HomeMy WebLinkAboutA13-0052 cut sheets .,�
Superior Alarm and Electronics , Inc . � o rk C) rd e r
P . O . Box 4910 --- —
�dwards , CO 81632 Date W . O . No .
' � ° 608
r
Name / Address Sf� ip To
John I Iayward � 641 �reen Mountain Dr
Eagle, CO
' '' 81651
P . O . No . Project
HAY WA
Item Description Ordered U/M
Mf1T-�1 Interlogix Micra KEY-FOB 1
GC-60-S l 1 -01 -95 WIREL� SS INFRARED 1VIOTION SENSOR 1
LAI3 - S�1 Labor: �larm System ' 1
TRIP Trip Charge
• Additional items ordered per Mr. Hayward
Internal Notes : ��
T/S panel does not send signals
Install Living rm smolce
Change Livng Room sinoke battery
GZange MBR sinoke battery
Test all devices / n -�,
Add RF motion in great room �� '
Program Micro Key Fob �• , '
Sales Tax - Eagle County & CO State ' �►
. . � :���� � . � . � �� . � . . . �
� o� r/�j /`v' 1�//,���� M � � . . � . �. .
.. � . . l�J " . . . . . . . � . .
, . . ' � in �.,,� . ��
a
. .� � . .. ! - � � _ . . . . .. . . . . . .. . . . . � ' . . . . . . . ..
� �• � �
Su erior Alar�n and E:� lectron � c � Inc
p
r P . O . Box 4910 Edwards CO 81632 Eagle Cnty (970) 926-8788 F'��x (970) 926-8790 admin@superioralarmco . com
SWO Number 495 � Date 6 . � 8 . � 3 Time � � Technician D DICT11tl'QV _ _ _ _ _ _ _ _�
- Sx Ca l l Bac k- 1 s t tec h � �
Acct Name : Heyward John ID: C �
__ _ .
_= Service Requested By OWngr
Customers . Premise : 641 Green Mountain Drive �
Sup�rior Alarm and Electronics , Inc . 1No rk O rd e r
. P . O . Box 4910
Edwards , CO 81632 Date W. O . No ,
6/ 19/2013 495
Name / Address Ship To
John Hayward 641 C��reen Mountain Dr
Eagle, CO
81651
P . O . No . Project
HAY W A
Item Description Ordered U/M
GE-80-265 -4 INTERLOGIX CONCORD 4 ALARM PANEL with built in wireless 1
capability
GE-60-746-01 INTERLOGIX CONCORD PAN�L STANDARD LCD K.EYPAD 1
AS -XF1650 ALARM CONTROL PANEL POWER SUPPLY i
YUA-NP712 ALARM CONTROL PANEL B�1LCK-UP BATTERY 1 ea
GE-RF- 151001 INTERLOGIX 3 /4' RECESSED VVIRELESS DOOR COr1TACT 9
GE-60- 511 -01 -95 INTERLOGIX WIRELESS INFRARED MOTION SEN��OR 2
GE-60-744-95R INTERLOGIX WIRELESS MOISTURE SENSOR 1
GE-60-504- 10-319 . 5 INTERLOGIX WIRELESS FREEZE SENSOR 2
GE-TX-6010-01 - 1 INTERLOGIX WIRELESS SMOKE DETECTOR 2
GE-600-6520-95 INTEROGIX MONITORED WIRELESS CARBON MONOXIDE 2
DETECTOR ----..�„��
MAT-A INTERLOGIX MICRO KEY-FOB ' �'`•-� 1 ~`
SYS -MHW MINI HORN IN WHITE 2
Sparrow2 SPARROW 2 VOIP ALARM COMMUNICATION MODULE I
LAB - SA Labor : Alarm System 13
LEV-41108-RWS LEVITON CATS NETWORK WALL-JACK IN WHITE 4
SIE-M150 SIEMENS 66 PUNCH BLOCK 1
Page 1
Superior Alarm and Electronics , Inc . V110 rk C� rd e r
P . O . Box 4910 —
� Edwards , CO 81632 Date W. O . No .
6/ 19/2013 495
Name / Address Shi �� To
John Hayward 641 Green Mountain Dr
Eagle, CO
81651
� P . O . No . Project
HAYWA
Item Description Ordered U/M
ICC-H2-MB89DOWH 66 PUNCH BLOCK BRACKET 2
LAB - SLV Labor: Low Voltage System to include : 7
1 . Hard-wire 4 network locations - study, master bedroom 'I'V location,
Iower level south bedroom and the kitchen island
2 . Add a punch block and clean the home-run CatS wiring
3 . Install owner supplied WiFi access point on the top of th�� kitchen
island
4. Install owner supplied WiFi router in the mechanical roo�m at the
home-run
Sales Tax - Eagle County & CO State
Page 2
�� � � .. ra :� ���e �.. � � ��� ►-i ��c� �� rh� Te �nn � �� � ,, :
iurcr,�^.a�aa..,..ciz:.—.-anza�.�'.ni.c::u:+:�r.^tr..�:x•:.r..r_�,....�..:ruuu:ui_�c�u.� ... '.���_ ��
.r , . _ _ _ _�� �..
- � . �. .. . � �� � Y
C �.isiomf� r : �_ _m Mailing P,dd �as � : ,� � �_� � � _.� � +� ��.
vwner will PU �� ic� at ofiice Yes No �
m - � _
w
.. �t:r,".m.v.o-r.n.-�-ra::.� •se�sras]'.cuv'.�:Srm^_t:ar_exnn�:s�r.nrnux:asi:uc•�x�cusc`V.• ^ •.,.•-. •.. -„^�,-. -^.-•• y.�,i,�,+.,;y�rT.'i�., '••'-•-^ss.�.:se.YS+rSiC:tT..2..]cat'n.^'.—..c ^L�.^"••-••••••.•__••'•c�,a�•.- •-�"�,1'�-�a . � /r3."+8' :"SaII..�nr.� �•:�r.tnz.�r_ss:.:3C.--�.:e�cle..-�^_»�e::(_�:e:m:: s.. . u(vvs:.;:�:�.+.-
�.._ .
, �. _ ,.`._ �_.
�
i �
� �c A ,� t � n � �ay � f � �ry ° 1 ype : ...____-�--�- , r � q�.- �' �t��
� �' � , .
.,: .�r.:�r.. . . x ... �...�. .:.c_�.r.l._���s.�r��n:�� �.aaa ���.��___�....__._..._.__�..�.�...��....��«a�..._,.___�� � ,
� OC� tI011 :
(�valuate Proqrarnminc� Access :
� �� c� �.� �: ot� c9 � yart� r� ts �ve �•ar,� e : Sec :
'/YJ.C:'1 Y�.�Y'S:`S::GL:'SO`..LZIt'3:.ELS:G'�::d2",S 1C4ii1:3.(`11S:i1T.'1'�w�T2ilL.L�"T_11LC.`IiA1LL^LO
Fire : JEarisdiction :
I_.TS : .--___�__..�� _ ------ __
Qther. �. ist :
___._.__.
�r � -- .� � . .;._.�. Q ,��-�r �-- :� �-- .��,�
I�3 � st Pan � l L. oc:ation : _� ._. _____ �._ - - _____�`�..M. ''�� ������._____._._________�..._
1 ' I , c� �� e I_ in � L.ocatian : -<:.��►-�.p� *� c��:.��-''�Z_ �.��.cV , �
\ A '� .� ..'J
�� ��`� '
..r_._._ �_�.._ �_r�=. ,...._� . . ....r..��_..���.��.� �r � �� _..._�
,��C� !' ower I._ ocatiori : g ` .� ' /� �:��Z��� `�- �, m � �� �..._.
_ _�________...._____ __.._._. ._��_.__.._____�_. _ -- .--- ��_" ��-�_---_______
P -Iarcl�n��ii�P � iren (_ocatic� ns :
p�Vo �: � �� �.ocli �� il � t�r Is � tae � :
(Test exisling local smolces(tandem sound) V ^
f_vc� i « � t�: Fisi � in � wire for: {<LS : � �p � �.�,a� � 9 , �� {�/y, ,.,
���� � ^^ ������ ��. r'�� � --�'t_.� � �J�.�J'YJ� '� '�'�/L,��-�' �,A � V `� �t � 'T"v�..� i �
�2 � CU : �� . �'°� �, ; n t _ lc"�, �- t�
'�' "i C' �'.,.
O/� H /ST 6< na��c :
� ireiis : ,--. �� � � , .
,
_ ,._..._ „�,� � � e.�'� ��l �� � �'� ���.._
P". �,�1 ^� � X��p6' Uv� , 6... {L.Y I7+ N64 �� � i.� 1 � , VW�� �b'""16... �_`'�1�v � i.� t. Ye e • •`"' . .
_____�1�'?!�`1!1 -�_ �!�"`��____.._. __ —
��, �_. �... �: �f Ga s �., � �� �;;, �a ��' �$ �� �� �� � C° �1 � ���,/ I �; �', � � �.) ��� �� �" �., �� � . -, � 5�� tfC$�/ � ..�� S� m� �. A �AB� �
t_c�r,ation C P RF F� W I_oc � tic� n E P I�� F t -I1/\I L ;�
_ .,__ __..w___._________.__._._ _ ---_. ` �.____.�
.______ �__�.._. _ __ .
,� - - '�'� � _��.,__._.
f�oc� r � � '�1 � � l.p'' � molt� Iv� ��)'+�-. t/" i,,�^°
______-�-�-�-_ __ _....�_:..�_...�._d � __ ..�
Doo�� „ ��-�-__—_--___ ---�- �,- � Smolce �_-��_� .�._.,� �--�`-� �
.._.�_.�.._._�.� . _a� __ � __..._...�_ r-���v, '� `°'�--�°1..__ `�
�,� �) U �,.�.,. ... �.` .._�...�.m.,... — - � .. � ...v_. ( la..t6,.a.��.... a � � �...... .... ...,.. ..a....,..... _ ....
_.. _. ._���.�=��_._.....^�_..__..:���`'�� _ __ ._____ __ Sn�i �l�e ��` �'� � �i � _ v-.
q. A� _._ �...._�__ ��+..._.. _...�._.. �.._�. �
_(=) oor �i/ 1 �/1 - T��Y-.Y1� __�-____ �.ie�'_ ��= _._..__ Smolce � �� �:�� - - _� .�t� � l�
. . , — , ... __ — _ r..___
�'71T10�(E.-' "� �'__ �.��'��')"",� _..___ �_ 'j.,,,•��
[.) l')C7C __� V I �,/{ ��. C'�'fl'q/Y�_... � _ �~ � ` J" �� .�
, .__
f) ooi , �._��,� _ �.�� ���� _____ -- '�°' �f .� .Smolte � �:1� � ., _ _ _._.�!'`
a ..._�. ...�e..w____�� `"
Uoo � �J�°�.,_ _ . _.._.�.- , �� � � � vl,/` ..... Smoke � � jl�a: - ,� � _ .._. _ __ ._..
._..._. . ._ .�. _ _. ._._______ �. _ _ �r°..� _�__._ �' _ �--
�_� �� �> �:_.�=�— ��,�� .� ...� _..�..� _�' s �noi<e � �
- - --.-... �a��'�P__���..���-.�`� � __ L-~°-
, ------ --
(�oor __��� � ` "v'� -- - � `°'� _Smolce �. :. ( � � �' � -�.,i"
- -- -.�._._ _ ;--___..- _ _ .._ ..._�
f:) oos.__. . . _ _ Smo {<e '� _� �... �_.� "l ___..�. _ � ' -_-�'''�_ ___.
- � _ . _ _. ,__�„ =11i�� -- _
A/iotior� _..��i �Y 1, .1/i �.c��"Y� _ .,_..�''� �� _.�.
flllotic� r� � '� : ` � �¢ ��. .�.. �� _ I-leat ._..._�._........._.�� - -- - �� . __
l� �ti �� r� �� t-I � at
__ -----__..., . __._ . — _ ____ _
_,_�. _..__.
_.�,. .�. ___��. . �._... _..._._ ..�..n .. .�_�..z_. �..�.._._.�
s , ._._.._..�._ -
KC � .C�'"l � ta'i '���' (� S . � --- __ -- - _ _._______
___ ���-Q ", �i _ ..�' E>ct . Horn/Strc� l � e
I<C; Sy �.,��1�Q,j, 1/� ' �. r �,,�' 'i.�°° � I TS —.__..Y_.___---- �_ .._.. _ ___ ._
�, ___.__�� �--�- _.�.. �_.. .- - -- --__.�..�._.___�_ _ -�--- - --
I <G ,7 LTS
�.__�_ _._._ _---.�. _._._.,,— - -- - -� �._�_ ..Y..__._.
_.� .,__.�.�___.�...- - - ...._--- - - - - - _._._._.__. .._._.._..._._ _�._....�___ ._
. , .
CO � .. �. _ �. . , .. .. .
._._ ._._. .r `�` '��, .......... _.._,.�
--- - - -�-----..-- - --- - ----- _.--�-___.... -
���--------�-�'��=r� $/ �__._ Gas _� ..r._.. . _ __. ___ _�___
CC� --- -� { 1 -- __ �.�" � Water I�r�._._�.�� __ � _ �� ._.
�?���.�.�_______..�.
