/2" 65 GROOVED X THREADED MI-DEGG-200 4" 102 2" 52 GROOVED X GROOVED MI-DEGG-250 6" 152 2 1/2" 65 GROOVED X GROOVED Job Name Page No: Section No: Contractor Schedule No: Purchase Order No: M IFAB reserves the right to make changes in material and design without formal notice and obligation. USA:1-800-465-2736 www.mifab.com CAN:1-800-387-3880 Page Cl 10 A �00� 514 OFFSET C.P.V.C. - STEEL - COPPER 9905/9906 HANGER f r �f l 11/2" Hanger/Restrainer o SIZE-3/4"thru 2"pipe. MATERIAL-Carbon Steel. FINISH-Mil. Galvanized.. LISTINGS- *us EX 4231,EX 2551 PATENT-No.6,648,278. ® © Stabilize-Only FUNCTION-Use on C.P.V.C.,Copper or Steel pipe. Hanger and restrainer on top,bottom or side position. r' a _ V INSTALLATION- Per N.F.P.A 13, 13R and 13D on top,bottom or side of beam. Space by pipe type. On 3/8"wood web use#906 backing nuts. -see drawing. Snap over pipe then squeeze strap back allowing pipe to slide freely. On copper-insulate pipe. FASTENERS-UL Listed per NFPA 13 in WOOD: CPVC pipe-#905 screw-no pre-drill. Hanger,Restrainer Copper pipe- #905 screw- no pre-drill. and Support Steel pipe- 1/4"x11/2"lag screw- no pre-drill. in STEEL: I( CPVC pipe- 1/4" or#14 Tek Screw. Copper pipe- 1/4"or#14 Tek Screw. Steel pipe- 1/4" or#14 Tek Screw. FEATURES * 1 1/2"Offset. * 3/4"and 1"pipe size have common center-line. *Leg design produces superior strength. *Offset edge eliminates abrasion. stabilize-Only *Required AFCON#905 screw has 5/16"hex head- included r ORDERING-Part#and pipe size. 1� AFCON#906 sold separately. 'i) INDEX 05/03 WILKINS, Model 975XL a 4LR-N-&company Reduced Pressure Principle Assembly SPECIFICATION SUBMITTAL SHEET APPLICATION Designed for installation on potable water lines to protect against both backsiphonage and backpressure of contami- nated water into the potable water supply.Assembly shall provide protection where a potential health hazard exists. VFW FEATURES STANDARDS COMPLIANCE Sizes: ❑ 3/4" ❑ 1" ❑ 1 1/4" ❑ 1 1/2" ❑ 2" ASSEO Listed 1013 IAPMOO Listed Maximum working water pressure 175 PSI ULO Classified(less shut-off valves or with OS&Y valves) Maximum working water temperature 180°F C-ULO Classified Hydrostatic test pressure 350 PSI CSAO Certified End connections Threaded ANSI B1.20.1 AWWA Compliant C511 Approved by the Foundation for Cross Connection OPTIONS Control and Hydraulic Research at the University of (Suffixes can be combined) Southern California NYC MEA425-89-M VOL3 ❑ - with full port QT ball valves (standard) MATERIALS ❑ L - less ball valves Main valve body Cast Bronze ASTM B 584 ❑ U - with union ball valves Access covers Cast Bronze ASTM B 584 ❑ MS - with integral relief valve monitor switch Fasteners Stainless Steel, 300 Series ❑ P - for reclaimed water systems Elastomers Silicone (FDAApproved) ❑ S - with bronze "Y"type strainer ❑ BMS - with battery operated monitor switch Bona Nitrite (FDAApproved) Polymers Nory l NSF Listed ❑ FDC - with fire hydrant connection; 2" only Springs Stainless steel, 300 series ❑ TCU - with test cocks up ❑ V - with union swivel elbows (3/4" & 1") ❑ SE - with street elbows ❑ FT - with integral male 450 flare SAE test fitting E E ACCESSORIES O ❑ Air gap (Model AG) o o ❑ Repair kit (rubber only) F o O o ❑ Thermal expansion tank (Model XT) 0 0 ❑ Soft seated check valve (Model 40XL) D C B ❑ Shock arrester(Model 1250) A ❑ QT-SET Quick Test Fitting Set ❑ Ball valve handle locks G ❑ Test Cock Lock (Model TCL24) Relief Valve discharge port: 3/4"- 1" - 0.63 sq. in. DIMENSIONS &WEIGHTS (do not include pkg.) 1 1/4"-2" - 1.19 sq. in. DIMENSIONS(approximate) WEIGHT MODEL A UNION B LESS BALL LESS WITH SIZE A BALL VALVES VALVES C D E F G BALL BALL VALVES VALVES in. mm in. mm in. mm in. mm in. I mm in. I mm in. mm in. I mm in. I mm Ibs I kg lbs. kg 3/4 20 12 305 133/4 349 73/4 197 21/8 54 3 76 31/2 89 5 127 161/8 410 10 4.5 12 5.5 1 25 13 330 141/2 368 73/4 197 21/8 54 3 76 31/2 89 5 127 173/8 441 10 4.5 14 6.4 1 1/4 32 17 432 1813/16 478 1015/16 278 23/4 70 31/2 89 1 5 127 t3/4 171 229/16 573 22 10 28 12.7 1 1/2 40 173/8 441 193/8 492 1015/16 278 23/4 70 3 1/2 89 5 127 171 241/16 611 22 10 28 12.7 2 50 181/2 470 201/2 521 1015/16 278 23/4 70 3 1/2 89 5 127 171 261/2 673 22 10 34 15.4 D• REVISION: BF-975XL(LG) 1/11 Page 1 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766 In Canada:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 11-2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website:http://www.zurn.com FLOW CHARACTERISTICS MODEL 975XL 3/4", 1", 1 11/4", 11 1/2" &2" (STANDARD&METRIC) FLOW RATES(1/s) 1.26 2.52 3.8 5.0 3.2 6.3 9.5 12.6 15.8 a 112" 137 20 3/4"(20mm) 1"(25mm) 20 1 1/4"(32mm) (40m 0 15 15 - 2"(5omm). 103 0 W W W 10 10 69 CO W W UJI IX a 5 5 0 20 40 60 80 5 0 50 100 150 200 250 a FLOW RATES(GPM) O Rated Flow(Established by approval agencies) Capacity thru Schedule 40 Pipe TYPICAL INSTALLATION Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec 1/8" 1 1 2 3 Local codes shall govern installation requirements. To be 1/4" 2 2 3 5 installed in accordance with the manufacturers'instructions 3/8" 3 4 6 9 and the latest edition of the Uniform Plumbing Code.Unless otherwise specified, the assembly shall be mounted at a 1/2" 5 7 9 14 minimum of 12" (305mm)and a maximum of 30" (762mm) 3/4" 8 12 17 25 above adequate drains with sufficient side clearance for 1" 13 20 27 40 testing and maintenance. The installation shall be made 1 1/4" 23 35 47 70 so that no part of the unit can be submerged. 1 1/2" 32 48 63 95 2" 52 78 105 167 CENTRAL STATION ALARM PROTECTIVE PANEL ENCLOSURE I BATTERY MONITOR SWITCH* 12"MIN. 30"MAX 30"MAX. OPTIONAL AIR GAP WATER METER AIR GAP DRAIN FITTING II II II p DIRECTION OF FLOW FLOOR FLOOR DRAIN INLET SHUT-OFF DIRECTION OF FLOW ED INDOOR INSTALLATION OUTDOOR INSTALLATION (*Shown w/optional BMS) SPECIFICATIONS The Reduced Pressure Principle Backflow Preventer shall be ASSE® Listed 1013, rated to 180°F and supplied with full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal polymers shall be NSF® Listed NorylTM and the seat disc elastomers shall be silicone. The first and second checks shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed indoors, the installation shall be supplied with an air gap adapter and integral monitor switch. The Reduced Pressure Principle Backflow Preventer shall be a WILKINS Model 975XL. WILKINS a Zurn company, 1747 Commerce Way,Paso Robles,CA93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1 L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website:http://Www.zurn.com Page 2 of 2 tqCD Fire L Buddin I)Products Technical Services: Tel: (800)381-9312/Fax: (800)791-5500 The Tyco® 2 thru 8 inch (DN50 thru DN200) Model PRV-1 Pressure Re- ducing Valves are factory assembled . and fully trimmed valve arrangements for pressure control.They are used on a water filled pipe where it is necessary -Tr to reduce a higher inlet pressure to a lower delivery pressure under static and/or residual flowing conditions.The PRV-1 is intended to automatically - maintain the outlet "set pressure" (static and residual) within a close range, regardless of fluctuations in the higher pressure inlet line or varying flow rates. The PRV-1 is provided with a factory NORTH AMERICA outlet "set pressure" of 125 psi (8,6 Available Body Styles, End Connections&Sizes bar); however it may be field set to a nominal outlet "set pressure" of 80 to Nominal Valve Size 225 psi (5,5 to 15,5 bar) per its FM Body End Connection Approval or 80 to 150 SI 5,5 to 10,3 Style 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch pP p ( (DN50) (DN80) (DN100) (DN150) (DN200) bar) per its UL Listing. Thread x Thread • N/A N/A N/A N/A Typical applications are as follows: Globe Groove x Groove • • • • N/A ❑Within the main header(Ref. Figure Flange x Flange N/A N/A • • • 1) supplying wet pipe, dry pipe, del- uge, or preaction system risers, • =Available N/A=Not Available and/or a standpipe system supply- ing hose connections. SOUTH AMERICA, CENTRAL AMERICA&EASTERN HEMISPHERE I I As part of a sectional floor control Available Body Styles, End Connections&Sizes assembly (Ref. Figure 2) supplying sprinkler systems, and/or hose sta- Nominal Valve Size Body tions. Style End Connection 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch Features are as follows: (DN50) (DN80) (DN100) (DN150) (DN200) ❑Can be Installed In any orientation. Thread x Thread • • N/A N/A N/A ❑ Eliminates any required bleeding of Globe Groove x Groove • • • • N/A trapped air from the diaphragm chamber during installation. Flange x Flange N/A • • • • ❑Globe or angle pattern. Thread x Thread • • N/A N/A N/A Accurate pressure control. Angle Groove x Groove • • • • N/A I I Standard nylon coated internal and external. Flange x Flange N/A • • • N/A (continued) • =Available N/A Not Available ❑One piece, one moving part dia- WET PIPE DRY PIPE phragm. SPRINKLER SPRINKLER ❑ In-line service. RISER RISER MAIN MAIN F1 One pilot valve sub-assembly pro- DRAIN vides for any outlet "set pressure", DRAIN i.e., 80 to 225 psi (5,5 to 15,5 bar). MAIN CONTROL MAIN WARNING PRV-1 VALVE RELIEF CONTROL HOSE The Model PRV-1 Pressure Reducing MAIN — VALVE VALVE STATIONS Valves described herein must be in- HEADER stalled and maintained in compliance with this document, as well as with the applicable standards of the National PRV-1 Fire Protection Association,in addition to the standards of any other authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- FIGURE 1 ing their fire protection system and de- TYPICAL MAIN HEADER APPLICATION vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Due to the flow regulating charac- teristic of this device, its impact on system hydraulics should be carefully considered, especially when retrofit- ted into existing systems. Downstream pressure adjustment RELIEF VALVE is only to be performed by experi- enced personnel who understand the impact of adjusting the down- stream pressure and who take full PRV-1 responsibility of the readjustment SPRINKLERS from the factory setting. The Pilot SECTIONAL Valve is provided with a Tamper Cap, CHECK which upon removal for purposes of FLOOR VALVE RISER downstream adjustment will provide CONTROL SECTIONAL MANIFOLD an indication that the PRV-1 may have HOSE CONTROL OR been altered from its factory setting. VALVE VALVE ZONE i CHECK nHOSE IEF VALVE Z SPRINKLERS SECTIONAL CHECK FLOOR VALVE CONTROL SECTIONAL CONTROL VALVE FIGURE 2 T YPICAL SECTIONAL FLOOR CONTROL APPLICATION VALVE PARTS 7 DIAPHRAGM OUTLET CHAMBER NO. DESCRIPTION CITY. Refer to Kit PRESSURE 3 1 Valve Body ........... 