HomeMy WebLinkAboutA13-0057 DATA SHEETS DF-52418:E1 •A1-20 MS-9050UD(E) , - Flf'�•�IT�AI'c�I�C1'1S Fire Alarm Control Panel with DACT �y Hvneywell General --..- The Fire•Lite MS-9050UD(E) is a Fire Alarm Control Panel (FACP) and Digital Alarm Communicator/Transmitter (DACT) combined into one circuit board. This compact, intelligent addressable control panel supports up to 50 addressable devices of any type of detectors and modules. With an exten- -[:- - sive list of powerful features,the MS-9050UD programs just like � i Fire•Lite's larger products, yet fits into applications previously - � served only by conventional panels. --�- The MS-9050UD's integral DACT transmits system status � (alarms,troubles,AC loss,etc.)to a Central Station via the pub- lic switched telephone network. It also allows remote and local ` programming of the control panel using the PK-CD Upload/ _ Download utility. In addition, the control panel may be pro- s , ■ grammed or interrogated off-site via the public switched tele- ' � phone network. Any personal computer with WindowsT"� 95 or greater, and compatible modem with a speed of 14.4 kbps or ':� faster and Fire•Lite Upload/Download software kit PK-CD, may _�___'"�_�� � serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walk-test data,current status and system voltages. • Point trouble identification. The power supply and all electronics are contained on a single • Waterflow selection per module point. circuit board supported on a new quick install chassis and • Alarm verification selection per detector point. housed in a metal cabinet. Available accessories include local . Maintenance alert warns when smoke detector dust accumu- and remote upload/download software, remote annunciators, lation is excessive. and reverse polarity/city box transmitter. (4XTMF) One-person audible or silent walk test with walk-test log and New options include a UL listed printer, PRN-6F and the new • printout. IPDACT Internet Monitoring module.The FireWatch Series inter- . System alarm verification selection per detector point. net monitoring modu�es IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet,saving the monthly ' PAS (Positive Alarm Sequence) and Pre-signal per point cost of two telephone lines. Although not required, the second- (NFPA 72 compliant). ary telephone line may be retained providing backup communi- • Up to eight ANN-BUS annunciators cation over the public switched telephone line. • Remote Acknowledge, Alarm Silence, Reset and Drill via NOTE: Unless otherwise specified, the term MS-9050UD is used addressable modules or remote annunciator. in this data sheet to refer to both the MS-9050UD and the MS- • Upload/Download (local or remote) of program and data via 9050UDE FACPs. For MS-9050UDC, refer to DF-60445. integral DACT. Features SLC COMMUNICATION LOOP Listed to UL Standard 864,9th edition. • Single addressable SLC loop which meets NFPA Style 4, 6 � and 7 requirements. • Auto-program (learn mode) reduces installation time. . 50 addressable device capacity(any combination of address- Reports two devices set to the same address. able detectors and modules). • On-board DACT. • Compatible with Fire•Lite's addressable devices(refer to SLC • Two independently programmable Style Z (Class A) or Style Wiring Manual). Y(Class B)NAC circuits. • Selectable strobe synchronization for System Sensor,Whee- NOTIFICATION APPLIANCE CIRCUITS(NACS) lock,and Gentex devices. • Two independently programmable output circuits. Circuits • Remote Acknowledge, Silence, Reset and Drill via address- can be configured for the following outputs: able monitor modules. -Style Y(Class B) • Two programmable relays and one fixed trouble relay. -Style Z(Class A) • Built-in Programmer. –Door Holder Service(cannot be used for notitication appliances) • Telephone Line ACtive LEDs. –Aux Powe1'Soul'Ce(cannot be used for notification appliances) • EIA-232 PC interface. • Silence Inhibit and Autosilence timer options. • Integral 80-character LCD display with backlighting. • Continuous, March Time, Temporal or California code for • Real-time clock/calendar with automatic daylight savings main circuit board NACs with two-stage capability. control. • Selectable strobe synchronization per NAC. • History file with 500 event capacity. • 2.5 A total power for NACs. • Automatic detector sensitivity testing(NFPA 72 compliant). NOTE: Maximum or total 24VDC system power shared between • Automatic device type-code verification. all NAC circuits and the ANN-BUS is 2.7 A. DF-52418:E1 •1/27/12—Page 1 of 4 PROGRAMMING AND SOFTWARE -__ • Autoprogram (learn mode) reduces installation time. � • Custom English labels (per point) may be manually entered or selected from an internal library file. r • Two programmable Form-C relay outputs. - � • 20 software zones. • Continuous fire protection during online programming at the __ front panel. MS-9o5oUD • Program Check automatically catches common errors not FireAlarm !"I�. linked to any zone or input point. Control Panel _ __�� � OFFLINE PROGRAMMING: Create the entire program in � ANN-8o your office using a Windows0-based software package(order � programming kit PK-CD, containing PS-Tools, separately). � r � � Upload/download system programming locally. SD355 Printer Vser interface Photo Detector Gateway LED INDICATORS ANN-S/PG • AC Power(green) I�, • Fire Alarm (red) • Supervisory(yellow) AD355 Graphic LED Module • Trouble(yellow) Adapt Detector ANN-I/0 • Alarm Silenced signals(yellow) p�- KEYPAD �'°� • 16 key alpha-numeric pad H355/H355R/H355HT Relay Motlule • Acknowledge/Step Heat Detector ANN-RLY p2R • Alarm Silenced Strobe • Drill(Manual Evacuate) � • Reset(lamp test) M�F-300 Product Line Information Dual Monitor Module P2R MS-9050UD(E): Combination DACT/Fire Alarm Control Panel Strobe with one SLC loop. Includes main circuit board with display, Power Supply chassis with transformer,backbox with door,plastic bag contain- � _ FCPS-2aFS6 ing screws, cables, key, etc., manual. (For MS-9050UDC, refer '—' FCPS-24FS8 - SD355T to DF-60445.) Photo/Thermal P2R PK-CD: Contains PS-Tools programming software for Win- Strobe dows0-based PC computer(cable not included). � DP-51050: Optional dress panel for the MS-9050UD. Multi-Modules TR-CE:Optional trim ring for semi-flush mounting. MMF-300 • CRF-300-6 Six-Relay Control Module BB-2F:Optional cabinet for one or two modules. Monitor Module • CMF-300-6 Six-Circuit Supervised Control Module BB-6F: Optional cabinet for up to six modules mounted on • MMF-302-6 Six-Zone Intertace Module CHS-6 chassis. : • MMF-300-10 Ten-Input Monitor Module gg_26: Battery backbox, holds up to two 25 AH batteries and � CHG-75. MMF-3o2 BB-55F: Battery box, houses two 55 AH batteries 2-Wire Detector Monitor Motlule � CHS-6: Chassis, mounts up to six multi-modules in a BB-6F � cabinet. � � CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. D355PL Beam Detector CHG-120F: Remote battery charging system for lead-acid bat- Duct Detector BEAM-335/(S) teries with a rating of 55 to 120 AH. Requires additional BB-55F for mounting. MS-9050UD BAT Series: Batteries,see data sheet DF-52397. PRT/PK-CABLE: Cable printer/personal computer interface � ADDRESSABLE FIRE ALARM cable. CONTROL PANEL PRN-6F: UL listed compatible event printer. Uses tractor fed BG-12LX Atltlressable paper. Manual Pull Station IPDACT, IPDACT 2/2UD Internet Monitoring Module: Mounts in bottom of enclosure with optional mounting kit (PN IPBRKT). Connects to primary and secondary DACT telephone output ports for internet communications over customer provided ether- Page 2 of 4—DF-52418:E1 •1/27/12 net internet connection. Requires compatible Teldat Visoralarm 4.0"(10.16 cm.)box. Includes plastic cover plate and end-of-line Central Station Receiver. Can use DHCP or static IP. (See data resistor.Module may be configured for either a Style B(Class B) sheet df-52424 for more information.) or Style D(Class A) IDC. IPBRKT: Mounting kit for IPDACT-2/2UD in common enclosure. MDF-300: Dual Monitor Module. Same as MMF-300 except it IPSPLT:Y-adaptor option allows connection of both panel dialer provides two Style B(Class B)only IDCs. outputs to one IPDACT-2/2UD cable input. MMF-301: Miniature version of MMF-300. Excludes LED and AC-TRMBLK: AC Terminal Block mounts to a metal bracket, in Style D option. Connects with wire pigtails. May mount in device turn, mounts to the FACP chassis. Use AC-TRMBLK when wire backbox. nuts are not allowed for AC connections to the transformer. MMF-302A:Similar to MMF-300A.Addressable Monitor Module for one zone of conventional two-wire detectors. Requires reset- OPTIONAL MODULES table 24 VDC power. Refer to the Device Compatibility Docu- 4XTMF Reverse Polarity Transmitter Module: Provides a ment for listed compatible devices and quantity limitation. supervised output for local energy municipal box transmitter, CMF-300:Addressable Control Module for one Style Y/Z(Class alarm and trouble. Includes a disable switch and disable trouble g�A) zone of supervised polarized Notification Appliances. LED. Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification ANN-SEC: Optional secondary ANN-BUS interface module. Appliance Circuit option requires external 24 VDC to power noti- Note: Used on�y with firmware 3.0 or higher. fication appliances. COMPATIBLE ANNUNCIATORS CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. ANN-80(-W): Remote LCD annunciator mimics the information Mounts directly to a 4.0" (10.16 cm.) box, surface mount using displayed on the FACP LCD display. Recommended wire type is the SMB500. un-shielded.(Basic model is red;order-W version for white;see gG-12LX: Addressable manual pull station with interface mod- DF-52417.) ule mounted inside. ANN-I/O: LED Driver Module provides connections to a user 1300:This module isolates the SLC loop from short circuit condi- supplied graphic annunciator. (See DF-52430.) tions(required for Style 6 or 7 operation). ANN-LED: Annunciator Module provides three LEDs for each SMB500: Used to mount all modules except the MMF-301 and zone: Alarm, Trouble, and Supervisory. Ships with red enclo- M301. sure. (See DF-60241.) ANN-RLED: Provides alarm (red) indicators for up to 30 input MMF-300-10:Ten-input monitor module. Mount one or two mod- zones or addressable points. (See DF-60241.) ules in a BB-2F cabinet(optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. ANN-RLY: Relay Module provides 10 programmable Form-C MMF-302-6: Six-zone interface module.Mount one or two mod- relays. Can be mounted inside the cabinet. (See DF-52431.) ules in a BB-2F cabinet(optional). Mount up to six modules on a ANN-S/PG: Serial/Para�lel Printer Gateway module provides a CHS-6 chassis in a BB-6F cabinet. connection for a serial or parallel printer. (See DF-52429.) CMF-300-6:Six-circuit supervised control module.Mount one or ADDRESSABLE DEVICES two modules in a BB-2F cabinet(optional).Mount up to six mod- All feature a polling LED and rotary switches for addressing. ules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6: Six-relay control module (Form-C relays). Mount CP355:Addressable low-profile ionization smoke detector. one or two modules in a BB-2F cabinet (optional). Mount up to SD355:Addressable low-profile photoelectric smoke detector. six modules on a CHS-6 chassis in a BB-6F cabinet. SD355T: Addressable low-profile photoelectric smoke detector NOTE: For more information on Compatible Addressabie Devices with thermal sensor. for use with the MS-9050UD,see the following data sheets(docu- SD355R: Remote test capable addressable photoelectric ment numbers): AD355 (DF-52386), BG-12LX (DF-52013), CMF- smoke detector for use with DNR(W)duct detector housing. 300-6(DF-52365),CRF-300-6(DF-52374),CMF/CRF Series(DF- 52130), CP355 (DF-52383), H355 Series (DF-52385), 1300 (DF- H355: Fast-response, low-profile heat detector. 52389), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10 H355R: Fast-response, low-profile heat detector with rate-of- (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF- rise option. 52384). H355HT: Fast-response, low-profile heat detector that activates ADDRESSABLE DEVICE ACCESSORIES at 190°F/88°C. End-of-Line Resistor Assembly (R-47K and R-3.9K): The AD355: Low-profile, intelligent, "AdapY' multi-sensor detector 47k ohm assembly supervises the MMF-300, MDF-300, MMF- (B350LP base included). 301, and CMF-300 module circuits. The 3.9k ohm assembly BEAM355: Intelligent beam smoke detector. supervises the MMF-302 module circuit. These resistors are BEAM355S: Intelligent beam smoke detector with integral sen- included with each module. sitivity test. Power Supervision Relay: Supervises the power to 4-wire D355PL: InnovairFlex low-flow non-relay duct-detector housing; smoke detectors and notification appliances. includes SD355R. DNR: InnovairFlex low-flow non-relay duct-detector housing. W�ring Requirements (Order SD355R separately.) While shielded wire is not required, it is recommended that all DNRW: InnovairFlex low-flow non-relay duct-detector housing, SLC wiring be twisted-pair to minimize the effects of electrical with NEMA-4 rating. Watertight. (Order SD355R separately.) interference. Refer to the panel manual for wiring details. MMF-300: Addressable Monitor Module for one zone of nor- mally-open dry-contact initiating devices. Mounts in standard DF-52418:E1 •1/27/12—Page 3 of 4 SYSTEM SPECIFICATIONS System Capacity condensing) at 32°C ± 2°C (90°F ± 3°F). However, the usefu� life of the system's standby batteries and the electronic compo- • Intelligent Signalling Line Circuits......................................... 1 nents may be adversely affected by extreme temperature ranges • Addressable device capacity..............................................50 and humidity. Therefore,it is recommended that this system and • Programmable software zones...........................................20 its peripherals be installed in an environment with a normal room • Annunciators.........................................................................8 temperature of 15—27°C/60—80°F. Electrical Specifications NFPA Standards AC Power: MS-9050UD 120 VAC,60 Hz, 3.0 A. MS-9050UDE: The MS-9050UD(E) complies with the following NFPA 72 Fire 240 VAC,50 Hz, 1.5 A.Wire size:minimum 14 AWG(2.00 mm2) Alarm Systems requirements: with 600 V insulation. Nonpower-limited,supervised. —LOCAL (Automatic, Manual, Waterflow and Sprinkler Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger Supervisory). Capacity: 7-18 AH (MS-9050UD cabinet holds maximum of two —AUXILIARY (Automatic, Manual and Waterflow) (requires 18 AH batteries.) 4XTMF). Communication Loop: Supervised and power-limited. —REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and Notification Appliance Circuits: Terminal Block provides con- supervisory relays may be connected to UL 864 listed nections for two NACs, Style Y (Class B) or Style Z (Class A). transmitters. For reverse polarity signaling of alarm and Special Application power. Power-limited, supervised circuitry. trouble,4XTMF is required.) Maximum signaling current per circuit:2.5 A. End-of-Line Resis- _pROPRIETARY(Automatic, Manual and Waterflow). tor:4.7k ohm,�/z watt(P/N 71252 UL listed)for Style Y(Class B) NAC. Refer to the Fire•Lite Device Compatibility Document for —CENTRAL STATION (Automatic, Manual and Waterflow, listed compatible devices. and Sprinkler Supervised). Two Programmable Relays and One Fixed Trouble Relay: —OT, PSDN (Other Technologies, Packet-switched Data Net- Contact rating: 2.0 A@ 30 VDC (resistive), 0.5 A@ 30 VAC Work) (resistive). Form-C relays, nonpower-limited, nonsupervised. Agency Listings and Approvals Cabinet Specifications The listings and approvals below apply to the basic MS- Door: 19.26"(48.92 cm.) high x 16.82" (42.73 cm.)wide x 0.72" 9050UD(E) control panel. In some cases, certain modules may (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" not be listed by certain approval agencies, or listing may be in (42.29 cm.)wide x 5.25" (13.34 cm.) deep.Trim Ring(TR-CE): process.Consult factory for latest listing status. 22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide. • UL: S624 • FM approved Shipping Specifications • CSFM:7165-0075:210 Weight: 26.9 Ibs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) • MEA:442-06-E high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. NOTE: See DF-60445 for ULC-listed model. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 — 49°C/32—120°F and at a relative humidity 93%±2%RH (non- FireLiteOO AlarmsO and System SensorC� are registered trademarks of Honeywell International Inc. MicrosoftOO and Windows0 are registered trademarks of the Microsoft Corporation. �02012 by Ho�eywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING&MANUFACTURINC All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 4 of 4—DF-52418:E1 •1/27/12 df-52417:c•B-90 ANN-so � Fire•�iTe�A�arms 80-Character LCD Seria� �►nnunciator by Honeywell General The ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC ,-� ` Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi- tions. The ANN-80 and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. �� Connected devices are powered, via two additional wires, by w ,1,� � either the host FACP or a remote UL-listed,filtered power supply. � � ANN-80 is red;for white,order ANN-80-W. � � The ANN-80 displays English-language text of system point _, __ _ � information including device type, zone, independent point ., ' alarm, trouble or supervisory status, as well as any custom �\�'►\�.a�...�l�\� alpha labels programmed into the control panel. It includes con- I � trol switches for remote control of critical system functions. (A �_ keyswitch prevents unauthorized operation of the control m �._..._, • switches.) , �—� �--� Up to eight ANN-80s may be connected to the ANN-BUS of each FACP No programming is required, which saves time dur- � ing system commissioning. 