f13-0021 stamped approved
BETTERIDGE RESIDENCE 110 EAST MEADOW DR. #26/27 VAIL, CO 81657 HYDRAULIC CALCULATIONS 6/6/2013 CORPORATION VAIL VALLEY FIRE SPRINKLER CORP. 57 HEREFORD LANE EDWARDS, CO 81632 PH: (970) 914-5014 Hydraulic Calculations Location: 110 EAST MEADOW DR. #26/27, VAIL, COLORADO 81657, Project Name: BETTERIDGE RESIDENCE Drawing Name: 130501__v7.cad Calculation Date: 6/6/2013 for Design Remote Area Location: Residential Area of Application: 328.50ft² (Actual 328.50ft²) Coverage per Sprinkler: 196.00ft² Type of sprinklers calculated: 4 2ND LEVEL Pendent 1Remote Area Number: Occupancy Classification: No. of sprinklers calculated: Density:0.100gpm/ft² Volume of Dry or PreAction System: In-rack Demand: Hose Streams: Type of System: at Node:Type:Allowance at Source Wet N/Aat Node:N/A gpm 10.0 gpm N/A (including Hose Streams where applicable):Total Water Required 75.020@80.37From Water Supply at Node 1: Name of Contractor:VAIL VALLEY FIRE SPRINKLER CO PAUL HUBBARD. VAIL FIREAuthority Having Jurisdiction: Address: Phone Number:Name of designer: 57 HEREFORD LANE,EDWARDS, CO 81632 (970) 914-5014 Notes: 6/6/2013© M.E.P.CAD, Inc.Page 1AutoSPRINK® VR10 v10.0.59.0 3:32:06PM1 Hydraulic Summary Report Description: Residential Job Number: 130501 - Calculation #1 Node Flow(gpm) Total Hose Streams 0.00 Safety MarginRequiredAvailable Node Hose Flow Static Residual Flow Total Demand (gpm)(psi)(psi)(gpm)(psi)(gpm)(psi)(psi)@@Name 1 100.815 75.020 25.795200.00100.000101.000 80.37Water Supply Design EngineerJob Number Total Water Required (Including Hose Allowance) 80.37 Maximum Pressure Unbalance In Loops 0.000 Additional Hose Supplies 0.00 Hose Allowance At Source Supplies 171.75gal Residential 0.100gpm/ft² 196.00ft² 328.50ft² (Actual 328.50ft²) 4 Occupancy Area of Application Coverage Per SprinklerNumber Of Sprinklers Calculated Density Calculation #1 Job Suffix Volume capacity of Dry PipesVolume capacity of Wet Pipes Maximum Velocity Under Ground 29.50 between nodes 10 and 14 Maximum Velocity Above Ground 4.9 K-Factor 19.60 at 16.000 Most Demanding Sprinkler Data System VAIL, COLORADO 81657 Job Site/Building VAIL FIRE110 EAST MEADOW DR. #26/27 AHJ 108221BETTERIDGE RESIDENCE Job State Certification/License NumberJob Name: PAUL HUBBARD.130501 Contractor Contractor Number 028 Name of Contractor: VAIL VALLEY FIRE SPRINKLER CO Address 1 57 HEREFORD LANE Address 2 EDWARDS, CO 81632 Contact Name Contact Title ExtensionPhone (970) 914-5014 FAX E-mail Web-Site CLINT JANSSEN Address 3 Address 1 Address 2 Drawing Name 130501__v7.cad System Flow Demand 80.37 Remote Area(s) Address 3 6/6/2013© M.E.P.CAD, Inc.Page 1AutoSPRINK® VR10 v10.0.59.0 3:31:50PM Hydraulic Graph Water Supply Node: 1 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Date: 6/6/2013 Summary Sheet N 1.85 © M.E.P.CAD, Inc.6/6/2013 Page 2AutoSPRINK® VR10 v10.0.59.0 3:32:07PM Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Residential Job Number: 130501 - Calculation #1 Sprinkler 101 19.60 19.60 4.9 16.000 Sprinkler 102 19.74 19.60 4.9 16.226 Sprinkler 103 20.40 19.60 4.9 17.340 Sprinkler 104 20.63 19.60 4.9 17.721 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.6/6/2013 Page 3AutoSPRINK® VR10 v10.0.59.0 3:32:08PM Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Date: 6/6/2013 Node @ @ Supply Analysis Static (psi) Required Pressure (psi)(gpm) Total DemandAvailable (psi) Flow (gpm) Residual (psi)Name 100.0001 75.02080.37200.00 100.815101.000Water Supply Node Analysis NotesDischarge at Node (gpm) Pressure at Node (psi) Node TypeElevation (Foot)Node Number -9-7 80.3775.020Supply1 19-9 19.6016.000Sprinkler101 20-3 19.7416.226Sprinkler102 22-9 20.4017.340Sprinkler103 25-3 20.6317.721Sprinkler104 -1-11 71.2392 -1-11 70.7703 -0-11 70.1654 1-0 67.8205 2-0 67.1756 18-9 51.8207 18-9 51.1768 18-9 43.5209 25-9 29.22010 20-3 16.50911 20-9 17.43912 20-9 16.74513 25-9 20.12914 25-9 19.10015 © M.E.P.CAD, Inc.6/6/2013 Page 4AutoSPRINK® VR10 v10.0.59.0 3:32:10PM Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Date: 6/6/2013 NotesDischarge at Node (gpm) Pressure at Node (psi) Node TypeElevation (Foot)Node Number 23-1 17.92716 25-9 18.94117 © M.E.P.CAD, Inc.6/6/2013 Page 5AutoSPRINK® VR10 v10.0.59.0 3:32:10PM Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-Factor Elev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 2-0 20-3 2-6 -0.217 0.726 19-9 0-6101 11 ¾• • • • • Route 1 • • • • •(See Notes) 0.8110 16.00019.60 0.290477 Sprinkler 19.60 4.9 E(2-0) 150 5-0 20-9 14-3 -0.217 1.147 20-3 9-311 12 1 (See Notes) 1.0550 16.509 0.08068719.60 E(3-0), EE(2-0) 150 8-0 25-9 16-7 -2.168 4.857 20-9 8-712 14 1 (See Notes) 1.0550 17.43919.74 0.292771 Flow (q) from Route 2 39.34 T(8-0) 150 25-9 8-3 9.091 25-9 8-314 10 1 1.0550 20.12941.03 1.097850 Flow (q) from Route 3 80.37 150 9-0 18-9 27-5 3.035 11.266 25-9 18-510 9 1¼(See Notes) 1.2910 29.220 0.41074480.37 3E(3-0) 150 14-0 18-9 33-8 8.300 18-9 19-89 7 1¼(See Notes) 1.2910 43.520 0.24669461.01 2T(7-0) 150 28-0 2-0 44-9 7.246 8.108 18-9 16-97 6 1½(See Notes) 1.5270 51.820 0.18133780.37 E(5-0), 4Tr(3-0), sCV(11-0), BV 150 1-0 1-0 0.434 0.212 2-0 1-06 5 1½ 1.6100 67.175 0.21175080.37 120 4-11 -0-11 8-8 0.863 1.482 1-0 3-95 4 1½(See Notes) 1.6820 67.820 0.17111780.37 2LtE(2-6) 120 -1-11 1-0 0.434 0.171 -0-11 1-04 3 1½ 1.6820 70.165 0.17111780.37 120 41-8 -1-11 68-9 0.000 0.469 -1-11 27-13 2 3 (See Notes) 3.2600 70.770 0.006819 mecT(20-2) 80.37 fT(21-6) 120 © M.E.P.CAD, Inc.6/6/2013 Page 6AutoSPRINK® VR10 v10.0.59.0 3:32:12PM1 Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-Factor Elev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 149-7 -9-7 247-1 3.324 0.458 -1-11 97-62 1 4 (See Notes) 4.2600 71.239 0.00185380.37 12fE(8-11), 2fT(21-1), S 120 1 0.00 Hose Allowance At Source 80.37 Route 1Total(Pt) 75.020 2-0 20-9 2-6 -0.217 0.736 20-3 0-6102 13 ¾• • • • • Route 2 • • • • •(See Notes) 0.8110 16.22619.74 0.294266 Sprinkler 19.74 4.9 E(2-0) 150 8-0 20-9 8-6 0.695 20-9 0-613 12 1 (See Notes) 1.0550 16.745 0.08173919.74 T(8-0) 150 17.439 Total(Pt)Route 2 2-0 23-1 2-4 -0.138 0.725 22-9 0-4103 16 ¾• • • • • Route 3 • • • • •(See Notes) 0.8110 17.34020.40 0.312904 Sprinkler 20.40 4.9 E(2-0) 150 17-0 25-9 26-10 -1.162 2.336 23-1 9-1016 15 1 (See Notes) 1.0550 17.927 0.08691720.40 3E(3-0), T(8-0) 150 25-9 3-3 1.028 25-9 3-315 14 1 1.0550 19.10020.63 0.316512 Flow (q) from Route 4 41.03 150 20.129 Total(Pt)Route 3 4-0 25-9 4-6 -0.217 1.437 25-3 0-6104 17 ¾• • • • • Route 4 • • • • •(See Notes) 0.8110 17.72120.63 0.319264 Sprinkler 20.63 4.9 T(4-0) 150 25-9 1-10 0.160 25-9 1-1017 15 1 1.0550 18.941 0.08868320.63 150 19.100 Total(Pt)Route 4 46-0 18-9 97-1 7.656 18-9 51-19 8 1 • • • • • Route 5 • • • • •(See Notes) 1.0550 43.520 0.078856 T(8-0) 19.36 4T(8-0), 2E(3-0) 150 © M.E.P.CAD, Inc.6/6/2013 Page 7AutoSPRINK® VR10 v10.0.59.0 3:32:12PM1 Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-Factor Elev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 13-0 18-9 21-10 0.644 18-9 8-108 7 1¼(See Notes) 1.2910 51.176 0.02950319.36 2E(3-0), T(7-0) 150 51.820 Total(Pt)Route 5 © M.E.P.CAD, Inc.6/6/2013 Page 8AutoSPRINK® VR10 v10.0.59.0 3:32:12PM1 Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 1 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1.51 Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90°cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90°Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap 4.87 )(150 1.33 140 1.16 130 0.713 100Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.6/6/2013 Page 9AutoSPRINK® VR10 v10.0.59.0 3:32:11PM1 Hydraulic Calculations Location: 110 EAST MEADOW DR. #26/27, VAIL, COLORADO 81657, Project Name: BETTERIDGE RESIDENCE Drawing Name: 130501__v7.cad Calculation Date: 6/6/2013 for Design Remote Area Location: Residential Area of Application: 219.99ft² (Actual 219.99ft²) Coverage per Sprinkler: 196.00ft² Type of sprinklers calculated: 4 3RD LEVEL Pendent 2Remote Area Number: Occupancy Classification: No. of sprinklers calculated: Density:0.100gpm/ft² Volume of Dry or PreAction System: In-rack Demand: Hose Streams: Type of System: at Node:Type:Allowance at Source Wet N/Aat Node:N/A gpm 10.0 gpm N/A (including Hose Streams where applicable):Total Water Required 78.200@82.91From Water Supply at Node 1: Name of Contractor:VAIL VALLEY FIRE SPRINKLER CO PAUL HUBBARD. VAIL FIREAuthority Having Jurisdiction: Address: Phone Number:Name of designer: 57 HEREFORD LANE,EDWARDS, CO 81632 (970) 914-5014 Notes: 6/6/2013© M.E.P.CAD, Inc.Page 1AutoSPRINK® VR10 v10.0.59.0 3:32:30PM2 Hydraulic Summary Report Description: Residential Job Number: 130501 - Calculation #2 Node Flow(gpm) Total Hose Streams 0.00 Safety MarginRequiredAvailable Node Hose Flow Static Residual Flow Total Demand (gpm)(psi)(psi)(gpm)(psi)(gpm)(psi)(psi)@@Name 1 100.804 78.200 22.604200.00100.000101.000 82.91Water Supply Design EngineerJob Number Total Water Required (Including Hose Allowance) 82.91 Maximum Pressure Unbalance In Loops 0.000 Additional Hose Supplies 0.00 Hose Allowance At Source Supplies 171.75gal Residential 0.100gpm/ft² 196.00ft² 219.99ft² (Actual 219.99ft²) 4 Occupancy Area of Application Coverage Per SprinklerNumber Of Sprinklers Calculated Density Calculation #2 Job Suffix Volume capacity of Dry PipesVolume capacity of Wet Pipes Maximum Velocity Under Ground 20.32 between nodes 8 and 20 Maximum Velocity Above Ground 4.9 K-Factor 19.60 at 16.000 Most Demanding Sprinkler Data System VAIL, COLORADO 81657 Job Site/Building VAIL FIRE110 EAST MEADOW DR. #26/27 AHJ 108221BETTERIDGE RESIDENCE Job State Certification/License NumberJob Name: PAUL HUBBARD.130501 Contractor Contractor Number 028 Name of Contractor: VAIL VALLEY FIRE SPRINKLER CO Address 1 57 HEREFORD LANE Address 2 EDWARDS, CO 81632 Contact Name Contact Title ExtensionPhone (970) 914-5014 FAX E-mail Web-Site CLINT JANSSEN Address 3 Address 1 Address 2 Drawing Name 130501__v7.cad System Flow Demand 82.91 Remote Area(s) Address 3 6/6/2013© M.E.P.CAD, Inc.Page 1AutoSPRINK® VR10 v10.0.59.0 3:32:59PM Hydraulic Graph Water Supply Node: 1 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 2 Date: 6/6/2013 Summary Sheet N 1.85 © M.E.P.CAD, Inc.6/6/2013 Page 2AutoSPRINK® VR10 v10.0.59.0 3:32:31PM Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Residential Job Number: 130501 - Calculation #2 Sprinkler 201 19.60 19.60 4.9 16.000 Sprinkler 202 19.75 19.60 4.9 16.248 Sprinkler 203 21.70 19.60 4.9 19.606 Sprinkler 204 21.86 19.60 4.9 19.905 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.6/6/2013 Page 3AutoSPRINK® VR10 v10.0.59.0 3:32:33PM Job Name: BETTERIDGE RESIDENCE Remote Area Number: 2 Date: 6/6/2013 Node @ @ Supply Analysis Static (psi) Required Pressure (psi)(gpm) Total DemandAvailable (psi) Flow (gpm) Residual (psi)Name 100.0001 78.20082.91200.00 100.804101.000Water Supply Node Analysis NotesDischarge at Node (gpm) Pressure at Node (psi) Node TypeElevation (Foot)Node Number -9-7 82.9178.200Supply1 28-2 19.6016.000Sprinkler201 28-2 19.7516.248Sprinkler202 28-2 21.7019.606Sprinkler203 28-2 21.8619.905Sprinkler204 -1-11 74.3912 -1-11 73.8943 -0-11 73.2804 1-0 70.8475 2-0 70.1896 18-9 54.3547 18-9 48.0308 18-9 53.6289 28-8 16.50918 28-8 17.35719 29-8 32.20220 28-8 20.26621 28-8 21.28922 © M.E.P.CAD, Inc.6/6/2013 Page 4AutoSPRINK® VR10 v10.0.59.0 3:32:34PM Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 2 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-Factor Elev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 2-0 28-8 2-6 -0.217 0.726 28-2 0-6201 18 ¾• • • • • Route 1 • • • • •(See Notes) 0.8110 16.00019.60 0.290477 Sprinkler 19.60 4.9 E(2-0) 150 28-8 10-6 0.847 28-8 