1 NR GAUGE 2 2 Diaphragm ........... 1 (a) ° 3 andhole Cover ....... 1 NR 4,5,6 F 4 Flat Washer, 2 Inch Valve,M12 ......4 CH 3&4 Inch Valves,M16 ..4 CH 6&8 Inch Valves,M16 ..8 CH 8 5 Hex Bolt, 8 2 Inch Valve,M12 x 35 ..4 CH 3&4 Inch Valves, 6 x 55 .... ...4 CH In 6 Inch Valve,M16 16 x x 45 ..8 CH 8 Inch Valve,M16 x 55 ..8 CH INLET 6 Hex Nut,M16, DOWNSTREAM PRESSURE 4 Inch Valve Only.......4 CH OUTLET CAVITY GAUGE 7 Pilot Valve ............ 1 (b) 8 Water Pressure Gauge ..2 (c) 9 Strainer .............. 1 (d) PRESSURE I 10 Pressure Sensor Insert .. 1 (e) SENSOR INSERT y L� UPSTREAM 11 Tubing and Fittings ..... 1 (f) INLET (SEE DETAIL) CAVITY REPLACEMENT PARTS NO. DESCRIPTION P/N STRAINER (a) Diaphragm, (SEE DETAIL) 1 Fits Either Body Style, Includes Item 2 only: GLOBE BODY STYLE 2 Inch Valves ............. 92-570-2-011 3 Inch Valves ............. 92-570-2-012 INTERIOR INTERIOR 4 Inch Valves ............. 92-570-2-013 6 Inch Valves ............. 92-570-2-014 OF OUTLET VALVE OF INLET VALVE 8 Inch Valves ............. 92-570-2-015 SENSOR CAVITY BODY CAVITY BODY (b) Pilot Valve ............... 92-570-2-200 INLET FACES + (c) Water Pressure Gauge ..... 92-570-2-201 TO TO (d) Strainer: DOWNSTREAM TRIM TRIM 2,3,&4 Inch Valves ....... 92-570-2-202 6&8 Inch Valves.......... 92-570-2-209 10 9 (e) Pressure Sensor Insert: 2 Inch Valve.............. 92-570-2-203 PRESSURE SENSOR STRAINER 3 Inch Valve.............. 92-570-2-204 INSERT DETAIL DETAIL 4 Inch Valve.............. 92-570-2-205 6 Inch Valve.............. 92-570-2-206 8 Inch Valve.............. 92-570-2-207 OUTLET DIAPHRAGM (f) Tubing and Fitting Kit, PRESSURE 7 CHAMBER Excludes Items 7,8,9,and 10 GAUGE Globe Style Valve: 2 Inch Valve.............. 92-570-3-001 0 3 3 Inch Valve.............. 92-570-3-002 2 4 Inch Valve.............. 92-570-3-003 6 Inch Valve.............. 92-570-3-004 8 Inch Valve.............. 92-570-3-005 / 4,5,6 Angle Style Valve: 8 2 Inch Valve.............. 92-571-3-001 3 Inch Valve.............. 92-571-3-002 4 Inch Valve.............. 92-571-3-003 �y�� 6 Inch Valve.............. 92-571-3-004 11 ' / 8 NOTES: 1. NR-Not Replaceable DOWNSTREAM INLET 2. CH-Common Hardware OUTLET CAVITY PRESSURE GAUGE PRESSURE SENSORINSERT DOWNSTREAM DOWNSTREAM (SEE DETAIL) 1 OUTLET FLOW OUTLET FLOW DIAPHRAGM O 0 O O TAB IS ORIENTED 0 0 PERPENDICULAR TO O 0 O O OUTLET FLOW STRAINER UPSTREAM (SEE DETAIL) INLET CAVITY GLOBE ANGLE ANGLE BODY STYLE FIGURE 3 MODEL PRV-1 PRESSURE REDUCING VALVE -ASSEMBLY- Factory Outlet "Set Pressure": End Connections: 125 psi (8,6 bar) Threaded end connections are avail- Field Outlet"Set Pressure" Range: able NPT threaded or threaded per ISO 7/1. Flanged end connections Approvals: 80 to 225 psi (5,5 to 15,5 bar)per its are available drilled per Table A. FM Approval, or 80 to 150 psi (5,5 to Grooved end connections are per in- UL Listed. FM Approved. 10,3 bar) per its UL Listing dustry standard groove specifica- The UL Listing is based on Pressure Loss With Inlet Pressure tions. 7 Installation requirements refer- Above "Set Pressure" Construction (Ref. Figure 3): enced in the Standard for Installa- The inlet pressure minus the outlet Body. Rilsan* blue coated ductile tion of Sprinkler Systems, NFPA "set pressure" equals pressure loss. iron per ASTM A536-77, Grade 65- 13, or the Standard for Installation For example:assumimg that the inlet 45-12. of Standpipe and Hose Valves, flowing pressure is 225 psi(15,5 bar) Handhole Cover. Rilsan* blue NFPA 14, as applicable. and the field outlet "set pressure" is coated ductile iron per ASTM A536- Li Inspection, testing, and mainte- 130 psi (9,0 bar), the pressure loss 77, Grade 65-45-12. nance requirements referenced in is 95 psi (6,5 bar). the Standard for Inspection, Test- Pressure Loss with Inlet Pressure Diaphragm. Nylon fabric reinforced, ing, and Maintenance of Water- Below "Set Pressure" natural rubber per ASTM D2000. Based Fire Protection Systems, Refer to Graphs A thru E. (These Diaphragm Cover Fasteners. Gal- NFPA 25. vanized carbon steel. graphs are a requirement of UL and L-]The Model PRV-1 being field set to should be used as reference only.) Pilot Valve. Brass and stainless provide the required outlet pres- Rated Flowing Range: steel with nylon fabric reinforced, sures and flows for the given appli- natural rubber per ASTM D2000 dia- cation. 2 inch (DN50): 0 to 250 GPM phragm. Li The Model PRV-1 being tested af- (0 to 946 LPM) Strainer. Brass and stainless steel. ter installation in accordance with 3 inch (DN80): 0 to 550 GPM Pressure Gauges. 2-1/2 inch (65 NFPA 13 and/or NFPA 14 as appli- (0 to 2080 LPM) mm) diameter, stainless steel case, cable. 4 inch (DN100): 0 to 1000 GPM 0 to 350 psi (25 bar). ❑The Model PRV-1 being tested pe- (0 to 3785 LPM) Tube, Fittings, and Needle Valve. riodically thereafter in accordance 6 inch (DN150): 0 to 2200 GPM Copper, brass, and stainless steel. with NFPA 25. (0 to 8325 LPM) *Rilsan is a registered trademark of Maximum Inlet Pressure: 8 inch (DN200): 0 to 4000 GPM ATOFINA Chemicals, Inc. (The Ril- 250 psi (17,2 bar) (0 to 15140 LPM) san coating is a polyamide (Nylon 11)coating.) Flange Drilling Specification Nominal Dimensions in Inches and(mm) Nominal ANSI B16.1 ' ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129 Valve Size (Class 125) (PN10)2 (PN16)3 (10K) (Table E) Dim. Dim, Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. A B N A B N A B N A B N A B N 3Inch 6.00 0.75 6.30 0.75 5.90 0.59 5.75 0.71 (DN80) (152,4) (19,0) 4 (160,0) (19,0) 8 (150,0) (15,0) 8 (146,0) (18,0) 4 USE 4Inch 7.50 0.75 8 ISO 005-2 7.09 0.75 8 6.89 0.59 8 7.00 0.71 8 (DN100) (190,5) (19,0) (PN16) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0) 6Inch 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 (DN150) (241,3) (22,2) 8 (240,0) (23,0) 8 (240,0) (19,0) 8 (235,0) (22,0) 8 8Inch 11.75 0.88 8 11.61 0.91 8 11.61 0.91 12 11.42 0.75 12 11.50 0.87 8 (DN200) (298,5) (22,2) (295,0) (23,0) (295,0) (23,0) (290,0) (19,0) (292,0) (22,0) 'Same drilling as forANSI 816.5(Class 150)and ANSI B16.42(Class 150). Dim.A Qty.N 'Same drilling as for BS 4504 Section 3.2(PN10)and DIN 2532(PN10). Bolt Circle— Number of 'Same drilling as for BS 4504 Section 3.2(PN16)and DIN 2532(PN16). Diameter Bolt Holes Dim.B Bolt Hole Diameter o—o TABLE A DIMENSIONAL SPECIFICATION FOR SELECTION OF FLANGE DRILLING TAMPER ADJUSTING CAP SCREW OUTLET PRESSURE LOCKNUT GAUGE PILOT VALVE NEEDLE VALVE (FACTORY SET, REGULATING DIAPHRAGM DO NOT READJUST) SPRING CHAMBER ♦ EXIT FLOW SUPPLY LINE INLET PRESSURE PILOT GAUGE VALVE SYSTEM SEAT WATER SUPPLY PRESSURE OUTLET CAVITY INLET CAVITY SENSING LINE II INTERIOR INTERIOR VALVE OF OUTLET j I VALVE OF INLET BODY CAVITY SENSOR BODY CAVITY INLET FACES PRV-1 PRV-1 UPSTREAM DIAPHRAGM SEAT i TO TO TRIM PRESSURE TRIM STRAINER SENSORINSERT FIGURE 4 MODEL PRV-1 PRESSURE REDUCING VALVE —OPERATION— low the "set pressure" of the spring, I-I As the flow demand continues down- exit flow from the Diaphragm Chamber stream of the PRV-1 and the "set through the Pilot Valve to the PRV-1 pressure" is met, the Pilot Valve With reference to Figure 4,the system outlet cavity resumes and pressure in Seat closes.As the Pilot Valve Seat water supply pressure from the inlet the Diaphragm Chamber decreases. closes to reduce the opening, pres- cavity of the PRV-1 enters the Dia- sure is trapped in the Diaphragm phragm Chamber through a Strainer The regulated flow through the Pilot Chamber at a point that allows the and Needle Valve. The factory set Valve decreases and increases the Diaphragm to remain lifted from the Needle Valve provides the required pressure in the diaphragm chamber to PRV-1 Seat to retain the down- orifice size for the supply line to the sufficiently open and close the PRV-1, stream "set pressure". Diaphragm Chamber to optimize per- as required, to regulate the down- formance. stream "set pressure". 