1"' � � �, ��� Features • Listed to UL Standard 864,9th Edition. • Backlit 80-character LCD display(20 characters x 4 lines). • Supervisory • Mimics all display information from the host panel. • Alarm Silenced • Control switches for System Acknowledge, Signal Silence, Drill,and Reset. $pecifications • Control switches can be independently enabled or disabled • Operating voltage range: 18 VDC to 28 VDC. at the FACP. • Current consumption @ 24 VDC nominal(filtered and non- • Keyswitch enables/disables control switches and mechani- resettable):40 mA maximum. cally locks annunciator enclosure • Ambient temperature:32°F to 120°F(0°C to 49°C). • Keyswitch can be enabled or disabled at the FACP. • Relative humidity: 93% ±2% RH (noncondensing) at 32°C • Enclosure supervised for tamper. ±2°C(90°F±3°F). • System status LEDs for AC Power, Alarm, Trouble, Supervi- • 5.375" (13.65 cm.) high x 6.875" (17.46 cm.) wide x 1.375" sory,and Alarm Silence. (3.49 cm.)deep. • Local sounder can be enabled or disabled at the FACP. • For use indoors in a dry location. • ANN-80 connects to the ANN-BUS terminal on the FACP and • All connections are power-limited and supervised. requires minimal panel programming. • Displays device type identifiers, individual point alarm, trou- pgency Listings and Approvals ble,supervisory,zone,and custom alpha labels. • Time-and date display field. The listings and approvals below apply to the ANN-80. In some cases, certain modules may not be listed by certain approval • Surface mount directly to wall or to single, double, or 4" agencies, or listing may be in process. Consult factory for latest square electrical box. listing status. • Semi-flush mount to single, double, or 4" square electrical . UL: S2424 box. Use ANN-SB80KIT for angled view mounting. • Can be remotely located up to 6,000 feet(1,800 m)from the ' FM approved panel. • CSFM: 7120-0075:211 • Backlight turns off during AC loss to conserve battery power • MEA:442-06-E but will turn back on if an alarm condition occurs. • May be powered by 24 VDC from the host FACP or by remote The ANN-BUS power supply(requires 24 VDC). • Up to eight ANN-SOs can be connected on the ANN-BUS. POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY Controls and Indicators The ANN-BUS can be powered by an auxiliary power supply when the maximum number of ANN-BUS devices exceeds the • AC Power ANN-BUS power requirements. See the FACP manual for more • Alarm information. • Trouble df-52417:c•05/22/09—Page 1 of 2 ANN-BUS DEVICE ADDRESSING After ca�culating the total worst case current draw, the following Each ANN-BUS device requires a unique address (ID Number) table specifies the maximum distance the modules can be in order to communicate with the FACP A maximum of 8 devices located from the FACP on a single wire run. The table ensures can be connected to the FACP ANN-BUS communication circuit. 6.0 volts of line drop maximum. In general,the wire length is lim- See the FACP manual for more information. ited by resistance, but for heavier wire gauges, capacitance is the limiting factor. WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT These cases are marked in the chart with an asterisk ('). Maxi- The ANN-80 connects to the FACP ANN-BUS communications mum length can never be more than 6,000 feet (1,800 m), circuit. To determine the type of wire and the maximum wiring regardless of gauge used. See table below. distance that can be used with FACP ANN-BUS accessory mod- WIRE REQUIREMENTS: POWER CIRCUIT ules, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus.The total worst • 14 to 18 AWG (0.75 -2.08 mm2) wire for 24 VDC power cir- case current draw is calculated by adding the individual worst cuit is acceptable. Power wire distance limitation is set by 1.2 case currents for each module. volt maximum line drop form source to end of circuit. NOTE: For total worst case current draw on a single ANN-BUS • All connections are power-limited and supervised. refer to appropriate FACP manual. • A maximum of eight ANN-80 modules may be connected to this circuit. Communication Pair Wiring Distance: FACP to Last ANN-BUS Module Total Worst Case 22 Gauge 18 Gauge 16 Gauge 14 Gauge Current Draw(amps) 0.100 1,852 ft. 4,688 ft. '6,000 ft. `6,000 ft. 0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft. 0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft. 0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft. 0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft. 0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft. 0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft. 0.800 231 ft. 586 ft. 933 ft. 1,476 ft. 0.900 206 ft. 521 ft. 829 ft. 1,312 ft. 1.000(max.) 185 ft. 469 ft. 746 ft. 1,181 ft. WIRING CONFIGURATION ORDERING OPTIONS: The following figure illustrates the wiring between the FACP and ANN-80: Red 80 character LCD Annunciator. ANN-BUS devices. ANN-80-W:White,80 character LCD Annunciator. ANN-BUS and power ANN-S880KIT R: Red surface mount backbox with angled wiring are supervised wedge. and power-limited. ANN-SB80KIT W: White surface mount backbox with angled � e A . _ wedge. T61 4 3 2 1 ANN-BUS Device (- + ne O MS-9050UD res 1 2 3 4 5 6 7 8 FACP Wiring to ANN-BUS Device FireLiteO Alarms is a registered trademark of Honeywell International Inc. 02009 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. - We cannot cover all specific applications or anticipate all requirements. ENGINEERING&MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 2 of 2—df-52417:c•05/22/09 DF-52013:D•E-100 BG-12�x � Fire•�iTe�A�arms Addressable Manual Pull Station by H o n eywe I I - , - General The Fire•Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for . Fire•Lite's addressable fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station.This II leads fire personnel quickly to the location of the alarm. Features . Maintenance personnel can open station for inspection and � � address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word"ACTIVATED" appears to clearly indicate the station has been operated. - • Captive screw terminals wire-ready for easy connection to �,,✓ � ' SLC loop(accepts up to 12 AWG/3.25 mm2 wire). - • Can be surface mounted (with SB-10 or SB-I/O) or semi- r flush mounted. Semi-flush mount to a standard single- ___ ___ gang,double-gang,or 4" (10.16 cm)square electrical box. - -- • Smooth dual-action design. � a' • Meets ADAAG controls and operating mechanisms guide- LL lines (Section 4.1.3[13]); meets ADA requirement for 5 Ib. maximum activation force. • Highly visible. usually needed for semi-flush mounting with 4" (10.16 cm) or • Attractive shape and textured finish. double-gang boxes(not with single-gang boxes). • Key reset. • Includes Braille text on station handle. Operation • Optional trim ring(BG12TR). Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word "ACTI- • Meets UL 38, Standard for Manually Actuated Signaling VATED" (in bright yellow) appears at the top of the handle, Boxes. while a portion of the handle protrudes from the bottom of the station.To reset the station, simply unlock the station with the Construction key and pull the door open.This action resets the handle;clos- Shell, door, and handle are molded of durable polycarbonate ing the door automatically resets the switch. material with a textured finish. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual Specifications switch.Two rotary decimal switches allow address settings (1 —159 with Breakaway Tab removed for MS-9600 Series, 1 — • Shipping Weight: 9.6 oz. (272.15 g) 99 and MS-9200UDLS, 1 —50 for MS-9050UD). • Normal operating voltage:24 VDC. • nnaximum s�c ioop voitage:2a.o v�c. Architectural/Engineering • Maximum SLC standby current: 375�A. $pecifications • Maximum SLC alarm current:5 mA. Manual Fire Alarm Stations shall be non-coded, with a key- • Temperature Range:32°F to 120°F(0°C to 49°C) operated reset lock in order that they may be tested, and so • Relative Humidity: 10%to 93%(noncondensing) designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key.An operated sta- • For use indoors in a dry location tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of Installation red-colored polycarbonate material with clearly visible operat- The BG-12LX will mount semi-flush into a single-gang,double- ing instructions provided on the cover. The word FIRE shall gang,or standard 4" (10.16 cm)square electrical outlet box,or appear on the front of the stations in white letters, 1.00 inches will surface mount to the model SB-10 or SB-I/O surface back- �2•54 cm) or larger. Stations shall be suitable for surface box. If the BG-12LX is being semi-flush mounted, then the mounting on matching backbox SB-10 or SB-I/O;or semi-flush optional trim ring (BG12TR) may be used. The BG12TR is mounting on a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box, and shall be installed DF-52013:D•4/13/2012—Page 1 of 2 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR:Optional trim ring. 17003: Keys,set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess.Consult factory for latest listing status. • UUULC Listed: S711 (listed for Canadian and non-Cana- dian applications). • MEA:67-02-E. • CSFM: 7150-0075:0184. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. FireLiteOO Alarms�is a registered trademark of Honeywell International Inc. �02012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. - We cannot cover all specific applications or anticipate all requirements. EN6INEERIN6 8 MANUFACTURIN& All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 2 of 2—DF-52013:D•4/13/2012 DF-52384:C•E-160 SD355(A) Series � Flf''e•LIT��A�arms Addressable Photoelectric Smoke Detectors by H o n eywe I I - , - General The SD355(A), SD355T(A), and SD355R(A)addressable, low- profile plug-in photoelectric detectors use a state-of-the-art pho- __ toelectric sensing chamber with communications to provide open area protection and are used exclusively with Fire•Lite's �'` - Addressable Fire Alarm Control Panels (FACPs). The SD355T(A)adds thermal sensors that will alarm at a fixed tem- ` - - � perature of 135°F (57°C). Since these detectors are address- able, they will help emergency personnel quickly locate a fire � during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sen- sor light to provide a local, visible sensor indication. Remote ��1 LED annunciator capability is available as an optional acces- •���,• sory, PN RA100Z(A). The SD355R(A) is a remote test capable detector for use with D355PL(A) or DNR(A)/DNRW duct smoke detector housings. SD355(A) in B210LP(A) Base m Features s�c ioop Applications • Two-wire loop connection. Use photoelectric detectors in Iife-safety applications to provide • Unit uses base for wiring. a broad range of fire-sensing capability, especially where smol- Addressing dering fires are anticipated. lonization detectors are often better • Addressable by device. than photoelectric detectors at sensing fast,flaming fires. • Rotary, decimal addressing: 01 – 99 with MS-9200 series, and 01 –159 with MS-9600 series. Construction Architecture These detectors are constructed of off-white fire resistant plas- • Unique single-source, dual-chamber design to respond tic. SD355(A) series plug-in, low-profile smoke detectors are quickly and dependably to a broad range of fires. designed to commercial standards and offer an attractive • Sleek, low-profile design. appearance. • Integral communications and built-in type identification. �nstallation • Built-in tamper-resistant feature. • Removable cover and insect-resistant screen for simple field SD355(A) series plug-in detectors use a detachable mounting cleaning. base to simplify installation,service and maintenance. Operation Mount base(all base types)on an electrical backbox which is at • Withstands air velocities up to 4,000 feet-per-minute (20 m/ least 1.5" (3.81 cm) deep. For a chart of compatible junction sec.)without triggering a false alarm. boxes,see DF-60059. • Factory preset at 1.5% nominal sensitivity for panel alarm NOTE: Because of the inherent supervision provided by the SLC threshold level. loop, end-of-line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4 (Class B) wiring. SD355R(A) • Visible LED"blinks"when the unit is addressed(communicat- mounts in a D355PL(A)or DNR(A)/DNRW duct detector housing. ing with the fire panel)and latches on in alarm. Mechanicals Operation • Sealed against back pressure. Each SD355(A) series detector uses one of 99 possible • Direct surface mounting or electrical box mounting. addresses on the MS-9200 series and up to 318 (159 on each • Mounts to:single-gang box,3.5"(8.89 cm)or 4.0"(10.16 cm) loop) on the MS-9600 series Signaling Line Circuit (SLC). It octagonal box,or 4.0"(10.16 cm)square electrical box(using responds to regular polls from the system and reports its type a plaster ring—included). and status. Other system features The addressable photoelectric sensor in the SD355(A) series • Fully coated circuit boards and superior RF/transient protec- has a unique unipolar chamberthat responds quickly and uni- tion. formly to a broad range of smoke conditions. It can withstand • 94-VO plastic flammability rating. wind gusts up to 4,000 feet-per-minute (20 m/sec.) without • Low standby current. sending an alarm level signal. Because of its unipolar chamber, the SD355(A) series is approximately two times more respon- Options sive than most photoelectric sensors.This makes it a more sta- • Remote LED output connection, PN RA100Z(A). ble detector. DF-52384:C•12/07/2011—Page 1 of 2 Detector Sensitivity Test INTELLIGENT BASES Each detector can have its sensitivity tested (required per NFPA NOTE:"A"suffix indicates ULC Listed model. 72, Chapter 14 on Inspection, Testing and Maintenance) when NOTE:The detector's plug-in base can be changed off for special installed/connected to a MS-9200 series or MS-9600 series applications. For details about intelligent bases and their mount- addressabie fire alarm control panel.The results of the sensitiv- ing,see DF-60059. ity test can be printed off the MS-9200 series or MS-9600 series B2�OLP(A): Plug-in detector base (included); standard U.S. for record keeping. flanged low-profile mounting base. B210LPBP: Bulk pack of B210LP;package contains 10. Specification B501(A):Standard European flangeless mounting base. Voltage range: 15-32 VDC(peak). B501 BP: Bulk pack of 6501; package contains 10. Standby current:300 NA @ 24 VDC. B200SR(A): Intelligent sounder base capable of producing LED current:6.5 mA @ 24 VDC(latched"ON"). sound output with ANSI Temporal 3 or continuous tone. Air velocity:4,000 ft./min.(20 m/sec.)maximum. Replaces B501 BH series bases in retrofit applications. Size:2.1"(5.33 cm) high; base determines diameter. B224RB(A): Plug-in System Sensor relay base. Screw termi- -6210LP(A):6.1"(15.5 cm)diameter. nals: up to 14 AWG (2.0 mmz). Relay type: Form-C. Rating: 2.0 A@ 30 VDC resistive; 0.3 A@ 110 VDC inductive; 1.0 A@ 30 -6501(A):4.1"(10.4 cm)diameter. VDC inductive. -B200SR(A):6.875" (17.46 cm)diameter. g224B1(A): Plug-in System Sensor isolator detector base. -B224RB(A):6.2" (15.748 cm)diameter. Maximum 25 devices between isolator bases(see DF-52389). Weight:3.6 oz. (102 g). ACCESSORIES Operating temperature range: for SD355(A): 0°C to 49°C F110: Retrofit flange to convert 6210LP(A) to match the (32°F to 120°F); for SD355T(A): 0°C to 38°C (32°F to 100°F). g350LP(A) profile, or to convert older high-profile bases to low- SD355R(A): installed in a DNR(A)/DNRW -20°C to 70°C (-4°F profile. to 158°F). F110BP: Bulk pack of F110; package contains 15. Temperature:0°C-49°C(32°F-120°F). F210: Replacement flange for B210LP(A)base. Relative humidity: 10%-93%, non-condensing. RA1002(A): Remote LED annunciator.3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and Listings B210LP(A)bases only. Listings and approvals below apply to the SD355(A), SM6600: Surface mounting kit SD355T(A),and SD355RT(A)detectors. In some cases,certain M02-04-OO:Test magnet. modules may not be listed by certain approval agencies, or list- ing may be in process. Consult factory for latest listing status. M02-09-00:Test magnet with telescoping handle. • UL Listed: S1059. XR2B: Detector removal tool. Allows installation and/or removal • ULC Listed: S1059. of detector heads from bases in high ceiling applications. • CSFM:7272-0075:0194. XP-4: Extension pole for XR2B.Comes in three 5-foot(1.524 m) • MEA:243-02-E. sections. • FM approved. T55-127-010: Detector removal tool without pole. BCK-200B: Black detector covers for use with SD355(A) only; Product Line Information box of 10. WCK-200B: White detector covers for use with SD355(A) only; NOTE:"A"suffix indicates ULC Listed model. box of 10. SD355: Adressable photoelectric detector; B210LP base included. SD355A: Sames as SD355 with ULC Listing; B210LPA base included. SD355T: Same as SD355 but with thermal element; B210LP base included. SD355TA: Same as SD355T with ULC Listing; B210LPA base included. SD355R: Remote test capable addressable photoelectric detec- tor for use with a D355PL(A) or DNRA/DNRW duct detector housing; B210LP base included. SD355RA: Same as SD355R with ULC Listing for use with a D355PLA or DNRA duct detector housing; 6210LPA base InClUded. Fire•LiteOO Alarms is a registered trademark of Honeywell International Inc. �02011 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. - We cannot cover all specific applications or anticipate all requirements. EN6INEERIN6 8 MANUFACTURIN& All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 2 of 2-DF-52384:C•12/07/2011 DF-52385:D•E-710 H355(A) Series � Flf'�•LITE�ALc�I�C1'1� Intelligent Addressable Thermal Detectors �y H v n eywe I I - , - General The Fire•Lite Alarms H355(A) Series thermal detectors are addressable sensors that use a state-of-the-art thermistor �i `" sensing circuit for fast response.These sensors provide open- �' area protection and are intended for use with Fire•Lite's addressable Fire Alarm Control Panels(FACPs). The H355(A) and H355R(A) sensors provide fixed tempera- - I�: ture alarm detection at 135°F (57°C). The H355R(A) sensor � � also responds to rate-of-rise conditions of greater than 15°F (8.3°C) per minute. The H355HT(A) is a fixed high-tempera- ��� ture detector that activates at 190°F (88°C). These thermal .