HomeMy WebLinkAboutF13-0020 EQUIPMENT.pdf Bulletin 006 Rev. G
Model RFC30 (SIN RA0611) °J
J ® Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Rel bi
CD
Residential Flat Concealed
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum `
design density of 0.05 gpm/ft2 with v
low GPM requirements.
Features
1. Very low water flow requirements. :
2. Cover plate attachment (Plain or Perforated) ,
with 112" (13mm)Total adjustment.
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
2. NYC MEA 258-93-E
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW positively attached and blends into the ceiling, concealing
Product Description the most dependable fire protection available,an automat-
Model RFC30, RFC43 and RFC49 Concealed Residen- is sprinkler system.
tial Sprinklers are fast response residential fusible solder The RFC30, RFC43 and RFC49 are UL Listed Residential
link automatic sprinklers. Residential sprinklers differ from Sprinklers to be installed in the residential portions of any
standard sprinklers primarily in their response time and occupancy in accordance with NFPA 13, 13R, & 13D.
water distribution patterns. The RFC30, RFC43 and RFC49 can reduce the need for
Model RFC30, RFC43 and RFC49 sprinklers discharge precise cutting of drop nipples. The threaded cover plate
water in a hemispherical pattern below the sprinkler de- assembly can be adjusted without tools to fit accurately
flector. Residential distribution patterns are higher and against the ceiling. The fire protection system need not be
generally contain a finer droplet size than standard sprin- shut down to adjust or remove the cover plate assembly.
kler patterns. Application and Installation
The combination of speed of operation and high dis- The RFC30, RFC43 and RFC49, for residential installa-
charge pattern required for residential sprinklers has dem- tions, use a 165°F(74°C)fusible solder link in a tuning fork
onstrated, in fire testing, an ability for controlling residen- style sprinkler frame with a drop-down deflector. This as-
tial fires, and thereby providing significant evacuation time sembly is recessed into the ceiling and concealed by a flat
for occupants. cover plate. The cover plate is attached to the skirt, using
The RFC30, RFC43 and RFC49 Sprinklers provide the 135°F (57°C) ordinary temperature classification solder.
best form of fire protection by combining an attractive ap- When the ceiling temperature rises, the solder holding
pearance and 1/2" (13mm) of cover adjustment for ease of the cover plate releases the cover allowing the deflector
installation. The small diameter cover plate is easily and to drop into position and exposing the sprinkler inside to
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
ceiling temperature. The subsequent operation of the sol- OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30,
der link opens the waterway and causes the deflector to RFC43 AND RFC49 CONCEALED SPRINKLERS MUST
drop into position to distribute the discharging water in a BE INSTALLED ONLY WITH 135°F RATED COVERS.
hemispherical pattern below the sprinkler deflector. Any Note:A leak tight'/2" NPT(R1/2)sprinkler joint can be ob-
adjustment of thread engagement between the cover tained with a torque of 8-18 ft-lbs (10,8- 24,4 N-m). Do not
plate and cup will assure that the drop-down deflector is tighten sprinklers over maximum recommended torque. It
properly located below the ceiling. The residential distri- may cause leakage or impairment of the sprinklers.
bution pattern contains a finer droplet size than a standard Cover assemblies provide up to 1/2" (13mm) of adjust-
sprinkler, and the pattern produces significantly higher ment. Turn the cover clockwise until the flange is in con-
wall wetting. tact with the ceiling. For the push-on/thread-off option, the
After a 25/8 inch diameter hole is cut in the ceiling, the cover assembly is pushed onto the cup and final adjust-
sprinkler is to be installed with the Model FC Wrench. ment is made by turning the cover clockwise until the skirt
When installing a sprinkler, the wrench is first positioned flange makes full contact with the ceiling. Cover removal
into the sprinkler/cup assembly and around the hexagonal requires turning in the counter-clockwise direction.
body of the sprinkler frame. The Wrench must bottom out In ceilings that have a plenum space above the sprinkler,
against the cup in order to ensure proper, safe installation. the plenum space may have neutral or negative pressur-
The sprinkler is then tightened into the pipe fitting. When ization but must not be positively pressurized. Inspect all
inserting or removing the wrench from the sprinkler/cup sprinklers after installation to ensure that the gap between
assembly, care should be taken to prevent damage to the cover plate and ceiling and the 4 slots in the cup are
the sprinkler. DO NOT WRENCH ON ANY OTHER PART all open and free from any air flow impediment.
Temperature Rating
Sprinkler Cover Plate Max.Ambient Temp.
165°F/74°C 135°F/57°C 100°F/38°C
Installation Data: RFC30 (SIN RA0611)
Thread Sprinkler Maximum Minimum Minimum Required
Size K Factor Spacing Distance to Distance between Sprinkler Discharge
inch (mm) ft. (m) Wall sprinklers Flow Press.
ft. (m) ft. (m) gpm (Lpm) psi (bar)
112"(15mm) 3.0 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 9(34.1) 9.0(0.62)
112"(15mm) 3.0 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 10(37.8) 11 (0.76)
Note: 1 bar= 100 Kpa
Installation Data: RFC43 (SIN RA0612)
Thread Sprinkler Maximum Minimum Minimum Required
Size K Factor Spacing Distance to Distance between Sprinkler Discharge
inch (mm) ft. (m) Wall sprinklers Flow Press.
ft. (m) ft. (m) gpm (Lpm) psi(bar)
1/2"(15mm) 4.3 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8(0.54)
1/2"(15mm) 4.3 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63)
'/2"(15mm) 4.3 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 9.1 (0.63)
'/2"(15mm) 4.3 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(l.21)
1/2"(15mm) 4.3 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 21 (79) 23.8(l.64)
Note: 1 bar= 100 Kpa
Installation Data: RFC49 (RA0616)
Thread Sprinkler Maximum Minimum Minimum Required
Size K Factor Spacing Distance to Distance between Sprinkler Discharge
inch (mm) ft. (m) Wall sprinklers Flow Press.
ft. (m) ft. (m) gpm (Lpm) psi (bar)
112"(15mm) 4.9 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 13(49) 7.0(0.48)
112"(15mm) 4.9 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 7.0(0.48)
112"(15mm) 4.9 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 7.0(0.48)
112"(15mm) 4.9 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 17(64.3) 12.0(0.83)
112"(15mm) 4.9 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 20(75.7) 16.7(l.14)
Note: 1 bar= 100 Kpa
FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.
2.
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprinklers engagement between the cover plate and the cup will
should be inspected quarterly and the sprinkler system assure that the drop-down deflector is properly located
maintained in accordance with NFPA 25. Do not clean below the ceiling. A plastic protective cap shall be
sprinklers with soap and water, ammonia or any other provided and factory installed inside the sprinkler cup
cleaning fluids. Remove dust by using a soft brush or gen- to protect the drop-down sprinkler deflector from dam-
tle vacuuming. Remove any sprinkler cover plate assem- age, which could occur during construction before the
bly which has been painted(other than factory applied)or cover plate is installed. Standard cover finish: [Chrome]
damaged in any way. A stock of spare sprinklers should [White] [Specialty—specify]. Residential concealed
be maintained to allow quick replacement of damaged or sprinklers shall be Reliable Model RFC30, SIN RA0611
operated sprinklers. Prior to installation, sprinklers should (Bulletin 006), Model RFC43, SIN RA0612(Bulletin 006)
be maintained in the original cartons and packaging until or Model RFC49, SIN RA0616(Bulletin 006).
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation. Ordering Information Cover Plate FinishesM
Specify: Standard Finishes
Model RFC30, RFC43 and RFC49 Residential 1. Sprinkler Model Chrome
Concealed Sprinkler Specification 2. Cover Plate Finish White Paint
3. Thread-On or Special Application
Sprinklers shall be cULus Listed low flow residential con- Push-On Feature FinishesM
cealed sprinklers with drop-down deflector and adjust- Bright Brass
able flat cover plate engineered for a minimum design Finished Bronze
density of 0.05 gpm/ft2. Sprinkler frame and deflector Black Plating
shall be of bronze frame construction having a 112" NPT Black Paint
thread. Thermal element shall consist of an approved Off White
black-painted beryllium-nickel fusible solder link with Satin Chrome
symmetric lever mechanism, maintaining a Teflon-coated (1) Other finishes and colors are
Belleville spring washer and machined brass cap water available on special order.
seal assembly containing no plastic parts. Sprinkler Consult factory for details.
K-factor shall be nominal 3.0(44), 4.3(62.4), and 4.91 Coverplate custom paint is
(70) having a 5/,6", 3/8" and 7/,6" orifice. Temperature rating semi-gloss, unless specified
otherwise.
shall be Ordinary 165°F(74°C); cover plate temperature (Z) For the perforated style cover-
rating to be 135°F(57C). Cover plate assembly shall plate, consult factory for avail-
consist of a brass cover plate and copper alloy retainer ability on these and other cus-
flange allowing a 112" cover plate adjustment. Any secure tom finishes.
I"x 1 REDUCING
TEE OR ELBOW
LAL iiu ui -_
-- -- j
28"[66.55mmJ
25 16°[58.42mm] DIA HOLE IN CEILING
L J
CUP__
2"[50.8mm] MAX.
FACE OF FITTING
TO FACE OF CEILING
DIMENSION
CEILING
I [72.70mm] MAX. I1I
COVER ADJUSTMENT 16°[4.96mm]J
FLAT COVER PLATE 316 [84.21mm] DIA. DOM
ASSEMBLY
SPRINKLER
006FGOIB
COVER PLATE: lz�2" (12.7mm] ADJUSTMENT
3.
Reliable. . . For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by a��R I The Reliable Automatic Sprinkler Co.,Inc. (D Recycled
® (800)431-1588 Sales Offices Paper
' (800)848-6051 Sales Fax Revision lines indicate updated or new data.
