HomeMy WebLinkAboutA13-0046 DATA SHEETS Honeywell
VISTA-32FB
COMMERCIAL PARTITIONED FIRE AND �`'� '"
.�;,�'.t�;
�. .. ,
BURGLARY ALARM CONTROL PANEL . . �i� _�•:�-�
;,. C� ,
� _ �
�, � �, --
,� � . �
� � ` _ '�
�.
�.1 t;_ ,�,
Now UL864 9th Edition Approved
Designed to integrate seamlessly with CCTV, access control initiating devices, notification circuits, communication devices,
and Honeywell's full range of fire and burglary components, keypads, RF receivers and relays are also supported.
the new VISTA-32FB provides the ultimate protection of life The VISTA-32FB has been designed to mount quickly
and property. The UL Listed commercial fire and burglary and easily.
control panel supports up to two partitions and up to
32 zones/points using hardwired, wireless and V-Plex�
addressable technologies. A diverse line of Honeywell
FEATURES
• Supports addressable V-Plex access • Automatic smoke detector sensitivity • False alarm reduction features:
control points using VistaKey maintenance testing -Exit error logic
(One to Four doors) -Exit delay reset
• Commercial Wireless Fire and
• Supports eight hardwired zones, Burglary -Cross zoning
-Call waiting defeat
24 V-Plex addressable points/zones, . Notification Appliance Circuits (two): -Recent close report
or 32 wireless points/zones -Programmable
• Can control two separate areas - Individually silenceable
• Supports commercial hardwired,
addressable V-Plex polling loop
(partitions) independently . Carbon monoxide (CO)zone support and wireless zones
• Stores up to 512 events and can (Rev 5 and higher)
accommodate 75 user codes • Listed to UL864 9th Edition (Rev 5
• Programmable on-board auxiliary and higher)
• Easily programmed and maintained relay
with newly upgraded Compass
Downloader Software
VISTA-32FB Honeywell
COMMERCIAL PARTITIONED FIRE AND
BURGLARY ALARM CONTROL PANEL
ADDITIONAL FEATURES
• Hardwired zones —Two-wire smoke detector • Up to four doors using VistaKey
—Provides nine style B hardwired zone/group expansion module V-Plex Access Control
zones adds two or four zones
• Stored events for one call retrieval
—EOLR supervised for Fire and UL —Eight zone—Class A and B
• Communication
burglary installations extender module
—Panel operation during download
—Supports N.O. or N.C. sensors —Eight zone—Class B extender _Split/Dual Reporting
— Individually assignable to one of module
eight partitions —One zone supervised contact Applications
—Up to 16 two-wire smoke detectors monitor module The VISTA-32FB control is well suited
for a variety of applications as an
each on zone one and two(32 total) • UL Listed wireless expansion
integrated fire and burglary control.
• Patented addressable V-Plex ollin —Supports up to 32 wireless zones/ Some of the a lications su
p g pp pported are:
points using 5881 ENHC or
loop technology medical and professional buildings,
5883H Receiver
—Supports up to 24 two-wire V-Plex churches or synagogues, office
zones/points —Supervised by control for buildings, schools, strip malls,
—Global polling technology for check-in signals residences and factory or warehouse
faster processing —Tamper protection for transmitters
environments.
—Supervised by panel — Individually assignable up to Installation
— Individually assignable to partitions, eight partitions The VISTA-32FB alarm system has
notification circuit (bell) output or —Supports wireless smoke detectors been designed to mount both quickly
and easily. It meets all applicable
aux relay • Event reporting requirements for UL commercial fire
—4,000 ft. capability without the use . Local printer for access or and burglary installations.
