F12-0027 stamped approved
By David Rhoades at 8:28 am, Jun 20, 2012 302 XXXXX CT BLDG XXXXXXXXXXXXXXXXXXX 210108240020 XXXXXXXXXXXXXXXXXXXXXXXXXX ELLIS, GAIL GALVIN (OWNER)PRJ11-0022 B11-0071 F12-0027 Hydraulic Summary Report Description: KITCHEN / DINING CALC AREA Job Number: CH0142 Node Flow(gpm)Total Hose Streams 100.00 Safety Margin Required Available Node Hose FlowStaticResidualFlowTotal Demand (gpm)(psi)(psi)(gpm)(psi)(gpm)(psi)(psi)@ @ 1 107.27196.52710.744 583.00 100.00100.000 108.000159.65 Design Engineer Job Number Total Water Required (Including Hose Allowance)159.65 Maximum Pressure Unbalance In Loops 0.000 Additional Hose Supplies 100.00 Hose Allowance At Source Supplies 29.79gal NA NA NA NA 4 Occupancy Area of Application Coverage Per Sprinkler Number Of Sprinklers Calculated Density Manually Flowing Job Suffix AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Volume capacity of Dry Pipes Volume capacity of Wet Pipes 6.35 between nodes 1 and 2 Maximum Velocity Under Ground 21.89 between nodes 5 and 6 Maximum Velocity Above Ground 4.3 K-Factor 14.40 at 11.215 Most Demanding Sprinkler Data System 302 HANSON RANCH DR VAIL, CO. 81657 Job Site/Building VAIL FIRE 302 HANSON RANCH DR AHJ 12-032 302 HANSON RANCH DR - MILL CREEK COURT Job State Certification/License Number Job Name:STEVE ALLEN CH0142 Contractor Contractor Number 032 Name of Contractor:WESTERN STATES FIRE PROTECTION Address 1 274 CENTER DRIVE Address 2 Contact NameContact Title PM Extension Phone 720-219-0574 FAX 303-792-9049 E-mail STEVE.ALLEN@WSFP.US Web-Site STEVE ALLEN Address 3 GLENWOOD SPRINGS, CO 80601 Address 1 Address 2 Drawing Name 302 Hanson Ranch Rd - Mill Creek Court.cad System Flow Demand 59.65 Remote Area(s)Address 3 VAIL, CO. 81657 06/15/2012 © M.E.P.CAD, Inc.Page 1 AutoSPRINK® VR8 v8.1.11 7:31:45AM Pipe TypeDiameterFlowVelocityFriction LossLengthPressure DownstreamElevationDischargeK-FactorPtPnFittingsEq. LengthSummary Upstream Total Length HWC Hydraulic Analysis Job Number: CH0142 Report Description: KITCHEN / DINING CALC AREA • • • • • Route 1 • • • • •Pf Pe Pv DR1.055014.405.290.0456142'-11¾0.409 1019'-614.404.311.215Sprinkler,6'-0-0.857 811'-5¾10.7672E(2'-0), T(2'-0)8'-11¾150 Pf Pe Pv BL1.055028.9410.620.1659422'-60.415 811'-5¾14.5410.767Flow (q) from Route 3-0.200 711'-11¼10.9822'-6 150 Pf Pe Pv BL1.055043.4615.950.3519927'-102.761 711'-11¼14.5110.982Flow (q) from Route 2-0.627 613'-4½13.1167'-10 150 Pf Pe Pv BL1.055059.6521.890.63243645'-11¼38.544 613'-4½13.11615'-01.467 510'-053.1274E(2'-0), 3T(2'-0), EE(1'-0)60'-11¼150 Pf Pe Pv CM1.291059.6514.620.23661716'-10¾5.418 510'-053.1276'-0 410'-058.545E(2'-0), T(3'-0), cplg(1'-0)22'-10¾150 Pf Pe Pv FR1.527059.6510.450.1044628'-111.193 410'-058.5452'-6 310'-059.738E(2'-6)11'-5 150 Pf Pe Pv FR2.009059.656.040.02746343'-9¾14.870 310'-059.73817'-017.052 2-29'-491.660 4E(3'-6), BFP(-13.200), Tr(1'-0), 2cplg(1'-0)60'-9¾150 Pf Pe Pv UG1.959059.656.350.03104962'-62.049 2-29'-491.660Supply,3'-62.818 1-35'-1096.527E(3'-6), S66'-0 150 159.65 100.00Hose Allowance At Source 1 • • • • • Route 2 • • • • •Pf Pe Pv BL1.055014.515.330.0462880'-20.100 10211'-11¼14.514.410.882Sprinkler,2'-0 711'-11¼10.982T(2'-0)2'-2 150 • • • • • Route 3 • • • • •Pf Pe Pv BL1.055014.545.340.0464507'-100.457 10310'-0¾14.544.410.923Sprinkler,2'-0-0.613 811'-5¾10.767E(2'-0)9'-10 150 • • • • • Route 4 • • • • •Pf Pe Pv DR1.055016.195.940.0566804'-10½0.616 1049'-616.194.314.183Sprinkler,6'-0-1.683 613'-4½13.1162E(2'-0), T(2'-0)10'-10½150 1.51 4.87 150 1.33 140 1.16 130 0.713 100 Equivalent Pipe Lengths of Va lves and Fittings (C=120 only)Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.06/15/2012Page 1 AutoSPRINK® VR8 v8.1.11 7:27:13AM Pipe TypeDiameterFlowVelocityFriction LossLengthPressure DownstreamElevationDischargeK-FactorPtPnFittingsEq. LengthSummary Upstream Total Length HWC Hydraulic Analysis Job Number: CH0142 Report Description: KITCHEN / DINING CALC AREA Pipe Type Legend AOArm-Over BLBranch Line CMCross Main DNDrain DRDrop DYDynamic FMFeed Main FRFeed Riser MSMiscellaneous OROutrigger RNRiser Nipple SPSprig STStand Pipe UGUnderground Units Legend DiameterInch ElevationFoot Flowgpm Dischargegpm Velocityfps Pressurepsi LengthFoot Friction Losspsi/Foot HWCHazen-Williams Constant PtTotal pressure at a point in a pipe PnNormal pressure at a point in a pipe PfPressure loss due to friction between points PePressure due to elevation difference between indicated points PvVelocity pressure at a point in a pipe Fittings Legend ALVAlarm Valve AngVAngle Valve bBushing BalVBall Valve BFPBackflow Preventer BVButterfly Valve CCross Flow Turn 90°cplgCoupling CrCross Run CVCheck Valve DelVDeluge Valve DPVDry Pipe Valve E90° Elbow EE45° Elbow Ee111¼° Elbow Ee222½° Elbow fFlow Device fdFlex Drop FDCFire Department Connection fE90° FireLock(TM) Elbow fEE45° FireLock(TM) Elbow flgFlange FNFloating Node fTFireLock(TM) Tee gGauge GloVGlobe Valve GVGate Valve HoHose HoseHose HVHose Valve HydHydrant LtELong Turn Elbow mecTMechanical Tee NozNozzle P1Pump In P2Pump Out PIVPost Indicating Valve POPipe Outlet PRVPressure Reducing Valve PrVPressure Relief Valve redReducer/Adapter SSupply sCVSwing Check Valve SprSprinkler StStrainer TTee Flow Turn 90°TrTee Run UUnion WirFWirsbo WMVWater Meter Valve ZCap © M.E.P.CAD, Inc.06/15/2012Page 2 AutoSPRINK® VR8 v8.1.11 7:27:13AM Device (gpm)Actual FlowMinimum Flow (gpm)(K)K-Factor (psi)Pressure Summary Of Outflowing Devices