(914)829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.05/12 P/N 9999970261
tyro Flo w Tyco Fire
Control Products
BlazeMaster
0
FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET
TVCO F/RE PRODUCTS
451 North Cannon Avenue
Lansdale, Pennsylvania 19446
www.tyco-fire.com
TECHN ICAL SERVICES
TEL: (800) 381-9312 • FAx (800) 791-5500
Ewa: techserv@tycofp.com
No. 19-1.5
TD915
4-1.1.20
9/2001
Iso0
Y
ooa Introduction
Tyco Fire Products (TFP) BlazeMaster®CPVC pipe and the same time, they provide superior heat resistance and
fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping
automatic fire sprinkler systems.They are made from a materials used in the plumbing trade. Various adapters are
specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female
post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability.
the art additives. TFP BlazeMaster®CPVC products are Grooved adapters connect directly to grooved end valves
easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings.
Technical Data
Sizes: 3/4"-3" Manufacture Source: U.S.A.
Maximum Working Pressure: 175 psi Material:
Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5
MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and
Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80)
Technical Manual,for exact listing/approval information Color: Orange
Pi e
Nom.Pipe Size Avg.O.D.Inches Avg. I.D. Inches Wt.Lbs./Ft. Wt.H2O filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt.per Lift Lbs.
3/4" 1.050 0.874 0.17 0.43 7875 1413
V. 1.315 1.101 0.26 0.67 5040 1320
11/4" 1.660 1.394 0.42 1.07 2835 1191
11/2" 1.900 1.598 0.55 1.40 2205 1136
2" 2.375 2.003 0.86 2.20 1260 1063
2 '/2" 2.875 2.423 1.26 3.22 1215 1531
3" 3.500 2.952 1.87 4.79 720 1344
Fittings T/°_
T/O �
450 Elbow T/O_ _._. _ Reducing _. _._._ 90° Elbow
900 Elbow T/O 2 41
Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt.
80050 3/4" 40 3/8" 0.08 lb. No. Size Sch. -172 lb. 80025 '/4" 40 '/16" 0.091b.
80051 1" 40 3/8" 0.11 lb. 80032 1" x 3/4" 40 "/,6" 13/,6" 0.16 80026 1" 40 3/4" 0.14 lb.
80052 11/4" 40 3/4" 0.20 lb. 80027 11/4" 40 '/8" 0.21 lb.
80053 1 11/2" 80 1 116" 1 0.31 lb. 80028 1 1112" 80 11/16" 1 0.40 lb.
80054 2" 80 3/4" 0.56 lb. 80029 2" 80 11/4" 0.79 lb.
80055 2112" 80 3/4" 0.89 lb. 80030 21/2" 80 11/2" 1.14 lb.
80056 3" 80 1" 1.19 lb. 80031 3" 80 113/,6" 1.82 lb.
i *T/0 -l-T/O z Tee j T'° Reducing Cross Cross T/O T/O T/O z T/O' __I__ T/O'
Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt.
80000 3/4" 40 5/8" 0.11 lb. No. Size Sch. 1 2 lb. 80009 3/4"
40 '/16" 0.131b.
80001 1" 40 3/4" 0.19 lb. 80015 1"x 3/4" 40 "/,6" 1 11/,6" 10.28 80010 1" 40 15/,6" 0.23 lb.
80002 11/4" 40 7/8" 0.26 lb. 80011 174" 40 15/16" 0.34 lb.
80003 1 11/2" 80 1 1" 1 0.51 lb. 80012 1 1'/2" 80 1716" 0.67 lb.
80004 2" 80 13/8" 0.90 lb. 80013 2" 80 13/8" 1 1.00 lb.
80005 21/2" 80 19/,6"1 1.59 lb. 80014 21/2" 80 19/16" 1.91 lb.
80006 3" 80 111/16" 2.41 lb. 80008 3" 801 113/,6" 2.89 lb.
z�
"o,PaN T/O T/O T/O
Coupling _ _._ _._ _. Cap _ Reducer
T.-- - Bushing
i
Part No. Size Sch. T/O Wt.
Part No.j1h2 Sch. T/O Wt. Part No. Size Sch. T/O Wt. 80200 1" x 3/4" 40 '/,6" 0.04 Ib.
80075 40 1/8" 0.07 Ib. 80100 3/4" 40 6/16" 0.04 Ib. 80201 11/4"x 3/4" 40 7/16" 0.11 Ib.
80076 40 1/8" 0.11 Ib. 80101 1" 40 3/3" 0.06 Ib. 80202 11/4" x 1" 40 6/16" 0.12 Ib.
80077 40 3/,6" 0.12 Ib. 80102 11/4" 40 1/2" 0.10 Ib. 80203 1112"x 3/4" 80 5/8" 0.16 Ib.
80078 80 3/,6" 0.25 Ib. 80103 11/2" 80 5/8" 0.20 Ib. 80204 11/2"x 1" 80 1/2" 0.14 Ib.
80079 80 3/16" 0.38 Ib. 80104 2" 80 5/8" 0.31 Ib. 80205 1112" x 11/4" 80 3/8" 0.17 Ib.
80080 80 3/,6" 0.67 Ib. 80105 21/2" 80 '/8" 0.58 Ib. 80206 2" x 3/4" 80 3/4" 0.27 Ib.
80081 80 3/16" 0.91 Ib. 80106 1 3" 80 1" 0.88 I b., 80207 2" x 1" 80 "/16" 0.26 Ib.
80208 2" x 11/4" 80 9/16" 0.24 1b.
T/O 80209 2" x 11/2" 80 7/,6" 0.19 Ib.
Grooved 80215 21/2"x 1" 80 115/,6" 0.42 Ib.
Coupling _ _._._ _._._._ _ P;PI0,0. 80214 21/2" x 11/4" 80 13/4" 0.45 Ib.
Adapter 80213 21/2" x 11/4' 80 15/8" 0.46 Ib.
80211 21/2"x 2" 80 19/,8" 0.29 Ib.
Part No. Size Sch. T/O Wt. Pipe OD 80210 3" x 2" 80 2 3/16" 0.72 Ib.
80160 11/4" x 11/4" Grooved 40 2 5/16 0.78 Ib. 11/4" (1.660") 80212 3" x 21/2" 80 115/,6" 0.47 Ib.
80161 11/2" x 11/2" Grooved 80 2 5/,6 0.95 Ib. 11/2" (1.900")
80162 2" x 2" Grooved 80 2 5/16 1.42 Ib. 2" (2.375")
80163 21/2" x 21/2" Grooved 80 2 5/16" 2.28 Ib. 21/2" (2.875")
-- T/0'
80164 3" x 3" Grooved 80 21/4" 3.00 Ib. 3" (3.500") Reducing
80168 3" x 76.1 mm Grooved 80 21/4" 2.72 Ib. 76.1 mm (3.000") Tee
T/0' - T/0'
---- T/O Part T/O Wt.
No. Size Sch. 1 2 3 lb.._
Female _. ._._._. ._. ._ ._ 80132 3/4" x 3/4"x 1" 40 3/4" 3/4" 5/8" 0.14
Adapter 80133 1"x 3/4"x 3/4" 40 1/4' "/16" 3/4' 0.14
80134 1" x 3/4 x 1" 40 5/8" 3/4" 3/4" 0.17
Part No. Size Sch. T/O Wt. 80260 1" x 1" x 3/4" 40 3/4" 3/4" 11/16" 0.16
80142 3/4"x 3/4" NPT 40 5/8" 0.41 Ib. 80135 11/4"x 1"x 3/4" 40 7/16" 1 3/4" 15/14' 0.21
80145 1"x 1" NPT 40 3/4" 0.63 Ib. 80136 1 1/4"x 1"x 1" 40 "/16" 3/4" 15/,6" 0.22
80146 11/4"x 1'/4" NPT 40 7/8" 1.03 Ib. 80137 11/4" x 1"x 11/4" 40 13/16" 15/,6" 13/16" 0.26
80147 11/2"x 11/2" NPT 80 1" 1.42 Ib. 80261 11/4" x 1'/4" x 3/4' 40 5/8" 5/8" 7/8" 0.23
80148 2"x 2" NPT 80 13/8" 2.66 Ib. 80262 11/4" x 11/4" x 1" 40 3/4" 3/4" 7/8" 0.26
80138 11/4" x 1'/4" x 11/2" 80 1" 1" 1" 0.43
T/O 80140 11/2"x 11/4"x 3/4" 80 '/2" 5/8" 1" 0.36
80141 11/2"x 11/4" x 1" 80 1/2" 5/8" 11/8" 0.38
Male 80263 11/2"x 11/2"x 3/4' 80 9/,6" 9/16" 1" 0.36
Adapter 80264 1112" x 11/2" x 1" 80 9/,6" 9/16" 1" 0.38
80275 11/2" x 11/2" x 1 1/4" 80 7/8" 1/8" 1" 0.45
Part No. Size Sch. T/O Wt. 80265 2" x 2" x3/4" 80 3/4" 3/4" 13/8" 0.61
80157 3/4" x 3/4" NPT 40 15/,6" 0.33 Ib. 80266 2" x 2"x 1" 80 '/8" 7/8" 13/8" 0.66
80158 1"x 1" NPT 40 13/8" 0.56 1b. 80274 2"x 2"x 11/4" 80 11. 1" 13/8" 0.74
80267 2"x 2"x 11/2" 80 11/8" 11/8" 13/8" 0.78
-T/O 80271 21/2" x21/2" x 1" 80 111/16" 111/16"" 19/,6" 1.43
80272 21/2"x 21/2"x 11/4" 80 111/16" 11'/,6" 19/16" 1.46
Reducing 80273 21/2" x 21/2" x 11/2 80 111/14' 11'/,6" 19/,6" 1.48
Coupling 80276 21/2"x 21/2"x 2" 80 1 11/16" 111/16" 19/,6" 1.50
80270 3"x 3"x 11/2" 80 13/4' 13/4' 113/,6" 2.28
Part No.I Size I Sch. T/O Wt. 80268 3" x 3"x 2" 80 1 13/4' 13/4' 13/4' 2.25
80220 11" x 3/4"1 40 1/6" 0.08 Ib. 80269 3"x 3" x 21/2" 80 1 13/4' 13/," 115/,6" 2.44
MITI
T/O T/O
Sprinkler Head Adapter Ilk._ Sprinkler Head Adapter ,_,[ib
wi th Brass Threaded Insert with Brass Threaded Insert
Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt.
