HomeMy WebLinkAboutB13-0330 Inspection Items for B13-0330 11:49 07/16/2015
Sec Item Id Descri tion A r Re Items Action Inheritable
* 10 BLDG-FOOTING Yes R 1 AP No
* 20 BLDG-Foundation/Steel Yes R 1 AP No
110 ELEC-Service Yes R 2 AP No
u.w * 190 ELEGFinal Yes R 2 AP No
* 90 BLDGFinal Yes R 3 AP No
* 542 PLAN-FINAL Yes R 4 AP No
Total Rows:6
Page 1
�;
TOWN OF VAIL'
Department of Community Development
75 South Frontage Road
Vail, CO 81657
Tel: 970 -479 -2128
www.vailgov.com
Development Review Coordinator
BUILDING PERMIT APPLICATION
(Separate applications are required for alarm & sprinkler)
Project Street Address: Project #: ?gf-5 k 3 " b 1 V ;L
�5:coa_ E7- LIAO Skejj DR #:
(Number) (Street) (Suite #) � - QQ ?
Sc°slf�o�1� Building Permit #: O
Building /Complex Name:
Contractor Information k—)/f-,-*,:) I Lot #: Block # Subdivision:
Business Name: s6flf i I (/_f )/Yes 1 V2 C
Business Address: t"[) X gr C/ q work Class: New ( ) Addition ( ) Alteration'
City �4 State Zip: Type of Building:
Contact Name: � /�`�.[� f [ �Q
Single-Family( )Duplex ( ) Multi-Family( )
Commercial W) Other( )
Contact Phone:
Contact E -Mail: SGj)/I/l�j , f1T�,e5]�G,CQ�NWork Type: Interior ( ) Exterior ( )Both
I hereby acknowledge that I have read this application, filled out
in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to
comply with the information and plot plan, to comply with all Town
ordinances and state laws, and to build this structure according to
the town's zoning and subdivision codes, design review ap-
proved, International Building and Residential Codes and other
ordinances of the Town applicable thereto.
X
Owner /Owner's Representative Signature (Required)
Applicant Information
Applicant Name:GL�
Applicant Phone: 7U — 3 -16 ,76
Applicant E- Mail:cj , ei I07 014Y1e5 I// JJIGj
Project Information �/�
Owner Name: AM e�' l CCU v( l &W &-
Parcel #: J= I o I - 67-2 -,-')o cc —/
(For Parcel #, contact Eagle County Assessors Office at (970- 328 -8640 or visit
www.eaglecou nty. usipatie)
For Office Use Only: O
Fee Paid: Q CFO
Received From:
Cash Check #
CC: Visa / MC Last 4 CC # exp date:
Auth #
: (use additional sheet if necessary)
Date Received: im IE
C�[EOMCE
AUG 13 2013
1WN OF VAIL
2013 -Feb 01
Valuation of
Work Included Plans Included Work
Electrical !jYes ( )No (
)Yes' ( )No rI
Mechanical 00Yes ( )No (
)Yes ( )No
Plumbing (,)Yes ( )No (
)Yes ( )No_ r
Building (f OYes ( )No (
)Yes ( )No�
Value of all work being performed:
$ 1
(value based on IBC Section 109.3 & IRC Section 108.3) 7 I
Electrical Square Footage
Detailed Scope and Location of Work:
c.o se etc, J""
Q i2C/b
U J %lock
c�� l! S vt
f s fu
: (use additional sheet if necessary)
Date Received: im IE
C�[EOMCE
AUG 13 2013
1WN OF VAIL
2013 -Feb 01
NOTE: TH/S PERMIT MUST BE POSTED ON JOBS/TE AT ALL T/MES
,.
�o�ro���,..
Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657
p. 970.479.2139, f. 970.479.2452, inpsections 970.479.2149
COMBINATION BLDG PERMIT Permit #: 613-0330
Project #: PRJ13-0142
Job Address: 560 E LIONSHEAD CR VAIL Applied.....: 08/14/2013
Location......: EAGLE BASIN GONDOLA Issued. . . : 10/16/2013
Parcel No....: 210107220001
OWNER VAIL CORP 08/14/2013
390 INTERLOCKEN CRESCENT STE 1000
BROOMFIELD, CO
80021
APPLICANT STERLING HOMES INC 08/14/2013 Phone: 970-748-1700
SAM STERLING
PO BOX 3699
i VAIL
CO 81658
License: C000003404
CONTRACTOR STERLING HOMES INC 08/14/2013 Phone: 970-748-1700
SAM STERLING
PO BOX 3699
I VAIL
CO 81658
License: C000003404
Description:
ENCLOSE EXISTING PAD BELOW GONDOLA W/BLOCK WALL 8� STONE
VENEER TO MATCH EXISTING. INSTALL ELECTRICAL INFRASTRUCTURE.
Occupancy: Type Construction: Valuation: $79,200.00
...........................................................,..,......«.._.,..,..... FEE SUMMARY .._............,.....x.,.........�..........,,.........,,,.........,.«...,.......
Building Permit-----------> $853.75 Bldg Plan Check----------> $554.94 Use Tax Fee-----------------------> $1,384.00
Electrical Permit---------> $747.50 Elec Plan Check-----------> $485.88 Restuarant Plan Review--------> $0.00
Mechanical Permit------> $40.00 Mech Plan Check---------> $10.00 Additional Fees--------------------> $0.00
Plumbing Permit--------> $15.00 Plmb Plan Check---------> $3.75 Recreation Fee--------------------> $0.00
Investigation-----------------------> $0.00
Will Call------------------------------> $20.00
� TOTAL PERMIT FEES--------------> $4,114.82
Payments-------------------------------> $4,114.82
BALANCE DUE------------------------> a0.00
.................................................................x,.....,....,..,,...........,..................,,....................,..._....��.............,..,..,.:..�.............
DECLARATIONS
I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the town's zoning and subdivision codes, design review approved, International Building and Residential Codes and
other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149
OR AT OUR OFFICE FROM 8:00 AM -4:00 PM.
�
combination permit_012811
�
t
��f#'� �� 1'� 1
.....................................................................................................................................................................................
CONDITIONS OF APPROVAL TO BE MET PRIOR TO FINAL SIGN OFF
1
Permit#: 613-0330 Address: 560 E LIONSHEAD CR VAIL
Owner: VAIL CORP Location: EAGLE
BASIN GONDOLA
.....................................................................................�...,.,..,..,,.......,,.,.....,................,,.........,....,...,....................,.,......
!
combination permit_012811
i
Y
�
!U�1[� Or 1t71L ,
***.,*************..***«*«**«««**�.************«„*«««**««**«***«********�**«*************«.***********«****„««****************.******«*****«****.«****
REQUIRED INSPECTIONS AND STATUSES
�
Permit#: B13-0330 Address: 560 E LIONSHEAD CR VAIL
Owner: VAIL CORP Location: EAGLE
BASIN GONDOLA
«********************««*«*******�*«********«*.,******�*********�**�*,.*****«************�*******.,.***********************�*.*******�,.**************�***
Item: 00010 BLDG-FOOTING
Item: 00020 BLDG-Foundation/Steel
Item: 00110 ELEC-Service
Item: 00120 ELEC-Rough
Item: 00200 MECH-Rough
Item: 00220 PLMB-Rough/D.W.V.
Item: 00240 PLMB-Gas Piping
Item: 00310 MECH-Heating
Item: 00320 MECH-Exhaust Hoods
Item: 00340 MECH-Misc.
Item: 00030 BLDG-Framing
Item: 00050 BLDG-Insulation
Item: 00060 BLDG-Sheetrock Nail
Item: 00070 BLDG-Misc.
