HomeMy WebLinkAboutA10-0117TOWN OF VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2]35
VAIL FIRE DEPARTMENT
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ALARM PERMIT
Job Address: 2171 N FRONTAGE RD WEST VAIL
Location.....: SPACE 9
Parcel No...: 210311415012
Project No :
OWNER WEST VAIL MALL CORP
299 MILWAUKEE 501
DENVER
CO 80206
APPLICANT VAIL ELECTRONICS, LTD
PO BOX 3940
AVON
CO 81620
License: 198-5
CONTR.ACTOR VAIL ELECTRONICS, LTD
PO BOX 3940
AVON
CO 81620
License: 198-5
12/2s/2olo
Permit #: A10-0117
Status . . . : ISSUED
Applied . . : 12/28/2010
Issued . . . O]/11/201 1
Expires . .: 07/10/2011
12/28/2010 Phone: 970-827-9120
12/28/2010 Phone: 970-827-9120
Desciption: FIRE ALARM WORK FOR TENANT FINISH FOR QDOBA MEXICAN GRILL
RESTAURANT.
Valuation: $2,400.00
**�***+**+»»****�*#*�+r��++*s***s�******�*****�**+******s***a****�*+ FF.E SU M M A R Y****+*��******s***�*�+�r+�*�***+***a►****�**r+*+r*++*++�+
F:lectrical---------> $o . oo Total Calculated Fees--> $3�8 . o0
DRB Fee---------> $0. 00 Additional �ces----------> $0. 00
Investigation----> $0.00 TotalPermitFee--------> $3�8.00
Will Call---------> $0. 00 Paymcnts------------------> $378. 00
TO"I'Al., FF..ES--> $378.00 BALANCE DUE--------> $0. 00
**��********►�**+**�**►*�*s#�r*r**a***+*�r*:r***tr***«r:+s*+*��***�*s*****:*s:+*�**a*«*****+�**************s*++***aa****�a+*******���*«a**•*�+
Approvals:
Item: 05600 FIRE DEPARTMENT
O1/03/2011 mvaughan Action: AP
**,:,:++***,:*�++.++.++*,:**+��«����+�»+.+*,.,,.»,.++++,•.�,:,:�+.»*..»«.+..,,*.**,..**.+.********�.��**.**�+�***,*****.*��+.*****+*.�+�+*�*��*�*��
CONDITIONS OF APPROVAL
*�.***.�....�*..���**..*�***�***.*,***«�.*�*.***..«**.****�**..��......***�*�#***�*********.****�*�***�**.«****��*��*...*�.��***#*�.****���*�
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
RF.QUESTS FOR INSPECTION SHALL BF. MADF. TWF.NTY-FOUR HOl1RS IN
AT 970-479-2252 FROM 8:00 AM - 5 PM.
SICYNQ�'[1R1�6�IER OR CONTRACTOR FOR HIMSELF AND OWNEF
******************************�*************************************************************
TOWN OF VAIL, COLORADO Statement
*****************************+**************************************************************
Statement Number: R110000033 Amount: $378.00 O1/11/201110:24 AM
Payment Method:Credit Crd Init: SAB
Notation: VISA-DONALD
ANDERSON-VAIL ELECTRONICS
-----------------------------------------------------------------------------
Permit No: A10-0117 Type: ALARM PERMIT
Parcel No: 2103-114-1501-2
Site Address: 2171 N FRONTAGE RD WEST VAIL
Location: SPACE 9
Total Fees: $378.00
This Payment: $378.00 Total ALL Pmts: $378.00
Balance: $0.00
**�****************************************+*************************�**********************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 FIRE ALARM PERMIT FEES 90.00
PF 00100003112300 PLAN CHECK FEES 288.00
� � ����' ° � C � `' Department of Community Development
�` �'x���'�x't �� � , �� i
,,
., . . ', a . , % t
. . _ 5 Sou h Frontage Road
. ,-�� "`�, •,���� '� ����,�° `� ;'�� Vail, Colorado 81657
. , �, , �
': � `• � � Tel: 970-479-2128
, .