80175E 3/4" x'/2" NPT 80 '/16" 0.20 Ib. 80175W 3/4"x'/2" NPT 40 '/14' 0.19 Ib.
80176E 1" x'/2" NPT 80 '/16" 0.22 Ib. 80176W 1" x'/2" NPT 40 '/,4' 0.18 Ib.
80177WL 3/4" x'/2" NPT 40 9/16" 0.16 Ib.
80179 1 x 3/4' NPT 40 3/4" 0.43 Ib. i
I
T/O'
T/O
Back-to-Back Cross = ---.- -. .--. .-. -.- .-
Sprinkler Head Adapter with Brass Threaded Insert =
(Spigot) -.---...- -- -- T/o'
I
with Brass Threaded Insert L '
I
T/O: I T/O
Part No. Size Sch. T/O Wt. Part T/O Wt.
80177L 3/4" x'/2" NPT 40 1/2" 0.16 Ib. No. Size Sch. 1 2 Ib.
80178 1" x'/2" NPT 40 1/2" 0.20 Ib. 80462 1" x 1"x'/2" NPT x'/2" NPT 40 6/8" 1'/8" 0.46
80463 1" x 1"x'/2" NPT x'/2" NPT 40 6/8" 15/,6" 0.47
T/O I
Sprinkler Head Adapter
900 Elbow -- }
T+' Back-to-Back Tee T'° _ _._ _. .-;-. .-.
with Brass Threaded Insert ----
with Brass Threaded Insert f
I T/O T/O
Part T/O Wt. Part Size Sch. T/O Wt.
No. Size Sch. 1 2 Ib. No. 1 2 Ib.
80199 3/4" x'/2" NPT 40 5/8" 5/,6" 0.20 80459 1" x 1/2" NPT x'/2" NPT 40 11h4' 16h4' 0.48
80189 1" x'/2" NPT 40 3/,4' 13/,6" 0.26 80460 1" x'/2" NPT x'/2" NPT 40 11h6" 1'/e" 0.46
Part T/O Wt.
No. Size Sch. 1 2 3 Ib,
80250 3/4"x 3/4"x'/2" NPT 40 6/8" 5/8" 1" 0.22
80251 1"x 1" x 1/2" NPT 40 11/16" 11/16" 13/16" 0.29
r 80249 1"x 1" x 1" NPT 40 15/16" 15/,6" 1'/,6" 0.73
Sprinkler Head Adapter T/0, 80256 11/4" x 1"x'/2" NPT 40 '/,s" 9/16" 11/8" 0.30
Tee - -- -- - -- -± 80252 11/4"x 11/4"x'/2" NPT 40 1/i6" '/16" 1'/8" 0.31
with Brass Threaded Insert ' 80257 11/2"x 11/4'x 1/2" NPT 80 9/,6" 5/8" 1116" 0.43
80254 11/2"x 1'/2"x'/2" NPT 80 9/16" 9/16" 1'/,6" 0.46
80258 2"x 1112"x'/2" NPT 80 1/2" 5/8" 15/6" 0.56
80253 2"x 2" x'/2" NPT 80 /2" /2" 15/8" 0.62
Limited Warranty
Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in
material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will
expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured
by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to
misuse,improper installation,corrosion,or which have not been installed,maintained,modified or repaired in accordance with
applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having
Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced,at Tyco Fire Products sole
option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the
sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or
incomplete information supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE,IN CONTRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL
THEORY,FOR INCIDENTAL,INDIRECT,SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LIMITED TO LABOR
CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED,INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
tqCO/Flow Control/Tyco Fire
Products
z 0§Z
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
7
OFFSET CPVC HANGER #905 #906
1.5000: 3.00
SIZE-3/4"thru 3"pipe.
MATERIAL-Carbon Steel.
FINISH-Mil. Galvanized..
LISTING/APPROVAL-
&a 203-EX 4231,EX 2551
PATENT-No.6,648,278.
FUNCTION- 3/4"-2" Hanger/restrainer for horizontal CPVC,Copper or Steel pipe.
Listed hanger/restrainer in all 3 mounting positions,i.e.vertical surface and both top and
bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a ceiling.
Size 2 1/211 Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions.
i.e.vertical surface and both top and bottom of horizontal surface.
Size 31' Hanger for horizontal CPVC pipe in two mounting positions,side and bottom.
i.e.vertical surface and bottom of horizontal surface.
Stabilizes vertical piping by providing horizontal restraint.
INSTALLATION- Per NFPA 13, 13R and 13D.
Space by pipe type. Install on wood,concrete or steel-See Drawings.
Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed Restraint
When #905 threads are exposed in wood,install#906 backing nut. 3/4"thru 2"
SPECIAL NOTE: When installing on CPVC sprinkler system pipe: F-
Verify that all assembly components are cleaned of any surface oil. k7—i
FASTENERS-UL Listed per NFPA 13
WOOD- 3/4"-3" CPVC pipe-#905 screw-no pre-drill.
3/4"-2"Copper pipe- #905 screw- no pre-drill.
3/4"-2" Steel pipe- 1/4"xl 1/2"lag screw- no pre-drill.
Thru 5/8"gypsum board- 1/4"x 2"lag screw. 17
STEEL-min. 18 GA. - 3/4"-3" CPVC pipe- 1/4"or#14 Tek Screw.
3/4"-2" Copper pipe- 1/4"or#14 Tek Screw.
3/4"-2" Steel pipe- 1/4"or#14 Tek Screw.
CONCRETE:Required minimum load each fastener= 5(wt)+250lbs.
2
FEATURES
* 1 1/2"Offset-loose fit allows pipe to slide. Id
* 3/4"and I"pipe size made with common center-line.
Listed Restraint
*Patented design for superior strength. 3/4"thru 2"
* Offset edge eliminates abrasion.
*AFCON#905 screw has 5/16"hex head- included.
ORDERING-Part#and pipe size.
AFCON#906 backing nut sold separately.
Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly.
Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems
not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not
limited to loss of business or profit,when non-AFCON products have been,or are used.
6/08
WILKINS Model 11
'-• • Valve
with I..
-• BV-pass
SPECIFICATION SUBMITTAL SHEET
APPLICATION
ia} Designed for installation on potable water lines to reduce
high inlet pressure to a lower outlet pressure.The high flow
-- ,,,y, capacity makes this device most suitable for industrial wa-
�u ter lines and commercial irrigation systems.The direct act-
ing integral by-pass design prevents buildup of excessive
system pressure caused by thermal expansion. The bal-
FEATURES anced piston design enables the regulator to react in a
Sizes: ❑ 1/2" ❑ 3/4" ❑ 1" ❑ 1 1/4" smooth and responsive manner to changes in system flow
❑ 1 1/2" ❑ 2" ❑ 2 1/2" ❑ 3" demand,while at the same time, providing protection from
Maximum working water pressure 300 psi inlet pressure changes.
Maximum working water temperature 180° F STANDARDS COMPLIANCE
Reduced pressure range 25 psi to 75 psi
Factory preset(fieldset 2 1/2"&3") 50 psi ASSE®Listed 1003(1/2"thru 2 1/2" )
Threaded connections(FNPT) ANSI B1.20.1 0 IAPMO®Listed (1/2"thru 3" )
Copper connections(FC) ANSI B 16.22 0 City of Los Angeles Approved(1/2"thru 3")
Maximum hot water temperature 180°F @ 100 psi CSA®Certified(1/2"thru 2")
Cold water rated temperature 73.4°F @ 400 psi MATERIALS
OPTIONS(Suffixes can be combined) Main valve body Cast bronze ASTM B 584
❑ - standard with single union FNPT inlet x FNPT Access covers Cast bronze ASTM B 584
outlet(1/2"thru 2")and less union(21/2"&3") Brass ASTM B 16
❑ C - copper sweat connection (1/2"thru 2") Fasteners Stainless steel, 300 series
❑ HR - 75 psi to 125 psi spring range, factory set Stem&plunger Cast bronze ASTM B 584
at 85 psi (fieldset 2 1/2"&3") Brass ASTM B 16
❑ HLR - 10 psi to 125 psi spring range,factory set Elastomers Buna Nitrile(FDA approved)
at 50 psi EPDM (FDA approved)
❑ HT - 210°F maximum temp Cap gaskets Natural vulcanized fibre
❑ L - less integral by-pass check valve(3/4"-2") Acetal (DelrinTm 500), NSF Listed
❑ LPV - 210°F maximum temp with 10 psi to 35 psi Springs Oil tempered wire,ASTM A 229
spring range, factory set at 20 psi Seat Stainless steel, 300 series
❑ LPC - 180°F maximum temp with 10 psi to 35 psi
spring range, factory set at 20 psi D
❑ SC - sealed cage bell housing and stainless steel
adjustment screw
❑ SW - made for salt water service
❑ YSBR - with bronze"Y"strainer on inlet
❑ 510 - 400 psi inlet rating and 75 psi to 125 psi
spring range,factory set at 85 psi B
(fieldset 2 1/2"&3")
❑ P - tapped and plugged for gauge
❑ CPVC - CPVC tailpiece connection(3/4"-1") 0 WILKINS
ACCESSORIES 500
❑ Repair kit(rubber only) c
A
DIMENSIONS&WEIGHTS(do not include pkg.)
DIMENSIONS (approximate)
SIZE WEIGHT
CONNECTIONS A B C D
in. mm in. mm in. mm in. mm in. mm Ibs. I kg.