ICnox � _ — _____
y Siren � �,,;�t�' . �. �� ��....... � ,� -._ ��, _"
--- _ _____.� _ e___._... ..s_.... _ �_. ._.�,.
C) N�.h:,��IPJ F' �t19�a1f:� IF C�' O � � IF�3t� � 1 ! .^�_� W Siren � .1 �c..�.'����`�lr/ � � �6 � �` � .� ......_ _ � -_�_ ^� _.-_.
��� �� �:� ��� � ��-� � � � r° �:� I � �� � �i � � � �:-1 � ��� � � �Ji �: i�� �� � �i� �� �D �� �=� �� �� t�. � � � � o � s� � c� ���� � �� ��� �� � �
.
.. .,
�� ,- � ��"'S ��
Superior Alarm & Electrar� ics
Residential T'est and Inspectio �t Checklist
S st� m � Check Test Performed Account #
Fire Clean Smokes
Test smokes using smoke, test sensitivity as required- note a�E� Age :
� Make/Model of Smokes
Send & Verify Fire Signal-All Zones
Confirm Flow Switch & Tampers Connection & Panel Functnon Tag Date : Company ;
Test all heats-with heat if possible, dilce the fixed heats.
Check Smoke power while Tandem Sounding Min 11 .5 Volts
Modify polarity reversal as required
Change 9V Batteries & Test all local smokes
Check Power Supervision-4 wire fire circuits
Security Open all doors/verify each zone at panel
Adjust Switches if needed �
Walk Test Motions- check stay mode motion bypass
Clean Cobwebs around motions
Arm System and Trip All Zones �
Verify Signal-All Zones
Test Panic Function-Fire/Police/Medical
Change Concord 4 Dialer abort to 15 seconds
Low Temp Test by cooling device
Verify Signal-all Zones
Gas Test with butane lighter (not lit) Age :
Verify Signal-all Zones
Water Bug Test with Moisture
Verify Signal-all Zones
CO Push Test button Do not use gas or canned air Age :
Check for CO coveragein house
Panel Remove Lock & Replace with Phillips Head Screws (6 x 1/2 ��crew)
Load Test Panel Battery Change if 3+ yrs Date : Test:
Load Test UPS Battery Phone System or Watercop Date :
Add RJ31 Jack
Set clock & verify daily test time Time:
Turn off Daylight Savings Time featu�e
Failure to communicate - make sure i�' s not audible
Change dialer- 949- 1860 (26-) or 949-9705 (147-)
Check for Phone Line Seizure
Check Transformer screwed in to outlet if possible - change ta Phillips head screw
�.:
Instal zone list in panel .
Ensure correct panel line telco is listed
FBI XL-4 : Turn off dialtone detector
FBI XL2 , XL3 ,XL31 , & XL4-define all key ad anics
FBI X12, XL3, XL 31 -Add 2 Pauses
Misc . Change Installer Code to company st�ndard
Instal Window & Panet Decals if needed (remove old type)
Log Only NTT for 24 Hours- VISTA- 1 WEEK
Note exact location of all of all devices on spreadsheet.
Batteries 3.6 V Lithiums 4-5 yrs - change all at once
Lithiums on fire devices - change annually
ALL Alkaline (AA, AAA & 9 V) - change annually
I certify the above is true & correct on / / Technician :
. _ -- -- - - - - - - -
Acct #: X ID: X Panel On Line : Panel Type �h ❑
--------� �_--� �_- - ------- -- . .I-- ---j
- -- -- - - - - - - }
Premise : Deactivation Date : Last Owner:
�-- ------ - - -�(�� 1 �--- ------- _ .__�-- --_.l
Last TI : 1 Tech : # Tech � Total Nrs : I
Subdivision : r- ----- -- - -� -----1 I _l �__ 1 L----`. __ �
City : ' � ^ "- --- Target month � Mandatory Res Fire T I ❑
� ---------------..-_ -------� T I Notes : --------- --- -- ----- - .. - ---- - -------- -- ---- . -- ___
State : Zip Code:
--- ------ �— �
._. . . . .,,_,. - -- -- -- ----- ---- --- ----
._..- - .
Dealer 717 Acct Type : ;
_ ____ __ _ _ _ Spreadsheet ❑ Field Sh�eet � Zone List ❑ Knox Box ❑ Print Box � _ . �
- r --- - - -
CS Receiver Telc 0( ) - 0 Panel Batt Replaced : Installer Code :
__ _----------------------� �--- —� I -- . -- - - _ . I
- - --- --- --- __ __ _ . _ ..
--- - -
Panel Telco 1 : Police Dept: r _ _ --_ _- -- - - _) f - - -- - - _ -. . t _._� _��
_ _ . . _ . . - -- --- p ----- --- - ---- - - _ _
- - -
Panel Telco 2 : _ � Fire De t: � � ( I
-- - _ _...
_ _--- - - ---- -- _ _ . _.. _ _ . __ _ _-
_ .
Pane! Locatian : Patrol Service :
__ __..__ _ __ __ _ --- - - ----I � --- --- - --- - -- -- - -� I
D�.� scription Alarm Verify Response
Description Alarm Restore Response Ke ,y�pad fire : NO FD
-------- 1�-- --- --�
Timer Test : Keyp,ad Police NO pp
- ---
-..- ------- -
--- --- l
Low Battery: Rp Keypacl Medical YES PD
- ----- --� [:=�=--1 � -----_I
Zone Description Alarm Restore Verify �4udible Response by : Notes
_
--------- ---- --- --------- �
- --
:.
_ .- - I �---� r Yes� �Ye' I � -- �
� ... ..._ -- --- -- - --- --� (�J �--� � Yes� �Yesi �----i
_ . _ _ - — — -
I-_::---:_ __:-_ ___ -._ ..-__ _. ___________-_� � � L�_l �Yes L Y�s� �-- --- 1
� . _ :::: --_:.:-:- : .-- ._-�._-_-__-_-_----_-__-� �� l_�l Yes� L Y��s� �----�
1 -1
I __ - - ..__ .-- - -- ----- ------ ----- --1 �� �__J Yes �YE.s� � -�
— -- - -- — r � r
I. .. __ _ . ____ . .------- ----- ----- __� �l �� Yes �YE.� I�-�
_ T _ .__
-I
- - - --.._. ----- - --- -
___
_ _._ ..-- -- --- ----__--------------�J — �� Yes C:s� C---�
- — - - - - --
--
� _..---... . ___---- —---- - � � � Yes Css� �--�
�. : .::_:_::__�__ _---:-_:_----___-=------� _—_� � n Yes CE.� �----�
�. _: :. - - -_ _-_ _-_---_-._"-___-__--- � l�-� � Yes CE� � � �
�.--.. ___- -- --------...._ _-_--------- '--� �� � � Yes �YE;,s, L�
I: J [ : f:: -- - - - ---- ----------- J � C� Y� [YP�� ��
I_ : ::_ _ -- _-_=
_ — —�— .----T-----.—°-- "_ _. — _
I � � I
i �
� s
�
,�
�-
�- � _
� � ;��
� .
� ' ��)
7 ,. '
�► S Q G`� � , � �
� x � 4 , �. -� + � ,
Q) /' 4
' '� �: ' 4 � I+ _ /�
!. ���r
:�II=) • �1? �� � �/ � � �� � ' � ,�� � �,, Y �
�„ . , � � � � � t� � � � ,, x �
��� �, , � . �
r:>.. «� �� � � �
\.X , � � � ` • �
F_, "n� �a� 11� l� � � ��7 �' � � �"' �'
- -
itf �tS 1 �
IYl Cl_ I]_ _ __..._ _.._.. .__._., _ .._ . . .
. .__ . _._ --- — -- --- -- -- ---- -- --- -- --- ---- -- --- -
- -
�_ ...- - __ _ _
_ . . .. .._ _..._ ----- -- ---- -- -- �. —
+�' � � � " ' � �
�. . � � c� c� � � � � � � �. �
7-, � '�" r "� � J v r ' �1 �
' � � � � � _ ! � i� {� � � � �
f"il ('�
.1'
w�l
ci ( �4t: :`i `
iii � ii � ` Y _ VI _ _ � � � � ,� � �
_ _ . _ . . _ .. .__ .
IY1 ,.,..r K[; -- - ---- ---- — -- . .�- --- . .__.
-- - -- --- -
cu
.� � � � ,
«> �„"'' �
� :� ,,�, '„f d► t � � - ^ o( c t �1 J1 t
ri . � � " � � V , . - " � � +�
+'.� �j q� --� �3 _� _�1 -� -� - - _�! � _: �1 c/� 3 �.� ,�, _ _
, ._ _ __ _ .- -- - -- - - --- — — --- — � ,� — --- --- -- ---- -- ---- -- _ _— -- - -
_ _
� ��6
4 � � �
'� . -�
�
�c} �
�. � �
��
�; :. � t
�u �
u
� t ''� t
4 �1^�^ � �
` • ) y �\
�fJ � � �
� /� J � I
1) ll) � (� � 1 y �„ l' � ` r 4
( ' tCS �A, � � J .
.__ Y � ' .� � • � . � • � L
�� L
.i i C) O � . O ✓ __ �. . ,. �
.
f.] O _ __ . . . _._ _ _ :._. .. . .... .. . .._ ... ..
_
. .___ '____ _ -_ -_ -___. _-__ . ... .
�i' . � . _ ' _.. . _ __ ' ____ ' '___ '._ _'- .__ .- --_. ____ __ ___._ .____ ._"_. .-_ . . . . _ . --__.; __ __ _-__. -
! � � I
t... /'� � �
C> s � S T , . � i" v '� � �(J + S
Q ♦ � r� r � 1 .� �( � � � s
�� � � � �, ..� " :� . s
lA.. rr � �
:L,� � �' � _ , �
flfl � _- -- ----- --- --- ---_ _-- - -- -- — --- -- ----- -- -- --- -- -� -Q --- -- -- ---- --- —_ ..-� --- --- - -- _ _ '*_'. _
�cf 1 I � _,,, �-' K .�
� � a- .� � �� � � � �
U> I . . .
C. ���
I �a II C� - -- - — -- -- --- - - -- ---- --- - -- ._ . . _ ._ ._ . . .. _ .. _ . .
,I . _ . . ... _ - -- -- -- — -- — --- --- - -- - ---- ---- - - — - - ` � � I C
, � O ��' � ' ;
I � � . I � a �
, r
; � I , Q -" c � ` � � - Q � � j � i � ' '
a , i ,� � p � � i �; i
. �� � � i ,
u � ! � � q � � � ; , ,
u� ' 9� (�. � � ' � ' I , , ; �
d, ; I � , ' � I ; ; �
� . ' ' . . i � � ' � S� ; � � � � , �
`� ' ' � ai (, O � � � I '
� s s s ' � '
� /�\ ,
o : ,
� \ � i n � N m � � � � `' C a '�� • ,� ',1! i � ,
, . � � Y , o �, i ;
i°' ; Q_ °: a n; _ .a. a_ � ' '- "' ,yi ,� � i ; �
v , � >, a� n� ai /' .� .. ��.�._.._.____ _. � _._ _ .� ..... �____._.___�._.
u_ I I , Y `� Y_ O C� O I �_�. _ _. �_.�._�._.._�._._ -
-- ___-----__— _�_.�_�._ f}�
1�
_ _ _ — -i;– ___T___ __.._ __ __ —
� I I ' �
I
_i
.I
�
u>
n�
� ' �It:
C)
1; ai
m ' �:_ j:
r:�.. u) m
� ' !u (u
�: c_ c_
tU 111 tlS
I'il lL I]_ _ -- _ __ _. .— -- .. - _ _ _ _. .
r.....
��
i
r:s� �
.t:
ca �� f:
, � �
t:, c�
cts U
.. _ . . . _ . . . ._ . . . . _
IYl �f. -- -- _ _- - -- -- --- ---- ---- --
— --- --- —
tl.Y
C ?
1h
��\�
�-1
v�
� Z .
��.y
'' _ _- . . _ _.._.. .__. . __ _.._ ._. _.._ .. .. . . .. . ..
. . -. __'_ '_. __-_ '_-_. '- ____'_ '_'_ _-"
_
� -' ._ ._ _ ' -.'" __- ___ _"_ ' _- '_ _ _- ___' .
�,
�)
�.j .:�
llS
c)
C:)
--�
N .
t)
j> Q)
r ,� 4�
�u
.ia c_
.i; 'ti
t.) (�)
�1.. �L _ --- - — . _ . .. - - . ._ _ . . - - . .. _ . _. _ .
�.
t�
c�
lA_
L31�
'U
lTl - -- - --- - _ _ __ .
I
cU I .
t:: i��
� �� ! _ . . . I ��
-- -- -- - ---- ----- ---- -- - ____. _ _ __ I . _ _ .
� --- --- --- --- -- --- --- --- — --- -- --- --
' , . .-- -- ---- -- --- --- -- -- -- '
� I I ( i I I � � I
�.. � i I � I i i ' � , �
� ; I I I ( ; i � ; i
I � �
; , � ;
i I � �
' a. I � I I I I � ! i
c� � � ! j I ' ; ;
v> I � � , : �
� 1� i I I � j I I � i
� � ' � N � � I � i ` , i .
