HomeMy WebLinkAboutB13-0258 corrections required
Date:7/17/2013
Re: B13-0258 1040 Vail View Drive
Dear Mr. Reynolds
RESPONSE INSTRUCTIONS
● Submit two complete sets of revised construction documents containing the requested
information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING
COMMENTS
Architectural Comments:
1. Provide a site plan showing the location of the proposed work in relation to other structures, property lines etc. Reference section 107.2.5 IBC
2012 edition.
2. What occupancy classification is the stairs serving? Reference Chapter 107.2.3 IBC 2012 edition.
3. Is these stairs to be accessible stairs? Please clarify.
Structural
Comments:
1. Plans are to be sealed by the registrant per state law and section 107.1 IBC.
2. Plans are to reflect codes of the design as well as the design loads. Reference section
1603.1 IBC
3. Plans to reflect required special inspections or indicate none required per section 1603.1 IBC.
4. Plans have not been provided for the proposed retaining walls. Provide
plans for the prosed retaining walls to include draining design, if part of design. Include all surcharges in design.
PLANNING COMMENTS
Reviewed and accepted
FIRE COMMENTS
NA
Sincerely,
Martin A. Haeberle
Chief Building Official