10-618 19 1 1.0550 16.509 0.08068719.60 150 31-0 29-8 52-2 -0.434 15.279 28-8 21-219 20 1 (See Notes) 1.0550 17.35719.75 0.292954 Flow (q) from Route 2 39.35 5E(3-0), 2T(8-0) 150 10-0 18-9 25-6 4.733 11.095 29-8 15-620 8 1¼(See Notes) 1.2910 32.20243.56 0.435087 Flow (q) from Route 3 82.91 E(3-0), T(7-0) 150 13-0 18-9 21-10 6.324 18-9 8-108 7 1¼(See Notes) 1.2910 48.030 0.28984666.57 2E(3-0), T(7-0) 150 28-0 2-0 44-9 7.246 8.589 18-9 16-97 6 1½(See Notes) 1.5270 54.354 0.19208482.91 E(5-0), 4Tr(3-0), sCV(11-0), BV 150 1-0 1-0 0.434 0.224 2-0 1-06 5 1½ 1.6100 70.189 0.22430082.91 120 4-11 -0-11 8-8 0.863 1.570 1-0 3-95 4 1½(See Notes) 1.6820 70.847 0.18125882.91 2LtE(2-6) 120 -1-11 1-0 0.434 0.181 -0-11 1-04 3 1½ 1.6820 73.280 0.18125882.91 120 41-8 -1-11 68-9 0.000 0.497 -1-11 27-13 2 3 (See Notes) 3.2600 73.894 0.007223 mecT(20-2) 82.91 fT(21-6) 120 149-7 -9-7 247-1 3.324 0.485 -1-11 97-62 1 4 (See Notes) 4.2600 74.391 0.00196382.91 12fE(8-11), 2fT(21-1), S 120 © M.E.P.CAD, Inc.6/6/2013 Page 5AutoSPRINK® VR10 v10.0.59.0 3:32:36PM2 Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 2 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-Factor Elev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 1 0.00 Hose Allowance At Source 82.91 Route 1Total(Pt) 78.200 4-0 28-8 4-6 -0.217 1.326 28-2 0-6202 19 ¾• • • • • Route 2 • • • • •(See Notes) 0.8110 16.24819.75 0.294632 Sprinkler 19.75 4.9 T(4-0) 150 17.357 Total(Pt)Route 2 2-0 28-8 2-6 -0.217 0.876 28-2 0-6203 21 ¾• • • • • Route 3 • • • • •(See Notes) 0.8110 19.60621.70 0.350565 Sprinkler 21.70 4.9 E(2-0) 150 28-8 10-6 1.022 28-8 10-621 22 1 1.0550 20.266 0.09737821.70 150 25-0 29-8 32-1 -0.434 11.347 28-8 7-122 20 1 (See Notes) 1.0550 21.28921.86 0.353519 Flow (q) from Route 4 43.56 3E(3-0), 2T(8-0) 150 32.202 Total(Pt)Route 3 4-0 28-8 4-6 -0.217 1.600 28-2 0-6204 22 ¾• • • • • Route 4 • • • • •(See Notes) 0.8110 19.90521.86 0.355509 Sprinkler 21.86 4.9 T(4-0) 150 53.628 Total(Pt)Route 4 14-0 18-9 33-8 0.726 18-9 19-89 7 1¼• • • • • Route 5 • • • • •(See Notes) 1.2910 53.62816.34 0.021571 Flow (q) from Route 6 16.34 2T(7-0) 150 52.558 Total(Pt)Route 5 46-0 18-9 97-1 5.598 18-9 51-18 9 1 • • • • • Route 6 • • • • •(See Notes) 1.0550 48.030 0.05765716.34 5T(8-0), 2E(3-0) 150 49.529 Total(Pt)Route 6 © M.E.P.CAD, Inc.6/6/2013 Page 6AutoSPRINK® VR10 v10.0.59.0 3:32:36PM2 Date: 6/6/2013 Job Name: BETTERIDGE RESIDENCE Remote Area Number: 2 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1.51 Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90°cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90°Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap 4.87 )(150 1.33 140 1.16 130 0.713 100Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.6/6/2013 Page 7AutoSPRINK® VR10 v10.0.59.0 3:32:36PM2 CORPORATION 57 HEREFORD LANE EDWARDS, CO 81632 PH: (970) 914-5014 BETTERIDGE RESIDENCE 110 EAST MEADOW DR. #26/27 VAIL, CO 81657 EQUIPMENT SUBMITTAL 6/6/2013 Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems Page 1 of 6 APRIL 2013 TFP443 Worldwide Contacts www.tyco-fire.com General Description The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are decora- tive, fast response, fusible solder sprin- klers designed for use in residential oc- cupancies such as homes, apartments, dormitories, and hotels. The Cover Plate/Retainer Assembly con- ceals the sprinkler operating compo- nents above the ceiling. The flat profile of the Cover Plate provides the optimum aesthetically appealing sprinkler design. Additionally, the concealed design of the Series LFII Residential Flat-Plate Con- cealed Pendent Sprinklers provides 1/2 inch (12,7 mm) vertical adjustment. This adjustment provides a measure of flex- ibility when cutting fixed sprinkler drops. The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are in- tended for use in the following systems: • wet and dry pipe residential sprin- kler systems for one- and two-fam- ily dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprin- kler systems for residential occu- pancies up to and including four sto- ries in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The Series LFII Residential Sprinklers have been designed with heat sensitiv- ity and water distribution characteristics proven to help in the control of residen- tial fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap protects the sprinkler during ceiling installation or finish. After ceiling installation is com- plete, the Protective Cap is removed and the Cover Plate/Retainer Assem- bly is installed. Removing the Protec- tive Cap is required for proper sprinkler performance. Dry Pipe System Application The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler offers a laboratory approved option for design- ing dry pipe residential sprinkler sys- tems, whereas, most residential sprin- klers are laboratory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Flat-Plate Con- cealed Sprinklers (TY2524) need not be increased over the number of design sprinklers (hydraulic design area) speci- fied for wet pipe sprinkler systems, as is customary for density/area sprinkler systems designed per NFPA 13, 13D, or 13R. Consequently, the Series LFII Residen- tial Flat-Plate Concealed Sprinklers (TY2524) offer the features of non-wa- ter filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems de- signed to NFPA 13, 13D, or 13R. Non- water filled pipe will permit options for areas sensitive to freezing. NOTICE The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) described herein must be installed and maintained in compliance with this doc- ument and the applicable standards of the National Fire Protection Association, in addition to the standards of any au- thorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manu- facturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY2524 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. TFP443Page 2 of 6 3-3/16" DIA. (81,0 mm) 1/2" NPT 2-1/2" DIA. (63,5 mm) MOUNTING SURFACE3/16" (4,8 mm) 1/8" GAP (3,2 mm) FACE OF SPRINKLER FITTING 7/8" (22,2 mm) 1-1/8" (28,6 mm) TIP DEFLECTOR IN OPERATED POSITION 1/2" (12,7 mm) THREADED ADJUSTMENT SPRINKLER- SUPPORT CUP ASSEMBLY OPERATED SPRINKLER 1-7/8"±1/4" (47,6 mm ±6,4 mm) SPRINKLER- SUPPORT CUP ASSEMBLY COVER- RETAINER ASSEMBLY COVER PLATE RETAINER DISPOSABLE PROTECTIVE CAP SPRINKLER/SUPPORT CUP ASSEMBLY COVER PLATE/RETAINER ASSEMBLY COVER PLATE EJECTION SPRING RETAINER WITH THREAD DIMPLES SOLDER TAB SEALING ASSEMBLY COMPRESSION SCREW DEFLECTOR (OPERATED POSITION) SPRINKLER WRENCHING AREA SOLDER LINK ELEMENT LEVER DEFLECTOR CAP BODY (1/2" NPT) SADDLE SUPPORT CUP WITH ROLL FORMED THREADS GUIDE PIN GUIDE PIN HOUSING THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE (TY2524) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) FIGURE 2 W-TYPE 18 SPRINKLER WRENCH TFP443 Page 3 of 6 Technical Data Approvals UL and C-UL Listed The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only listed with the Series LFII Concealed Cover Plates having a factory-applied finish. For details on approvals, refer to the De- sign Criteria section. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K=4.9 GPM/psi1/2 (70,6 LPM/bar1/2) Temperature Rating Sprinkler: 160°F (71°C) Cover Plate: 139°F (59°C) Vertical Adjustment 1/2 inch (12,7 mm) Finishes Refer to the Ordering Procedure section. Physical Characteristics Cover Plate/Retainer Assembly: Cover Plate . . . . . . . . . . . . . Copper Ejection Spring ....Stainless Steel Retainer ................Brass Sprinkler/Support Cup Assembly: Body ...................Brass Cap ...................Bronze Saddle . . . . . . . . . . . . . . . . . . Brass Sealing Assembly . . . . . . .Beryllium Nickel w/ TEFLON Soldered Link Halves . . . . . . Nickel Lever ..................Bronze Compression Screw . . . . . . . Brass Deflector . . . . . . . . . . . . . . . Bronze Guide Pin Housing........Bronze Guide Pins .............Bronze Support Cup . . . . . . . . . . . . . . Steel Operation When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup As- sembly. At this point, the Deflector, sup- ported by the Guide Pins, drops down to its operated position. The Solder Link Element of the Sprinkler/ Support Cup Assembly is comprised of two link halves that are soldered togeth- er with a thin layer of solder. When the rated temperature is reached, the sol- der melts and the two link halves sepa- rate, allowing the sprinkler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are UL and C-UL Listed for installation in ac- cordance with this section: Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, re- fer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be accept- able to the authority having jurisdiction. System Type Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems. Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin- kler flow rate are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the mini- mum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. The number of “design sprinklers” spec- ified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable cover- age area • A minimum discharge of 0.1 gpm/ft2. over the “design area” comprised of the four most hydraulically demand- ing sprinklers for the actual coverage areas being protected by the four sprinklers The number of “design sprinklers” specified in NFPA 13 for wet pipe sys- tems is to be applied when designing dry pipe systems. Dry Pipe System Water Delivery When using the Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) in dry pipe sprinkler systems, the time for water delivery must not ex- ceed 15 seconds for the most remote operating sprinkler. Obstruction to Water Distribution. Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity Install sprinklers relative to the ceiling mounting surface as shown in Figure 3. The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup can delay sprinkler op- eration in a fire situation. Sprinkler Spacing The minimum spacing between sprin- klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot ex- ceed the length of the coverage area (Table A) being hydraulically calculated (e.g., a maximum of 12 feet for a 12 ft. x 12 ft. coverage area or 20 feet for a 20 ft. x 20 ft. coverage area.) TFP443Page 4 of 6 Maximum Coverage Area (a) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow and Residual Pressure(b, c) Ordinary Temp Rating 160°F (71°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) 12 x 12(3,7 x 3,7)12(3,7)13 (49,2)7.0 (0,48)Smooth Ceilings 7/8 to 1-1/8 inches. Beamed Ceilings per NFPA 13D 13R, or 13 Installed in beam 7/8 to 1-1/8 inches below bottom of beam Concealed 8 (2,4) 14 x 14(4,3 x 4,3)14(4,3)13 49,2)7.0 (0,48) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49,2) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12.0 (0,83) 20 x 20(6,1 x 6,1)20(6,1)20 (75,7)16.7 (1,15) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pres- sures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Maximum Coverage Area (a) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) DRY PIPE SYSTEM Minimum Flow and Residual Pressure(b) Ordinary Temp Rating 160°F (71°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,7 x 3,7) 12 (3,7) 15 (56,8) 9.4 (0,65)Smooth Ceilings 7/8 to 1-1/8 inches. Beamed Ceilings per NFPA 13D 13R, or 13 Installed in beam 7/8 to 1-1/8 inches below bottom of beam Concealed 8 (2,4) 14 x 14(4,3 x 4,3)14(4,3)15 (56,8)9.4 (0,65) 16 x 16 (4,9 x 4,9) 16 (4,9) 16 (60,6) 10,7 (0,74) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12.0 (0,83) 20 x 20 (6,1 x 6,1) 20 (6,1) 21 (79,5) 18,4 (1,27) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP443 Page 