Item: 00190 ELEC-Final
Item: 00290 PLMB-Final
Item: 00390 MECH-Final
Item: 00090 BLDG-Final
Item: 00542 PLAN-FINAL
Item: 00420 Special Inspect-final rept
combination permit_012811
i
_= Department of Community Development
75 South Frontage Road
� Vail, CO 81657
TOWN OF VAIL � Tel: 970.479.2128
www.vailgov.com
Development Review Coordinator
TRANSMITTAL FORM
Use this form when submitting additional information for planning applications or building permits.
This form is also used for requesting a revision to building permits. A two hour minimum building review
fee of$110 will be charged uper+ reissuance��f the permit.
ApplicationlPermit#(s) information applies
to: Attention: ( ) R� isions
, Y /1 ��� (.��tesponse to Correction Letter
� � � (..J attached copy of correction letter
,��1 �_ � � r `� ( ) Deferred Submittal
`� ( ) Other
�
Project Street Address: '
5�'�-_.� ��; - r,-,cc>�S f-f-�=--�� �r ���-�C
(Numberj (Street) (Suite#)
Building/Complex Name:�t t�NS�-f��� �Z'�'''���--� Description of Transmittal/List of Changes, Items Attached:
1 t, z,
, (�'�V�S�`77 �' �/f-'� s?�'�-7 (���
Applicant Information ; �. `
= flG�l-�-�t�-5 � /.���� �r�c�- n�,c,�`T�e�e-�
(architect, contractor, owner/owner's rep) ,
p ` �^ a ' O�' �--a�tGt1 E'��,�' ��`-'���a f�
Contact Name: {�lG�(.-t� '�'�, t-���'' � �
Address: �� ��� 3�� r
City ��"� �— State: CC�. Zip: �( � ��
Contact Name: (use additional sheet if necessary)
q _. _
Contact Phone: 1 7�'"3�� ' �2�� Building Permits:
Revised ADDITIONAL Valuations (Labor&Materials)
Contact E-Mail: �c������51��1�^�G N b t'7�S (DO NOT include original valuation)
V,q-�L . c:b:'�1
I hereby acknowledge that I have read this application,filled out ; Building: $
in full the information required,completed an accurate plot plan,
and state that all the information as required is correct. I agree to ;Plumbing: $
comply with the information and plot plan,to comply with all Town -;
ordinances and state laws, and to build this structure according ectrical: $
' to the town' ning and subdivision e gn review ap-
proved,In rn ional B ' ing an i enti Codes and o er Mechanical: $
ordinan of �e T appli theret . /�� ' �
X Total: $ ,�%
Owne wner's Representative Signa ure(Required)
Date Received:
p [� C� C � � C
For Office Use Only: �°�
Fee Paid: �c,� �1 � ����
Received From:
Cash Check# TOWN OF VAIL
CC: Visa/MC Last 4 CC# exp,date:
Authorization#
Department of Community Development
� 75 South Frontage Road
TOWN OF VAtL � `' va�i, co s�ss7
Tel: 970.479.2128
www.vailgov.com
Development Review Coordinator
TRANSMITTAL FORM
Use this form when submitting additional information for planning applications or building permits.
This form is also used for requesting a revision to building permits. A two hour minimum building review
fee of$110 will be charged upon reissuance of the permit.
