HomeMy WebLinkAboutB13-0217 Rev3 comment letter Date: 9/13/13 Re: B13-0217 Revisions Dear Mr. Trout RESPONSE INSTRUCTIONS ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: Sheet ID2 1. The proposed murphy bed is not allowed in the garage. You may not have an exit from a sleeping room threw the garage. Reference section 310.1 IBC. 2. Please show the garage complying with the energy code now that a conditioned space is proposed. Structural Comments: Reviewed and accepted Plumbing Comments: Sheet ID1 1. Clarify vent less appliance. Not allowed to have vent less gas appliances in the Town of Vail as amended per town code. Mechanical Comments: Sheet ID2 1. How is the garage to be heated now that plumbing fixtures are proposed for this space. Electrical Comments: Sheet ID1 1. Revise electrical load calculations to reflect new heating load. Assuming fireplace is to be electrical? 2. Indicate lighting to be 75% high efficacy per the energy code. 3. Show location of smoke and co detectors per IRC PLANNING COMMENTS Sheet ID2 The additional square footage in the garage requires planning approval. Please contact the planning department for approval FIRE COMMENTS PUBLIC WORKS COMMENTS Sincerely, Martin A. Haeberle Chief Building Official