5 of 6 Installation The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must be installed in accordance with this section: General Instructions Damage to the Solder Link Element dur- ing installation can be avoided by han- dling the sprinkler by the Support Cup only; that is, do not apply pressure to the Solder Link Element (Figure 1). A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min- imum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insuf- ficient adjustment in the Cover Plate/ Retainer Assembly by under- or over- tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install pendent sprinklers in the pendent position, with the center- line of the sprinkler perpendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe-thread sealant ap- plied to the pipe threads, and using the W-Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler/Sup- port Cup Assembly into the fitting. The W-Type 18 Wrench accepts a 1/2 inch ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec- tive Cap helps prevent damage to the Deflector and Guide Pins during ceiling installation and/or during application of the finish coating of the ceiling. NOTICE As long as the protective Cap remains in place, the system is considered “Out Of Service”. Step 5. After the ceiling has been com- pleted with the 2-1/2 inch (63 mm) diam- eter hole and in preparation for install- ing the Cover Plate/Retainer Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely. If the sprinkler has been damaged and the deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 6. Screw on the Cover Plate/Re- tainer Assembly until its flange contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate/Retainer Assembly cannot be engaged with the Mounting Cup or the Cover Plate/Retainer Assem- bly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinkler (TY2524) must be maintained and serviced in accordance with ths section: Before closing a fire protection system main control valve for maintenance work on the fire protection system that it con- trols, obtain permission to shut down the affected fire protection system from the proper authorities and notify all person- nel who may be affected by this action. Absence of a Cover Plate may delay the sprinkler operation in a fire situation. The owner must assure that the sprin- klers are not used for hanging any ob- jects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-opera- tion in the event of a fire or inadvertent operation may result. When properly installed, there is a nomi- nal 1/8 inch (3,2 mm) air gap between the lip of the Cover Plate and the ceil- ing, as shown in Figure 3. This air gap is necessary for proper operation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling needs repainting after sprinkler installation, exercise care to ensure that the new paint does not seal off any of the air gap. Failure to do so may impair sprinkler operation. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted units. Non-factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire. Do not pull the Cover Plate relative to the Retainer. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied or overheated sprinklers must be replaced. Care must be exercised to avoid dam- age to the sprinklers - before, during, and after installation. Sprinklers dam- aged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan- dards of any other authorities having ju- risdiction. Contact the installing contrac- tor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. General Description TheSeriesTY-FRB,5.6K-Factor, HorizontalandVerticalSidewallSprin- klersdescribedinthisdatasheetare quickresponse-standardcoverage, decorative3mmglassbulbtypespray sprinklersdesignedforuseinlightand ordinaryhazard,commercialoccupan- ciessuchasbanks,hotels,shopping malls,etc.Theyaredesignedforin- stallationalongawallorthesideofa beamandjustbeneathasmoothceil- ing.Sidewallsprinklersarecommonly usedinsteadofpendentorupright sprinklersduetoaestheticsorbuilding constructionconsiderations,where pipingacrosstheceilingisnotdesir- able. TherecessedversionoftheSeries TY-FRBHorizontalSidewallSprinkler isintendedforuseinareaswitha finishedwall.Itusesatwo-pieceStyle 10RecessedEscutcheonwith1/2inch (12,7mm)ofrecessedadjustmentor upto3/4inch(19,1mm)oftotaladjust- mentfromtheflushsidewallposition, oratwo-pieceStyle20RecessedEs- cutcheonwith1/4inch(6,4mm)of recessedadjustmentorupto1/2inch (12,7mm)oftotaladjustmentfromthe flushsidewallposition.Theadjust- mentprovidedbytheRecessedEs- cutcheonreducestheaccuracyto whichthefixedpipenipplestothe sprinklersmustbecut. Corrosionresistantcoatings,where applicable,areutilizedtoextendthe lifeofcopperalloysprinklersbeyond thatwhichwouldotherwisebeob- tainedwhenexposedtocorrosiveat- mospheres.Althoughcorrosionresis- tantcoatedsprinklershavepassedthe standardcorrosiontestsoftheappli- cableapprovalagencies,thetestingis notrepresentativeofallpossiblecor- rosiveatmospheres.Consequently,it isrecommendedthattheenduserbe consultedwithrespecttothesuitability ofthesecoatingsforanygivencorro- siveenvironment.Theeffectsofambi- enttemperature,concentrationof chemicals,andgas/chemicalvelocity, shouldbeconsidered,asaminimum, alongwiththecorrosivenatureofthe chemicaltowhichthesprinklerswillbe exposed. WARNINGS TheSeriesTY-FRBSprinklersde- scribedhereinmustbeinstalledand maintainedincompliancewiththis document,aswellaswiththeapplica- blestandardsoftheNationalFirePro- tectionAssociation,inadditiontothe standardsofanyotherauthoritieshav- ingjurisdiction.Failuretodosomay impairtheperformanceofthesede- vices. Theownerisresponsibleformaintain- ingtheirfireprotectionsystemandde- vicesinproperoperatingcondition. Theinstallingcontractororsprinkler manufacturershouldbecontacted withanyquestions. Model/Sprinkler Identification Numbers TY3331-Horizontal TY3431-Vertical Technical Data Approvals ULandC-ULListed. FM,LPCB,andNYCApproved. (RefertoTableAforcompleteap- provalinformationincludingcorrosion resistantstatus.) MaximumWorkingPressure RefertoTableB. DischargeCoefficient K=5.6GPM/psi1/2 (80,6LPM/bar1/2) TemperatureRatings RefertoTableA. Finishes Sprinkler:RefertoTableA. RecessedEscutcheon:WhiteCoated, ChromePlated,orBrassPlated. SeriesTY-FRB—5.6K-factor HorizontalandVerticalSidewallSprinklers QuickResponse,StandardCoverage Page1of6 TFP176APRIL,2006 TechnicalServices:Tel:(800)381-9312/Fax:(800)791-5500 IMPORTANT AlwaysrefertoTechnicalData SheetTFP700forthe“INSTALLER WARNING”thatprovidescautions withrespecttohandlingandinstal- lationofsprinklersystemsandcom- ponents.Improperhandlingandin- stallationcanpermanentlydamage asprinklersystemoritscompo- nentsandcausethesprinklertofail tooperateinafiresituationorcause ittooperateprematurely. PhysicalCharacteristics Frame.............Bronze Button.........Brass/Copper SealingAssembly.......... .....BerylliumNickelw/Teflon† Bulb...............Glass CompressionScrew.....Bronze HSWDeflector........Bronze VSWDeflector........Copper Patents U.S.A.5,810,263 Operation TheglassBulbcontainsafluidwhich expandswhenexposedtoheat.When theratedtemperatureisreached,the fluidexpandssufficientlytoshatterthe glassBulb,allowingthesprinklerto activateandwatertoflow. Page2of6 TFP176 TYPE TEMP.BULB LIQUID NATURAL BRASS CHROME PLATED WHITE*** POLYESTER 155°F/68°C 175°F/79°C 200°F/93°C SPRINKLERFINISH(SeeNote11) RECESSED HORIZ. SIDEWALL (TY3331)* Figure3 135°F/57°C Orange Red Yellow Green 1,2,4,9,10 NOTES: 1.ListedbyUnderwritersLaboratories,Inc.(UL)asQuickResponseSprinklersforuseinLightandOrdinaryHazardOccupanciesata 4to12inch(100to300mm)topofdeflectortoceilingdistance. 2.ListedbyUnderwritersLaboratoriesInc.foruseinCanada(C-UL)asQuickResponseSprinklersforuseinLightandOrdinary HazardOccupanciesata4to12inch(100to300mm)topofdeflectortoceilingdistance. 3.ApprovedbyFactoryMutualResearchCorporation(FM)asQuickResponseSprinklersforuseinLightHazardOccupanciesata 4to12inch(100to300mm)topofdeflectortoceilingdistance. 4.ApprovedbytheLossPreventionCertificationBoard(LPCBRef.No.007a/04)ata4to6inch(100to150mm)topof deflectortoceilingdistance.TheLPCdoesnotratethethermalsensitivityofhorizontalsidewallsprinklers. 5.ListedbyUnderwritersLaboratories,Inc.asQuickResponseSprinklersforuseinLightandOrdinaryHazardOccupancies. 6.ListedbyUnderwritersLaboratoriesforuseinCanada(C-UL)asQuickResponseSprinklersforuseinLightandOrdinaryHazard Occupancies. 7.ApprovedbyFactoryMutualResearchCorporation(FM)asQuickResponseSprinklersforuseinLightHazardOccupancies. 8.ApprovedbytheLossPreventionCertificationBoard(LPCBRef.No.094a/06&007a/04)asQuickResponseSprinklers. 9.ApprovedbytheCityofNewYorkunderMEA354-01-E. 10.ApprovedbytheLossPreventionCertificationBoard(LPCBRef.No.094a/06)ata4to6inch(100to150mm)topof deflectortoceilingdistance.TheLPCdoesnotratethethermalsensitivityofhorizontalsidewallsprinklers. 11.WherePolyesterCoatedandLeadCoatedSprinklersarenotedtobeULandC-ULListed,thesprinklersareULandC-ULListed asCorrosionResistantSprinklers.WhereLeadCoatedSprinklersarenotedtobeFMApproved,thesprinklersareFMApprovedas CorrosionResistantSprinklers. *InstalledwithStyle10(1/2"NPT)3/4"TotalAdjustmentRecessedEscutcheon. **InstalledwithStyle20(1/2"NPT)1/2"TotalAdjustmentRecessedEscutcheon. ***Frameanddeflectoronly.Listingsandapprovalsapplytocolor(SpecialOrder). TABLEA LABORATORYLISTINGSANDAPPROVALS LEAD COATED N/A 1,2,3,9 K 5.6 1/2" NPT HORIZ. SIDEWALL (TY3331) 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue 1,2,3,4,9,10 5.6 1/2" NPT VERTICAL SIDEWALL (TY3431) Installed Pendent or Upright 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C 286°F/141°C Blue Green Yellow Red Orange 5,6,7,8,9 5,6,7,9 Orange Red Yellow Green RECESSED HORIZ. SIDEWALL (TY3331)** Figure4 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C 1,2,3,4,9 N/A 1,2,3,9 1,2,9 † D u P o n t R e g i s t e r e d T r a d e m a r k Design Criteria TheSeriesTY-FRBHorizontaland VerticalSidewallSprinklersarein- tendedforfireprotectionsystemsde- signedinaccordancewiththestand- ardinstallationrulesrecognizedbythe applicableListingorApprovalagency (e.g.,ULListingisbasedonthere- quirementsofNFPA13,andFMAp- provalisbasedontherequirementsof FM’sLossPreventionDataSheets). OnlytheStyle10or20RecessedEs- cutcheon,asapplicable,istobeused forrecessedhorizontalinstallations. TFP176 Page3of6 FIGURE1 5.6K-FACTORQUICKRESPONSE SERIESTY-FRBHORIZONTALSIDEWALL(TY3331)SPRINKLERS 1-Frame 2-Button 3-Sealing Assembly 4-Bulb 5-Compression Screw 6-Deflector *Temperatureratingis indicatedondeflectoror adjacenttoorificeseat onframe. **Pipethread connectionsperISO7/1 canbeprovidedon specialrequest. 24 5 PLATESEATING ESCUTCHEON (11,1 mm) NOMINAL MAKE-IN SURFACE 13 2-7/8" DIA. ESCUTCHEON 10or 20 RECESSED (73,0mm) WRENCH FLATS 1-1/2" (38,1mm) 2-3/16" (55,6mm) 7/16"1-13/16" (46,0mm) STYLE HAT DEFLECTOR 1/2" NPT 6 CENTERLINE WATERWAY OFSPRINKLER 9/16" (14,3mm) * ** TYPE NATURAL BRASS CHROME PLATED WHITE POLYESTER SPRINKLERFINISH RECESSEDHORIZ. SIDEWALL(TY3331) NOTES: 1.Themaximumworkingpressureof250psi(17,2bar)onlyappliestotheListingbyUnderwritersLaboratories,Inc.(UL);theListingby UnderwritersLaboratories,Inc.foruseinCanada(C-UL);and,theApprovalbytheCityofNewYork. TABLEB,MAXIMUMWORKINGPRESSURE LEAD COATED N/A K 5.6 1/2" NPT HORIZONTALSIDEWALL (TY3331) VERTICALSIDEWALL (TY3431)175PSI(12,1BAR) 175PSI(12,1BAR) 250PSI(17,2BAR) OR 175PSI(12,1BAR) (SEENOTE1) Installation TheSeriesTY-FRBSprinklersmust beinstalledinaccordancewiththefol- lowinginstructions: NOTES Donotinstallanybulbtypesprinklerif thebulbiscrackedorthereisalossof liquidfromthebulb.Withthesprinkler heldhorizontally,asmallairbubble shouldbepresent.Thediameterofthe airbubbleisapproximately1/16inch (1,6mm)forthe135°F/57°Cto3/32 inch(2,4mm)forthe286°F/141°C temperatureratings. Aleaktight1/2inchNPTsprinklerjoint shouldbeobtainedwithatorqueof7 to14ft.lbs.