11 Should the downstream pressure The operation sequence is as follows: start to fall below the"set pressure", Exit flowfrom the Diaphragm Chamber the Pilot Valve Seat re-opens to al- through the Pilot Valve is controlled by -When there is no flow demand low for a decrease in pressure in the a regulating spring that is factory set, downstream of the PRV-1, the Diaphragm Chamber to allow the and subsequently field adjustable, to PRV-1 Seat is closed and the Pilot PRV-1 to open further and then once the desired downstream"set pressure" Valve Seat is closed. With the Pilot again establish the downstream"set that is to be maintained.A sensing line Valve Seat closed, pressure is pressure". connects the outlet of the Pilot Valve trapped in the Diaphragm Chamber to the system piping downstream of to seat the Diaphragm and the [-I When the downstream pressure is at the PRV-1 via the Pressure Sensor PRV-1 remains closed. or above the "set pressure" and as- Insert in the outlet cavity. suming there is a flow demand ❑When there is a flow demand down- downstream of the PRV-1, the Pilot When the downstream pressure rises stream of the PRV-1 and the PRV-1 Valve Seat is closed to trap a suffi- above the"set pressure"of the spring, outlet pressure drops below the"set cient pressure in the Diaphragm exit flow from the Diaphragm Chamber pressure,the Pilot Valve Seat opens Chamber to allow the PRV-1 to re- through the Pilot Valve to the PRV-1 to relieve pressure from the Dia- main open to provide the "set pres- outlet cavity is stopped and pressure phragm Chamber allowing the sure". increases in the Diaphragm Chamber. PRV-1 to open. When downstream pressure falls be- facilitate a flow test at the sprinkler or multiple hose valves, as required, system demand. will be necessary to simulate hose stream demand. For the purposes of the following in- The following items must be consid- struction, the opening of a "flow test ered and applied accordingly for an valve" simulates either the sprinkler installation that will be using the Model demand or hose stream demand, as PRV-1 Pressure Reducing Valve: The Tyco®Model PRV-1 Pressure Re- applicable. The sprinkler demand or ducing Valve must be installed with the hose stream demand must be at least ❑The PRV-1 may be installed verti- flow arrow located on the Diaphragm 50 GPM (190 LPM) for 2 to 6 inch cally or horizontally and in any orien- Cover pointing in the intended direc- (DN50 to DN150) valves and at least tation without affecting its operating tion of flow.Installation dimensions are 100 GPM (380 LPM) for 8 inch efficiency. When planning the posi- provided in Figures 5 and 6. (DN200) valves. tioning of the PRV-1, it is recom- mended that consideration be given Before the PRV-1 is installed, pipe There is no need to vent any trapped to the viewing of the pressure lines should be flushed of all chips, air from the Diaphragm Chamber. gauges. Consideration should also scale and foreign matter.Care must be Filling The System: be given to positioning the PRV-1 so exercised to assure that the trim is not that the diaphragm cover is facing damaged during installation. Do Not Step 1. Verify that downstream drain up.With the cover facing up,internal Lift The Valve By Its Trim. valves are closed and that there are no access is more easily achieved. leaks. NOTES Step 2.Partially open a valve or valves ❑The PRV-1 must be in an area that The inlet and outlet connections must at the end of the system (e.g., an fin- is easily accessible for maintenance be made based on the direction of flow not subject to freezing spector's test connection on a wet pipe purposes, 1 g arrow provided on the handhole cover. system)to allow trapped air to escape temperatures, and not subject to The valve cannot operate if connected when filling the system. physical damage. backwards. Step 3. Slowly and partially open the The valve is designed forfresh water Do not alter the trim. Altering the trim water supply control valve feeding the service. When corrosive atmos- may render the valve ineffective and PRV-1. pheres and/or contaminated water impair the system operation. supplies are present, it is the Step 4. After the system fills with owner's responsibility to verify com- water, close the valve or valves that patibility with the pressure reducing had been partially opened in Step 2. valve, pilot valve, and trim. Step 5. Completely open the main ❑The difference between the water water supply control valve feeding the supply pressure and the desired out- PRV-1. let (downstream) pressure must be Downstream Pressure Adjustment: 25 psi (1,7 bar)or greater per its FM Steps 1 through 12 are to be per- Approval or 50 psi (3,4 bar) or formed when placing the Model PRV-1 Step 6. Remove the Tamper Cap from greater per its UL Listing.The differ- Pressure Reducing Valve in service. the Pilot Valve by first loosening its set ential maintains accuracy control of screw and then unscrewing the Tam- the discharging pressure over the WARNING per Cap. full rated flowing range. Downstream pressure adjustment is only to be performed by experi- Step 7. Open the "flow test valve" to ❑Cavitation may occur when the inlet enced personnel who understand simulate either the desired sprinkler pressure is greater than twice the the impact of adjusting the down- demand or hose stream demand. "set pressure". For this case, the stream pressure and who take full pressure should be reduced in two responsibility of the readjustment NOTE steps by using two PRV-1's in se- from the factory setting. The Pilot If surging flow occurs,attempt to bleed ries. Valve is provided with a Tamper Cap, trapped air from the system via the which upon removal for purposes of inspector's test valve and any other When reducing pressure for a sprin- downstream adjustment will provide valve that can vent trapped air. khan system,a relief valve of not less than 1/2 inch (DN15)in size shall be an indication that the PRV-1 may have Step 8. Loosen the locknut on the ad- located downstream of the PRV-1. been altered from the factory setting. justing screw of the Pilot Valve. The relief valve shall be set at a Adjustment of the Needle Valve is Step 9. Turn the adjusting screw pressure equal to the lowest pres- factory set and must not be altered. clockwise to increase outlet pressure sure rated component downstream The Needle Valve is provided with a or counterclockwise to decrease outlet of the PRV-1. NOTE:FM Approval is tamper indication, which upon removal pressure. based on the use of the 112 inch, for purposes of any adjustment will Ste 10. After achieving the desired Watts Regulator, Series 530C Pres- provide an indication that the PRV-1 performance, tighten the locknut on sure Relief Valve. may have been altered from the fac- ❑When reducing pressure for a sprin- tory setting. the adjusting screw. kler system, a listed indicating valve Step 11. Close the "flow test valve". shall be provided on the inlet side of NOTES Observe the outlet pressure gauge the PRV-1. Per the requirements of NFPA 13, a and compare to the required "set means shall be provided downstream pressure". If the required "set Ares- ❑When reducing pressure for a sprin- of the PRV-1 to simulate the sprinkler sure" is not achieved, repeat Step 8 kler system, means shall be pro- system demand. In the case of hose and proceed accordingly. vided downstream of the PRV-1 to stations, the opening of a hose valve Step 12. Replace the Tamper Cap and first be obtained from the proper tighten its set screw. authorities and all personnel who may The pressure reducing valve is now be affected by this decision must be set for service. notified. The Model PRV-1 Pressure Reducing Products manufactured by Tyco Fire& NOTES Valve requires no lubrication, packing Building Products (TFBP) are war- Due to the spring tolerance within the or preventative maintenance; how- ranted solely to the original Buyer for Pilot Valve, it may be necessary to ever, replacement of the diaphragm ten (10)years against defects in mate- alternate back and forth between re- every five years is recommended. rial and workmanship when paid for sidual and static conditions to achieve Flow Tests. Flow tests per NFPA are and properly installed and maintained the desired "set pressure"for both re- required every five years, at which under normal use and service. This sidual and static conditions. point the outlet pressure is compared warranty will expire ten (10) years After any downstream pressure ad- to previous tests. If necessary the from date of shipment by TFBP. No justment, the following items are to be PRV-1 can be readjusted following the warranty is given for products or com- recorded on a tag attached to the Placing The Valve In Service section. ponents manufactured by companies valve: If the desired pressure cannot be not affiliated by ownership with TFBP - Valve installation location achieved, the Diaphragm and/or Pilot or for products and components which Valve should be replaced. have been subject to misuse,improper -Inlet static pressure Diaphragm Replacement. Prior to re- installation, corrosion, or which have not been installed, maintained, modi- - Outlet static pressure placing the Diaphragm, the PRV-1 fied or repaired in accordance with ap- -Inlet residual pressure must be taken out of service and com- plicable Standards of the National