1/2 15 SINGLE UNION 41/2 108 6 152 1 5/8 41 23/4 70 3 1.5
3/4 20 SINGLE UNION 45/8 118 6 152 1 1/8 29 23/4 70 4 2.0
1 25 SINGLE UNION 51/8 130 67/8 175 1 5/8 41 35/16 84 6 3.0
1 1/4 32 SINGLE UNION 65/16 160 71/4 184 1 1 3/4 45 4 102 7 3.0
1 1/2 40 SINGLE UNION 85/16 211 1 10 254 1 7/8 48 5 127 14 6.5
2 50 SINGLE UNION 91/2 241 103/4 273 21/8 54 6 1/2 165 1 20 9.0
2 1/2 65 LESS UNION 10 254 141/2 368 3 76 8 203 28 12.5
3 80 1 LESS UNION 1 11 1/8 283 16 406 31/2 89 8 203 44 20.0
D• REVISION:
i0 i
Page 1 of 2
FLOW CHARACTERISTICS
MODEL 500 1/2"THRU 3" (STANDARD & METRIC)
FLOW RATES(1/s)
3.2 6.3 9.5 12.6 15.8 18.9
20 1/2" 3/4" 1" 11/4" 11/2" 2" 21/2' 3° 138
y 15 -(15mm} (20mm 25mm 32mm 40mm 50mm� 65mm 80mm 104 @
a Y
LL 10 69 U_
0 0
5 35
U_ 0 L_
0 50 100 150 200 250 300
FLOW RATES(GPM)
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in
accordance with the manufacturers' instructions and the latest edition of the Uniform Plumbing Code.The assembly
shall be installed with sufficient side clearance for testing and maintenance.The Model 500 may be installed in any
position. If installed in a pit or vault, specify the "SC" sealed cage option. Multiple installations are recommend for
wide demand variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50
psi outlet). CAUTION:Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify
correct pressure setting. Do not bottom adjustment bolt on bell housing.
'IJ" Illill�IITIII' �
MODEL 975XL o � ,
RPZ BACKFLOW PREVENTER OPTIONAL PRESSURE O IITII III i,l'
— — — — — — — — — GAUOE 111111-1
PROTECTIVE = `~'
ENCLOSURE o
11 MODEL 850 =
— — SHUT-OFF VALVE
OPTIONAL PRESSURE
GAUGE
MODEL DUI
DIELECTRIC UNION 12"MIN. -
- 30,MAX. = —
II
—
VERTICAL INSTALLATION
I-111-- III�IF -III—III —III—IIII
—III =111- - — III MODEL 500 TO HANDLE LOW
DEMANDS(SET@ 65 PSI
DIRECTION OF FLOW
II I I IIII
TYPICAL INSTALLATION
MODEL 500FC TO HANDLE DIRECTION OF FLOW
HIGH DEMANDS(SET @ 55 PSI)
SPECIFICATIONS BATTERY INSTALLATION
The Pressure Reducing Valve shall consist of a bronze body and bell housing, a separate access cover for the plunger
and a bolt to adjust the downstream pressure.The bronze bell housing and access cap shall be threaded to the body
and shall not require the use of ferrous screws. The assembly shall be of the balanced piston design and shall reduce
pressure in both flow and no-flow conditions. The assembly shall be accessible for maintenance without having to
remove the body from the line.The Pressure Reducing Valve shall be a WILKINS Model 500.
Page 2 of 2
WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 11_2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) ° Website: http://www.zurn.com
-WILKINS SPECIFICATION SUBMITTAL SHEET
A ,.COMPANY Model 975XL
Reduced Pressure Principle Assembly
=> APPLICATION
Designed for installation on potable water lines to protect
against both backsiphonage and backpressure of contami-
nated water into the potable water supply.Assembly shall
FEATURES provide protection where a potential health hazard exists.
Sizes: ❑ 3/4" ❑ 1" ❑ 11/4 ❑ 11/2 ❑ 2"
Maximum working water pressure 175 PSI STANDARDS COMPLIANCE
Maximum working water temperature 180°F ❑ ASSEO Listed 1013
Hydrostatic test pressure 350 PSI ❑ IAPMOO Listed
End connections Threaded ANSI B1.20.1 ❑ ULO Classified(lessshut-off valves or with OS&Y valves)
OPTIONS ❑ C-ULO Classified
❑ CSAO Certified
(Suffixes can be combined) ❑ AWWA Compliant
❑ Approved by the Foundation for Cross Connection
❑ - with full port QT ball valves(standard) Control and Hydraulic Research at the University of
❑ L - less ball valves Southern California
❑ U - with union ball valves
❑ MS - with integral relief valve monitor switch
❑ P - for reclaimed water systems MATERIALS
❑ S - with bronze"Y"type strainer Main valve body Cast Bronze ASTM B 584
❑ BMS - with battery operated monitor switch Access covers Cast Bronze ASTM B 584
❑ FDC - with fire hydrant connection;2"only Fasteners Stainless Steel, 300 Series
❑ TCU - with test cocks up Elastomers Silicone (FDA Approved)
❑ V - with union swivel elbows Buna Nitrile (FDA Approved)
❑ SE - with street elbows Polymers NorylTM, NSF Listed
❑ RV - with test cocks supplied on the opposite side Springs Stainless steel, 300 series
❑ FT - with integral male 450 flare SAE test fitting
ACCESSORIES E
❑ Air gap(Model AG) O /
❑ Repair kit(rubber only) o o
❑ Thermal expansion tank(Model WXTP) F o O o
❑ Soft seated check valve(Model 40) 0 0
❑ Shock arrester(Model 1250)
D c B
A
G
DIMENSIONS&WEIGHTS(do not include pkg.)
DIMENSIONS(approximate) WEIGHT
MODEL SIZE A UNION
A BALL BLESS BALL C D E F G LESS BALL WITH BALL
VALVES VALVES VALVES VALVES
in. mm in. mm in. I mm in. I mm in. I mm in. I mm in. I mm in. I mm in. I mm Ibs. ka Ibs. k
3/4 20 12 305 14 356 73/4 197 21/8 54 3 76 31/2 89 5 127 153/4 400 10 4.5 12 5.5
1 25 13 330 141/4 362 73/4 197 2 1/8 54 3 76 31/2 89 5 127 173/4 451 1 10 4.5 14 6.4
1 1/4 32 17 432 19 483 1015/16 278 23/4 70 31/2 89 5 127 63/4 171 22 559 22 10 28 12.7
1 1/2 40 17 3/8 441 20 508 1015/16 278 23/4 70 31/2 89 5 127 63/4 171 231/8 587 22 10 28 12.7
2 1 50 181/2 470 21 1/4 540 1015/16 278 23/4 70 J3 1/2 89 5 127 63/4 171 25 1/2 648 22 10 34 15.4
Pagel of 2 DocuMeBF 975XL(LG) RE V.
FLOW CHARACTERISTICS
Model 975XL 3/4" & 1" (STANDARD) a Model 975XL 11/4", 1'/2" &2" (STANDARD)
a 3/4" 1.. a
C6 � 11/4 11/2" 2"
15 15
0 0
W 10 W 10
cl: Cc
I 5 0 20 40 60 80 ° 5 0 50 100 150 200 250
FLOW RATES(GPM) o FLOW RATES(GPM)
Model 975XL 20mm &25mm (METRIC) Model 975XL 32mm,40mm &50mm (METRIC)
al 150 a 150 32mm 40mm 50mm
120 2omm 25mm 120
Cn 0 90 90
cr cr
n 60 Co 60
W W
cr ir
D 30 0 1 2 3 4 5 a 30
0 3 6 9 12 15
FLOW RATE(1/s) O Rated Flow FLOW RATE(1/s)
(Established by approval agencies)
TYPICAL INSTALLATION Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
Local codes shall govern installation requirements. To be 1/8" 1 1 2 3
installed in accordance with the manufacturers'instructions 1/a" 2 2 3 5
and the latest edition of the Uniform Plumbing Code. Un- 3/8" 3 4 6 9
less otherwise specified,the assembly shall be mounted at 1/2" 5 7 9 14
3/4" 8 12 17 25
a minimum of 12"(305mm)and a maximum of 30"(762mm) 1.1 13 20 27 40
above adequate drains with suff icient side clearance for test- 1 1/4" 23 35 47 70
ing and maintenance.The installation shall be made so that 1 1/2" 32 48 63 95
no part of the unit can be submerged. 2" 52 78 105 167
CENTRAL
STATION
ALARM
PANEL PROTECTIVE
ENCLOSURE II •II / II I I
BATTERY
MONITOR
SWITCH a
12"MIN. 12"MIN
30"MAX. 30"MAX
OPTIONAL AIR GAP
AIR GAP WATER METER
FITTING
0 o c o c DRAIN
lu
p
FLOOR o / II II DIRECTION OF FLOW� II
FLOOR DRAIN—�
DIRECTION OF FLOW — INLET SHUT-OFF
INDOOR INSTALLATION OUTDOOR INSTALLATION
(Shown w/optional EMS)
SPECIFICATIONS
The Reduced Pressure Principle Backflow Preventer shall be ASSE®Listed 1013, rated to 180°F and supplied with
full port ball valves.The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal
polymers shall be NSF®Listed NorylTM and the seat disc elastomers shall be silicone.The first and second checks
shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed
indoors, the installation shall be supplied with an air gap adapter and integral monitor switch.The Reduced Pressure
Principle Backflow Preventer shall be a WILKINS Model 975XL.