Oi C � ` I I
� `•.l � 27 17 YJ .e-� +-� -.-. I I � � ' '
i Ll. I I � �,
�d� Q) Cl. L1 L�.l. � p_ (1- , � I � ,
C� � Q_ Q)� 4)' ) -� '� � � � I , I j �
c � >, � I
' ( �� _
I
___ ._._..` .—
��_. � , �- , � Y � o 0 o I .�_._.�_._..___�__.._. .. _.�__._ �__---________ __
� . .
ADEMCO 4193SN Serialized Interface Module (SIM)
- For connecting alarm sensing devices and switches to
ADEMCO multiplex polling loop
Quantity: 1 ea.
Requires control panel with SERIAL NUMBER device capability
(e.g., Vista-40, etc.)
Consult control panel instructions for compatibility
C E c UL us
LISTED
S789
� �
N7644V3 Rev.C 7/05 EN7 6 4 4 V3 k S
Installation Instructions
ADEMCO 4193SN Serialized Interface Module (SIM)
The ADEMCO 4193SN is a serialized two-zone expander used to connect alarm
sensing devices to controls that support serial number polling loop devices(i.e.,Vista-
40, Vista-50P, and Vista-100).
The ADEMCO 4193SN can be configured as one supervised zone (10K EOLR) and
one unsupervised zone, or two unsupervised zones (normally closed devices only).
Consult the control panel installation instructions for programming information.
Electrical Specifications:
Voltage: 8-12VDC (as supplied from the ADEMCO control panel for multiplex
polling loop)
Current: 1.5mA
WHITE(LOOP 1)SUPERVISED EOLR 10K
RED(+)
YELLOW(LOOP 1)UNSUPERVISED
POLLING
LOOP GREEN(LOOP 2)uNSUPERVISED
BLACK(-) BLACK(COMMON) ry
WIRING DIAGRAM �
C V� US
LISTED
S789
For Fire Applications:
The ADEMCO 4193SN must be mounted inside the control panel cabinet or inside a
UL Listed junction box. Loop 1 must be used in the supervised configuration for Fire.
Loop 2 may be used for Burglary.
For UL Burglary Applications:
If using an unsupervised zone of the ADEMCO 4193SN, the unit must be mounted
within 3-feet of the alarm initiating device,with no intervening barriers.
Honeywell
5192SD/SDT Addressable Photoelectric Smoke Detector
Installation and Maintenance Instructions
SPECIFICATIONS
Diameter(including mounting bracket): 5.5 inches (140 mm)
Height(including mounting bracket): 1.7 inches (43 mm)
Weight: 5.3 ounces(150 grams)
Installation Temperature Range: 32°F to 100°F(0°C to 38°C)
Installation Humidity Range: 10%to 93% relative humidity, non-condensing
Air Velocity: 4000 ft./min. maximum
Heat Sensor(5192SDT only): 135° F fixed temperature electronic thermistor
System Voltage Range: 7—14 V
Standby Current(maximum @ 12 V):
LED off: 1.2 mA
LED on: 2.8 mA
Before installing detectors, please thoroughly read the supporting Ademco control panel installation instructions, which provide de-
tailed information on detector spacing, placement,zones, and special applications. Copies of the installation instructions are available
from Ademco. NFPA 72 and NEMA guidelines should also be observed.
GENERAL DESCRIPTION
The Model 5192SD/SDT photoelectric smoke detector uses a state-of-the-art optical sensing chamber. This detector is designed to
provide open area protection and to be used with compatible UL-listed Ademco control panels.An LED on each detector flashes every
10 seconds. If the sensing chamber is unable to detect smoke, the LED will cease to blink. When a unit reports an alarm condition to
the control panel,the panel will send a code command to steadily light that unit's LED. If the same loop has multiple detectors report-
ing alarm, only the first detector that reported alarm would have its LED turned on steadily. However, the panel will latch the address
of all the remaining detectors that reported alarm. The 5192SD/SDT detector is intended for use in an Ademco 2-wire polling loop
system. It is addressed by either dip switch or internal serial number and has high and low manintenance that is enabled with dip
switch position 8. (NOTE: Maintenance is shipped factory default OFF-dip switch 8 is set to"ON"position).A two-screw, removable
terminal block is used to connect to the system. Both detector power and communication between detector and control panel are ac-
complished over the same two wires.
MOUNTING INSTRUCTIONS
Each 5192SD/SDT detector is supplied with a mounting bracket that permits the detector to be mounted:
1.To a single gang box.
2. Directly to a 312 inch or 4 inch octagonal box.
3.To a 4 inch square electrical box by using a plaster ring.
TAMPER RESISTANCE
This detector includes a tamper-resistant feature that prevents its removal from the base without the use of a tool.To enable this fea-
ture, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket(see Figure
2),then install the detector.To remove a detector from the bracket once it has been made tamper resistant, use a small screwdriver to
depress the tamper-resistant tab located in the slot on the mounting bracket, and turn the detector counterclockwise.
Figure 1.Surface mounting 5192SD on 3'/z inch Figure 2.5192SD/SDT detector mounting bracket:
and 4 inch octagon box:
TAMPER RESISTANT TAB
TAMPER$LOT (CUT OFF SMALL TAB TO
(DEPRESSTABTO .i ACTIVATETAMPER-RESIST
REMOVE DETECTOR) FEATURE)
0 f �\
��
�� ALIGNMENT �
ARROWS
50193-00 � S0242-00
AD400-19-00 1 156-1002-011 R
Honeywell International Inc., 165 Eileen Way,Syosset, NY 11791
WIRING INSTALLATION GUIDELINES
All wiring must be installed in compliance with the National Electrical Code, local codes, and any special requirements of the authority
having jurisdiction. Proper wire gauges should be used.The conductors used to connect the smoke detectors to the control panel and
accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from
responding properly in the event of a fire.
The screw terminal block accepts 14 to 22 gauge wire. For best system performance, all wiring should be installed in separate
grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring.Twisted pair or shielded cable may
be used to provide additional protection against electrical interference. If shielded cable is used,the shield connection to and from the
detector must be continuous by using wire nuts, crimping, or soldering as appropriate for a reliable connection.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel speci-
fications for the total loop resistance allowed for the control panel being used before wiring the detector loops. Wire connections are
made by stripping about'/a"'of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening
the screw to secure the wire in place.
NOTE: Using twisted, shielded wire will result in decreased overall cable run as specified in the control installation instructions.
INSTALLATION
Remove power from the control unit or initiating device circuits before installing detectors.
1. Wire the plug-in screw terminal block(see Figure 3) and plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the mounting bracket.
3. Turn the detector clockwise in the mounting bracket until it clicks into place.
4. After all the detectors have been installed, apply power to the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities that the system is in operation.
Figure 3.Wiring diagram for 5192SD/SDT smoke detector:
-- OPTIONAL CABLE SHI`ELD
/1 /T � � /T `������
'F.
I � I I I I � ' I
�J �� �J �� ��
H �
w GND
J
m J
a Z
�a
�O � + � +
o� —
w�
c~n O
�U
� SWITCH REMOVABLE
TERMINAL BLOCK
sozis-oo
ACAUTION
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
DETECTOR ID NO.
IMPORTANT: The 5192 smoke detector provides for both DIP switch and serial number addressing. DIP switch positions 1-7 are
used for setting the zone number with older controls which only support DIP switch addressing.The permissible DIP switch addresses
are from 10 to 63 as shown in Table 1. If the 5192 smoke detector is to be used with newer controls that support serial number ad-
dressing,you MUST configure the detector as a serial number device during the zone programming procedure for those controls. DIP
switch addressing of the 5192 with controls that support serial number addressing may result in polling loop trouble conditions.
TESTING THE 5192SD/SDT SENSITIVITY
NOTE: Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily
out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. Notify the proper authorities that the
system is back in operation when finished testing.
Detectors must be tested after installation and following periodic maintenance. Both smoke and heat detection testing are recom-
mended for verifying system protection capability.Test the 5192SD/SDT as follows:
AD400-19-00 2 156-1002-011 R
Table 1. Permissible Dip Switch Addresses:
DIP SWITCH POSITION DIP SWITCH POSITION DIP SWITCH POSITION
Zone Zone Zone
Number 1 2 3 4 5 6 7i Sz Number 1 2 3 4 5 6 7i Sz Number 1 2 3 4 5 6 7i Sz
10 N N N ON N 31 ON ON 48 ON ON ON ON ON
11 ON ON ON ON 32 ON ON ON ON ON ON 49 ON ON ON ON
12 ON ON ON ON ON 33 ON ON ON ON ON 50 ON ON ON ON
13 ON ON ON ON 34 ON ON ON ON ON 51 ON ON ON
14 N ON ON ON 35 ON ON ON ON 52 ON ON ON ON
15 ON ON ON 36 ON ON ON ON ON 53 ON ON ON
16 ON ON ON ON ON ON 37 ON ON ON ON 54 ON ON ON
17 ON ON ON ON ON 38 ON ON ON ON 55 ON ON
18 ON ON ON ON ON 39 ON ON ON 56 ON ON ON ON
19 ON ON ON ON 40 ON ON ON ON ON 57 ON ON ON
20 N N ON ON ON 41 ON ON ON ON 58 ON ON ON
21 ON ON ON ON 42 ON ON ON ON 59 ON ON
22 ON ON ON ON 43 ON ON ON 60 ON ON ON
23 ON ON ON 44 ON ON ON ON 61 ON ON
24 ON ON ON ON ON 45 ON ON ON 62 ON ON
25 ON ON ON ON 46 ON ON ON 63 ON
26 ON ON ON ON 47 ON ON S/Na
27 ON ON ON NOTES:Blank position=OFF
28 ON ON ON ON 1,DIP Switch position 7 must always be set ON.
29 ON ON ON p,DIP Switch position S disables maintenance signals if ON;enables maintenance signals if OFF.
30 ON ON ON It must be set to ON for all applications except for panels that can support maintenance signals.
Failure to do so may result in False Check conditions on the system.
3.Serial Number addressing occurs when DIP switch positions 1-7 are OFF.
A. Test Switch
1. Press and hold the recessed test switch, located on the detector housing (see Figure 4), for 5 seconds with a 0.18 inch
maximum diameter tool such as an Allen wrench or small screwdriver.
2. An alarm should be annunciated at the system's control or console within 5 seconds. Some systems also cause the detec
tor's LED to latch on during the alarm. Otherwise,the LED continues to blink every 10 seconds.
B. Test Module(Model No. MOD400R)
The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as described in the test
module's manual.
C. Auto-maintenance Feature
Test sensitivity from the control panel if applicable (refer to control panel test procedure).
D. Smoke Entry Test
The recommended field test tool is the GEMINI model 501 aerosol generator set to represent 4%/ft. to 5%/ft. obscuration as de-
scribed in the Gemini manual. Using the bowl-shaped applicator, apply aerosol until detector alarms.
E. Direct Heat Method(5192SDT only)
Direct the heat from a 1000 to 1500 watt hair dryer toward either of the thermistors. Hold the heat source about 12 inches from the
detector in order to avoid damage to the plastic.Heat detectors that go into alarm reset only after they have cooled sufficiently.Check
the control panel to determine whether the Reset switch,or other auxiliary device or control momentarily interrupts loop power.
Detectors that fail to alarm during any of the above tests should first be cleaned as outlined in MAINTENANCE. If the detector still fails
to activate, return it for repair.
Figure 4.Top and side views showing test switch location
LED /� `\`.
\
r� �
TEST MODULE PUSH RECESSED
SOCKET � SWITCH WITH A
�%'
RECESSED TEST 0.18"MAX. DIAMETER TOOL
SW ITCH so2os-oo
soiss-oo
ACAUTION
Dust covers are an effective way to limit the entry of dust into smoke sensing chambers. However, they may not completely prevent
airborne dust particles from entering the detector. Therefore,Ademco recommends removal of detectors before beginning construc-
tion or other dust producing activities. Be sure to remove dust covers from any detectors left in place during construction as part of
returning the system to service.
AD400-19-00 3 156-1002-011 R
AUTO-MAINTENANCE FEATURE Figure 5. Removal of cover and screen for cleaning:
This detector can transmit a LOW SENSITIVITY or HIGH SEN-
SITIVITY signal in addition to the basic normal and alarm levels.
These HIGH and LOW SENSITIVITY signals are communicated
to the control panel and indicate that the detector may not be able � REMOVABLE
to detect smoke or may false alarm.Supporting control panels use HOUSING
these maintenance signals to effect prompt cleaning or replace-
ment of the malfunctioning detector,which is uniquely identified at
the control panel by the detector's polling address.The auto-main- ;� REMOVABLE
tenance feature may be enabled by placing dip switch position#8 "_ � SCREEN
to the"off"position.This may be necessary to be compatible with
some panels. Refer to Ademco control panel installation instruc- SENSING
tions to determine if maintenance features are supported. CHAMBER
MAINTENANCE COVER
NOTE: Before removing the detector, notify the proper authori-
ties that the smoke detector system is undergoing maintenance SENSING
and will temporarily be out of service. Disable the zone or system ; � CHAMBER
undergoing maintenance to prevent unwanted alarms.
NOTE: (Model 5192SDT only) Before removing the detector f BASE
cover, note the position of the thermistors. Make sure the therm- so�ss-oo
istors are not bent over when the housing is replaced.