of shielded cable
VISTA related event
— Extender/Isolation bus modules
Honeywell
SPECIFICATIONS
Electrical Main Dialer Agency Listings
• Primary power: 18VAC @ 72VA • Line seize: Double Pole • FCC Part 15, Class B; FCC Part 68
ADEMCO No. 1451 . Ringer equiv.: 0.7B • UL864/NFPA 72, Central Station and
• Quiescent current draw: 300mA . Formats: ADEMCO Low Speed, Remote Station (Fire)
• Backup battery: ADEMCO 4+2 Express, ADEMCO • UL609 Local Mercantile
- 12VDC, 7AH min to 34.4AH max High Speed, ADEMCO Contact ID, Premises/Mercantile Safe&Vault
-Lead acid battery(gel type) Sescoa and Radionics . UL365 police station connected
•Alarm power: 12VDC, 1.7A max for Cabinet dimensions burglar alarm
each notification (bell) circuit output . 14.5" H X 12.5" W X 3" D • UL610 Central Station
•Aux. standby pwr: 12VDC, 1 A max Burglar Alarm
Environmental
•Total power: 2.3A at 12VDC, . Storage temp: 14° F to 158° F • California State Fire Marshal
3.4A at 24VDC from all sources (-10° C to 70° C) • FM
• 24 hours with 1A standby load . Operating temp: 32° F to 122° F • CAN/ULC S304-Central and
Fusing (0° C to 50° C) Monitoring Station Burglar Alarm Unit
• Battery input, aux. and notification • Humidity: 85% RH • CAN/ULC S527-Central Unit for
(bell) circuit outputs are protected . EMI: Meets or exceeds the Fire Alarm Systems
using PTC circuit protectors. All following requirements: • CAN/ULC S303- Local Burglar
outputs are power limited. - FCC Part 15, Class B Device Alarm Unit
- FCC Part 68
• CAN/ULC S525-Audible Signal
- IEC EMC Directive
Appliances
VISTA-32FB
COMMERCIAL PARTITIONED FIRE AND BURGLARY ALARM CONTROL PANEL
COMPATIBLE DEVICES
Auxiliary Devices • 4190WH AlarmNet Communicators
• 4204-Relay Module, • 4193SN Two Zone Serial • 7545i-ENT- Internet/Intranet
four form C contacts Interface Module Communicator
• 4204CF-Two supervised • 4208U Loop Expansion Module • 7845GSM-Digital Cellular
output circuits -eight zones Communicator
• 5140DLM-Supervised Dialer • 4208SNF Eight Zone/2 Class A/6 • 7845i-GSM-Internet and Digital
• 5881 ENHC-RF Receiver Class B Expander Module Cellular Communicator
• 5883H-RF Receiver • 4293SN One Zone Serial
• 6160CR-2- Red Alpha Keypad Interface Module Access Control
•VistaKey V-Plex(addressable)
• 6160- Burglary Keypad • 4297 Isolator/Extender Module Access Control
• 6220S-System printer used with •V-Plex VSI Isolator Module .VistaKey-SK Starter Kit
4100SM serial module V-Plex Smoke Detectors •VistaKey-EX Expansion Kit
Two-Wire Smoke Detectors • 5193SD
Commercial Wireless Devices
Conventional • 5193SDT
• 5808W3-Photoelectronic
• System Sensor V-Plex Passive Infrared Detectors Smoke/Heat Detector
• ESL . gggMX • 5806W3-Photoelectric Smoke
• DSC • IS2500SN Detector
Horn/Strobes • DT7500SN • 5809-Wireless Heat Detector
• System Sensor • QUEST2260SN • 5817CB-Wireless
•Wheelock Commercial Transmitter
V-Plex Contacts
• Gentex • 4194WH • 5869- Hold-Up Transmitter
Manual Pull Stations • 4939SN-WH • 5881 ENHC-RF Receiver
• 5140MPS-1 • 4944SN-WH • 5883H-RF Receiver
• 5140MPS-2 • 4959SN
V-Plex(Addressable) Devices V-Plex Glassbreak Detectors
• 4101 SN Relay Zone Module • FG1625SN
• 4190SN Remote Point Module
-two zones
Product specifications subject to change.