Fire pletely drained. With reference to Fig- Protection Association, and/or the - Outlet residual pressure ure 3, the Diaphragm Tab is oriented standards of any other Authorities -Intended outlet flow perpendicular to the outlet flow. When Having Jurisdiction. Materials found reinstalling the Diaphragm Cover, the by TFBP to be defective shall be either The tag is not to be removed until after Diaphragm Cover Fasteners must be repaired or replaced, at TFBP's sole the system has been accepted by the uniformly and securely tightened option. TFBP neither assumes, nor Authority Having Jurisdiction. It is rec- using a cross-draw sequence. After authorizes any person to assume for it, ommended that the tag not be re- tightening, double check to make cer- any other obligation in connection with moved even after acceptance by the tain that all of the Diaphragm Cover the sale of products or parts of prod- Authority Having Jurisdiction unless fasteners are securely tightened. ucts.TFBP shall not be responsible for another means of record keeping is pilot Valve Replacement. Prior to re- sprinkler system design errors or inac- maintained. moving the Pilot Valve, the PRV-1 curate or incomplete information sup- must be taken out of service and com- plied by Buyer or Buyer's repre- pletely drained.When installing the re- sentatives. placement Pilot Valve,the trim compo- In no event shall TFBP be liable, in nents must be replaced exactly as they contract, tort, strict liability or under were. After reinstalling the Pilot Valve any other legal theory, for incidental, and before returning the PRV-1 into indirect,special or consequential dam- service, completely unscrew the Ad- ages, including but not limited to labor justing Stem of the replacement Pilot charges, regardless of whether TFBP Inspection, testing, and maintenance Valve so as to obtain a minimum outlet was informed about the possibility of must be performed in accordance with "set pressure". Then proceed to use such damages, and in no event shall the requirements of the NFPA,and any the instructions under Placing The TFBP's liability exceed an amount impairment must be immediately cor- Valve In Service section to place the equal to the sales price. rected. PRV-1 in service. The foregoing warranty is made in lieu The owner is responsible for the in- NOTES of any and all other warranties, ex- spection, testing, and maintenance of The Pilot Valve is not field repairable. press or implied, including warranties their fire protection system and de- Attempting to repair the Pilot Valve of merchantability and fitness fora a�r- vices in compliance with this docu- may render the valve ineffective and ticular purpose. ment, as well as with the applicable impair the system operation. This limited warranty sets forth the ex- standards of any authorities having ju- risdiction. The installing contractor or Completely unscrewing the Adjusting clusive remedy for claims based on product manufacturer should be con- Stem of the replacement Pilot Valve failure of or defect in products, materi- tacted relative to any questions. will help to avoid an accidental over als or components, whether the claim pressurization of the system piping is made in contract, tort, strict liability Automatic sprinkler systems should be prior to achieving the desired "set or any other legal theory. inspected,tested,and maintained by a pressure". This warranty will apply to the full ex- qualified Inspection Service in accord- ance with local requirements and/or tent permitted by law.The invalidity, in national codes. whole or part, of any portion of this warranty will not affect the remainder. NOTE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls,permission to shut down the affected fire protection systems must Thread x Thread End Connections Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve lbs. Sizes A B C D E F k 2" 7.51 1.49 7.32 6.41 8.18 2.36 15.2 (DN50) (191) (38) (186) (163) (208) (60) (6,9) 3" 11.14 1.77 8.19 7.48 9.25 3.93 30.6 DN80 283 45 208 190 235 100 13,9 Groove x Groove End Connections 0 0 F Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve lbs. E Sizes A B C D E F k 2" 7.51 1.49 7.32 6.41 8.18 2.36 15.2 (DN50) (191) (38) (186) (163) (208) (60) (6,9) Y 11.14 1.77 8.19 7.48 9.25 3.93 30.6 D (DN80) (283L__ 45 208 _190 _235 (100) 13,9 4" 13.62 4.37 8.70 7.91 9.68 4.52 45.2 C (DN100) (346) (111) (221) (201) (246) (115) (20,5) 6" 17.79 3.30 9.88 6.73 11.49 5.90 118.0 DN150 452 84 251 171 292 150 53,5 � Flange x Flange End Connections ON B Nominal Nominal Installation Dimensions in Inches and(mm) Weight A _ Valve lbs. Sizes A B C D E F k 3" 11.14 3.93 8.19 7.48 9.25 3.93 46.3 (DN80) (283) (100) (208) (190) (235) (100) (21,0) 4" 12.00 2.24 8.70 7.91 9.68 4.52 65.0 DN100 305 57 221 201 246 115 29,5 6" 15.98 5.59 9.88 6.73 11.49 5.90 118.0 (DN150) (406) (142) (251) (171) (292) (150) (53,5) 8" 18.50 6.69 11.14 7.16 12.55 6.96 166.5 DN200 470 170 283 182 319 177 75,5 FIGURE 5 MODEL PRV-1 PRESSURE REDUCING VALVE -GLOBE STYLE INSTALLATION DIMENSIONS- Thread x Thread End Connections Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve lbs. Sizes A B C D E F G k 2" 3.54 3.18 7.32 6.41 8.18 2.40 2.40 15.9 (DN50) (90) (81) (186) (163) (208) (61) (61) (7,2) 3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 34.1 DN80 154 115 208 190 235 100 100 15,5 Groove x Groove End Connections F Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve lbs. ! Sizes A B C D E F G k E 2" 3.54 3.18 7.32 6.41 8.18 2.40 2.40 15.9 0,V_LJ (DN50) (90) (81) (186) (163) (208) (61) (61) (7,2) 3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 34.1 (DN80) (154) (115) (208) (190) (235) (100) (100) (15,5) D G 4" 6.33 4.56 8.70 7.91 9.68 4.52 4.52 44.0 C (DN100) (161) (116) (221) (201) (246) (115) (115) (19,9) 6" 8.89 6.69 9.88 6.73 11.49 5.90 5.90 89.3 DN150 226 170 251 171 292 150 150 40,5 Flange x Flange End Connections B Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve Sizes A B C D E F G lbs. ��A k 3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 35.1 (DN80) (154)_ (115) (208) (190) (235)_ (100) (100) (15,9) 4" 6.33 4.56 8.70 7.91 9.68 4.52 4.52 67.3 (DN100) (161) (116) (221) (201) (246) (115) (115) (30,5) 6" 8.89 6.69 9.88 6.73 11.49 5.90 5.90 116.2 DN150 226 170 251 171 292 150 150 52,7 FIGURE 6 MODEL PRV-I PRESSURE REDUCING VALVE -ANGLE STYLE INSTALLATION DIMENSIONS- 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 d 130 A=70 PSI INLET PRESSURE B=50 PSI INLET PRESSURE U 120 z w 110 D 100 O U) 90 w d 80 U) Z 70 O a 60 A z Li 50 U=) 40 B U) 0 30 a- w 20 J 0 10 O 0 0 25 50 75 100 125 150 175 200 225 250 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A-1 2 INCH(DN50)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A= 140 PSI INLET PRESSURE B=100 PSI INLET PRESSURE - v 120 A C=50 PSI INLET PRESSURE z w 110 100 a U) 90 B w IL 80 U) z 70 d 60 z w 50 U=) 40 cn C uJ 30 d w 20 J D 10 O 0 0 25 50 75 100 125 150 175 200 225 250 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A-2 2 INCH(DN50)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE - B=50 PSI INLET PRESSURE U 120 z w 110 Of =< 100 O (D 90 w a 80 W Z 70 D a 60 z A w 50 U=) 40 U) — B — UJ 30 a w 20 J D 10 O 0 0 50 100 150 200 250 300 350 400 450 500 550 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH B-1 3 INCH(DN80)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 U) 130 A=140 PSI INLET PRESSURE B= 100 PSI INLET PRESSURE U 120 A C=50 PSI INLET PRESSURE z w 110 100 O 90 B w a 80 z 70 a 60 z w 50 UE) 40 U) C ow 30 a w 20 J 10 O 0 0 50 100 150 200 250 300 350 400 450 500 550 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH B-2 3 INCH(DN80)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 U) 130 A=70 PSI INLET PRESSURE -- B=50 PSI INLET PRESSURE U 120 z w 110 Of =< 100 O (D 90 w a 80 W Z 70 D a O 60 A z w 50 w =) 40 B U) UJ 30 a w 20 J 10 O 0 0 100 200 300 400 500 600 700 800 900 1000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH C-1 4 INCH(DN100)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 U) 130 A U 120 z w 110 A=140 PSI INLET PRESSURE B= 100 PSI INLET PRESSURE 100 C=50 PSI INLET PRESSURE O B (j) 90 w a 80 z 70 a 60 z w 50 40 C ow 30 a w 20 J 10 O 0 0 100 200 300 400 500 600 700 800 900 1000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH C-2 4 INCH(DN100)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 U) 130 A=70 PSI INLET PRESSURE -- B=50 PSI INLET PRESSURE U 120 z w 110 Of =< 100 O (D 90 w a 80 W Z 70 D a 60 z A w 50 U=) 40 U B UJ 30 a w 20 J D 10 O 0 0 250 500 750 1000 1250 1500 1750 2000 2250 2500 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH D-1 6 INCH(DN150)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 130 A=140 PSI INLET PRESSURE B= 100 PSI INLET PRESSURE U 120 A C=50 PSI INLET PRESSURE z w 110 100 O 90 B w a 80 z 70 a 60 z w 50 UE) 40 U) C ow 30 a w 20 w 10 O 0 0 250 500 750 1000 1250 1500 1750 2000 2250 2500 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH D-2 6 INCH(DN150)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE - B=50 PSI INLET PRESSURE U 120 z w 110 Of =< 100 O (D 90 w a 80 W Z 70 D A a 60 z w 50 U=) 40 B U) LU 30 a w 20 J 10 O 0 0 500 1000 1500 2000 2500 3000 3500 4000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH E-1 8 INCH(DN200)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference only.