Report Description: KITCHEN / DINING CALC AREA Job Number: CH0142 Sprinkler10114.4014.404.311.215 Sprinkler10214.5114.404.410.882 Sprinkler10314.5414.404.410.923 Sprinkler10416.1914.404.314.183 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.06/15/2012Page 2 AutoSPRINK® VR8 v8.1.11 7:33:45AM Hydraulic Graph Report Description: KITCHEN / DINING CALC AREA Job Number: CH0142 System Demand (Including Hose Allowance at Source)System Demand 100.000 @ 583.00 Residual: Pressure 108.000 Static: Pressure Supply at Node 1 Hydraulic Graph Supply at Node 1 96.527 @ 59.65 96.527 @ 159.65 Available Pressure at Time of Test 107.271 @ 159.65 © M.E.P.CAD, Inc.06/15/2012Page 3 AutoSPRINK® VR8 v8.1.11 7:31:51AM a company A B G C D F E in.mmin.mmin.mmin.mmin.mmin.mmin.mmin.mmin.mmlbs.k g lbs.k g 3/42012305143567 3/41972 1/8543763 1/289512715 3/4400104.5125.5 1251333014 1/43627 3/41972 1/8543763 1/289512717 3/4451104.5146.4 1 1/432174321948310 15/162782 3/4703 1/28951276 3/41712255922102812.7 1 1/24017 3/84412050810 15/162782 3/4703 1/28951276 3/417123 1/858722102812.7 25018 1/247021 1/454010 15/162782 3/4703 1/28951276 3/417125 1/264822103415.4 WEIGHT LESS BALL VALVES WITH BALL VALVES DEFG MODEL SIZE A DIMENSIONS (approximate)A UNION BALL VALVES B LESS BALL VALVES C •12" MIN 30" MAX PROTECTIVE ENCLOSURE OPTIONAL WATER METER INLET SHUT-OFF AIR GAP DRAIN DIRECTION OF FLOW BATTERY MONITOR SWITCH AIR GAP FITTING 12" MIN.30" MAX.FLOOR DRAIN DIRECTION OF FLOW FLOOR CENTRAL STATION ALARM PANEL Pipe size5 ft/sec7.5 ft/sec10 ft/sec15 ft/sec 1/8"1123 1/4"2235 3/8"3469 1/2"57914 3/4"8121725 1"13202740 1 1/4"23354770 1 1/2"32486395 2"5278105167 Capacity thru Schedule 40 Pipe 0 20 40 60 80 5 10 15 20 0 50 100 150 200 250 5 10 15 20 Rated Flow (Established by approval agencies)FLOW RATES (GPM)PRESSURE LOSS (PSIG) 69 PRESSURE LOSS (kpa) FLOW RATES (l/s)MODEL 975XL 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC)35 3/4" (20mm)1" (25mm)1 1/4" (32mm)2" (50mm)103 15.8 12.6 9.5 6.3 3.2 5.0 3.8 2.52 1.26 1½"(40mm)137 13.2 57.6 FOR HYDRAULIC CALCULATIONS ONLY. THE BACKFLOW WILL NOT BE INSTALLED AT THIS TIME. • a company DIRECTION OF FLOW WATER METER SHUT-OFF VALVE MODEL BR4 REGULATOR HOSE BIBB HOSE BIBB PRESSURE GAUGE 0 0 180 180 140 140 100 100 60 60 20 20 80 80 120 120 160 160 200 200 psi psi 40 40 PRESSURE GAUGE DIRECTION OF FLOW WATER METER SHUT-OFF VALVE MODEL BR4 REGULATOR HOSE BIBB WILKINS OPERATION OF ZURN INDUSTRIES, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com a company DOCUMENT #:REVISION:BV-800C5/05 Model 800C Swing Away Ball Valves For Liquid or Gas Installations SPECIFICATION SUBMITTAL SHEET APPLICATION Designed for installation on liquid or medical gas lines as a means of positive shut-off. The "swing away" design al-lows for repair and maintenance without removing the device from the line.DIMENSIONS & WEIGHTS (do not include pkg.)FEATURES Sizes: ½" ¾" 1" 1½" 2" 2 ½" 3"Maximum pressure400 PSI WOG Copper connections (FC)ANSI B16.22 MATERIALS Main valve bodyForged brass ( ½"-1")Cast bronze ASTM B 584 (1 ½"-3")BallBrass ASTM B 16, chrome plated Seat & p ackingTeflon O-ringsBuna Nitrile, NSF Listed A B C OPTIONS -with female copper inlet x outlet CL-with copper "L" tube extensions ACCESSORIES Repair kit; o-rings, stem and seats Bracket for locking ball valve handle in open position (Model BVLCK)Bracket and padlock (Model BVLCKP)SPECIFICATION The three piece swing away ball valve shall consist of a copper alloy body, two tailpieces, a hard-chromed copper alloy ball, two Teflon seats, a stem and coated handle. The stem shall be blow-out proof and the ball & seats replace-able in-line without the use of special tools. Tailpieces shall be designed to accept sweated copper tube or provided with copper tailpiece extensions. The three piece swing away ball valve shall be a WILKINS Model 800C.in.mmin.mmin.mmin.mmlbs.kg.1 /2152 1/8541 5/8413 7/89810.5 3/4202 3/4701 7/8483 7/89810.5 1253 1/2892514 1/211421.0 1 1/2404 7/81242 7/873615273.0 2505 1/21403 1/879615294.0 2 1/2656 3/81623 5/8926152178.0 3806 3/41724 3/8111123052210.0 SIZE WEIGHTS DIMENSIONS (approximate)ABC ModelRFC43(SINRA0612)ModelRFC49(SINRA0616)FlatConcealed ResidentialSprinklers AConcealedResidential Sprinklerengineeredfora minimumdesigndensity of0.05gpm/ft 2 withlowGPM requirements.Features 1.Verylowwaterflowrequirements.2.½(13mm)Totaladjustment.3.Thread-On/Thread-Offor Push-On/ThreadOff coverattachmentoption.4.Smoothaestheticceilingprofile.5.Availableinbrass,chromeand blackplatedorpaintedfinishes.ProductDescription ModelRFC43andRFC49ConcealedResidentialSprinklers arefastresponseresidentialf usiblesolderlinkautomatic sprinklers.Residentialsprinklersdifferfromstandard sprinklersprimarilyintheirresponsetimeandwater distributionpatterns.ModelRFC43andRFC49sprinklersdischargewaterina hemisphericalpatternbelowthesprinklerdeflector.Residentialdistributionpatternsarehigherandgenerally containafinerdropletsizethanstandardsprinklerpatterns.Thecombinationofspeedofoperationandhighdischarge patternrequiredforresidentialsprinklershasdemonstrated,infiretesting,anabilityforcontrollingresidentialfires,and therebyprovidingsignifi cantevacuationtimeforoccupants.TheRFC43andRFC49Sprinklersprovidethebestformof fireprotectionbycombininganattractiveappearanceand ½(13mm)ofcoveradjustmentforeaseofinstallation.The smalldiametercoverplateiseasilyandpositivelyattached andblendsintotheceiling,concealingthemostdependable