Application/Permit#(s) information applies
to: Attention: ( ) Revisions
'7 � (�-�Response to Correction Letter
� � �� � l�t i K� �`!� �`L� '' f� p attached copy of correction letter
�,,f) --� i � _(,) , i � ( ) Deferred Submittal
�� ► �'� ( ) Other
Project Street Address:
`' G� O ���5% C� r.>Jv S �}�� � ( f�C C C
(Number) (Street) (Suite#)
Building/Complex Name:�/°�S� G� ���� � Description of Transmittal/List of Changes, Items Attached:
Applicant_Information �1�� /°RO Z��`�''P�aV � 1, (�. S/r(�'
(architect, contractor, owner/owner's rep) s`�C � ���L����� �� �
Contact Name: �(C ��fl j—v � (� i RO t�► [� l �.J [�CL � `p�d� �C� q
Address: �5�� �����' 'Z'°� �
City (/�i L State:�c� Zip: �/6 S�c�,
ContaCt Name: (use additional sheet if necessary)
Contact Phone: ��0 �j`j o � a3� Building Permits:
Revised ADDITIONAL Valuations (Labor 8�Materials)
Contact E-Mail: R\c � � s��'u��`���5 vJN��DO NOT include original valuation)
� c c��ti,
I hereby acknowledge that I have read this application,filled out ; Building: $
in full the information required,completed an accurate plot plan,
and state that all the information as required is correct. I agree to Plumbing: $
comply with the information and plot plan,to comply with all Town '
ordinances and sta taws, and to build this structure according ', Electrical: $
to the town's zo ' and subdivisi n co s, design iew -
proved, Inter al Bui i g an R idential Co es and her Mechanical: $
ordinance To pplic thereto. �
X Total: $
Owner/Owner's Representative Signature(Require
Date Received:
� � � U V �
For Office Use Only: D
Fee Paid: ,���„ � q ��1�
Received From:
Cash Check#
CC: Visa/MC Last 4 CC# exp.date: TOWN OF VAIL
Authorization #
I
P
��E����������1��1�� ...---.v- _
��� ��y
Fire Protec�ion & Life Safety Svstem Evaluation
client:
American Tower Corparation
CO Don Clark
3 Pilgrim Road
Windham,NH 03087
Phone: 603.818.8229
I'roject:
Vail Resort Hub CO
ATC Outdoor DAS
Eagle Bahn Gondola
' SbQ East Lionshead Circle
Vail, Colorado $1657
Project#&2913001
October 9, 2013
ARVADA OF�ICE g�ER���p COLORADO 5PRINGS OFFICE
5420 WARD ROAD,SUITE 200 ���yyjyJ(f(jgy 10�7 NEW ALLEGIANCE DRiVE,SUITE 400
ARVADA,COLORADO 80002 QOlORA00 SPRINGS,COLORADO Sa921
363.422.]40D 719.533.1112
♦
�
Vail�agle Bahn Gondola—ATC Outdoor DAS 1
Rondinelli Life Safety a BCER Group has been commissioned by American Tower as requested
by the Tawn of Vail Fire and Ernergency Services to evaluate the impact of the ATC Outdoor
DAS on the existing fire protection and life systems af the Vail Eagle$asin Gondola as
connected to the Arrabelle. Below is a description ofthe new installatian on the existing systems
and our recommendation.
' BUILDING DESCRIPTION
The project is the installation of electronic equipment far the purposes of providing a means far cellular
' carriers to provide their customers ceiluIar sen�ice in and around the Vail Mountain area.This in know as
' a DAS (Distributed Antenna System}.The signal distribution is via fiber to remote antenna locations off-
site.The space will be cnmpromised of open floor space under the Eagie Bahn Gondola Deck(Lift 19).
The new electronic equipment will be installed,operated and maintained as presented in the July 29,2013
Permit Drawings.This installatian is nat occupied except for maintenance of the equipment.
The Eagte Bahn Gondola is eonnected to the Arrabelie Complex and consists of equipment for the
operation of the Gondoia as well as providing access and egress from the Arrabelle Complex.The
Gandoia was provided with additional fire protection and egress improvements when the Arrabelle
Complex was constructed.These systems included sprinkler pratection,fia-e alarm notification and special
extinguishment systerns for electrical equipment raoms.
APPLICABLE CODES AND STANDARDS
• 2012 International Bnilding Code(IBC)
• 2Q 12 International Fire Code(IFC)
• Town of Vail Amendments and Policies
OCCUPANCY CLASSIFICATION
The existing oecupancy is nat changed ar impacted with the addition of this ec�uipment.
EGRESS AND OCCUPANT LOADS
Egress is curre�itty provided at grade level via the Gondola from Arrabelle.'The exits are the spirat stair
connecting the grade level to the upper Gondola level and a set of doars that exits directly to tl�e exteriar.