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 U) 130 A A=140 PSI INLET PRESSURE - B= 100 PSI INLET PRESSURE U 120 C=50 PSI INLET PRESSURE z w 110 100 O 0 90 B Of w a 80 z 70 a 60 z w 50 40 C U) ow 30 a w 20 J 10 O 0 0 500 1000 1500 2000 2500 3000 3500 4000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH E-2 8 INCH(DN200)PRESSURE REDUCING VALVE OUTLET PRESSURE VERSES FLOW SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) Pressure Reducing Valve: Specify: Globe Type, (specify size), 125 psi Outlet "Set Pressure"with(T x T, G x G, or F x F) Connection, P/N (specify from below). Pressure Reducing Valve: P/N's for GLOBE BODY STYLE Specify: (Globe or Angle)Type, (spec- AVAILABLE IN AMERICAS ify size), 125 psi Outlet"Set Pressure" with (specify) Connection (and for 2 Inch T x T flanged valves specify flange drilling), NPT................ P/N 52-570-8-060 P/N (specify from complete listing on 2 Inch G x G Page 16). 2.37 inch(60,3 mm) Groove O.D........... P/N 52-570-8-920 ❑Valve Type & Size (Globe, 2, 3, 4, 6, or 8 Inch) 3 Inch G x G (Angle, 2, 3, 4, or 6 Inch 3.50 inch(88,9 mm) Groove O.D.. ........ P/N 52-570-8-922 1 125 psi Outlet"Set Pressure" Pressure 4 Inch G x G 11 Connection Type Groove inch.D. .. mm) Threaded, Grooved, Flanged) Groove O.D. ......... P/N 52-570-8-923 ( g ) 4 Inch F x F For threaded, specify NPT or ISO ANSI Flange......... P/N 52-570-8-023 6 Inch G x G For grooved, specify O.D. Pipe Size 6.62 inch(168,3 mm) -2 inch (DN50): Groove O.D. ......... P/N 52-570-8-925 2,88 inch (60,3 mm) O.D. 6 Inch F x F ANSI Flange. ........ P/N 52-570-8-025 - 3 Inch (DN80): 8 Inch F x F 3.50 inch (88,9 mm) O.D. ANSI Flange......... P/N 52-570-8-026 -4 inch (DN100): Pressure Relief Valve: 4.50 inch (114,3 mm) O.D. Specify: 1/2 inch (DN15) Watts Regu- -6 inch (DN150): lator, Series 530C Pressure Relief 6.62 inch (168,3 mm) O.D. or Valve for use downstream of a PRV-1 6.50 inch (165,1 mm) O.D. being used for reducing pressure in -8 inch (DN200): sprinkler system, P/N 92-570-2-208. 8.62 inch (219,1 mm) O.D. Replacement Valve Parts: For flanged, specify flange drilling Specify: (description) for use with per (specify) size Model PRV-1 Pressure Reducing Valve, P/N (see Figure 3). -ANSI B16-1 (Class 125) - ISO 7005-2 (PN16) - ISO 7005-2 (PN10), 8 inch valve only -JIS B2210 (10K) -AS 2129 (Table E) NOTES Refer to Table A for flange drilling di- mensional specifications. Pressure Relief Valve: Specify: 1/2 inch (DN15) Watts Regu- lator, Series 530C Pressure Relief Valve for use downstream of a PRV-1 being used for reducing pressure in sprinkler system, P/N 92-570-2-208. Replacement Valve Parts: Specify: (description) for use with (specify) size Model PRV-1 Pressure Reducing Valve, P/N (see Figure 3). P/N's for GLOBE BODY STYLE P/N's for ANGLE BODY STYLE 2 Inch TxT 2 Inch TxT NPT................ P/N 52-570-8-060 NPT................ P/N 52-571-8-060 2 Inch TxT 2 Inch TxT ISO ................ P/N 52-570-8-160 ISO................ P/N 52-571-8-160 2 Inch GxG 2 Inch GxG 2.37 inch(60,3 mm) 2.37 inch(60,3 mm) Groove O.D........... P/N 52-570-8-920 Groove O.D.. ........ P/N 52-571-8-920 3 Inch TxT 3 Inch TxT NPT................ P/N 52-570-8-062 NPT................ P/N 52-571-8-062 3 Inch TxT 3 Inch TxT ISO ................ P/N 52-570-8-162 ISO................ P/N 52-571-8-162 3 Inch GxG 3 Inch GxG 3.50 inch(88,9 mm) 3.50 inch(88,9 mm) Groove O.D.. ........ P/N 52-570-8-922 Groove O.D.......... P/N 52-571-8-922 3 Inch FxF 3 Inch FxF ANSI Flange......... P/N 52-570-8-022 ANSI Flange......... P/N 52-571-8-022 3 Inch FxF 3 Inch FxF ISO(PN16)Flange.... P/N 52-570-8-112 ISO(PN16)Flange ... P/N 52-571-8-112 3 Inch FxF 3 Inch FxF JIS Flange........... P/N 52-570-8-722 JIS Flange .......... P/N 52-571-8-722 3 Inch FxF 3 Inch FxF AS Flange........... P/N 52-570-8-522 AS Flange........... P/N 52-571-8-522 4 Inch GxG 4 Inch GxG 4.50 inch(114,3 mm) 4.50 inch(114,3 mm) Groove O.D. ......... P/N 52-570-8-923 Groove O.D. ........ P/N 52-571-8-923 4 Inch FxF 4 Inch FxF ANSI Flange......... P/N 52-570-8-023 ANSI Flange ........ PIN 52-571-8-023 4 Inch FxF 4 Inch FxF ISO(PN16)Flange.... P/N 52-570-8-113 ISO(PN16)Flange ... P/N 52-571-8-113 4 Inch F x F 4 Inch F x F JIS Flange........... P/N 52-570-8-723 JIS Flange .......... P/N 52-571-8-723 4 Inch FxF 4 Inch FxF AS Flange........... P/N 52-570-8-523 AS Flange........... P/N 52-571-8-523 6 Inch GxG 6 Inch GxG 6.62 inch(168,3 mm) 6.62 inch(168,3 mm) Groove O.D. ......... P/N 52-570-8-925 Groove O.D. ........ P/N 52-571-8-925 6 Inch GxG 6 Inch GxG 6.50 inch(165,1 mm) 6.50 inch(165,1 mm) Groove O.D. ......... P/N 52-570-8-945 Groove O.D. ........ P/N 52-571-8-945 6 Inch F x F 6 Inch F x F ANSI Flange......... P/N 52-570-8-025 ANSI Flange ........ P/N 52-571-8-025 6 Inch FxF 6 Inch FxF ISO(PN16)Flange.... P/N 52-570-8-115 ISO(PN16)Flange ... P/N 52-571-8-115 6 Inch FxF 6 Inch FxF JIS Flange........... P/N 52-570-8-725 JIS Flange .......... P/N 52-571-8-725 6 Inch F x F 6 Inch F x F AS Flange........... P/N 52-570-8-525 AS Flange........... P/N 52-571-8-525 8 Inch F x F ANSI Flange......... P/N 52-570-8-026 8 Inch FxF ISO(PN10)Flange.... P/N 52-570-8-116 8 Inch FxF ISO(PN16)Flange.... P/N 52-570-8-126 8 Inch FxF JIS Flange........... P/N 52-570-8-726 8 Inch F x F AS Flange........... P/N 52-570-8-526 ©2007 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 AHEAD OF • 8/3/2010 300 PSI WWP Bronze Ball Valves Dezincification Fire Protection Valve • Two-Piece Body • Chrome Plated Ball • Resistant Blowout-Proof Stem • Reinforced PTFE Seats 300 PSI/20.7 Bar Non-Shock Cold Water CONFORMS TO MSS SP-110 • UL LISTEDt • FM APPROVEDt MATERIAL LIST lip PART SPECIFICATION 1. Handle Nut Zinc Plated Steel KT-585-70-UL 2. Handle Zinc Plated Steel Clear Chromate '/d'-1"Full Port with Plastisol Grip Threaded 3. Threaded Pack Gland Brass ASTM B16 4. Packing PTFE KT-580-70-UL 5. Stem Silicon Bronze ASTM B371 Alloy C69430 11/4"-3"Standard Port or ASTM B99 Alloy C65100 Threaded 6. Thrust Washer Reinforced PTFE 7. Ball Brass ASTM B124 Alloy C37700 or ASTM B Alloy C36000 with Hard Chrome Plate C 8. Seat Ring(2) Reinforced PTFE 9. Body Cast Red Bronze ASTM B584 Alloy C84400 10. Body End Piece Cast Red Bronze ASTM B584 Alloy C84400 s 1/4"and 1/8"size only has A304 stainless steel grounding washer. 2 5 I 4 6 B 7 s A 8 10 KT-585-70-UL Full Port DIMENSIONS-WEIGHTS-QUANTITIES NPT x NPT KT-585-70-UL Dimensions Size A B C D Port Weight Box Master KT-580-70-UL In. mm. In. mm. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty. Standard Port NPT x NPT 1/4 8 2.00 51 1.75 44 5.00 127 .38 10 .45 .20 10 100 3/8 10 2.00 51 1.75 44 5.00 127 .38 10 .45 .20 10 100 1/2 15 2.44 62 1.88 48 5.19 132 .50 13 .64 .29 10 100 3/4 20 2.94 75 2.25 57 6.25 159 .75 19 1.33 .60 5 50 1 25 3.34 85 2.38 59 6.44 164 1.00 25 1.79 .81 5 20 KT-580-70-UL Dimensions Size A B C D Port Weight Box Master In. mm. In. mm. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty. 11/4 32 3.94 100 2.63 67 6.75 171 1.00 25 2.17 .99 5 20 11/2 40 4.31 110 3.00 76 8.91 228 1.25 32 3.27 1.49 5 20 2 50 4.63 117 3.25 83 9.06 230 1.50 38 5.09 2.31 5 10 21/2 65 5.84 148 3.53 90 9.66 245 2.00 51 8.25 3.79 2 6 3 80 7.09 202 4.41 112 11.53 293 2.50 64 15.65 7.11 1 4 t UL Listed,FM Approved for trim and drain use(UL Subject 285)-Sizes 1/4"thru 2". FM U� APPROVED NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227 m TECH SERVICES PH:1.888.446.4226•FAX:1.888.336.4226•INTERNATIONAL OFFICE PH:+1.574.295.3327•FAX:+1.574.295.3455 www.nibco.com NIBCO' vvww.nibco.com AHEAD OF • 200 PSI WWP Bronze Check Valves Dezincification Fire Protection Valve * Horizontal Swing a Rubber Disc Resistant 200 PSI/13.8 Bar Non-Shock Cold Water CONFORMS TO MSS SP-80 MATERIAL LIST PART SPECIFICATION KT-403-W 1. Bonnet Bronze ASTM B62 Threaded or B584 Alloy C84400 2. Body Bronze ASTM B62 or B584 Alloy C84400 3. Hinge Pin Bronze ASTM B140 Alloy C31400 or B134 Alloy C23000 4. Disc Hanger Bronze ASTM B62 5. Hanger Nut Bronze ASTM B97 Alloy C65500 or Brass ASTM B16 6. Disc Holder Bronze ASTM B62 7. Seat Disc Nitrile(W) 1 PTFE(Y)# a 8. Seat Disc Nut Brass ASTM B16 s or B97 Alloy C65500 9. Hinge Pin Plug Bronze ASTM B140 Alloy C32000 (Not Shown) I B *10. Seat Disc Washer Stainless Steel *Sizes 3/a",1",11/4"and 11/2"only. 8 t 21/?and 3"size only. 10 A DIMENSIONS-WEIGHTS-QUANTITIES KT-403-W Dimensions NPTx NPT Size A B Weight Box Master. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty. 112 15 2.44 62 1.69 43 .58 .26 10 50 3/4 20 2.94 75 1.88 48 .92 .42 10 50 1 25 3.56 90 2.31 59 1.55 .70 5 30 11/4 32 4.19 106 2.69 68 2.32 1.05 5 20 11/2 40 4.50 114 2.94 75 3.00 1.36 2 10 2 50 5.25 133 3.81 97 4.87 2.21 2 10 2112 65 8.00 203 5.06 129 11.48 5.22 1 5 3 80 9.25 235 6.25 159 17.53 7.97 1 4 Sizes 21/2"and 3"supplied as T-433-Y with PTFE seat disc. NIBCO check valves may be installed in both horizontal and vertical lines with upward flow or in any intermediate position. WARNING-Valve must be installed downstream of receiver tank if used in line with reciprocating air compressor. ® NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227 TECH SERVICES PH:1.888.446.4226•FAX:1.888.336.4226•INTFRNATIONAL OFFICE PH:+1.574.295.3327•FAX:+1.574.295.3455 www.nibco.com T E TAN D�R AI�N FM !