� ! �,�► . � ., ,.. Y�s' ,
: - •
. . � ,
;� 4 ": w� i� � - - ���' � Fax: 970-479-2452
� � . *,�,�w�.��, � ,,, �` Web: www.vailgov.com
� " — j n„�y �'� - �+���i���Development Review.Coordinator
r��?i.�� �i�� .k . _ ,. .._ . 4 ,� < x- _....._. . ' ' , '��.'�_."�.�u��,,.°�« .� `.�
FIRE ALARM PERMIT
Commercial and Residential Fire Alarm shop drawings are required at the time of application
submittal and must included information listed on the 2nd page of this form. Application will
not be accepted without this information.
Project Street Address:
2161 N. FRONTAGE ROAD
(Number) (Street)
BuildinglComplex Name: �ST VAIL MALL
Contractor Information:
Company: VAIL ELECTRONICS
Company Address: PO BOX 3940
City: AVON State: CO
Contact Name: DON ANDERSON
Contact Phone: 970-827-9120
E-Mail DON@VAILELECTRONICS.NET
(Suite #)
Office Use:
Project#: �KSID— ��7(pq
Building Permit #: � ��'" �� oZ ,�
Alarm Permit #: /7 � � � � � � �
Lot #: Block # Subdivision:
Detailed Description of Work: FIRE ALARM WORK
Zip: 81620 TO ACCOMMODATE TENANT FINISH IN
Town of Vail Contractor Registration No.: 198-S
Deborah aq�h'��byDeEara1�51unn
DN: wDebaa� SMner, o-SAar�er
X life Salery. ou�FVE.
Shaner �'.��'��°�°•���-°s
Date:1010.13 3816 30:10 -0)'00'
Contractor Signature (required)
Property Information
Parcel #: 2103-114-15-012
(For parcel #, contact Eagle County Assessors Office at 970-328-8640 or
visit www.eaglecounty.us/patie)
Tenant Name:
Owner Name: �ST VAIL MALL CORP
Complete Valuation for Fire Alarm Permit:
Fire Alarm $:
5,��,P
��
EXISTING SPACE.
(use additional sheet if necessary)
Does a Fire Alarm Exist? Yes (�) No ()
Does a Sprinkler System Exist? Yes () No ( �)
Work Class:
New ( ) Addition ( ) Remodel ( � ) Repair ( )
Retro-Fit ( ) Other ( )
Type of Building:
Single-Family ( ) Duplex ( ) Multi-Family ( )
Commercial ( + ) Restaurant ( ) Other ( )
Date Received:
�� � l ts7 I f' LI �J �
$2400 E
iIJ'�,�i DEC 2� 2010
u
' �-nt^�t�� r�� ��,4!L
29-May-09
�� SYSTEM
�� SENSOR °
Selectable-Output
Horns, Strobes, and
Horn Strobes
SpectrAlerr'Advance selectable-ourpur horns, srrobes,
and horn strobes are rich with features guaranteed to
cut installation rimes and maximize profits.
Features
• Plug-in design with minimal intrusion into the back box
•Tamper-resistant construction
• Automatic selection of 12- or 24-volt operation at 1 S and 15/75
candela
• Field-selectable candela settings on wall and ceiling units: 15, 15/75,
30, 75, 95, 110, 115, 135, 150, 177, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and three volume selections
• Universal mounting plate for wall and ceiling units
• Mounting plate shorting spring checks wiring continuity before
device installation
Electrically compatible with existing SpectrAlert products
Compatible with MDL sync modute
Agency Listings
sicxnuxc �::
�� F M MEA °.
a roved >>zs-�ES3�e�o�,���,>�,�b.��
LISTED APPROVEO PP „zs-,ES„�o,�,,,�„o�e,.
S4oti(cnimes,nomstrobes,norns) 1o�357t MFAa52-OS-E chimezcwbes)
5551 i (sttobes) 7135-1653�.189 (AOrns, chimes)
���
� ��� _ _
. �
f o m S s t e 5 e
;��..
, ;,�.
�
� . �AfS•....
Ms �� � 1�y��
4 Aa
Tha SpactrAlert Advance sarias offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE-printed devices, SpectrAlert Advance can
meet virtually any application requirement.
