Loading...
HomeMy WebLinkAboutF13-0030 cut sheets Fire Sprinkler System Material Data Sheets For Lionshead Centre 208/308 Expansion 520 E. Lionshead Circle Vail, CO 81657 Prepared by: Jason Brochu Project Manager Designer Western States Fire Protection Co. 7026 S. Tucson Way Centennial, CO 80112 Cell: (303) 928-0192 Office: (970) 618-3294 Fax: (970) 945-9504 Email: jason.brochu@wsfp.us WSFP# CS2046 September 3, 2013 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bu l l e t i n 1 7 6 Re v . B Bulletin 176 Rev. B Model F1 Residential Sprinklers for Design Density of .10 gpm/ft2 Model F1 Res Sprinklers Listed to meet the minimum design density as required by UL1626. Types: 1. F1 Res 30 Pendent 2. F1 Res 30 Recessed/F2 3. F1 Res 30 Recessed/FP 4. F1 Res 30 CCP Pendent 5. F1 Res 49 Pendent 6. F1 Res 49 Recessed Pendent/F1 7. F1 Res 49 Recessed Pendent/FP 8. F1 Res 49 CCP Pendent 9. F1 Res 58 Pendent 10. F1 Res 58 Recessed Pendent/F1 11. F1 Res 58 Recessed Pendent/FP 12. F1 Res 58 CCP Pendent 13. F1 Res 44 & 58 HSW 14. F1 Res 44 & 58 HSW Recessed HSW/F2 15. F1 Res 58 HSWX 16. KRes58 HSWX 17. F1 Res 44 SWC 18. F1 Res 76 Pendent 19. F1 Res 76 Recessed Pendent/F1 20. F1 Res 76 Recessed Pendent/FP 21. F1 Res 76 CCP Pendent F1 Res 30, 49, 58 & 76 Recessed Pendent/F1 The 3mm glass-bulb pendent sprinklers permit the ef- ficient use of residential water supplies for sprinkler cover- age in residential fire protection design. Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the water- way for water flow onto the deflector, evenly distributing the discharged water to control a fire. Technical Data: • Thermal Sensor: Nominal 3mm glass-bulb • Sprinkler Frame : Brass Casting • Sprinklers’ Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi • Thread Size: ½” NPT (R1/2) • K-Factor: 3.0 (Actual) - F1 Res 30 Pendent Sprinkler 4.9 (Actual) - F1 Res 49 Pendent Sprinkler 5.8 (Actual) - F1 Res 58 Pendent & HSW/HSWX Sprinkler 7.6 (Actual) - F1 Res 76 Pendent Sprinkler 4.4 (Actual) - F1 Res 44 HSW Sprinkler • Density: Minimum 0.10 gpm/ft2 F1 Res 30, 49, 58 & 76 Recessed Pendent/FP F1 Res 30, 49, 58 & 76 CCP Pendent F1 Res 44 & 58 Recessed HSW/F2Listings & Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents US Patent No. 6,516,893 applies to the Model F1 Res 49 & 58 Pendent Sprinklers US Patent No. 7,353,882 applies to Model F1 Res 44 & 58 HSW Sprinklers US Patent No. 7,784,555 applies to Model F1 Res 44 SWC Sprinkler Patent Pending - Model F1 Res 76 Pendent Sprinkler Product Description Model F1Res Pendent sprinklers (Figs. 1, 2, 3 & 4) combine excellent durability, high sensitivity glass-bulb and low profile decorative design. F1 Res 44 SWC F1 Res 58 HSWX 2. Application Model F1 Res Sprinklers are used for Residential Fire Pro- tection according to UL 1626 Standard. Be sure that orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of The National Fire Protection Association or the approving authority having jurisdiction. When using F1 Residential Sprinklers for systems design to NFPA 13D or NFPA 13R, use listed area of coverage and minimum flow and pressure requirements shown in Bulletin 135. For systems designed to NFPA 13, use information in this bulletin. The number of design sprinklers shall be the most hydraulically demanding sprinklers as required by NFPA 13. Flows and pressures can not be below the baseline flows and pressurers. NFPA 13 For residential sprinkler systems designed to NFPA 13, a minimum density of 0.1 gpm/ft2 must be provided over the “design area” that includes the four (4) hydraulically most demanding sprinklers for the actual coverage areas being protected by the 4 sprinklers. The minimum required dis- charge from each of the four most hydraulically demanding sprinklers shall be the greater of the following: 1. The flow rates given in the Reliable Residential Sprinkler Technical Bulletins referenced in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area (for actual coverage areas less than or between those indicated in the respective technical bulletin, it is re- quired to use the minimum required flow for the next largest coverage area); or 2. A minimum discharge density of 0.1 gpm/ft2 applied over the “design area” consisting of the four most hy- draulically demanding sprinklers for the actual cov- erage areas being protected by the four sprinklers. The maximum dimension of the actual coverage