(9,5to19,0Nm).Amaxi- mumof21ft.lbs.(28,5Nm)oftorque maybeusedtoinstallsprinklerswith 1/2NPTconnections.Higherlevelsof torquemaydistortthesprinklerand causeleakageorimpairmentofthe sprinkler. Donotattempttomake-upforinsuffi- cientadjustmentintheescutcheon platebyunder-orover-tighteningthe sprinkler.Readjustthepositionofthe sprinklerfittingtosuit. The SeriesTY-FRBHorizontaland VerticalSidewallSprinklers mustbe installedinaccordancewiththefollow- inginstructions. Step1.Horizontalsidewallsprinklers aretobeinstalledinthehorizontal positionwiththeircenterlineofwater- wayperpendiculartothebackwalland paralleltotheceiling.Theword“TOP” ontheDeflectoristofacetowardsthe ceiling. Verticalsidewallsprinklersaretobe installedinthependentoruprightpo- sitionwiththearrowontheDeflector pointingawayfromthewall. Step2.Withpipethreadsealantap- pliedtothepipethreads,handtighten thesprinklerintothesprinklerfitting. Step3.Tightenthesprinklerintothe sprinklerfittingusingonlytheW-Type 6SprinklerWrench(Ref.Figure5), WithreferencetoFigure1or2,the W-Type6SprinklerWrenchistobe appliedtothewrenchflats. The SeriesTY-FRBRecessedHori- zontalSidewallSprinklers mustbe installedinaccordancewiththefollow- inginstructions. StepA.Recessedhorizontalsidewall sprinklersaretobeinstalledinthe horizontalpositionwiththeircenterline ofwaterwayperpendiculartotheback wallandparalleltotheceiling.The word“TOP”ontheDeflectoristoface towardstheceiling. StepB.AfterinstallingtheStyle10or 20MountingPlateoverthesprinkler threads,handtightenthesprinklerinto thesprinklerfitting. StepC.Tightenthesprinklerintothe sprinklerfittingusingonlytheW-Type 7RecessedSprinklerWrench(Ref. Figure6).WithreferencetoFigure1, theW-Type7RecessedSprinkler Wrenchistobeappliedtothesprinkler wrenchflats. StepD.Aftertheceilinghasbeenin- stalledorthefinishcoathasbeenap- plied,slideontheStyle10or20Clo- sureovertheSeriesTY-FRBSprinkler andpushtheClosureovertheMount- ingPlateuntilitsflangecomesincon- tactwiththeceiling Careand Maintenance TheSeriesTY-BFRSprinklersmust bemaintainedandservicedinaccord- ancewiththefollowinginstructions: NOTES Beforeclosingafireprotectionsystem maincontrolvalveformaintenance workonthefireprotectionsystemthat itcontrols,permissiontoshutdown theaffectedfireprotectionsystem mustbeobtainedfromtheproper authoritiesandallpersonnelwhomay beaffectedbythisactionmustbeno- tified. Theownermustassurethatthesprin- klersarenotusedforhangingofany objects;otherwise,non-operationin theeventofafireorinadvertentopera- tionmayresult. Absenceofanescutcheon,whichis usedtocoveraclearancehole,may delaythetimetosprinkleroperationin afiresituation. Sprinklersthatarefoundtobeleaking orexhibitingvisiblesignsofcorrosion Page4of6 TFP176 FIGURE2 5.6K-FACTORQUICKRESPONSE SERIESTY-FRBVERTICALSIDEWALL(TY3431)SPRINKLERS 1-Frame 2-Button 3-Sealing Assembly 4-Bulb 5-Compression Screw 6-Deflector 7-EjectionSpring *Temperatureratingisindicatedondeflectororadjacenttoorificeseatonframe. **PipethreadconnectionsperISO7/1canbeprovidedonspecialrequest. PLATESEATING ESCUTCHEON WRENCH FLATS (11,1 mm) NOMINAL MAKE-INSURFACENPT 1/2" SECTIONPENDENTUPRIGHT CROSS 3 1 2 5 4 6* 7 (55,6mm) 2-3/16" (38,1mm) 1-1/2" SHOWNSHOWN ** FROMANDBE PERPENDICULAR POINTAWAY TOTHE BACK WALLSURFACE ARROWMUST 7/16" 2-3/16" (55,6mm) mustbereplaced. Automaticsprinklersmustneverbe painted,plated,coatedorotherwise alteredafterleavingthefactory.Modi- fiedsprinklersmustbereplaced. Sprinklersthathavebeenexposedto corrosiveproductsofcombustion,but havenotoperated,shouldbereplaced iftheycannotbecompletelycleaned bywipingthesprinklerwithaclothor bybrushingitwithasoftbristlebrush. Caremustbeexercisedtoavoiddam- agetothesprinklers-before,during, andafterinstallation.Sprinklersdam- agedbydropping,striking,wrench twist/slippage,orthelike,mustbere- placed.Also,replaceanysprinkler thathasacrackedbulborthathaslost liquidfromitsbulb.(Ref.Installation Section). Frequentvisualinspectionsarerec- ommendedtobeinitiallyperformedfor corrosionresistantcoatedsprinklers, aftertheinstallationhasbeencom- pleted,toverifytheintegrityofthecor- rosionresistantcoating.Thereafter, annualinspectionsperNFPA25 shouldsuffice;however,insteadofin- spectingfromthefloorlevel,arandom samplingofclose-upvisualinspec- tionsshouldbemade,soastobetter determinetheexactsprinklercondi- tionandthelongtermintegrityofthe TFP176 Page5of6 FIGURE3 SERIESTY-FRBRECESSEDHORIZONTALSIDEWALLSPRINKLER WITHTWO-PIECE3/4INCHTOTALADJUSTMENT STYLE10RECESSEDESCUTCHEON FIGURE5 W-TYPE6SPRINKLERWRENCH WRENCH RECESS (END"A"USEDFOR 1/2"NPT MODELS) FIGURE6 W-TYPE7RECESSED SPRINKLERWRENCH RECESS WRENCH WITHSPRINKLER ENGAGEMENT IN TOENSURE WRENCHING AREA PUSHWRENCH MOUNTING 3/4"(19,1mm) 1-1/4"(31,8 mm) PLATE CLOSURE SURFACE MOUNTING (73,0 mm) 2-1/4"DIA. (57,2 mm) 1/4"(6,4 mm) 3/4"(19,1mm) (3,2mm) 1/8" 5/8±1/4" FACEOF FITTING SPRINKLER (15,9±6,4mm) 2-7/8"DIA. SERIES TY-FRB FIGURE4 SERIESTY-FRBRECESSEDHORIZONTALSIDEWALLSPRINKLER WITHTWO-PIECE1/2INCHTOTALADJUSTMENT STYLE20RECESSEDESCUTCHEON MOUNTING 1"(25,4mm) 1-1/4"(31,8 mm) PLATE CLOSURE SURFACE MOUNTING (73,0 mm) 2-1/4"DIA. (57,2 mm) 1/4"(6,4 mm) 1/2"(12,7mm) (3,2mm) 1/8" 1/2±1/8" FACEOF FITTING SPRINKLER (12,7±3,2mm) 2-7/8"DIA. SERIES TY-FRB corrosionresistantcoating,asitmay beaffectedbythecorrosiveconditions present. Theownerisresponsibleforthein- spection,testing,andmaintenanceof theirfireprotectionsystemandde- vicesincompliancewiththisdocu- ment,aswellaswiththeapplicable standardsoftheNationalFireProtec- tionAssociation(e.g.,NFPA25),in additiontothestandardsofanyother authoritieshavingjurisdiction.Thein- stallingcontractororsprinklermanu- facturershouldbecontactedrelative toanyquestions. Itisrecommendedthatautomatic sprinklersystemsbeinspected, tested,andmaintainedbyaqualified InspectionServiceinaccordancewith localrequirementsand/ornational codes. Limited Warranty ProductsmanufacturedbyTycoFire& BuildingProducts(TFBP)arewar- rantedsolelytotheoriginalBuyerfor ten(10)yearsagainstdefectsinmate- rialandworkmanshipwhenpaidfor andproperlyinstalledandmaintained undernormaluseandservice.This warrantywillexpireten(10)years fromdateofshipmentbyTFBP.No warrantyisgivenforproductsorcom- ponentsmanufacturedbycompanies notaffiliatedbyownershipwithTFBP orforproductsandcomponentswhich havebeensubjecttomisuse,improper installation,corrosion,orwhichhave notbeeninstalled,maintained,modi- fiedorrepairedinaccordancewithap- plicableStandardsoftheNationalFire ProtectionAssociation,and/orthe standardsofanyotherAuthorities HavingJurisdiction.Materialsfound byTFBPtobedefectiveshallbeeither repairedorreplaced,atTFBP’ssole option.TFBPneitherassumes,nor authorizesanypersontoassumeforit, anyotherobligationinconnectionwith thesaleofproductsorpartsofprod- ucts.TFBPshallnotberesponsiblefor sprinklersystemdesignerrorsorinac- curateorincompleteinformationsup- pliedbyBuyerorBuyer’srepre- sentatives. InnoeventshallTFBPbeliable,in contract,tort,strictliabilityorunder anyotherlegaltheory,forincidental, indirect,specialorconsequentialdam- ages,includingbutnotlimitedtolabor charges,regardlessofwhetherTFBP wasinformedaboutthepossibilityof suchdamages,andinnoeventshall TFBP’sliabilityexceedanamount equaltothesalesprice. Theforegoingwarrantyismadeinlieu ofanyandallotherwarranties,ex- pressorimplied,includingwarranties ofmerchantabilityandfitnessforapar- ticularpurpose. Thislimitedwarrantysetsforththeex- clusiveremedyforclaimsbasedon failureofordefectinproducts,materi- alsorcomponents,whethertheclaim ismadeincontract,tort,strictliability oranyotherlegaltheory. Thiswarrantywillapplytothefullex- tentpermittedbylaw.Theinvalidity,in wholeorpart,ofanyportionofthis warrantywillnotaffecttheremainder. Ordering Procedure Whenplacinganorder,indicatethe fullproductname.RefertothePrice ListforcompletelistingofPartNum- bers. Contactyourlocaldistributorforavail- ability. SprinklerAssemblieswithNPT ThreadConnections: Specify:(SpecifyModel/SIN),Quick Response,(specifyK-factor),(specify temperaturerating),SeriesTY-FRB (specifyHorizontalSidewallorVertical Sidewall)Sprinklerwith(specifytype offinishorcoating),P/N(specifyfrom TableC). RecessedEscutcheon: Specify:Style(10or20)Recessed Escutcheonwith(specify*)finish,P/N (specify*). *RefertoTechnicalDataSheetTFP770. SprinklerWrench: Specify:W-Type6SprinklerWrench, P/N56-000-6-387. Specify:W-Type7SprinklerWrench, P/N56-850-4-001. Page6of6 TFP176 TYCOFIRE&BUILDINGPRODUCTS,451NorthCannonAvenue,Lansdale,Pennsylvania19446 P/N57—XXX—X—XXX 155°F/68°C155 TEMPERATURE RATING 135°F/57°C1351 SPRINKLER TABLEC PARTNUMBERSELECTION SERIESTY-FRBHORIZONTALANDVERTICALSIDEWALLSPRINKLERS 175°F/79°C 286 200°F/93°C200 286°F/141°C 175 WHITEPOLYESTER NATURALBRASS 9 4 MODEL/SIN CHROMEPLATED 7 LEADCOATED 378 HORIZONTALSIDEWALL 375 VERTICALSIDEWALL TY3331 TY3431 3 WHITERAL9010)* *EasternHemispheresalesonly. AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 4 All of the advantages found in copper as a metal have been capitalized to the utmost in the manufacture of NIBCO Fittings. Because of the accuracy of construc tion and design, copper plumbing is more efficient and less expensive. NIBCO manufactures nine general types of fittings: Wrot Pressure; Cast Pressure; Wrot Drainage; Cast Drainage; Flanges; Flared Tube; Threaded Bronze; Insert Fittings for PEX; Barbed Insert Fittings for Polybutylene. Each has its particular place and use and each offers its own advantages when used for the proper service requirement. ALLOY AND FINISH — NIBCO Fittings are made from highest quality raw materials available — Cast Fittings are made from Copper Alloy C84400 which consists of 81% Copper, 7% Lead, 3% Tin, and 9% Zinc per ASTM Specification B584. Wrot Copper Fittings are made from commercially pure copper mill products per ASTM Specifications B75 Alloy C12200. NIBCO fittings are produced to meet requirements of applicable standards wherever practicable. NIBCO brand wrot and cast fittings are manufactured in the U.S.A. and Mexico. The manufacturing plants at Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico are registered to ISO 9002 quality standards. Following is suggested phrasing to be incorporated in your specifications or bills of material for Copper Tube Fittings. WROT SOLDER JOINT FITTINGS — “Wrot Solder Joint Fittings shall be produced to one of the following specifications: 1. Material and workmanship shall be in accordance with ASME/ANSI B16.22; Wrought Copper and Copper Alloy Solder Joint Pressure Fittings.” Specifications 2. The dimensional, material and workmanship shall meet the requirements of MSS SP-104; Wrought Copper Solder Joint Pressure Fittings.” 3. The dimensional, material and workmanship of 5"–12" copper fittings shall meet the requirements of MSS SP-109 “Welded Fabricated Copper Solder Joint Pressure Fittings.” 