HomeMy WebLinkAboutB12-0329 REV2 TRANSMITTAL, REQUESTED INFO Department of Community Development
75 South Frontage Road
TOWN O F VA I I. ' Vail, CO 81657
Tel: 970.479.2128
www.vailgov.com
Development Review Coordinator
TRANSMITTAL FORM
Use this form when submitting additional information for planning applications or building permits.
This form is also used for requesting a revision to building permits. A two hour minimum building review
fee of$110 will be charged upon reissuance of the permit.
Application/Permit#(s)information applies
to: Attention: ) Revisions
�� Response to Correction Letter
attached copy of correction letter
Deferred Submittal
Other
TJa-o
Project Street Addrg,s:
�, �oU�R`d V l/
(Number) (Street) I 9 AE Suite#)
Building/Complex Name: fa I t.(J / W) Description of Transmittal/List of Changes, Items Attached:
Applicant Information
(architect, contractor,owner/owner's rep)
Contact Name:
t rr
Address:�.1 Z 5 () � > �S � C I IZ � ��� - S� !✓i rS
City 6! x K-* �1 State: zip:
Contact Name: l T 7Z- 9G
(use additional sheet if necessary)
Contact Phone: -? H r Building Permits:
Contact E-Mail: J @ �E fa CQ-, Revised ADDITIONAL Valuations (Labor&Materials)
ire/ (�� �J_l.
T (DO NOT include original valuation)
-
I hereby acknowledge that I have read this application,filled out Building: $
in full the information required,completed an accurate plot plan,
and state that all the information as required is correct. I agree to Plumbing: $
comply with the information and plot plan,to comply with all Town
ordinances and state laws, and to build this structure according Electrical: $
to the town's zoning and subdivision codes, design review ap-
proved,International Building and Residential Codes and other Mechanical: $
ordinan"6 of the Town ap licable thereto.
X , { � � Total: $
Owner/ wner's Representative nature(Required)
Date Received:
For Office Use Only: D
Fee Paid: SEP 0 4 2013
Received From:
Cash Check# C�
CC: Visa/MC Last 4 CC# exp.date: TOWN OF VA I L
Authorization#
B12-0329 : Entries for Item:190 - ELEC-Final 09:55 09/04/2013
Action Comments By Date Unique_
. , Key
DN Provide GFI breaker settings from sgremmeT 08/14/2013 A000161
manufacture 294
all name plates to be installed
provide lug torque schedules
panic hardware at door to MDP room
provide all en finer testing results
Total Rows: 1
Page 1
Inspection Items for B12-0329 09:54 09/04/2013
Sec Item Id Description --ApprTReq Items Action Inheritable
* 20 BLDG-Foundation/Steel No R 0 No
* 120 ELEC-Rough Ys R 3 AP No
* 190 ELEC-Final R 1 DN No
90 BLDG-Final R 1 DN No
Total Rows:4
Page 1
wr •�►
Superior client service. Practical solutions.
GUARANTEE ELECTRICAL CONTRACTING
Avon & Vail Colorado
Avon / Vail WWTP Upgrades
June 3-4 File: G3479-1
Project Manager: Ar'c Proskurniak
infol�magnoiv.com my neejing & Technical Field Services Canada
wwv..mcgnoiv.corn United States
Document !D: CANF-5tv103) Cmle
96 Inverness Drive East, Suite R
Englewood, CO 80112
303.7Q9,1273 303.790.4815 300.462.3157
File: G3479-1
06/21/2013
GUARANTEE ELECTRICAL CONTRACTING Via: ® email
21250 EAST 31ST CIRCLE ❑ fax
AURORA, CO 80011 ❑ mail
Attention: Jeremy Wilson
Project Manager
Dear Mr. Wilson.
Re: Avon / Vail WWTF Upgrades
We are pleased to submit our report and test sheets pertaining to the project mentioned above.
The work was performed by Paul Chihoski and the undersigned, with the helpful assistance of
you and your onsite representative Mike Hartsfield.
All on-site work was completed during our site visits on June 3 & 4.
Based on our analysis of the test results, the equipment tested is in acceptable condition and
suitable for continued service. However, during the course of our activities, we made certain
observations which should be investigated outlined under summary of results below. We suggest
you review the test results at your convenience to better appreciate the condition of your
equipment, and we invite any questions that may arise following your review.
We trust this report meets with your approval and requirements. Should you need further
information or assistance, please do not hesitate to contact us.
We take this opportunity to thank you for your continued cooperation and assistance during our
site visits, and for retaining the services of Magna IV Engineering. We look forward to being of
service to you in the future.
Yours Truly,
MAGNA IV ENGINEERING
Aric Proskurniak
Field Service Client Manager
AP
in;o< rrnagnoiv.com Engineering 8 Technical Field Services _anoda
wwv.,.magnaiv.com United States
Document ID: CANT-5M03! Chile
INDEX
1 .0. EXECUTIVE SUMMARY..............................._.............................._.............................._...................4
2.0. SCOPE Or WORK ..............................—.......................................................................................5
3.0. SUMMARY OF 7ESTS...............................».............................................................».......................5
4.0. SUMMARY OF RESULTS AND DEFICIENCIES ..............................._.............................._................b
5.0. TEST RESULTS..............................................................._.............................._.............................._...7
Document ID: CANE-5M031 3 *o
4
1.0. EXECUTIVE SUMMARY
The services of Magna IV Engineering were retained by Guarantee Electrical Contracting
to perform low voltage acceptance testing at the waste water treatment plants located
in Vail and Avon Colorado.
Our scope of work for the project included acceptance testing, function testing,
cleaning, and inspection of electrical distribution equipment based on the standards
developed between Guarantee Electrical Contracting and Magna IV Engineering,
previous projects, IEEE, NETA and NEMA standards, and Magna's practices and
procedures for acceptance testing.
Based on our test results, the equipment tested is suitable for service at rated capacities.
Section 4.0 of this report detail the deficiencies and recommendations that were found
during our activities. Please review the Summary of Results and Deficiencies to determine
what actions should be scheduled and budgeted for prior to and during the next
maintenance period to optimize the operation of your equipment.
We strongly recommend continuing a maintenance program to ensure oil equipment is
tested annually or included in a 4-year plan to continue the reliable and, most
importantly, safe operation of the equipment.
Docurnena D: CANF-SM031 4
2.0. SCOPE OF WORK
Our scope of work for this project included the following equipment:
2.1. 600 Volt Equipment
• Circuit breakers
• Switchboards
• Service Entrance Disconnect Switch (Vail site)
• Low voltage cables (Avon site)
• Meters
• Transfer Switch (Vail site)
3.0. SUMMARY OF TESTS
All tests performed are based on the scope of work developed between Guarantee
Electical Contracting and Magna IV Engineering, previous projects, IEEE, NETA and NEMA
standards, and Magna's practices and procedures for acceptance testing.
Specific tests performed on the power distribution equipment are as follows:
3.1. Circuit Breakers
• Visual inspection
• Nameplate verification
• Complete cleaning
• Electrical and mechanical function tests
• Contact resistance test
• Insulation integrity test
• Random torque test of terminations and accessible connections
3.2. Switchboards
• Visual inspection
• Nameplate verification
• Complete cleaning
• Electrical and mechanical function tests
• Contact resistance test
• Phase identification
• Insulation integrity test
• Random torque test of terminations accessible connections
3.3. Transfer Switch
• Visual inspection
• Liquid level check
• Nameplate verification
• Insulation resistance test
• Function test
• Random torque test of accessible connections
Document 10' CANE-5P WII
3.4. Low Voltage Cables
• Visual inspection
• Random torque test of accessible connections
• Continuity test
• Phase identification and verification
• Insulation resistance test
4.0. SUMMARY OF RESULTS AND DEFICIENCIES
1 When completeing the testing activities at the Avon site, it was noticed that the
ground bus splicing on MCC-6 was not correctly installed. Correct splicing is
important for proper grounding of the electrical system and helps to protect in the
event of an electrical fault. After bringing the issue to Mike's attention, corrective
measures were taken to resolve the defeciency.
5.0. TEST RESULTS
Please review the enclosed test sheets for detailed test results and field observations.
Document ID: CANF-5tA031 ? i-._,I,
VAIL WASTEWATER TREATMENT PLANT
TEST RESULTS
Document ID: CANF-5M031 7 1 Page
PREPARED FOR "--
SMAINT11111CIR/C w�~w
LOW VOLTAGE MOTOR CONTROL CENTER CANF-5EO45
WO# G3479-1 TAG# DS-1 DATE June 4,2013
SITE VAIL WWTF TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED VOLTS 600 YEAR 2013
MODEL MDP RATED AMPS 1600 BIL(KV) NL
SO# SDN0364912 RATED FREQ. 60 ENCL. NEMA IA
#OF SECT. 2 BRACING (KA) 65
TEST SUMMARY
REF.NETA STANDARD 7.16.2.1
TEST SUMMARY OK FAIL TNOT COMMENTS
Z COMPARED TO DRAWING ✓ COMPARED TO VE2-02
NAMEPLATE VERIFICATION/CHECK ✓ VISUAL
a VISUAL INSPECTION ✓ NO DAMAGE
Z
CONTACT RESISTANCE ✓ SEE RESULTS BELOW
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
W
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
DAMAGE ✓ NONE APPARENT
ANCHORAGE ✓ BOLTED TO CONCRETE PAD IN 4 CORNERS
GROUNDING ✓ NOT YET TERMINATED TO SOURCE
COVER PANELS ✓ APPEAR TO CLOSE AS APPROPRIATE
AREA CLEARANCES ✓ VERIFIED
DIRT ACCUMULATION ✓ CLEAN
CORRECT LABELING ✓ COMPARED TO VE2-02
NOTES
1 COVER PANELS NOT YET INSTALLED
2
3
4
VAIL MCC Page 1 of 8
PREPARED FOR
Lf Tl�/G' .�wcwrw
fiUlRANTEEE C
LOW VOLTAGE MOTOR CONTROL CENTER F7ANF 5E045
WO# G3479-1 TAG# DS 1 DATE June 4,2013
LAYOUT
MCC FRONT VIEW
METER
FEED MAIN
CABLES
`JAIL MCC Page 2 of 8
PREPARED FOR
URAHTfEELE Tl3/C
oU C
LOW VOLTAGE MOTOR CONTROL CENTER CANF-5E045
WO# G3479-1 TAG # DS-1 DATE June 4, 2013
TEST RESULTS
IAMB.TEMP 68.7°F
HUMIDITY 35%
CONTINUITY / RESISTANCE TESTS
EQ.# D00003 RESISTANCE(pQ)
FROM TO PHASE A PHASE B PHASE C
MAIN BUS SECT 1 MAIN BUS SECT 2 40 40 40
FROM TO GROUND BUS
GROUND BUS SECT 1 GROUND BUS SECT 5 40
VAIL MCC Page 3 of 8
PREPARED FOR
�a�RA�rEEE�ECrR�c -�wcrw
LOW VOLTAGE MOTOR CONTROL CENTER CANF-5E045
WO# G3479-1 TAG # DS-1 DATE June 4,2013
TEST RESULTS
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ.# D0002 RESULTS (MO) - 0-0-GND
TEST SETUP TEST VOLTS TIME PHASE A PHASE B PHASE C
1 500 60 sec. >20 000 >20 000 >20 000
2 1000 60 sec. >20 000 >20 000 >20 000
3
4
VAIL MCC Page 4 of 8
PREPARED FOR _
I�UARUNTEEELECTR/C �w�~w
LOW VOLTAGE MOTOR CONTROL CENTER CANF-5EO45
WO# G3479-1 TAG# MDP-1 DATE June 4,2013
SITE VAIL WWTF TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED VOLTS 600 YEAR 2013
MODEL MDP RATED AMPS 1600 BIL(KV) NL
SO# NL RATED FREQ. 60 ENCL. NEMA IA
#OF SECT. 1 BRACING (KA) 65
TEST SUMMARY
REF.NETA STANDARD 7.16.2.1
TEST SUMMARY OK FAIL TESTED
COMMENTS
Z COMPARED TO DRAWING ✓ COMPARED TO VE2-02
NAMEPLATE VERIFICATION/CHECK ✓ VISUAL
d VISUAL INSPECTION ✓ NO DAMAGE
Z
CONTACT RESISTANCE ✓ SEE RESULTS BELOW
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
W
r
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
DAMAGE ✓ NONE APPARENT
ANCHORAGE ✓ BOLTED TO CONCRETE PAD IN 4 CORNERS
GROUNDING ✓ NOT YET TERMINATED TO SOURCE
COVER PANELS ✓ APPEAR TO CLOSE AS APPROPRIATE
AREA CLEARANCES ✓ VERIFIED
DIRT ACCUMULATION ✓ CLEAN
CORRECT LABELING ✓ COMPARED TO VE2-02
NOTES
1 COVER PANELS NOT YET INSTALLED
2
3
4
VAIL MCC Page 5 of 8
PREPARED FOR
aUARi ffirliELECTR/C .•�•�•�•••�•
LOW VOLTAGE MOTOR CONTROL CENTER CANF-5E045
WO# G3479-1 TAG# MDP-1 DATE June 4, 2013
LAYOUT
MCC FRONT VIEW
1000AT
600AT
600AT
350AT
150AT
VAIL MCC Page 6 of 8
PREPARED FOR ,
MAWARTEEELECTR/C
LOW VOLTAGE MOTOR CONTROL CENTER CANF-5E045
WO# G3479-1 TAG # MDP-I DATE June 4, 2013
TEST RESULTS
IAMB.TEMP 68.7°F
HUMIDITY 35
