HomeMy WebLinkAboutA13-0050 Scope of Work c� „ �
wc �� ���, F� � ��
� , ��
Commercial $pecialists of Western Colorado, LLC
August 14, 2013
Vail Fire Department
42 West Meadow Drive
Vail, CO 81657
Attn: Mike Vaughan, Fire Marshal
Pjct : Lions Square Lodge Unit 753
Re : Scope of Work for Fire Alarm System
Dear Mike,
The following is a scope of work to be perFormed for the remodel at Lions Square Lodge
Square Lodge Unit 753. The scope of work will be to bring the remodeled area up to NFPA
standards adopted by Vail Fire Department and Installation standards. We will be pulling new
wire throughout the unit. New smoke detectors will be installed in each bedroom, the entry
the living room area, top of stairs and the upper bedroom. The entry device, living room
device and top of stairs device will be multi-criteria FCO-851 devices, which incorporate the
CO detector. Each device will be mounted on a B200S addressable sounder base. This
base provides the temporal three notification for both the local alarm and the general alarm
function and temporal four for the CO alarm activation. We will be installing electrical boxes
at each of these locations, center of the room. These devices will be added to the current
main fire alarm control system, a Notifier NFS2-3030 control panel located in the closet
behind the front desk.
Once work has been completed and tested, CSWC will contact Vail Fire to schedule a final
fire alarm test of the remodeled area.
If there are any questions or concerns about the above information, please feel free to contact
me at any time.
Sincerely,
Commercial Specialists of Western Colorado, LLC
7'�fn ?A1 av�oC
Tim Ward
General Manager
210 Marmot Lane Unit 5B/PO Box 3913 Eagle,Colorado 81631