Page 2 of 2
WILKINS OPERATION OF ZURN INDUSTRIES, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 11-2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com
MK*@Tkill- VALVE DMAPQ OFNE9
1/4"-2" 175 PSI (1207kPa) WW-V-1967
C ca-us "S",
uS 7�
C
LISTED 4-
5 8-
RATINGS 6 3 B
•175 psig WOG
•CSA(AGA/CGA)&LIL Ratings`
•Vacuum to 29" 9�
*(Except 1/4"&3/8") 2
FEATURES
•Full Port Design
•Full Flow, High Cv
•One Piece Bronze Body
•Stainless Steel stem and disc A•Viton Seal
•Excellent throttling characteristics DIMENSIONS
•Requires no system pressure to seal
•30°F to 275°F Temperature Range UNITS 1/4" 3/8" 1/2" 3/4" 1" 1-1/4" 1-112" 2"
DN6 DN10 DN15 DN20 DN25 DN32 DN40 DN50
APPLICATIONS A INCHES 2.25 2.38 1.88 2.00 2.13 2.63 2.88 3.25
MM 57.2 60.3 47.6 50.8 54.0 66.7 73.0 82.6
•Natural Gas Shut-off B INCHES 1.50 1.63 1.75 2.19 2.31 2.63
('/z"psi and 5 psi) mm 38.1 41.3 44.5 55.6 58.7 66.7
•LP Gas Shut-off INCHES 3.50 5.00
•Gas and Air Systems c mm 88.9 127.0
•Fuel Oil(Types 1-6) cv 10 13 25 43 85 112 180
•Oil Systems Torque in/lb 18 22 35 50 70 120
•Liquid Service including water lWeight (Ibs) 0.5 0.8 1.0 1.7 33
•Throttling, Balancing&Shut-off
•Vacuum Service ACCESSORIES
* Do not use on hot water over 120°F '
Tee Handle Option Oval Handle Option Memory Stop Handle
To Order Tee Handle Option, To Order Oval Handle Option, Option
Add suffix"T"to Model Number. Add suffix"R"to Model Number. To Order Memory Stop Option,
(E.g.BB2-100T) (E.g.BB2-100R) Use this Model Number,BB2-102
MATERIALS
ITEM PART MATERIALS ASTM SPEC.
Extension Stem
1 Body Bronze ASTM-8584 '. - Options
2 Disk Stainless Steel Type 304 °' Stem extensions are
Calibrated Memory Stop available in 1-1/4"&
3 Stem Stainless Steel Type 303 2-1/2"lengths.The
4 Hex Nut Stainless Steel Type 302 Handle Option design permits valve
This Flow Set Handle Provides a installation behind
5 Gland Rod Bronze CA-360 Visual 90 X Scale to panels or inside equipment
6 Packing Nylon Position Memory Stop.The enclosures.
Option is Designed for 1-114"Extension,Order BB2-103
7 Handle Steel w/Zinc Plating Balancing Applications.Order using
Model Number BB2FS100. 2-1/4"Extension,Order BB2-104
8 Flat Grip Vinyl 1-1/4"Extension with Memory Stop,Order
9 Disc Seat Viton NOTE:Some Accessories Can be BB2-105
Combined for Added Versatility. 2-1/4"Extension with Memory Stop,Order
Contact the Factory. BB2-106
The information presented on this sheet is correct at the time of publication. Milwaukee
Valve reserves the right to change design,and/or material specifications without notice.
For the most current information access wwwmilwaukeevalve.com.
MILWAUKEE VALVE��
BB2 100-0 CDR V
M0DF11000
TE i .FM
I 4 L o
TEST
eve-ate
I'UP,
a
LSD
x 'YL K�J6i
❑ The AGF Manufacturing Inc. Model 1000 TESTANDRAIN Provides Both The Test
Function And The Express Drain Function ForA Wet Fire Sprinkler System.
❑ The Model 1000 Complies With All Requirements Of NFPA-13, NFPA-13R,
And NFPA-13D.
❑ The Model 1000 TESTANDRAIN IsA Sngle Handle Ball Valve That Is Light Weight And
Compact, IncludesA Tamper Resistant Test Orifice, Integral Tamper Resistant Sght
Glasses,And Is300 PSI Rated .
• Available In A Full Range Of SzesFrom 3/4"To 2" NPT& BSPTWith All Specifiable
Orifice Sze s 3/8", 7/16", 1/2", 17/32", 5/8" (ELO), & 3/4" (ESFR).
• The Orifice Sze Is Noted On The Indicator Plate And The Valve Is Tapped For
A Pressure Gauge.
• Locking Kit Available Which Provides %periorVandal Resistance And Prevents
Unintentional Alarm Activation.
our Nw
sAUtoc'90
G`C\e on the Internet
at
prl-
. .
10/00 7
(w) FM
MODEL 1000 300 PSI
I
TESTmDRAIN .
3/4!' ill 1 114!' 1 1/211 211
PLAN VIEW FRONT VIEW/VERTICAL INSTALLATION
f � A l FROM BRANCH
I � GAUGE INLET
B PROVIDED
D t�
TO DRAIN I QO
C
STREET EL DRAIN
O
FRONT VIEW/HORIZONTAL INSTALLATION I TO DRAIN
STREET
�E ORPIIPEL
I I` I
j
qIEST TO D RAIN F RIGHT HAND/STRAIGHT INSTALLATION
TO DRAIN APPROVALS:
G
❑ ULand ULC Listed
❑ FM Approved except 3/4"
ORIFICE SIZE ❑ NYC-BSA NO.720-87-SM
AVAILABLE - 3/8, 7/16, 1/2, 17/32, ELO(5/8)*, ESFR(3/4)* ❑ CA.State Fire Marshall
DIMENSIONS- INCHES
SIZE A B C D E F G H
3/4"** 5 1/16' 1 1/2' 2 3/16' 35/8" 33/8" 1 13/16' 4 9/16' 63/8" MATERIAL LIST
128mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.,
5 1/16' 1 1/2' 23/16" 35/8" 3 3/8' 1 13/16' 49/16.' 63/8" PART: MATERIAL:
128mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm
�/ "
57/16" 1 11/16' 29116" 4 1/4' 35/16" 1 15/16' 59/16" 5 1/2' HANDLE STEEL
1 4 137.70mm 42.70mm 65.36mm 108.36mm 82.84mm 50.89mm 141.39mm 192.28mm STEM ROD BRASS
1
1/2' 166338 mm 4550/m m' 83.50/mm 527mm1 99.18/mm 6.97/mm 2086.63mm 2 33..60mm BODY BRONZE
VALVE SEAT IMPREGNATED TEFLON
2" 67/16" 1 13/16' 3 1/4' 5 1/16' 37/8" 2 5/8' 8 1/4' 10 7/8' INDICATOR PLATE STEEL
163.38mm 45.50mm 81.50mm 127mm 99.18mm 66 97m 206.63mm 273.60mm HANDLE LOCK SPRING STEEL
"Available on 1 1/4"to 2"size units only. **3/4"UL Listed only.
LISTED 2"ELO/ESFR IS UL : FM APPROVED
1 1/4"ELO/ESFR IS UL LISTED
UL LISTING EX4019
AGFMANUFAClURING INC. JOB NAME:
100 Quaker Lane ARCHITECT:
Malvern,FA 19355 USA
Telephone:(610)240-4900 ENGINEER:
Fax:(610)240-4906
www.testandrain.com MADE IN U.S.A. CONTRACTOR:
FOR SMALL PIPE VSR-SF
r
(E) POTTER VANE TYPE WATERFLOW
The Symbol of Protection ALARM SWITCH WITH RETARD
UL,ULC,CSFM Listed and NYMEA Accepted,CE Marked
Service Pressure: Up to 250 PSI (17,2 BAR)
Minimum Flow Rate for Alarm: 8-10 GPM(30-38 LPM)
Maximum Surge: 18 FPS(5,5 m/s)
sF Enclosure: Die-cast, red enamel finish
Cover held in place with tamper resistant screws
Contact Ratings: Two sets of SPDT(Form C)
15.0 Amps at 125/250 VAC
2.0 Amps at 30 VDC
Conduit Entrances: Two knockouts provided for 1/2" conduit.
Usage: Listed plastic, copper and schedule 40 iron pipe.
Fits pipe sizes - 1" (25mm), 1 1/4" (32mm), 1 1/2"
(38mm) and 2" (50mm)
Note: 12 paddles are furnished with each unit, one for
each pipe size of threaded and sweat TEE, one for 1"
4: (25mm) CPVC, one for 1" (25mm) CPVC (Central),
one for 1 1/2" (38mm) polybutylene and one for 1 1/2"
(38mm) threaded (Japan).
(CTS-Copper tubing size)
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4/IP55 rated enclosure-use with appropriate conduit
fitting.
• Temperature range: 40° F to 120° F, 4,5° C to 49° C)
Caution: This device is not intended for applications in
explosive environments.
Service Use:
Stock No.1113000 Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
U.S. Pat. No.3921989, Canadian Pat. No. 1009680 Residential occupancy up to four stories NFPA-13R
Other Patents Pending National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090018
The Model VSR-SF is a vane type waterflow switch for use on wet Screw the device into the TEE fitting as shown in Fig. 2. Care
sprinkler systems that use 1" (25mm), 1 1/4" (32mm), 1 1/2" must be taken to properly orient the device for the direction of
(38mm) or 2" (50mm) pipe size. The unit may also be used as waterflow.
a sectional waterflow detector on large systems. The vane must not rub the inside of the TEE or bind in any way.
The unit contains two single pole double throw snap action The stem should move freely when operated by hand.
switches and an adjustable, instantly recycling pneumatic re- The device can also be used in copper or plastic pipe installa-
tard.The switches are actuated when a flow of 8-10 gallons per tions with the proper adapters so that the specified TEE fitting
minute (30-38 LPM)or more occurs downstream of the device. may be installed on the pipe run.
The flow condition must exist for a period of time necessary to
overcome the selected retard period. INSPECTION AND TESTING: Check the operation of the unit by
opening the inspector's test valve at the end of the sprinkler line
INSTALLATION: These devices may be mounted in horizontal or the drain and test connection,if an inspector's test valve is not
or vertical pipe. On horizontal pipe they should be installed on provided.
the top side of the pipe where they will be accessible. The units
should not be installed within 6"(15cm)of a valve,drain or fitting If there are no provisions for testing the operation of the flow
which changes the direction of the waterflow. Select the proper detection device on the system,application of the VSR-SF is not
paddle for the pipe size and type of TEE used see Fig. 1 for recommended or advisable
instructions on changing paddle. The unit has a 1"NPT bushing The frequency of the inspection and testing and its associated
for threading into a non-corrosive TEE. See Fig.2 for properTEE protective monitoring system should be in accordance with the
size, type and installation. Use no more than three wraps of applicable NFPA Codes and Standards and/or authority having
teflon tape. jurisdiction (manufacturer recommends quarterly or more fre-
quently).