fireprotectionavailable,anautomaticsprinklersystem.TheRFC43andRFC49areULListedResidentialSprinklers tobeinstalledintheresidentialportionsofanyoccupancyin accordancewithNFPA13,13R,&13D.TheRFC43andRFC49canreducetheneedforprecise cuttingofdropnipples.Thethreadedcoverplateassembly canbeadjustedwithouttoolstofitaccuratelyagainstthe ceiling.Thefireprotectionsystemneednotbeshutdownto adjustorremovethecoverplateassembly.ApplicationandInstallation TheRFC43andRFC49,forresidentialinstallations,usea 165 F(74 C)fusiblesolderlinkinatuningforkstylesprinkler framewithadrop-downdeflector.Thisassemblyisrecessed intotheceilingandconcealedbyaflatcoverplate.Thecover plateisattachedtotheskirt,using135 F(57 C)ordinary temperatureclassificationsolder.Whentheceiling temperaturerises,thesolder holdingthecoverplatereleases thecoverallowingthedeflectortodropintopositionand TheReliableAutomaticSprinklerCo.,Inc.,103FairviewParkDrive,Elmsford,NewYork10523 Bulletin006 Rev.D Listings&Approval 1.ListedbyUnderwritersLaboratories,andcertifiedbyULforCanada(cULus)2.NYCMEA258-93-E ULListingCategories ResidentialAutomaticSprinklers ULGuideNumber VKKW Bulletin006 Rev.D exposingthesprinklerinsidetoceilingtemperature.The subsequentoperationofthesolderlinkopensthewaterway andcausesthedeflectortodropintopositiontodistributethe dischargingwaterinahemisphericalpatternbelowthe sprinklerdeflector.Anyad justmentofthreadengagement betweenthecoverplateandcupwillassurethatthe drop-downdeflectorisproperlylocatedbelowtheceiling.Theresidentialdistributionpatterncontainsafinerdropletsize thanastandardsprinkler,andthepatternproduces significantlyhigherwallwetting.Aftera25/8inchdiameterholeiscutintheceiling,the sprinkleristobeinstalledwiththeModelFCWrench.When installingasprinkler,thewrenchisfirstpositionedintothe sprinkler/cupassemblyandaroundthehexagonalbodyof thesprinklerframe.TheWrenchmustbottomoutagainstthe cupinordertoensureproper,safeinstallation.Thesprinkler isthentightenedintothepipefitting.Wheninsertingor removingthewrenchfromthesprinkler/cupassembly,care shouldbetakentopreventdamagetothesprinkler.DONOT WRENCHONANYOTHERPARTOFTHESPRINKLER/CUP ASSEMBLY.MODELRFC43ANDRFC49CONCEALED SPRINKLERSMUSTBEINSTALLEDONLYWITH135°F RATEDCOVERS.Coverassembliesprovideupto 1 2 (13mm)of adjustment.Turnthecoverclockwiseuntiltheflangeisin contactwiththeceiling.Forthepush-on/thread-offoption,thecoverassemblyispushedontothecupandfinal adjustmentismadebyturningthecoverclockwiseuntilthe skirtflangemakesfullcontactwiththeceiling.Cover removalrequiresturninginthecounter-clockwisedirection.Inceilingsthathaveaplenumspaceabovethesprinkler,theplenumspacemayhaveneutralornegative pressurizationbutmustnotbepo sitivelypressurized.Inspect allsprinklersafterinstallationtoensurethatthegapbetween thecoverplateandceilingandthe4slotsinthecupareall openandfreefromanyairflowimpediment.SprinklerCoverPlate Max.Ambient Temp.165 o F/74 o C135 o F/57 o C100 o F/38 o C TemperatureRating ThreadSize inch(mm)K Factor Sprinkler Spacing ft.(m)Maximum Distance toWallft.(m)Minimum Distancebetween sprinklers,ft.(m)MinimumRequired SprinklerDischarge Flow gpm(Lpm)Press.psi(bar)½(15mm)½(15mm)½(15mm)½(15mm)½(15mm)4.3 4.3 4.3 4.3 4.3 12x12(3.6x3.6)14x14(4.3x4.3)16x16(4.9x4.9)18x18(5.5x5.5)20x20(6.0x6.0)6(1.83)7(2.13)8(2.43)9(2.74)10(3.05)8(2.43)8(2.43)8(2.43)8(2.43)8(2.43)12(45)13(49)13(49)18(68)21(79)7.8(0.54)9.1(0.63)9.1(0.63)17.5(1.21)23.8(1.64)InstallationData:RFC43(SINRA0612)Note:1bar=100Kpa 2.ThreadSize inch(mm)K Factor Sprinkler Spacing ft.(m)Maximum Distance toWallft.(m)Minimum Distancebetween sprinklers,ft.(m)MinimumRequired SprinklerDischarge Flow gpm(Lpm)Press.psi(bar)½(15mm)½(15mm)½(15mm)½(15mm)½(15mm)4.9 4.9 4.9 4.9 4.9 12x12(3.6x3.6)14x14(4.3x4.3)16x16(4.9x4.9)18x18(5.5x5.5)20x20(6.0x6.0)6(1.83)7(2.13)8(2.43)9(2.74)10(3.05)8(2.43)8(2.43)8(2.43)8(2.43)8(2.43)13(49)13(49)13(49)17(64.3)20(75.7)7.0(0.48)7.0(0.48)7.0(0.48)12.0(0.83)16.7(1.14)InstallationData:RFC49(RA0616)Note:1bar=100Kpa FORSLOPEDCEILINGAPPLICATIONSSEERASCOBULLETIN035.CALCED AT 14.4 GPM FOR 12 X 12 SPACING @ .1 DENSITY Maintenance ModelRFC43andRFC49ConcealedSprinklersshouldbe inspectedquarterlyandthesprinklersystemmaintainedin accordancewithNFPA25.Donotcleansprinklerswithsoap andwater,ammoniaoranyot hercleaningfluids.Remove dustbyusingasoftbrushorgentlevacuuming.Removeany sprinklercoverplateassemblywhichhasbeenpainted(other thanfactoryapplied)ordamagedinanyway.Astockof sparesprinklersshouldbemaintainedtoallowquick replacementofdamagedoroperatedsprinklers.Priorto installation,sprinklersshouldbemaintainedintheoriginal cartonsandpackaginguntilusedtominimizethepotentialfor damagetosprinklersthatwouldcauseimproperoperationor non-operation.OrderingInformation Specify:1.SprinklerModel 2.CoverPlateFinish 3.Thread-Onor Push-OnFeature StandardFinishes Chrome White SpecialApplication Finishes BrightBrass BlackPlating BlackPaint OffWhite SatinChrome CoverPlateFinishes (1)(1)Othercolorsandfinishes available.Consultfactory fordetails.Note:Paintoranyother coatingsappliedoverthe factoryfinishwillvoidall approvalsandwarranties.3.ModelRFC43andRFC49Residential ConcealedSprinklerSpecification SprinklersshallbecULusListedlowflowresidential concealedsprinklerswithdrop-downdeflectorand adjustableflatcoverplateengineeredforaminimumdesign densityof0.05gpm/ft 2 .Sprinklerframeanddeflectorshallbe ofbronzeframeconstructionhavinga½”NPTthread.Thermalelementshallconsisto fanapprovedblack-painted beryllium-nickelfusiblesolderlinkwithsymmetriclever