ORDERING
VISTA-32FB Commercial Fire and Partitioned Burglary Alarm Platform
V32FB-9 UL864 Rev 9 Version (Rev 5 and higher)
Automation and Control Solutions
Honeywell Security&Communications Honeywe"
2 Corporate Center Dr. Suite 100
Melville, NY 11747
1.800.467.5875 wisTS2FBi�
October2010
www.honeywell.com oO 20�o Honeywell�nternationa�Inc.
���:�:GFI��IF't�IEC;:�::�:�+:,�:
= FEHC�',' T��i i��:f°1
6160 �-
ALPHA DISPLAY KEYPAD �4
— ��*.r:�ISRR�IE����*
i -i = ��AU4' T� ��`M
i
WITH DOOR ATTACHED ..,,�� .�.. f „ z m 3 ,:.
��_ .� a w s - i s,w.
.�r. �,-., a 9.�
� .,:;. a x
WITHOUT DOOR
The 6160 Deluxe Keypad is easy to install and simple to The oversized function keys are easily accessed even when
use. The attractive white console blends with any decor and the keypad door is closed, and can be programmed for fire,
features a contoured, removable door that conceals burglary, personal emergencies and other operations. Colored
illuminated soft-touch keys. The 6160 also features a new self-adhesive labels are included.
larger and brighter 32-character display with easy-to-read
plain-English status messages.
FEATURES
• Large, easy-to-use keypad • Zones and system events displayed • System functions clearly labeled
• Keys continuously backlit for greater in plain English • Functions performed by just entering
visibility • No confusing blinking lights security code plus command
• Speaker with audible beeps • Four programmable function keys • White with removable door blends
to indicate: with any decor
- System status
- Entry/exit delay
- Other alarm situations
SPECIFICATIONS
Physical Wiring Compatibility
• 5-5/16"H x 7-3/8"W x 1-3/16"D • - (Black): Ground • Fully compatible with all
(135mm x 190mm x 30mm) . + (Red): +12 VDC (Aux. Power) VISTA controls.
Current
• D1 (Green): "Data in"to control panel
• Standby-40mA
• DO (Yellow):"Data out"from
•Activated Transmission-160mA control panel
ORDERING
6160 Alpha Display Keypad
Honeywell Security&Custom Electronics �������'
Honeywell International Inc.
PO Box 9035 cooso,o
Syosset, NY 11791 U6160/D
September 2006
www.honeywell.com o 2oos HoneyWeu inter�at�o�ai i��.
•i, L V L
P R 0 D U C T I N F 0 R M A T I 0 N B U L L E T I N
� � .;.; . . 449 / 448 SERIES
,;;.,.:.
,. � f �f��' _ � �� Self-Diagnostic, Four-
��:f, _ . �
� � R�� ` � Wire, Photoelectric
���i�: _ � ,�
�{� .�:-v ��
,f,�,:�r
f,���.�� Smoke Detectors
fas: _
Model numbers:
449AT,449C,449CT,449CRT,449CST,449CSTE,
� , 449CSRT,449CSRH,449CTE
-•. -Y.,
� _.:.��;: :. �.�_.. : o L F M U LC
:� � LISTED APPROVED
_;f � .r
- -;;•r,��=r-� California State Fire Marshal Approved
MEA(New York City)Approved
ULC model numbers:
448AT,448C,448CT,448CST,448CSRH,448CTE
• Intelligent, self-diagnostics The ESL 449/448 Series self-diagnostic, four-wire
smoke detectors continually monitor their own
• On-site maintenance alert sensitivity and operational status, and provide a
visual trouble indication if they drift out of sensitivity
• Field replaceable optical chamber range orfail internal diagnostics. This unique,
• Low-p rof i l e d esi g n patented technology meets N FPA 72 field sensitivity
testing requirements without the need for external
• Plug-in terminal block meters.
Additional diagnostic information is activated by
• Advanced false alarm immunity applying a magnet near the detector's integral reed
switch. This initiates a self-diagnostic routine and
provides visual indication of sensitivity level, or if
service is required.