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTED IN USA MKT.#8800003-REV AA PAGE 1 OF 2
MFG.45400802-11/02
FOR SMALL PIPE V S R-`�r
(E) POTTER VANE TYPE WATERFLOW
The Symbol of Protection ALARM SWITCH WITH RETARD
FIG. 1 DO NOT LEAVE COVER FIG. 2
OFF FOR EXTENDED
Retard Adjustment: PERIOD OF TIME
To change time, turn knob �®
(either direction) for desired FLOW
time delay. Use the minimum 0 1(413 �APPROX.
amount of retard necessary t" MOUNT so (RED)E N.C.M
prevent false alarms. A "B" ARROW ON
BUSHING (BLACK) N.C.
setting is usually adequate for POINTS IN
DIRECTION OF 0�
this. Factory set at"B". WATERFLOW �i►
Shown with optional
m NET
THREADED Cover Tamper Switch DEPTH
FITTING ON p Kit.
SIZES
DIRECTION OF
WATER FLOW RUN OF THE
TEE MAY BE
THREADED OR
SWEAT TYPE
I
DIRECTION OF Screw the device into the tee fitting as shown.Care must be taken to
WATERFLOW properly orient the device for the direction of waterflow.On sweat tees,no
DWG. #737-31 threaded bushings,inserts,or adapters are permitted,unless they comply
DWG. #802-30 with the dimensions listed in the chart below.
Important: Important-The depth to the inside bottom of the tee should have the
There are 12 paddles fur- CAUTION:
TO PREVENT LEAKAGE APPLY TEFLON TAPE SEALANT following dimensions:
nished with each unit. One for TO MALE THREADS ONLY. DO NOT USE ANY OTHER
each size of threaded,sweat or TYPE OF LUBRICANT OR SEALANT.
APPROXIMATE DEPTH REQUIREMENT
plastic TEE as described in
TEE SIZE THREADED SWEAT CTS, POLYBUTYLENE CPVC
Fig. 2. These paddles have APPROX. RETARD SETTINGS (IN SEC.)
raised lettering that shows the 0 A B C D E 1" x 1" x 1" 2 1/16" 1 3/4° N/A 2 7/16"
pipe size and type of TEE that 0 10-25 20-40 35-55 50-70 60-90 1 1/4" x 1 1/4" x 1" 2 7/16" 2 7/16" N/A N/A
the are t0 be used with. The 1 1/2" x 1 1/2" x 1" 2 11/16" 2 1/4" 2 1/2" N/A
y 2" x 2" x1" 3 3/16" 2 3/4" N/A N/A
proper paddle must be used.
The paddle must be properly DWG. N735-33
attached (see drawing) and Warning: Do not use more than three wraps of teflon tape.
the screw that holds the pad-
dle must be securely tight-
ened.
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL
FIG. 3
INCOMING CAUTION:
O� An uninsulated section of a single conductor should not be looped around
the terminal and serve as two separate connections. The wire must be
G d severed, thereby providing supervision of the connection in the event that
OufGGIN DWG #923-3 the wire becomes dislodged from under the terminal.
FIG. 4 TYPICAL ELECTRICAL CONNECTIONS FIG. 5
NOTES: To remove knockouts: Place
2 SETS OF
NORMALLY OPEN CONTACTS WATERFLOW ZONE EOLR FROM 1. The model VSR-SF has two screwdriver at edge of knock-
CLOSE ON ALARM ON FIRE PANEL FIRE PANEL
EDLR switches,one can be used to outs, not in the Center.
V Y
C�,. ,� �< No operate a central station,
proprietary or remote signal-
ing unit, while the other is
COMM NO NO I COMM NO NC used to operate a local au-
M au-dible or visual annunciator.
POSITIVE DC 2. For supervised circuits see
THE NC AND NO MARKINGS OR HOT AC "Switch Terminal Connec-
AN ALARM CONDITION,
ON THE SWITCH ARE FOR NEGATIVE DC BELL tlons" drawing and caution
w
THE CONTACTS ARE REVERSED OR NEUTRAL AC
WHEN THE DEVICE IS IN OWG 1761-2 note(Fig.3). o
THE NORMAL CONDITION.
DWG./761-4
APPLICATION WARNING!
Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterflow switches
that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or
chemical suppression systems.
PRINTED IN USA MKT.#8800003-REV AA PAGE 2 OF 2
MFG.#5400802-11/02
(E)POTTER UNIVERSAL BALL
The Symbol of Protection VALVE SWITCH
UL and CUL Listed,FM,CSFM Approved
Dimensions:(including mounting clamps)
Large Clamps: 6"L x 5"W x 5.2"H
�Pp7j� 15,2 cm L x 12,7 cm W x 13,2 cm H
Small Clamps: 6"L x 4"W x 5.2"H
aevS 15,2 cm L x 10,2 cm W x 13,2 cm H
Weight: With Large Clamps:13.6 oz.(386,9 g.)
With Small Clamps:11.0 oz.(311,2 g.)
Enclosure: Non-Corrosive Composite Material
Environmental Limitations:
•NEMA 4 rated enclosure when proper electrical fittings
are used.(IP67)
•Temperature range:-40°F to 150°F(-40°C to 65°C)
•Not for use in hazardous locations
Housing Cover Tamper:Activated by housing cover
removal,(Stock No.1000035 only).
Contact Ratings:
SPDT Contacts: 10A at 125/250 VAC
2A at 30 VDC
RBVS Stock No.1000040(w/o Cover Tamper) SPDT Cover Tamper: 3A at 250 VAC
RBVS-T Stock No.1000035(w/Cover Tamper)
Patent Pending
GENERAL TESTING
The Model RBVS is designed to monitor the fully open The RBVS and its associated protective monitoring system should betested in
position of a ball valve installed in a sprinkler system. accordance with applicable NFPA codes and standards and/orthe authority
The unit will fit on most ball valves installed on back- havingjurisdiction(manufacturer recommends quarterly or more frequently).
flow-preventers and alarm trim lines of dry,alarm,and
deluge sprinkler valves.The switch operates if the
ball valve handle is moved from the open position.How-
ever,the switch does nottrackthe position ofthe handle
or ball.When the ball valve handle is in the open position,
a spring-loaded switch button will contact the valve FIGA INTERNAL COMPONENTS
handle.When the handle is moved from the open position,
this switch button extends to the tripped position,and the NORMALLY OPEN
RBVS contacts change state,thereby opening orclosing
a circuit.A cover tamper switch is available and is NORMALLY CLOSED
activated bythe removal ofthe RBVS housing cover.Ifan COMMON
attempt is made to remove the RBVS by the removal of 0
the mounting brackets,the unitwill beset intothetripped STRAIN RELIEF
mode by this action. SWITCH BUTTON
BLACK - N.O.
COVER RED- N.C. LOCATION
The RBVS can be mounted to the hex portion ofthe ball TAMPER wAITEE - COM ON HANDLE
valve or back-flow-preventerorto the adjoining pipe via
two clamps.The RBVS is shipped with two sets of m°
mounting clamps to accommodate various pipe and NO NT so
g p p p SWITCH BUTTON PLASTIC COATING
valve sizes,refer to Table 1.An"L"shaped and offset IS APPROX. 1"FROM ftEMOVEO FROM
bracketfor mounting the switch enclosure and an exten- HANDLE INSIDE END BALL VALVE HANDLE
Sion bracket add to the mounting flexibility cftheRBVS. IN SWITCH BUTTON
g y DWG#1086-1 CONTACT AREA
See"Typical Mounting Diagram"and"Installation and
Operation"on following page.
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•mvW.pottersignal.com
PRINTED IN USA MFG.#5401086-REV P PAGE 1 OF 3
9103
(E)POTTSZ UNIVERSAL BALL
The Symbol of Protection VALVE SWITCH
INSTALLATION ON LEVER HANDLE(SEE FIG.2)
(and be activated by)the metal ofthe handle.
1. Selectclamps and clamping bolts based upon pipe/valvesize, 9. Tighten clamping screws alternatelyto an eventual 30 in-lbs.
see Table 1. (minimum)oftorque.
2. Insert rubber clamp grippers into clamps,see Fig.2. 10. Maintain position of switch enclosure over valve handle
3. Place one clamp on top of pipe/ball valve near the valve and secure bolt that holds the extension bracket to the
handle and insert clamping bolts through it. clamping assembly.It may be necessary to close valve to
4. Place other clamp over clamping bolts from beneath the access this bolt.
installation and thread hex nuts onto the clamping bolts, 11. Position"L"bracket so that it contacts the back edge of the
but do not fully tighten,(be sure hex nuts seat properly in valve handle,and secure its bolt.It may be necessary to
clamp hex recesses).(NOTE:Some installations may require close valve to access this bolt.
one ofthe mounting bolts to be inserted from the bottom ofthe 12. With the actuator fully retracted, position RBVS switch
brackets and then trimmed to allow the extension bracketto enclosure to contact the valve handle squarely,see Fig.1.
clear.See Fig.4) 13. With RBVS switch enclosure held squarely in contact with
5. Attach extension bracket(if necessary to use for position- valve handle,securely tighten the two tamper resistant
ing)to top clamp using 1/,-20 X%"Hex bolt and washer,but screws on the backside of the enclosure.
do not fully tighten. 14. Close and open the valve to verify operation.The actuator
6. Attach "L" bracket (RBVS switch enclosure is loosely should easily retract when the valve handle is in the open
attached to"L"bracket)to extension bracket using 1/4-20 X position.
%"Hex bolt and washer,but do not fully tighten. 15. Fully open the valve.