area cannot be any greater than the maximum coverage area indicated in the technical bulletins referenced in Table A. Design Note: Using the As = S x L method to deter- mine the sprinkler protection area of coverage in ac- cordance with NFPA 13, apply the 0.1 gpm/ft2 density to this area to determine the minimum required flow. Compare this flow to the minimum 0.05 gpm/ft2 cU- Lus Listed flow for the appropriate coverage area in the technical bulletin for the specific residential sprin- kler. If the flow stated in the technical bulletin is less than the calculated 0.1 gpm/ft2 density flow required, the .1 density flow must then be used in the equation Q=K, solving for P, to establish the minimum required pressure using the sprinkler K-factor. Note: In many cases the listed flow of individual residential sprin- klers may exceed the required minimum 0.05 gpm/ft2 density. Reliable has available residential sprinklers with larger K-factors (K=5.8 and K=7.6) that will pro- vide lower pressure demands for 0.1 gpm/ft2 densi- ties in NFPA 13 residential applications. Example No. 1 Room Size= 12 ft x 20 ft (3.6 m x 6.1 m) Coverage Area= 12 x 20 = 240 ft2 (22.3 m2) Flow @ 0.10 gpm/ft2 density= 240 x 0.10 = 24 gpm Using an F1 Res 49 Pendent Sprinkler, K=4.9 Pressure= (24/4.9)2 = 24 psi (1.65 bar) The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m) cover- age area using the baseline density of 0.05 gpm/ft2 will be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 bar). There- fore, the minimum flow required is 24 gpm @ 24 psi (90.8 L/min @ 1.65 bar). Example No. 2 Room Size= 8 ft x 20 ft (2.4 m x 6.1 m) Coverage Area= 8 x 20 = 160 ft2 (14.9 m2) Flow @ 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm Using an F1 Res 49 Pendent Sprinkler, K=4.9 Pressure= (16/4.9)2 = 10.7 psi (0.74 bar) The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m) cover- age area using the baseline density of 0.05 gpm/ft2 will be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 bar). Therefore, the minimum flow required is 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 bar). Example No. 3 Room Size= 10 ft x 16 ft (3.0 m x 4.91 m) Coverage Area= 10 x 16 = 160 ft2 (14.9 m2) Flow @ 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm Using an F1 Res 76 Pendent Sprinkler, K=7.6 The baseline flow for a 16 ft x 16 ft coverage area is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Therefore, the minimum flow and pressure is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Example No. 4 Room Size= 14 ft x 18 ft (4.3 m x 5.5 m) Coverage Area= 14 x 18 = 252 ft2 (23.6 m2) Flow @ 0.10 gpm/ft2 density= 252 x 0.10 = 25.2 gpm (94.6 L/min) Using an F1 Res 76 Pendent Sprinkler, K=7.6 Pressure= (252/7.6)2 = 11 psi (0.76 bar) The baseline flow and pressure of an 18 ft x 18 ft cover- age area is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Therefore, the minimum flow and pressure is 25.2 gpm @ 11 psi (94.6 L/min @ 0.76 bar). In general residential sprinklers require fl ows and pressures as listed for 0.05 densities to achieve the proper spray pattern so the fl ows and pressures at 0.05 density are the baseline fl ows and pressures. Flows and pressures below the listed 0.05 density shall not be used. 3. Installation Models F1 Res sprinklers are to be installed as shown. Model F1, F2 and FP Escutcheons, illustrated herewith, are the only recessed escutcheons to be used with Mod- el F1 Res sprinklers. Use of any other recessed escutch- eon will void all approvals and warranties. For installing Model F1 Res Pendent sprinklers use only the Model D sprinkler Wrench; for installing Models F1 Res Recessed Pendent, CCP sprinklers use only the Model GFR2 sprin- kler wrench; for installing Model F1 Res recessed HSW sprinklers use only the Model GFR2 Sprinkler wrench. Use of wrenches other than those specified may dam- age these sprinklers. Note: A ‘leak tight” sprinkler joint can be obtained with the following torque: • 3/4” NPT (R3/4) – 14-20 ft-lbs (19 - 27.1 N-m) • ½” NPT (R1/2) – 8-18 ft-lbs (10.8 – 24.4 N-m) Do not tighten sprinklers over maximum recom- mended torque. It may cause leakage or impairment of the sprinklers. F1 escutcheon, 3/4” (19mm) adjustment • Model F1 Res 30, 49, 58 & 76 Pendent • Model F1 Res 30, 49, 58 & 76 Recessed Pendent / F1/F2 Note: See escutcheon table for dimensions. Fig. 1 Fig. 2 **Baseline fl ows and pressures for 0.05 density Defl ector - to - ceiling Maximum 1” (25mm) to 4” (100mm) Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)13 (49) 7.0 (0.48) R3516 14 x 14 (4.3x4.3)13 (49) 7.0 (0.48) 16 x 16 (4.9x4.9)13 (49) 7.0 (0.48) 18 x 18 (5.5x5.5) 17 (64.3)12.0 (0.83) 20 x 20 (6.1x6.1) 20 (75.7)16.7 (1.14) 4. Technical Data: F1 Res 49 Pendent and Recessed Pendent Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm)°F°C°F°C 1/2” NPT (R1/2)7/16” (11)155 175 68 79 175 (12)100 150 38 66 4.92.25 (57) Escutcheon*, F1 or F2, Data: Type Adjustment Inch (mm) “A” Inch (mm) Face of fi tting to ceiling Inch (mm) F1 3/4” (19.0)Min.