mechanism,maintainingaTef lon-coatedBellevillespring washerandmachinedbrasscapwatersealassembly containingnoplasticparts.Sprin klerK-factorshallbenominal 4.3(62.4),havinga7/16”orifi ce.Temperatureratingshallbe Ordinary165 F(74 C);coverplatetemperatureratingtobe 135 F(57 C).Coverplateassemblyshallconsistofabrass coverplateandcopperalloyretainerflangeallowinga½”coverplateadjustment.Any secureengagementbetween thecoverplateandthecupwillassurethatthedrop-down deflectorisproperlylocatedbelowtheceiling.Aplastic protectivecapshallbeprovide dandfactoryinstalledinside thesprinklercuptoprotectthedrop-downsprinklerdeflector fromdamage,whichcouldoccurduringconstructionbefore thecoverplateisinstalled.Standardcoverfinish:[Chrome][White][Specialty–specify].Residentialconcealedsprinklers shallbeReliableModelRFC43,SINRA0612(Bulletin006)or ModelRFC49,SINRA0616(Bulletin006). Manufacturedby:Revisionlinesindicateupdatedornewdata E.G.PrintedinUSA.12/06P/N9999970261 Recycled Paper TheequipmentpresentedinthisbulletinistobeinstalledinaccordancewiththelatestpertinentStandardsoftheNationalFireProtectionAssocia tion,FactoryMutual ResearchCorporation,orothersimilarorganizationsandalsowiththeprovisionsofgovernmentalcodesorordinances,wheneverapplicable.Productsmanufacturedanddistributedb yRELIABLEhavebeenprotectinglifeandpropertyforo ver80years,andareinstalledandservicedbythemost highlyqualified andreputablesprinklercontractorslocatedthroughout theUnitedStates,Canad aandforeigncountries.TheReliableAutomaticSprinklerCo.,Inc.(800)431-1588SalesOffices (800)848-6051SalesFax (914)829-2042CorporateOffices www.reliablesprinkler.com InternetAddress Reliable...ForCompleteProtection Reliableoffersawideselectionofsprinklercomponents.Followingaresomeofthemany precision-madeReliableproductsthatguardlifeandpropertyfromfirearoundtheclock.•Automaticsprinklers •Flushautomaticsprinklers •Recessedautomaticsprinklers •Concealedautomaticsprinklers •Adjustableautomaticsprinklers •Dryautomaticsprinklers •Intermediatelevelsprinklers •Opensprinklers •Spraynozzles •Alarmvalves •Retardingchambers •Drypipevalves •Acceleratorsfordrypipevalves •Mechanicalsprinkleralarms •Electricalsprinkleralarmswitches •Waterflowdetectors •Delugevalves •Detectorcheckvalves •Checkvalves •Supertrolelectricalsystem •Sprinkleremergencycabinets •Sprinklerwrenches •Sprinklerescutcheonsandguards •Inspectorstestconnections •Sightdrains •Balldripsanddrumdrips •Controlvalveseals •Airmaintenancedevices •Aircompressors •Pressuregauges •Identificationsigns •Firedepartmentconnection TheReliableAutomaticSprinklerCo.,Inc.,103FairviewParkDrive,Elmsford,NewYork10523 Bulletin176 Rev.A Bulletin176 Rev.A ModelF1ResSprinklersengineeredforthelowestflows tomeettheminimumdesigndensityof.05gpm/ft 2 Types:1.F1Res49Pendent 2.F1Res49RecessedPendent/F1 3.F1Res49RecessedPendent/FP 4.F1Res49CCPPendent 5.F1Res58Pendent 6.F1Res58RecessedPendent/F1 7.F1Res58RecessedPendent/FP 8.F1Res58CCPPendent 9.F1Res44&58HSW 10.F1Res44&58HSWRecessedHSW/F2 11.F1Res76Pendent 12.F1Res76RecessedPendent/F1 13.F1Res76RecessedPendent/FP 14.F1Res76CCPPendent Listings&Approvals 1.ListedbyUnderwritersLaboratoriesInc.and ULCertifiedforCanada(cULus)ProductDescription ModelF1ResPendentsprinklers(Figs.1,2,3&4)combineexcellentdurability,highsensitivityglass-bulb andlowprofiledecorativedesign.The3mmglass-bulbpendentsprinklerspermitthe efficientuseofresidentialwatersuppliesforsprinkler coverageinresidentialfireprotectiondesign.ThelowflowF1Ressprinklersarespecially engineeredforfastthermalresponsetomeetthe sensitivefireprotectionapplicationneedsofthelatest residentialmarketstandards(UL1626Standard *Uponfireconditions,risingheatcausesasprinkler’s heat-sensitiveglass-bulbtoshatter,releasingthe waterwayforwaterflowontothedeflector,evenly distributingthedischargedwatertocontrolafire.Application ModelF1ResSprinklersareusedforResidentialFire ProtectionaccordingtoUL1626Standard *.Besure thatorificesize,temperaturerating,deflectorstyleand sprinklertypeareinaccordancewiththelatest publishedstandardsofTheNationalFireProtection Associationortheapprovingauthorityhaving jurisdiction.WhenusingF1ResidentialSprinklersforsystems designtoNFPA13DorNFPA13R,uselistedareaof coverageandminimumflowandpressurerequirements showninBulletin135.ForsystemsdesignedtoNFPA13,useinformationin thisbulletin.Thenumberofdesignsprinklersshallbethe mosthydraulicallydemandingsprinklersasrequiredby NFPA13.Flowsandpressurescannotbebelowthe baselineflowsandpressurers.F1Res49,58&76 RecessedPendent/F1 F1Res49,58&76 RecessedPendent/FP F1Res49,58&76 CCPPendent ULListingCategory ResidentialAutomaticSprinkler ULGuideNumber VKKW Patents USPatentNo.6,516,893appliestothe ModelF1Res49&58PendentSprinklers TechnicalData:•ThermalSensor:Nominal3mmglass-bulb •SprinklerFrame:BrassCasting •Sprinklers’PressureRating:175psi FactoryHydrostaticallyTestedto500psi •ThreadSize:½”NPT(R1/2)•K-Factor:4.9(Actual)-F1Res49PendentSprinkler 5.8(Actual)-F1Res58Pendent&HSWSprinkler 7.6(Actual)-F1Res76PendentSprinkler 4.4(Actual)-F1Res44HSWSprinkler •Density:Minimum0.10gpm/ft 2 F1Res44&58 RecessedHSW/F2 ModelF1 ResidentialSprinklersfor DesignDensityof.10gpm/ft 2 NFPA13 ForresidentialsprinklersystemsdesignedtoNFPA13,aminimumdensityof0.1gpm/ft 2 mustbeprovidedover the“designarea”thatincludesthefour(4)hydraulically mostdemandingsprinklersfortheactualcoverage areasbeingprotectedbythe4sprinklers.Theminimum requireddischargefromeachofthefourmost