1. Remove the detector housing by gently prying the four hous- 5. Replace the chamber by orienting it so that the arrow on the
ing tabs on the bottom of the base with a small-bladed screw- top aligns with the arrow on the printed circuit board. Care-
driver and pull the housing from the base. Use caution to fully press the screen on to the sensing chamber, making
avoid damaging the thermistors (5192SDT only). sure it fits tightly.
2. Vacuum the screen carefully without removing it. 6. Replace the housing by aligning the three triangular slots on
3. Remove the screen assembly by pulling it straight out (see the base with their counterparts on the housing. Gently press
Figure 5). Remove chamber cover. the housing until it locks in place. Check to make sure the
4. Clean the sensing chamber by vacuuming or blowing out thermistors are in the upright position (5192SDT only).
dust and particles. 7. Reinstall the detector.
8. Notify the proper authorities that the system is back in operation.
Please refer to insert for the Limitations of Fire Alarm Systems
LIMITED WARRANTY
Honeywell International Inc.,acting through its Security&Custom Electronics business("Seller") 165 Eileen Way,Syosset, New York 11791,warrants
its product(s)to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use
and service for 24 months from the date stamp control on the product(s)or,for product(s)not having a manufacturer's date stamp,for 12 months from
date of original purchase unless the installation instructions or catalog sets forth a shorter period,in which case the shorter period shall apply.Seller's
obligation shall be limited to repairing or replacing,at its option,free of charge for materials or labor,any product(s)which is proved not in compliance
with Seller's specifications or proves defective in materials or workmanship under normal use and service. Seller shall have no obligation under this
Limited Warranty or otherwise if the product(s)is altered or improperly repaired or serviced by anyone other than Honeywell factory service.Connection
of any device(s)to a communicating bus of a Honeywell security system (e.g., keypad bus, polling loop)other than those manufactured or approved
by Honeywell shall void this warranty. For warranty service, return product(s)transportation prepaid,to Honeywell Factory Service, 165 Eileen Way,
Syosset,New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHER-
WISE,WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY
CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY
OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the product(s) it sells may not be compromised or circumvented;that the product(s)will prevent any personal injury or
property loss by burglary, robbery, fire or otherwise; or that the product(s)will in all cases provide adequate warning or protection. Customer under-
stands that a properly installed and maintained alarm system may only reduce the risk of a burglary, robbery, fire, or other events occurring without
providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result.
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A
CLAIM THAT THE PRODUCT(S) FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE,WHETHER DIRECTLY OR INDIRECTLY,
FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE,REGARDLESS OF CAUSE OR ORIGIN,SELLER'S
MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT(S),WHICH SHALL BE THE COMPLETE
AND EXCLUSIVE REMEDYAGAINST SELLER.
AD400-19-00 4 156-1002-011 R
002005 Honeywell International Inc.
K3590-ADV4 2/09 Rev.A
Honeywe�� ADEMCO 6150 & 6160
REMOTE KEYPADS
INSTALLATION AND SETUP GUIDE
Keypad Features ADEMCO 6150 ADEMCO 6160
Fixed-Word 2-Line A1 ha
Backlit Display ✓(see note) ✓ (see note)
Dedicated Function Keys ✓ ✓
Built-in Sounder Piezo Speaker
Note:Permanent display backlighting is an option on some controls(see the control's instructions for details).
GENERAL INFORMATION WIRING AND INSTALLATION
The ADEMCO 6150 and ADEMCO 6160 are addressable The keypads can be surface mounted directly to a drywall,
Remote Keypads designed for use with ADEMCO control or to a single-or double-gang electrical box.
panels.Addresses are set via the keypad keys. 1. Push the two case release snaps at the bottom of the
The keys on the keypads are continuously backlit for keypad with the blade of a medium screwdriver(this will
convenience. push in the release snap), then pull that side of the case
Supervised by control panel(if supported). back away. Insert the screwdriver in the side of the
KEYPAD DISPLAYS AND LEDS keypad(between the front and back case) and gently
twist to release the side locking tab. Repeat for the other
The keypads have the following display features: side.Refer to Figure 1 for location of the case back
release snaps and locking tabs.
Fixed 2-line 2-digit Custom
Model Word Alpha Zone Zone 2. Route wiring from the control panel through the opening
Display Display Identifier Descriptors in the case back.
6150 X X 3. Mount the case back to a wall or electrical box.
6160 X X 4. Wire directly from the keypad's terminal block to the
The following table shows the LEDs and their functions: terminal block on the control paneL (See Wiiing Table
below).
LED Function
Red Lights when the system is armed in any mode NOTE:No more than one wire per terminal may be
Green Lights when the system is"ready"to be armed. Connected. If daisy-chained configuration is required,
pig-tail wires together so that only one wire is
SPECIAL FUNCTION KEYS terminated under the screw. Use 16-24 AWG wire only!
The keypads also feature function keys. These keys may be
programmed for panic alarms or other special functions W�ring Table(All Keypads)
such as macros. See the control's instructions for details. Keypad Control Panel Wire Color
-G Data In Green
Function keys must be held down for at least 2
seconds to activate an alarm; key pairs are activated - -Aux Pwr(GND) Black
immediately. + +Aux. Pwr Red
-Y Data Out Yellow
Function Keys
See the control panel's Installation and Setup Guide for
A or[1] and[=!=] more complete details.
B or[=;=] and[#] 5. Reattach the keypad to its case back.
C or[3] and[#]
D
FUNCTION KEY LABELS
e � %' A set of adhesive-backed labels with some typical function
symbols (i.e., fire,police,personal emergency, etc.)is
.°"`°° � provided. These labels can be placed on or next to the keys
pE�o�� O to identify each key's function for the end user(as
O
� determined by the control panel's capability and
0 programming; see the control's instructions).
Nore: OPERATING THE KEYPAD
TO REMOVE CASE BACK �
PUSH INTHETWO MOUNTING � ° For o eratin instructions, see the User Guide for the
SNAPS LOCATED ALONG THE ° I� g
BOTTOM OFTHE KEYPAD � o � control panel used with this keypad.
AND LIFT UP. o
� �'' SPECIFICATIONS
\ � �
> Physical:
RETAINWG 6150: 4-7/S"H x 6-1/4"W x 1"D
SNAPS LOCKING
TAB � 6160: 5-5/16"H x 7-3/S"W x 1-3/16"D
Figure 1. Removing the Case Back
Displays:
SETTING THE KEYPAD ADDRESS 6150: Fixed-Word LCD (backlit).
The keypad can either be set for an address of 00-30,or to 6160: 2 x 16 alpha-numeric supertwist LCD,
the non-addressable mode (31). The keypad's default backlit.
address is 31.
To change the keypad's address, do the following: Sounder:
1. Enter address mode: Power up the keypad. Within 60 6150: Piezo-electric(fire alarm is loud,pulsing
seconds of power-up,press and hold down the [1] and [3] single tone; (all Keypads)burglary alarm is
keys at the same time for 3 seconds. (If unable to enter loud, continuous, dual tone).
address mode,power up and try again.) 6160: Speaker.
The current keypad address will be displayed, and the
cursor will be under the"tens"digit. If 10 seconds have Voltage: 12VDC (power-limited)
passed with no key entry,the keypad automatically exits
address mode. You must power down,power up and Current:
start address mode again. 6150: 70mA(ARMED LED lit,LCD backlight and
NOTE: The keypad will not enter address mode if the sounder on), reduces to 40mA when panel is
panel to which it is connected is in programming mode. operating in standby mode (backlight off�.
6160: 150mA(ARMED LED lit,LCD backlight
2. Set the current address to"00": Press [0] to clear the and sounder on), reduces to 40mA when
current"tens"digit. The cursor will move to the"ones" panel is operating in standby mode
digit position. Press [0) to clear the current"ones" digit. (backlight of�.
The cursor will move back to the"tens"digit position.
3. Enter the keypad's address: Enter the proper"tens" digit NFPA-72 Compliant.
of the keypad's address. The cursor will move to the
"ones" digit position. Enter the proper"ones" digit of the
keypad's address. Note that address"31"sets the
keypad to non-addressable mode.
4. Exit address mode:
Press [�] to save the displayed address and exit address
mode.
VIEWING THE KEYPAD ADDRESS
Press and hold down the [1] and [3] keys at the same time
for about 3 seconds. The current address is displayed. No
key entry is allowed. Press any key to exit or wait 10
seconds to exit viewing mode.
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY
INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
For the latest warranty information, please go to:
http://www.security.honeywell.com/hsc/resources/wa/index.html
Honeywel' 2pOrBox 9040,nMelv�'�IIeeNY 11747o II IIIIIIII I IIIII I I I I I III I I I I
Copyright OO 2009 Honeywell International Inc. K3590-ADV4 2/09 ROV.A
www.honeywel I.com/secu rity
K0903V1 2/06 Rev.B
Honeywell ADEMCO 6160RF
Keypad/Transceiver
Installation and Setup Guide
GENERAL INFORMATION
The ADEMCO 6160RF keypad/transceiver is a combination unit that combines the functions of the following
devices:
• 6160 Alphanumeric Addressable Keypad
• 5881H RF Receiver
• 5800TM Transmitter Module
The 6160RF Keypad/Transceiver may be used on any control panel that supports 5800 Series wireless devices
(e.g.,VISTA-10P, VISTA-15P,VISTA-20P).
FEATURES
• Supports wireless key transmitters (e.g.; 5804) and bi-directional transmitters(e.g.; 5804BD, 5828/5828V).
• Supports wireless keys with high-security(encryption) capability(e.g.; 5804E).
• Provides a nominal range of 200 feet' for RF transmitters (some transmitters have a shorter range).
• Supports RF jam detection when the receiver is enabled.
• Capable of sending status signals (Armed, Ready, etcJ to bi-directional units such as 5804BD, 5804BDV and
5828/5828V.
uL The following 5800 series transmitters are not intended for use in UL installations: 5802, 5804, 5804BD, 5804BDV, 5804E,
5814, 5816TEMP, 5819, 5819BRS, 5819WHS, 5828/5828V and 5850.
INSTALLING THE 6160RF 2. Pass the wiring from the control panel through
Locate the 6160RF in an area and at a height where the opening in the case back. (see the control
it is convenient for user operation. The 6160RF must panel's instructions for proper run lengths.)
be at least 10 ft from the control panel to ensure
proper operation of the RF receiver. a. If surface wiring is being used, wiring may be
Mounting and Wiring routed through the top or the bottom left-side
The 6160RF has terminal blocks for connection to breakout in the case back. The breakouts must
power and data wires. Removing the keypad's case be punched out using a screwdriver before
back provides access to the terminal blocks.
mounting the case back.
The 6160RF can be surface mounted directly to b. If desired,wires may be strain-relieved to the
walls, or to a single- or double-gang electrical box. wire tie point on the inside of the case back
Follow these steps to mount and wire the keypad: with a tie wrap (not supplied).
1. Push the two case release snaps at the bottom of 3. Mount the case back to a wall or to an electrical
the keypad with the blade of a medium box using the 25mm-long self-tapping screws
screwdriver(this will push in the release snap), supplied(mollies for drywall are not supplied).
then pull that side of the case back away. Insert 4. Connect the power and data wires from the
the screwdriver in the side of the keypad control panel to the terminals on the 6160RF as
(between the front and back case) and gently indicated in Figure 2 and Table 1.
twist to release the side locking tab. Repeat for
the other side. Refer to Figure 1 for location of the
case back release snaps and locking tabs. ❑ ❑ o O
_ � �' ���� �o
� �
��;�>
� � ❑
� 0
NOTE: o o�
TO REMOVE REAR COVER
PUSHINTHETWOMOUNTING Q �-
SNAPSLOCATEDALONGTHE
BOTTOM OFTHE KEVPAD
AND LIFT COVER UP. \ O
0 }1
mouNnNG �oc�clNG WIRING TERMINALS
RE�EASE �B (TO CONTROL PANEL) e
SNAPS e
Figure 1. Removing the Case Back Figure 2-6160RF Wiring Details
Table 1 -Wiring Table 5. Reattach the keypad to the mounted case back.
Keypad Control Panel Wire Color Attach the top of the keypad first, and then
G�(Data Out) Data In Green press the bottom section down until it snaps
- -Aux Pwr(GND) Black into place securely.
+ +Aux Pwr Red
�Y(Data In) Data Out Yellow 6. Peel off protective film on the LED panel and
install the keypad labels as required.
APPLICATION GUIDELINES FOR THE 6160RF
Use the following guidelines when planning an installation:
If... And... Then...
This is the only You want to use both • Set the keypad to a device address assigned to the desired partition.*
transceiver on the receiver and • Enable the receiver.
the system, transmitter function
on a single-partition • Program a system House ID in the control panel (this will enable the transmitter
system, function).**
• Set the wireless devices that will communicate with this 6160RF to the same
system House ID.
There is another You want to use only • Set the keypad to a device address assigned to the desired partition.*
receiver or the transmitter • Disable the receiver.
transceiver on function on a second
the system, partition, • Program a DIFFERENT House ID in the 6160RF than is programmed in the control
panel.*/**
� Set the wireless devices that will communicate with this 6160RF to the same
House ID as the 6160RF.