7. Be sure ball valve is in the fully open position. 16. Remove the coverand wire main switch and tamperswitch
8. Slide loosely assembled RBVS switch enclosure to a if applicable.Carefully route tamper switch wires through
position that permits the switch button to contact the valve strain relief channel in switch enclosure. Fully seat the
handle approximately 1"from its inside end.See Fig.1 for wires into the bottom of the channel.See Fig.1.
approximate location.Cutand removethe plasticcoatingfrom 17. Replace RBVS switch enclosure cover and securely
the ball valve handleto allowthe RBVS switch buttontocontact tighten cover screw.
FIG.2 TYPICAL MOUNTING DIAGRAM TABLE 1 CLAMP SIZING
Pipe/Valve Size Clamp Clamping Bolts
LENGTH 1/2"to 314"(12,5 to 19mm) Small 10-32 x 2-1/2"
6'
SWITCH 1"to 2"(25 to 50 mm) Large 1/4-20 x 4"
® ENCLOSURE 7
L.eaACKEr HEIGHT SWITCH TERMINAL CONNECTIONS,
° 5.2" CLAMPING PLATE TERMINAL
EXT.BRACKET
(IF NECESSARY) CAUTION: An uninsulated
section of single conductor
CLAMPS should not be looped around
�0, the terminal and serve as two
Cep separate connections. The
GRIPPERS WIDTH wire must be severed,thereby
II'
a••(SMALL) �� providing supervision of the
DWG/1066-2 5"(LARGE) 66 P,�,roz.1-3 connection in the event that the
wire becomes dislodged from
under the terminal.
TYPICAL ELECTRICAL CONNECTIONS
LOCAL CIRCUIT
TRANSFORMER OR BATTERY POWER STYLE D(CLASS A)SUPERVISED LOOP STYLE B(CLASS B)SUPERVISED CIRCUIT
NC.
DEWS 0 COM. COM. TO x C_
0 CONTROE CPI. EN0-0f-IINE RESSTOR
OLIRCE RICO.N.C.RICO. UNT 0
0v/0.
11DBB-4
TAMPER SWITCH CONNECTIONS
COVER TAMPER &RBVS CONNECTED COVER TAMPER & RBVS WIRED
TO THE SAME ZONE ON THE FACP TO SEPERATE ZONES
COVER
M PER
Co.. N.O.COM. r
COM N.O. COM.
FRCP COVER EOLR N.C.
TMIPER FACP EOLR rAC N.O. EOLR
D.C.#1086-5
PRINTED IN USA MFG.#5401086-REV P PAGE 2 OF 3
9/03
(E)POTTER RBVS
UNIVERSAL
BALL
The Symbol of Protection VALVE SWITCH
INSTALLATION ON TEE HANDLE(SEE FIG.3) the RBVS switch button to contact(and be activated by)the
metal ofthe handle.
1. Selectclamps and clamping bolts based upon pipe/valve size,
see Table 1. 8. Tighten clamping screws alternately and 1/,20 X%"bolt to
30 in-lbs.(minimum)of torque.
2. Insert rubber clamp grippers into clamps,see Fig.3
9. With the valve handle fully open,slide the RBVS housing
3. Place one clamp on top of pipe/ball valve near the valve down until the switch operates plus 1/8 inch.Tighten the
handle and insert clamping bolts through it. screws holding the RBVS to the"offset'bracket.
4. Place other clamp over clamping bolts from beneath the 10. Remove the RBVS switch enclosure cover.
installation and thread hex nuts onto the clamping bolts,
but do not fully tighten,(be sure hex nuts seat properly in 11. Close and open the valve to verify operation.The actuator
clamp hex recesses). should easily retract up when the valve handle is in the
open position.
5. Loosely attach "L" bracket to the"offset" bracket and
"offset"bracket to the RBVS housing. 12. Fully open the valve.
6. Be sure ball valve is in the fully open position. 13. Wire main switch and tamper switch(if applicable).Care-
fully route tamper switch wires through strain relief channel
7. Slide loosely assembled RBVS switch enclosure to a in switch enclosure.Fully seat the wires into the bottom of
position that permits the switch button to contact the valve the channel.See Fig.1.
handle approximately 1/2"from the end ofthe handle.Cutand
remove the plastic coating from the ball valve handle to allow 14. Replace RBVS switch enclosure cover and securely
tighten cover screw.
FIG.3
SWITCH ENCLOSURE
p� OFFSET BRACKET
QCY
"L' BRACKET
CLAMPS
CLAMP
GRIPPERS DWG #1086-3
FIG.4
REVS
O
SOME INSTALLATIONS MAY CAUSE
INTERFERENCE BETWEEN MOUNTING BOLT
AND OFFSET BRACKET. INSTALL BOLT FROM
BOTTOM AND TRIM AS NEEDED TO CORRECT. PIPE
O
DWG.#1086-6
PRINTED IN USA MFG.#5401086-REV P PAGE 3 OF 3
9103
WHEELOCK
(E) POTTER SERIES MT AND MT STROBE
The Symbol of Protection MULTITONE ELECTRONIC SIGNALS
Wheelock's MT and MT Strobe Series Multitone Electronic Signals offer a choice of eight(8)nationally and internationally
recognized alerting sounds: Horn, Bell, March Time Horn,Code-3 Tone,Code-3 Horn,Slow Whoop,Siren or Hi/Lo Tone.
Wheelock's Code-3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications
without requiring additional coding means. With MT and MT Strobe Signals, one alarm appliance meets most of your
signaling needs. Wheelock's MT and MT Strobe Signals are UL Listed, FM, CSFM and NYMEA Approved.
Features
One alarm appliance with (8) eight selective signals to
provide superior sound penetration for various ambient
and wall conditions with two field selectable sound output
levels.
• Code-3 Horn and Tone meet NFPA/ANSI/ISO temporal i
pattern for standard emergency evacuation signaling. I
i=
• Audible and strobe can operate from a single signaling D
circuit.
• Designed to meet or exceed NFPA/ANSI Standards and
ADA Accessibility Guidelines. 110 VAC model does not
meet ADA requirements.
• Low current draw with low temperature compensation to
reduce power consumption and wiring costs.
• Low cost installation via standard electrical boxes.
Attractive flush or surface mounting options available. MT-24-1575w-FR SHOWN
MT-121575W-FR MT 12/24 MT-24-1575W-FR* MT4-115-WH-VFR
(Strobe/Horn) (Horn) (Strobe/Horn) Indoor (Strobe/Horn)
Model Stock No. 1610921 Stock No. 1610914 Stock No. 1610915 Stock No. 1610216
Mounting Options** Mounting Options** Mounting Options** Mounting Options**
D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,J,K,N,O,R
dBA and Current Ratings
Average Current Ratings(Amps) dBA Reverberant Ratings dBA Anechoic Ratings
Per UL 464
Tone @ 24VDC @ 12VDC @ 24VDC @ 12VDC @ 12 and 24VDC
HI STD HI STD HI STD HI STD HI STD
Horn 0.038 0.024 0.095 0.019 92 87 90 77 99 93
Bell 0.019 0.012 0.030 0.010 86 80 85 69 92 87
March Time Horn 0.038 0.024 0.095 0.019 89 84 89 74 99 93
Code-3 Horn 0.038 0.024 0.095 0.019 88 83 88 73 99 93
Code-3 Tone 0.027 0.016 0.057 0.014 85 80 84 70 95 90
Slow Whoop 0.047 0.025 0.095 0.024 90 89 89 75 99 94
Siren 0.034 0.022 0.078 0.019 89 84 89 75 98 93
Hi/Lo 0.020 1 0.013 0.042 0.011 86 81 86 71 93 88
* For outdoor installation use MTWP-2475W-FR with IOB-R backbox.
* See next page for mounting options.
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTED IN USA MKT.#8850002-REV H PAGE 1 OF 2
2/03
WHEELOCK
(E) POTTER SERIES MT AND MT STROBE
The Symbol of Protection MULTITONE ELECTRONIC SIGNALS
MOUNTING ACCESSORIES
(D)4"SQUARE,FLUSH(BO) (E)4"SQUARE,DEEP,FLUSH(BO) (F)DOUBLE-GANG,FLUSH(BO)
1 C O op p O
p/O
1 O O
0,/ OOl0 1 0010
0 1 O
,O O
O
MAXIMUMNUM BEROFCONDUCTORS MAXIMUM N UMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS
AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12
4 4 4 4 8 8 8 4 4 4 4 4
(J)BB BACKBOX (K)WBB WEATHER RESISTANT BACKBOX (L)ISP SURFACE ADAPTER
(Order Code:2830) (Order Code:2959) (Order Code:5306)
Standard steel backbox with knockouts for Sturdy die-cast housing,threaded conduit hole Indoor use.
interior surface mounting,concealed conduit and knockout for outdoor applications.It is
mounting or semi-flush applications. It is painted to match the signal.
painted to match the signal.
�Ye
r-Tll OQOO 0 000 ,w
T:Y•-a�a�ne
MAXIMUMNUM BEROFCONDUCTORS MAXIMUM NUMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS
AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12
4 4 9 4 4 4 4 4 a 8 8 4
(0)RP-R RETROFIT PLATE (R)SFP SEMI-FLUSH PLATE (M)IOB BACKBOX
(Order Code:5042) (Order Code:2957) (Order Code:5046)
Stamped aluminum surface wall plate which For surface mounting MT products.
mounts behind the basic unit and serves to
cover recessed backboxes in semi-flush
'^—I mounting applications.It is painted to match
the signal.
tW YL!W
1M O O O
oe
g
MAXIMUM NUMBER OF CONDUCTORS
TWO. /8850002-1 AWG.#18 AWG.#16 AWG.#14 AWG.#12
8 8 8 4
MOUNTING NOTES
CAUTION:The mounting options figures show the maximum number of field wires(conductors)that can enterthe backbox used with each mounting option.If these limits are
exceeded,there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical code(NEC),Wheelock recommends use of the largest backbox option and the use of
approved stranded field wires whenever possible,to provide additional wiring room for easy installation and minimum stress on the product from wiring.