This series is easily cleaned by simply replacing
ESL's proprietary field-replaceable optical chamber. All
models are designed to reduce false alarms from
dust, insects, RFI, and external light.
An integral combination rate-of-rise and fixed
135°F (57°C), 50-foot rated, heat sensor is available
with all "T" model detectors (see selection guide),
allowing latching of the alarm for either smoke or
heat. The 449CSRH includes an isolated alarm
output for heat and activates an internal non-latching
sounder (local alarm) for smoke, making it ideal for
motel/hotel and dormitory rooms where smoking is
permitted.
continued
ESL 449 Series Sl�noke Detectors
Architectural and Engineering Specifications
The ESL 449 Series low-profile, self-diagnostic,four-wire The proprietary optical sensing chamber is field replaceable,
smoke detectors work on the light scattering principle.A allowing quick and easy cleaning and maintenance.
pulsed infrared light-emitting diode serves as the light source, Models with auxiliary relays are approved for releasing
and a high-speed photodiode as the sensing element. When service.
the amount of light reflected onto the photodiode reaches the This low profile product is equipped with a hinged cover, a
sensitivity setting,the smoke sampling rate increases. Three concealed tamper-resistant latch, and insect screens.
(3)successive smoke sensings above the sensitivity setting Wiring terminates in plug-in, clamp-type screw terminals.
are required to sound an alarm.This design has superior Detectors mount to a standard single-gang electrical box, a
protection against false alarms caused by dust, insects, RF four-inch octagonal,four-inch square electrical box, or
and ambient-light. WIREMOLD 5739 fixture box.
A confirmed alarm causes the normally flashing power Smoke Detector Spacing
indicator LED to light continuously and the alarm relay to On smooth ceilings(as defined in NFPA 72),spacing of 30 feet
operate. A trouble indication is automatically displayed by (g.1 meters)may be used as a guide. Other spacing may be used
flashing the LED every second. This meets NFPA 72 field depending on ceiling height,high air movement,and other
sensitivity testing requirements. An internal 85 dB horn conditions or response requirements.
(available in"S" models)emits a temporal 3 when the
detector alarms and a steady tone when power polarity is t
reversed.
,.85•�4���m,� 6.,•�,5.5�m) —
� I
1 �—0 —
Product Data
Sensitivit 3.1 - 1.0%/ft. max. -CST..........................................................................40mA
y................................................. ( )
3.1 +0.50%/ft. (min) -CSRT, CSRH, CSTE................................................51 mA
Operating temp. range ............... 32°F to 120°F(0°C to 50°C) Typical avg. polarity reverse current
Operating humidity range....................................0 to 95% RH -CST, CSRT, CSTE, and CSRH................................10mA
Minimum voltage-C, CT, CRT, CST, CSRT, CSRH , Sounder specifications.........................................85 dB at 10'
-CSTE.........................................................................8.5V Heat detector specifications
-AT..............................................................................5.1V -fixed temperature ..................................... 135°F(57.2°C)
Maximum voltage-C, CT, CRT, CST, CSRT, CSRH, -rate of rise .... 15°F/min. &>105°F(8.3°C/min. &>40.6°C)
-CSTE...........................................................................33V Auxiliary relay contacts 2A @ 28 VDC or 120 VAC (resistive)
-AT................................................................................27V Alarm contacts ........................ 500 mA @ 36 VDC(resistive)
Maximum ripple(peak to peak)........................................ 10% Field wiring size.................................................. 14-24 AWG
Typical average standby current.....................................70aA Packaging .......................10 detectors are packed in a carton
-CSTE........................................................................23mA Color....................................................white cover/white base
Typical alarm current-C, CT and AT ............................ 15mA with UV inhibitor to prevent yellowing
-CRT..........................................................................31 mA Listin UL 268, ULC FM, CSFM and MEA
g..............................
Selection Guide
Designator Feature Description
H Isolated Fixed Temp. Isolated fixed 135°F(57°C)and rate of rise heat detector,independently trips the LED and
alarm and Rate of Rise output.Smoke detector activates intemal sounder(local alarm)and auxiliary relay,but
Heat Detector does not latch.Approved as both single station smoke alarm and system heat detector.
Ideal for hotel,motel and dormitory rooms where smoking is allowed.
R Auxiliary Relay Used to activate other devices such as elevator recall,door holders,strobes,etc.Listed for
releasing service.
S Built-in Sounder 85dB built-in sounder alarms when smoke is detected or when power wiring polarity is
reversed.
T Intergrated Fixed Intergrated Fixed 135°F(57°C)temperature and rate of rise heat detector.
Temp.and Rate of Either heat detector or smoke detector can trip and latch LED and alarm protection.
Rise Heat Detector relay outputs.
E Built-in end of line Relay is normally energized and will trip with loss of power.Can also provide notification
power supervision relay when detector needs maintenance.
in t e r I o g i►i•.. PH�3.692.�5Z ��,������x.���
US4 8 Canada: 800.547.2556 Irnerlogix,Cadd�c,H,lil and�trol aretraAmiarksof
Technical Service: 800.6487424 FaxBack:800.4832495 irnenogix,inc
w�vw.sentrd.wrn www.ir�eaiogi�csearity.mm
E-3965 Rev B-1101
�� SYSTEM �
��� SENSOR° �` -___.�
� ,
'�
BI
5600 Series Mechanical � `
Heat Detectors ��� � � +
_� �
. _
...s.
� � �,
System Sensor's 5600 series mechanical heat detectors '�
offer a low-cost means for property protection against ;
�
�
fire, and for non-life-safety installations where smoke �`
� ,,�
detectors are inappropriate.
`__ ?�,������� �':-` - ,
Features Multiple configurations.The 5600 series offers a full-line of
•Multiple configurations for installations configurations to accommodate a broad range of applications.Both
—Single-and dual-circuit models single-and dual-circuit models are available for low-and high-
—Fixed temp and combination fixed-temp/rate-of-rise temperature ratings with either fixed temperature or combination
135°F or 194°F ratings. fixed temperature/rate-of-rise(ROR)activation.The ROR element of
the fixed/ROR models is restorable to accommodate field-testing.
•Plain housing for residential installations(Model 5601 P)
•Easy-to use terminal screws Installation flexibility.To satisfy a variety of installation needs,
•A broad range of back box mounting options: the 5600 series easily mounts to single-gang and octagonal back
—Single gang boxes.And these models accommodate four-square back boxes,
—3.5""and 4"Octagonal when used with a square to round plaster ring.The reversible
—4""square with square to round plaster ring mounting bracket permits both flush-and surface-mount back box
installations.
•Reversible mounting bracket
Visual identification.The 5600 series provides dear markings on
the exterior of the unit to ensure that the proper detector is being
used.Alphanumeric characters identify the activation method,as
well as the temperature rating,in Fahrenheit and Celsius degrees.
Fixed temperature models are identified FX,while combination
fixed/rate of-rise units are marked FX/ROR.The 5600 series also
provides a post-activation indicator in the form of a collector.When
the detector is activated,the collector drops from the unit,making it
easy to identify the unit in alarm.
Agency Listings
�
u� F M MEA «(��
a roved ��'°°'°
LISTED APPROVED pp
s_,oi io,aoce i.�-os-e ;zio-;zo���zz,
Specifications
Mechanical heat detector shall be a System Sensor 5600 series model number ,listed to Underwriters Laboratories UL 521 for Heat Detectors for Fire
Protective Signaling Systems.The detector shall be either a single circuit or a dual-circuit type,normally open.The detector shall be rated for activation at either
135°F(57°C)or 194°F(90°C),and shall activate by means of a fixed temperature thermal sensor,or a combination fixed temperature/rate-of-rise thermal sensor.