You want to use only • Set the keypad to a device address assigned to the Partition 1.
the transmitter • Disable the receiver.
function on a single-
partition system, • Program a House ID in the 6160RF that matches the system House ID
programmed in the control panel.*
• Set the wireless devices that will communicate with this 6160RF to the same
House ID.
Notes:
* On VISTA-40 panels and above, wireless keypads (e.g., 5804BD)can only be used on a single partition. This
partition is programmed in f"ield 1*48, and must match the partition assigned to the 6160RF. Wireless keys can
be used on more than one partition, using a House ID programmed in the 6160RF and the devices. In this case,
the wireless keys must be assigned to the same partition as the 6160RF.
�* On VISTA-20P panels, the 6160RF will use the House ID programmed in the panel for the partition to which
it is assigned. Wireless keypads can only be used on Partition l.
PROGRAMMING THE 6160RF
Refer to the following procedure to program the 6160RF:
STEP DESCRIPTION DISPLAY CHOICES
1. Enter the program mode by pressing the [1]and[3]keys simultaneously
for a few seconds within 60 seconds after applying power.
2. (Keypad Address)Enter the two-digit keypad address. Press the[='s�]key CDIYADD1PE55 = XX 00-31
to continue.
Notes: (1) Refer to the control panel's installation instructions for the
acceptable keypad addresses.
(2) On the VISTA-40 and above the 6160RF's partition assignment must
match the RF keypad partition assignment programmed in field
(1*48).
3. (Receiver Enable)Enter[1]to enable,or[0]to disable Receiver.Enable !2E[�jf��� 1= ON
the receiver if RF transmitters or wireless keypads are programmed into 0= OFF
the control and no other receivers are enabled.Press the [=i=]key to Qn �Q= fl��l
continue.
- 2 -
STEP DESCRIPTION DISPLAY CHOICES
4. (Receiver Address)If receiver is enabled,enter the two-digit receiver RFtADDJPE55=XX 00-30
address. (01-30).
Note: Refer to the control panel's installation instructions for the acceptable
receiver addresses.
Press the [='s=]key to continue.
5. (House ID)This prompt will only appear if the receiver is disabled. If the }{Q(fSE fd= x)( 00-31
receiver is enabled the 6160RF will use the House ID programmed in
the panel. Refer to Application Guidelines section when selecting a
House ID.
To program a House ID:Enter 01-31.
To disable the transmitter:Enter 00
Note: Each device that will receive status from the 6160RF must be set to the
same House ID as the 6160RF(refer to Application Guidelines section).
Press the[='s=]key to continue.
6. (Enable High Security Mode)Enter[1]to select High Security Mode. }{j�xS�Q��lT� 1= Enable
Note: If the High Security mode is enabled,the 6160RF will only recognize 0= Disable
encrypted devices. If this mode is disabled,the 6160RF will process p��jjj p�
commands both encrypted and non-encrypted devices.*
Press the[=i=]key to continue.
7. (Disable High Security Devices)Press the[='s=]key to skip this prompt (jfSf38LF f.{SdFf/r� 1=YES
and exit Program Mode. MQ jjJ_ �fs o= NO
Notes: (1) The [�k] key must be pressed several times in order to save the
programmed data.
(2) If you need to disable encrypted devices,refer to the Disabling High
Security Devices section.
� *When operating the system in High-Security mode,5804BD wireless keys will still function. If you want the system to
recognize only encrypted wireless devices,program only encrypted devices in the system.
ACTIVATING HIGH SECURITY DEVICES
This following procedure should be followed if using High-Security(encrypted) devices.
STEP DESCRIPTION
1, Follow the normal procedure for programming the device into the control panel(refer to the Installation
Instructions for the device that you are programming). Exit out of Programming Mode.
2. Put the control panel in Go/No Go Test mode. (See the Installation Guide for the panel being installed.)
g. Follow the instructions supplied with each wireless device to enroll the device in High-security mode.After each
device is enrolled the 6160RF will momentarily display"SECURITY DEVICE"along with the device number and
its serial number.
Note:The 6160RF will support a maximum of 8 devices. If you attempt to enroll additional devices the keypad will display
"EXCEEDED NUMBER""ALLOWED DEVICES".
DISABLING HIGH SECURITY DEVICES
This mode gives you the ability to disable high security on all wireless keys that have been enrolled in the
6160RF. This is particularly useful if a user loses a wireless key.
Once high-security (encrypted) devices have been disabled, they will only operate if the 6160RF is set to listen to both
� encrypted and non-encrypted devices(programming step 6,above).To completely disable the devices,they must be deleted
' from the control panel.
STEP DESCRIPTION DISPLAY CHOICES
1. After the keypad has been powered for at least 60 seconds hold rQnROORFSS=xx 00-31
down the [1] and [3] keys at the same time for 3 seconds. The
current keypad address will be displayed. (You cannot change the
keypad's address at this point.)Press the[=i=]key to continue.
2_ (Delete High Security Devices)Press the [1]key to remove all high- OJSRSLF HS DFU� 1=YES
security(encrypted)devices. Press the[=i=]key to continue. �� jTJ_y�s 0 = NO
g. If YES was selected in Step 2 the unit will display a confirm fjR��Q(f SUQ�� 1=YES
request to delete the stored high security device.Press the [1]key nd jT1_yFS 0 = NO
to accept,followed by the[=:=]key to exit the programming mode.
- 3-
TROUBLESHOOTING
The error messages listed in the following table cause the 6160RF to produce a single ding tone. The table
describes the error messages and the corrective actions.
Display Probable Cause Corrective Action
Low Bat(with Low battery in the wireless device. 1. Replace the battery if the wireless transmitter has a replaceable battery.
zone no.) 2. Replace the transmitter if the wireless transmitter does not have a
replaceable battery.
Open Ckt No data is being received from the control panel. Verify that the keypad�Y(yellow)wire is connected properiy.
Check 100 1.The control panel does not see the 6160RF 1 a.Verify that the keypad�Y(yellow)and G� (green)wires are
* Receiver,or the Receiver is not functioning. connected properly.
Check 1x�c
1 b.Verify that the control's receiver address is correct.
2.Another device on the keypad terminals is not 2. Verify the wiring connections between the control and all other devices.
communicating to the control panel.
*�=the device address of the receiver.
SPECIFICATIONS
Physical: 5-3/8"H x 7-3/8"W x 1-1/4"D Current: Standby 50mA
(137mm x 187mm x 32mm) Backlighting on and
Wiring: Refer to Table 1 Sounder on 150mA
Range: 200 ft(60.9 m)nominal Display: 2 x 16 alphanumeric supertwist LCD,backlit
Frequency: 345 MHz Sounder: Tone Generator Integrated Circuit.(fire alarm is loud pulsing tone;
burglary/audible panic alarm is continuous tone)
FOR DETAILS ON THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM,REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL PANEL BEING
INSTALLED IN CONJUCTION WITH THIS DEVICE.
FCC STATEMENT&INDUSTRY CANADA STATEMENT
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1)This device may not
cause harmful interference,and(2)This device must accept any interference received,including interference that may cause undesired operation.
Federal Communications Commission (FCC)Part 15 Statement
This equipment has been tested to FCC requirements and has been found acceptable for use.The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly,that is,in strict accordance with the manufacturer's instructions,may
cause interference to radio and television reception.It has been type tested and found to comply with the limits for a Class B computing device in accordance with the
specifications in Part 15 of FCC Rules,which are designed to provide reasonable protection against such interterence in a residential installation.However,there is no
guarantee that interference will not occur in a particular installation.If this equipment does cause interference to radio or television reception,which can be determined
by turning the equipment off and on,the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna,have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits
If necessary,the user should consult the dealer or an experienced radio/television technician for additional suggestions.The user or installer may find the following
booklet prepared by the Federal Communications Commission helpful:"Interference Handbook."This booklet is available from the U.S.Government Printing Office,
Washington,DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or
modifications could void the user's authority to operate the equipment.
LIMITED WARRANTY
Honeywell International Inc.,acting through its Security&Custom Electronics business("Seller")165 Eileen Way,Syosset,New York 11791,warrants its products to be
in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the
date stamp control on the product or,for products not having an Ademco date stamp,for 12 months from date of original purchase unless the installation instructions or
catalog sets forth a shorter period,in which case the shorter period shall apply.Seller's obligation shall be limited to repairing or replacing,at its option,free of charge
for materials or labor,any product which is proved not in compliance with Seller's specifications or proves defective in materials or workmanship under normal use and
service.Seller shall have no obligation under this Limited Warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than Ademco
factory service.For warranty service,return product transportation prepaid,to Factory Service,165 Eileen Way,Syosset,New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND
BEYOND THE DESCRIPTION ON THE FACE HEREOF.IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES
FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the products it sells may not be compromised or circumvented;that the products will prevent any personal injury or property loss by
burglary, robbery,fire or otherwise; or that the products will in all cases provide adequate warning or protection. Customer understands that a properly installed and
maintained alarm may only reduce the risk of a burglary, robbery,fire or other events occurring without providing an alarm,but it is not insurance or a guarantee that
such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL
INJURY,PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING.HOWEVER,IF SELLER IS HELD LIABLE,WHETHER
DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN,
SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT,WHICH SHALL BE THE COMPLETE AND EXCLUSIVE
REMEDY AGAINST SELLER.This warranty replaces any previous warranties and is the only warranty made by Seller on this product.No increase or alteration,written or
verbal,of the obligations of this Limited Warranty is authorized.
II I II II II I II I II I II III I I III II III Hone�ell 165 o yegn oaoos Ho es eti�NewYo ak111791
K0903V1 2/06 Rev.B www.honeywell.com/security
,__ ,., . . ,.. � . , ..
` f ` ' � " 14Q���r�
. �
� '`" -'°"° �'• • Adds 4 programmable relays
to selected Vista panels
�� °3 � :. � �� �"-- Easily wired to control
..:_�. �a,.�{' fi]!--'. "^,�—�.��� •
,, - -- � panel
V - � �:
� ;��. � �= • Fits inside Universal
�� � ';, �;,�;� Control Cabinet
, r .��;� ,�.,�:
�� � � �€�, • Expand existing security
�'�'� s stems with additional
:�--�;� �, �- Y
� �` tl output capabilities
;' - ,. ��t,��: •
� � �` �` '�'" ractiv case de
� � �, sign
�- �r, ;
� tt e
i5��F�.�;%ih ��� �� �� � ��� � • Check Control
=,-r�, ��.. �� . �
. �� Documentation for
- �` =T�'���� r �`- - � '���`. >��x =� ` -� '� com atibilit with 4204.
_ - � :;: �, K �,,. P Y
a7��. ���.a�r ��a�� s���i���,��r�or��
When your installation require- Physical:
ments call for additional relay Width: 6-1/2" (169mm)
outputs, the 4204 is your answer. Height: 4-1/4" (108mm) t� �` : �� ---�-
The 4204 Intelligent Relay Board Depth: 1-1/4° (32mm) � � _ °'�':��
adds relays which are connected Electrical ��
to the Control/Communicator via �-- �i��""`
Voltage: 12VDC ��
the control's console wiring. The �
relay outputs are programmed by (from control's ` � w�,anA
the appropriate control for a remote console ,
connection oints `' "`'��
variety of functions. p �
Current: 15mA standby plus
The 4204 is ideal for applications 40mA per active
that require additional sounding relay
devices, strobe lights or other Multiple 4204s may be located next to the
devices that need or desire to be control in another Universal Can. (See
controlled by the control panel.
control documentation for compatibility).
The 4204 is housed in a white �
plastic case for wall mounting and �
can be mounted in a Universal ,�, �I'}'.j ��� � �
¢���� �' N
Can. If the 4204 is remotely ". � ,4.�. .~"Aa.� �
mounted, there are provisions to �-- -� ,
tamper protect the cover, and the - �
unit so that it cannot be t �
_
disconnected from the console ` -
wiring without detection by the � �,'� ���A '
control. t �.. '- � ��45n �' r� � ; -
�.
,� �,,..,.�. �
� ��-�- _ _..
;���.,, _ - _�_ __ -
�
������ Universal Can with 4204 and battery • Universal Can with console wiring
connection to the 4204.
•4204 may be mounted directly on the wall
165 Eileen Way • Syosset, NY 1 1791 adjacent and wired to the control panel.
F01/23/93
I I I
��
� �
5800WAVE
WIRELESS SIREN
�
Honeywell's 5800WAVE is a fully wireless siren that provides periodic status information and battery back up for an added level
of performance and protection. The flexible design simplifies installation, saves time and installs in seconds at any location
without the need to run wires. System status is shown on the 5800WAVE with three LED's directly on the front of the unit.
FEATURES
• Siren output level is 95 dB at three feet • AC powered with a rechargeable • Lowers labor costs and
12 hour battery backup saves time
•Transmits module status, including
mounting tamper, low battery and • Plugs in to any standard duplex • Simplifies installation
AC loss to the control panel receptacle and installs in seconds
• Compatible with LYNXR (Rev 10
• LED; show system status of the device • Provides temporal pulse sounding for or higher) and VISTA controls that
fire alarms support the 5883 transceiver
SPECIFICATIONS
• Dimensions: 4.5" W x 7.5" H x 2.25" D • Frequency of Operation: 345 MHz • Current: 202mA Typical
(114mm x 191 mm x 57mm)
• Input Voltage: 120VAC • Operational Temperature
• Output Level: 95 dB at three feet 32° F to 122° F(0°to 50°C)
ORDERING
5800WAVE Wireless Siren
Honeywell Security&Communications
Honeywell Hon���ll
2 Corporate Center Dr. Suite 100
P.O. Box 9040
Melville, NY 11747 vaaaowAV��
March 2008
www.honeywell.com oO 2008 Honeywe�l Internationa�Inc.