= 3/4 (19.1) Max.=11/2 (38.1) 3/16 - 15/16 (4.7 - 24.0) F2 1/2” (12.7)Min.= 15/16 (23.8) Max.=11/2 (38.1) 3/16 - 11/16 (4.7 - 17.4) * Note: Escutcheons F1 or F2 may be used with Model F1 Res 49 & 58 Recessed Pendent Sprinkler *Defl ector - to - ceiling Maximum 4” (100mm) to 8” (203mm) Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)15 (57) 9.4 (0.65) R3516 14 x 14 (4.3x4.3) 16 (60.5) 10.6 (0.73) 16 x 16 (4.9x4.9) 17 (64.3) 12.0 (0.83) 18 x 18 (5.5x5.5)19 (72)15.0 (1.0) 20 x 20 (6.1x6.1) 22 (83.2) 20.2 (1.4) *Note: The F1 Res 49 pendent and recessed pendent residential sprinklers can be installed per NFPA 13 in beamed ceilings meeting the following criteria: 1. Maximum beam depth = 7” (178mm) 2. Beam spacing at or greater than 7.5 ft. (2.3m) on center. Technical Data: F1 Res 58 Pendent and Recessed Pendent Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm) °F°C°F°C ½” NPT (R½)½” (13)155 175 68 79 175 (12)100 150 38 66 5.82.25 (57) **Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Ceiling -to-Defl ector Inch (mm) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)16 (61) 7.6 (0.53) 1-4 (25-100)R3513 14 x 14 (4.3x4.3)16 (61) 7.6 (0.53) 16 x 16 (4.9x4.9)16 (61) 7.6 (0.53) 18 x 18 (5.5x5.5)19 (72) 10.8 (0.75) 20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0) **Calculate for a .10 density but in no case go below the baseline flows & pressures Technical Data: F1Res 30 Pendent and Recessed Pendent (SIN R3511) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm)°F°C°F°C ½” NPT (R½)21/64” (8.2)175 (12)155 175 68 79 100383.02.25 (57) **Baseline fl ows and pressures for 0.05 density Max. Coverage area Ft x Ft (m x m) Max. Spac- ing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rat- ing (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/ min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6)12 (3,6)8 (30,3)7.0 (0,48)8 (30,3)7.0 (0,48)1 to 4 (25 to 100); ½ recessed using F2 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3)14 (4,3)10 (37,8)11 (0,76)10 (37,8)11 (0,76) For Ceiling types refer to NFPA 13, 13R or 13D **Calculate for a .10 density but in no case go below the baseline flows & pressures 5. Technical Data: F1 Res 76 Pendent and Recessed Pendent Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm)°F°C°F°C 3/4” NPT (R3/4)17/32 (13.5)155 175 68 79 175 (12)100 150 38 66 7.62.25 (57) Escutcheon*, F1 or F2, Data: Type Adjustment Inch (mm) “A” Inch (mm) Face of fi tting to ceiling Inch (mm) F1 3/4 (19.0)Min.= 3/4 (19.1) Max.=11/2 (38.1)3/16 - 15/16 (4.7 - 24.0) F2 1/2 (12.7)Min.= 15/16 (23.8) Max.=11/2 (38.1)3/16 - 11/16 (4.7 - 17.4) *Calculate for a .10 density but in no case go below the baseline flows & pressures *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)217.6 (0.53) R7618 14 x 14 (4.3x4.3)217.6 (0.53) 16 x 16 (4.9x4.9)217.6 (0.53) 18 x 18 (5.5x5.5)217.6 (0.53) 20 x 20 (6.1x6.1)239.2 (0.63) • Model F1 Res 30, 49, 58 & 76 Recessed Pendent / FP • Model F1 Res 30, 49, 58 & 76 CCP Pendent Fig. 3 Fig. 4 NOTE: The F1 Res 76 will use a 1” x ¾” reducer. FP push-on/thread-off escutcheon 6. Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent / FP Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pres- sure psi (bar) Max. Ambi- ent Temp. K Factor Sprinkler Length Inch (mm)°F°C°F°C°F°C ½” NPT (R½)7/16” (11)1556813557175 (12)100384.92.25 (57) CCP Options Data: “A” Cover Adjustment Inch (mm) “B” CCP Height Inch (mm) 1/2 (12.7)15/16 (24) 3/16 (4.7)3/4 (19) *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)13 (49) 7.0 (0.48) R3516 14 x 14 (4.3x4.3)13 (49) 7.0 (0.48) 16 x 16 (4.9x4.9)14 (53) 8.2 (0.56) 18 x 18 (5.5x5.5) 18 (68.1)13.5 (0.93) 20 x 20 (6.1x6.1) 20 (75.7)16.7 (1.14) FP Data “A”: FP Position “A” Inch (mm) Max. Recessed 7/16 (11) Min. Recessed 15/16 (24) Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for in- stallation in ceilings which have positive pressure in the space above. Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F°C°F°C°F°C ½” NPT (R½)½ (13)1556813557175 (12)100385.82.25 (57) *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)16 (61) 7.6 (0.53) R3513 14 x 14 (4.3x4.3)16 (61) 7.6 (0.53) 16 x 16 (4.9x4.9)16 (61) 7.6 (0.53) 18 x 18 (5.5x5.5)19 (72)10.8 (0.75) 20 x 20 (6.1x6.1) 22 (83.3)14.4 (1.0) *Calculate for a .10 density but in no case go below the baseline flows & pressures Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) CCP Assembly Temp. Rating Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F°C°F°C ½” NPT (R½)21/64” (8.2)175 (12)13557100383.02.25 (57) *Baseline fl ows and pressures for 0.05 density Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6)12 (3,6)8 (30,3)7.0 (0,48)1 to 4 (25 to 100); ½ (13mm) recessed using FP escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3)14 (4,3)11 (37,8)13.4 (0,92) For Ceiling types refer to NFPA 13, 13R or 13D *Calculate for a .10 density but in no case go below the baseline flows & pressures 7. *Calculate for a .10 density but in no case go below the baseline flows & pressures F1 Res 44 & 58 Recessed HSW/F2 • Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58 Recessed HSW/F2 Technical Data: F1 Res 44 HSW & HSW/F2 Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm)°F°C°F°C ½” NPT (R½)3/8 (10)155 175 68 79 175 (12)100 150 38 66 4.42.45 (62) Escutcheon, F2, Data: Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F21/2 (13)3/16 - 11/16 (4.7 - 17.4) *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) “A” Ceiling -to- Defl ector Inch (mm) Sprinkler Temp. Rating °F (°C) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6) 4 - 6 (101-152) 155 (68)175 (79)12 (45.4)7.5 (0.52) R3531 14 x 14 (4.3x4.3)155 (68)175 (79)14 (53.0)10.2 (0.71) 16 x 16 (4.9x4.9)155 (68)175 (79)16 (60.6)13.3 (0.92) 16 x 18 (4.9x5.5)155 (68)175 (79)18 (68.1)16.8 (1.16) 18 x 18 (5.5x5.5)155 (68)175 (79)19 (72.0)18.7 (1.29) 16 x 20 (4.9x6.1)155 (68)175 (79)23 (87.1)27.4 (1.89) 12 x 12 (3.6x3.6) 6 - 12 (152-305) 155 (68)175 (79)14 (53.0)10.2 (0.71) 14 x 14 (4.3x4.3)155 (68)175 (79)16 (60.6)13.3 (0.92) 16 x 16 (4.9x4.9)155 (68)175 (79)17 (64.4)15.0 (1.04) 16 x 18 (4.9x5.5)155 (68)175 (79)20 (75.7)20.7 (1.43) 16 x 20 (4.9x6.1)155 (68)175 (79)23 (87.1)27.4 (1.89) *Calculate for a .10 density but in no case go below the baseline flows & pressures Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F°C°F°C°F°C ¾” NPT (R3/4)17/32” (13.5)155 175 68 79 13557175 (12)100 150 38 66 7.62.25 (57) *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6)217.6 (0.53) R7618 14 x 14 (4.3x4.3)217.6 (0.53) 16 x 16 (4.9x4.9)217.6 (0.53) 18 x 18 (5.5x5.5)228.4 (0.58) 20 x 20 (6.1x6.1)2510.8 (0.74) 8. Technical Data: F1 Res 44 SWC Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating Cover Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) °F°C°F°C°F°C ½” NPT (R½)3/8 (10)1556813557175 (12)100384.42.45 (62) *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) “A” Ceiling -to- Defl ector Inch (mm) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6) 4 - 6 (101-152) 13 (49.2)8.7 (0.60) R3531 14 x 14 (4.3x4.3)14 (53.0)10.2 (0.71) 16 x 16 (4.9x4.9)17 (64.3)15.0 (1.1) 16 x 18 (4.9x5.5)19 (71.8)18.7 (1.13) 16 x 20 (4.9x6.1)23 (87.1)27.4 (1.89) 12 x 12 (3.6x3.6) 6 - 12 (152-305) 14 (52.9)10.2 (0.71) 14 x 14 (4.3x4.3)15 (56.7)11.7 (0.81) 16 x 16 (4.9x4.9)18 (68.1)16.8 (1.16) 16 x 18 (4.9x5.5)20 (75.6)20.7 (1.43) • Model F1 Res 44 SWC Fig. 5 *Calculate for a .10 density but in no case go below the baseline flows & pressures 9. Technical Data: F1 Res 58 HSW & HSW/F2 Thread Size Nominal Orifi ce Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) °F°C°F°C ½” NPT (R½)½ (13)155 175 68 79 175 (12)100 150 38 66 5.82.45 (62) Escutcheon, F2, Data: Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F2½ (13)3/16 - 11/16 (4.7 - 17.4) *Baseline fl ows and pressures for 0.05 density Max. Sprinkler Spacing ft (m) “A” Ceiling -to- Defl ector Inch (mm) Sprinkler Temp. Rating °F (°C) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identifi cation Number (SIN) 12 x 12 (3.6x3.6) 4 - 6 (101-152) 155 (68)175 (79)16 (60.6)7.6 (0.53) R3533 14 x 14 (4.3x4.3)155 (68)175 (79)18 (68.2)9.7 (0.67) 16 x 16 (4.9x4.9)155 (68)175 (79)21 (79.5)13.2 (0.91) 16 x 18 (4.9x5.5)155 (68)175 (79)25 (94.7)18.6 (1.28) 16 x 20 (4.9x6.1)155 (68)175 (79)29 (109.8)25 (1.73) 12 x 12 (3.6x3.6) 6 - 12 (152-305) 155 (68)175 (79)22 (83.3)14.4 (1.0) 14 x 14 (4.3x4.3)155 (68)175 (79)22 (83.3)14.4 (1.0) 16 x 16 (4.9x4.9)155 (68)175 (79)26 (98.4)20.1 (1.39) 16 x 18 (4.9x5.5)155 (68)175 (79)31 (117.4)28.6 (1.97) *Calculate for a .10 density but in no case go below the baseline flows & pressure 10. Technical Data: F1Res 58 HSWX (SIN RA3533) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) Sprinkler Identifi cation Number (SIN)°F°C°F°C Bulb ½” NPT (R½)1/2” (13)175 (12)155 175 68 79 100 150 38 66 5.82.45 (62)RA3533 *Baseline fl ows and pressures for 0.05 density Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/ min) Pressure PSI (bar) 18 x 20 (5,5 x 6,1)18 (5,5)30 (114)26.8 (1,85)30 (114)26.8 (1,85) 4 to 6 (100 to 152); ½ (13) recessed using F2 escutcheon 8 (2,4) 20 x 20 (6,1 x 6,1)20 (6,1)30 (114)26.8 (1,85)30 (114)26.8 (1,85) 16 x 22 (4,9 x 7,3)16 (4,9)33 (125)32.4 (2,23)33 (125)32.4 (2,23) 16 x 24 (4,9 x 7,3)16 (4,9)38 (144)42.9 (2,96)38 (144)42.9 (2,96) 14 x 26 (4,3 x 7,9)14 (4,3)42 (160)52.4 (3,75)42 (160)52.4 (3,75) 18 x 20 (5,5 x 6,1)18 (5,5)35 (133)36.4 (2,5)35 (133)36.4 (2,5) 6 to 12 (152 to 305); ½ (13) recessed using F2 escutcheon 16 x 22 (4,9 x 6,7)16 (4,9)38 (144)42.9 (2,96)38 (144)42.9 (2,96) 16 x 24 (4,9 x 7,3)16 (4,9)42 (160)52.4 (3,6)42 (160)52.4 (3,6) 14 x 26 (4,3 x 7,9)14 (4,3)46 (174)62.9 (4,34)46 (174)62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D *Calculate for a 0.10 density but in no case go below the baseline floor and pressures. • Model F1 Res 58 HSWX (Bulb) • Model KRes58 HSWX (Link) Fig. 6 Technical Data: KRes58 HSWX (RA3593) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) Sprinkler Identifi cation Number (SIN)°F°C Link ½” NPT (R½)1/2” (13)175 (12)100385.82.45 (62)RA3593 *Baseline fl ows and pressures for 0.05 density Max. Coverage area Ft x Ft (m x m) Max. Spac- ing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Mini- mum Spacing Ft (m) Flow GPM (L/min) Pressure PSI (bar) 18 x 20 (5,5 x 6,1)18 (5,5)29 (109)25 (1,72) 4 to 6 (100 to 152); ½ (13) recessed using F2 escutcheon 8 (2,4) 20 x 20 (6,1 x 6,1)20 (6,1)30 (114)26.8 (1,85) 16 x 22 (4,9 x 7,3)16 (4,9)33 (125)32.4 (2,23) 16 x 24 (4,9 x 7,3)16 (4,9)38 (144)42.9 (2,96) 14 x 26 (4,3 x 7,9)14 (4,3)42 (160)52.4 (3,75) 18 x 20 (5,5 x 6,1)18 (5,5)35 (133)36.4 (2,5) 6 to 12 (152 to 305); ½ (13) Recessed using F2 escutcheon 16 x 22 (4,9 x 6,7)16 (4,9)38 (144)42.9 (2,96) 16 x 24 (4,9 x 7,3)16 (4,9)42 (160)52.4 (3,6) 14 x 26 (4,3 x 7,9)14 (4,3)46 (174)62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D *Calculate for a 0.10 density but in no case go below the baseline floor and pressures. 11. Maintenance Model F1 Res 30, 49, F1 Res 58 & F1 Res 76 Sprin- klers should be inspected quarterly, and the sprinkler system maintained in accordance with NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with soap and water, Ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Re- move any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause im- proper operation or non-operation. Model F1Res 30, 49 & 58 Pendent Sprinkler Specifi cations Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential pen- dent sprinklers engineered to provide a minimum de- sign density of 0.10 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the appli- cable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Deflector-to-ceiling distance list- ing shall be 1” to 8” maximum. Sprinkler frame and de- flector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb con- taining no plastic parts, and having a temperature rat- ing of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 4.9 & 5.8. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Residential pendent sprinklers shall be Reliable Model F1 Res 49 & 58, SIN R3516 & R3513 (Bulletin 135). 12. Model F1 Res 30, 49 & 58 Recessed Pendent/F1, Model F1 Res 30, 49 & 58 Recessed Pendent/F2, Model F1 Res 30, 49 & 58 Recessed Pendent/FP Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential recessed pen- dent sprinklers engineered to provide a minimum design density of 0.10 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s instal- lation guidelines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Deflector-to-ceiling distance listing shall be 1” to 8” maximum. Sprinkler frame and deflector shall be of bronze frame construction hav- ing a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb contain- ing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 4.9 (70). Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– spec- ify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with ½” adjustment (Model F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off design with ½” adjustment (Model FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residen- tial recessed pendent sprinklers shall be Reliable [Model F1 Res 49 & 58 Recessed Pendent/F1] [Model F1 Res 49 & 58 Recessed Pendent/F2] [Model F1 Res 49 & 58 Recessed Pendent/FP] SIN R3516 & R3513 (Bulletin 135). Model F1 Res 30, 49 & 58 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential concealed sprinklers engineered to provide a minimum design den- sity of 0.10 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be in- stalled in conformance with the manufacturer’s installa- tion guidelines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded ex- truded or cold head cup with 3 mm glass bulb contain- ing no plastic parts, and having a temperature rating of 155°F (68°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange. Meth- od of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” cover plate adjustment. Cover plate temperature rating shall be 135°F (57°C). A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color– specify]. ]. Con- cealed pendent sprinklers shall be Reliable Model F1 Res 49 & 58 CCP, SIN R3516 & R3513 (Bulletin 135). Model F1 Res 44, F1 Res 58 Horizontal Sidewall, F1 Res 58 HSWX & KRes58 HSWX Residential Sprinkler Specifi cations Sprinklers shall be [cULus Listed] low flow residen- tial horizontal sidewall sprinklers engineered to pro- vide a minimum design density of 0.10 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in con- formance with the manufacturer’s installation guide- lines and the applicable installation standard. Where horizontal sidewall residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprin- kler frame and deflector shall be of bronze frame con- struction having a ½” NPT thread. Water seal assem- bly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. The solder element (Link) version, the water seal consist of a cap with a bellville spring washer and a temperature rating of 165°F (74°C). The recessed assembly forthe HSWX (Bulb & Link) should be a steel two pieces escutcheon with 1/2” adjustment (Model F2) standard finish should be Bright Chrome and white painted. The F1 Res 58 HSW is also available with low lead frame. F1 Res 58 HSW and HSWX sprinklers shall have a nominal K Factor of 5.8 and F1 Res 44 a nomi- nal K factor of 4.4. Standard finish: [Bronze] [Chrome- plated] [White Polyester] [Special finish– specify]. Residential horizontal sidewall sprinklers shall be Reli- able Model F1 Res 44, F1 Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN R3531, RA3533 & RA3593 (Bulletin 135). Model F1 Res 44 & 58 Recessed Horizontal Sidewall Sprinkler Use description for the Model F1 Res 58 horizontal sidewall sprinkler with the following modifications: Re- place “horizontal sidewall sprinkler” with “recessed hori- zontal sprinkler.” Add: Recessed escutcheon assembly shall be a steel, two-piece escutcheon with ½” adjust- ment (Model F2). Standard finish shall be [brass][bright chrome] [white painted] [Special finish– specify]. Resi- dential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 58/F2, SIN R3513 (Bulletin 135). Model F1 Res 76 Pendent Sprinklers shall be [cULus Listed] low flow resi- dential pendent sprinklers engineered to provide a minimum design density of 0.10 gpm/ft2 over the list- ed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plat- ed] [White Polyester] [Special finish– specify]. Residen- tial pendent sprinklers shall be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135). Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, Model F1 Res 76 Recessed Pendent/FP Sprinklers shall be [cULus Listed] low flow residen- tial recessed pendent sprinklers engineered to provide a minimum design density of 0.10 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer’s technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon-coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with ½” adjustment (Mod- el F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off design with ½” adjustment (Model FP)]. Stan- dard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 76 Recessed Pendent/F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1 Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Model F1 Res 76 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] low flow residential concealed sprinklers engineered to provide a minimum design density of 0.10 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprin- klers shall be installed in conformance with the manufac- turer’s installation guidelines and the applicable installa- tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of 155°F (68°C). Cover plate assem- bly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” cover plate adjustment. Cover plate tem- perature rating shall be 135°F (57°C). A plastic protec- tive cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color– specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135). Finishes(1) Standard Finishes SprinklerF1, F2, FP Escutcheons Bronze Chrome Plated White Polyester Coated Brass Bright Chrome Plated White Painted Special Application Finishes SprinklerF1, F2, Escutcheons Bright Brass Black Plated Black Paint Off White Satin Chrome Bright Brass Black Plated Black Paint Off White Satin Chrome (1) Other finishes and colors are available on special order. Consult factory for details. Information Specify:Ordering 1. Sprinkler Model 2. Sprinkler Type 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 13. The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A 07/13 P/N 9999970322 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles • Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water flow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals • Air maintenance devices • Air compressors • Pressure gauges • Identification signs • Fire department connection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bu l l e t i n 0 0 6 Re v . H Bulletin 006 Rev. H Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1. Very low water flow requirements. 2. Cover plate attachment (Plain or Perforated) with ½” (13mm) Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacu- ation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, con- cealing the most dependable fire protection available, an automatic sprinkler system. The RFC30, RFC43 and RFC49 are UL Listed Residen- tial Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit ac- curately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. 2. Application and Installation The RFC30, RFC43 and RFC49, for residential instal- lations, use a 165°F (74°C) fusible solder link in a tun- ing fork style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classifica- tion solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to ceiling temperature. The subsequent operation of the solder link opens the waterway and causes the de- flector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler de- flector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The resi- dential distribution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces sig- nificantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexago- nal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe instal- lation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprin- kler/cup assembly, care should be taken to prevent dam- age to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COV- ERS. Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2” (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final ad- justment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover re- moval requires turning in the counter-clockwise direction. In ceilings that have a plenum space above the sprin- kler, the plenum space may have neutral or negative pressurization but must not be positively pressurized. Inspect all sprinklers after installation to ensure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air flow impedi- ment. Model (SIN) Thread Size Inch (mm) Nominal Orifi ce Inch (mm) Sprinkler Temp Rat- ing CCP Assembly Temp. Rating Max. Ambient Temp. K Factor Max. Pressure psi (bar) °F°C°F°C°F°C RFC 30 (RA0611)½” (15)21/64 (8,2)1657413557100383.0175 (12) RFC 43 (RA0612)½” (15)3/8 (10)1657413557100384.3175 (12) RFC 49 (RA0616)½” (15)7/16 (11)1657413557100384.9175 (12) Note: 1 bar = 100 Kpa RFC 30 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6)12 (3,6)9 (34,1)9.0 (0,62) 8 (2,4) 14 x 14 (4,3 x 4,3)14 (4,3)10 (37,8)11.0 (0,76) For Ceiling types refer to NFPA 13, 13R or 13D 3. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- klers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate assembly which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprin- klers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non-operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specifi cation Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop-down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K-factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91 (70) having a 5/16”, 3/8” and 7/16” orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a ½” cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). RFC 43 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6)12 (3,6)12 (4,5)7.8 (0,54) 8 (2,4) 14 x 14 (4,3 x 4,3)14 (4,3)13 (49)9.1 (0,63) 16 x 16 (4,9 x 4,9)16 (4,9)13 (49)9.1 (0,63) 18 x 18 (5,5 x 5,5)18 (5,5)18 (68)17.5 (1,21) 20 x 20 (6,1 x 6,1)20 (6,1)21 (79)23.8 (1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6)12 (3,6)13 (49)7.0 (0,48) 8 (2,4) 14 x 14 (4,3 x 4,3)14 (4,3)13 (49)7.0 (0,48) 16 x 16 (4,9 x 4,9)16 (4,9)13 (49)7.0 (0,48) 18 x 18 (5,5 x 5,5)18 (5,5)17 (69,3)12.0 (0,83) 20 x 20 (6,1 x 6,1)20 (6,1)20 (75,73)16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 05/13 P/N 9999970261 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Ordering Information Specify: 1. Sprinkler Model 2. Cover Plate Finish 3. Thread-On or Push-On Feature Cover Plate Finishes(1) Standard Finishes Chrome White Paint Special Application Finishes(2) Bright Brass Finished Bronze Black Plating Black Paint Off White Satin Chrome (1) Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) For the perforated style cover- plate, consult factory for avail- ability on these and other cus- tom finishes. AHEADOFTHEFLOW™ www.nibco.com Revision 5/14/02 NIBCO INC. WORLDHEADQUARTERS • 1516 MIDDLEBURYST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECHSERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONALSERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 52 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Copper Water Tube continued DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “M” TYPE “M”Hard Drawn Only:20-ft. (6.1m) Straight Lengths Usage:For general purpose plumbing, heating and drainage installations. TolerancesHard Drawn (Hard Drawn Only) OutsideTubing ODNominal WallWeightBurstingSafe Working NominalDiameterThicknessPer FootPressure A Pressure B Water TubeMin.Max. Size (In Inches)Inch(mm)Inch(mm)Inch(mm)Inch(mm)Lb(kg)psi(bars)psi(bars) 1/40.375(9.53)0.373(9.47)0.376(9.55)N/AN/AN/AN/AN/AN/AN/AN/A 3/80.500(12.70)0.497(12.62)0.501(12.73)0.025(0.64)0.145(0.07)N/AN/A855 (59) 1/20.625(15.88)0.622(15.80)0.626(15.90)0.028(0.71)0.204(0.09)6135 (423)741 (51) 5/80.750(19.05)0.747(18.97)0.751(19.08)N/AN/AN/AN/AN/AN/AN/AN/A 3/40.875(22.23)0.872(22.15)0.876(22.25)0.032(0.81)0.328(0.15)4717 (325)611 (42) 11.125(28.58)1.122(28.50)1.127(28.63)0.035(0.89)0.465(0.21)3865 (266)506 (35) 1 1/41.375(34.93)1.372(34.85)1.377(34.98)0.042(1.07)0.682(0.31)3875 (267)507 (35) 1 1/21.625(41.28)1.621(41.17)1.627(41.33)0.049(1.24)0.940(0.43)3550 (245)497 (34) 22.125(53.98)2.121(53.87)2.127(54.03)0.058(1.47)1.460(0.66)2935 (202)448 (31) 2 1/22.625(66.68)2.621(66.57)2.627(66.73)0.065(1.65)2.030(0.92)2800 (193)411 (28) 33.125(79.38)3.121(79.27)3.127(79.43)0.072(1.83)2.680(1.22)2665 (184)380 (26) 3 1/23.625(92.08)3.621(91.97)3.627(92.13)0.083(2.11)3.580(1.62)N/AN/A378 (26) 44.125(104.78)4.121(104.67)4.127(104.83)0.095(2.41)4.660(2.11)2215 (153)377 (26) 55.125(130.18)5.121(130.07)5.127(130.23)0.109(2.77)6.660(3.02)2490 (172)349 (24) 66.125(155.58)6.121(155.47)6.127(155.63)0.122(3.10)8.920(4.05)2000 (138)328 (23) 88.125(206.38)8.119(206.22)8.127(206.43)0.170(4.32)16.500(7.48)2285 (158)344 (24) 1010.125(257.18)10.119(257.02)10.127(257.23)0.212(5.38)25.600(11.61)N/AN/A344 (24) 1212.125(307.98)12.119(307.82)12.127(308.03)0.254(6.45)36.700(16.65)N/AN/A345 (24) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. A Based on actual laboratory test data provided by Copper Development Association, Inc. B Based upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa).