HomeMy WebLinkAboutB13-0292 PLANS APPROVED
RE
C
E
I
V
E
D
Da
t
e
:
By
:
B1
3
-
0
2
9
2
08
/
0
9
/
2
0
1
3
D.
RH
O
A
D
E
S
1425 Buffehr Creek
Load Calculation
General Lighting and Receptical Load:
4120 sqft x 3va = 12360va 220.12
1500 va x 2 =3000va 220.52a
1500 va x 1 =1500va 200.52b
Total connected load:16,860va
3000va @ 100%3000va 220.42
13,860va @ 35%4851va
Total 7,851va
Range/Oven Load:
7200va x 80%5740va 220.55 clm b
1800va x 80%1440va 220.55 clm a
Total 7200va
Dryer Load:
5000va 5000va 200.54
Fixed Appliance Load:units total
Refrigerator/wine 1.8kva 2 3.6kva
Micro 1.8kva 1 1.8kva
Disposal 804va 1 804va
Dishwasher 1.8kva 1 1.8kva
Washer 4.4kva 1 4.4kva
Hood 1.8kva 1 1.8kva
Total 14,204va
x 75%220.53
10,653va
Heating/Cooling Load:units total
Furnace 0.2 1 200va
A/C 0 0 0
Heat Tape 0 0 0
Total 200va
Largest Motor 1200va x 25%300va 220.5
Totals:
Lighting/Receptacles 7,851va
Range/Oven 7200va
Dryer 5000va
Fixed Appliances 10,653va
Heating 200va
Motor Load 300va
Total 31,204va
amps 208v 150.01a
amps 240v 130.01a
Existing Service Size 200amp