Honeywell
5808W3 _` ��,�-.-
PHOTOELECTRIC SMOKE/HEAT
DETECTOR WITH BUILT-IN � �
WIRELESS TRANSMITTER
�' � +►�
�
�
;� I
Honeywell's 5808W3 is a 3V lithium powered, Since there are no holes to drill or wires to run, you can
photoelectronic smoke/heat detector with a built-in preserve the beauty of the building while protecting it. The
wireless transmitter. It is intended for use with any 5808W3 is an ideal smoke detector for those difficult to wire
5800 Series Wireless Receiver/Transceiver for residential locations, applications where room aesthetics are critical, or
installations (for commercial installations, the 5881 ENHC where hazardous materials exist.
or the 5883H receiver is required).
All models also feature a restorable, built-in, fixed temperature
The transmitter can send alarm, tamper, maintenance(when (135°F)thermal detector that is also capable of sensing a
control panels are equipped to process maintenance signals), pre-freeze condition if the temperature is below 41°F.
and battery condition messages to the system's receiver.
Smoothing algorithms minimize nuisance alarms by
smoothing out short term spikes from dust and smoke—
virtually eliminating nuisance alarms.
FEATURES
• Improved Robust RF Field • Drift Compensation • Easy-to-install Mounting Base
Strength Virtually eliminates nuisance alarms The sturdy mounting base allows the
The distance between the detector from long-term dust build-up by detector to be more easily installed
and receiver has been significantly automatically adjusting the detector's on uneven surfaces (i.e. stucco). The
increased without the need for a sensitivity mounting base has larger mounting
repeater • Removable Detector Cover and ports, which accommodate drywall
• Smoothing Algorithms Chamber Top anchors for easy surface mounting.
Mathematical calculations in the The technician is able to quickly and
detector's software that minimize easily clean the detector chamber ADDITIONAL FEATURES:
nuisance alarms by smoothing out without disassembling the detector
short term spikes from dust and head • Utilizes one long-life 3V lithium
battery
smoke
• Approved UL Listings for Residential . Microcontroller runs on a 4.0 MHz
• Smart Check and Commercial Applications clock
A signal is sent to the control panel Both residential and commercial . Horn operates at 3.3 KHz with sound
when the detector requires cleaning. installation requirements are met pressure level of 85 dBA at 10 feet
This allows a regular, non-emergency
•Additional LED Status Indicators • Built-in wireless transmitter, temporal
service call to clean the detector ldentifying between alarm or trouble code 3 sounder
before it goes into alarm.
conditions is a snap with green and • Maintenance signal fully complies
red LED status indicators.A green LED with the sensitivity test requirement
denotes a normal condition while the specified in NFPA 72, 7-2.2 and is
red LED indicates abnormal conditions. approved by UL
5808W3
PHOTOELECTRIC SMOKE/HEAT DETECTOR WITH BUILT-IN WIRELESS TRANSMITTER
SPECIFICATIONS
• Dimensions •Air Velocity • Power Source
-Diameter: 5.3"", Height; 2.30" - 1,000 ft./min. max. -One 3V CR123A lithium Batteryt
•Weight • Operating Voltage •Audible Output
-8.5 ounces(without batteries) -2.5-3.6VDC -85 dB min. at 10 ft.
• Operating Temperature • Standby Current • Fixed Temperature Heat Sensor
-32-100° F(0-37.8° C) -8.5 mA avg. - 135° F Fixed
• Humidity Range •Alarm Current •Agency Listings
-0%to 95% RH, non-condensing -35 mA max. -UL268-Commercial and
Residential
*With adapter bracket(4.9"without mounting base)
tReplacement batteries include Duracell DL123A,Sanyo CR123A,Panasonic CR123A,or ADEMCO 466
ACCESSORIES(sold separately)
SENS-RDR Infrared RT Removal Tool
Sensitivity Reader -""'"�!� ;
�x5 Simplifies the attachment 2�; > �II�] -"
Reduce testing time with the , *� and removal of the �
handheld SENS-RDR infrared � detector head to the � . �"� '"„�
sensitivity reader. The reader I � mounting base; it may
simplifies sensitivity measurements be attached to a threaded `k • *
��� Y; �����a
and displays them precisely in extension pole or broom -
terms of percent per foot handle thereby eliminating �,
obscuration. The SENS-RDR the need for ladders. '
eliminates the need for magnets, _
voltmeters and ladders. ^� _ +: �
���ti� ' ------ '
--.�- ---—---_. _ �
ORDERING
5808W3 Photoelectric Smoke/Heat Detector with Built-in Wireless Transmitter
Accessories sold separately:
SENS-RDR Hand-held Sensitivity Reader
RT i3 Removal Tool used for easy installation and removal of head from base
Automation and Control Solutions
Honeywell Security&Communications HonG�Gl'
2 Corporate Center Dr. Suite 100
P.O. Box 9040
Melville, NY 11747 v5aoaws�sio
September 2008
www.honeywell.com OO 2008 Honeywell International Inc.
Honeywell
VISTA- 128BP SERIES � �� ' j -�
PARTITIONED COMMERCIAL BURGLARY ` �
ALARM CONTROL PANELS
� _
� 1
+� _ .���-rs�
The VISTA-128BPE is a powerful member of the Honeywell The VISTA-128BP and VISTA-128BPE(VISTA-128BP Rev.4)
family of commercial alarm panels, integrating burglary, CCTV are Listed for residential burglary, residential fire and commercial
and access control functions. Many features are available that burglary applications(see agency listings in this document for
extend the applications of the VISTA-128BP while simplifying more details). They are compatible with a wide range of
end-user operation. AlarmNet communications products for alarm reporting,
uploading/downloading and remote services.
FEATU RES
Standard features • Zone 7 may be used for keyswitch • Scheduled check-in
(VISTA-128BP and VISTA-128BPE): arming/disarming • Arm stay by group
• Provides nine style-B hardwired zones • Supports V-Plex°addressable
�staKe access control u to ei ht Enhanced features
• Supports up to 119 additional zones Y � p 9
using a built-in polling (V-Plex, doors and 250 cards) (V�STA-128BPE only):
multiplex)loop interface • Easily programmed and maintained ' Carbon monoxide(CO)zone
• Supports up to 127 wireless zones by Compass Windows-based type support
using up to two 5800 series wireless downloader • Expanded RS-232 capability
receivers (fewer if using hardwire • Supports up to 96 programmable for third party interface and
and/or polling loop zones) outputs automation
• Provides one power-limited bell circuit • Programmable to meet SIA false • Internet upload/download over
delivering 1.7Amp (max)at 12Vdc alarm prevention specifications. AlarmNet GSM, iGSM and IP
• Provides the ability to control eight To meet UL approval for ANSI/SIA communicators over the panel's
separate partitions independently, CP-01-2000 order part number keypad (ECP)bus
each functioning as if it had its own VISTA-128SIA • Ringback support for AlarmNet
separate control • Panel Linking up to eight panels communicators(confirmation of
• Accommodates 150 user codes with closing report)
• Supports eight numeric
seven authority levels pager numbers • 24-hour dialer test support for
AlarmNet devices
• Accommodates 32 keypad macro • Supports touchscreen Advanced
commands per system User Interface(AUI)
• Keeps a log of up to 512 events • Smoke detector reset at keypad
• vstavew-100 CCTV support - (�uick exit
• Supports up to 16 compatible two- • Group bypass
wire smoke detectors on zone 1 . Arm faulted
• Supports up to 50 latching-type . Event arming
glassbreak detectors on zone 8
Honeywell
VISTA- 128BP SERIES
PARTITIONED COMMERCIAL BURGLARY ALARM CONTROL PANELS
ADDITIONAL FEATURES
Basic Hardwired Zones • Tamper protection for supervised • A Master partition(9), used strictly to
Provides nine style-B hardwired zones transmitters assign keypads for the purpose of
with the following characteristics: • Individually assignable to one of viewing the status of all eight partitions
• EOLR supervision (optional for zones eight partitions at the same time(master keypads)
2-8)supporting N.O. or N.C. sensors Scheduling • All zones assignable to one of
EOLR su ervision re uired for fire eight partitions
� p q Provides the following scheduling
and UL burglary installations) capabilities: • Keypads assignable to one of eight
• Individuall assi nable to one of partitions or to Master partition 9 to
y g • Open/close schedules (for control of
eight partitions view system status
arming/disarming and reporting)
Pollin Loo Ex ansion • Ability to assign relays to one or all
g p p • Holiday schedules(allows different
Supports up to 119 additional zones time windows for open/close eight partitions
using a built-in polling (V-Plex, multiplex) schedules) • Ability to display fire and/or burglary
loo interface. Current draw can total and panic and/or trouble conditions
p • Timed events (for activation of relays, at all other partitions' keypads
up to 128mA. Polling loop zones have auto-bypassing and unbypassing,
the followin characteristics: (selectable option)
g auto-arming and disarming, etc.)
• Must use V-Plex devices � • Individually programmable account
Access schedules (for limiting system number, entry delay and exit delay by
• Supervised by control panel access to users by time) partition
• Individually assignable to one of • End user output programming mode
eight partitions (provides 20 timers for output control)
Wireless Expansion Eight Partitions
Supports up to 127 wireless zones Provides the ability to control eight
using up to two 5800 series wireless separate areas independently, each
receivers (fewer if using hardwire functioning as if it had its own separate
and/or polling loop zones). control. Partitioning features include:
Wireless zones have the following • A Common Lobby partition (1-8),
characteristics: which can be programmed to arm
• Supervised by control panel for automatically when the last partition
check-in signals (except certain that shares the common lobby is
non-supervised transmitters) armed, and to disarm when the first
partition that shares the common
lobby is disarmed
f-ry � -_ V-Plex Loop �__
_ � _-�.�� _ - � .�,..�,
FG1625SN Glassbreak 4208U Eight-zone 5193
4101SN DT7500SN Expansion Module and 4293SN Adapters Series Smoke Detectors
Relay Module V-Plex DUAL TEC 4208EX Eight-zone .
Motion Sensor V-Plex F�cpander
5881
ECP Bus Wireless
'� Receiver
,:_ -�
., ,._.. ,,...,�_. .. 6160 _
�. �" Console
710 .`��'.�..
Parallel Printer Light � VISTA-128BP
RS-232 �-��
Notifcation � 4204
.w. ... ; Relay
Appliances � Keyswitch py�Module
Serial Printer � � � �,�,. Option - �
�.,�.. � 4146 r ^
_ �
� �\ � , ���. Phone Line to Central Station
748
Horn
Alpha Paging -�-�:°, —o�— —��—
Module 7847i GSM iGSM
NOTE: Please refer to the website(www.honeywell.com/security/hsc)for the latest product information.
Honeywell
VISTA- 128BP SERIES
PARTITIONED COMMERCIAL BURGLARY ALARM CONTROL PANELS
ACCESSORIES
Auxiliary Devices • 5193SD Wireless Devices
• 4204- Relay Module, four form C • 5193SDT • 5804- Wireless Key
contacts Passive Infrared Detectors • 5804BD- Bidirectional Key
• 5881 Series- RF Receiver supporting , gggMX • 5804BDV- Bidirectional with voice
5800 wireless detectors
• 6160- Alpha Keypad/Annunciator • IS2500SN • 5816- Door/Window Transmitter
• 6220S- System Printer used with • DT7500SN • 5819- Shock Sensor
4100SM serial module • QUEST2260SN • 5827BD- Bidirectional Keypad
• VA8200- (PLM)Panel Linking Module V Plex(Addressable)Contacts • 5853- Glassbreak Detector
• VA8201 - (APM)Alpha Paging Module • 4939SN-WH • 5894 - Wireless PIR Motion Sensor
Manual Pull Stations • 4944SN-WH • 5890 - Passive Infrared Detection
• 5140MPS-1 • 4959SN, 9500SN • 5800PIR-OD- Outdoor
• 5140MPS-2 V-Plex Glassbreak Detectors Motion Sensor
V-Plex(addressable) Devices • FG1625SN • 5870API-Asset Protection Device
• 4101SN Single Relay/zone Module VISTA Interactive Phone Module ' 5800PIR/5800PIR-RES/5800PIR-
COM—Wireless Motion Detectors
• 4190SN Remote Point Module- • 4286 VIP Module • 580000/A- Wireless Carbon
two zones Optional Communicators Monoxide Detector
• 4193SN Two zone Serial Interface . AlarmNet Internet/Intranet • 5800RP- Wireless Repeater
Module communicators and digital cellular
• 4208EX- Eight zone expander for communicators • 5808W3 - Wireless Smoke Detector
ULC commercial installations Access Control • 5809- Wireless Heat Detector
• 4208U Loop Expansion Module- • VISTAKey V-Plex(addressable) Commercial Listed
eight zones Access Control Wireless Devices
• 4209U Group zoning Module- • VISTAKey-SK Starter Kit • 5817CB- Commercial UL Burglary,
two/four zones Universal Contact Monitoring
• 4293SN One zone Serial Interface • VISTAKey-EX F�cpansion Kit Transmitter�
Module • 5869- Commercial UL Wireless
• 4297 Isolation/Extender Module V-Plex CCTV Hold-up Button'
(addressable)smoke detectors • Optiflex CCTV module • 5881 ENHC and 5883H Receivers
• VSI Short/Overload Isolation Module "When used with 5881 ENHC and/or
5883H receiver.