hydraulicallydemandingsprinklersshallbethe greater ofthefollowing:1.TheflowratesgivenintheReliableResidential SprinklerTechnicalBulletinsreferencedinTableA forNFPA13Dand13Rasafunctionoftemperature ratingandmaximumallowablecoveragearea(for actualcoverageareaslessthanorbetweenthose indicatedintherespectivetechnicalbulletin,itis requiredtousetheminimumrequiredflowforthe nextlargestcoveragearea);or 2.Aminimumdischargedensityof0.1gpm/ft 2 appliedoverthe“designarea”consistingofthefour mosthydraulicallydemandingsprinklersforthe actualcoverageareasbeingprotectedbythefour sprinklers.Themaximumdimensionoftheactual coverageareacannotbeanygreaterthanthe maximumcoverageareaindicatedinthetechnical bulletinsreferencedinTableA.DesignNote:UsingtheA s =SxLmethodto determinethesprinklerprotectionareaofcoverage inaccordancewithNFPA13,applythe0.1gpm/ft 2 densitytothisareatodeterminetheminimum requiredflow.Comparethisflowtotheminimum 0.05gpm/ft 2 cULusListedflowfortheappropriate coverageareainthetechnicalbulletinforthe specificresidentialsprinkler.Iftheflowstatedinthe technicalbulletinislessthanthecalculated0.1 gpm/ft 2 densityflowrequired,the.1densityflow mustthenbeusedintheequationQ=K P ,solving forP,toestablishtheminimumrequiredpressure usingthesprinklerK-factor.Note:Inmanycases thelistedflowofindividualresidentialsprinklers mayexceedtherequiredminimum0.05gpm/ft 2 density.Reliablehasavailableresidentialsprinklers withlargerK-factors(K=5.8andK=7.6)thatwill providelowerpressuredemandsfor0.1gpm/ft 2 densitiesinNFPA13residentialapplications.ExampleNo.1 RoomSize=12ftx20ft(3.6mx6.1m)CoverageArea=12x20=240ft 2 (22.3m 2 )Flow@0.10gpm/ft 2 density=240x0.10=24gpm UsinganF1Res49PendentSprinkler,K=4.9 Pressure=(24/4.9)2 =24psi(1.65bar)Thebaselineflowfora20ftx20ft(6.1mx6.1m)coverageareausingthebaselinedensityof0.05 gpm/ft 2 willbe20gpm@16.7psi(75.7L/min@1.14 bar).Therefore,theminimumflowrequiredis24gpm@ 24psi(90.8L/min@1.65bar).ExampleNo.2 RoomSize=8ftx20ft(2.4mx6.1m)CoverageArea=8x20=160ft 2 (14.9m 2 )Flow@0.10gpm/ft 2 density=160x0.10=16gpm UsinganF1Res49PendentSprinkler,K=4.9 Pressure=(16/4.9)2 =10.7psi(0.74bar)Thebaselineflowfora20ftx20ft(6.1mx6.1m)coverageareausingthebaselinedensityof0.05 gpm/ft 2 willbe20gpm@16.7psi(75.7L/min@1.14 bar).Therefore,theminimumflowrequiredis20gpm@ 16.7psi(75.7L/min@1.14bar).ExampleNo.3 RoomSize=10ftx16ft(3.0mx4.91m)CoverageArea=10x16=160ft 2 (14.9m 2 )Flow@0.10gpm/ft 2 density=160x0.10=16gpm UsinganF1Res76PendentSprinkler,K=7.6 Thebaselineflowfora16ftx16ftcoverageareais21 gpm@7.6psi(79.5L/min@0.52bar).Therefore,the minimumflowandpressureis21gpm@7.6psi(79.5 L/min@0.52bar).ExampleNo.4 RoomSize=14ftx18ft(4.3mx5.5m)CoverageArea=14x18=252ft 2 (23.6m 2 )Flow@0.10gpm/ft 2 density=252x0.10=25.2gpm (94.6L/min)UsinganF1Res76PendentSprinkler,K=7.6 Pressure=(252/7.6)2 =11psi(0.76bar)Thebaselineflowandpressureofan18ftx18ft coverageareais21gpm@7.6psi(79.5L/min@0.52 bar).Therefore,theminimumflowandpressureis25.2 gpm@11psi(94.6L/min@0.76bar).I ngeneralresidentialsprinklersrequire flowsandpressuresaslistedfor0.05 densitiestoachievetheproperspraypattern sotheflowsandpressuresat0.05densityare thebaselineflowsandpressures.Flowsand pressuresbelowthelisted0.05densityshall notbeused.2. ModelF1Res49,58&76Pendent ModelF1Res49,58&76 RecessedPendent/F1/F2 Fig.1 Fig.2 F1escutcheon,3 4 (19mm)adjustment 3.Installation ModelsF1Ressprinklersaretobeinstalledas shown.ModelF1,F2andFPEscutcheons,illustrated herewith,aretheonlyrecessedescutcheonstobeused withModelF1Ressprinklers.Useofanyother recessedescutcheonwillvoidallapprovalsand warranties.ForinstallingModelF1ResPendent sprinklersuseonlytheModelDsprinklerWrench;for installingModelsF1ResRecessedPendent,CCP sprinklersuseonlytheModelGFR2sprinklerwrench;forinstallingModelF1ResrecessedHSWsprinklers useonlytheModelGFR2Sprinklerwrench.Useof wrenchesotherthanthosespecifiedmaydamage thesesprinklers.Note:A‘leaktight”sprinklerjointcanbeobtainedwith thefollowingtorque:•¾”NPT(R3/4)–14-20ft-lbs(19-27.1N-m)•½”NPT(R1/2)–8-18ft-lbs(10.8–24.4N-m)Donottightensprinklersovermaximum recommendedtorque.Itmaycauseleakageor impairmentofthesprinklers.Note:Seeescutcheontablefordimensions. 4.Thread Size Sprinkler Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.Actual K Factor Sprinkler Length Inch(mm)F C F C 1 2 NPT (R 1 2 )155 175 68 79 175(12)100 150 38 66 4.92.25(57)Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)13(49)7.0(0.48)R3516 14x14(4.3x4.3)13(49)7.0(0.48)16x16(4.9x4.9)13(49)7.0(0.48)18x18(5.5x5.5)17(64.3)12.0(0.83)20x20(6.1x6.1)20(75.7)16.7(1.14)Deflector-to-ceiling Maximum1 (25mm)to4 (100mm)Type Adjustment Inch(mm)“A”Inch(mm)Faceoffittingto ceiling Inch(mm)F1 3 4 (19.0)Min.=3 4 (19.1)Max.=1 1 2 (38.1)3 16 -15 16 (4.7-24.0)F2 1 2 (12.7)Min.=15 16 (23.8)Max.=1 1 2 (38.1)3 16 -11 16 (4.7-17.4)Escutcheon *,F1orF2,Data:*Note:Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)15(57)9.4(0.65)R3516 14x14(4.3x4.3)16(60.5)10.6(0.73)16x16(4.9x4.9)17(64.3)12.0(0.83)18x18(5.5x5.5)19(72)15.0(1.0)20x20(6.1x6.1)22(83.2)20.2(1.4)*Deflector-to-ceiling Maximum4 (100mm)to8 (203mm)*Note:TheF1Res49pendentandrecessedpendent residentialsprinklerscanbeinstalledperNFPA13in beamedceilingsmeetingthefollowingcriteria:1.Maximumbeamdepth=7 (178mm)2.Beamspacingatorgreatert han7.5ft.