The addition of the equi��ment will nat impact the existing egress or e�ress paths.However,with the
addition of the screening and gates peopie exitin�the grade level will be required to exit th ough the
access gate.The�ate swin�s in the direction of egress.Recommend ensuring that the�ate remains not
locked from the inside and permits passa e with no special knowled�e or procedure.
This gate must also remain accessible from the outside.The gate can be locked but should be provided
with a Tawn af Vail Fire Department Knox Box nlonnted at a f�re department approved location with
appropriate signage.
C:\USERS�SRONDINELIi\DESKtOP�VRDC HUB CO.DDC
ARVADA OFPICF ������UP COLORApO SPRINGS OFFICE
5420 WAR6 ROAD,SUI7E 200 p�y,rL�/�yyj�'j�jgy 10�7 NEW ALLEGIANCE DRIVE,SUITE AW
G
ARYADA,COIORADO 80002 COtORA60 SPRINGS,GOL6RAD0 8(}921
303.422.74W 719.533.1112
Vail Eagle Bahn Gondola—ATC Outdoor DAS 2
FTRE RATED SEPARATIONS
There is no special fire rated separation required for the installatian of this equipment.The permit plans
indicate that penetrations from the exterior through the wall will be sealed with UL listed fire caulking per
property owner appraval. Althougli not required by code,this recommendation is supported by our
review.
CONSTRUCTION TYPE A.ND AREA INCREASES
The addition of this equipment does not impact or change the construction type ar alIowable area of the
Gondoia.
FIRE PROTECTION SYSTEMS
' This building is provided with a code camplying NFPA 13 �re sprinkler sy�stem throughout tl3e grade
: level Gondola area including the exterior open air space the new equipment will be installed. Enclosed
areas i►i the Gondola also have alternate extinguishm�nt systems.This equipment will not irnpact the
current Iire protecfion system design and capabilities ofthe system.The equipment will be adequately
protected by the existing fire protection syste�n in the Gondola.
FIRE DETECTIUN AND ALARM SYSTEMS
The area is currently provide with a fire alarm systenn including manual fire pull station in the Gondnla
area near the exit and occupant notification throughout the gondola.Tliis equipment wilJ not impact the
current fire protectian system desi�n and capabilities af the system.
EMERGENCY AND STANDBY POWER SYSTEM
There is an existing generator system in the enclosed Gondola.The generator is fueled by nalural gas with
an emergency shut off located approximately 10 feet from exit doars at grade under the canopy of the
Gondola . This emergency shut off is currently marked with sigiage and is accessible from the exterior.
"I'he July 29,2013 permit drawings indicate an additional generator(natural gas)will be installed.
Accarding to American Tower on October S,2013 that installation will not oceur until a later date.The
installation af the additional generator wilI not impact the fire protection or egress from the Gondola.
Signage shauld be included indicating lacation of the emergency gas shut off with that ir►stallation.
FiRE SERVICE FEATURES
Fire DepartmehtAccess
Fire department access is currently provided to che Uandola,specificully tlie grade level.The installation
of this equipment including the screen wall and�ates will not be impacted by the installation of this
C:\USERS�SRONQINELLI\DESKTOP\VRDC HUB CO.DOC
ARVADA QFFIGE B� �. ��Q�� COLORApO SPRINGS OFPICE
5420 WAKD ROAD,SUITE 200 ���yy�f� 1fl807 NEW ALLEGIANCE DRIVE,SU17E 400
ARVADA,COLORADO 80002 COtORADO SPRINGS,COLORADO 86921
303.422.74D4 719.533.1112
.
i :
Vail Eagle Balu1 Gondola—ATC Outdoor DAS 3
equipment. Signage needs to be provided at the screen walUaccess gate indicating t�iat the `Natural Gas
Emer�ency Shut is Located in the Enclosed Area".