� i - ,,�,w.`-==
R�F �� .�
—�- -- 4190SN 4959SN 4944SN �'
IS2500SN 4208U 4193SN Remote Point Module Overhead Door Contact Contact VISTAKey V-Plex
V-Plex PIR Eight-zone Serial Interface Module Access Control
Motion Sensor Expansion Module i 5808W3 Module
5881ENHC � Wireless GlassbreakDetectors ;s���-aj,�,. �
Commercial Wireless Receiver Smoke ���r • �
ECP Bus �nnaxTWO> oete�to� -_—� saoo � ��
Series 5890 i �tl�
� Wireless — �
_ ,r„ w 6160 SS16 ' Devices r . Wireless PIR
Console Door/Window � _
-- . Transmitter / I \ �� � 4209U
Group Zoning
k �� ,��. Module ,��,
5869
Commercial UL� � � Supports Up To I
4204 � Wireless Hold-up 5817CB Universal 16 Conventional -
_.- Rela ' 4204CF ��^ Two-Wire ��
Y �'"�� Su ervised Button Contact Monitoring Smoke Detectors
,_ �� Module �f � �' NAC Module Transmitter
i
� VISTA-126BP � VISTA-1286P
,a I . I
. � .�
i� � '
Panel Linking Module , - Panel Linking Module x���A--�+-<
VISTA- 128BP SERIES
PARTITIONED COMMERCIAL BURGLARY ALARM CONTROL PANELS
SPECIFICATIONS
Agency Listed to the Electrical Main Dialer
Following Standards: • Voltage Input: From Honeywell No. • Formats Supported: ADEMCO
• UL609 Grade A Local Mercantile 1361 Plug-In Transformer or Contact ID, ADEMCO High Speed,
Premises and Mercantile Safe 1361 X10 transformer(for X 10 ADEMCO 4 + 2 F�Cpress, ADEMCO
and Vault installations)rated 16.5VAC,40 VA Low Speed, Sescoa and Radionics
• UL611/UL1610 Grades A, AA • Use 1361CN plug-in transformer Low Speed
Central Station for Canada • Line Seize: Double Pole
• UL365 Grades A, AA Police Connect • Alarm Sounder Output: 10VDC- • Ringer Equivalence: 0.7B
• UL985 Household Fire 13.8VDC, 1.7 amps max., (UL1023, Cabinet Dimensions
• UL1023 Household Burglar Alarm UL609 installations); 750mA less aux. 12-1/2" W X 14 1/2" H X 3" D
California State Fire Marshall (CSFM) current draw (UL985 installations)
• UL1635- Digital Alarm • Auxiliary Power Output: 9.6VDC-
Communicator System Units 13.8VDC, 750mA max. For UL
installations, the accessories
• CAN/ULC- S303 connected to the output must be UL
• CAN/ULC- S304 Listed, and rated to operate in the
• CAN/ULC- S545 above voltage range
• CAN/ULC- S1023 • Backup Battery: 12VDC, 4AH or 7AH
sealed-lead acid. YUASA NP4-12
• For commercial burglary attack proof (12V, 4AH)or NP7-12 (12V, 7AH)
requirements, use VISTA-ULKT attack recommended
proof enclosure
• Standby Time: Four hours min. with
750mA aux. load using 7AH battery
• Circuit Protectors: PTC circuit
breakers are used on battery input to
protect against reverse battery
connections and on alarm sounder
output to protect against wiring faults
(shorts). A solid state circuit breaker
is used on auxiliary power output to
protect against wiring faults (shorts).
ORDERING
VISTA-128BP Commercial Burglary Alarm Control Panel (UL Listed)
VISTA-128BPE Enhanced Commercial Burglary Alarm Control Panel (ETL Listed as VISTA-1286P Rev. 4, UL Pending)
VISTA-128SIAE SIA Approved Enhanced Commercial Burglary Alarm Control Panel
For more information:
www.honeywell.com/security/hsc
Automation and Control Solutions
Honeywell Security&Communications
2 Corporate Center Dr. Suite 100 Honeywell
P.O. Box 9040
Melville, NY 11747
1.800.467.5875 L/VSTAI2SBPD/D
April 2010
www.honeywell.com =O 2010 Honeywell International Inc.
.Install2�tivn Instruction fvr Pt�wer Superv�sion �Ilo�u�e
� zo4-�v
�� ��
�
��, �.� �
�
- � - �.
� 4 3 1 t 4 3 2 1
lI1Nt �
1114 �
� � , � . � . �. - � 45�.0.EGIR�
.,..�.•�r... �. .
��
9�D C1f L�
�
� �,� �� �U4-12124V
� � ��► � �
� .-��,.�-� �-�^�'°�.--�-�. �''
- + i - +
A S 2 1 7' ;8 9 4 3 2 �
l�tlf . � `' F'pyVFJr
��* ,�. . � - � ' � �RW�90N
� . .. _ . (�ElEG1AX`r��t�CS,
.� .,� �..� �
�
�� ,. ., ... . .
.. . . . � . . . . � ��
'Q " �,� � ` �..� �a4-121�4V
�� ��� � � � �
� ;. �.�-, .�--� .�,.-��,
- + - + - f
� a 3 x � � e s a a x � r s e s x �
u�rt
�_ �
� , c� +�8sc�e�x a�s�
mw ' �
� _
��
�� ;: `::.
r i n� �� iF� i
Power 5uper�►isinn Llnit 2@4-6V Power 5uper�isian Wnit 2IM4»12P24V
Qpereting Vo�tage 5.i -15 V[7C �perating voltage 8.5-33 VQC
OQerating Current 33 vnA� B VDC;6�rnA � i2 VDC �}perating Curre�st 14 mA � 12 VC)C;28 mA Q 24 VDC
Gontact Rating(resistive) 2A �26 VpG pr 115 VAC Cpr�tact Rating (cesistiv^e) 2 A � 26 V❑C or 115 VAC
INSTAL�ATIDN ENST��ICTIS�L�$
�,Connect brown initiating leads as inc�ic�ats�such that fhe end of line 3.Neatly dress wires and power su�enrisi�n unit into
de►rice is carsn�tgd in s�nes with the pawer sup�ervis+ng oonta�t. jurrcti�rn taox.
{see wiring d'aagramJ 4.Mount detecfar acc4rding ta manufacturers installaticm
2.Connect appropnate controf leads as s�rown. Red ineorning and red instructions.
from module t�terminal 1. Black incciming and bla�c from modu�e to
terminel 2.
5entrol,Inc.
E S L ����H�u$��: �,��.��.,�m
i 23A5 SW Leveton[Jriva r.�pe ePearrcauone wirnou�naoica.
Tualatin,O�i 87062 U.S.8�C ana�a;8 0(I=5 A 7-2 5 5 6 W s�a 5�r a i,inc.
1�;;'�lR t3[3�3 E��?'�}F S E hF T�U l L N C 503-692-�f152 Technicab 5upport:8f)Q-84$-7424 �PNnted on�yd�ad pape. E�+o�e
7028�REV.B
•i, L V L
P R 0 D U C T I N F 0 R M A T I 0 N B U L L E T I N
� � .;.; . . 449 / 448 SERIES
,;;.,.:.
,. � f �f��' _ � �� Self-Diagnostic, Four-
��:f, _ . �
� � R�� ` � Wire, Photoelectric
���i�: _ � ,�
�{� .�:-v ��
,f,�,:�r
f,���.�� Smoke Detectors
fas: _
Model numbers:
449AT,449C,449CT,449CRT,449CST,449CSTE,
� , 449CSRT,449CSRH,449CTE
-•. -Y.,
� _.:.��;: :. �.�_.. : o L F M U LC
:� � LISTED APPROVED
_;f � .r
- -;;•r,��=r-� California State Fire Marshal Approved
MEA(New York City)Approved
ULC model numbers:
448AT,448C,448CT,448CST,448CSRH,448CTE
• Intelligent, self-diagnostics The ESL 449/448 Series self-diagnostic, four-wire
smoke detectors continually monitor their own
• On-site maintenance alert sensitivity and operational status, and provide a
visual trouble indication if they drift out of sensitivity
• Field replaceable optical chamber range orfail internal diagnostics. This unique,
• Low-p rof i l e d esi g n patented technology meets N FPA 72 field sensitivity
testing requirements without the need for external
• Plug-in terminal block meters.
Additional diagnostic information is activated by
• Advanced false alarm immunity applying a magnet near the detector's integral reed
switch. This initiates a self-diagnostic routine and
provides visual indication of sensitivity level, or if
service is required.
This series is easily cleaned by simply replacing
ESL's proprietary field-replaceable optical chamber. All
models are designed to reduce false alarms from
dust, insects, RFI, and external light.
An integral combination rate-of-rise and fixed
135°F (57°C), 50-foot rated, heat sensor is available
with all "T" model detectors (see selection guide),
allowing latching of the alarm for either smoke or
heat. The 449CSRH includes an isolated alarm
output for heat and activates an internal non-latching
sounder (local alarm) for smoke, making it ideal for
motel/hotel and dormitory rooms where smoking is
permitted.
continued
ESL 449 Series Sl�noke Detectors
Architectural and Engineering Specifications
The ESL 449 Series low-profile, self-diagnostic,four-wire The proprietary optical sensing chamber is field replaceable,
smoke detectors work on the light scattering principle.A allowing quick and easy cleaning and maintenance.
pulsed infrared light-emitting diode serves as the light source, Models with auxiliary relays are approved for releasing
and a high-speed photodiode as the sensing element. When service.
the amount of light reflected onto the photodiode reaches the This low profile product is equipped with a hinged cover, a
sensitivity setting,the smoke sampling rate increases. Three concealed tamper-resistant latch, and insect screens.
(3)successive smoke sensings above the sensitivity setting Wiring terminates in plug-in, clamp-type screw terminals.
are required to sound an alarm.This design has superior Detectors mount to a standard single-gang electrical box, a
protection against false alarms caused by dust, insects, RF four-inch octagonal,four-inch square electrical box, or
and ambient-light. WIREMOLD 5739 fixture box.
A confirmed alarm causes the normally flashing power Smoke Detector Spacing
indicator LED to light continuously and the alarm relay to On smooth ceilings(as defined in NFPA 72),spacing of 30 feet
operate. A trouble indication is automatically displayed by (g.1 meters)may be used as a guide. Other spacing may be used
flashing the LED every second. This meets NFPA 72 field depending on ceiling height,high air movement,and other
sensitivity testing requirements. An internal 85 dB horn conditions or response requirements.
(available in"S" models)emits a temporal 3 when the
detector alarms and a steady tone when power polarity is t
reversed.
,.85•�4���m,� 6.,•�,5.5�m) —
� I
1 �—0 —
Product Data
Sensitivit 3.1 - 1.0%/ft. max. -CST..........................................................................40mA
y................................................. ( )
3.1 +0.50%/ft. (min) -CSRT, CSRH, CSTE................................................51 mA
Operating temp. range ............... 32°F to 120°F(0°C to 50°C) Typical avg. polarity reverse current
Operating humidity range....................................0 to 95% RH -CST, CSRT, CSTE, and CSRH................................10mA
Minimum voltage-C, CT, CRT, CST, CSRT, CSRH , Sounder specifications.........................................85 dB at 10'
-CSTE.........................................................................8.5V Heat detector specifications
-AT..............................................................................5.1V -fixed temperature ..................................... 135°F(57.2°C)
Maximum voltage-C, CT, CRT, CST, CSRT, CSRH, -rate of rise .... 15°F/min. &>105°F(8.3°C/min. &>40.6°C)
-CSTE...........................................................................33V Auxiliary relay contacts 2A @ 28 VDC or 120 VAC (resistive)
-AT................................................................................27V Alarm contacts ........................ 500 mA @ 36 VDC(resistive)
Maximum ripple(peak to peak)........................................ 10% Field wiring size.................................................. 14-24 AWG
Typical average standby current.....................................70aA Packaging .......................10 detectors are packed in a carton
-CSTE........................................................................23mA Color....................................................white cover/white base
Typical alarm current-C, CT and AT ............................ 15mA with UV inhibitor to prevent yellowing
-CRT..........................................................................31 mA Listin UL 268, ULC FM, CSFM and MEA
g..............................
Selection Guide
Designator Feature Description
H Isolated Fixed Temp. Isolated fixed 135°F(57°C)and rate of rise heat detector,independently trips the LED and
alarm and Rate of Rise output.Smoke detector activates intemal sounder(local alarm)and auxiliary relay,but
Heat Detector does not latch.Approved as both single station smoke alarm and system heat detector.
Ideal for hotel,motel and dormitory rooms where smoking is allowed.
R Auxiliary Relay Used to activate other devices such as elevator recall,door holders,strobes,etc.Listed for
releasing service.
S Built-in Sounder 85dB built-in sounder alarms when smoke is detected or when power wiring polarity is
reversed.