CONTINUITY / RESISTANCE TESTS
EQ.# D00003 RESISTANCE(p0)
FROM TO PHASE A PHASE B PHq54
TOP MAIN BUS SECT 1 BOTTOM MAIN BUS SECT 2 64 58
i
FROM TO NEUTRAL
TOP NEUTRAL BUS SECT I BOTTOM NEUTRAL BUS SECT 1 62
VAIL MCC Page 7 of 8
PREPARED FOR
�UARAA/TfEELECTR/C �w�"~w
LOW VOLTAGE MOTOR CONTROL CENTER F CANF-5E045
WO# G3479-1 TAG# MDP-1 DATE June 4,2013
TEST RESULTS
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ.# D0002 RESULTS(MD) - 0-0-GND
TEST SETUP TEST VOLTS TIME PHASE A PHASE B PHASE C
1 500 60 sec. >20 000 >20 000 >20 000
2 1000 60 sec. >20 000 >20 000 >20 000
3
4
VAIL MCC Page 8 of 8
PREPARED FOR
�UABANTfffLfCTR/C �w�"~w
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# DS-I DATE June 4,2013
PLANT VAIL WWTF TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 1600 YEAR NL
MODEL RD NOM.VOLTS 600 POLES 3
CAT# RD65K INT CAP (KA) 65 FREQ. 60
SERIAL# NP6635C68H15 BIL NL
TEST SUMMARY
REF.NETA STANDARD 7.6.1.1
TEST SUMMARY OK FAIL TES TOT COMMENTS
Z COMPARED TO DRAWING ✓ VE2-02
O NAMEPLATE VERIFICATION/CHECK ✓ VERIFIED
U V/ VERIFIED
a VISUAL INSPECTION
z
CONTACT RESISTANCE ✓
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
uj
N ✓
THERMAL MAGNETIC TRIP TEST
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓ GROUND CT WIRING CONFIRMED
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓ FUNCTIONED PRIMARY GND TRIP
UV/BLOWN FUSE DEVICES ✓
Vail Breakers Page 1 of 14
PREPARED FOR
�UARANTEEELECTR/C �w�~w
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG # DS-1 DATE June 4, 2013
TEST RESULTS
AMB.TEMP 68.7°F HUMIDITY 35%
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE(Nil) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 90 90 110
AFTER CLEANING (IF REQ'D) N/A N/A N/A
COMMENTS:
CONTACT RESISTANCE FROM SECTION 1 TO LOAD SIDE BREAKER
NEUTRAL BUS-76 UGHMS
GND BUS- 140 UGHMS
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ# D00002 RESULTS (MO) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AV E.
THERMAL 3007o(sec)
INST TRIP (LO) amps
MANUFACTURER TESTED
INST TRIP (HI) amps
IWITHSTAND (MID)
NOTES
1 GND FAULT PICKUP AND TRIP TESTED BY PRIMARY INJECTION SETTING"A"
2
3
4
5
Vail Breakers Page 2 of 14
PREPARED FOR w
�UABQ/YTffELfCTB/C �w�"~w
MOLDED CASE CIRCUIT BREAKER CANF-SE020
WO# G3479-1 TAG# 1000A BREAKER DATE June 4,2013
PLANT VAIL WWTF TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 1000 YEAR NL
MODEL HFD NOM.VOLTS 600 POLES 3
CAT# RD65K INT CAP(KA) 65 FREQ. 60
SERIAL# NOT VISIBLE BIL NE
TEST SUMMARY
REF.NETA STANDARD 7.6.1.1
TEST SUMMARY OK FAIL TES TOT COMMENTS
Z COMPARED TO DRAWING ✓ VE2-02
r- NAMEPLATE VERIFICATION/CHECK V/ VERIFIED
a VISUAL INSPECTION ✓ VERIFIED
N
Z
CONTACT RESISTANCE ✓
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
Lu ✓
THERMAL MAGNETIC TRIP TEST
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓
UV/BLOWN FUSE DEVICES ✓
Vail Breakers Page 3 of 14
i
PREPARED FOR w
ROaRWrEEEiECrRic
MOLDED CASE CIRCUIT BREAKER CANF-5E020
w0# G3479-1 TAG# 1000A BREAKER DATE June 4, 2013
TEST RESULTS
AMB.TEMP 68.7'F HUMIDITY 35
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE (N4) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 78 76 86
AFTER CLEANING (IF REQ-D) N/A N/A N/A
COMMENTS:
CONTACT RESISTANCE FROM SECTION I TOP TO LOAD SIDE BREAKER
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ # D00002 RESULTS (MO) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AVE.