(2.3m)oncenter.TechnicalData:F1Res49PendentandRecessedPendent Thread Size Sprinkler Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F C ½NPT (R½)155 175 68 79 175(12)100 150 38 66 5.82.25(57)Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Ceiling-to-Deflector Inch(mm)Sprinkler Identification Number(SIN)12x12(3.6x3.6)16(61)7.6(0.53)1-4 (25-100)R3513 14x14(4.3x4.3)16(61)7.6(0.53)16x16(4.9x4.9)16(61)7.6(0.53)18x18(5.5x5.5)19(72)10.8(0.75)20x20(6.1x6.1)22(83.3)14.4(1.0)TechnicalData:F1Res58PendentandRecessedPendent **Baselineflowsandpressuresfor0.05density **Baselineflowsandpressuresfor0.05density **Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures 5.ModelF1Res49,58&76 CCPPendent ModelF1Res49,58&76 RecessedPendent/FP FPpush-on/thread-off escutcheon Fig.4 Fig.3 NOTE:TheF1Res76willusea1"x¾"reducer.TechnicalData:F1Res76PendentandRecessedPendent Thread Size Sprinkler Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F C 3 4 NPT (R 3 4 )155 175 68 79 175(12)100 150 38 66 7.62.25(57)Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)217.6(0.53)R7618 14x14(4.3x4.3)217.6(0.53)16x16(4.9x4.9)217.6(0.53)18x18(5.5x5.5)217.6(0.53)20x20(6.1x6.1)239.2(0.63)Type Adjustment Inch(mm)“A”Inch(mm)Faceoffittingto ceiling Inch(mm)F1 3 4 (19.0)Min.=3 4 (19.1)Max.=1 1 2 (38.1)3 16 -15 16 (4.7-24.0)F2 1 2 (12.7)Min.=15 16 (23.8)Max.=1 1 2 (38.1)3 16 -11 16 (4.7-17.4)*Baselineflowsandpressuresfor0.05density *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures 6.Thread Size Sprinkler Temp.Rating CCP Assembly Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F°C F C ½NPT (R½)1556813557175(12)100384.92.25(57)Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)13(49)7.0(0.48)R3516 14x14(4.3x4.3)13(49)7.0(0.48)16x16(4.9x4.9)14(53)8.2(0.56)18x18(5.5x5.5)18(68.1)13.5(0.93)20x20(6.1x6.1)20(75.7)16.7(1.14)“A”CoverAdjustment Inch(mm)“B”CCPHeight Inch(mm)1 2 (12.7)15 16 (24)3 16 (4.7)3 4 (19)CCPOptionsData:FPPosition “A”Inch(mm)Max.Recessed 7 16 (11)Min.Recessed 15 16 (24)FPData“A”:TechnicalData:F1Res49CCPPendentandRecessedPendent/FP Note:SprinklersshowninFig.3andFig.4arenot suitableforinstallationinceilingswhichhave positivepressureinthespaceabove.Thread Size Sprinkler Temp.Rating CCP Assembly Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F°C F C ½NPT (R½)1556813557175(12)100385.82.25(57)Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)16(61)7.6(0.53)R3513 14x14(4.3x4.3)16(61)7.6(0.53)16x16(4.9x4.9)16(61)7.6(0.53)18x18(5.5x5.5)19(72)10.8(0.75)20x20(6.1x6.1)22(83.3)14.4(1.0)TechnicalData:F1Res58CCPPendentandRecessedPendent/FP Thread Size Sprinkler Temp.Rating CCP Assembly Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F°C F C ¾NPT (R3/4)155 175 68 79 13557175(12)100 150 38 66 7.62.25(57)Max.Sprinkler Spacing ft(m)Flow gpm(Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)217.6(0.53)R7618 14x14(4.3x4.3)217.6(0.53)16x16(4.9x4.9)217.6(0.53)18x18(5.5x5.5)228.4(0.58)20x20(6.1x6.1)2510.8(0.74)TechnicalData:F1Res76CCPPendentandRecessedPendent/FP *Baselineflowsandpressuresfor0.05density *Baselineflowsandpressuresfor0.05density *Baselineflowsandpressuresfor0.05density *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures ModelF1Res44&58HSW ModelF1Res44&58 RecessedHSW/F2 F2escutcheon,1 2 (13mm)adjustment Thread Size Sprinkler Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F C ½NPT (R½)155 175 68 79 175(12)100 150 38 66 4.42.45(62)Type Adjustment Inch(mm)FaceofFitting towall Inch(mm)F2 1 2 (13)3 16 -11 16 (4.7-17.4)Escutcheon,F2,Data:TechnicalData:F1Res44HSW&HSW/F2 Max.Sprinkler Spacing ft(m)“A”Ceiling-to-Deflector Inch(mm)SprinklerTemp.Rating F(C)Flow gpm (Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)4-6 (101-152)155(68)175(79)12(45.4)7.5(0.52)R3531 14x14(4.3x4.3)155(68)175 (79)14(53.0)10.2(0.71)16x16(4.9x4.9)155(68)175 (79)16(60.6)13.3(0.92)16x18(4.9x5.5)155(68)175 (79)18(68.1)16.8(1.16)18x18(5.5x5.5)155(68)175 (79)19(72.0)18.7(1.29)16x20(4.9x6.1)155(68)175 (79)23(87.1)27.4(1.89)12x12(3.6x3.6)6-12 (152-305)155(68)175(79)14(53.0)10.2(0.71)14x14(4.3x4.3)155(68)175 (79)16(60.6)13.3(0.92)16x16(4.9x4.9)155(68)175 (79)17(64.4)15.0(1.04)16x18(4.9x5.5)155(68)175 (79)20(75.7)20.7(1.43)16x20(4.9x6.1)155(68)175 (79)23(87.1)27.4(1.89)*Baselineflowsandpressuresfor0.05density *Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures 7.CALCED AT 14.4 GPM FOR 12 X 12 SPACING @ .1 DENSITY Thread Size Sprinkler Temp.Rating Max.Pressure psi(bar)Max.Ambient Temp.K Factor Sprinkler Length Inch(mm)F C F C ½NPT (R½)155 175 68 79 175(12)100 150 38 66 5.82.45(62)Type Adjustment Inch(mm)FaceofFitting towall Inch(mm)F2 1 2 (13)3 16 -11 16 (4.7-17.4)Escutcheon,F2,Data:TechnicalData:F1Res58HSW&HSW/F2 Max.Sprinkler Spacing ft(m)“A”Ceiling-to-Deflector Inch(mm)SprinklerTemp.Rating F(C)Flow gpm (Lpm)Pressure psi(bar)Sprinkler Identification Number(SIN)12x12(3.6x3.6)4-6 (101-152)155(68)175(79)16(60.6)7.6(0.53)R3533 14x14(4.3x4.3)155(68)175 (79)18(68.2)9.7(0.67)16x16(4.9x4.9)155(68)175 (79)21(79.5)13.2(0.91)16x18(4.9x5.5)155(68)175 (79)25(94.7)18.6(1.28)16x20(4.9x6.1)155(68)175(79)29(109.8)25(1.73)12x12(3.6x3.6)6-12 (152-305)155(68)175(79)22(83.3)14.4(1.0)14x14(4.3x4.3)155(68)175 (79)22(83.3)14.4(1.0)16x16(4.9x4.9)155(68)175 (79)26(98.4)20.1(1.39)16x18(4.9x5.5)155(68)175 (79)31(117.4)28.6(1.97)*Baselineflowsandpressuresfor0.05density 8.