The rate of rise element shall be activated by a rapid rise in temperature,approximately 15°F(83°C)per minute.The detector shall indude a reversible mounting
bracket for mounting to 3'/z-inch and 4-inch octagonal,single gang,and 4-inch square back boxes with a square to round plaster ring.Wiring connections shall
be made by means of SEMS screws that shall accommodate 14-22AWG wire.The detector shall contain alphanumeric markings on the exterlor of the housing
to identify its temperature rating and activation method.The rate of rise element of combination fixed temperature/rate of rise models shall be restorable,to
allow for field-testing.The detectors shall indude an external collector that shall drop upon activation to identify the unit in alarm.
•.
Maximum Installation Temperature 5601 P,5603,5621,and 5623:100°F(38°C)
5602,5604,5622,and 5624:150°F(65.6°Q
Operating Humidity Range 5 to 95%RH non-condensing
Dimensions with mounting bracket Diameter:4.57 inches(11.6cm)
Height: 1.69 inches(43cm)
Alarm Temperature 5601 P,5603,5621,and 5623:135°F(57°C)
5602,5604,5622,and 5624:194°F(90°C)
Weight 6 oz(170 grams)
Rate-of-RiseThreshold 15°F(83°Q rise per minute(models 5601 P,5602,5621,and 5622 only)
Mounting 3Yrinch octagonal back box
4 inch octagonal back box
Single gang back box
4-inch square back box with a square to round plaster ring
. .
Operating Voltage/Contact Ratings 6-125VAC/3A
6-28VDC/1 A
125VDC/03A
250VDC/O.IA
InputTerminals 14-22 AWG
eoai� xi xi aoaixi
O O O O O
�4� � � o � � i � i- �
5607P 5602,5622 5603,5623 5604,5624 5621
Ordering Information
- - �
5601 P Single None 135°F(57°C) Fixed Temperature/Rate of Rise 50 feet x 50 feet(15.24m x 15.2m)
5602 Single Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(1524m x 152m)
5603 Single Lettering 135°F(57°Q Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5604 Single Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5621 Dual Lettering 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(1524m x 152m)
5622 Dual Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(1524m x 15Zm)
5623 Dual Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5624 Dual Lettering 194°F(90°Q Fixed Temperature 25 feet x 25 feet(7.62m x 7b2m)
*NOTE:Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.
l\��� �\��� �ZOCE �_tc n Sen�
�� �� 3825 Ohio Avenue•St.Charles,IL 60174 ��a��rspe<�fi��o�ss�u,��<<o�rz ge �mou�,���<e.u�s��sys�emsenso�-�omro�
��� �����R� PhOIl2:80�-SENS�RZ•FdX:63�-3��-6495 currenrproduainformation,�mdudingthelares[verslonofthlsdatasheet.
A05-0351-002•11/06•i31676
�� SYSTEM _ . ,y _ ,_ , _
��� SENSOR° � ��;:���
�
. � *
C01224T
Carbon Monoxide �
��
Detector ,�
with RealTestTmTechnology � ,�,;��
i � .�� �
�
The System Sensor C01224T CO detector provides early - � _� �,,�:
��
warning by using electrochemical sensing technology ° -�
to measure carbon monoxide levels in the air.
Features With RealTest`"technology,the CO gas sensing cell of the
•RealTest�"technology allows installer to test detector with CO gas C01224T CO detector can be tested using a carbon monoxide gas
agent Simply hold the test button for two seconds.After the alarm
•Full compliance with UL 2075 cyde(temp 4)the green LED will flash about once per second,
•A code required trouble relay indicating that the detector is ready to accept CO for testing.
•Wiring supervision with SEMS terminals Spray a small amount of CO into the detector per the installation
instructions,and within seconds the detector will alarm,indicating
•A six year end-of-life timer successful gas entry.
