Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutDRB130283 Trane 2T Condensor SpecsrE ® 4TTR5024 -S U B- 101.00
NOTE: All dimensions are in mm /inches.
TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 1521 (5 FEET)
ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN -OFF WATER DOES NOT POUR
DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 305 112'1 FROM WALE AND ALL
SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.
T
ELECTRICAL SERVICE
PANEL
K
FIG. t
25 1 1 1 1
22.2 (7/8) DIA. HOLE
LOW VOLTAGE
28.6 (1 -1/81 DIA.
O. WITH
22 2 (7/81 DIA.
HOLE IN CONTROL
BOX BOTTOM FOR ELECTRICAL H
POWER SUPPLY I F
— R -0. FOR ALTERNATE ELECTRICAL ROUTING
OLIN SERVICE VALVE, J AS LINE I// TURN BALL SERVICE VALVE. "D"
"E" D. FEMALE BRAZE D. FEMALE BRAZED CONNECTION WITH /d" SAE
CONNECTION WITH /d" SAE G FLARE PRESSURE TAP FITTING.
FLARE PRESSURE TAP FITTINGS.
FIG. 2
From Dwg. D156010
MODELS
BASE
E' ' H I LINE SEAM CE
�e
C
VALVE, "E" I.D. FEMALE
E
F
BRAZED CONNECTION
1 11 1 j
K
WITH I/4" SAE FLARE
3
730
PRESSURE TAP FITTING.
756
3/4
GAS LINE SERVICE VALVE,
127 (5)
76 (3)
"D" I.D. FEMALE BAAZED
508 (20)
CONAE NET ION WITH 1/4" SAE FLARE
NO
PSSU RE TAP FITTING.
FIG. 2
From Dwg. D156010
MODELS
BASE
A
I B
C
I D
E
F
I G
1 11 1 j
K
4TTR5024E
3
730
829
756
3/4
3/8
127 (5)
76 (3)
197 57
508 (20)
COMPRESSOR HEAT
NO
(28 -3/4)
(32 -5/8)
(29 -3/4)
23-1
TYPE DRIVE - NO. SPEEDS
DIRECT - 1
CFM @ 0.0 IN. W.G. O
(7 -3/4) (2 -1/4)
NO. MOTORS - HP
2 Ton Split System Cooling -1 Ph
4TTR5024E
Product Specifications
OUTDOOR UNIT 00 4TTR5024E1000A
POWER CONNS. — V /PH /HZ ®
208/230/1/60
MIN. BRCH. CIR. AMPACITY
9
BR. CIR. l MAX. (AMPS)
15
PROT. RTG. } MIN. (AMPS)
15
COMPRESSOR
CLIMATUFF°
NO. USED - NO.SPEEDS
1 -1
VOLTS /PH /HZ
200/230/1/60
R.L. AMPS 0 - L.R. AMPS
6.8-38.6
FACTORY INSTALLED
1 62.9
START COMPONENTS (D
YES
INSULATION /SOUND BLANKET
YES
COMPRESSOR HEAT
NO
OUTDOOR FAN
PROPELLER
DIA. (IN.) - NO. USED
23-1
TYPE DRIVE - NO. SPEEDS
DIRECT - 1
CFM @ 0.0 IN. W.G. O
2690
NO. MOTORS - HP
1 - 1/8
MOTOR SPEED R.P.M.
850
VOLTS /PH /HZ
200/230/l/60
F.L. AMPS
.70
OUTDOOR COIL —TYPE
SPINE FINTM
ROWS - F.P.I.
1-24
FACE AREA (SQ. FT.)
16.25
TUBE SIZE (IN.)
3/8
REFRIGERANT
LBS. — R-41 OA (O. D. UNIT) ©
6 LBS., 3 OZ.
FACTORY SUPPLIED
YES
LINE SIZE - IN. O.D. GAS ©
3/4
LINE SIZE - IN. O.D. LIQ. ©
3/8
CHARGING SPECIFICATION
SUBCOOLING
10 °F
DIMENSIONS
H X W X D
CRATED (IN.)
34 x 30.1 x 33
WEIGHT
SHIPPING (LBS.)
201
NET (LBS.)
174
Certified in accordance with the Air - Source Unitary Air - conditioner Equipment certification program, which
is based on ARI standard 210/240.
Rated in accordance with ARI standard 270.
Calculated in accordance with Nail. Else. Codes. Use only HACR circuit breakers or fuses.
® Standard Air — Dry Coil — Outdoor
This value approximate. For more precise value see unit nameplate.
Max. linear length 60 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft,
For greater length consult refrigerant piping software Pub. No. 32- 3312 -0'
(' denotes latest revision).
This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to
compute minimum branch circuit ampacity and max. fuse size.The value shown is the branch circuit selection
current.
No means no start components. Yes means quick start kit components. PTC means positive temperature
coefficient starter.
A- weighted Sound Power Level [dB(A)]
Note: Tested in accordance with ARI Standard 270.95. (Not listed with ARI)
0 2009 Trane
SOUND POWER
A- WEIGHTED FULL OCTAVE SOUND POWER LEVEL dB - [dB(A)] High Stage
MODEL
LEVEL [dB(A)]
63 125 250 500 1000 2000 4000 8000
4TTR5024E1
79
23
45.4
57
70.9
1 74.2
1 70.5
1 62.9
52.6
Note: Tested in accordance with ARI Standard 270.95. (Not listed with ARI)
0 2009 Trane
Trane
www.trane.com
Mechanical
Specification Options
General
The 4TTR5 is fully charged from the
factory for up to 15 feet of piping. This
unit is designed to operate at outdoor
ambient temperatures as high as 115 °F.
Cooling capacities are matched with a
wide selection of air handlers and fur-
nace coils that are A.R.I. certified. The
unit is certified to UL 1995. Exterior is
designed for outdoor application.
Casing
Unit casing is constructed of heavy
gauge, G90 galvanized steel and
painted with a weather - resistant powder
paint
on all louvers, panels, prepaint on all
other panels. Corrosion and weather-
proof CMBP -G30 DuraTuffTm base.
Refrigerant Controls
Refrigeration system controls include
condenser fan and compressor contac-
tor. High and low pressure controls are
inherent to the compressor. A factory
installed liquid line drier is standard.
Compressor
The Climatuff° compressor features
internal over temperature and pressure
protection and total dipped hermetic
motor. Other features include: roto lock
suction and discharge refrigerant con-
nections, centrifugal oil pump and low
vibration and noise.
YNI re'TOUS
69T. C
ARI Standard CISTE
210/240 UAC
Condenser Coil
The outdoor coil provides low airflow
resistance and efficient heat transfer.
The coil is protected on all four sides by
louvered panels.
Low Ambient Cooling
As manufactured, this unit has a cool-
ing capability to 55 °F. The addition of
an evaporator defrost control with TXV
permits low ambient cooling to 30° F.
Accessories
Thermostats — Cooling only and heat/
cooling (manual and automatic change-
over). Sub -base to match thermostat
and locking thermostat cover.
05/09
Trane has a policy of continuous product and product data improvement and it reserves the right to change