T Intergrated Fixed Intergrated Fixed 135°F(57°C)temperature and rate of rise heat detector.
Temp.and Rate of Either heat detector or smoke detector can trip and latch LED and alarm protection.
Rise Heat Detector relay outputs.
E Built-in end of line Relay is normally energized and will trip with loss of power.Can also provide notification
power supervision relay when detector needs maintenance.
in t e r I o g i►i•.. PH�3.692.�5Z ��,������x.���
US4 8 Canada: 800.547.2556 Irnerlogix,Cadd�c,H,lil and�trol aretraAmiarksof
Technical Service: 800.6487424 FaxBack:800.4832495 irnenogix,inc
w�vw.sentrd.wrn www.ir�eaiogi�csearity.mm
E-3965 Rev B-1101
Stevinson Residence
4253 Spruce Way#B,Vail CO 81657
BUILDING CLASSIFICATIONS AND CODES
OCCUPANCY GROUP: R USE: Duplex
STORIES: 3 Story
SQUARE FOOTAGE: 2302
SPRINKLERED: No
APPLICABLE CODES: 2010 NFPA72 2009 I.F.0
2011 N.E.C. VAIL FIRE AMENDMENTS
2009 I.B.0
SYSTEM WIRING TYPES:
INITIATING DEVICE CIRCUIT: Wireless (RF)
NOTIFICATION CIRCUIT: Class B (Hardwired) &Wireless
SIGNALING LINE CIRCUIT: Class B (addressable)
SYSTEM TYPE:
SUPERVISING STATION TYPE: Central
AUDIBLE NOTIFICATION: Temporal
VISUAL NOTIFICATION: Private
Monitoring Method and Monitoring Agency
Method: Land Line
Agency: Central Security, Greeley Colorado
DESIGN STATEMENT
THIS PROJECT'S DESIGN IS FROM THE ENGINEERED PLANS AND SPECIFICATIONS
PREPARED BY:
ARCHITECTURAL PLANS DATED: 03/22/2012
MECHANICAL PLANS DATED: 03/22/2012
ELECTRICAL PLANS DATED: 03/22/2012
SPECIFICATIONS DATED: 03/22/2012
ADDENDUMS DATED: N/A
�`� SYSTEM _ -: � . � - _ _
��� SENSOR° �_ ;� , �::
;� �
.. * *
C01224T
Carbon Monoxide � �
Detector �
,
�
with RealTestTmTechnology A ,�„_ _
��.Y�� � �
The System Sensor C01224T CO detector provides early = _ . �� �,�:
warning by using electrochemical sensing technology
to measure carbon monoxide levels in the air.
Features With RealTest`"technology,the CO gas sensing cell of the
•RealTest�"technology allows installer to test detector with CO gas C01224T CO detector can be tested using a carbon monoxide gas
agent Simply hold the test button for two seconds.After the alarm
•Full compliance with UL 2075 cyde(temp 4)the green LED will flash about once per second,
•A code required trouble relay indicating that the detector is ready to accept CO for testing.
•Wiring supervision with SEMS terminals Spray a small amount of CO into the detector per the installation
instructions,and within seconds the detector will alarm,indicating
•A six year end-of-life timer successful gas entry.
•12/24 VDC
•A current draw of 20mA in standby and 40mA in alarm If dangerous amounts of carbon monoxide is detected,the C01224T
detector will alert residents by sounding and flashing a temp-4 signal
•Versatile mounting for wall and ceiling alarm.Protection is guaranteed 24/7 by a central station,regardless
•Electrochemical sensing technology of whether residents are away from home,sleeping or already
suffering from the efFects of C0.
This specific device is designed for system operation.The detector is
fully listed to UL 2075.It offers a code required trouble relay to send
a sensor failure or end-of-life signal to the control panel and the
central station.It also uses SEMS-type terminal Philips head screws
to provide a quicker and more positive wiring connection and code
required wiring supervision.The C01224T detector offers a low
current draw,allowing more devices to be connected to the panel
without having to purchase a more expensive panel or an extra
power supply.
The C01224T model will operate on most industry security and fire
Agency Listings alarm control panels because it is is a 12/24VDC detector.
U`
LISTED
�o�s
C01224T Carbon Monoxide Detector Specifications
Carbon monoxide detector shall be a System Sensor model number C01224T,listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and
Sensors.The detector shall be equipped with a sounder and a trouble relay.The detector's base shall be able to mount to a single-gang electrical box or direct
(surface)mount to the wall or ceiling.Wiring connections shall be made by means of SEMS screws.The detector shall provide dual color LED indication,which
blinks to indicate normal standby,alarm,or end-of-Iife.When the sensor supervision is in a trouble condition,the detector shall send a trouble signal to the
panel.When the detector gives a trouble or end-of-life signal,the detector shall be replaced.The detector shall provide a means to test CO gas entry into the CO
sensing cell.The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.
Operating Voltage 12/24 VDC
Audible Signal 85 dB in alarm
Standby Current 20 mA
Alarm Current 40 mA(75 mA test)
Alarm Contact Ratings 0.5 A@ 30 VDC
Trouble Contact Ratings 0.5 A@ 30 VDC
Size Length:5.1 in,Width: 33 in,Height:13 in
Approximate Weight 7 oz
Operating Temperature Range 32°F to 104°F(0°C to 40°C)
Operating Humidity Range 22 to 90%RH
InputTerminals 14 to 22 AWG
Mounting Single gang back box;surface mount to wall or ceiling
Operation Modes
.. - � - �
Normal(standby) Blink 1 per minute — —
Alarm — Blink in temp 4 pattem Sound in temp 4 pattern
RealTest""Feature: The System Sensor C01�24T carbon monoxide detector with RealTest` can evaluate the functionality of the CO sensing cell using
canned tcst agent.
- . . <�
_ �� �_ \
^ • • � �- i�� r � I�
� �:
� �
Push and hold theTest/Hush button for Spray canned CO agent Into the detector. Verify CO sensing at the control panel.The
two seconds to enter RealTest mode.The detector will automatically exit RealTest
green LED will flash once every second to alarm mode after about 20 60 seconds.
indicate RealTest mode has started.
NOTE:Check with local codes and the AHJ to determine whether or not a functional gas test is desired for an Installation.
Hush Feature: Pushing theTest/Hush button will silence the sounder for S minutes(except in RealTest mode).
Trouble Feature: When the detector is in a trouble condition,it will send a trouble signal to the panel.
End of IifeTimer: After the detector's internal sensor has reached the end of its life,a trouble signal will be sent to the panel.This will indicate that it is
time to replace the detector.An electrochemical carbon monoxide detector lifespan is approximately six years,and the detector must
be replaced by the date marked on the inside of the product.
Ordering Information
�-
C01224T 12/24 volt,4 wire system monitored carbon monoxide detector with RealTest""Technology
�� SYSTEM ozoo8 sy,em sen=o�.
w, 3825�h10 f�V2YlUe•St.�{ldY�eS,��6�174 ?roductspe6�ca�onssub�rcttorn gcwithoutnotrce.uis�sysremsensor.comfor
�' �l' SE/�/SOR Ph0112:8��-SENS�RZ•FdX:63�-3��-6495 cwren[producUnfom�ation,lndudingehelacestversionofthlsdatasheet.
� A05-0437-000•8/OS•H1953
• • � � •
. � � . .
. � 1 � �
Models Available
Single-circuit Models �:�R�
5601P 135°F Fixed Temperature / Rate-of-Rise .'w � .. .
5602 194°F Fixed Temperature / Rate-of-Rise
5603 135°F Fixed Temperature
i
5604 194°F Fixed Temperature
�
� `
Dual-circuit Models � �`° a
5621 135°F Fixed Temperature / Rate-of-Rise — �.g'`} , ,
5622 194°F Fixed Temperature / Rate-of-Rise
5623 135°F Fixed Temperature + �� �" ;.�:, ;-�-
��
5624 194°F Fixed Temperature "''��'''"'�
. � •
Product Overview
Multiple configurations available to System Sensor's 5600 series mechanical heat detectors offer a low-cost means for
satisfy a broad range of installations: property protection against fire, and for non-life-safety installations where smoke
• Single-and dual-circuit models detectors are inappropriate.
• Fixed temp and combination
fixed-temp/rate-of-rise Multiple configurations. The 5600 series offers a full-line of configurations to
• 135°F or 194°F ratings. accommodate a broad range of applications. Both single- and dual-circuit mod-
els are offered, each available for low- and high-temperature ratings with either
Plain housing available for residential fixed temperature or combination fixed temperature/rate-of-rise (ROR) activa-
installations (model 5601P) tion. The ROR element of the fixed/ROR models is restorable, to
accommodate field-testing tihe unit.
Easy to use terminal screws that provide
a more positive wiring connection Installation flexibility. To satisfy a variety of installations, the 5600 series
A broader range of back box easily mounts to single-gang and octagonal back boxes. These models also
mounting options: accommodate four-square back boxes, when used with a square to round
• Single gang plaster ring. The mounting bracket is reversible to allow for flush- and
• 3.5" and 4" Octagonal surface-mount back box installations.
• 4" square with square to round
plaster ring Visual identification. The 5600 series provides clear markings on the exterior
of the unit to ensure that the proper detector is being used. Alphanumeric
Reversible mounting bracket for characters identify the activation method, as well as the temperature rating, in
flush and surface mount installations degrees Fahrenheit and Celsius. Fixed temperature models are identified "FX",
while combination fixed/rate-of-rise units are marked "FX/ROR". The 5600
series also provides a post-activation indicator in the form of a collector. Once
the detectar has been activated, the collector drops from the unit, to easily
identify the specific unit in alarm.
O ��
FM MEA � � �
�` ��.��
LISTED APPROVED approved �RV�`�
52101 3016008 199-03-E 7270-1209227
Engineering Specification
Mechanical heat detector shall be a System Sensor 5600 series model number ,listed to Underwriters Laboratories UL 521
for Heat Detectors for Fire Protective Signaling Systems. The detector shall be either a single-circuit or a dual-circuit rype, normally
open. The detector shall be rated for activation at either 135°F (57°C) or 194°F (90°C), and shall activate by means of a fixed tem-
perature thermal sensor, or a combination fixed temperature/rate-of-rise thermal sensor. The rate-of-rise element shall be activated by a
rapid rise in temperature, approximately 15°F (8.3°C) per minute. The detector shall include a reversible mounting bracket for mount-
ing to 3%z-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a square to round plaster ring. Wiring connec-
tions shall be made by means of SEMS screws that shall accommodate 14-22AWG wire. The detector shal] contain alphanumeric
maekings on the exteriar of the housing to identify its temperature rating and activation method. The rate-of-rise element of combina-
tion fixed temperature/rate-of-rise models shall be restorable, to allow for field-testing. The detectors shall indude an eXternal collector
that shall drop upon activation to identify the unit in alarm.
Electrical Specifications
Operating Voltage/ Contact Ratings
6—125VAC/ 3A
6—28VDC/ 1A
125VDC / 0.3A
250VDC / 0.1A
Physical Specifications
Maximum Installation Temperature Alarm Temperature Rate-of-Rise Threshold
5601P, 5603, 5621, and 5623: 100°F(38°C) 5601P, 5603, 5621, and 5623: 135°F(57°C) 15°F(8.3°C) rise per minute
5602, 5604, 5622, and 5624: 150°F(65.6°C) 5602, 5604, 5622, and 5624: 194°F(90°C) (models 5601P, 5602, 5621, and 5622 only)
Operating Humidity Range Input Tenninals Mounting
5 to 95%RH non-condensing 14-22 AWG 31fz-inch octagonal back box
4-inch octagonal back box
Dimensions with mounting bracket Single gang back box
Diameter: 4.57 inches(11.6cm) Weight 4-inch square back box with a square to round
Height: 1.69 inches(4.3cm) 6 oz. (170 grams) plaster ring
Ordering Information
Identification Method Temperature
Model Circuit on Exterior Rating Activation UL Protected Spacing—10 Foot Ceiling*
5601P Single None 135°F(57°C) Fixed Temperature/ Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m)
5602 Single Lettering 194°F(90°C) Fixed Temperature/ Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m)
5603 Single Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5604 Single Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5621 Dual Lettering 135°F(57°C) Fixed Temperature/ Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m)
5622 Dual Lettering 194°F(90°C) Fixed Temperature/ Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m)
5623 Dual Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5624 Dual Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
*NOTE:Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.
noai� xi xi aoaixa
O O O O O
4° ! °Fi � ° ; � �
�
5601P 5602,5622 5603,5623 5604,5624 5621
System Sensor Sales and Service
System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor—Far East System Sensor—India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.8832.0119 Ph: 85.22.191.9003 Ph:91.124.237.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx:86.29.8832.5119 Fx:85.22.736.6580 Fx: 91.124.237.3118
Ph: 800/SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor—Australia System Sensor—Russia
Fx: 630/377-6495 ph: 44.1403.891920 Ph: 65.6273.2230 Ph: 613.54.281.142 Ph: 70.95.937.7982
www.systemsensor.com Fx:44.1403.891921 Fx: 65.6273.2610 Fx:613.54.281.172 Fx: 70.95.937.7983
OO 2005 System Sensor.The company reserves the right to change product specifications without notice. A05-0351-001•3/05•#1402