Like the entire SpectrAlert Advance product line, horns, strobes,
and horn strobes include a variety of features that increase their
application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back
box, which make installations fast and foolproof while virtually
eliminating costly and time-consuming ground faults. Furthermore,
a univer9al mounting plate with an onboard shorting spring tests
wiring continuity before the device is installed, protecting devices
from damage.
In addition, field-selectable candela settings, automatic selection
of 12- or 24-volt operation, and a rotary switch for horn tones with
three volume selections enables installers to easily adapt devices to
suit a wide range of application requirements.
n
[��f�,�l�`!/I�
�'� ���. DEC 2 �� 2010
1"ON1N C�F VAIL
Alert Advance Specifications
General
SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 x 4 x 1 fz-inch back box, 4-inch octagon back box, or doub�e-gang back
box. Two-wire products shall also mount to a single-gang 2 x 4 x 1'/e-inch back box. A universal mounting plate shall be used for mounting ceiling and
wall products. The notification appliance circuit wiring shall terminate at the universal mounting piate. Also, SpectrAlert Advance products, when used with
the Sync•Circuit" Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.
When used with the Sync•Cirwit Module,l2-volt-rared notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification
appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit
from a regulated DC or full-wave rectified unfiltered power supply. Strobes and hom strobes shall have field-se�ectable candela settings induding 15, 15/75, 30,
75, 95, 110, 11 S, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpeccrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be
wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at
1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reFlector rystem.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The
hom strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling
appliances, Flashing at 1 Hz over the strobei entire operating voltage range.The strobe light shall consist of a xenon Flash tube and associated lens/reFlector
system. The hom shall have three audibiliry options and an option ro switch between a temporal three-pattem and a non-temporal (continuous) pattem. These
options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the soundecThe horn on hom strobe models
shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service. The module shall synchronize
SpectrAlert strobes at 1 Hz and homs at temporal three. Also, while operating the strobes, the module shall silence the homs on hom strobe models over a
single pair of wires. The module shall mount to a 4"/,e x 4"/,e x 2'/e-inch back box. The module shall also control two Style Y(dass 6) circuits or one Style Z
(class A; circuit The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they
control.lhe module shall not operate on a coded power supply
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 9396 non-condensing
Strobe Ffash Rate 1 flash per second
Nominal Voltage Regulated 12 DUFWR or regulated 24 DVFWR'
Opereting Voltage Range2 8 to 17.5 V(12 V nominal) or 16 to 33 V(24 V nominal)
InputTerminal Wire Gauge
nt Dimensions (including lens)
Wall-Mount Dimensions (including lens)
Horn Dimensions
Wall-Mount Back Box Skirt Dimensions (BBS-2, BBSW-2)
12 to 18 AWG
6.8"diameter x 2.5" high (173 mm diameter x 64 mm high)
5.6"Lx4.7"Wx2.5"D(142mmLx119mmWx64mmD)
5.6"Lx4.7"Wx1.3"D(142mmLx119mmWx33mmD)
5.9"Lx5.0"Wx2.2"D(151 mmLx 128mmWx56mmD)