� detectors provide addressable property protection in a variety of applications. Two LEDs on each sensor light to provide a local, visible sen- H355(A) in B210LP(A) Base m sor indication. Remote LED annunciator capability is available using an optional accessory,the RA100Z. • 94-5V plastic flammability rating. Features options: SLC loop: • Remote LED output connection to optional RA100Z remote LED annunciator. • Two-wire SLC loop connection. • Flanged surface mounting kit. • Unit uses base for wiring. addressiny: Installation • Addressable by device. H355(A) Series plug-in intelligent thermal detectors use a • Rotary, decimal addressing: 01 —159 with MS-9600 series, detachable base to simplify installation, service and mainte- 01 —99 with MS-9200 series. nance. Installation instructions are shipped with each detector. Architecture: Mount base (all base types) on an electrical backbox which is • Sleek, low-profile,stylish design. at least 1.5"(3.81 cm)deep. For a chart of compatible junction • State-of-the-art thermistor technology for fast response. boxes,see DF-60059. • Integral communications and built-in device-type identifica- NOTE: Because of the inherent supervision provided by the SLC tion. loop, end-of-line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4(Class"B")wiring only. • Built-in tamper resistant feature. • Built-in functional test switch activated by external magnet. App�jC1t10f1S Operation: Use thermal detectors for protection of property. • Factory preset at 135°F (57°C) for the H355(A) and H355R(A); 190°F(88°C)for the H355HT(A). (;onstruction • Rate-of-rise triggers at 15°F (8.3°C) per minute for the H355R(A). These detectors are constructed of off-white fire-resistant plastic. The H355(A) Series plug-in intelligent thermal detec- • 360°-field viewing angle of the visual alarm indicators (two tors are designed to commercial standards and offer an attrac- bicolor LEDs). LEDs blink red in Normal condition and turn tive appearance. on steady red in Alarm. • Visible LEDs"blink"every time the unit is addressed. Qperation Mechanicals: Each H355(A) Series detector uses one of 159 (MS-9600 • Sealed against back pressure. series) or 99 (MS-9200 series) possible addresses on a con- • SEMS screws for wiring of the separate base. trol panel SLC loop. It responds to regular polls from the con- • Designed for direct-surface or electrical-box mounting. trol panel and reports its type and the status. If it receives a Plugs into separate base for ease of installation and main- test command from the panel (or a local magnet test), it stimu- • tenance. lates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the • Separate base allows interchange of photoelectric, ioniza- panel. The H355(A) Series offers features and performance tion and thermal sensors. that represent the latest in thermal detector technology. Other system features: • Remote test feature from the panel. • Walk test with address display. • Low standby current. DF-52385:D•5/17/2013—Page 1 of 2 Spefications INTELLIGENT BASES Size:2.1" (5.3 cm)high; base determines diameter. NOTE:"A"suffix indicates ULC Listed model. —B210LP(A): 6.1" (15.5 cm)diameter. NOTE:The detector's plug-in base can be changed off for special applications. For details about intelligent bases and their mount- —B501(A):4.1" (10.4 cm)diameter. ing,see DF-60059. —B200SR(A):6.875" (17.46 cm)diameter. B210LP(A): Plug-in detector base (included); standard U.S. —B224RB(A): 6.2" (15.745 cm)diameter. flanged low-profile mounting base. Shipping weight:4.8 oz. (137 g). B210LPBP: Bulk pack of B210LP; package contains 10. Installation temperature: B501(A): Standard European flangeless mounting base. —H355(A), H355R(A):—4°F to 100°F(-20°C to 38°C). B501 BP: Bulk pack of B501; package contains 10. —H355HT(A):—4°F to 150°F(-20°C to 66°C). B200SR(A): Intelligent sounder base capable of producing Humidity range: 10% to 93% relative humidity (noncon- sound output with ANSI Temporal 3 or continuous tone. densing). Replaces B501 BH series bases in retrofit applications. Voltage range: 15 to 32 VDC peak. B224RB(A): Plug-in System Sensor relay base. Screw termi- Standby current: 300 �aA @ 24 VDC (one communication nals: up to 14 AWG(2.0 mm2). Relay type: Form-C. Rating:2.0 every five seconds with LED blink enabled). A@ 30 VDC resistive; 0.3 A@ 110 VDC inductive; 1.0 A@ 30 VDC inductive. LED current:6.5 mA @ 24 VDC. B224BI(A): Plug-in System Sensor isolator detector base. Mounting: B210LP(A) flanged base, included. See "Product Maximum 25 devices between isolator bases(see DF-52389). Line Information: Intelligent Bases"if using a different base. Fixed-temperature setpoint: 135°F (57°C) for the H355(A) ACCESSORIES and H355R(A); 190°F(88°C)for the H355HT(A). F110: Retrofit flange to convert B210LP(A) to match the Rate-of-rise detection: responds to greater than 15°F(8.3°C) B350LP(A) profile, or to convert older high-profile bases to per minute. low-profile. F110BP: Bulk pack of F110;package contains 15. Listings and Approvals F210: Replacement flange for B210LP(A)base. Listings and approvals below apply to the H355(A) Series RA100Z(A): Remote LED annunciator. 3—32 VDC. Mounts to detectors. In some cases, certain modules may not be listed a U.S. single-gang electrical box. For use with B501(A) and by certain approval agencies, or listing may be in process. B210LP(A) bases only. Consult factory for latest listing status. SM6600: Surface mounting kit • UL Listed:S2517. M02-04-OO:Test magnet. • ULC Listed (models H355A, H355RA, H355HTA). M02-09-00:Test magnet with telescoping handle. • CSFM approved: 7270-0075:0195. FM approved. XR2B: Detector removal tool. Allows installation and/or � removal of detector heads from bases in high ceiling applica- tions. Product Line Information XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 NOTE:"A"suffix indicates ULC Listed model. m)sections. H355: Intelligent thermal sensor; 135°F(57°C);6210LP base T55-127-010: Detector removal tool without pole. included. H355A: Same as H355 but with ULC Listing; B210LPA base included. H355R: Same as H355 with rate-of-rise feature; B210LP base included. H355RA: Same as H355R but with ULC Listing; B210LPA base included. H355HT: Intelligent fixed high-temperature thermal detector; 190° F(88°C); B210LP base included. H355HTA: Same as H355HT but with ULC Listing; B210LPA base included. Fire•LiteOO Alarms is a registered trademark of Honeywell International Inc. �02013 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING&MANUFACTURINC All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 2 of 2—DF-52385:D•5/17/2013 •i, L V L P R 0 D U C T I N F 0 R M A T I 0 N B U L L E T I N � � .;.; . . 449 / 448 SERIES ,;;.,.:. ,. � f �f��' _ � �� Self-Diagnostic, Four- ��:f, _ . � � � R�� ` � Wire, Photoelectric ���i�: _ � ,� �{� .�:-v �� ,f,�,:�r f,���.�� Smoke Detectors fas: _ Model numbers: 449AT,449C,449CT,449CRT,449CST,449CSTE, � , 449CSRT,449CSRH,449CTE -•. -Y., � _.:.��;: :. �.�_.. : o L F M U LC :� � LISTED APPROVED _;f � .r - -;;•r,��=r-� California State Fire Marshal Approved MEA(New York City)Approved ULC model numbers: 448AT,448C,448CT,448CST,448CSRH,448CTE • Intelligent, self-diagnostics The ESL 449/448 Series self-diagnostic, four-wire smoke detectors continually monitor their own • On-site maintenance alert sensitivity and operational status, and provide a visual trouble indication if they drift out of sensitivity • Field replaceable optical chamber range orfail internal diagnostics. This unique, • Low-p rof i l e d esi g n patented technology meets N FPA 72 field sensitivity testing requirements without the need for external • Plug-in terminal block meters. Additional diagnostic information is activated by • Advanced false alarm immunity applying a magnet near the detector's integral reed switch. This initiates a self-diagnostic routine and provides visual indication of sensitivity level, or if service is required. This series is easily cleaned by simply replacing ESL's proprietary field-replaceable optical chamber. All models are designed to reduce false alarms from dust, insects, RFI, and external light. An integral combination rate-of-rise and fixed 135°F (57°C), 50-foot rated, heat sensor is available with all "T" model detectors (see selection guide), allowing latching of the alarm for either smoke or heat. The 449CSRH includes an isolated alarm output for heat and activates an internal non-latching sounder (local alarm) for smoke, making it ideal for motel/hotel and dormitory rooms where smoking is permitted. continued ESL 449 Series Sl�noke Detectors Architectural and Engineering Specifications The ESL 449 Series low-profile, self-diagnostic,four-wire The proprietary optical sensing chamber is field replaceable, smoke detectors work on the