� OF USA PATENT#4741361 AND OTHER PATENTS PENDIN ■ ■ Visit us on the Internet at ■ ■ ■ ■ SMO 10/00 MOMMM11- �� FM MODEL 1000 300 PSI D 3 ill 1 1 IN, 1 1/211 211 PLAN VIEW FRONT VIEW/VERTICAL INSTALLATION 1 � A 1 FROM BRANCH I � GAUGE INLET B I/ PROVIDED TO DRAIN QO C :-��OF'] 1 STREET EL DRAIN O FRONT VIEW/HORIZONTAL INSTALLATION I TO DRAIN STRET ' E I OR PIPE L TEST TO DRAIN F RIGHT HAND/STRAIGHT INSTALLATION 4 H TO DRAIN z IG U ORIFICE SIZE J AVAILABLE - 3/8, 7/16, 1/2, 17/32, ELO(5/8)*, ESFR(3/4)* J DIMENSIONS- INCHES SIZE A B C D E F G H MATERIAL LIST PART: MATERIAL: HANDLE STEEL STEM ROD BRASS BALL C.P.BRONZE BODY BRONZE VALVE SEAT IMPREGNATED TEFLON INDICATOR PLATE STEEL HANDLE LOCK SPRING STEEL • D: FM APPROVEBE ELO/ESFR IS UL LISTED UL LISTING EX4019 JOB NAME: ARCHITECT: ENGINEER: MADE IN U.S.A. CONTRACTOR: FOR SMALL PIPE VSR-S ePOTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL,ULC,CSFM Listed and NYMEA Accepted Service Pressure: Up to 300 PSI(20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive l OmAmps min.at 24 VDC Conduit Entrances:Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic,copper and schedule 40 iron pipe. Fits pipe sizes-1"(25mm), 1 1/4"(32mm), 1 1/2"(38mm) and 2"(50mm) Stock No. 1144440 Note: 12 paddles are furnished with each unit,one for each pipe size of threaded and sweat TEE,one for 1"(25mm)CPVC, one for 1"(25mm)CPVC(Central),one for 1"threaded Nibco CPVC,and one for 1 1/2"(38mm)threaded(Japan). AR N I N Environmental Specifications: • NEMA-4/I1`54 Rated enclosure suitable for indoor or outdoor Installation must be perfomed by qualified personnel and in use with factory installed gasket and die-cast housing when used accordance with all national and local codes and ordinances. with appropriate conduit fitting. Shock hazard. Disconnect power source before servicing. • Temperature range:40°F to 120°F,(4,5°C to 49°C)UL Serious injury or death could result. Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NFPA-13 injury or death could result. One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional:Cover Tamper Switch Kit,Stock No.0090148 (See Fig.7 for terminations) Replaceable Components:Retard/Switch Assembly,stock no.1029030 The Model VSR-S is a vane type waterflow switch for use on wet Installation sprinkler systems that use 1"(25mm), 11/4"(32mm),1'h"(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On (50mm)pipe size.The unit may also be used as a sectional waterflow horizontal pipe they should be installed on the top side of the pipe where detector on large systems. they will be accessible.The units should not be installed within 6"(15cm) The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the waterflow. an adjustable, instantly recycling pneumatic retard. The switches are Select the proper paddle for the pipe size and type of TEE used see Fig. actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The unit has a 1"NPT bushing downstream of the device.The flow condition must exist for a period of for threading into a non-corrosive TEE.See Fig.2 for proper TEE size, time necessary to overcome the selected retard period. type and installation.Use no more than three wraps of teflon tape. Enclosure Screw the device into the TEE fitting as shown in Fig.2.Care must be The VSR-S switches and retard device are enclosed in a general purpose, taken to properly orient the device for the direction of waterflow. die-cast housing.The cover is held in place with two tamper resistant The vane must not rub the inside of the TEE or bind in any way.The screws which require a special key for removal.A field installable cover stem should move freely when operated by hand. tamper switch is available as an option which may be used to indicate The device can also be used in copper or plastic pipe installations with unauthorized removal of the cover. See bulletin number 5401103 for the proper adapters so that the specified TEE fitting may be installed installation instructions of this switch. on the pipe run. Note:Do not leave cover off for an extended period of time. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5401206-REV G PAGE 1 OF 3 12/08 E) POTTER FOR SMALL PIPE VSR—S VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig.1 Fig.2 Retard Adjustment DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME FLOW 4,31 AppROx. (1❑/16' The time delay is factory set at 30 f 10 seconds. COVER TAMPER SWITCH The delay can be adjusted by rotating the retard — adjustment knob from 0 to the max setting(60- \ DEPTH 90 seconds).The time delay should be set at the minimum required to prevent false alarms. Screw the device into the tee fitting as shown. Care must be taken to properly orient the DIRECTION OF MOUNT SO device for the direction of waterflow.On sweat WATER FLOW ARROW ON BUSHING POINTS tees,no threaded bushings,inserts,or adapters IN DIRECTION F� are permitted,unless they comply with the dimensions listed in the chart below. °Wn»,3,-3' THREADED Important-The depth to the inside bottom of FITTING ON the tee should have the following dimensions: ALL ES A WA R N I N G RUN OF THE E T TEE Approximate Depth Requirement MAY BE There are 12 paddles famished with each unit, THREADED OR Tee Size Threaded Sweat CPVC SWEAT PIPE One for each size of threaded,sweat or plastic —DIRECTION OF r.x V x 1" 21/16" 13/4" 2 7/16" \� TEE as described in Fig.2.These paddles have WATERFLO W 1 1/4"x 1 1/4"x 1" 2 7/16" 2 7/16" N/A raised lettering that shows the pipe size and type DWO#802�QA 1 1/2"x 1 1/2"x 1" 2 11/16" 2 1/4" N/A of TEE that they are to be used with.The proper 2"x 2"x i" 3 3/16' 2 3/4" N/A paddlemustbeused.Thepaddlemustbeproperly Shown with optional Cover Tamper Switch Kit. attached(see drawing)and the screw that holds AWARNING the paddle must be securely tightened Do not use more than three wraps of teflon tape. Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring (Shown with cover in place) WAR N I N G v An uninsulated section of a single conductor should not be looped s around the terminal and serve as two separate connections.The wire + + + coo DWCa 923.3 must be severed,thereby providing supervision of the connection in 0 the event that the wire become dislodged from under the terminal. G N.O. N.G. Failure to sever the wire may render the device inoperable risking (WxT) (RED) (BL K) severe property damage and loss of life. DWG#8810018-2 Fig.4 Typical Electrical Connections Fig.5 Fig.6 To remove knockouts: Breakoutthinsectionofcoverwhenwmng ® z NEUTRAL DC OR Place screwdriver at edge of both switches from one conduit entrance. o BELL NEUTRAL AC g z knockouts,not in the center. p POSITIVE DC OR 3 HOTAC O i o I z WATERFLOW ZONE ON ® o FIRE PANEL 0 Notes: 1. The Model VSR-S has two switches,one can be used to operate a central station,proprietary or remote signaling unit,while the other is used to operate a local audible or visual annunciator. 0 2. For supervised circuits see"Switch Terminal Connections"drawing W and caution note(Fig.3). PRINTED IN USA MFG.#5401206-REV G PAGE 2 OF 3 12/08 FOR SMALL PIPE VSR-S ePOTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Testing Removal The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should associated protective monitoring system should be in accordance with be shut tight and the system completely drained before waterflow applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced. jurisdiction(manufacturer recommends quarterly or more frequently.) • Turn off electrical power to the detector,then disconnect wiring. An inspector's test valve(usually located at die end ofthe most remote branch • Use a wrench on the flats of the bushing.Turn the switch line)should always be used for test purposes.If there are no provisions for counterclockwise to disengage the pipe threads. testing the operation of the flow detection device on the system,application • Gently lift with your fingers,roll the vane so it will fit through the of the VSR-S is not recommended or advisable. hole while continuing to lift the waterflow detector. A minimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe. ® Please advise the person responsible for testing of the A CAUTION fire protection system that this system must be tested in accordance with the testing instructions. Waterflow switches that are monitoring wet pipe sprinkler systems Maintenance shall not be used as the sole initiating device to discharge AFFF, Inspect detectors monthly for leaks. If leaks are found, replace the deluge,or chemical suppression systems.Waterflow switches used detector.The VSR-S waterflow switch should provide years of trouble- for this application may result in unintended discharges caused free service.The retard and switch assembly are easily field replaceable. by surges,trapped air,or short retard times. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Mounting Dimensions 3.50" 5.56" GROUND SCREWS (89.0 mm) (141.2 mm) ® 2.00" (50.8 mm) i 2.34" (59.4 mm) 4.89" + + (52.3 mm) O ® FLOW ® 1"-11 1/2 NPT DWG#1206-5 PRINTED IN USA MFG.