CAUTION:Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit,especially if sheathed multiconductor cable
or 3/4"conduit fittings are used.
1. Mounting hardware for each mounting option is supplied.
2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance forthe installed product.When extension rings are required,conduit should enter
through the backbox,not the extension ring.Use Steel City#53151(1-1/2"deep)or#53171(2-1/8"deep)extension rings(as noted in the mounting options)or equivalent
with the same cut-out area.
3. When terminating field wires,do not use more lead length than required.Excess lead length could result in insufficient wiring space for the appliance.
4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.This is especially
important for stiff,heavy gauge wires and wires with thick insulation or sheathing.
5. Do not pass additional wires(used for other than the appliance)through the backbox.Such additional wires could result in insufficient wiring space for the appliance.
PRINTED IN USA MKT.#8850002-REV H PAGE 2 OF 2
2/03
. 111 Series UARDIAN
Flush Fire • • • FFIRERE UIPMENT, INC.
Residential •
• Used as an auxiliary connection through which the fire department
can pump water to supplement existing water supplies
• Provides 250 GPM flow(minimum), per 2'/2"inlet
6002 6014/6015 • Single inlet connections incorporate a straight-thru, non-clappered
design with female NPT outlets
AUTO ¢.
t
rte. • Two and three-way inlet connections feature brass bodies(angle
I or straight pattern),with integral drop-clapper inlets and female
N PT outlets
R IIh7lS6 lS1
6016/6017 Y • Standard components:
Female hose thread swivel inlets, plugs with chains and
identification plate
•Cast brass construction", standard
'Optional brass finishes on exposed surfaces, add suffix to model no.
h
-B Polished;-C Rough Chrome Plated;-D Polished Chrome Plated
6024-6029 Single Inlet Connections
Back outlet Top/Bottom outlet W41/2"002 6014 6015 6016 6017
�g� �A� c '/z„ 21/2„ 3„ 21/2" 3„
1/z" 21/z" 21/z" 21/z" 21/z"
�� B � � O.D. 7"O.D. 7"O.D. 7".0Q 7"SO
Identification Plate Lettering: AUTO SPKR
21h"Nipple Plate 3'h"DIA
(by others)
SwivelInlet� ° ° O • • Connections
9"
Plug 3'h" • • _
7%"
L 1, 6024 Back 4"x 21/2"x 21/2" •2 115/8" 77/8" ---
6025 Bottom 4" x 21/z" x 21/z" 2 121/8" 6'/8" 71/8"
6026 To 4"x 21/2"x 21/2" 2 121/8" 67/8" 71/s"
6027 Back 6"x 21/2"x 21/2" 2 115/8" 77/8" ---
AUTOD f"•Fh:i 6028 Bottom 6" x 21/2" x 21/2" 2 121/8" 75/8" 71/8"
6029 To 6"x 21/2"x 21/2" 2 121/8" 75/8" 71/s"
` 1 6034 Back 4" x 21/2"x 21/2" x 21/2" 3 173/8" 61/8" ---
- 6035 Bottom 4" x 21/2" x 21/2" x 21/2" 3 173/8" 75/8" 71/8"
t4, 6036 To 4" x 21/2"x 21/2" x 21/2" 3 173/8" 75/8" 71/8"
y 6037 Back 6" x 21/2"x 21/2" x 21/2" 3 173/s" 61/8"
6038 Bottom 6" x 21/2"x 21/2" x 21/2" 3 173/8" 75/8" 71/8"
6034-6039 6039 Top 6" x 21/2"x 21/2" x 21/2" 3 173/8" 75/8" 71/s"
Identification Plate Lettering:
Back Outlet Top/Bottom outle�t
A •AUTO SPKR •AUTO SPKR&STANDPIPE
� ��� \ �c� •STANDPIPE •DRY STANDPIPE
L L t
2'h"Nipplee L�l l�l 3'/z"DIA
(by others) Plate
Swivels 0
Inlet 0 0 O O Notes
Plug 3,,,. • Pipe nipples for connecting bodies to swivel inlets, by others
• Always specify hose threads and identification plate lettering
I�23"' 65/8 • Contact factory for current UL listing/FM approvals and special
requirements
58
WILKINS Model WXTP
Expansion
a company Water Thermal SPECIFICATInN SUBMITTAL SHEE-
APPLICATION
Designed for installation on potable water lines between the
backflow preventer or pressure reducing valve and the water
heater to protect against water thermal expansion. When
system pressure increases,water enters the tank's bladder
which expands into the pre-charged air chamber, keeping
system pressure below the relief valve setting.
� a
STANDARDS COMPLIANCE
FEATURES 0 IAPMO®Listed UPS NSF
Sizes (liters): ❑ 8 ❑ 18 ❑ 32 ❑ 50V NSF®Listed
❑ 75V ❑ 120V ❑ 165V ❑ 320V Certified to
ANSI/NSF 67
(V=vertical,free-standing)
Maximum working water pressure 150 PSI MATERIALS
End connections Threaded NPT
ANSI B1.20.1 Outer shell High Grade Steel
Precharge(adjustable) 40 PSI Coatings Epoxy finish(outer shell)
Connection Brass (sizes: 8 thru 32)
5 year warranty Stainless Steel (sizes: 50V thru 320V)
Bladder Butyl Rubber(FDA approved)
C_
ACCESSORIES OA
❑ BR4 - water pressure reducing valve
❑ TP1100A - temperature&pressure relief valve
❑ P1000A - pressure relief valve
❑ 975XL - reduced pressure backflow preventer
NOTE: Model WXTP tanks are certified to NSF Standard
B B
61 cold, but are suitable for temperatures up to 200°F.
0
C 0
A
WXTP 5OV-320V WXTP 8-32
DIMENSIONS&WEIGHTS(do not include pkg.)
TANK SPECIFICATIONS
MAXIMUM
TOTAL FACTORY DIMENSIONS
MODEL WORKING VOLUME ACCEPTANCE PRECHARGE DIAMETER HEIGHT SYSTEM WEIGHT
NUMBER PRESSURE GALLON VOLUME (PSI) CONNECTION
S in. mm in. mm Ibs. I kg
WX7FP-8 150 PSIG 2.1 0.84 40 8 1/2 216 11 1/2 292 3/4" MNPT 7 3.2
WXTP-18 150 PSIG 4.5 1.8 40 10 254 15 381 3/4" MNPT 10 4.5
WXTP-32 150 PSIG 8.5 3.4 40 12 1/2 318 193/16 487 3/4" MNPT 15 6.8
WXTP-50V 150 PSIG 14 5.6 40 16 406 21 11/16 551 1" FNPT 32 14.5
WXTP-75V 1 150 PSIG 1 20 1 8.0 1 40 16 406 28 13/161 732 1 1" FNPT 39 17.7
WXTP-120V 150 PSIG 32 12.8 40 1 21 533 27 13/16 706 1" FNPT 60 27.2
WXTP-165V 150 PSIG 44 17.6 40 1 21 533 363/16 919 1 1/4" FNPT 72 32.7
WXTP-320V 150 PSIG 85 34.0 40 26 660 447/16 1129 1 1/4" FNPT 140 63.4
NOTE: RELIEF VALVE MUST BE SET AT 150 PSIG MAXIMUM
.• REVISION:
WXT-WXTP 4105
Page 1 of 2
SIZING CHART
Supply WATER HEATER CAPACITY (U.S. gal)
Pressure(psig) 20 30 40 50 60 80 100 120 150 175 200
40 8 8 8 8 8 18 18 18 32 32 32
50 8 8 8 8 8 18 18 18 32 32 32
55 8 8 8 8 8 18 18 18 32 32 32
60 8 8 8 8 18 18 18 18 32 32 32
70 8 8 8 8 18 18 18 18 32 32 32
80 8 8 8 8 18 18 18 32 32 32 32
90 8 8 8 18 18 18 32 32 32 50V 50V
100 8 8 18 18 18 32 32 32 50V 50V 50V
110 8 18 18 18 32 32 32 50V 50V 75V 75V
120 18 18 32 32 32 50V 50V Ji 50V 120V 120V 120V
Supply WATER HEATER CAPACITY (U.S. gal)
Pressure(psig) 240 260 280 300 350 400 450 500 600 800 1000
40 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
50 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
55 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
60 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
70 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
80 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 165V
90 50V 50V 50V 75V 75V 75V 120V 120V 120V 165V 320V
100 75V 75V 75V 75V 120V 120V 120V 165V 165V 320V 320V
110 120V 120V 120V 120V 120V 165V 165V 320V 320V 320V X
120 165V 165V 165V 320V 320V 320V 320V 320V X X X
Based upon 100° F temperature rise(40° F to 140° F) X=multiple tanks required(contact your WILKINS Rep
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted on the cold
water supply and at least 18"from the cold water inlet to the heater. Note: If incoming water pressure is above 40 psi, the
precharge pressure of the expansion tank should be adjusted to equal the incoming water pressure, not to exceed 80 psi.
T&P VALVE
HOSE BIBB
HOT WATER T&P VALVE
HEATER B
MODEL 975XL MODELBRO NOT�7 JR
WATER PRESSURE MODEL 515XL HEATER
REDUCING VALVE
WATER NEESSURE
/ REDUCING VALVE
MODEL WXTP S�
DIRECTION OF FLOW �/ RAIN DIREOTIONOFFLOW RAIN
MODEL WXTP INSTALLATION MODEL WXTP INSTALLATION "V"SERIES
SPECIFICATIONS
The Water Thermal Expansion Tank shall be IAPMO® and NSF® Listed. The outer shell shall be high grade steel
with exterior coating. The bladder shall be FDA approved butyl rubber and prevent water from contact with shell
interior. The assembly shall incorporate a shrader valve for adjustable air precharge and a lead free bronze system
connection. The Water Thermal Expansion Tank shall be a WILKINS Model WXTP.
Page 2 of 2
WILKINS a Zurn Company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 1 L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com