•12/24 VDC
•A current draw of 20mA in standby and 40mA in alarm If dangerous amounts of carbon monoxide is detected,the C01224T
detector will alert residents by sounding and flashing a temp-4 signal
•Versatile mounting for wall and ceiling alarm.Protection is guaranteed 24/7 by a central station,regardless
•Electrochemical sensing technology of whether residents are away from home,sleeping or already
suffering from the efFects of C0.
This specific device is designed for system operation.The detector is
fully listed to UL 2075.It offers a code required trouble relay to send
a sensor failure or end-of-life signal to the control panel and the
central station.It also uses SEMS-type terminal Philips head screws
to provide a quicker and more positive wiring connection and code
required wiring supervision.The C01224T detector offers a low
current draw,allowing more devices to be connected to the panel
without having to purchase a more expensive panel or an extra
power supply.
The C01224T model will operate on most industry security and fire
Agency Listings alarm control panels because it is is a 12/24VDC detector.
U`
LISTED
�o�s
C01224T Carbon Monoxide Detector Specifications
Carbon monoxide detector shall be a System Sensor model number C01224T,listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and
Sensors.The detector shall be equipped with a sounder and a trouble relay.The detector's base shall be able to mount to a single-gang electrical box or direct
(surface)mount to the wall or ceiling.Wiring connections shall be made by means of SEMS screws.The detector shall provide dual color LED indication,which
blinks to indicate normal standby,alarm,or end-of-Iife.When the sensor supervision is in a trouble condition,the detector shall send a trouble signal to the
panel.When the detector gives a trouble or end-of-life signal,the detector shall be replaced.The detector shall provide a means to test CO gas entry into the CO
sensing cell.The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.
Operating Voltage 12/24 VDC
Audible Signal 85 dB in alarm
Standby Current 20 mA
Alarm Current 40 mA(75 mA test)
Alarm Contact Ratings 0.5 A@ 30 VDC
Trouble Contact Ratings 0.5 A@ 30 VDC
Size Length:5.1 in,Width: 33 in,Height:13 in
Approximate Weight 7 oz
Operating Temperature Range 32°F to 104°F(0°C to 40°C)
Operating Humidity Range 22 to 90%RH
InputTerminals 14 to 22 AWG
Mounting Single gang back box;surface mount to wall or ceiling
Operation Modes
.. - � - �
Normal(standby) Blink 1 per minute — —
Alarm — Blink in temp 4 pattem Sound in temp 4 pattern
RealTest""Feature: The System Sensor C01�24T carbon monoxide detector with RealTest` can evaluate the functionality of the CO sensing cell using
canned tcst agent.
- • • <� '�
_ � � \
� i
^ � �
�� r � I�
� �:
� 0
Push and hold theTest/Hush button for Spray canned CO agent Into the detector. Verify CO sensing at the control panel.The
two seconds to enter RealTest mode.The detector will automatically exit RealTest
green LED will flash once every second to alarm mode after about 20 60 seconds.
indicate RealTest mode has started.
NOTE:Check with local codes and the AHJ to determine whether or not a functional gas test is desired for an Installation.
Hush Feature: Pushing theTest/Hush button will silence the sounder for S minutes(except in RealTest mode).
Trouble Feature: When the detector is in a trouble condition,it will send a trouble signal to the panel.
End of IifeTimer: After the detector's internal sensor has reached the end of its life,a trouble signal will be sent to the panel.This will indicate that it is
time to replace the detector.An electrochemical carbon monoxide detector lifespan is approximately six years,and the detector must
be replaced by the date marked on the inside of the product.
Ordering Information
�-
C01224T 12/24 volt,4 wire system monitored carbon monoxide detector with RealTest""Technology
�� SYSTEM ozoo8 sy,em sen=o�.
w, 3825�h10 f�V2YlUe•St.�{ldY�eS,��6�174 ?roductspe6�ca�onssub�rcttorn gcwithoutnotrce.uis�sysremsensor.comfor
�' �l' SE/�/SOR Ph0112:8��-SENS�RZ•FdX:63�-3��-6495 cwren[producUnfom�ation,lndudingehelacestversionofthlsdatasheet.