Key Boxes
Key box should be added at the screen walUaccess gate to provide access ta the covered Gondola area.
The location of the key box is to approved by the Fire Department.
RECOMMENDATION
Rondinelli Life Safefy a BCER Group has reviewed the July 29,2p13 Permit Drawings for installation of
the DAS aiid associated equipment. This installation as described in the Permit Drawings do not impact
the existing fire protection and life safcty systems."I'his includes no impact on the access to or egress
from the�,agle Bahn Gondola(Lift 19).
If there are any questions pertaining to this report please call me at 3Q3.422.7400.
h. „�
Prepared by; /���F C Q(�a�
Rondi li Life Safety '� �9 �
. ;�'� 90
� �� ��J �
;��F
� ..�-r,�..,�,,,,,
Stephe Rondineili,AIA � � � ' �' " $ r'
Princip Fire�rotection anc�Life Safety �`° '���� �
�j
V
C����' `���� �D 4 2e�
�p AR� � � 13
��� - .... �ac`r��t
�'ra�U+�,r�t� ��.t�� r��-~
C:\USERS\5RONDINELU\DE5K70P\VRDC NUB CO.DOC
ARYAOA OFFIGE �������� COLQRADO$PRINGS OFF�CE
542Q WARD ROAD,SUITE 200 P�t,d�t�/�qy SO807 NEW ALLEGIANCE DREVE,SUITE 400
ARVADA,COLORADO 80002 P COLORADO 5PRlNGS,COLORADO 80921
303•4Z7.�406 714.533.1112
0
jo _
01 -06 -2014 Inspection Request Reporting Page 7
4.12 gm Vail, CO - City O{
Requested Inspect Date: Tuesdayy Januaryry 07 2014
Site Address: 560 E LIbNSHEAL Cat VAIL
EAGLE BASIN GONDOLA
A /P /D Information
Activity: B13 -0330 Type: COMBO Sub Type: ACOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area:
Owner: VAIL CORP
Applicant: STERLING HOMES INC Phone: 970 - 748 -1700
Contractor: STERLING HOMES INC Phone: 970 - 748 -1700
Description: ENCLOSE EXISTING PAD BELOW GONDOLA W/ BLOCK WALL & STONE VENEER TO MATCH
EXISTING. INSTALL ELECTRICAL INFRASTRUCTURE.
Comment: PERMIT SCANNED - ROUTED TO PLAN RACK G1, JOE B., FIRE - SBELLM
Comment: CR2 transmittal with Fire info for MM. scanned to laserfiche and routed to Fire and C -4 - CGODFREY
Comment: paCGODFmEY CR1 routed to C -4
Requested Inspection(s
Item: 190 ELEC -Final Requested Time: 08:00 AM
Requestor: STERLING HOMES INC Phone: 970- 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Item: 290 PLMB -Final Requested Time: 08:30 AM
Requestor: STERLING HOMES INC Phone: 970 - 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Item: 390 MECH -Final Requested Time: 09:00 AM
Requestor: STERLING HOMES INC Phone: 970 - 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Item: 420 Special Inspect-final rept Requested Time: 10:30 AM
Requestor: STERLING HOMES INC Phone: 970 - 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Inspection History
Item: 10 BLDG - FOOTING —Approved '*
11/05/13 Inspector: sgremmer Action: AP APPROVED
Comment:
Item: 20 BLDG - Foundation /Steel ** Approved **
11/05/13 Inspector: sgremmer Action: AP APPROVED
Comment: Gas pipe went thorugh the foundation wall this was OK per Jake Farber of excel energy his number
is 970- 390 -5627
REPT131
Run Id: 14787
542 PLAN -FINAL
Requested Time:
08:00 AM
STERLING HOMES INC
Phone:
970-748-1700
904 -6369
A Cigned
RUT R
Entered By:
JMONDRAGON K
Exp:
iiTime
Item:
90 BLDG -Final
Requested Time:
09:30 AM
Requestor:
STERLING HOMES INC