THERMAL 30070(sec)
INST TRIP (LO) amps
MANUFACTURER TESTED
INST TRIP (HI) amps
WITHSTAND (MID)
NOTES
1
2
3
4
5
Vail Breakers Page 4 of 14
PREPARED FOR w ,
�UABAA/TfffLfCTR/C 'J"w11r"~w
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# 600A BREAKER DATE June 4, 2013
PLANT VAIL WWFF 2ND FROM TOP TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 600 YEAR NL
MODEL HFD NOM.VOLTS 600 POLES 3
CAT# RD65K INT CAP (1 65 FREQ. 60
SERIAL# NOT VISIBLE BIL NL
TEST SUMMARY
IREF.NETA STANDARD 7.6.1.1
TEST SUMMARY OK FAIL TESTOT COMMENTS
Z COMPARED TO DRAWING ✓ VE2-02
NAMEPLATE VERIFICATION/CHECK ✓ VERIFIED
a VISUAL INSPECTION ✓ VERIFIED
z
CONTACT RESISTANCE ✓
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
N ✓
~ THERMAL MAGNETIC TRIP TEST
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓
UV/BLOWN FUSE DEVICES ✓
Vail Breakers Page 5 of 14
PREPARED FOR
MAl3A/YTEEELECTR/C
MOLDED CASE CIRCUIT BREAKER CANF-SE020
WO# G3479-1 TAG# 600A BREAKER DATE June 4,2013
TEST RESULTS
AMB.TEMP 68.7°F HUMIDITY 357.
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE (u4) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 140 140 140
AFTER CLEANING (IF REQ-D) N/A N/A N/A
COMMENTS:
CONTACT RESISTANCE FROM SECTION 1 TOP TO LOAD SIDE BREAKER
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ # D00002 RESULTS (MO) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AVE.
THERMAL 300%(sec)
INST TRIP (LO) amps
MANUFACTURER TESTED
INST TRIP (HI) amps
IWITHSTAND (MID)
NOTES
1
2
3
4
5
Vail Breakers Page 6 of 14
PREPARED FOR
89KNO /T11111CTR/C I d 1111"w d"~w
MOLDED CASE CIRCUIT BREAKER I CANF-SE020
WO# G3479-1 TAG# 600A BREAKER DATE June 4, 2013
PLANT VAIL WWTF 3RD FROM TOP TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 600 YEAR NL
MODEL HFD NOM.VOLTS 600 POLES 3
CAT# RD65K INT CAP (KA) 65 FREQ. 60
SERIAL# NOT VISIBLE BIL NIL
TEST SUMMARY
REF.NETA STANDARD 7.6.1.1
TEST SUMMARY OK FAIL TESTED
COMMENTS
Z COMPARED TO DRAWING ✓ VE2-02
0 NAMEPLATE VERIFICATION/CHECK ✓ VERIFIED
a VISUAL INSPECTION ✓ VERIFIED
z
CONTACT RESISTANCE ✓
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
N ✓
uj THERMAL MAGNETIC TRIP TEST
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓
UV/BLOWN FUSE DEVICES ✓
Vail Breakers Page 7 of 14
PREPARED FOR _
co�Ra�rEEE�ECrRic � w�.wcwiw
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# 600A BREAKER DATE June 4,2013
TEST RESULTS
AMB.TEMP 68.7°F HUMIDITY 357.