� A05-0437-000•8/OS•H1953
�� SYSTEM _ _ . ,
, _,
� SENSOR° �"
� �
_-� --- �
- - � -
Mini-Horns = �� �' �
, � �� �-
� � �
b; ; ��
� � �—
, �` ."� �
The SpectrAlert�Advance series of mini-horn sounders "�� ��
�
are designed to simplify installations to provide '�
;��
primary and secondary signaling for fire and security � �� -____ _
�
applications. . t
SPECTR�ert
A � V A N C E
Features The MHR and MHW mini-horns operate at 12 and 24 volts and are
•12 and 24V operation ideal for hotel,motel or residential fire system applications,where
a smaller notification device is desired.The mini-horns offer high
•High and low volume settings and low volume settings,and temporal or non-temporal tones. The
•Temporal and non-temporal tones horns can be mounted to single gang back boxes for aesthetically
•Mounts to single gang back box sensitive applications. Synchronization is also provided when using
the MDL module.
•Compatible with MDL sync module
•Mechanically and electrically compatible with PA400 series The MHR and MHW mini-horns can operate between 32 and 120
Mini-Alert°°sounders degrees Fahrenheit from a regulated DC or full-wave rectified,
unfiltered power supply.They are listed to Underwriter's Laboratories
Standard UL 464 for fire protective signaling systems.
Agency Listings
U �
°� F M MEA ��
LISTED APPROVED approved �k
5401 I 3028007 MEA7 07 E i�5�1553:196
SpectrAlert�Advance Mini-Horn Specifications
Mini homs shall be a System Sensor Model MHR or MHW capable of operating at nominal 12 or 24VDC and shall mount to a single gang back box.Mini
horn shall be listed to Underwriter's Laboratories Standard UL464 for fire protective signaling systems.Mini-horns shall operate between 32 and 120 degrees
Fahrenheitfrom a regulated DC,orfull-wave rectified,unfiltered power supply.When used with the Syno-Circuit'"Module,l2-volt rated notification appliance
circuit outputs shall operate between nine and 175 volts;24 volt rated notification appliance circuit outputs shall operate between 17 and 33 volts.
Dimensions 4.6""L x 2.9"�N x.45""D
Weight 2.67 oz.
Operating Temperature Range 32°F to 120°F(0°C to 49°C)
Mounting Surface:single gang back box
Flush:4`x 4'"BBD deep back box(23/a""deep)
InputTerminals 12 to 18 AWG
Nominal Voltage Regulated 12DC/FWR or regulated 24DUFWR
Operating Voltage 8-33
Operating Voltage with MDL 9-33
UL Sound Output and Current Draw Data
.
Switch Setting Pattern Output Level 8-17.5 VDC 8-17.5 VFWR Nominal 12 VDC Nominal 12 VFWR 16-33 VDC 76-33 VFWR
1 Temporal High 68 67 71 70 78 76
2 Temporal Low 66 65 69 68 76 75
3 Nomtemporal High 72 71 75 74 80 79
4 Non temporal Low 70 69 73 72 78 77
�
8-17.5 Volts 16-33 Volts
Switch Position Sound Pattern Volume DC FWR DC FWR
1 Temporal High 12 10 17 15
2 Temporal Low 10 9 14 13
3 Non-temporal High 22 17 29 ZS
4 Non-temporal Low 17 13 �1 19
Ordering Information
�-
MHR Mini Horn,Red
MHW Minl Horn,White
�� SYSTEM ��or�svs�zmse�,��.
3825 Ohio Avenue•St.Charles,IL 60174 aroa�aspe<�a�uo�ss�u;��uornxngew�mo���,o�xe.u�s��sys�emsenso�.�omror
��� �����R� PhOIl2:80�-SENS�RZ•FdX:63�-3��-6495 cwrenrproduc[inforination,�mdudingthelaresrverslonofthlsda[azheet.
A05-0414-000•1/07•N1743