4. Certified to ANSI/NSF 61. CAST COPPER ALLOY SOLDER JOINT FITTINGS — “Cast Copper Alloy Solder Joint Fittings shall be in accor dance with ANSI Std. B16.18.” WROT DRAINAGE FITTINGS — “Wrot Drainage Fittings shall be in accordance with ASME/ANSI Std. B16.29.” CAST COPPER ALLOY SOLDER JOINT DRAINAGE FITTINGS — “Cast Copper Alloy Solder Joint Drainage Fittings shall be in accordance with ASME Std. B16.23.” CAST COPPER ALLOY FLARED TUBE FITTINGS — “Cast Copper Alloy Flared Tube Fittings shall be in accor- dance with ASME/ANSI Std. B16.26. CAST COPPER ALLOY FLANGES AND FLANGED FITTINGS— CLASS 150 — Cast Copper Alloy Flanges and Flanged Fittings shall meet the requirements of MSS SP-106 and/or the workmanship and dimensions of Federal Specifications WW-F-406 or ASME Std. B16.24. CLASS 125 — Material, workmanship and dimensions of flanges shall be in accordance with MSS SP-106. CAST BRONZE THREADED FITTINGS — “Cast Bronze Threaded Fittings shall be in accordance with ANSI/ASME B16.15.” POLYBUTYLENE COPPER INSERT TYPE VALVES AND FITTINGS — “Wrot Copper Insert Fittings shall be manufactured per the following specifications: MSS SP-103 or ASTM F1380.” NIBCO Copper Tube Fittings are all produced to above Standards. To simplify, write your specifications to read: “Copper Tube Fittings to be in accordance with specifications as outlined in NIBCO Catalog c-cf-0602.” WROT COPPER MEDICAL MEDICAL GAS SYSTEM COMPONENTS — Wrot copper fittings that are to be installed in medical gas applications shall be prepared in accordance with NFPA 99, Health Care Facilities Gas and Vacuum Systems and the Compressed Gas Association, Pamphlet G4.1. Packaging shall be adequately protective and include labeling that identifies the preparer and states that the product has been cleaned and bagged for oxygen or med gas service. For technical information and dimensions refer to the engineering section contained in this catalog. Revision 3/29/04 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 6 703-2 Fitting Adapter Ftg x F – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/2 x 1/4 0.11 17/32 3/4 x 1/2 0.12 19/16 1 x 3/4 0.38 131/32 1 x 1/2 0.15 17/16 2 1/2 1.65 215/16 3 2.47 31/4 703-5 Special Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.16 3/4 3/4 0.24 31/32 703-5B Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.15 3/4 ADAPTERS 603 Adapter C x F – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 0.03 13/32 1/8 x 1/4 0.03 1/2 1/4 0.03 5/8 1/4 x 3/8 0.05 21/32 3/8 0.04 11/16 3/8 x 1/2 0.09 29/32 3/8 x 1/4 0.03 9/16 1/2 0.09 27/32 1/2 x 3/4 0.14 1 1/2 x 3/8 0.04 17/32 1/2 x 1/4 0.05 1/2 5/8 x 3/4 0.12 29/32 5/8 x 1/2 0.11 3/4 3/4 0.15 29/32 3/4 x 1 0.21 11/8 3/4 x 1/2 0.10 5/8 1 0.24 31/32 1 x 1 1/4 0.28 17/32 1 x 3/4 0.19 25/32 1 x 1/2 0.24 5/8 1 1/4 0.33 13/32 1 1/4 x 1 1/2 0.40 11/4 1 1/4 x 1 0.27 31/32 1 1/2 0.44 11/8 1 1/2 x 2 0.50 11/32 2 0.63 13/32 2 x 1 1/2 0.74 13/16 2 1/2 1.13 – 3 1.94 – 703 Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/4 x 1/2 0.13 27/32 1/2 x 1 0.30 1 3/4 x 1 1/4 0.55 11/8 3/4 x 3/8 0.17 3/4 1 x 1 1/2 0.68 13/32 1 1/4 x 1 0.27 31/32 1 1/4 x 3/4 0.29 3/4 1 1/2 x 2 0.78 11/32 1 1/2 x 1 0.37 25/32 1 1/2 x 1 1/4 0.47 11/4 2 x 1 1/4 0.76 27/32 2 1/2 1.62 13/8 3 2.34 11/2 4 4.05 19/16 603-2 Fitting Adapter Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/4 0.03 13/32 3/8 0.06 13/16 1/2 0.09 17/16 1/2 x 3/8 0.05 11/4 3/4 0.13 111/16 1 0.27 21/32 1 1/4 0.31 21/8 1 1/2 0.43 25/16 2 0.61 217/32 Consult price sheet for Made to Order items and for minimum order quantities. Revision 2/6/07 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 9 Consult price sheet for Made to Order items and for minimum order quantities. CAPS 617 Tube Cap C – Wrot APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES 1/8 0.01 1/32 1/4 0.01 3/32 3/8 0.01 3/32 1/2 0.02 3/32 5/8 0.03 1/8 3/4 0.04 1/8 1 0.07 5/32 1 1/4 0.10 3/32 1 1/2 0.16 1/8 2 0.27 5/32 2 1/2 0.50 7/32 3 0.78 7/32 4 1.66 1/4 717 Tube Cap C – Cast APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES 5 5.48 7/16 6 9.07 17/32 717-D Drain Cap – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.06 21/32 COUPLINGS 600 Reducing Coupling C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 x 3/16 O.D. 0.01 5/32 5/16 O.D. x 1/8 0.01 3/16 1/4 x 5/16 O.D. 0.01 3/16 1/4 x 1/8 0.01 3/16 3/8 x 1/4 0.02 3/16 3/8 x 5/16 O.D. 0.01 1/4 3/8 x 1/8 0.01 1/4 1/2 x 3/8 0.03 3/16 1/2 x 1/4 0.02 1/4 1/2 x 1/8 0.03 11/32 5/8 x 1/2 0.05 3/16 5/8 x 3/8 0.04 11/32 5/8 x 1/4 0.03 13/32 3/4 x 5/8 0.07 3/16 3/4 x 1/2 0.06 9/32 3/4 x 3/8 0.06 3/8 3/4 x 1/4 0.05 11/32 1 x 3/4 0.11 11/32 1 x 5/8 0.09 3/8 1 x 1/2 0.10 11/32 1 x 3/8 0.10 13/32 1 1/4 x 1 0.16 5/16 1 1/4 x 3/4 0.18 17/32 1 1/4 x 5/8 0.18 5/8 1 1/4 x 1/2 0.14 7/16 1 1/2 x 1 1/4 0.23 5/16 1 1/2 x 1 0.22 9/16 1 1/2 x 3/4 0.20 3/8 1 1/2 x 1/2 0.19 1/2 2 x 1 1/2 0.41 9/16 2 x 1 1/4 0.35 11/16 2 x 1 0.37 7/16 2 x 3/4 0.34 17/32 2 x 1/2 0.35 23/32 2 1/2 x 2 0.59 9/16 2 1/2 x 1 1/2 0.65 11/16 2 1/2 x 1 1/4 0.65 13/16 2 1/2 x 1 0.73 29/32 Continues… APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 3 x 2 1/2 0.98 1/2 3 x 2 1.06 15/16 3 x 1 1/2 0.92 11/32 3 1/2 x 3 1.52 1/2 4 x 3 1/2 2.12 19/32 4 x 3 1.92 27/32 4 x 2 1/2 1.77 1 4 x 2 1.92 11/4 5 x 4 3.50 331/32 5 x 3 3.18 115/32 5 x 2 1/2 3.50 13/16 5 x 2 3.09 21/32 6 x 5 5.70 11/8 6 x 4 5.24 11/2 6 x 3 5.04 2 6 x 2 1/2 5.13 21/4 6 x 2 4.89 21/2 8 x 6 13.06 119/32 8 x 4 12.22 219/32 8 x 3 11.79 33/32 8 x 2 1/2 12.64 33/8 600-RS Coupling with Rolled Tube Stop C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 O.D. 0.01 1/16 3/16 O.D. 0.01 3/32 1/8 0.01 1/16 5/16 O.D. 0.01 3/32 1/4 0.01 1/16 3/8 0.01 3/32 1/2 0.03 3/32 5/8 0.04 3/32 3/4 0.06 3/32 7/8 0.09 3/32 1 0.11 3/32 1 1/4 0.16 1/8 1 1/2 0.23 1/8 2 0.41 1/8 2 1/2 0.65 1/8 3 0.93 1/8 3 1/2 1.45 5/32 4 1.93 7/32 Revision 2/6/07 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 12 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. 706-2 45° Fitting Elbow Ftg x C – Cast APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 4 4.31 311/32 15/16 607 90° Elbow – Close Rough C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1/8 0.01 13/32 13/32 1/4 0.02 9/32 9/32 3/8 0.03 1/2 1/2 1/2 0.04 3/8 3/8 1/2 x 3/8 0.04 9/16 21/32 3/4 0.10 17/32 17/32 3/4 x 5/8 0.12 29/32 7/8 3/4 x 1/2 0.10 17/32 3/4 1 0.21 23/32 23/32 1 x 3/4 0.16 23/32 5/8 1 1/4 0.31 11/32 11/32 1 1/4 x 1 0.31 15/8 115/32 1 1/2 0.46 17/32 17/32 1 1/2 x 1 1/4 0.35 15/32 13/32 2 0.84 11/2 11/2 2 x 1 1/2 0.58 17/16 11/4 2 1/2 1.41 127/32 127/32 3 2.07 23/32 23/32 3 1/2 2.94 23/8 23/8 4 4.23 225/32 225/32 5 7.74 27/8 27/8 6 10.95 37/16 37/16 8 29.50 423/32 423/32 707 90° Elbow – Close Rough C x C – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 x 1 0.42 15/8 115/32 1 1/4 x 3/4 0.34 9/16 13/16 1 1/4 x 1/2 0.28 15/32 27/32 1 1/2 x 1 0.54 11/16 1 1 1/2 x 3/4 0.42 19/32 31/32 1 1/2 x 1/2 0.40 5/8 29/32 2 x 1 1/4 0.86 7/8 11/4 2 x 1 0.78 3/4 11/4 2 x 3/4 0.69 5/8 11/4 2 1/2 x 2 2.16 13/16 19/32 3 x 2 1/2 2.26 111/16 11/2 3 x 2 2.68 13/8 19/16 4 x 3 5.18 129/32 215/32 607-I 90° Elbow – Intermediate Radius C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.06 19/32 19/32 5/8 0.09 7/8 7/8 3/4 0.14 13/16 3/16 1 0.24 11/16 11/16 607-LT 90° Elbow – Long Radius C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 3/16 O.D. 0.01 13/32 13/32 1/8 0.01 13/32 13/32 5/16 O.D. 0.02 9/16 9/16 1/4 0.02 17/32 17/32 1/4 x 1/8 0.01 19/32 1/2 3/8 0.04 23/32 23/32 1/2 0.08 7/8 7/8 1/2 x 3/8 0.06 13/16 13/16 1/2 x 1/4 0.03 25/32 21/32 5/8 0.10 13/32 13/32 5/8 x 1/2 0.09 11/16 11/16 3/4 0.16 11/8 11/8 3/4 x 5/8 0.13 11/4 13/32 3/4 x 1/2 0.10 11/8 11/16 7/8 0.28 119/32 119/32 1 0.28 17/16 17/16 1 x 3/4 0.20 11/4 11/8 1 x 5/8 0.15 113/32 13/32 1 1/4 0.42 17/8 17/8 1 1/4 x 1 0.33 125/32 11/2 1 1/2 0.66 21/4 21/4 2 1.23 215/16 215/16 2 1/2 1.96 311/16 311/16 3 2.93 41/32 41/32 4 5.95 51/4 51/4 Revision 2/7/07 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 15 707-6 90° Union Elbow C x C – Cast APPROX. DIM. A DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 3/8 0.17 31/32 5/16 1/2 0.24 1 7/16 3/4 0.39 117/32 9/16 1 0.64 121/32 23/32 1 1/4 1.07 119/32 23/32 708 90° Flanged Sink Elbow C x F – Cast NOM. APPROX. DIM. A DIM. C DIM. F SIZE NET WT./LBS. INCHES INCHES INCHES 1/2 0.20 7/8 9/16 13/4 764 90° Double Elbow C x C x C – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1 x 3/4 x 3/4 0.33 3/4 21/32 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. FITTING REDUCERS APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 4 x 3 1/2 2.09 25/8 4 x 3 2.00 31/32 4 x 2 1/2 1.56 31/32 4 x 2 1.76 313/32 5 x 4 3.30 39/16 5 x 3 2.97 41/16 5 x 2 1/2 3.30 411/32 5 x 2 2.88 411/16 6 x 5 5.56 43/16 6 x 4 5.09 49/16 6 x 3 4.67 51/16 6 x 2 1/2 4.47 511/32 6 x 2 4.51 519/32 8 x 6 12.33 515/32 8 x 5 10.35 515/16 8 x 4 11.10 67/16 8 x 3 10.63 615/16 8 x 2 1/2 11.41 73/16 8 x 2 10.86 77/16 741 Companion Flange C – Cast NOM. APPROX. DIM. B DIM. F DIM. G DIM. W SIZE NET WT./LBS. INCHES INCHES INCHES INCHES 1/2 0.55 1/8 31/2 3/16 23/8 3/4 0.71 1/8 37/8 3/16 23/4 1 1.26 1/8 41/4 1/4 31/8 1 1/4 1.42 1/8 45/8 1/4 31/2 1 1/2 1.82 1/8 5 5/16 37/8 2 2.76 1/8 6 3/8 43/4 2 1/2 4.29 1/8 7 3/8 51/2 3 5.26 1/8 71/2 7/16 6 4 7.60 1/8 9 7/16 71/2 5 9.04 1/8 10 7/16 81/2 6 12.68 1/8 11 1/2 91/2 NOTE: Dim. B = Tube Stop to Flange Face 600-2 Fitting Reducer Ftg x C – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/4 x 1/8 0.01 15/32 3/8 x 1/4 0.01 19/32 3/8 x 1/8 0.01 25/32 1/2 x 3/8 0.03 11/16 1/2 x 1/4 0.02 25/32 5/8 x 1/2 0.04 7/8 5/8 x 3/8 0.04 31/32 5/8 x 1/4 0.03 11/32 3/4 x 5/8 0.06 31/32 3/4 x 1/2 0.06 11/8 3/4 x 3/8 0.05 11/8 3/4 x 1/4 0.05 13/32 1 x 3/4 0.10 17/32 1 x 5/8 0.09 13/8 1 x 1/2 0.09 11/4 1 x 3/8 0.08 19/32 1 1/4 x 1 0.15 15/16 1 1/4 x 3/4 0.16 11/2 1 1/4 x 1/2 0.13 13/8 1 1/2 x 1 1/4 0.23 113/32 1 1/2 x 1 0.21 15/8 1 1/2 x 3/4 0.20 17/8 1 1/2 x 1/2 0.16 119/32 2 x 1 1/2 0.40 131/32 2 x 1 1/4 0.34 23/32 2 x 1 0.35 127/32 2 x 3/4 0.35 127/32 2 x 1/2 0.34 131/32 2 1/2 x 2 0.65 131/32 2 1/2 x 1 1/2 0.65 23/8 2 1/2 x 1 1/4 0.60 27/32 2 1/2 x 1 0.78 29/32 3 x 2 1/2 1.03 21/4 3 x 2 0.99 29/16 3 x 1 1/2 0.81 219/32 3 x 1 1/4 1.29 31/4 3 1/2 x 3 1.48 211/32 Continues… FLANGES – CLASS 125 Revision 2/8/07 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 18 APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 1 x 1/2 x 1 0.29 11/16 1 21/32 1 x 1/2 x 3/4 0.27 9/16 13/16 3/4 1 x 1/2 x 1/2 0.22 15/32 25/32 23/32 1 1/4 0.43 13/16 3/16 13/16 1 1/4 x 1 1/4 x 2 1.13 130/32 130/32 13/32 1 1/4 x 1 1/4 x 1 1/2 0.60 13/16 13/16 29/32 1 1/4 x 1 1/4 x 1 0.45 25/32 25/32 29/32 1 1/4 x 1 1/4 x 3/4 0.37 21/32 21/32 3/4 1 1/4 x 1 1/4 x 1/2 0.30 1/2 1/2 25/32 1 1/4 x 1 1/4 x 3/8 0.34 23/32 23/32 29/32 1 1/4 x 1 x 1 1/4 0.43 13/16 11/32 13/16 1 1/4 x 1 x 1 0.47 25/32 7/8 29/32 1 1/4 x 1 x 3/4 0.35 21/32 25/32 7/8 1 1/4 x 1 x 1/2 0.30 1/2 5/8 29/32 1 1/4 x 3/4 x 1 1/4 0.42 13/16 11/8 13/16 1 1/4 x 3/4 x 1 0.45 25/32 11/32 29/32 1 1/4 x 3/4 x 3/4 0.37 21/32 15/16 7/8 1 1/4 x 3/4 x 1/2 0.30 1/2 3/4 29/32 1 1/4 x 1/2 x 1 1/4 0.41 13/16 17/32 13/16 1 1/2 0.61 31/32 31/32 29/32 1 1/2 x 1 1/2 x 2 1.11 125/32 125/32 13/32 1 1/2 x 1 1/2 x 1 1/4 0.62 29/32 29/32 11/16 1 1/2 x 1 1/2 x 1 0.55 11/16 11/16 7/8 1 1/2 x 1 1/2 x 3/4 0.45 11/16 11/16 11/32 1 1/2 x 1 1/2 x 1/2 0.40 1/2 1/2 11/32 1 1/2 x 1 1/4 x 1 1/2 0.62 11/32 13/16 29/32 1 1/2 x 1 1/4 x 1 1/4 0.62 31/32 13/32 31/32 1 1/2 x 1 1/4 x 1 0.51 25/32 1 11/32 1 1/2 x 1 1/4 x 3/4 0.49 11/16 13/16 11/32 1 1/2 x 1 1/4 x 1/2 0.41 1/2 25/32 11/32 1 1/2 x 1 x 1 1/2 0.59 11/32 111/32 29/32 1 1/2 x 1 x 1 1/4 0.63 29/32 11/8 11/16 1 1/2 x 1 x 1 0.54 25/32 11/16 11/32 1 1/2 x 1 x 3/4 0.44 11/16 31/32 15/16 1 1/2 x 1 x 1/2 0.39 1/2 25/32 11/32 1 1/2 x 3/4 x 1 1/2 0.62 11/32 17/16 11/16 1 1/2 x 3/4 x 1 1/4 0.58 29/32 111/32 11/16 1 1/2 x 3/4 x 1 0.54 25/32 11/4 11/32 1 1/2 x 3/4 x 3/4 0.47 11/16 13/32 29/32 1 1/2 x 3/4 x 1/2 0.39 1/2 29/32 31/32 1 1/2 x 1/2 x 1 1/2 0.62 11/32 113/32 31/32 Continues… APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 2 1.30 19/32 19/32 11/32 2 x 2 x 2 1/2 2.34 2 2 121/32 2 x 2 x 1 1/2 1.17 11/4 11/4 123/32 2 x 2 x 1 1/4 1.12 9/32 9/32 17/8 2 x 2 x 1 0.90 27/32 27/32 11/4 2 x 2 x 3/4 0.88 19/32 19/32 11/4 2 x 2 x 1/2 1.17 11/4 11/4 21/4 2 x 1 1/2 x 2 1.16 19/32 17/8 111/32 2 x 1 1/2 x 1 1/2 1.15 11/4 13/4 123/32 2 x 1 1/2 x 1 1/4 1.15 7/32 13/4 111/32 2 x 1 1/2 x 3/4 0.83 21/32 15/16 17/32 2 x 1 1/2 x 1/2 1.12 11/4 125/32 21/4 2 x 1 1/4 x 2 1.58 19/32 115/32 19/32 2 x 1 1/4 x 