light scattering principle.A allowing quick and easy cleaning and maintenance. pulsed infrared light-emitting diode serves as the light source, Models with auxiliary relays are approved for releasing and a high-speed photodiode as the sensing element. When service. the amount of light reflected onto the photodiode reaches the This low profile product is equipped with a hinged cover, a sensitivity setting,the smoke sampling rate increases. Three concealed tamper-resistant latch, and insect screens. (3)successive smoke sensings above the sensitivity setting Wiring terminates in plug-in, clamp-type screw terminals. are required to sound an alarm.This design has superior Detectors mount to a standard single-gang electrical box, a protection against false alarms caused by dust, insects, RF four-inch octagonal,four-inch square electrical box, or and ambient-light. WIREMOLD 5739 fixture box. A confirmed alarm causes the normally flashing power Smoke Detector Spacing indicator LED to light continuously and the alarm relay to On smooth ceilings(as defined in NFPA 72),spacing of 30 feet operate. A trouble indication is automatically displayed by (g.1 meters)may be used as a guide. Other spacing may be used flashing the LED every second. This meets NFPA 72 field depending on ceiling height,high air movement,and other sensitivity testing requirements. An internal 85 dB horn conditions or response requirements. (available in"S" models)emits a temporal 3 when the detector alarms and a steady tone when power polarity is t reversed. ,.85•�4���m,� 6.,•�,5.5�m) — � I 1 �—0 — Product Data Sensitivit 3.1 - 1.0%/ft. max. -CST..........................................................................40mA y................................................. ( ) 3.1 +0.50%/ft. (min) -CSRT, CSRH, CSTE................................................51 mA Operating temp. range ............... 32°F to 120°F(0°C to 50°C) Typical avg. polarity reverse current Operating humidity range....................................0 to 95% RH -CST, CSRT, CSTE, and CSRH................................10mA Minimum voltage-C, CT, CRT, CST, CSRT, CSRH , Sounder specifications.........................................85 dB at 10' -CSTE.........................................................................8.5V Heat detector specifications -AT..............................................................................5.1V -fixed temperature ..................................... 135°F(57.2°C) Maximum voltage-C, CT, CRT, CST, CSRT, CSRH, -rate of rise .... 15°F/min. &>105°F(8.3°C/min. &>40.6°C) -CSTE...........................................................................33V Auxiliary relay contacts 2A @ 28 VDC or 120 VAC (resistive) -AT................................................................................27V Alarm contacts ........................ 500 mA @ 36 VDC(resistive) Maximum ripple(peak to peak)........................................ 10% Field wiring size.................................................. 14-24 AWG Typical average standby current.....................................70aA Packaging .......................10 detectors are packed in a carton -CSTE........................................................................23mA Color....................................................white cover/white base Typical alarm current-C, CT and AT ............................ 15mA with UV inhibitor to prevent yellowing -CRT..........................................................................31 mA Listin UL 268, ULC FM, CSFM and MEA g.............................. Selection Guide Designator Feature Description H Isolated Fixed Temp. Isolated fixed 135°F(57°C)and rate of rise heat detector,independently trips the LED and alarm and Rate of Rise output.Smoke detector activates intemal sounder(local alarm)and auxiliary relay,but Heat Detector does not latch.Approved as both single station smoke alarm and system heat detector. Ideal for hotel,motel and dormitory rooms where smoking is allowed. R Auxiliary Relay Used to activate other devices such as elevator recall,door holders,strobes,etc.Listed for releasing service. S Built-in Sounder 85dB built-in sounder alarms when smoke is detected or when power wiring polarity is reversed. T Intergrated Fixed Intergrated Fixed 135°F(57°C)temperature and rate of rise heat detector. Temp.and Rate of Either heat detector or smoke detector can trip and latch LED and alarm protection. Rise Heat Detector relay outputs. E Built-in end of line Relay is normally energized and will trip with loss of power.Can also provide notification power supervision relay when detector needs maintenance. in t e r I o g i►i•.. PH�3.692.�5Z ��,������x.��� US4 8 Canada: 800.547.2556 Irnerlogix,Cadd�c,H,lil and�trol aretraAmiarksof Technical Service: 800.6487424 FaxBack:800.4832495 irnenogix,inc w�vw.sentrd.wrn www.ir�eaiogi�csearity.mm E-3965 Rev B-1101 DF-52121:C•E-325 MMF-300(A) Series, � Flf''e•LIT��A�arms MDF-300(A) Addressable Monitor Modules by Honeywell - , - General Four different monitor modules are available for Fire•Lite's � _ intelligent control panels to suit a variety of applications. Moni- �:� - tor modules are used to supervise a circuit of dry-contact input � � �' � `, devices,such as conventional heat detectors and pull stations, '^'" or monitor and power a circuit of two-wire smoke detectors 1^ "°'° � ,;;;�`j ' (MMF-302(A)). � =E��w,.rEO�PmE�. � MMF-300(A)is a standard-sized module(typically mounts to a =�_���� 4" [10.16 cm] square box) that supervises either a Style D � A� " ss�Pa�-� ����.�,z , (Class A) or Style B (Class B) circuit of dry-contact input ,.E,,,,, ..��re., devices. .e=� A,., e„�,a��,.=oaE,owEa�M.Eo MMF-301(A)is a miniature monitor module a mere 1.3° (3.302 aa,U� cm)H x 2.75°(6.985 cm)W x 0.5"(1.270 cm) D used to super- A`a'°' A ) vise a Style B(Class B) circuit of dry-contact input devices. Its .+�`, � �' —' __ compact design allows the MMF-301(A) to be mounted in a � �` ' '" �� � ���� • �a;,_: � sing le-gang box be hin d t he device it monitors. � ��' ° �;;,.� �.�_�i�� MMF-302(A) is a standard-sized module used to monitor and � ������`' � �����°�� � supervise compatible two-wire, 24 volt, smoke detectors on a `° Style D(Class A) or Style B(Class B)circuit. � - MDF-300(A)is a standard-sized dual monitor module used to MMF-300(A)(Type H) monitor and supervise two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two may be wired as an NFPA Style B(Class B) or Style D (Class separate,consecutive addresses in intelligent,two-wire systems. A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor LiteSpeedT"' is a communication protocol developed by (provided) terminates the Style B circuit. No resistor is Fire•Lite Engineering that greatly enhances the speed of com- required for supervision of the Style D circuit. munication between analog intelligent devices. Intelligent MMF-300(A) OPERATION devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU Each MMF-300(A) uses one of the available module stops the group poll and concentrates on single points. The addresses on an SLC loop. It responds to regular polls from net effect is response speed greater than five times that of the control panel and reports its type and the status(open/nor- other designs. designs. mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control MMF-300(A) Monitor Module panel. The LED latches steady on alarm (subject to current limitations on the loop). • Built-in type identification automatically identifies this device as a monitor module to the control panel. MMF-300(A) SPECIFICATIONS • Powered directly by two-wire SLC loop. No additional power Nominal operating voltage: 15 to 32 VDC. required. Maximum current draw:5.0 mA(LED on). • High noise(EMF/RFI) immunity. Average operating current: 350 NA (LED flashing), 1 com- • SEMS screws with clamping plates for ease of wiring. munication every 5 seconds,47k EOL. • Direct-dial entry of address: 01 -159 on MS-9600 series Maximum IDC wiring resistance:40 ohms. panels,01 -99 on other compatible systems. • LED flashes during normal operation and latches on steady EOL resistance:47K ohms. to indicate alarm. Temperature range: 32°F to 120°F(0°C to 49°C). The MMF-300(A) Monitor Module is intended for use in intelli- Humidity range: 10%to 93%noncondensing. gent, two-wire systems, where the individual address of each Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x module is selected using the built-in rotary switches. It pro- 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x vides either a two-wire or four-wire fault-tolerant Initiating 2 125" (5.398 cm)deep box. Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The MMF-300(A) can be used to replace M300(A) modules in existing systems. MMF-300(A)APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit DF-52121:C•10/06/2010—Page 1 of 4 MMF-301(A) Mini Monitor Module Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65"(1.651 cm)deep. • Built-in type identification automatically identifies this device as a monitor module to the panel. Wire length: 6" (15.24 cm) minimum. • Powered directly by two-wire SLC loop. No additional power required. MMF-302(A) Interface Module • High noise(EMF/RFI) immunity. • Supports compatible two-wire smoke detectors. • Tinned,stripped leads for ease of wiring. • Supervises IDC wiring and connection of external power • Direct-dial entry of address: 01 — 159 on MS-9600 series source. panels,01 —99 on other compatible systems • High noise(EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. 3 14?5 0 � ADDRESS 0 � • Direct-dial entry of address: 01 — 159 on MS-9600 series � 13 '�� 2 � 2 panels,01 —99 on other compatible systems. � 11� � 4 LOOP � 4 • LED flashes during normal operation. • LED latches steady to indicate alarm on command from 10 5 5 control panel. 9 $ � 6 9 8 � 6 TENS ONES The MMF-302(A) Interface Module is intended for use in intelli- � gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- � � wire conventional smoke detectors. It transmits the status(nor- Y mal, open, or alarm)of one full zone of conventional detectors � � �W Q back to the control panel. All two-wire detectors being moni- � � � m tored must be UL compatible with the module. The MMF- 302(A) can be used to replace M302(A) modules in existing systems. MMF-302(A)APPLICATIONS Use the MMF-302(A) to monitor a zone of two-wire smoke The MMF-301(A) Mini Monitor Module can be installed in a detectors. The monitored circuit may be wired as an NFPA single-gang junction directly behind the monitored unit. Its Style B(Class B)or Style D (Class A) Initiating Device Circuit. small size and light weight allow it to be installed without rigid A 3.9 K ohm End-of-Line Resistor (provided) terminates the mounting. The MMF-301(A) is intended for use in intelligent, end of the Style B or D (class B or A) circuit (maximum IDC two-wire systems where the individual address of each module loop resistance is 25 ohms). Install ELR across terminals 8 is selected using rotary switches. It provides a two-wire initiat- and 9 for Style D application. ing device circuit for normally-open-contact fire alarm devices. The MMF-301(A) can be used to replace M301(A) modules in MMF-302(A)OPERATION existing systems. Each MMF-302(A) uses one of the available module MMF-301(A)APPLICATIONS addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status(open/nor- Use to monitor a single device or a zone of four-wire smoke mal/short) of its Initiating Device Circuit (IDC). A flashing LED detectors,manual fire alarm pull stations,waterflow devices,or indicates that the module is in communication with the control other normally-open dry-contact devices. May also be used to panel. The LED latches steady on alarm (subject to current monitor normally-open supervisory devices with special super- limitations on the loop). visory indication at the control panel. Monitored circuiUdevice is wired as an NFPA Style B(Class B) Initiating Device Circuit. MMF-302(A)SPECIFICATIONS A 47K ohm End-of-Line Resistor(provided)terminates the cir- Nominal operating voltage: 15 to 32 VDC. cuit. Maximum current draw:5.1 mA(LED on). MMF-301(A)OPERATION Maximum IDC wiring resistance:25 ohms. Each MMF-301(A) uses one of the available module Average operating current: 300 uA, 1 communication and 1 addresses on an SLC loop. It responds to regular polls from LED flash every 5 seconds,3.9k eol. the control panel and reports its type and the status(open/nor- mal/short)of its Initiating Device Circuit(IDC). EOL resistance:3.9K ohms. MMF-301(A) SPECIFICATIONS External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms Nominal operating voltage: 15 to 32 VDC. maximum. Current: 90 mA per module maximum. Average operating current: 350 �aA, 1 communication every Temperature range: 32°F to 120°F(0°C to 49°C). 5 seconds, 47k EOL; 600 uA Max. (Communicating, IDC Shorted). Humidity range: 10%to 93%noncondensing. Maximum IDC wiring resistance:40 ohms. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Maximum IDC Voltage: 11 Volts. 2.125" (5.398 cm)deep box. Maximum IDC Current:400�A. EOL resistance:47K ohms. Temperature range;32°F to 120°F(0°C to 49°C). Humidity range: 10%to 93%noncondensing. Page 2 of 4—DF-52121:C•10/06/2010 MDF-300(A) Dual Monitor Module Product Line Information The MDF-300(A) Dual Monitor Module is intended for use in NOTE:"A"suffix indicates ULC-listed model. intelligent, two-wire systems. It provides two independent two- MMF-300(A): Monitor module. wire initiating device circuits(IDCs)at two separate,consecutive addresses. It is capable of monitoring normally open contact fire MMF-301(A): Monitor module, miniature. alarm and supervisory devices.The module has a single panel- MMF-302(A): Monitor module,two-wire detectors. controlled LED. NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir- MDF-300(A): Monitor module, dual, two independent Class B cuits ONLY. Style D (Class A) IDC circuits are NOT supported in circuits. any application. SM6500: Optional surface-mount backbox. MDF-300(A)SPECIFICATIONS NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51309. Normal operating voltage range: 15 to 32 VDC. Maximum current draw:6.4 mA(LED on). APChIteCtS'/Engineers' Specifications Average operating current: 750 NA(LED flashing). Specifications of these devices and all FireLite products are Maximum IDC wiring resistance: 1,500 ohms. available from FireLite. Maximum IDC Voltage: 11 Volts. Maximum IDC Current:240 NA EOL resistance:47K ohms. Maximum SLC Wiring resistance:40 Ohms. Temperature range:32°to 120°F(0°to 49°C). Humidity range: 10%to 93%(non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125" (5.398 cm)deep. MDF-300(A) AUTOMATIC ADDRESSING The MDF-300(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the MDF-300(A) is set to address "26", then it will automati- cally assign itself to addresses"26"and"27". NOTE: "Ones" addresses on the MDF-300(A) are 0, 2, 4, 6, or 8 only.Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. QCAUTION: Avoid duplicating addresses on the system. Installation MMF-300(A), MMF-302(A), and MDF-300(A) modules mount directly to a standard 4" (10.16 cm)square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SM6500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes,ordinances,and regu- lations. These modules are intended for power-limited wiring only. The MMF-301(A)module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes,ordinances,and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL: S2424 • ULC: S2424 • FM Approved • CSFM: 7300-0075:0185 • MEA:72-01-E DF-52121:C•10/06/2010—Page 3 of 4 Fire•LiteO and LiteSpeedO are registered trademarks and FireWatchT"^ is a trademark of Honeywell International Inc. �02010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. - We cannot cover all specific applications or anticipate all requirements. EN6INEERIN6 8 MANUFACTURIN& All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firelite.com Page 4 of 4—DF-52121:C•10/06/2010 �� SYSTEM ��� SENSOR° - _ _ _ - - �� � , . � C01224T and C01224TR • • • � _ Carbon Monoxide - , � : Detectors �F . . with RealTest°Technology ,� , , � ', �-�- -�_ The System Sensor C01224T and C01224TR(round) y ,� , * Carbon Monoxide(CO)Detectors use a highly accurate and reliable electrochemical sensing cell to provide early ,� ,�' warning of dangerous CO levels. Features With RealTest�technology,the CO gas sensing cell used in the C01224T and C01224TR CO detectors can be tested using a • ReaiTestOO enables a functional test using canned CO CO gas agent,fully meeting the requirements of NFPA 720:2009. • Full compliance with UL 2075 Simply put the detector into RealTest mode, spray a small amount • A code-required trouble relay of CO into the detector per the installation instructions,and within seconds the detector will alarm, indicating successful gas entry. (See • Wiring supervision with SEMS terminals the reverse page or the user manual for complete instructions.) • A six-year end-of-life timer • 12/24 VDC When dangerous amounts of CO are detected,the C01224T and A low current draw of 20 mA in standby and 40 mA in alarm C01224TR detectors alert residents by sounding and flashing a � temp 4 signal alarm.With 24/7 central station monitoring, residents • Versatile mounting for wall and ceiling are guaranteed protection whether they are away from home, • Accurate and reliable electrochemical sensing technology sleeping,or already suffering from the effects of CO. • Optional CO-PLATE CO Detector Replacement Plate to upgrade The C01224T and C01224TR are designed for system operation. previously installed competitor detectors to the C01224T These detectors are fully listed to UL 2075 and offer a code- required trouble relay to send a sensor failure or end-of-life signal to the control panel and the central station.The C01224T and C01224TR also use SEMS-type terminal Philips head screws for quicker and more positive wiring connections and code-required wiring supervision.With a low current draw,these detectors enable more devices to be connected to the panel, limiting the need to purchase extra power supplies or more expensive paneis.As 12/24 VDC detectors,the C01224T and C01224TR will operate on most industry security and fire alarm control panels. Agency Listings ��.