Phone:
970 - 748 -1700
Comments:
904 -6369
Assigned To:
SGREMMER
Entered By:
JMONDRAGON K
Action:
Time Exp:
Item: 190 ELEC -Final Requested Time: 08:00 AM
Requestor: STERLING HOMES INC Phone: 970- 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Item: 290 PLMB -Final Requested Time: 08:30 AM
Requestor: STERLING HOMES INC Phone: 970 - 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Item: 390 MECH -Final Requested Time: 09:00 AM
Requestor: STERLING HOMES INC Phone: 970 - 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Item: 420 Special Inspect-final rept Requested Time: 10:30 AM
Requestor: STERLING HOMES INC Phone: 970 - 748 -1700
Comments: 904 -6369
Assigned To: SGREMMER Entered By: JMONDRAGON K
Action: Time Exp:
Inspection History
Item: 10 BLDG - FOOTING —Approved '*
11/05/13 Inspector: sgremmer Action: AP APPROVED
Comment:
Item: 20 BLDG - Foundation /Steel ** Approved **
11/05/13 Inspector: sgremmer Action: AP APPROVED
Comment: Gas pipe went thorugh the foundation wall this was OK per Jake Farber of excel energy his number
is 970- 390 -5627
REPT131
Run Id: 14787
05- 02.2014 Inspection Request Reporting Page 9
4:03 gm Vail, CO- Ci_W Of -- -
Requested Inspect Date: Monday, Mayy 05 2014
Site Address: 560 E LIONSHEAD CR VAIL
EAGLE BASIN GONDOLA
A /P /D Information
Activity: B13 -0330 Type: COMBO Sub Type: ACOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area:
Owner: VAIL CORP
Contractor: STERLING HOMES INC Phone: 970 - 748 -1700
Description: ENCLOSE EXISTING PAD BELOW GONDOLA W/ BLOCK WALL & STONE VENEER TO MATCH
EXISTING. INSTALL ELECTRICAL INFRASTRUCTURE.
Requested Inspection(s)
Item: 90 BLDG -Final
Reque ntsr � —� _ I
Comments: Wn&o
Assigned To:
Action: Time Exp:
Comment: ff
Comment: OVAL RE QUIRED
Inspection History
Requested Time: 11:00 AM
Phone:
Entered By: JMONDRAGON K
Item:
10 BLDG - FOOTING ** Approved **
11/05/13
Inspector: sgremmer Action: AP APPROVED
Comment:
Item:
20 BLDG - Foundation /Steel ** Approved **
11/05/13
Comment:
Inspector: sgremmer Action: AP APPROVED
Gas pipe wenfthorugh the foundation wall this was OK per Jake Farber of excel energy his number
is 970 - 390 -5627
Item:
110 ELEC - Service Approved **
11/21/13
Inspector: sgremmer Action: NR NOT READY FOR INSPECTION
Comment:
11/25/13
Inspector: sgremmer Action: AP APPROVED
Comment:
this service is a temp for communication
Item:
190 ELEC -Final
** Approved **
01/08/14
Comment:
Inspector: sgremmer Action: DN DENIED
Typed panel schedule
01/20/14
Inspector: JRM Action: AP APPROVED
Comment:
Item:
90 BLDG -Final
y 01/08/14
Comment:
Inspector: sgremmer Action: DN DENIED
Planning to ff
SM
01/20/14
Inspector: Action: CR CORRECTION REQUIRED
Comment:
PLANNING APPROVAL REQUIRED
Item:
542 PLAN -FINAL
01/08/14
Inspector: JB Action: DN DENIED
Comment:
Stone veneer does not match the stone foundation of the Eagle Bahn gondola base terminal (stone
is too light, mortar too dark and misapplied).
Also, the applicant was instructed to provide a copy of Vail Resorts application to mitigate the erosion
occurring at the southeast portion of the site prior to requesting a Final Planning Inspection.
REPT131 Run Id: 14769