1 1/2 1.16 11/4 131/32 123/32 2 x 1 1/4 x 1 1/4 1.19 15/16 111/32 111/32 2 x 1 1/4 x 1 0.90 27/32 19/32 111/32 2 x 1 1/4 x 3/4 0.85 21/32 1 18/27 2 x 1 x 2 1.11 11/8 125/32 11/4 2 x 1 x 1 0.89 27/32 19/32 111/32 2 x 3/4 x 2 1.15 19/32 23/16 11/4 2 x 1/2 x 2 1.15 19/32 23/8 11/4 2 1/2 2.40 15/8 15/8 15/8 2 1/2 x 2 1/2 x 2 1.97 15/16 15/16 121/32 2 1/2 x 2 1/2 x 1 1/2 1.53 13/32 13/32 121/32 2 1/2 x 2 1/2 x 1 1/4 1.72 13/32 13/32 127/32 2 1/2 x 2 1/2 x 1 1.34 25/32 25/32 111/16 2 1/2 x 2 1/2 x 3/4 1.34 25/32 25/32 113/16 2 1/2 x 2 1/2 x 1/2 1.34 25/32 25/32 21/8 2 1/2 x 2 x 2 1/2 1.99 121/32 23/32 121/32 2 1/2 x 2 x 2 1.95 111/32 15/8 123/32 2 1/2 x 2 x 1 1/2 1.57 13/32 213/32 121/32 2 1/2 x 2 x 1 1/4 1.57 13/32 119/32 127/32 2 1/2 x 2 x 1 1.40 25/32 19/32 13/4 2 1/2 x 2 x 3/4 1.35 25/32 19/32 127/32 2 1/2 x 1 1/2 x 1 1/2 1.76 13/32 113/32 13/8 2 1/2 x 1 1/4 x 2 1/2 2.40 121/32 27/16 121/32 2 1/2 x 1 x 2 1/2 2.04 121/32 223/32 121/32 2 1/2 x 3/4 x 2 1/2 2.00 121/32 211/16 121/32 2 1/2 x 1/2 x 2 1/2 2.46 11/2 27/32 11/2 Continues… APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 3 3.15 17/8 17/8 21/32 3 x 3 x 2 1/2 3.55 129/32 129/32 23/8 3 x 3 x 2 3.19 115/32 115/32 131/32 3 x 3 x 1 1/2 3.08 115/32 115/32 29/32 3 x 3 x 1 1/4 3.10 115/32 115/32 27/16 3 x 3 x 1 2.12 27/32 27/32 131/32 3 x 3 x 3/4 2.39 27/32 27/32 23/16 3 x 3 x 1/2 1.82 27/32 27/32 23/8 3 x 2 1/2 x 3 3.08 17/8 23/8 131/32 3 x 2 1/2 x 2 1/2 3.12 129/32 211/32 25/32 3 x 2 1/2 x 2 2.28 115/32 127/32 131/32 3 x 2 x 3 3.62 129/32 217/32 115/16 3 x 2 x 2 1/2 3.56 129/32 29/16 25/16 3 x 2 x 2 3.22 115/32 131/32 131/32 3 x 1 1/2 x 3 3.13 129/32 225/32 23/32 3 x 1 1/4 x 3 3.63 129/32 225/32 115/16 3 x 1 x 3 3.20 131/32 219/32 23/16 3 x 3/4 x 3 3.55 131/32 229/32 23/16 3 1/2 5.20 217/32 217/32 217/32 4 8.12 213/32 213/32 217/32 4 x 4 x 3 6.70 21/32 21/32 221/32 4 x 4 x 2 1/2 6.65 21/32 21/32 35/32 4 x 4 x 2 5.82 115/32 115/32 27/16 4 x 4 x 1 1/2 3.94 111/32 111/32 217/32 4 x 4 x 1 1/4 4.04 111/32 111/32 229/32 4 x 4 x 1 3.72 1 1 29/16 4 x 4 x 3/4 3.70 1 1 211/16 4 x 3 x 4 7.05 225/32 37/32 217/32 4 x 3 x 3 5.03 21/32 215/32 215/32 4 x 3 x 2 1/2 5.04 21/32 215/32 229/32 4 x 3 x 2 5.87 115/32 131/32 27/16 4 x 2 1/2 x 4 7.19 225/32 315/32 227/32 4 x 2 x 4 7.08 225/32 319/32 227/32 Continued on next page. NOTE: Tee sizes are read Run x Run x Outlet. 611 Tee C x C x C – Wrot continued TEES continued Consult price sheet for Made to Order items and for minimum order quantities. Revision 2/8/07 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 49 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Copper Water Tube continued DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “M” TYPE “M” Hard Drawn Only: 20-ft. (6.1m) Straight Lengths Usage: For general purpose plumbing, heating and drainage installations. Tolerances Hard Drawn (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Nominal Diameter Thickness Per Foot Pressure A Pressure B Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 (59) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.028 (0.71) 0.204 (0.09) 6135 (423) 741 (51) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.032 (0.81) 0.328 (0.15) 4717 (325) 611 (42) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.035 (0.89) 0.465 (0.21) 3865 (266) 506 (35) 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35) 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.049 (1.24) 0.940 (0.43) 3550 (245) 497 (34) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28) 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.072 (1.83) 2.680 (1.22) 2665 (184) 380 (26) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 (26) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153) 377 (26) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 (24) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.212 (5.38) 25.600 (11.61) N/A N/A 344 (24) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36.700 (16.65) N/A N/A 345 (24) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. A Based on actual laboratory test data provided by Copper Development Association, Inc. B Based upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). Revision 5/12/02 AHEAD OF THE FLOW ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 81 Copper Water Tube continued COPPER TUBE – TYPES, STANDARDS, APPLICATIONS, TEMPERS AND LENGTHS Commercially Available Lengths Tube Type Color Code Standard Application Nominal or Standard Sizes Drawn Annealed Type K Green ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) 20 ft. (6.1m) Fire Protection 10-inch 18 ft. (5.5m) 18 ft. (5.5m) Solar 12-inch 12 ft. (3.7m) 12 ft. (3.7m) Fuel/Fuel Oil Coils: 1/4-inch to 1-inch – 60 ft. (18.3m) HVAC – 100 ft. (30.5m) Snow Melting 11/4-inch & 11/2-inch – 60 ft. (18.3m) 2-inch – 40 ft. (12.2m) – 45 ft. (13.7m) Type L Blue ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 10-inch 20 ft. (6.1m) 20 ft. (6.1m) Fire Protection 12-inch 18 ft. (5.5m) 18 ft. (5.5m) Solar Fuel/Fuel Oil Natural Gas Coils: 1/4-inch to 1-inch – 60 ft. (18.3m) Liquified Petroleum (LP) Gas – 100 ft. (30.5m) HVAC 11/4-inch & 11/2-inch – 60 ft. (18.3m) Snow Melting 2-inch – 40 ft. (12.2m) – 45 ft. (13.7m) Type M Red ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 12-inch 20 ft. (6.1m) N/A Fire Protection Solar Fuel/Fuel Oil HVAC Snow Melting DWV Yellow ASTM B 306 Drain Straight Lengths: 11/4-inch to 8-inch 20 ft. (6.1m) N/A Waste Vent HVAC Solar ACR Blue ASTM B 280 Air Conditioning Straight Lengths: 1/4-inch to 41/8-inch 20 ft. (6.1m) 20 ft. (6.1m)1 Refrigeration Natural Gas Coils: 1/8-inch to 15/8-inch – 50 ft. (15.3m)1 Liquified Petroleum (LP) Gas OXY Type K ASTM B 819 Medical Gas Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) N/A MED Green OXY/MED OXY/ACR Type L ACR/MED Blue Type G Yellow ASTM B 837 Natural Gas Straight Lengths: 3/8-inch to 11/8-inch 12 ft. (3.7m) 12 ft. (3.7m)1 Liquified Petroleum (LP) Gas 20 ft. (6.1m) 20 ft. (6.1m)1 Coils: 3/8-inch to 7/8-inch – 60 ft. (18.3m)1 – 100 ft. (30.5m)1 1 Available as special order only. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Revision 5/12/02 Main Office/Manufacturing Facility•1375 Sampson Ave. •Corona, CA 92879 •Ph: 909.737.5599 •Fax: 909.737.0330 Customer Service•800.786.5266 www.tolco.com 36 wwwwww..ttoollccoo..ccoomm Revision 5/24/2001 ™ ® a brand of Dimensions • Weights Data Table for Fig.20S PipeHoleMax.Rec.Approx. Sizes A BCDSizeLoad Lbs.Wt./100 1/241/8 5/1627/8 3/47/1641021 3/445/16 7/16315/167/1641024 149/16 9/1633/8 11/8 7/1641026 11/4 415/16 11/1633/4 11/2 7/1641030 11/2 53/16 13/1641/4 15/8 7/1641033 253/4 11/16 43/4 21/4 7/1641038 21/2 61/4 19/16 51/4 23/4 7/16610102 367/8 15/8 57/8 33/8 7/16610118 31/2 73/8 17/8 63/8 37/8 7/16610130 483/8 21/8 743/8 9/16725159 597/16 25/8 77/8 53/8 9/16725191 6101/2 33/16 87/8 67/16 9/16725234 81441/4 111/2 83/8 11/16900446 Size Range — 1/2" thru 8" pipe Material — Carbon Steel Function — Recommended for supporting pipe with fittings vertically or horizontally to walls or ceiling.Fig.20S will support pipe flush with mounting surface. Approvals — Conforms to Federal Specification WW-H-171E, Type 26 and Manufacturers Standardization Society SP-69, Type 26. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size, material and finish Size Range — 1/2" thru 2" pipe Material — Carbon Steel Function — Light duty strap that attaches pipe or copper tubing to horizontal or vertical structure. Finish — Pre-Galvanized Note — Available with felt lining, order TOLCO™ Fig.21F. Order By — Figure number and pipe size Fig.20 - StandardPipe Strap Fig.20S - FlushMount PipeStrap Fig. 21 - “Tin Strap” Dimensions • Weights Data Table for Fig.20 PipeHoleMax.Rec.Approx. Sizes A BCDSizeLoad Lbs.Wt./100 1/237/8 3/431/16 15/32 7/1641016 3/4413/1631/8 15/16 7/1641021 149/16 7/833/8 11/2 7/1641026 11/4 415/16 133/4 17/8 7/1641030 11/2 53/16 13/16 41/4 21/8 7/1641033 253/4 17/16 43/4 25/8 7/1641038 21/2 61/4 111/16 51/4 31/8 7/16610102 367/8 257/8 33/4 7/16610118 31/2 73/8 21/4 63/8 41/4 7/16610130 483/8 21/2 743/4 9/16725159 597/16 31/16 77/8 513/16 9/16725191 6101/2 35/8 87/8 67/8 9/16725234 81445/8 111/2 911/16900446 Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 909.737.5599 • Fax: 909.737.0330 Distribution Center • 8790 Fruitridge Road • Sacramento, CA 95826 • Ph: 916.388.7800 • Fax: 916.388.1401 Manufacturing Facility • 4851 Homestead Road, Bldg. 118 • Houston, TX 77028 • Ph: 713.672.0058 • Fax: 713.672.0074 www.tolco.com 31 Fig. 200 “Trimline” Adjustable Band Hanger Size Range – 1/2 thru 8 inch pipe. Material – Carbon Steel, Mil. Galvanized to G-90 specifications. Function – For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features · (1/2 thru 2 inch) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily installed around pipe. · (2-1/2 thru 8 inch) Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Approvals – Underwriters' Laboratories Listed (1/2” thru 8”) in the U.S. (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4” thru 8”). Conforms to Federal Specifications WW-H-171E, Type 10, and Manufacturers Standardization Society SP-69, type 10. Maximum Temperature - 650°F. Finish – Mil. Galvanized, for Stainless Steel materials order TOLCO™ Fig. 200WON. Order By – Figure number and pipe size. Pipe Size Rod Size Inch Metric* B Max. Rec. Load bs. Approx. Wt./100 1/2 3/8 8mm or 10mm 3-1/8 2-5/8 400 11 3/4 3/8 8mm or 10mm 3-1/8 2-1/2 400 11 1 3/8 8mm or 10mm 3-3/8 2-5/8 400 12 1-1/4 3/8 8mm or 10mm 3-3/4 2-7/8 400 13 1-1/2 3/8 8mm or 10mm 3-7/8 2-7/8 400 14 2 3/8 8mm or 10mm 4-1/2 3 400 15 2-1/2 3/8 10mm 5-5/8 4-1/8 600 27 3 3/8 10mm 5-7/8 4 600 29 3-1/2 3/8 10mm 7-3/8 5-1/4 600 34 4 3/8 10mm 7-3/8 5 1000 35 5 1/2 12mm 9-1/8 6-1/4 1250 66 6 1/2 12mm 10-1/8 6-3/4 1250 73 8 1/2 12mm 13-1/8 8-3/4 1250 136 *Order Fig. 200M Revision 5/24/2001 5 To find a distributor near you, call 800-BUILDEX Not less than 2” nominal width (1-1/2”) up to 3-1/2” pipe; not less than 3” (2-1/2”) nominal width 4” & 5” pipe Minimum 2-1/2” from bottom for branch lines. Minimum 3” from bottom for main lines. Exception: This requirement shall not apply to 2” or thicker nailing strips resting on top of steel beams. Floor Joist HORIZONTAL MOUNT WO O D W O O D W O O D W O O D W O O D SIDEWINDERS® for Wood Installs HORIZONTALLY into the side of wood structures easily and quickly! Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs) UL Test Load (lbs) Box Qty Case Qty 1/4"8018957 SWG 100 1/4 x 1"622 (Fir)25 125 1/4"8019957 SWG 200 1/4 x 2"1725 (Fir)25 125 3/8"8020957 SWG 10 1/4 x 1"622 (Fir)300 25 125 3/8"8021957 SWG 20 1/4 x 2"1725 (Fir)1050 25 125 3/8"8073925 SWG 20-SS 1/4 x 2"1725 (Fir)850 25 125 3/8"8022925 SWG 25-380 3/8 x 2-1/2"2249 (Fir)1500 25 125 3/8"8023925 SWG 30 1/4 x 3"1884 (Fir)25 125 #14 SW Red Nut Driver Part # 8114910 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. INSTALLATION STEPS - VERTICAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill. 2. Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill should be in a vertical position. 3. Push the face of the nut driver tight to the member. When the nut driver spins freely on the SAMMYS, stop drill and remove. 4. The SAMMYS is now ready to receive 1/4”, 3/8”, 1/2” or metric all thread rod, bolt stock. (The 1/2” requires the #14SW red nut driver) Note: When installing DSTR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. INSTALLATION STEPS - HORIZONTAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill. 2. Insert the SAMMYS into the #14SW (red) nut driver (p/n 8114910). With drill unit in a horizontal position and at a right angle to the structural member, begin installation. 