�� ��� oL l���i �L� ��K LISTED �� F307195 E304075 5276-1653�0194 C01224T and C01224TR Carbon Monoxide Detector Specifications Carbon monoxide(CO)detector shall be a system-connected System Sensor model number C01224T or C01224TR listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and Sensors.The detector shall be equipped with a sounder and a trouble relay.The detector's base shall be able to mount to a single-gang electrical box or direct(surface)mount to the wall or ceiling.Wiring connections shall be made by means of SEMS screws.The detector shall provide dual-color LED indication that blinks to indicate normal standby,alarm,or end-of-life.When the sensor supervision is in a trouble condition,the detector shall send a trouble signal to the panel.When the detector gives a trouble or end-of-life signal,the detector shall be replaced.The detector shall provide a means to test CO gas entry into the CO sensing cell.The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.The detector shall perform in the detection of CO up to 12,000 feet above sea level and alarm within the time specified by ANSI/UL 2034 for CO concentrations of 70, 150 and 400 parts per million(ppm), as verified by a Nationally Recognized Test Laboratory. Operating Voltage 12/24 VDC Audible Signal 85 dB in alarm Standby Current 20 mA Alarm Current 40 mA(75 mA test) Alarm Contact Ratings 0.5 A@ 30 VDC Trouble Contact Ratings 0.5 A@ 30 VDC Size:C01224T Length:5.1 in,Width: 3.3 in,Height: 1.3 in C01224TR Diameter:6 in, Height: 1.3 in Approximate Weight C01224T:7 oz;C01224TR: 11 oz Operating Temperature Range 32°F to 104°F(0°C to 40°C) Operating Humidity Range 22 to 90%RH InputTerminals 14 to 22 AWG Mounting Single-gang back box;surface mount to wall or ceiling Operation Modes .. . . Normal(standby) Blink 1 per minute — — Alarm — Blink in temp 4 pattern Sound in temp 4 pattern RealTest°Feature: The System Sensor C01224T and C01224TR Carbon Monoxide Detectors with RealTest enable evaluation of the functionality of the CO sensing cell using a canned CO test agent. _ – � .�� .. � � � � . Push and hold the Test/Hush button for Spray canned CO agent into Verify CO sensing at the two seconds to enter RealTest mode.The the detector. control panel.The detector will green LED will flash once every second automatically exit RealTest alarm to indicate RealTest mode has started. mode after about 20-60 seconds. NOTE:Check with local codes and the ANJ to determine if a functional gas test is desired for an installation. Hush Feature: Pushing the Test/Hush button will silence the sounder for 5 minutes(except in RealTest mode). Trouble Feature: When the detector is in a trouble condition, it will send a trouble signal to the panel. End-of-Life Timer: After the detector's internal sensor has reached the end of its life,a trouble signal will be sent to the panel to indicate it is time to replace the detector.An electrochemical CO detector lifespan is � about six years.The detector must be replaced by the date marked on the inside of the product. � � CO-PLATE: System Sensor also offers the CO-PLATE CO Detector Replacement Plate to cover the footprint(when _ � � necessary)of previously installed competitive carbon monoxide detectors that require replacement. Ordering Information co P�ArE .- C01224T 12/24 volt,4-wire system-monitored carbon monoxide detector with RealTestO Technology C01224TR 12/24 volt,4-wire system-monitored round carbon monoxide detector with RealTestO Technology CO-PLATE CO detector replacement plate to cover the footprint of previously installed competitive detectors as necessary �� �/STEM 3825 Ohio Avenue•St.Charles, IL 60174 ozo,zsYSCemsenso�. I Phone:800-SENSOR2•Fax:630-377-6495 P�oducts�eciticationssubjecttocha�gewrthoutnotice Visitsystemsenso�com � �Cw/�O�� for current product intormation,induding the latest version of this data sheet. ��V www.systemsensor.com SCD500100•4/12 �� SYSTEM P ��� SENSOR° � �-�� F �; �'��, � ib � � I R �IL �°���' � _ - Indoor Selectable- E � : � , Output Horns, , -- r- Strobes and � .�1�;� ���: { `, � ��', ;� , � , Horn Strobes for ` � � � �'` n � Wall Applications � � SpectrAlert�Advance audible visible notification products SPECTfZ'f��G� are rich with features guaranteed to cut installation times ,4 o v .ea n� c e and maximize profits. Features The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry. • Plug-in design with minimal intrusion into the back box With white and red plastic housings,wall and ceiling mounting • Tamper-resistant construction options, and plain and FIRE-printed devices,SpectrAlert Advance • Automatic selection of 12-or 24-volt operation at 15 and can meet virtually any application requirement. 15/75 candela Like the entire SpectrAlert Advance product line,wall-mount horns, • Field-selectable candela settings on wall units: 15, 15/75,30,75, 95, 110, 115, 135, 150, 177,and 185 strobes,and horn strobes include a variety of features that increase their application versatility while simplifying installation.All devices • Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box, • Rotary switch for hom tone and three volume selections making installations fast and foolproof while virtualiy eliminating Universal mounting plate for wall units costly and time-consuming ground faults. • Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage, SpectrAlert Advance utilizes a universal mounting plate • Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring, so installers can test wiring Compatible with MDL sync module continuity before the device is installed. • Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections. Agency Listings /� SIGNALING /r��� O `�\��/ � F M MEA �,����.� d YOVEf� �"5-1653�.186(Indoors�robes) LISTED APPPOVED pp 71?5-1653 188(horn 5trobe5. 54011(chimes,hom strobes.horns) 3023572 MEA45&05-E chlme strobES) S5512(strobes) 7135-1653�.189(homs,chlmes) SpectrAlert Advance Specifications General SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 1 Yz-inch back box,4-inch octagon back box,or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit�M Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-voit-rated notification appliance circuit outputs shall operate between 8 and 17.5 volts;24-vo�t-rated notification appliance circuit outputs shall operate between 16 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. .- Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Rangez 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) InputTerminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6'"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6""L x 4.7""W x 1.3""D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Back Box Skirt Dimensions(BBS-2,BBSW-2) 5.9""L x 5.0'"W x 2.2""D(151 mm L x 128 mm W x 56 mm D) Wall-MountTrim Ring Dimensions(sold as a 5 pack)(TR-HS,TRW- 5.7`L x 4.8'"W x 0.35'"D(145 mm L x 122 mm W x 9 mm D) HS) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2. P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS00601 UL Current Draw Data . . 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 1�� NA NA 281 251 185 NA NA 286 258 � 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 � 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Tones and Sound Output Data . 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 �Settings 7, 8, and 9 are not available on 2-wire horn strobes. AVDS00601 SpectrAlert Advance Dimensions 4.7"� 2.5" 5.05" �2.23'=►� � I ��.�, � � � � o � � �� � 5.6„ 5.98„ 0 0 � � � � � � � � Wall-mount horn strobes Wall back box skirt SpectrAlert Advance Ordering Information •- - •- Wall Horn Strobes Horns P2R"t 2-Wire Horn Strobe,Standard cd$,Red HR Horn, Red P2RH` 2-Wire Horn Strobe, High cd, Red HW Horn,White P2W" 2-Wire Horn Strobe,Standard cd,White Accessories P2WH` 2-Wire Horn Strobe, High cd,White BBS-2 Back Box Skirt,Wall, Red P4R* 4-Wire Horn Strobe,Standard cd,Red BBSW-2 Back Box Skirt,Wall,White P4RH 4-Wire Horn Strobe, High cd, Red TR-HS Trim Ring,Wall, Red P4W 4-Wire Horn Strobe,Standard cd,White TRW-HS Trim Ring,Wall White Wall Strobes SR*t Strobe,Standard cd,Red SRH't Strobe,High cd, Red SW` Strobe,Standard cd,White SWH" Strobe,High cd,White Notes: *Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2R-P. t Add"-SP"to model number for"FUEGO°marking on cover,e.g.,P2R-SP. $°Standard cd"refers to strobes that include 15,15/75,3Q 75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings. l`��� ����� 002012 System Sensor. � � 3825 Ohio Avenue•St.Charles, IL 60174 P�oducts�ecit�icationssubjecttochanyewahoutnotice,Visitsystemse�soccom � ��� SE/VSORP Phone:800-SENSOR2•Fax:630-377-6495 forcurrentproductmformatro�mduda�gme�atestve�sionotmisdatasheet. AVDS00601•3/12