*Calculatefora.10densitybutinnocase gobelowthebaselineflows&pressures 9.OrderingInformation Specify:1.SprinklerModel 2.SprinklerType 3.TemperatureRating 4.SprinklerFinish 5.EscutcheonFinish Maintenance ModelF1Res49,F1Res58&F1Res76Sprinklers shouldbeinspectedquarterly,andthesprinklersystem maintainedinaccordancewithNFPA25,13,13D,and 13R.Donotcleansprinklerwithsoapandwater,Ammonia oranyothercleaningfluids.R emovedustbyusingasoft brushorgentlevacuuming.Removeanysprinklerwhich hasbeenpainted(otherthanfactoryapplied)ordamaged inanyway.Astockofsparesprinklersshouldbe maintainedtoallowquickreplacementofdamagedor operatedsprinklers.Priortoin stallation,sprinklersshould remainintheoriginalcartonsandpackaginguntilused.Thiswillminimizethepotentialfordamagetosprinklersthat couldcauseimproperoperationornon-operation.StandardFinishes SprinklerF1,F2,FPEscutcheons Bronze ChromePlated WhitePolyesterCoated Brass BrightChromePlated WhitePainted SpecialApplicationFinishes SprinklerF1,F2,Escutcheons BrightBrass BlackPlated BlackPaint OffWhite SatinChrome BrightBrass BlackPlated BlackPaint OffWhite SatinChrome Finishes (1)(1)Otherfinishesandcolorsareavailableonspecialorder.Consultfactoryfordetails.ModelF1RES49Residential SprinklerSpecifications ModelF1Res49&58Pendent Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialpendent sprinklersengineeredtoprovideaminimumdesign densityof0.10gpm/ft 2 overthelistedcoveragearea.Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’s installationguidelinesandtheapplicableinstallation standard.Wherependentresidentialsprinklersare installedunderslopedceilingshavingapitchofupto[4/12][8/12],thesprinklerss hallbelistedforsuchuse.Deflector-to-ceilingdistancelistingshallbe1”to8”maximum.Sprinklerframeanddeflectorshallbeofbronze frameconstructionhavinga½”NPTthread.Waterseal assemblyshallconsistofaTeflon-coatedBellevillespring washerandtop-loadedextrudedcupwith3mmglassbulb containingnoplasticparts ,andhavingatemperature ratingof[155 F(68 C)][175 F(79 C)].Sprinklersshall haveanominalK-factorof4.9&5.8.Standardfinish:[Bronze][Chrome-plated][WhitePolyester][Specialfinish–specify].ResidentialpendentsprinklersshallbeReliable ModelF1Res49&58,SINR3516&R3513(Bulletin135).ModelF1Res49&58RecessedPendent/F1,ModelF1Res49&58RecessedPendent/F2,ModelF1Res49&58RecessedPendent/FP Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialrecessed pendentsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft 2 overthelistedcoveragearea.Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’sinstallation guidelinesandtheapplicableinstallationstandard.Where pendentresidentialsprinklersareinstalledundersloped ceilingshavingapitchofupto[4/12][8/12],thesprinklers shallbelistedforsuchuse.Deflector-to-ceilingdistance listingshallbe1”to8”maximum.Sprinklerframeand deflectorshallbeofbronzeframeconstructionhavinga½”NPTthread.Watersealassemblyshallconsistofa Teflon-coatedBellevillespringwasherandtop-loaded extrudedcupwith3mmglassbulbcontainingnoplastic parts,andhavingatemperatureratingof[155 F(68 C)][175 F(79 C)].SprinklersshallhaveanominalK-factorof 4.9(70).Standardfinish:[Br onze][Chrome-plated][White Polyester][Specialfinish –specify].Recessedescutcheon assemblyshallbeasteel,two-pieceescutcheon[with½”adjustment(ModelF2)][with¾”adjustment(ModelF1)][of push-onandthreadoffdesignwith½”adjustment(Model FP)].Standardfinishshallbe[brass][brightchrome][white painted].Residentialrecessedpendentsprinklersshallbe Reliable[ModelF1Res49&58RecessedPendent/F1][ModelF1Res49&58RecessedPendent/F2][ModelF1 Res49&58RecessedPendent/FP]SINR3516&R3513 (Bulletin135). 10.ModelF1Res49&58CCPPendent(Concealed)Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialconcealed sprinklersengineeredtoprovideaminimumdesign densityof0.10gpm/ft 2 overthelistedcoveragearea.Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshall beinstalledinconformancewiththemanufacturer’s installationguidelinesandtheapplicableinstallation standard.Wherependentresidentialsprinklersare installedunderslopedceilingshavingapitchofupto [4/12][8/12],thesprinklers shallbelistedforsuchuse.Sprinklerframeanddeflectorshallbeofbronzeframe constructionhavinga½”NPTthread.Waterseal assemblyshallconsistofaTeflon-coatedBelleville springwasherandtop-loadedextrudedcupwith3mm glassbulbcontainingnopl asticparts,andhavinga temperatureratingof155 F(68 C).Coverplate assemblyshallconsistofabrasscoverplateandcopper alloyretainerflange.Methodofattachingthecoverplate tothesprinklercupshallbeapush-onandthread-off designallowinga½”coverplateadjustment.Cover platetemperatureratingshallbe135 F(57 C).Aplastic protectivecapshallbeprovi dedandfactoryinstalled insidethesprinklercuptoprotectthesprinklerfrom damage,whichcouldoccurduringconstructionbefore thecoverplateisinstalled.Standardcoverplatefinish:[White][CustomColor–specify].].Concealedpendent sprinklersshallbeReliableModelF1Res49&58CCP,SINR3516&R3513(Bulletin135).ModelF1Res44&58HorizontalSidewall Sprinkler Sprinklersshallbe[cULusListed][NewYorkCityMEA Approved(258-93-E)]lowflowresidentialhorizontal sidewallsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft 2 overthelistedcoverage area.Listedflowsasspecifiedbythemanufacturer’s technicaldatasheetsaretobeused.Residential sprinklersshallbeinstalledinconformancewiththe manufacturer’sinstallationguidelinesandtheapplicable installationstandard.Wherehorizontalsidewall residentialsprinklersareinstalledunderslopedceilings havingapitchofupto[4/12][8/12],thesprinklersshall belistedforsuchuse.Sprinklerframeanddeflectorshall beofbronzeframeconstructionhavinga½”NPTthread.WatersealassemblyshallconsistofaTeflon-coated Bellevillespringwasherandtop-loadedextrudedcup with3mmglassbulbcontainingnoplasticparts,and havingatemperatureratingof[155 F(68 C)][175 F (79 