HomeMy WebLinkAboutM05-0213 inspection M05-0213: Entries for Item:390 - MECH-Final 13:37 06/11/2013
Action Comments By Date Unique_
Ke
CR UNIT 14 GCD 07/10/2006 A000091
1.BOILER ROOM NOT COMPLETE 338
2.GRILLS DIFFUSERS NOT INSTALLED
3.EXHAUST FOR BOILER CROSSED
4.RE-ATTACH DRYER BOOSTER FAN
UNIT 13
1.SUPPORT PIPE IN MECH ROOM
2.2"PVC PIPE IS BURNED AND HAS
PRIMER IN SAME SPOT. PIPE IS
WEAKEND.
3.FLOOR DRAIN CLOGGED OR TAPED
OVER.
4.RE-ATTACH DRYER DUCT AND
POOSTERFAN
BOTH UNITS POTABLE WATER IN BOILER
ROOMS REQS VACUUM BREAKER/BACK
FLOW
PI UNIT 14 ITEMS 1&3 REQ REINSPECT. GCD 07/12/2006 A000091
ITEMS 2&4 APPROVED. UNIT 13 ALL ITEMS 403
CORRECTED AND APPROVED,
_ BOTH UNIT OK FOR TCO. _
CR UNIT 14 REQS INSPECTION GCD 03/28/2007 A000099
276
AP CORRECTIONS APPROVED. shahn 05/09/2007 A000100
500
Total Rows:4