Ceiling-Mount Back Box Skirt Dimensions (BBSG2, BBSCW-2) 7.1"diameter x 2.2"high (180 mm diameter x 57 mm high)
Wall-MountTrim Ring Dimensions (sold as a 5 pack) (TR-H5, TRW-HS) 5.7" L x 4.8"W x 035"D (145 mm L x 122 mm W x 9 mm D)
Ceiling-MountTrim Ring Dimensions (sold as a 5 pack) (TRC-H5, TRCW-HS) 6.9"diameter x 0.35" high (175 mm diameter x 9 mm high)
Notes:
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
A05-0395-007
UL Current Draw Data
Standard
Candela Range
High
Candela Range
Candela
15
15/75
30
75
95
110
115
135
150
177
185
s-i �s voics
D� FWR
123 128
142 148
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
16-33 Volts
DC FWR
66 71
77 81
94 96
158 153
181 176
202 195
210 205
228 207
246 220
281 251
286 258
�
8-17.5 Volts 16-33 Volts
Sound Pattern d8 DC FWR DC FWR
Temporal High 57 55 69 75
Temporal Medium 44 49 58 69
Temporal Low 38 44 44 48
Non-temporal High 57 56 69 15
Non-temporal Medium 42 SO 60 69
Non-temporal Low 41 44 50 50
Coded High 57 55 69 75
Coded Medium 44 51 56 69
Coded Low 40 46 52 50
8-17.5 Volts 16-33 Volts
DClnput 15 15/75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non Temporal High 141 152 91 100 116 176 201 221 229
Non Temporal Medium 133 145 75 85 102 163 187 207 216
Nondemporal Low 131 144 68 79 96 156 182 201 �10
FWR Input
Temporal High 136 155 88 97 112 168 190 210 Z18
Temporal Medium 129 152 78 88 103 160 184 202 20Fi
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
16-33 Volts 76-33 Volts
DClnput 135 150 177 185 FWRlnput 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non Temporal Low 214 2Z9 256 262
Horn Tones and Sound Output Data
8-17.5 16-33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern d6 DC FWR DC FWR DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal Low 71 73 7G 76 83 80 94 89
4 Non Temporai High 82 82 88 88 93 9� 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 75 75 81 81 88 84 96 92
7' Coded High 82 82 88 88 93 92 101 101
8f Coded Medium 78 78 85 85 90 90 97 98
9' Coded Low 75 75 81 81 88 85 96 9�
1Settings 7, 8, and 9 are not available on 2-wire hom strobe.
noso3vs-am
SpectrAlert Advance Dimensions
�4.,- 2.5- _ 6.8-
Oia.
I
� - 2.5'
5.6'
Wall-mount horn strobes Ceiling-mount horn strobes
�.1- r-2.2s-»�
5.05"� �2.23:1 Dia.
1
��0�0
� �
5.98"
O
O O O O
d o o Q
Wall back box skirt
SpectrAlert Advance Ordering Information
Wall Hom Strobes
P2R"f 2-Wire Hom Strobe, Standard cd=, Red
P2RH• 2-Wire Horn Strobe, High cd, Red
P2W' 2-Wire Hom Strobe, Standard cd, White
P2WH' 2-Wire Hom Strobe, High cd, White
P4R` 4-Wire Hom Strobe, Standard cd, Red
P4RH 4-Wire Hom Strobe, High cd, Red
P4W 4-Wire Hom Strobe, Standard cd, White
Wall Strobes
SR*f Strobe, Standard cd, Red
SRH`f Strobe, High cd, Red
SW` Strobe, Standard cd, White
SWH" Strobe, High cd, White
Ceiling Horn Strobes
PC2R' 2-Wire Hom Strobe, Standard cd, Red
PQRH 2-Wire Horn Strobe, High cd, Red
PQW"1 2-Wire Hom Strobe, Standard cd, White
PC2WH' 2-Wire Horn Strobe, High cd, White
PC4R 4-Wire Hom Strobe, Standard cd, Red
PC4RH 4-Wire Hom Strobe, High cd, Red
PC4W 4-Wire Horn Strobe, Standard cd, White
Ceiling back box skirt
Ceiling Strobes
SCR Strobe, Standard cd, Red
SCRH Strobe, High cd, Red
SCW` Strobe, Standard cd, White
SCWH Strobe, High cd, White
Horns
HR Horn, Red
HW Horn, White
Accessories
BBS-2 Back Box Skirt, Wall, Red
BBSW-2 Back Box Skirt, Wall, White
BBSC-2 Back Box Skirt, Ceiling, Red
BBSCW-2 Back Box Skirt, Ceiling, White
TR-HS Trim Ring, Wall, Red
TRW-HS Trim Ring, Wall White
TRGHS Trim Ring, Ceiling, Red
TRCW-HS Trim Ring, Ceiling, White
Notes:
" Add "-P'to modei number for plain housing (no'FIRE'marking on cover), e.g., P2R-F
t Add"-SP'to model numberfor'FUEGO'marking on cover, e.g., P2R-SP.