C)].SprinklersshallhaveanominalK-factorof5.8.Standardfinish:[Bronze][Chrome-plated][White Polyester][Specialfinish–sp ecify].Residentialhorizontal sidewallsprinklersshallbeReliableModelF1Res58,SINR3513(Bulletin135).ModelF1Res44&58Recessed HorizontalSidewallSprinkler UsedescriptionfortheModelF1Res58horizontal sidewallsprinklerwiththefollowingmodifications:Replace“horizontalsidewallsprinkler”with“recessed horizontalsprinkler.”Add:Recessedescutcheon assemblyshallbeasteel,two-pieceescutcheonwith½”adjustment(ModelF2).Standardfinishshallbe [brass][brightchrome][whitepainted][Specialfinish–specify].Residentialrecessedhorizontalsidewall sprinklersshallbeReliableModelF1Res58/F2,SIN R3513(Bulletin135).ModelF1Res76Pendent Sprinklersshallbe[cULusListed]lowflowresidential pendentsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft 2 overthelistedcoveragearea.Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’sinstallation guidelinesandtheapplicableinstallationstandard.Sprinklerframeanddeflectorshallbeofbronzeframe constructionhavinga¾”NPTthread.Watersealassembly shallconsistofaTeflon-coated Bellevillespringwasherand machinedcupwith3mmglassbulbcontainingnoplastic parts,andhavingatemperatureratingof[155 F(68 C)][175 F(79 C)].SprinklersshallhaveanominalK-factorof 7.6.Standardfinish:[Bronz e][Chrome-plated][White Polyester][Specialfinish–specify].Residentialpendent sprinklersshallbeReliableModelF1Res76,SINR7618 (Bulletin135). ModelF1Res76RecessedPendent/F1,ModelF1Res76RecessedPendent/F2,ModelF1Res76RecessedPendent/FP Sprinklersshallbe[cULusListed]lowflowresidential recessedpendentsprinklersengineeredtoprovidea minimumdesigndensityof0.10gpm/ft 2 overthelisted coveragearea.Listedflowsasspecifiedbythe manufacturer’stechnicaldatasheetsaretobeused.Residentialsprinklersshallbeinstalledinconformance withthemanufacturer’sinstallationguidelinesandthe applicableinstallationstandard.Sprinklerframeand deflectorshallbeofbronzeframeconstructionhavinga ¾”NPTthread.Watersealassemblyshallconsistofa Teflon-coatedBellevillespringwasherandmachined cupwith3mmglassbulbcontainingnoplasticparts,and havingatemperatureratingof[155 F(68 C)][175 F (79 C)].SprinklersshallhaveanominalK-factorof7.6.Standardfinish:[Bronze][Chrome-plated][White Polyester][Specialfinish–specify].Recessed escutcheonassemblyshallbeasteel,two-piece escutcheon[with½”adjustment(ModelF2)][with¾”adjustment(ModelF1)][ofpush-onandthreadoffdesign with½”adjustment(ModelFP)].Standardfinishshallbe [brass][brightchrome][whitepainted].Residential recessedpendentsprinklersshallbeReliable[ModelF1 Res76RecessedPendent/F1][ModelF1Res76 RecessedPendent/F2][ModelF1Res76Recessed Pendent/FP]SINR7618(Bulletin135).ModelF1Res76CCPPendent(Concealed)Sprinklersshallbe[cULusListed]lowflowresidential concealedsprinklersengineeredtoprovideaminimum designdensityof0.10gpm/ft 2 overthelistedcoveragearea.Listedflowsasspecifiedbythemanufacturer’stechnical datasheetsaretobeused.Residentialsprinklersshallbe installedinconformancewiththemanufacturer’sinstallation guidelinesandtheapplicableinstallationstandard.Sprinklerframeanddeflectorshallbeofbronzeframe constructionhavinga¾”NPTthread.Watersealassembly shallconsistofaTeflon-coated Bellevillespringwasherand machinedcupwith3mmglassbulbcontainingnoplastic parts,andhavingatemperatureratingof155 F(68 C).Coverplateassemblyshallconsistofabrasscoverplate andcopperalloyretainerflange.Methodofattachingthe coverplatetothesprinkle rcupshallbeapush-onand thread-offdesignallowinga½”coverplateadjustment.Coverplatetemperatureratingshallbe135 F(57 C).A plasticprotectivecapshallbep rovidedandfactoryinstalled insidethesprinklercuptoprotectthesprinklerfrom damage,whichcouldoccurduringconstructionbeforethe coverplateisinstalled.Standar dcoverplatefinish:[White][CustomColor–specify].].Concealedpendentsprinklers shallbeReliableModelF1Res76CCP,SINR7618(Bulletin 135).11. Reliable...ForCompleteProtection Reliableoffersawideselectionofsprinklercomponents.Followingaresomeofthemany precision-madeReliableproductsthatguardlifeandpropertyfromfirearoundtheclock.•Automaticsprinklers •Flushautomaticsprinklers •Recessedautomaticsprinklers •Concealedautomaticsprinklers •Adjustableautomaticsprinklers •Dryautomaticsprinklers •Intermediatelevelsprinklers •Opensprinklers •Spraynozzles •Alarmvalves •Retardingchambers •Drypipevalves •Acceleratorsfordrypipevalves •Mechanicalsprinkleralarms •Electricalsprinkleralarmswitches •Waterflowdetectors •Delugevalves •Detectorcheckvalves •Checkvalves •Electricalsystem •Sprinkleremergencycabinets •Sprinklerwrenches •Sprinklerescutcheonsandguards •Inspectorstestconnections •Sightdrains •Balldripsanddrumdrips •Controlvalveseals •Airmaintenancedevices •Aircompressors •Pressuregauges •Identificationsigns •Firedepartmentconnection Theequipmentpresentedinthisbulletinistobeinstalledinaccordancewith thelatestpertinentStandardsofth eNationalFireProtectionAssocia tion,FactoryMutualResearch Corporation,orothersimilarorganizationsandalsowiththepro visionsofgovernmentalcodesorordinances,wheneverapplicable.Productsmanufacturedanddistributedb yRELIABLEhavebeenprotectinglifeandpropertyforo ver80years,andareinstalledandservicedbythemost highlyqualifiedandreputable sprinklercontractorslocatedthroughouttheU nitedStates,Canadaandforeigncountries.Manufacturedby (800)431-1588SalesOffices (800)848-6051SalesFax (914)829-2042CorporateOffices www.reliablesprinkler.com InternetAddress Revisionlinesindicateupdatedornewdata.EG.PrintedinU.S.A.10/07P/N9999970322 Recycled Paper