#5401206-REV G PAGE 3 OF 3 12/08 RBVS P POTTER UNIVERSAL BALL ® The Symbol of Protection VALVE SWITCH —- UL and cUL Listed,FM,CSFM Approved Dimensions: (including mounting clamps) ` Large Clamps: 6"L x 5"W x 5.2"H —" 15,2 cm L x 12,7 cm W x 13,2 cm H - Itpvs Small Clamps: 6"L x 4"W x 5.2"H 15,2 cm L x 10,2 cm W x 13,2 cm H Weight: With Large Clamps: 13.6 oz.(386,9 g.) With Small Clamps: 11.0 oz.(311,2 g.) Enclosure: Non-Corrosive Composite Material Environmental Limitations: • NEMA 4 rated enclosure when proper electrical fittings are used.(IP67) • Temperature range:40°F to 150°F(-40°C to 65°C) • Not for use in hazardous locations Housing Cover Tamper: Activated by housing cover removal US Patent No.6,945,509 (Stock No. 1000035 only) Contact Ratings: SPDT Contacts: l0A at 125/250 VAC RBVS Stock No. 1000040(w/o Cover Tamper) 2A at 30 VDC RBVS-T Stock No. 1000035(w/Cover Tamper) SPDT Cover Tamper: 3A at 250 VAC General Installation On Lever Handle(See Fig.2) The Model RBVS is designed to monitor the fully open position of a ball valve 1. Select clamps and clamping bolts based upon pipe/valve size,see Table 1. installed in a sprinkler system.The unit will fit on most ball valves installed on 2. Insert rubber clamp grippers into clamps,see Fig.2. back-flow-preventers and alarm trim lines of dry,alarm,and deluge sprinkler 3. Place one clamp on top of pipe/ball valve near the valve handle and valves.The switch operates if the ball valve handle is moved from the open insert clamping bolts through it. position.However,the switch does not track the position of the handle or ball. 4. Place other clamp over clamping bolts from beneath the installation and When the ball valve handle is in the open position,a spring-loaded switch button thread hex nuts onto the clamping bolts,but do not fully tighten,(be sure will contact the valve handle.When the handle is moved from the open position, hex nuts seat properly in clamp hex recesses).(NOTE:Some installations this switch button extends to the tripped position,and the RBVS contacts change may require one of the mounting bolts to be inserted from the bottom of state,thereby opening or closing a circuit.A cover tamper switch is available and the brackets and then trimmed to allow the extension bracket to clear. is activated by the removal of the RBVS housing cover.If an attempt is made See Fig.4) to remove the RBVS by the removal of the mounting brackets,the unit will be 5. Attach extension bracket(if necessary to use for positioning)to top clamp set into the tripped mode by this action. using'/4-20 X 3/d'Hex bolt and washer,but do not fully tighten. The RBVS can be mounted to the hex portion of the ball valve or back-flow- 6. Attach"L"bracket(RBVS switch enclosure is loosely attached to"L" preventer or to the adjoiningpipe viatwo clamps.The RBVS is shippedwith two bracket)to extension bracket using'/4-20 X 3/4"Hex bolt and washer,but sets of mounting clamps to accommodate various pipe and valve sizes,refer to do not fully tighten. Table 1.An"L"shaped and offset bracket for mounting the switch enclosure and 7. Be sure ball valve is in the fully open position. 8. Slide loosely assembled RBVS switch enclosure to a position that permits an extension bracket add to the mounting flexibility of the RBVS.See"Typical the switch button to contact the valve handle approximately V from its Mounting Diagram"and"Installation and Operation"on following page. inside end.See Fig.1 for approximate location.Cut and remove the plastic Testing coating from the ball valve handle to allow the RBVS switch button to The RBVS and its associated protective monitoring system should be tested contact(and be activated by)the metal of the handle. in accordance with applicable NFPA codes and standards and/or the authority 9. Tighten clamping screws alternately to an eventual 30 in-lbs.(minimum) having jurisdiction(manufacturer recommends quarterly or more frequently). of torque. 10. Maintain position of switch enclosure over valve handle and secure bolt Fig.1 Internal Components that holds the extension bracket to the clamping assembly. It may be NORMALLY OPEN necessary to close valve to access this bolt. 11. Position"L"bracket so that it contacts the back edge of the valve handle,and NORMALLY CLOSED secure its bolt.It may be necessary to close valve to access this bolt. COMMON 12. With the actuator fully retracted,position RBVS switch enclosure to contact the valve handle squarely,see Fig. 1. STRAIN RELIEF ® ® 13. With RBVS switch enclosure held squarely in contact with valve handle, _ SWITCH BUTTON securely tighten the two tamper resistant screws on the backside of the COVER B RED - N.O. LOCATION enclosure. TAMPER WHITE - COM ON HANDLE 14. Close and open the valve to verify operation.The actuator should easily o retract when the valve handle is in the open position. 15. Fully open the valve. MOUNT So SWITCH BUTTON PLASTIC COATING pp 16. Remove the cover and wire main switch and tamper switch if applicable. IS APPROX. i" FROM REMOVED FROM Carefully route tamper switch wires through strain relief channel in switch HANDLE INSIDE END BALL VALVE HANDLE enclosure.Fully seat the wires into the bottom of the channel.See Fig.1. IN SWITCH BUTTON 17. Replace RBVS Switch enclosure cover and securely tighten cover Screw. DWG #1086-i CONTACT AREA eP Y 5" Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5401086-REV U PAGE 1 OF 2 5/08 RBVS (E,) POTTER UNIVERSAL BALL The Symbol of Protection VALVE SWITCH Fig.2 Typical Mounting Diagram Table 1 Clamp Sizing LENGTH Pipe Valve/Size Clamp Clamping Bolts 6" SWITCH 1/211 to 3/411(12,5 to 19mm) Small 10-32 x 2 1/2 ENCLOSUAK 111 to 2"(25 to 50mm) Large 1/4-20 x 4" "L" BRAC EIGHT Switch Terminal Connections,Clamping Plate Terminal ED-EXT. BRAC 5.2•'(IF NECESI tclo� o A CAUTION El— CLAMPAnuninsulatedsectionofsingleconductor should not be looped around the terminal and serve as two seperate connections.The CLAMP oJ�� "WO#921-3 wire must be severed,thereby providing GRIPPERS supervision of the connection in the event that the wire becomes dislodged from DWG #1086-2 5° (LARGE) under the terminal. Typical Electrical Connections LOCAL CIRCUIT TRANSFORMER OR BATTERY POWER STYLE D (CLASS A) SUPERVISED LOOP STYLE B (CLASS B) SUPERVISED CIRCUIT N.C. SIGNALING COM. COM. TO N.C. N.O. DEVICE N.O. y N.O. CONTROL CON. N 0 END-OF-LINE RESISTOR N.C!/&--\ N.C. /\ UNIT DWG. #1066-4 Tamper Switch Connections Fig.3 COVER TAMPER & RBVS CONNECTED COVER TAMPER & RBVS WIRED SWITCH ENCLOSURE TO THE SAME ZONE ON THE FACP TO SEPERATE ZONES COVER COM. N.O.COM. D- TAMPER OFFSET BRACKET COM. N.O. COM. FACP COVER EOIR N.C. TAMPER FACP EOLR FAC EOLR N.O. DWG.#1086-5 Installation on Tee Handle(See Fig.3) 9 1. Select clamps and clamping bolts based upon pipe/valve size,see Table 1. BRACKET 2. Insert rubber clamp grippers into clamps,See Fig.3. 3. Place one clamp on top of pipe/ball valve near the valve handle and C—PS insert clamping bolts through it. 4. Place other clamp over clamping bolts from beneath the installation ARP ERS DWC#IG 6-3 and thread hex nuts onto the clamping bolts,but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses). 5. Loosely attach "L" bracket to the "offset" bracket and "offset" bracket to the RBVS housing. Fig.4 6. Be sure ball valve is in the fully open position. 7. Slide loosely assembled RBVS switch enclosure to a position that RBVS permits the switch button to contact the valve handle approximately , . 1/2"from the end of the handle.Cut and remove the plastic coating from the ball valve handle to allow the RBVS switch button to contact (and be activated by)the metal of the handle. 8. Tighten clamping screws alternately and''/4-20 X3/,"bolt to 30 in-lbs. (minimum)of torque. SOME INSTALLATIONS MAY 9. With the valve handle fully open, slide the RBVS housing down CAUSE INTERFERENCE BETWEEN IN BOLT until the switch operates plus 1/8 inch.Tighten the screws holding OFFSET BRACK ET.INSTA LL BOLT the RBVS to the"offset"bracket. FROM BOTTOM AND TRIMAS�i PIPE 10.Remove the RBVS switch enclosure cover. NEEDED TO CORRECT. 11.Close and open the valve to verify operation.The actuator should easily retract up when the valve handle is in the open position. 12.Fully open the valve. 13.Wire main switch and tamper switch(if applicable).Carefully route tamper switch wires through strain relief channel in switch enclosure. DWG#1086-6 Fully seat the wires into the bottom of the channel.See Fig. 1. 14.Replace RBVS switch enclosure cover and securely tighten cover screw. PRINTED IN USA MFGN 5401086-REV U PAGE 2 OF 2 5/08 WHEELOCK (E) POTTER SERIES MT AND MT STROBE The Symbol of Protection MULTITONE ELECTRONIC SIGNALS Wheelock's MT and MT Strobe Series Multitone Electronic Signals offer a choice of eight(8)nationally and internationally recognized alerting sounds: Horn,Bell,March Time Horn,Code-3 Tone,Code-3 Horn,Slow Whoop,Siren or Hi/Lo Tone. Wheelock's Code-3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications without requiring additional coding means. With MT and MT Strobe Signals, one alarm appliance meets most of your signaling needs. Wheelock's MT and MT Strobe Signals are UL Listed, FM, CSFM and NYMEA Approved. Features • One alarm appliance with (8) eight selective signals to provide superior sound penetration for various ambient % and wall conditions with two field selectable sound output levels. I ►- • Code-3 Horn and Tone meet NFPA/ANSI/ISO temporal I pattern for standard emergency evacuation signaling. • Audible and strobe can operate from a single signaling n circuit. R • Designed to meet orexceed NFPA/ANSI Standards and E ADA Accessibility Guidelines. 