#"Standard cd'refers to shobes that indude 7 5, 15/75, 30, 75, 95, 110, and 115 candela settings. "High cd'refers to shobes that indude 135, 150, 177, and 185 candela settings.
�� SYSTEM 3825 Ohio Avenue • St. Charles, IL 60174 R�a�,n oioo9 smr,�� sr�,.��
�1� SENSOR� �fi�o��,��o�ha���,��,�����e�,��,n�e,��„o,��,fo,
Phone: 800-SENSOR2 • Fax:630-377-6495 '""`�w°a„a�„��o,,,a,d„amym<ia�«s��«�o�amnaa�a�n�e�
A05-0395-007•4/09•Y1132
SD355(A), SD355T(A),
SD355R(A)
Addressable Photoelectric
Smoke Detectors
The SD355(A) and SD355T(A) addressable, low-profile plug-
in photoelectric detectors use a state-of-the-art photoelectric
sensing chamber with communications to provide open area
protection and are used exclusively with Fire•Lite's Address-
able Fire Alarm Control Panels (FACPs). The SD355T(A) adds
thermal sensors that will alarm at a fixed temperature of 135°F
(57°C). Since these detectors are addressable, they will help
emergency personnel quickly locate a fire during its early
stages, potentially saving precious rescue time while also
reducing property damage. Two LEDs on each sensor light to
provide a local, visible sensor indication. Remote LED annun-
ciator capability is available as an optional accessory (P/N
RA100Z(A)). The SD355R is a remote test capable detector
for use with D355PL or DNR(W) duct smoke detector hous-
ings.
Features
sLC loop:
• Two-wire loop connection.
• Unit uses base for wiring.
Addressing:
• Addressable by device.
• Direct Decade entry of address: 01 – 99 with MS-9200
series, and 01 – 159 with MS-9600 series.
Architecture:
• Unique single-source, dual-chamber design to respond
quickly and dependably to a broad range of fires.
• Sleek, low-profile design.
• Integral communications and built-in type identification.
• Built-in tamper-resistant feature.
• Removable cover and insect-resistant screen for simple
field cleaning.
Operation:
• Withstands air velocities up to 4,000 feet-per-minute (20 m/
sec.) without triggering a false alarm.
• Factory preset at 1.5% nominal sensitivity for panel alarm
threshold level.
• Visible LED "blinks" when the unit is addressed (communi-
cating with the fire panel) and latches on in alarm.
Mechanicals:
• Sealed against back pressure.
• Direct surface mounting or electrical box mounting.
• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16
cm) octagonal box, or 4.0" (10.16 cm) square electrical box
(using a p/aster ring — inc/uded).
Ofher system features:
• Fully coated circuit boards and superior RF/transient pro-
tection.
94-VO plastic flammability rating.
Low standby current.
Options:
• Remote LED output connection (P/N RA100Z).
df-52384:b • E-160
� Fine•�iTe�A�arms
by Honeywell
Addressable Devices
SD355 with B350LP base
SD355T with B350LP base
Applications
Use photoelectric detectors in life-safety applications to pro-
vide a broad range of fire-sensing capability, especially where
smoldering fires are anticipated. lonization detectors are often
better than photoelectric detectors at sensing fast, flaming
fires.
Construction
These detectors are constructed ot off-white LEXAN�.
SD355(T) plug-in, low-profile smoke detectors are designed to
commercial standards and offer an attractive appearance.
Installation
SD355(T) plug-in detectors use a detachable mounting base
to simplify installation, service and maintenance. Mount base
on box which is at least 1.5 inches (3.81 cm) deep. Suitable
boxes include:
• 4.0" (10.16 cm) square box with plaster ring.
• 4.0" (10.16 cm) octagonal box.
• 3.5" (8.89 cm) octagonal box.
• Single-gang box.
NOTE: Because of the inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring `T-taps" or
branches are permitted for Style 4(C/ass B) wiring. SD355R
mounts in a D355PL or DNR(W) duct detector housing.
df-52384:b • 3/12/10 — Page 1 of 2
Operation
Each SD355/T/R uses one of 99 possible addresses on the
MS-9200 series and up to 318 (159 on each loop) on the MS-
9600 series Signaling Line Circuit (SLC). It responds to regular
polls from the system and reports its type and status.