3. When the nut driver spins free on the SAMMYS, stop the drill and remove. 4. The unit is now ready to receive 1/4”, 3/8” or metric all thread rod or bolt stock. Note: When installing SWDR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. Composite/Truss Consult truss manufacturer for recommended installation point. *Pre-drilling may be required for Model SWG 25-380 (tools available on pg 10 ) Product Features • No pre-drilling required. • Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. • Saves time from traditional methods. • Reduces installation cost. • Made in the U.S.A. Installs VERTICALLY and swivels up to 17° in wood structure Main Office/Manufacturing Facility•1375 Sampson Ave. •Corona, CA 92879 •Ph: 909.737.5599 •Fax: 909.737.0330 Customer Service•800.786.5266 www.tolco.com 68 wwwwww..ttoollccoo..ccoomm Revision 5/24/2001 ™ ® a brand of Fig.98 - Rod Stiffener Size Range — Secures 3/8" thru 7/8" hanger rod Material — Carbon Steel Function — Secures channel to hanger rod for vertical seismic bracing. Finish — Electro Galvanized Note — Available in HDG finish or Stainless Steel materials. Order By — Figure number Fig.99 - All ThreadRodCut to Length Size Range — Secures 3/8" thru 7/8" rod in 1" increments Material — Carbon Steel Maximum Temperature — 750°F Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, rod diameter, rod length and finish Fig.100 - All ThreadRodFullLengths Size Range — Secures 3/8" thru 7/8" rod in 10’lengths Material — Carbon Steel Maximum Temperature — 750°F Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, rod diameter and finish Dimensions • Weights RodMax.Rec.Load Lbs. SizeFor Service Temps 650°F750°F 3/8610540 1/211301010 5/818101610 3/427102420 7/837703360 Dimensions • Weights Max Rec.Load Lbs. RodFor Service TempsApprox. Size650°F750°FWt./100 1/424021512 3/861054029 1/21130101053 5/81810161084 3/427102420123 7/837703360169 149604420222 11/4 80007140360 11/2 1163010370510 PRINTED IN USA MKT. #8800003 - REV X MFG. #5400802 - 12/01 VSR-SF VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 1 OF 2 UL, ULC, CSFM Listed and NYMEA Accepted, CE Marked Service Pressure: Up to 250 PSI (17,2 BAR) Minimum Flow Rate for Alarm: 8-10 GPM (30-38 Lpm) Maximum Surge: 18 FPS (10 m/s) Enclosure:Die-cast, red enamel finish Cover held in place with tamper resistant screws Contact Ratings:Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Usage:Listed plastic, copper and schedule 40 iron pipe. Fits pipe sizes - 1" (25mm), 1 1/4" (32mm), 1 1/2" (38mm) and 2" (50mm) Note: 12 paddles are furnished with each unit, one for each pipe size of threaded and sweat TEE, one for 1" (25mm) CPVC, one for 1" (25mm) CPVC (Central), one for 1 1/2" (38mm) polybutylene and one for 1 1/2" (38mm) threaded (Japan). (CTS-Copper tubing size) Environmental Specifications: •Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. •NEMA 4/IP55 rated enclosure - use with appropriate conduit fitting. •Temperature range: 40° F to 120° F, 4,5° C to 49° C) Caution:This device is not intended for applications in explosive environments. Service Use: Automatic SprinklerNFPA-13 One or two family dwellingNFPA-13D Residential occupancy up to four storiesNFPA-13R National Fire Alarm CodeNFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090018 Stock No. 1113000 U.S. Pat. No. 3921989, Canadian Pat. No. 1009680 Other Patents Pending The Model VSR-SF is a vane type waterflow switch for use on wet sprinkler systems that use 1" (25mm), 1 1/4" (32mm), 1 1/2" (38mm) or 2" (50mm) pipe size. The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic re- tard. The switches are actuated when a flow of 8-10 gallons per minute (30-38 Lpm) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. INSTALLATION: These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" (15cm) of a valve, drain or fitting which changes the direction of the waterflow. The unit has a 1" NPT bushing for threading into a non-corrosive TEE. See Fig. 2 for proper TEE size, type and installation. Screw the device into the TEE fitting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterflow. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. The device can also be used in copper or plastic pipe installa- tions with the proper adapters so that the specified TEE fitting may be installed on the pipe run. INSPECTION AND TESTING: Check the operation of the unit by opening the inspector’s test valve at the end of the sprinkler line or the drain and test connection, if an inspector’s test valve is not provided. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-SF is not recommended or advisable The frequency of the inspection and testing and its associated protective monitoring system should be in accordance with the applicable NFPA Codes and Standards and/or authority having jurisdiction (manufacturer recommends quarterly or more fre- quently). Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MKT. #8800003 - REV X MFG. #5400802 - 12/01 VSR-SF VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FOR SMALL PIPE PAGE 2 OF 2 CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. FIG. 1 Important: There are 12 paddles fur- nished with each unit. One for each size of threaded, sweat or plastic TEE as described in Fig. 2. These paddles have raised lettering that shows the pipe size and type of TEE that they are to be used with. The proper paddle must be used. The paddle must be properly attached (see drawing) and the screw that holds the pad- dle must be securely tight- ened. FIG. 2 NOTES: 1.The model VSR-SF has two switches, one can be used to operate a central station, proprietary or remote signal- ing unit, while the other is used to operate a local au- dible or visual annunciator. 2.For supervised circuits see “Switch Terminal Connec- tions” drawing and caution note (Fig. 3). FIG. 4 TYPICAL ELECTRICAL CONNECTIONS Retard Adjustment: To change time, turn knob (either direction) for desired time delay. Use the minimum amount of retard necessary to prevent false alarms. A “B” setting is usually adequate for this. Factory set at “B”. FIG. 3 SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL FIG. 5 To remove knockouts: Place screwdriver at edge of knock- outs, not in the center. APPLICATION WARNING! Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterflow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Screw the device into the tee fitting as shown. Care must be taken to properly orient the device for the direction of waterflow. On sweat tees, no threaded bushings, inserts, or adapters are permitted, unless they comply with the dimensions listed in the chart below. Important - The depth to the inside bottom of the tee should have the following dimensions: PRINTED IN USA RBVS UNIVERSAL BALL VALVE SWITCH PAGE 1 OF 2MFG.# 5401086 - REV U 5/08 US Patent No. 6,945,509 General The Model RBVS is designed to monitor the fully open position of a ball valve installed in a sprinkler system. The unit will fi t on most ball valves installed on back-fl ow-preventers and alarm trim lines of dry, alarm, and deluge sprinkler valves. The switch operates if the ball valve handle is moved from the open position. However, the switch does not track the position of the handle or ball. When the ball valve handle is in the open position, a spring-loaded switch button will contact the valve handle. When the handle is moved from the open position, this switch button extends to the tripped position, and the RBVS contacts change state, thereby opening or closing a circuit. A cover tamper switch is available and is activated by the removal of the RBVS housing cover. If an attempt is made to remove the RBVS by the removal of the mounting brackets, the unit will be set into the tripped mode by this action. The RBVS can be mounted to the hex portion of the ball valve or back-fl ow- preventer or to the adjoining pipe via two clamps. The RBVS is shipped with two sets of mounting clamps to accommodate various pipe and valve sizes, refer to Table 1. An "L" shaped and offset bracket for mounting the switch enclosure and an extension bracket add to the mounting fl exibility of the RBVS. See "Typical Mounting Diagram" and "Installation and Operation" on following page. Testing The RBVS and its associated protective monitoring system should be tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). UL and cUL Listed, FM, CSFM Approved Dimensions: (including mounting clamps) Large Clamps: 6" L x 5" W x 5.2" H 15,2 cm L x 12,7 cm W x 13,2 cm H Small Clamps: 6" L x 4" W x 5.2" H 15,2 cm L x 10,2 cm W x 13,2 cm H Weight: With Large Clamps: 13.6 oz. (386,9 g.) With Small Clamps: 11.0 oz. (311,2 g.) Enclosure: Non-Corrosive Composite Material Environmental Limitations: • NEMA 4 rated enclosure when proper electrical fi ttings are used. (IP67) • Temperature range: -40°F to 150°F (-40°C to 65°C) • Not for use in hazardous locations Housing Cover Tamper: Activated by housing cover removal (Stock No. 1000035 only) Contact Ratings: SPDT Contacts: 10A at 125/250 VAC 2A at 30 VDC SPDT Cover Tamper: 3A at 250 VAC Fig.1 Internal Components Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com RBVS Stock No. 1000040 (w/o Cover Tamper) RBVS-T Stock No. 1000035 (w/Cover Tamper) Installation On Lever Handle (See Fig. 2) 1. Select clamps and clamping bolts based upon pipe/valve size, see Table 1. 2. Insert rubber clamp grippers into clamps, see Fig. 2. 3. Place one clamp on top of pipe/ball valve near the valve handle and insert clamping bolts through it. 4. Place other clamp over clamping bolts from beneath the installation and thread hex nuts onto the clamping bolts, but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses). (NOTE: Some installations may require one of the mounting bolts to be inserted from the bottom of the brackets and then trimmed to allow the extension bracket to clear. See Fig. 4) 5. Attach extension bracket (if necessary to use for positioning) to top clamp using ¼-20 X ¾" Hex bolt and washer, but do not fully tighten. 6. Attach "L" bracket (RBVS switch enclosure is loosely attached to "L" bracket) to extension bracket using ¼-20 X ¾" Hex bolt and washer, but do not fully tighten. 7. Be sure ball valve is in the fully open position. 8. Slide loosely assembled RBVS switch enclosure to a position that permits the switch button to contact the valve handle approximately 1" from its inside end. See Fig. 1 for approximate location. Cut and remove the plastic coating from the ball valve handle to allow the RBVS switch button to contact (and be activated by) the metal of the handle. 9. Tighten clamping screws alternately to an eventual 30 in-lbs. (minimum) of torque. 10. Maintain position of switch enclosure over valve handle and secure bolt that holds the extension bracket to the clamping assembly. It may be necessary to close valve to access this bolt. 11. Position "L" bracket so that it contacts the back edge of the valve handle, and secure its bolt. It may be necessary to close valve to access this bolt. 12. With the actuator fully retracted, position RBVS switch enclosure to contact the valve handle squarely, see Fig. 1. 13. With RBVS switch enclosure held squarely in contact with valve handle, securely tighten the two tamper resistant screws on the backside of the enclosure. 14. Close and open the valve to verify operation. The actuator should easily retract when the valve handle is in the open position. 15. Fully open the valve. 16. Remove the cover and wire main switch and tamper switch if applicable. Carefully route tamper switch wires through strain relief channel in switch enclosure. Fully seat the wires into the bottom of the channel. See Fig. 1. 