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE (N4) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 130 140 140
AFTER CLEANING (IF REQ-D) N/A N/A N/A
COMMENTS:
CONTACT RESISTANCE FROM SECTION 1 TOP TO LOAD SIDE BREAKER
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ# D00002 RESULTS(MO) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED
500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AVE.
THERMAL 3007o(sec)
INSTTRIP (LO) amps
MANUFACTURER TESTED
INST TRIP (HI) amps
WITHSTAND (MID)
NOTES
1
2
3
4
5
Vail Breakers
Page 8 of 14
PREPARED FOR
fiaARaffirEEElECrR/c
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG # 350A BREAKER DATE June 4,2013
PLANT VAIL WWFF 4TH FROM TOP TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 350 YEAR NL
MODEL HFD NOM.VOLTS 600 POLES 3
CAT# RD65K INT CAP (KA) 65 FREQ. 60
SERIAL# NOT VISIBLE BIL NL
TEST SUMMARY
REF.NETA STANDARD
TEST SUMMARY OK FAIL TEBTOT COMMENTS
Z COMPARED TO DRAWING ✓ VE2-02
NAMEPLATE VERIFICATION/CHECK ✓ VERIFIED
H VISUAL INSPECTION ✓ VERIFIED
Z
CONTACT RESISTANCE ✓
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
N
uj THERMAL MAGNETIC TRIP TEST ✓
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓
UV/BLOWN FUSE DEVICES ✓
Vail Breakers
Page 9 of 14
PREPARED FOR
8UARANTEEELECTR/C
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# 350A BREAKER DATE June 4, 2013
TEST RESULTS
IAMB.TEMP 68.7°F HUMIDITY 35
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE(pQ) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 210 220 220
AFTER CLEANING (IF REQ'D) N/A N/A N/A
COMMENTS:
CONTACT RESISTANCE FROM SECTION 1 TOP TO LOAD SIDE BREAKER
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ# D00002 RESULTS (Mfg) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AVE.
THERMAL 30017.(sec)
INST TRIP (LO) amps MANUFACTURER TESTED
INST TRIP (HI) amps
WITHSTAND(MID)
NOTES
1
2
3
4
5
Vail Breakers Page 10 of 14
PREPARED FOR _
ca�R,��rEEE�ECrR�c � �w�w�w
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# 150A BREAKER DATE June 4, 2013
PLANT VAIL WWTF 5TH FROM TOP TEST BY AP
AREA MDP-1 ROOM STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 150 YEAR NL
MODEL HFD NOM.VOLTS 600 POLES 3
CAT# RD65K INT CAP (KA) 65 FREQ. 60
SERIAL# NOT VISIBLE BIL NL
TEST SUMMARY
REF.NETA STANDARD 7.6.1.1
TEST SUMMARY OK FAIL TEBTOT COMMENTS
Z COMPARED TO DRAWING ✓ VE2-02
PNAMEPLATE VERIFICATION/CHECK ✓ VERIFIED
H VISUAL INSPECTION V/ VERIFIED
z
CONTACT RESISTANCE ✓
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
L., ✓
Lu THERMAL MAGNETIC TRIP TEST
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓
UV/BLOWN FUSE DEVICES ✓
Vail Breakers
Page 11 of 14
PREPARED FOR
,90,49,9NMIRICTN/C
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# 150A BREAKER DATE June 4, 2013
TEST RESULTS
AMB.TEMP 68.7°F HUMIDITY 35
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE (p0) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 3500 3500 3500
AFTER CLEANING (IF REQ-D) N/A N/A N/A
COMMENTS:
CONTACT RESISTANCE FROM SECTION I TOP TO LOAD SIDE BREAKER
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ# D00002 RESULTS (MD) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AVE.