The SD355lT/R addressable photoelectric sensor's unique
unipolar chamber responds quickly and uniformly to a broad
range of smoke conditions and can withstand wind gusts up to
4,000 feet-per-minute (20 m/sec.) without sending an alarm
level signal. Because of its unipolar chamber, the SD355/T/R
is approximately two times more responsive than most photo-
electric sensors. This makes it a more stable detector.
Detector Sensitivity Test
Each detector can have its sensitivity tested (required per
NFPA 72, Chapter 14 on Inspection, Testing and Maintenance)
when installed/connected to a MS-9200 series or MS-9600
series addressable fire alarm control panel. The results of the
sensitivity test can be printed off the MS-9200 series or MS-
9600 series for record keeping.
Specification
Voltage range: 15 - 32 VDC (peak).
Standby current: 300 NA � 24 VDC.
LED current: 6.5 mA � 24 VDC (latched "ON").
Air velocity: 4,000 ft./min. (20 m/sec.) maximum.
Diameter: 6.1" (15.5 cm) installed in B350LP base.
Height: 2.1' (5.33 cm) installed in B350LP base.
Weight: 3.6 oz. (102 g).
Operating temperature range: for SD355(A): 0°C to 49°C
(32°F to 120°F); for SD355T(A): 0°C to 38°C (32°F to 100°F).
SD355R(A): installed in a DNR(W) -20°C to 70°C (-4°F to
158°F).
Temperature: 0°C - 49°C (32°F - 120°F).
Relative humidity: 10%- 93%, non-condensing.
Listings
Listings and approvals below apply to the SD355(A) and
SD355T(A) detectors. In some cases, certain modules may
not be listed by certain approval agencies, or listing may be in
process. Consult factory for latest listing status.
• UL Listed, file S1059.
• ULC Listed, file S1059.
• CSFM approved: file 7272-0075:194.
• MEA approved: file 243-02-E.
• FM approved.
Product Line Information
NOTE: 'A" suffix indicates ULC-Listed model.
SD355: Adressable photoelectric detector; 6350LP base
included.
SD355A: Sames as SD355 with ULC Listing (B350LPA base
included).
SD355T: Same as SD355 but with thermal element; 6350LP
base included.
SD355TA: Same as SD355T with ULC Listing (6350LPA base
included).
SD355R: Remote test capable addressable photoelectric
detector for use with a D355PL or DNR(W) duct detector hous-
ing.
6350LP(A): Plug-in detector base. Dimensions: 6.1" (15.5
cm). Mounting: 4.0" (10.16 cm) square box with or without
plaster ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 cm)
octagonal box, or single-gang box. All mounting boxes have a
minimum depth of 1.5" (3.81 cm).
6224R6(A): Plug-in System Sensor re/ay detector base.
Diameter: 6.2" (15.75 cm). Mounting: 4.0" (10.16 cm) square
box with or without plaster ring, 4.0" (10.16 cm) octagonal box,
or 3.5" (8.89 cm) octagonal box. All mounting boxes have a
minimum depth of 1.5" (3.81 cm).
622461(A): Plug-in System Sensor iso/ator detector base.
Maximum 25 devices between isolator bases (see DF52389).
Diameter: 62" (15.75 cm). Mounting: 4.0" (10.16 cm) square
box with or without plaster ring, 4.0" (10.16 cm) octagonal box,
or 3.5" (8.89 cm) octagonal box. All mounting boxes have a
minimum depth of 1.5" (3.81 cm).
B200SR: Sounder base capable of producing temporal-3 or
steady sound output.
ACCESSORIES:
RA100Z(A): Remote LED annunciator. 3- 32 VDC. Mounts to
a U.S. single-gang electrical box. For use with B501(A) and
8350LP(A) bases only.
SMK400E: Surface mounting kit provides for entry of surface
wiring conduit. For use with B501(A) base only.
RMK400: Recessed mounting kit. For use with 8501(A) base
only.
M02-04-OO:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or removal
of detector heads from bases in high ceiling applications.