17. Replace RBVS switch enclosure cover and securely tighten cover screw. PRINTED IN USA RBVS UNIVERSAL BALL VALVE SWITCH MFG.# 5401086 - REV U 5/08 PAGE 2 OF 2 OUTG O I N G INC O M I N G DWG# 923-3 Installation on Tee Handle (See Fig. 3) 1. Select clamps and clamping bolts based upon pipe/valve size, see Table 1. 2. Insert rubber clamp grippers into clamps, See Fig. 3. 3. Place one clamp on top of pipe/ball valve near the valve handle and insert clamping bolts through it. 4. Place other clamp over clamping bolts from beneath the installation and thread hex nuts onto the clamping bolts, but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses). 5. Loosely attach "L" bracket to the "offset" bracket and "offset" bracket to the RBVS housing. 6. Be sure ball valve is in the fully open position. 7. Slide loosely assembled RBVS switch enclosure to a position that permits the switch button to contact the valve handle approximately 1/2" from the end of the handle. Cut and remove the plastic coating from the ball valve handle to allow the RBVS switch button to contact (and be activated by) the metal of the handle. 8. Tighten clamping screws alternately and ¼-20 X ¾" bolt to 30 in-lbs. (minimum) of torque. 9. With the valve handle fully open, slide the RBVS housing down until the switch operates plus 1/8 inch. Tighten the screws holding the RBVS to the "offset" bracket. 10. Remove the RBVS switch enclosure cover. 11. Close and open the valve to verify operation. The actuator should easily retract up when the valve handle is in the open position. 12. Fully open the valve. 13. Wire main switch and tamper switch (if applicable). Carefully route tamper switch wires through strain relief channel in switch enclosure. Fully seat the wires into the bottom of the channel. See Fig. 1. 14. Replace RBVS switch enclosure cover and securely tighten cover screw. Fig. 3 Typical Electrical Connections Fig. 2 Typical Mounting Diagram Tamper Switch Connections Switch Terminal Connections, Clamping Plate Terminal Table 1 Clamp Sizing Fig. 4 SOME INSTALLATIONS MAY CAUSE INTERFERENCE BETWEEN MOUNTING BOLT AND OFFSET BRACKET. INSTALL BOLT FROM BOTTOM AND TRIM AS NEEDED TO CORRECT. RBVS PIPE DWG# 1086-6 Pipe Valve/SizeClampClamping Bolts 1/2" to 3/4" (12,5 to 19mm)Small10-32 x 2 1/2 1" to 2" (25 to 50mm)Large1/4-20 x 4" An uninsulated section of single conductor should not be looped around the terminal and serve as two seperate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. Model 1011A TESTan DRaIn® Dimensions Orifice Size Available: 3⁄8", 7⁄16", 1⁄2", 17⁄32", ELO (5⁄8")*, ESFR (3⁄4")*, & K25** SIZE A B C D E F G H ¾"79⁄16" (191 mm) 11⁄2" (37.5 mm) 23⁄16" (57 mm) 35⁄8" (93 mm) 33⁄8" (86 mm) 113⁄16" (46 mm) 49⁄16" (117 mm) 63⁄8" (162.5 mm) 1"79⁄16" (191 mm) 11⁄2" (37.5 mm) 23⁄16" (57 mm) 35⁄8" (93 mm) 33⁄8" (86 mm) 113⁄16" (46 mm) 49⁄16" (117 mm) 63⁄8" (162.5 mm) 11⁄4"715⁄16" (201 mm) 111⁄16" (43 mm) 29⁄16" (65 mm) 41⁄4" (108 mm) 35⁄8" (91 mm) 115⁄16" (51 mm) 59⁄16" (141 mm) 51⁄2" (192 mm) 1½"815⁄16" (227 mm) 113⁄16" (45 mm) 31⁄4" (81.5 mm) 51⁄16" (127 mm) 37⁄8" (99 mm) 25⁄8" (67 mm) 81⁄4" (207 mm) 107⁄8" (274 mm) 2"815⁄16" (227 mm) 113⁄16" (45 mm) 31⁄4" (81.5 mm) 51⁄16" (127 mm) 37⁄8" (99 mm) 25⁄8" (67 mm) 81⁄4" (207 mm) 107⁄8" (274 mm) * Available on 11⁄4" to 2" size units only ** Available on 11⁄2" and 2" size units only TO DRAIN TO DRAIN H F G E A A INLET D B C Approv A ls UL and ULC Listed: (EX4019 & EX4533) FM Approved NYC-BSA No. 720-87-SM Job Name:__________________________________ Architect: ___________________________________ Engineer: ___________________________________ Contractor: _________________________________ USA Patent # 4741361 and Other Patents Pending mA teri A ls Handle: Steel Stem: Rod Brass Ball: C.P. Brass Body: Bronze Valve Seat: Impregnated Teflon® Indicator Plate: Steel Relief Valve: Bronze Bypass Fittings: Brass Bypass Tubing: Nylobraid mo D el 1011A - Front view mo D el 1011A - pl A n view AGF Manufacturing Inc. 100 Quaker Lane, Malvern, PA 19355 Phone: 610-240-4900 Fax: 610-240-4906 www.testandrain.com Model 1011A 300 PSI Bronze Ball Valve, Model 7000 Pressure Relief Valve Factory Rated at 175 PSI with other settings available the mo D el 1011A provi D es A ll o F the F ollowing … From the 2007 Edition of NFPA 13 Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system. Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s) – shall be provided with a drain connection having a minimum size as shown in Table 8.16.2.4.2. Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain. Chapter A.8.17.4.2 (Wet Pipe System) test connection is permitted to terminate into a drain capable of accepting full flow… using an approved sight test connection containing a smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler… Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Chapter 8.17.4.2.4 shall be permitted to be installed in any location… downstream of the waterflow alarm. Chapter 8.17.4.3.1 (Dry Pipe System) a trip test connection not less than 1" in diameter, terminating in a smooth bore corrosion-resistant orifice, to provide a flow equivalent to one sprinkler… Chapter 8.17.4.3.2 The trip test connection… with a shutoff valve and plug not less than 1", at least one of which shall be brass. Chapter 7.1.2 - a gridded wet pipe system shall be provided with a relief valve set to operate at 175 PSI or 10 PSI in excess of the maximum system pressure, whichever is greater. Chapter 8.16.1.2.3* A relief valve of not less than ½" in size shall be provided on the discharge side of the pressure-reducing valve set to operate at a pressure not exceeding 175 PSI. Chapter A.8.16.1.2.3 - consideration should be given to piping the discharge from the (pressure relief) valve & 8.16.2.4.3 Specifications · Material List Size 2 in A - Total Length 5.88 in B - Height 3.25 in Ship Weight 9.00 lb Quantity per Carton 1 Valve Type Check Valve Pressure Class 200 psi 400 WOG 200 WSP Specifications Item # Model 50 - 2", Model 50 Lift Check Valve Spring Loaded Lift Check Complies with MSS-SP-80-97 400 WOG at 180 ° Max 100% Pressure Tested Threaded Ends Soft Disc Integral Seat *Contains lead. Not for use in water systems intended for human consumption* Equipped with 24S disc for water service, Not recommended for steam. larger image larger image United Brass Works, Inc. 714 South Main Street Randleman, NC 27317 USA Phone: 336-498-2661 Fax: 336-498-4267 Toll-free: 800-334-3035 Email: sales@ubw.com Website: http://www.ubw.com All Categories > Fire Protection Valves & Products > Fire Protection Products - Lift Check Valves > Model 50 Lift Check Valve > Item # Model 50 - 2" United Brass Works, Inc. - Item # Model 50 - 2", Model 50 Lift Check Valvehttp://ubw.thomasnet.com/printitem/fire-protection-products-lift-check-v... 1 of 2 5/14/2012 11:55 AM End Connection Threaded Application Gas Oil Steam Water Bonnet Type Union UL Listed No FM Approved No MEA Approved No MSS Compliant Yes Canadian Registration No Pressing Machine Part No Material List United Brass Works, Inc. - Item # Model 50 - 2", Model 50 Lift Check Valvehttp://ubw.thomasnet.com/printitem/fire-protection-products-lift-check-v... 2 of 2 5/14/2012 11:55 AM Specifications · Material List Size 1 in A - Total Length 2.97 in C - Height Closed 4.25 in B - Diameter 2.75 in Ship Weight 1.76 lb Quantity Unit Pack 6 Quantity per Case 36 Valve Type Globe Valve Pressure Class 125 psi 200 WOG 125 WSP Specifications Item # Model 125SUL - 1", Model 125SUL Globe Valve Soft Disc UL Listed for Fire Sprinkler Service at 250 WOG 200 WOG at 180 ° Max 100% Pressure Tested Threaded Ends Integral Seat Rising Stem Swivel Disc Holder *Contains lead. Not for use in water systems intended for human consumption* larger image larger image United Brass Works, Inc. 714 South Main Street Randleman, NC 27317 USA Phone: 336-498-2661 Fax: 336-498-4267 Toll-free: 800-334-3035 Email: sales@ubw.com Website: http://www.ubw.com All Categories > Fire Protection Valves & Products > Fire Protection Products - Globe Valves > Model 125SUL Globe Valve > Item # Model 125SUL - 1" United Brass Works, Inc. - Item # Model 125SUL - 1", Model 125SUL ...http://ubw.thomasnet.com/printitem/fire-protection-products-globe-valv... 1 of 2 10/29/2011 3:01 PM End Connection Threaded Application Gas Oil Water Stem Type Rising Bonnet Type Screwed UL Listed Yes FM Approved No MEA Approved No MSS Compliant No Canadian Registration No Pressing Machine Part No Material List United Brass Works, Inc. - Item # Model 125SUL - 1", Model 125SUL ...http://ubw.thomasnet.com/printitem/fire-protection-products-globe-valv... 2 of 2 10/29/2011 3:01 PM Submittal data sheets can ONLY be ordered as a "Submittal Data Sheet Pack", using MC# 4400. They are not available to order on an indi- vidual basis, however each data sheet is available on the Amtrol Web Site and can be downloaded and printed for use as needed. Rev. 03/06 18 FIRE-X-TROL® FPT Series, Fire Protection Expansion Tanks(ASME) B A FPT-5-C FPT-12-C CHARGING VALVE SYSTEM CONNECTION MODELS: B A FPT-20V-C -30V-C -42V-C -60V-C CHARGING VALVE c -70V-C FPT FPT FPT FPT SYSTEM CONNECTION MODELS: In-Line Models ModelTankABSys.Ship No.Vol.HeightDiameterConn.Wt. Lit.Gal.mmins.mmins.ins.kglbs. FPT-5-C152.1264103⁄8 25410 3⁄4 NPTF9.521 FPT-12-C246.4397155⁄8 30512 3⁄4 NPTF15.436 Maximum Operating Conditions Operating Temperature-20°F (-29°C) to 200°F (93°C) Working Pressure175 PSIG (12 bar) Specifications DescriptionStandard Construction Standard Factory Pre-charge25 PSIG (1.7 bar) System ConnectionStainless Steel Diaphragm MaterialHigh-Performance Rubber Compound Liner MaterialPolypropylene ShellSteel CoatingFPT Red Fluid Compatibility With or Without Antifreeze Per NFPA13 Stand Models ModelTankABCSys.Ship No.Vol.HeightDiameterDim.Conn.Wt. Lit.Gal.mmins.mm ins.mmins.ins.kglbs. FPT-20V-C308.0495191⁄2 30512273103⁄4 3⁄4 NPTF23.652 FPT-30V-C5314.0486191⁄8 419161⁄4 324123⁄4 3⁄4 NPTF4497 FPT-42V-C6617.5616241⁄4 419161⁄4 324123⁄4 3⁄4 NPTF52.7116 FPT-60V-C9525.083833419161⁄4 324123⁄4 3⁄4 NPTF70154 FPT-70V-C12934.01054411⁄2 419161⁄4 324123⁄4 3⁄4 NPTF90197 FPT-80V-C20053.0908353⁄4 610244061611⁄4 NPTF114251 FPT-120V-C25066.01111433⁄4 610244061611⁄4 NPTF127.6281 FPT-180V-C29277.01235485⁄8 610244061611⁄4 NPTF160.3353 FPT-210V-C34190.01410551⁄2 610244061611⁄4 NPTF173.4382 Job Name___________________________________________ Location____________________________________________ ____________________________________________ ____________________________________________ Engineer____________________________________________ Contractor__________________________________________ Contractor P.O. No.___________________________________ Sales Representative_________________________________ Model No. Ordered___________________________________ Constructed per ASME Code Section VIII, Division 1. All dimensions and weights are approximate. 175 PSIG Working Pressure Step 1 L = Change in Antifreeze Solution Volume 0.621 Sv = Volume of System 18 Dl = Density of solution at lowest temp 1.050 Dh = Density of solution at highest temp 1.015 Densities are listed at NFPA 13 2002 Figure 7.5.2.5(b) Step 2 Vec = Minimum required volume (gal) of expansion chamber 1.8 P0 = Pre-charge pressure of chamber 98 P1 = Static pressure on supply side of backflow 101 P2 = Maximum allowable system working pressure 175 T0 = Temperature of chamber air at pre-charge 75 T1 = Lowest expected temperature of air in tank 60 T2 = Highest expected temperature of air in tank 80 L = Result of step 1 0.621 Notes: All pressures and temperatures absolute (psia and rankin) psia = measured + 15 psi rankin = temperature + 460 Expansion Chamber Sizing