THERMAL 300%(sec)
INST TRIP (LO) amps
MANUFACTURER TESTED
INST TRIP (HI) amps
IWITHSTAND (MID)
NOTES
1
2
3
4
5
Vail Breakers Page 12 of 14
PREPARED FOR
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG # ATS BREAKER DATE June 4, 2013
PLANT VAIL WWTF TEST BY AP
AREA BENCH TESTED STANDARD ACCEPTANCE APPROVED BY PC
NAMEPLATE DATA
MANUF. EATON RATED AMPS 30 YEAR NL
MODEL HFD NOM.VOLTS 600 POLES 3
CAT# HFD3030L INT CAP (KA) 65 FREQ. 60
SERIAL# 13032801 BIL NL
TEST SUMMARY
REF.NETA STANDARD
TEST SUMMARY OK FAIL TES TOT COMMENTS
Z COMPARED TO DRAWING ✓ CONFLICT WITH VE2-02
NAMEPLATE VERIFICATION/CHECK ✓ VERIFIED
H VISUAL INSPECTION V, VERIFIED
Z
I
CONTACT RESISTANCE ✓ SEE RESULTS BELOW
INSULATION RESISTANCE ✓ SEE RESULTS BELOW
N
LU
THERMAL MAGNETIC TRIP TEST ✓
INSPECTIONS
DESCRIPTION OK FAIL N/A COMMENTS
AUX WIRING ✓
FUNCTION TEST-OPEN/CLOSE ✓ FUNCTIONED
DIRT ACCUMULATION/CORROSION ✓ CLEAN
TIGHTEN BOLTS/MISSING HARDWARE ✓ TORQUED
STATUS INDICATION ✓ FRONT OF BREAKER
LUGS ✓ CABLES NOT CONNECTED
THERMAL/MAGNETIC TRIP ✓
SHUNT/ELECTRIC TRIP ✓
UV/BLOWN FUSE DEVICES ✓
Vad Breakers
Page 13 of 14
PREPARED FOR --
MOLDED CASE CIRCUIT BREAKER CANF-5E020
WO# G3479-1 TAG# ATS BREAKER DATE June 4,2013
TEST RESULTS
AMB.TEMP 68.7°F HUMIDITY 35
CONTACT RESISTANCE TEST
EQ.# D00003 RESISTANCE (pO) DIAGRAM
DESCRIPTION PHASE A PHASE B PHASE C
INITIAL 3000 3000 3000
AFTER CLEANING (IF REQ'D) N/A N/A N/A
COMMENTS:
LINE TO LOAD OF BREAKER
INSULATION RESISTANCE REFER TO NETA TABLE 100.1
EQ# D00002 RESULTS(Mfg) - 0-0-GND
TEST VOLTS TIME PHASE A PHASE B PHASE C
CONTACTS OPEN 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
CONTACTS CLOSED 500 30 sec. >20 000 >20 000 >20 000
1000 30 sec. >20 000 >20 000 >20 000
THERMAL/MAGNETIC TRIP TEST - PRIMARY INJECTION REFER TO NETA TABLE 100.7 AND 100.8
TESTS PHASE A PHASE B PHASE C MANUF. AVE.
THERMAL 3007o(sec)
INST TRIP (LO) amps
MANUFACTURER TESTED
INST TRIP (HI) amps
IWITHSTAND (MID)
NOTES
1 NEED TO LOOK INTO BREAKER SIZE
2
3
4
5
Vail Breakers Page 14 of 14
GUARA.LT TEE Page / of
ELECTRICAL CONTRACTING 21250 East 31st Circle,Aurora,CO 60011 Nip(303)373-2400 tx (303)373-4722 a gecowest.com
RESISTANCE TESTING OF EQUIPMENT AND FEEDERS 'R� /bco V
Equipment Serial# Cable# Location A T - Gnd B (D -Gnd C m -Gnd N (D - Gnd AO - 13 (l) A T - C (l) SO -CO
f,
Cy(J
7
7
Tested By. l� a " !r'r'r pr
Witness: i
Date:
_GUARANTEE Page of
ELFCTRICAL CONTRACTING 21250 East 31st Circle,Aurora.CO 80011 !,t, (303)373-2400 r,(303)373-x1772\22 .--i,gecowest.com
DESISTANCE TESTING OF EQUIPMENT AND FEEDERS �pc.JQ
Equipment Serial # Cable# Location A m - Gnd 130 - Grid C m - Gnd N (D - Gnd A (P- B 0 A (P - C (D B (P-C
rl
-3 1 J1 rrl
SO
Tested By:
W itness: '/ 1- a' l
0%..e
Date:
GUARANTEE Page of
FLEC'FRICAL co,4'rRACTING 21250 East 31 st Circle,Aurora,CO 80011 (303)373-2400 (303)373-4722 —b gecowe"t.cmr'
RESISTANCE TESTING OF EQUIPMENT AND FEEDERS
Equipment Serial# Cable # Location AO -Gnd B4) - Gnd C (D - Gnd N (l) -Gnd A (D - 13 (1) 0 -CO
("try,
:2
C.,
7
Tested By: 11V lr !- / /!