XP-4: Extension pole for XR26. Comes in three 5-foot (1.524
m) sections.
T55-127-010:Detector removal tool without pole.
BCK-200B: Black detector covers, box of 10 .
WCK-2006: White detector covers, box of 10 .
FlashScan� registered trademark of Honeywell Intemational Inc. Bay-
blend� is a registered trademark of Bayer Corporation.
m2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
'�O �oo� This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
FNiIlYEE11Ni i MAIYUFACNRINC All specifications are subject to change without notice.
QUALITY SISTEMS
For more information, contact Fire•Lite Alarms. Phone: (S00) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Page 2 of 2- df-52384:b • 3/12/10
H355(A) Series
Intell�gent Addressable Thermal
Detectors
General
The Fire�Lite Alarms H355 Series thermal detectors are
addressable sensors that use a state-of-the-art thermistor
sensing circuit for fast response. These sensors are designed
to provide open-area protection and are intended for use with
the Fire•Lite's addresable Fire Alarm Control Panels (FACPs).
The H355(A) and H355R(A) sensors provide fixed tempera-
ture alarm detection at 135°F (57°C). The H355R(A) sensor
also responds to rate-of-rise conditions of greater than 15°F
(8.3°C) per minute. The H355HT(A) is a fixed high-tempera-
ture detector that activates at 190°F (88°C). These thermal
detectors provide cost effective, addressable property protec-
tion in a variety of applications.
Two LEDs on each sensor light to provide a local, visible sen-
sor indication. Remote LED annunciator capability is available
as an optional accessory (P/N RA400Z).
Features
SLC loop:
• Two-wire SLC loop connection.
• Unit uses base for wiring.
Addressing:
• Addressable by device.
• Direct Decade entry of address: 01 —159 with MS-9600, 01
— 99 with MS-9200UD.
Architecture:
• Sleek, low-profile, stylish design.
• State-of-the-art thermistor technology for fast response.
• Integral communications and built-in device-type identifica-
tion.
• Built-in tamper resistant feature.
• Built-in functional test switch activated by external magnet.
Ope�ation:
• Factory preset at 135°F (57°C) for the H355(A) and
H355R(A); 190°F (88°C) for the H355HT(A).
• Rate-of-rise triggers at 15°F (8.3°C) per minute for the
H355R(A).
• 360°-field viewing angle of the visual alarm indicators (two
bicolor LEDs). LEDs blink green in Normal condition and
turn on steady red in Alarm.
• Visible LEDs "blink" every time the unit is addressed.
Mechanica/s:
• Sealed against back pressure.
• SEMS screws for wiring of the separate base.
• Designed for direct-surface or electrical-box mounting.
• Plugs into separate base for ease of installation and main-
tenance.
• Separate base allows interchange of photoelectric, ioniza-
tion and thermal sensors.
Other system features:
• Remote test feature from the panel.
• Walk test with address display.
• Low standby current.
df-52385:A • E-710
� Fine•�iTeaA�arms
by Honeywell
H355 with 6350LP base
• 94-5V plastic flammability rating.
Options:
• Remote LED output connection to optional RA400Z
remote LED annunciator.
• Recessed (RMK400) or surface (SMK400E) base mount-
ing kits.
installation
H355(A) Series plug-in intelligent thermal detectors use a
detachable base to simplify installation, service and mainte-
nance. Installation instructions are shipped with each detector.
Mount base (all base types) on box that is at least 1.5" (3.81
cm) deep. Suitable boxes include:
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box (except relay or isolator base).
NOTE: Because of the inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring `T-taps" or
branches are permitted for Style 4(Class "B ) wiring only.
Applications
Use thermal detectors for protection of property.
Construction
These detectors are constructed of off-white BayblendO. The
H355(A) Series plug-in intelligent thermal detectors are
designed to commercial standards and offer an attractive
appearance.
