HomeMy WebLinkAboutF13-0008 FLUSH TEST.pdf CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR U NQERGROUN© PIPING ROCEDURE pon completion of work,inspection and tests shall be made by the contractor's representative and Witnessed by an owner's representative. AlI defects shalt be xmted and system left in service before contractor's personnel finally leave the job. certrfrcate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities,owners,and contractor. It is understood ie Owner's napresentative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to comply with approving uthority's requirements or local ordinances_ ZOPERTY NAME 3OPERTY ADDRESS ACCEPTED BY APPROVIN01 AUTHORETY('S)NAMES ADDRESS PL/IIUS INSTALLATION CONFORMS TO ACCEPTED PLANS YES NO EQUIPMENT USED I'S APPROVED ❑YES [J NO IF NO,EXPLAIN DEVIATIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION 0 YES ❑ NO OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN VMMCMNS HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CAME AND MAINTENANCE CHARTS BEEN LEFT ON THE PREMISES? ❑YES ❑ NO _. .IF NO,EXPLAIN i]YES ❑ NO YES ❑ NO L.00A1110114 SUPPLIES BUILDING: PIPE TYPI=S AND CLASS t� __, _ TYPE JOINT PIPE CONFORMS TO NFPA-24 STANDARD �S NO UNDERGROUND:' FITTINGS CONFORM TO NFPA44 STANDARD:- NO YES PIPES IF NO,EXPLAIN AND JOINTS JOINTS NEEDING ANCHORAGE CLAMPED,STRAPPED,OR BLOCKED IN NO YES ACCORDANCE WITH NFPA-24 STANDARD IF NO,EXPLAIN FLUSHING. Flow the required rate until water to clear as Indicated by no collection of foreign matmiel in burlap begs at outlets such as hydrants and blow-offs. Flush at flaws not less than 390 GPM(1476 Llm1n)for 4-inch pipe,380 GPM(3331 Umin)for 64nch pipe,1560 GPM(5905 Umin)for Bench pipe,2440 GPM (9235 Llmin)for 10.Inch pipe,and 3520 GPM(13323 Urnin)for 112-Inch pipe. When supply cannot produce stipulated flow rates,obtain maximum available. HYDROSTATIC. Hydrostatic tests shall be made Rot Jess than 2W psi(13.8 bars)for two hours Or 5O psi(3A bars)above static pressure in excess of 150 psI TEST (10.3 bars)for two hours. DESCRIPTION LEAKAGE.- New Pipe laid with rubber gasketed joints shall,If the workmanship Is satisfactory,have little or no leakage at the Joints. The amount of leakage at the joints shall r,ot exceed 2 qts.Per hr.(1.89 Ilh)per 100 joints Irrespective of pipe diameter. The leakage shall be distributed over all joints. If such leakage otxurs at a few Joints the InsWiatlon shall be considered unsatisfactory and necessary repairs made. The amour$of allowable,leakage specified above may be Increased by 1 L Oz per in.Valve diameter per hr.(30 mLJ25 mm1h)for each metal seated valve Isolating the test section. If dry barrel hydrants are tested with the main valve open,so the hydrants are under pressure,an additional 5 oz per minute(150 rnUmin)leakage is permitted for each hydrae NEW UNDERGROUND PIPING FLUSHED A CORD G TO NFPA-24 STANDARD NO YES BY(COMPANY) � �Clr/t Iy� 'i IF NO,EXPLAIN HOW FLUSHING FLOW WAS OBTAINED THROUGH WHAT TYPE OPENING FLUSHING a PUBLIC WATER ❑ TANK OR RESERVOIR ❑ FIRE PUMP 3 HYDRANT BUTT ZJ OPEN PIPE TESTS LEAD-INS FLUSHED ACCORDING TO NFPA-24 STANDARD J2F NO YES BY(COMPANY) IF NO,EXPLAIN HOW FLUSHING WAS OBTAINED THROUGH WHAT TYPE OPENING Zr PUBLIC WATER [] TANK OR RESERVOIR [] FIRE PUMP Y CONN.TO FLANGE&SPIGOT Ed OPEN PIPE (OVER) ALL NEW UNDERGROUND PIPING HYDROSTATICALLY TESTED AT .JOINTS COVERED HYDROSTATIC.. [.'.] TEST l b - FOR HOURS YJ YES © NO PSI TOTAL AMOUNT OF LEAKAGE MEASURE} L•I`A"GE GALS. HOURS TEST ALLOWABLE LEAKAGE GALS, HOURS HYDRANTS NUMBER INSTALLED TYPE AND MAKE ALL OPERATE SATISFACTORILY —� ❑ YES E3 NO WATER CONTROL VALVES LEFT WIDE OPEN Ll YES .. NO CONTROL IF NO,STATE REASON VALVES HOSE THREADS OF FIRE DEPARTMENT CONNECTIONS AND HYDRANTS INTERCHANGEABLE WITH THOSE OF FIRE DEPARTMENT ANSWERING ALARM DYES [I NO.. DATE LEFT IN SERVICE NAME OF INSTALLING CONTRACTOR: TESTS WrrNESSED BY . F RTY OWNER�sI NED) TRI SIGNATURES �C+�-- FOR INST L IGNED) TITLE FOR LOCAL Fit MARS IGNED) TITLE DATE FOR RESPONSIBLE A PLO (SI ) TITLE DATE )DITIONAL EXPLANATION AND NOTES �W.CK)