Witness:
I
Date:
GUARANTEE __ Page / of Z.
ELECTRICAL_ CONTRACTING 21250 East 31st Circle,Aurora.CO 80011 pt,(303)373-2400 f.(303)373-4722 web gecowest.com
RESISTANCE TESTING OF EQUIPMENT AND FEEDERS ' ✓
Equipment Serial# Cable# Location A m -Gnd B m -Gnd C O -Gnd N O - Gnd A m - B 0 A m - C (D B 4)-C m
z 4
. b
i
3
oa
Tested By: , Lalr;
Witness:
(I� ?) Date:
GUARAN TEE Page of
FLFCTRICAI_ CONTRACTING 21250 East 31st Circle,Aurora,CO 80011 pi,(303)373-2400 rx(303) 373-4722 f,gecowest.com
RESISTANCE TESTING OF EQUIPMENT AND FEEDERS 0
Equipment Serial# Cable# Location A 4) -Gnd B 0 -Gnd C (D -Gnd N (P -Gnd A(P - B O A4) -C4) B 0 -C O
r
C><
-3
Z al
p .
Tested By:
Witness: 4
0 1oor
GUARANTEE
,L F C T R I CA L CONTRACTING 21250 East 31st Circle,Aurora,CO 80011 vn(303)373-2400 r.(303)373-4722 wen gecowest.com
TORQUE WRENCH CALIBRATION DATE:
TORQUE APPLICATION DATE: (, —1 5- ►�
EQUIPMENT : - Z
EQUIPMENT SERIAL # : E)N
LOCATION: �1 Qc�i t c �oM
BOLT SIZE:
TORQUE VALUE: S
WORK DONE BY: a
WITNESSED BY: J�r7 K"a kt
GAG u 2
GUARANTEE
FLFCTRICAI. ((7N 7 RA(-TING 21250 East 31st Circle,Aurora.CO 60011 Pn(303)373-2400 r.(303)373-4722 ec gecowest.com
TORQUE WRENCH CALIBRATION DATE:
TORQUE APPLICATION DATE:
EQUIPMENT : h GC -&AA
EQUIPMENT SERIAL # :
LOCATION: E
BOLT SIZE:
TORQUE VALUE: t
WORK DONE BY: a.
WITNESSED BY:
A sc- -y
C' z
GUARANTEE
F,LECTRICAL CONTRACT 1N(; 21250 East 31st Circle,Aurora,CO 80011 ph(303)373-2400 f.(303)373-4722 wco$ecowest.com
TORQUE WRENCH CALIBRATION DATE: q- t:3
TORQUE APPLICATION DATE:
EQUIPMENT : (V\cc I i
EQUIPMENT SERIAL # : qS �r
LOCATION: �� r�
BOLT SIZE:
TORQUE VALUE: 3 ��
WORK DONE BY: YoSf- ?-Jd 't z
WITNESSED BY: unaC�
�kll X
��duj
GUARANTEE
Et-ECCFRICAI. CON I RACTING 21250 East 31st Circle,Aurora,CO 80011 ph(303)3732400 f,(303)373-472 2 ..ten gecowest.com
TORQUE WRENCH CALIBRATION DATE:
TORQUE APPLICATION DATE: - S �
EQUIPMENT : /tACC wes T -
EQUIPMENT SERIAL # : 3 G FIST C �C
LOCATION: E/e (Loo M
BOLT SIZE: 5//z// '1411C h
TORQUE VALUE: 3 6' /- 6_5
WORK DONE BY: 71' M 14,rinJ 12Ya n Swu//a4�
WITNESSED BY: ,50,se 20J r-% fvGZ
A 0 x 3
TI, k`st � .3
C �
IQs c � 3
CVO IA(,1
GUARANTEE
ELECTRICAL CONTRACTING 21250 East 31st Circle,Aurora,CO 80011 ph(303)373-2400 t.(303)373-4722 wen gecowest.com
TORQUE WRENCH CALIBRATION DATE: q- q- /3
TORQUE APPLICATION DATE:
EQUIPMENT : r,
EQUIPMENT SERIAL # :
LOCATION: 66,ne.e,Itn,2
BOLT SIZE: -31,C-
TORQUE VALUE:
WORK DONE BY: ,�• \
WITNESSED BY: ��, ��^ �i ( �L►
fi3
G� PHA
YC
/I --