Operation
Each H355(A) Series detector uses one of 159 (MS-9600) or
99 (MS-9200UD) possible addresses on a control panel SLC
loop. It responds to regular polls from the control panel and
reports its type and the status. If it receives a test command
from the panel (or a local magnet test), it stimulates its elec-
tronics and reports an alarm. It blinks its LEDs when polled
and turns the LEDs on when commanded by the panel. The
H355(A) Series offers features and performance that repre-
sent the latest in thermal detector technology.
df-52385:A • 12/17/08 — Page t of 2
Specifations
Diameter: 6.1" (15.5 cm) installed in 6350LP(A)
Height: 2.1" (5.33 cm).
Weight: 4.8 oz. (137 g).
Installation temperature: �°F to 100°F (-20°C to 38°C).
Humidity range: 10% to 93% relative humidity (noncon-
densing).
Voltage range: 15 to 32 VDC peak.
Standby current: 300 NA � 24 VDC (one communication
every five seconds with LED blink enabled).
LED current: 6.5 mA � 24 VDC.
Mounting: B350LP(A) flanged base, included.
Fixed-temperature setpoint: 135°F (57°C) for the H355(A)
and H355R(A); 190°F (88°C) for the H355HT(A).
Rate-of-rise detection: responds to greater than 15°F (8.3°C)
per minute.
Listings and Approvals
Listings and approvals below apply to the H355(A) Series
detectors. In some cases, certain modules may not be listed
by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
• MEA approved: file 387-02-E
• UL Listed, file S2517
• ULC Listed (models H355A, H355RA, H355HTA)
• CSFM approved: file 7270-0075:195
• FM approved
Product Line Information
NOTE: "A"suf/ix indicates ULC-Listed mode%
H355: Intelligent thermal sensor; B350LP base included.
H355A: Same as H355 but with ULC Listing (B350LPA base
included).
H355R: Same as H355 with rate-of-rise feature; 6350LP base
included.
H355RA: Same as H355R but with ULC Listing (6350LPA
base included).
H355HT: Intelligent fixed high-temperature thermal detector;
6350LP base included.
H355HTA: Same as H355HT but with ULC Listing (B350LPA
base included).
B350LP(A): Plug-in detector base (included). Dimensions:
6.1' (15.5 cm). Mounting: 4.0" (10.16 cm) square box with or
without plaster ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89
cm) octagonal box, or single-gang box. All mounting boxes
have a minimum depth of 1.5" (3.81 cm).
8224R6(A): Plug-in System Sensor re/ay detector base.
Diameter: 6.2" (15.75 cm). Mounting: 4.0" (10.16 cm) square
box with or without plaster ring, 4.0" (10.16 cm) octagonal box,
or 3.5" (8.89 cm) octagonal box. All mounting boxes have a
minimum depth of 1.5" (3.81 cm).
822461(A): Plug-in System Sensor iso/ator detector base.
Maximum 25 devices between isolator bases (see DF-52389).
Diameter: 6.2" (15.75 cm). Mounting: 4.0" (10.16 cm) square
box with or without plaster ring, 4.0" (10.16 cm) octagonal box,
or 3.5' (8.89 cm) octagonal box. All mounting boxes have a
minimum depth of 1.5" (3.81 cm).
B501 BH-2(A): Plug-in System Sensor standard sounder
base. Diameter: 6.0" (15.24 cm). Mounting: 4.0" (10.16 cm)
square box with or without plaster ring. Mounting boxes have a
minimum depth of 1.5" (3.81 cm).
6501 BHT 2(A): Plug-in System Sensor temporal tone
sounderbase.
ACCESSORIES:
RA400Z(A): Remote LED annunciator. 3- 32 VDC. Mounts to
a U.S. single-gang electrical box. For use with B501(A) and
B350LP(A) bases only.
SMK400E: Surface mounting kit provides for entry of surface
wiring conduit. For use with 6501(A) base only.
RMK400: Recessed mounting kit. For use with 6501(A) base
only.
M02-04-OO:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or removal
of detector heads from bases in high ceiling applications.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
m) sections.
Fire•Lite� Alarms is a registered trademark of Honeywelt Interna6onal Inc.
Bayblend� is a registered trademark of Bayer Corporation.
�2008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
I� O �0 0� This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
9YCINEHINC i MANIFACilAIN6 All specifications are subject to change without notice.
QUALITY S�STENS
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Page 2 of 2- df-52385:A • 12/17/OB