110 VAC model does not meet ADA requirements. • Low current drawwith lowtemperature compensation to reduce power consumption and wiring costs. • Low cost installation via standard electrical boxes. Attractive flush or surface mounting options available. MT-24-1575w-FR SHOWN MT-121575W-FR MT 12/24 MT-24-1575W-FR* MT4-115-WH-VFR (Strobe/Horn) (Horn) (Strobe/Horn) Indoor (Strobe/Horn) Model Stock No. 1610921 Stock No. 1610914 Stock No. 1610915 Stock No. 1610216 Mounting Options** Mounting Options** Mounting Options** Mounting Options** D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,J,K,N,O,R dBA and Current Ratings Average Current Ratings(Amps) dBA Reverberant Ratings dBA Anechoic Ratings Per LIL 464 Tone @ 24VDC @ 12VDC @ 24VDC @ 12VDC @ 12 and 24VDC HI STD HI STD HI STD HI STD HI STD Horn 0.038 0.024 0.095 0.019 92 87 90 77 99 93 Bell 0.019 0.012 0.030 0.010 86 80 85 69 92 87 March Time Horn 0.038 0.024 0.095 0.019 89 84 89 74 99 93 Code-3 Horn 0.038 0.024 0.095 0.019 88 83 88 73 99 93 Code-3 Tone 0.027 0.016 0.057 0.014 85 80 84 70 95 90 Slow Whoop 0.047 0.025 0.095 0.024 90 89 89 75 99 94 Siren 0.034 0.022 0.078 0.019 89 84 1 89 75 98 93 Hi/Lo 0.020 1 0.013 0.042 0.011 86 81 1 86 71 93 88 * For outdoor installation use MTWP-2475W-FR with IOB-R backbox. ** See next page for mounting options. Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8850002-REV H PAGE 1 OF 2 2/03 WHEELOCK (E) POTTER SERIES MT AND MT STROBE The Symbol of Protection MULTITONE ELECTRONIC SIGNALS MOUNTING ACCESSORIES (D)4"SQUARE,FLUSH(BO) (E)4"SQUARE,DEEP,FLUSH(BO) (F)DOUBLE-GANG,FLUSH(BO) 1 C 0O Gp O O p 1/0 0 0 CD O 00 00 1 O i 0, MAXIMUM NUMBER OF CONDUCTORS MAXIMUM N UMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 4 d 4 4 8 8 8 4 4 4 4 4 (J)BB BACKBOX (K)WBB WEATHER RESISTANT BACKBOX (L)ISP SURFACE ADAPTER (Order Code:2830) (Order Code:2959) (Order Code:5306) Standard steel backbox with knockouts for Sturdy die-cast housing,threaded conduit hole Indoor use. interior surface mounting,concealed conduit and knockout for outdoor applications.It is mounting or semi-flush applications. It is painted to match the signal. painted to match the signal. yYf� ,-YN •�A '�f- -Yf }Y. W_ MAXIMUM ''In 39/J3 0-b f-Y. I /r:an-ao�e,e MAXIMUM NUMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 4 4 4 4 4 4 4 4 8 8 8 4 (0)RP-R RETROFIT PLATE (R)SFP SEMI-FLUSH PLATE (M)IOB BACKBOX (Order Code:5042) (Order Code:2957) (Order Code:5046) Stamped aluminum surface wall plate which For surface mounting MT products. mounts behind the basic unit and serves to cover recessed backboxes in semi-flush A—I mounting applications.It is painted to match the signal. a-Yf f-,Am O° -f MAXIMUM NUMBER OF CON DUCTORS DWG. p8850002-1 AWG.#18 AWG.#16 AWG.#14 AWG.#12 8 B 8 4 MOUNTING NOTES CAUTION:The mounting options figures show the maximum numberoffield wires(conductors)that can enterthe backbox used with each mounting option.Ifthese limits are exceeded,there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. Although the limits shown for each mounting option comply with the National Electrical code(NEC),Wheelock recommends use of the largest backbox option and the use of approved stranded field wires whenever possible,to provide additional wiring room for easy installation and minimum stress on the product from wiring. CAUTION:Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit,especially if sheathed multiconductor cable or 3/4"conduit fittings are used. 1. Mounting hardware for each mounting option is supplied. 2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance forthe installed product.When extension rings are required,conduit should enter through the backbox,not the extension ring.Use Steel City#53151(1-1/2"deep)or#53171(2-1/8"deep)extension rings(as noted in the mounting options)or equivalent with the same cut-out area. 3. When terminating field wires,do not use more lead length than required.Excess lead length could result in insufficient wiring space for the appliance. 4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.This is especially important for stiff,heavy gauge wires and wires with thick insulation or sheathing. 5. Do not pass additional wires(used for other than the appliance)through the backbox.Such additional wires could result in insufficient wiring space for the appliance. PRINTED IN USA MKT.#8850002-REV H PAGE 2 OF 2 2/03 WILKINS Model WXTP Expansion a company Water Thermal SPECIFICATION SUBMITTAL SHEET ps APPLICATION Designed for installation on potable water lines between the backflow preventer or pressure reducing valve and the water heater to protect against water thermal expansion. When system pressure increases,water enters the tank's bladder which expands into the pre-charged air chamber, keeping system pressure below the relief valve setting. STANDARDS COMPLIANCE FEATURES 0 IAPMO®Listed UPS Sizes (liters): ❑ 8 ❑ 18 ❑ 32 ❑ 50V NSF®Listed ❑ 75V ❑ 120V ❑ 165V ❑ 320V (V=vertical,free-standing) Maximum working water pressure 150 PSI MATERIALS End connections Threaded NPT ANSI B1.20.1 Outer shell High Grade Steel Precharge(adjustable) 40 PSI Coatings Epoxy finish(outer shell) Connection Brass (sizes: 8 thru 32) 5 year warranty Stainless Steel (sizes: 50V thru 320V) Bladder Butyl Rubber(FDA approved) ACCESSORIES ❑ BR4 - water pressure reducing valve ❑ TP1100A - temperature&pressure relief valve ❑ P1000A - pressure relief valve ❑ 975XL - reduced pressure backflow preventer NOTE: Model WXTP tanks are certified to NSF Standard 61 cold, but are suitable for temperatures up to 200°F. DIMENSIONS&WEIGHTS(do not include pkg.) DOCUMENT#: REVISION: WXT-WXTP 4/05 Page 1 of 2 SIZING CHART Based upon 100° F temperature rise(40° F to 140° F) X=multiple tanks required(contact your WILKINS Rep TYPICAL INSTALLATION Local codes shall govern installation requirements. Unless otherwise specified,the assembly shall be mounted on the cold water supply and at least 18"from the cold water inlet to the heater. Note: If incoming water pressure is above 40 psi, the precharge pressure of the expansion tank should be adjusted to equal the incoming water pressure,not to exceed 80 psi. MODEL WXTP INSTALLATION MODEL WXTP INSTALLATION"V"SERIES SPECIFICATIONS The Water Thermal Expansion Tank shall be IAPMO®and NSF® Listed. The outer shell shall be high grade steel with exterior coating. The bladder shall be FDA approved butyl rubber and prevent water from contact with shell interior.The assembly shall incorporate a shrader valve for adjustable air precharge and a lead free bronze system connection.The Water Thermal Expansion Tank shall be a WILKINS Model WXTP. Page 2 of 2 WILKINS a Zurn Company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 11-2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com GUARDIAN FIRE EQUIPMENT,INC. DETAIL AND SUBMITTAL SHEET MIAMI, FL Ph.800.327.6584•Fax 800.827.3869 . 111 Dept. • • Project/Location: Date: Architect/Engineer: Contractor: DAppropriate Selection Used as auxiliary connections through which the fire department can pump water to supplement existing water supplies. Provides 250 GPM flow (mini- t'/z"Nipple Plate ) O mum), per 21/2" inlet. (by others O Swivel is ° nlet Single- inlet connections incorporate astraight-thru, non-clappered de- Plug sign with female NPT outlets. soot 3" 43/a' Two and three-way inlet connections feature brass bodies (angle or straight pattern), with integral drop-clapper inlets and female NPT outlets. 21/z or 3" 3'/'or4'h"Dia. Nipple Plate (by others) Standard components, all connections: swivel o Female hose thread swivel inlets, plugs with chains and identification Inlet plate. Cast brass construction, standard. Plug/ 3/2" 7"� 6014/6015 . - IF, 6002 ❑ 6014 ❑ 6015 ❑6016 ❑6017 2vz"or 3" Tb"or Ova"Dia. Nipple— Plate 1'/z" 2'/2" 3" 2'/2" 3" (by others) 1'/z' 21/2" 2'/2" 2'/2" 2'/2" Swivel o 7„ Inlet'/z"O.D. 7"O.D. 7"O.D. 7"SO 7"SO Indentification Plate Lettering:AUTO SPKR Plug 6016/6017 Two and Three-Way Connections ..M �A�� W � A\ I �C 1g • .. B e g []6024 Back 4"x 2'/z°'x 2'/z°' 2 115/6" T/8" --- 75/8" �- � \ [] 21/2'6025 (by 6025 Bottom 4"x 21/2"x 21/2" 2 121/8" 67/8" 71/s" 75/8" Nipple (by others) Plate F-- 3'/d'Dia. ❑6026 Top 4"x 2'/2'x 21/2" 2 121/8" 67/8" 71/8" 75/8" Swivel o o 7 ❑6027 Back 6"x 2'/2°'x 2'/2" 2 115/8" 77/8" --- 75/8' Plug 3v _d'1 ❑6028 Bottom 6"x 21/2"x 21/2" 2 121/8" 75/8" 71/8" 75/8" D 06029 Top 6"x 21/2"x 2'/2" 2 121/8" 8" 9" 7" ts„ ❑6034 Back 4"x 2'/2"x 2'/2"x 2'/2" 3 173/8" 6'/8" --- 65/8" 6024-6029 ❑6037 Back 6"x 21/2"x 21/2"x 21/2" 3 173/8" 61/8' --- 65/8' ❑6038 Bottom 6"x 2'/2"x 21/2"x 21/2" 3 173/8" 75/8" 7'/s" 65/8" A C []6039 � � 6039 Top 6"x 21/2"x 21/2"x 21/2" 3 173/8" 75/8' 71/8" 65/8" g�i� B = 7 Indentification Plate Lettering 21/2"Nipple ❑AUTO SPKR [-]AUTO SPKR&STANDPIPE (by other.) Plate 3112"Dia. Swivel ❑STANDPIPE ❑DRY STANDPIPE Inlet O O g" Plug D Optional Finish:❑-B Polished Brass Threads: z3° ❑-C Rough Chrome Plated ❑NST 6034-6039 ❑-D Polished Chrome Plated ❑Other Contact factory for current listings and approvals